Installation Instructions Supplement Coaxial Venting System for Vitodens 100-W, WB1A and Vitodens 200-W, WB2A boilers 5441 088 v1.0 09/2009 Safety and Installation Requirements Pleaseensurethattheseinstructionsarereadandunderstoodbeforecommencinginstallation.Failuretocomply with the instructions listed below can cause product/property damage, severepersonalinjury, and/or lossoflife. Workingontheequipment The installation, adjustment, service, and maintenance of this product must be done by a licensedprofessional heatingcontractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner, or control. Ensure mainpower supply to equipment, the heating system, and all external controls has been deactivated. Close main gassupplyvalve. Take precautions in all instances to avoid accidental activation of power during service work. Ensure that the installation literature of other components is referenced. This supplement provides specific information for the installation of the Coaxial Venting System on Vitodens 100-W, WB1A and Vitodens 200-W, WB2A series gas-fired condensing boilers. The venting system is tested and ULC S636 listed by Intertek. Look for the Intertek marking shown on the left and found on each component to identify the new ULC listed coaxial system. Do not mix pipe, fittings, or joining methods from different vent system manufacturers. Do not use adhesives of any kind with this venting system. Wheninstallingthecoaxialventing systemonVitodens200-W,models WB2A44and60,atransitionadaptor D mustbeinstalledimmediatelyafter theboilerventpipeadaptor.Thelength oftheadaptorisnotconsideredinthe enclosedmountingtemplate.Moveside wallventopeninglocationto115/8”/ 295mm a abovemountingbracket. Please file in Service Binder WhentoUseThisSupplement BeforeGettingStarted.... A C B A Reference point top edge of boiler B Mounting bracket C Mounting template D Transition adaptor (WB2A 44, 60 only) E Vent opening with transition adaptor a 11 5/8” / 295 mm D a E Fig.1 IMPORTANT

InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Installation InstructionsSupplement

Coaxial Venting Systemfor Vitodens 100-W, WB1A and Vitodens 200-W, WB2A boilers

5441 088 v1.0 09/2009

Safety and Installation Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the

instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.

Working on the equipment

The installation, adjustment, service,and maintenance of this product mustbe done by a licensed professionalheating contractor who is qualified andexperienced in the installation, service,and maintenance of hot water boilers.There are no user serviceable parts onthe boiler, burner, or control.

Ensure main power supply toequipment, the heating system, and allexternal controls has been deactivated.Close main gas supply valve. Takeprecautions in all instances to avoidaccidental activation of power duringservice work.

Ensure that the installation

literature of other components

is referenced.

This supplement provides specific information for the installation of the Coaxial

Venting System on Vitodens 100-W, WB1A and Vitodens 200-W, WB2A series

gas-fired condensing boilers.

The venting system is tested and ULC S636 listed by Intertek. Look for the

Intertek marking shown on the left and found on each component to identify the

new ULC listed coaxial system.

Do not mix pipe, fittings, or joining methods from different vent systemmanufacturers. Do not use adhesives of any kind with this venting system.

When installing the coaxial venting

system on Vitodens 200-W, models

WB2A 44 and 60, a transition adaptor

D must be installed immediately after

the boiler vent pipe adaptor. The length

of the adaptor is not considered in the

enclosed mounting template. Move side

wall vent opening location to 11 5/8” /

295 mma above mounting bracket.

Ple

ase

file

inS

ervic

eB

ind

er

When to Use This Supplement

Before Getting Started....

A

C

B

A Reference point top edge of boilerBMounting bracketCMounting templateD Transition adaptor (WB2A 44, 60 only)E Vent opening with transition adaptora 11 5/8” / 295 mm

D

a

E

Fig. 1

IMPORTANT

Page 2: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

Fig. 2 Standard side wall venting layout, using basic vent kit components for vent systems 60/100, 80/125 and 100/150

1

2

3 4 5 6

7

A

A

B

a

Max. wall thickness19.6” / 500 mm

2

Side Wall Venting Layouts

Layout with basic coaxial vent kit componentry

Vent pipe adaptor

Transition adaptor (110/150 >100/150) for models WB2A 44, 60

Elbow, 87° (1 per carton)

Straight pipe, 3.3 ft. / 1 m long

Vent termination (incl. wall flashings)Important!

Total length of vent termination pipe

is 31” / 787 mm. If required, the vent

termination pipe may be shortened by

max. 12” / 305 mm (min. vent

termination length is 19” / 483 mm).

Protective screen

Warning!

Protective screen MUST be installed.

