2
www.AFLglobal.com or 800-890-8878 1 © 2011, AFL, all rights reserved. Revision 0, 8.22.11 Specifications are subject to change without notice. Installation Instructions HCT-INSP-002 Parts of the Assembly: HIBUS Conductor Trunnion Cap (1) HIBUS Conductor Trunnion Base (1) Clamping Bolts (2) Belleville Washer (2) Flat Washer (2) O-Rings (2) Bushings (4) Trunnion Mounting Bracket – Supplied by Customer Shown for installation only (style and hardware may vary) Installation Instructions 1. The conductor and accessory must be clean. 2. Loosen the bolt on the Trunnion Mounting Bracket. 3. Loosen clamp bolts enough that the cap can be removed from the base. (Ensure hardware remains in cap in the same configuration). 4. Insert trunnion base into the post of the Mounting Bracket. Installation Procedure for HIBUS ® HCT Series Conductor Trunnion (Assembly Reference B9414) TRUNNION BOLT TRUNNION BOLT SHOWN FLUSH WITH SURFACE TRUNNION CAP 1/2" CLAMPING BOLT 1/2" BELLEVILLE WASHER 1/2" FLAT WASHER O-RING (LOCATED ON BOLT THREADS) TRUNNION MOUNTING BRACKET SHOWN WITHOUT INSULATOR FOR CLARITY HIBUS CONDUCTOR TRUNNION BASE POST BUSHING TRUNNION MOUNTING BRACKET – POST

Installation Procedure for HIBUS HCT Series Conductor Trunnion

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation Procedure for HIBUS HCT Series Conductor Trunnion

www.AFLglobal.com or 800-890-88781

© 2011, AFL, all rights reserved. Revision 0, 8.22.11 Specifications are subject to change without notice.

Installation InstructionsHCT-INSP-002

Parts of the Assembly:

HIBUS Conductor Trunnion Cap (1)HIBUS Conductor Trunnion Base (1)Clamping Bolts (2)Belleville Washer (2)Flat Washer (2)O-Rings (2)Bushings (4)Trunnion Mounting Bracket – Supplied by Customer Shown for installation only (style and hardware may vary)

Installation Instructions1. The conductor and accessory must be clean.

2. Loosen the bolt on the Trunnion Mounting Bracket.

3. Loosen clamp bolts enough that the cap can be removed from the base. (Ensure hardware remains in cap in the same configuration).

4. Insert trunnion base into the post of the Mounting Bracket.

Installation Procedure for HIBUS® HCT Series Conductor Trunnion (Assembly Reference B9414)

TRUNNION BOLT

TRUNNION BOLT SHOWN FLUSH WITH SURFACE

TRUNNION CAP

1/2" CLAMPING BOLT

1/2" BELLEVILLE WASHER

1/2" FLAT WASHERO-RING (LOCATED ON BOLT THREADS)

TRUNNION MOUNTING BRACKET SHOWN WITHOUT INSULATOR FOR

CLARITY

HIBUS CONDUCTOR TRUNNION BASE

POST BUSHING

TRUNNION MOUNTING BRACKET – POST

Page 2: Installation Procedure for HIBUS HCT Series Conductor Trunnion

www.AFLglobal.com or 800-890-88782

© 2011, AFL, all rights reserved. Revision 0, 8.22.11 Specifications are subject to change without notice.

Installation InstructionsHCT-INSP-002

5. Insert Bolt into Base. Tighten bolt finger tight.

6. Visually inspect Base to insure that it is not cocked or misaligned in Mounting Bracket.

7. Torque Trunnion Bolt to manufacturer’s specified torque.

8. Place Conductor in trunnion base.

9. Position Cap over the conductor and seat conductor into the bushing grooves.

10. Hand tighten clamp bolts to engage threads with the base. Alternate tightening to ensure cap is not misaligned.

12. Visually inspect bushings to ensure proper alignment and seating of the conductor.

13. Torque clamping bolts on cap in 5 ft-lbs. increments alternating the tightening until 40 ft-lbs. have been achieved on each.

14. Assembly is complete.

Installation Procedure for HIBUS® HCT Series Conductor Trun-nion (Assembly Reference B9414)

HIBUS CONDUCTOR TRUNNION BASE

TRUNNION BOLT

TRUNNION BASE

TRUNNION CAP

BUSHING

CONDUCTOR