Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
www.AFLglobal.com or 800-890-88781
© 2011, AFL, all rights reserved. Revision 0, 8.22.11 Specifications are subject to change without notice.
Installation InstructionsHCT-INSP-002
Parts of the Assembly:
HIBUS Conductor Trunnion Cap (1)HIBUS Conductor Trunnion Base (1)Clamping Bolts (2)Belleville Washer (2)Flat Washer (2)O-Rings (2)Bushings (4)Trunnion Mounting Bracket – Supplied by Customer Shown for installation only (style and hardware may vary)
Installation Instructions1. The conductor and accessory must be clean.
2. Loosen the bolt on the Trunnion Mounting Bracket.
3. Loosen clamp bolts enough that the cap can be removed from the base. (Ensure hardware remains in cap in the same configuration).
4. Insert trunnion base into the post of the Mounting Bracket.
Installation Procedure for HIBUS® HCT Series Conductor Trunnion (Assembly Reference B9414)
TRUNNION BOLT
TRUNNION BOLT SHOWN FLUSH WITH SURFACE
TRUNNION CAP
1/2" CLAMPING BOLT
1/2" BELLEVILLE WASHER
1/2" FLAT WASHERO-RING (LOCATED ON BOLT THREADS)
TRUNNION MOUNTING BRACKET SHOWN WITHOUT INSULATOR FOR
CLARITY
HIBUS CONDUCTOR TRUNNION BASE
POST BUSHING
TRUNNION MOUNTING BRACKET – POST
www.AFLglobal.com or 800-890-88782
© 2011, AFL, all rights reserved. Revision 0, 8.22.11 Specifications are subject to change without notice.
Installation InstructionsHCT-INSP-002
5. Insert Bolt into Base. Tighten bolt finger tight.
6. Visually inspect Base to insure that it is not cocked or misaligned in Mounting Bracket.
7. Torque Trunnion Bolt to manufacturer’s specified torque.
8. Place Conductor in trunnion base.
9. Position Cap over the conductor and seat conductor into the bushing grooves.
10. Hand tighten clamp bolts to engage threads with the base. Alternate tightening to ensure cap is not misaligned.
12. Visually inspect bushings to ensure proper alignment and seating of the conductor.
13. Torque clamping bolts on cap in 5 ft-lbs. increments alternating the tightening until 40 ft-lbs. have been achieved on each.
14. Assembly is complete.
Installation Procedure for HIBUS® HCT Series Conductor Trun-nion (Assembly Reference B9414)
HIBUS CONDUCTOR TRUNNION BASE
TRUNNION BOLT
TRUNNION BASE
TRUNNION CAP
BUSHING
CONDUCTOR