Mounting clip, white (use at least 2)

Brass adaptor (see page 3)

Combustion air intake

Flue gas outlet

a Total vent length*1

*1 See page 8 “Vent Length Requirements”(Side Wall Venting).

5441088

v1.0

Page 3: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

7

8

9

Fig. 3 Side wall venting layout, using basic vent kit components for vent systems 60/100, 80/125 and 100/150

Transition adaptor

(used for models WB2A 44, 60 only)

3

Side Wall Venting Layouts (continued)

Layout with basic coaxial vent kit componentry (continued)

Mounting clip (c/w 4” screw)

Brass adaptor (supplied) (M8 x 5/16” -18) and set of screws (#8 x 3/8”)

9 All-threaded rod (field supplied)

5441088

v1.0

Page 4: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

4

Side Wall Venting Layouts (continued)

Layout with basic coaxial vent kit and accessory componentry

Vent pipe adaptor

Transition adaptor (110/150 >100/150) for models WB2A 44, 60

Straight pipe*1

3.3 ft. / 1 m longor1.6 ft. / 0.5 m long

Elbow, 87° (1 per carton)

Telescopic extension

Elbow, 45° (2 per carton)

Vent termination (incl. wall flashings)Important!

Total length of vent termination is

31” / 787 mm. If required, the vent

termination may be shortened by

max. 12” / 305 mm (min. vent

termination length is 19” / 483 mm).

Protective screen

Warning!

Protective screen MUST be installed.

Mounting clip, white (use at least 2)

Brass adaptor (M8 x 5/16” - 18) andSet of screws (#8 x 3/8”)

*1 Other lengths may be used provided thatthe maximum equivalent vent length is notexceeded. 5

441088

v1.0

Fig. 4 Side wall venting layout, using basic vent components and accessory parts for vent system 60/100, 80/125 and 100/150

2

3

4 5 6

7 8

1

3

3

6 9qP

Page 5: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

5

Component Guide (Side Wall Venting)

Telescopic extension installation

Fig. 5 Telescopic extension

The telescopic extension is used whereminor cutting or adjustment to thelength of the vent pipe is required. Seedimension “g” in table below.

Table 1.

Boiler model ain / mm

bin / mm

cin / mm

din / mm

ein / mm

f(max.

insertion)in / mm

gin / mm

WB1A 24, 30 2.4 / 60 4 / 100 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 10.4 / 265max. 16 / 405

WB2A 24(C), 32 3.1 / 80 5 / 125 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11 / 280max. 15.5 / 395

WB2A 44, 60 4/100 6 / 150 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11 / 280max. 15.5 / 395

5441088

v1.0

Ø b

Ø a

c

Ø a

Ø b

c

f

e

d

Fig. 6

g

Page 6: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

6

Component Guide (Side Wall Venting) (continued)

Vent termination installation

Table 2. Dimensions

Ventsystem

ain / mm

bin / mm

60/100 4.5 / 115 27.8 / 706

80/125 5.3 / 135 29 / 736

100/150 7.3 / 185 30.8 / 783

Table 3. Wall opening information

Vent system Opening Ø

60/100 4¼” / 108 mm

80/125 5¼“ / 133 mm

100/150 63/8” / 160 mm

When installing a side wall vent systemwith the minimum equivalent ventlength (87º elbow and vent terminationshortened to 19”/483 mm) from boilerback to the outside wall, a wallthickness of at least 6”/152 mm isrequired.For walls with a thickness of less than6” / 152 mm, means must be providedto offset the boiler from the wall.See Fig. 8.

Side wall vent termination installation

1. Provide side wall opening (see Table3.) to install vent termination.

2. Slide vent termination with wallflashing 2 into opening.

3. Attach wall flashing2 to inside ofwall using the screws and plugsprovided.

4. Attach wall flashing to outside ofwall.

5. To prevent movement of venttermination inside the wall, fastenflashing to vent pipe, using two#8 x 3/8” screws.(continued on next page)

Total length of vent termination is 31” /

787 mm. If required, the vent

termination may be shortened by max.

12” / 305 mm (min. vent termination

length is 19” / 483 mm).

Potential gaps between the vent-air

intake and the surrounding construction

which may cause air, rain or flue gases

to leak into the wall or the building,

must be sealed with approved outdoor

sealant/caulking to prevent leakage of

any kind.

5441088

v1.0

Fig. 7 Coaxial vent termination for vent system 60/100, 80/125 and 100/150

b

1 23

1Vent termination2Wall flashing (inside)3Wall flashing (outside)

6”/152 mm

Offset

Fig. 8

IMPORTANT

IMPORTANT

Page 7: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Side Wall Vent Installation

7

Component Guide (Side Wall Venting) (continued)

Vent termination installation (continued)

6. Secure protective screen (Fig. 9)into place, using the four stainlesssteel screws and plugs provided.

The protective screen MUST be

installed.

7. Connect vent termination from insideand route toward boiler with min. 3ºdownward slope.

Table 4. Dimensions

Model Vent system a b c

WB1A-24, -30 60/100 12” / 305 mm 7.5” / 190mm 9.5” / 241 mm

WB2A-24(C), -32 80/125 12” / 305 mm 6.7” / 170mm 9.5” / 241 mm

WB2A-44, -60 100/150 12” / 305 mm 4.7” / 120mm 9.5” / 241 mm

5441088

v1.0

Fig. 9 Protective screen, side view for vent systems 60/100, 80/125 and 100/150

6

IMPORTANT

Fig.10 Protective screen, front view

Page 8: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

Fig. 11 Equivalent vent length calculation

*1

8

Vent Length Requirements (Side Wall Venting)

Maximum vent length

Table 5.

Vent system

Boiler model 60/100 80/125 100/150

WB1A 24, 30 20 ft. / 6 m (see Fig. 11) 26 ft. / 8 m*1 (see Fig. 12) 33 ft. / 10 m*2 (see Fig. 12)

WB2A 24(C), 32 n.a. 20 ft. / 6 m (see Fig. 11) 26 ft. / 8 m*3 (see Fig. 13)

WB2A 44, 60 n.a. n.a. 20 ft. / 6 m (see Fig. 11)

*1If used with increasers 60/100 to 80/125. *2 If used with increasers 60/100 to 100/150. *3 If used with increasers 80/125 to 100/150.

87º elbowVent pipe (3.3 ft. / 1 m)Vent pipe (1.6 ft. / 0.5 m)Vent termination

*1 First elbow not included in equivalent

vent calculation.

� For maximum equivalent vent lengthon all models see tables 5. and 6.,and Figs. 11, 12 and 13.

�Do not exceed the maximum ventlength.

�Do not use more than five elbows(87º or 45º) within one vent system(first elbow is included in count).

� First 87º elbow on boiler is notincluded in equivalent vent lengthcalculation.

Table 6.

Type of fitting Equivalentlength

87º elbow/87º inspection tee

1.6 ft. / 0.5 m

45º elbow 1 ft. / 0.3 m

Equivalent vent length calculation

example

2 x 87º elbow 3.2 ft. / 1 m. . . . . . . . . . . . . . . . . . . . . . . .

2 x vent pipe (1 m) 6.6 ft. / 2 m. . . . . . . . . . . . . .

1 x vent pipe (0.5 m) 1.6 ft. / 0.5 m. . . . . . .

1 x vent termination 2.4 ft. / 0.73 m. . . . .

Total equivalent length13.8 ft. / 4.23 m

First elbow not included in equivalent

vent calculation.

Always include vent termination length

in calculations.

5441088

v1.0

IMPORTANT

Page 9: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

9

Vent Length Requirements (Side Wall Venting) (continued)

Maximum vent length with increasers (Vitodens 100-W, WB1A boiler)

Maximum vent length with increaser (Vitodens 200-W, WB2A boiler)

Minimum vent length

The minimum equivalent vent length for all models is 19” / 483

mm (length of the vent termination when cut to the minimum

permissible length). Please note that the first 87º elbow on boiler

is not included in equivalent length calculation.

5441088

v1.0

a

Coaxial increaserfor system 60/100 to 100/150

Coaxial increaserfor system 60/100 to 80/125

Fig. 12 Vitodens 100-W boiler with increasers

a

Coaxial increaser for system80/125 to 100/150

Fig. 13 Vitodens 200-W boiler with increaser

Page 10: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

10

Vertical Venting Layouts

Layout of vertical vent system with accessories

Please note that there is no basic vent kit available for this vertical vent system.

Select from the vertical vent components below as required. Do not exceed maximum equivalent vent length.

Vent pipe adaptor

Elbow, 87° (1 per carton)

Telescopic extension

Straight pipe

3.3 ft./1 m or1.6 ft./0.5 m

Elbow, 87° (1 per carton)

Elbow, 45° (2 per carton)

Vent termination

Never shorten vertical vent

termination.

IMPORTANT

Mounting clip (c/w 4” screw)

Wall band (c/w vent termination, notshown)_

Brass adaptor (c/w set of screws)

Roof flashing and storm collar (fieldsupplied)

Use other anchoring/support system

components as required.

Ensure that the venting system isproperly supported; the Vitodens100-W and 200-W boilers are notdesigned to support the weight of theventing system.

IMPORTANT

Fig. 14 General vertical venting layout for vent systems 60/100, 80/125 and 100/150

1

2

4

3 4

8 + qP

5

4

6

4

6

4 8

7

qQ

8

Page 11: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)Vertical Vent Installation (Coaxial)

11

Vertical Venting Layouts (continued)

General installation examples

Ensure that the venting system is

properly supported; the Vitodens 100-W

and Vitodens 200-W boilers are not

designed to support the weight of the

venting system.

5441088

v1.0

Fig. 15 Sloped roof installation Fig. 16 Flat roof installation Fig. 17 Sloped roof installation with offset

IMPORTANT

Page 12: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

12

Component Guide (Vertical Venting)

Telescopic extension installation

Fig. 18 Telescopic extension

The telescopic extension is used whereminor cutting or adjustment to thelength of the vent pipe is required. Seedimension “g” in table below.

Table 7.

Boiler model ain / mm

bin / mm

cin / mm

din / mm

ein / mm

f(max.

insertion)in / mm

gin / mm

WB1A 24, 30 2.4 / 60 4 / 100 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 10.4 / 265max. 16 / 405

W2A 24(C), 32 3.1 / 80 5 / 125 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11/ 280max. 15.5 / 395

WB2A 44, 60 4/100 6 / 150 0.4 / 10 7.9 / 200 9.6 / 245 1.2 / 30 min. 11/ 280max. 15.5 / 395

5441088

v1.0

Ø b

Ø a

c

d

Ø a

Ø b

c

f

e

Fig. 19

g

Page 13: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

13

Component Guide (Vertical Venting) (continued)

Vent termination installation

Fig. 20 Vent termination

ACombustion air intake

B Flue gas outlet

Øb

c

g

Øa

d

f

e

A A

B B

Table 8. Wall opening information

Vent system Opening Ø

60/100 4¼” / 108 mm

80/125 5¼“ / 133 mm

100/150 63/8” / 160 mm

Vertical vent termination installation

The vertical vent termination must not

be shortened outside the roof,

otherwise the overall length will be

shorter than required.

1. Install the vent termination for slopedor flat roof collars in accordance withthe manufacturer’s instructions.

2. The vent termination should beplaced from above on the sloped orflat roof collar.

3. Connect vent pipe from below.

Table 9. Dimensions, vent system

Boiler model a(in / mm)

b(in / mm)

c(in / mm)

d(in / mm)

e(in / mm)

f(in / mm)

g(in / mm)

WB1A 24WB1A 30

2.4 / 60 4 / 100 0.4 / 10 1.6 / 40 23 / 585 18.1 / 460 50.4 / 1280

WB2A 24(C)WB2A 32

3 / 80 5 / 125 0.4 / 10 2.2 / 57 18.7 / 476 22.8 / 580 53.3 / 1354

WB2A 44WB2A 60

4 / 100 6 / 150 0.4 / 10 n.a. 31.3 / 795 22.8 / 580 68.3 / 1735

5441088

v1.0

IMPORTANT

Page 14: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

14

Vent Length Requirements (Vertical Venting)

Maximum vent length

Table 10. Vitodens 100-W

Boiler model WB1A 24 30

a (max. length)60/100 vent system ft./m 33/10 33/10

Do not exceed the maximum vent length.

Table 11. Vitodens 200-W

Boiler model WB2A 24C 24 32 44 60

a (max. length)80/125 vent system100/150 vent system

ft./mft./m

33/10--

33/10--

27/8--

--33/10

--20/6

Do not exceed the maximum vent length.

5441088

v1.0

Fig. 21 Vent length “a”

a

Page 15: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

15

Vent Length Requirements (Vertical Venting) (continued)

Maximum vent length with increasers

Table 12. Maximum vertical vent length

(Vitodens 100-W, WB1A)

ModelNo.

WB1A 24, 30

Systemvent size

80/125*1 100/150*2

Max. ventlength

39.4 ft.12 m

46 ft.14 m

*1If used with increasers 60/100 to 80/125.

*2If used with increasers 60/100 to 100/150

Table 13. Maximum vertical vent length

(Vitodens 200-W, WB2A)

ModelNo.

WB2A 24C, WB2 32

Systemvent size

100/150*1 100/150*1

Max.ventlength (a)

39.4 ft.12 m

33 ft.10 m

*1If used with increasers 80/125 to 100/150.

5441088

v1.0

a

Coaxial increaserfor system 60/100 to 100/150

Coaxial increaserfor system 60/100 to 80/125

Fig. 22 Vent length “a”

Page 16: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Vertical Vent Installation (Coaxial)

16

Vent Length Requirements (Vertical Venting) (continued)

Equivalent vent calculation examples

Table 14.

Type of fitting Equivalentlength

87º elbow/87º inspection tee

1.6 ft. / 0.5 m

45º elbow 1 ft. / 0.3 m

Always include vent termination length

in calculations.

Equivalent vent length calculation

example

Vitodens 100-W, WB1A 30 andVitodens 200-W, WB2A 32(vent system 60/100) (see Fig. 23)

2 x 87º elbow 3.3 ft. / 1 m. . . . . . . . . . . . . . . . . . . . . . . .

2 x 45º elbow 2 ft. / 0.6 m. . . . . . . . . . . . . . . . . . . . . . . .

3 x vent pipe (0.5 m) 4.8 ft. / 1.5 m. . . . . . .

1 x vent pipe (1 m) 3.3 ft. / 1 m. . . . . . . . . . . . . .

1 x sliding coupling 0.8 ft. / 0.25 m. . . . . . .

1 x vent termination 3.9 ft. / 1.2 m. . . . . . . .

Total equivalent length18.1 ft. / 5.55 m

5441088

v1.0

Fig. 23 Equivalent vent length calculation, example

IMPORTANT

Page 17: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

17

Componentry

Table 15.

Vent system size Dimensions [in. / mm]

a b c

60/100 2.4 / 60 4 / 100 1.6 / 40

80/125 3 / 80 5 / 125 1.6 / 40

100/150 4 / 100 6 / 150 1.6 / 40

When cutting straight pipes to length,

debur and clean pipes.

Table 16.

Vent system size Dimensions [in./mm]

a b c

60/100 2.4/60 4/100 1.6/40

80/125 3/80 5/125 1.6/40

100/150 4/100 6/150 1.6/40

When cutting straight pipes to length,

debur and clean pipes.

Table 17.

Vent system size Dimensions [in./mm]

a b c d e

60/100 2.4/60 4/100 1.2/31 4.5/113 4/100

80/125 3/80 5/125 1.2/31 5/128 4.3/110

100/150 4/100 6/150 1.2/31 5.2/133 4.5/115

5441088

v1.0

Straight pipe (0.5 m)(can be cut to length if required)

c

Øb

Øa

19.7“ / 500 mm

Fig. 24

IMPORTANT

39.4”/1000 mm

Straight pipe (1 m)(can be cut to length if required)

c

Øb

Øa

Fig. 25

IMPORTANT

Elbow (87º)

Ø bØ a

88°

c

e

d

Fig. 26

Page 18: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

18

Componentry (continued)

Table 18.

Vent system size Dimensions [in./mm]

a b c d e

60/100 2.4/60 4/100 1.6/40 1.2/31 2.4/60

80/125 3/80 5/125 1.8/45 1.2/31 2.5/63

100/150 4.3/110 6/150 3.8/97 2/50 5/128

Table 19.

Vent system size Dimensions [in./mm]

a b c d e f

60/100 2.4/60 4/100 2/50 5/125 4/100 6/150

80/125 3.1/80 5/125 2/50 4.3/110 4/100 6/150

100/150 2.4/60 6/150 2/50 4.3/110 3.1/80 5/125

Table 20.

Vent system size Dimensions [in./mm]

a b c

60/100 2.4/60 4/100 min. 10.4/265max. 16/405

80/125 3.1/80 5/125 min. 11/280max. 15.5/395

100/150 2.4/60 6/150 min. 11/280max. 15.5/395

Table 21.

Vent system size Dimensions [in./mm]

a b

60/100 7.1/180 8.7/220

80/125 7.1/180 8.7/220

100/150 7.1/180 8.7/220

5441088

v1.0

Ø bØ a

c

43-45°

e d

Elbow (45°) (2 per carton)

Fig. 27

Increaser

Ø f

Ø bØ a

c

d

Ø e

Fig. 28

Telescopic extension

c

ab

Fig. 29

Wall flashing

Fig. 30

ba

Page 19: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

19

Componentry (continued)

Total length of vent termination pipe

is 31”/787 mm. If required, the vent

termination pipe may be shortened by

max. 12”/305 mm (min. vent

termination length is 19”/483 mm).

Table 22.

Vent system size Dimensions [in./mm]

a b c d

60/100 2.4/60 4/100 23.6/600 27.8/706

80/125 3/80 5/125 23.6/600 29/736

100/150 4/100 6/150 23.6/600 30.8/738

Table 23.

Boiler model Dimensions [in./mm]

a b c d e f g

WB2B80, 105 4.3/110 6/150 1.3/40 2/50 5.5/140 4.3/100 6/150

5441088

v1.0

Horizontal vent termination

Øa

Øb

c

d

front view,

not to scale

Fig. 31

IMPORTANT

b

aDimensions

a 12” / 405mmb 9.5” / 241mm

Protective screen

for side wall venting installations only

Fig. 32

Ø bØ a

c

e

d

Transition Adaptor 110>150

Fig. 33

fg

ØØ

Page 20: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

20

Componentry (continued)

Table 24. Dimensions, vertical vent termination

Boiler model a(in/mm)

b(in/mm)

c(in/mm)

d(in/mm)

e(in/mm)

f(in/mm)

g(in/mm)

WB1A 24, 30 2.4/60 4/100 0.4/10 1.6/40 23/585 18.1/460

50.4/1280

WB2A 24(C), 32 3/80 5/125 0.4/10 2.2/57 18.7/476

22.8/580

53.3/1354

WB2A 44, 60 4/100 6/150 0.4/10 n.a. 31.3/795

22.8/580

68.3/1735

Wall band

for installation on inside wall or ceiling(c/w vertical vent termination)

Table 25.

Vent system size Dimensions[in./mm]

a b

60/100 4/100 8.5/215

80/125 4.3/110 8.5/215

100/150 6/150 8.5/215

Mounting clip, white

for installation on inside wall or ceiling

Table 26.

Vent system size Dimensions[in./mm]

a

60/100 4/100

80/125 5/125

100/150 6/150

Brass adaptor

(c/w set of 20 #8 x 3/8” screws)

5441088

v1.0

Øb

c

g

Øa

d

f

e

A A

B B

Vertical vent termination

Fig. 34

a

b

Fig. 35

a

Fig. 36

5/16”-18

M8

Fig. 37

Page 21: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

21

Componentry (continued)

Basic vent kit components (Side Wall Vent System only)

Basic components

Vent pipe adaptor

(comes preinstalled on all

models)

Elbow, 87º

Straight pipe,

3.3 ft. / 1 m*1

Vent termination

(c/w wall flashings)

Protective screen

(c/w brass adaptor and set(c/w brass adaptor and set

of screws)

Mounting clip*2

Brass adaptor

(c/w set of 20 #8 x 3/8”

screws)

Vent accessories

Accessory components

Straight pipe,

1.6 ft. / 0.5 m*1

Elbow (45º)

(2 per carton)

Telescopic extension

Vent inspection tee/

Elbow (87º)

Straight tee (for system

60/100 only)

Coaxial increaser

(for system 60/100 to

80/125)

Coaxial increaser (for sys-

tem 80/125 to 100/150)

Coaxial increaser (for sys-

tem 60/100 to 100/150)

Joint lubricant

*1When ordering the straight pipe separately, order with

mounting clip and brass adaptor.*2When ordering mounting clip separately, order with

brass adaptor.5441088

v1.0

For replacement purposes or project-specific requirements,

individual parts can be ordered fromViessmann. Refer to the table

for an outline of basic vent kit componentry that can be orderedseparately.

For project-specific requirements, individual accessory parts can

be ordered from Viessmann. Refer to the table for an outline of

accessory parts available.

Page 22: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

22

5441088

v1.0

Page 23: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

23

5441088

v1.0

Page 24: InstallationInstructions Supplement CoaxialVentingSystem...InstallationInstructions Supplement CoaxialVentingSystem forVitodens100-W,WB1AandVitodens200-W,WB2Aboilers 5441088v1.0 09/2009

Componentry

Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • CanadaTel. (519) 885-6300 • Fax (519) 885-0887www.viessmann.ca • [email protected]

Viessmann Manufacturing Company (U.S.) Inc.45 Access RoadWarwick, Rhode Island • 02886 • USATel. (401) 732-0667 • Fax (401) 732-0590www.viessmann-us.com • [email protected]

24

5441088

v1.0

Technicalinformationsubjectto

changewithoutnotice.

Printedonenvironmentally