INSTALLED FILTER LEAKAGE TEST
PROCEDURE
INSTALLED FILTER LEAKAGE
TEST PROCEDURE
7/25/2019 Installed Filter Test Procedure
2/5
INSTALLED FILTER LEAKAGE TEST
PROCEDURE
I. Purpose:
- To check leakage between filter box and filter frame.
- To check the integrity of filter (fault of filter media)
The installed filter is passed if no leakage detected in two tests above.
Figure 1
- During the measurement in case of found particle which size is over 0.3 micro meters, stop
measurement and confirm the counting of particle.
- In case of no increase counting, it is understood as stuck particle and continues sampling.
II. Measuring device:
No. Device Manufacturer Model Origin Serialnumber
1 AnemometerPROVA
InstrumentAVM-03 Taiwan 9300447
2Particle
counterKANOMAX 3887A Japan 23713
III. Preparation works before testing:
Check the air duct, ensure the ducts are correctly installed. The room is cleaned to reach clean
room cleanliness and there is no particle generated inside of room.
IV. Testing procedure: (comply with Annex B.6 ISO 14644-3 2005)
1. Measure face velocity on filter
2. Measure concentration of 0.3 m particle above filter to define Cc[particles/cm3]
3. Based on filters efficiency, define maximum allowable integral MPPS (Most PenetratingParticle Size) penetration of the filter.
HEPA filter
HEPA filter
7/25/2019 Installed Filter Test Procedure
3/5
INSTALLED FILTER LEAKAGE TEST
PROCEDURE
For example, if the filters efficiency is 99.95% against particles of size 0.15 0.3 m then
Ps= 0.05%
4. From the table below, we have factor K = 10
Ps 5 x 10-4 5 x 10-5 5 x 10-6 5 x 10-7 5 x 10-8
K factor 10 10 30 100 300
5. Standard leak penetration of the filter PL= K.PS
6. Scan rate of probe is calculated from:
Sr [Cc(PL Ps) qvs+Ccx Psx qva] (Dp/Np)Where
Cc: particle concentration above HEPA filter, [particles/cm3];
Ps: maximum allowable integral MPPS (Most Penetrating Particle Size) penetration of the
filter;
PL: standard leak penetration of the filter;
qvs: standard flow rate, qvs= 1 ft3/s = 472 cm3/s (28.3 l/min);
qva: actual flow rate of particle counter (cm3/s);
Dp: probe dimension parallel to the scan direction (cm);
Np: expected number of particle counts [particles]; Npis paired with Cain Poisson table
Ca: observed acceptable count [particles]; Cais chosen from Poisson distribution table
NOTE: Srshould not exceed 8 [cm/s], if the calculated Sris over 8 [cm/s] then Np, Cais re-
calculated with Sr= 8 [cm/s].
Upper limit of the 95% confidence interval of a Poisson distribution
Observed
Ca
Upper limit
Np
Observed
Ca
Upper limit
Np When Npis
larger than 19.7
Ca= Np- 2Np
0 3.7 6 13.1
1 5.6 7 14.4
2 7.2 8 15.8
7/25/2019 Installed Filter Test Procedure
4/5
INSTALLED FILTER LEAKAGE TEST
PROCEDURE
3 8.8 9 17.1
4 10.2 10 18.4
5 11.7 11 19.7
Any observed counts greater than Cais sign of potential leak
NOTE: While scanning, probe should be maintained at a distance of 3 cm from filter face.
7. Stationary measuring is proceed if a potential leak is detected. At potential leak, re-
measure particle in sustained residence time T r, Trshould be set at one or a few times the
fixed interval of particle counter. Caof stationary measuring is calculated from equation Ca=
Npa- 2Npa
Npais calculated from equation : Npa= [Cc(PL Ps)qvs+ Ccx Psx qva]Tr
8. The installed filter leakage testing includes two stages:
- Stage one: Proceed scanning along filter gasket to check leakage between filter box
and filter frame
- Stage two: Proceed scanning filter surface to check the integrity of filter
7/25/2019 Installed Filter Test Procedure
5/5
Date:
S/N
Dimension
AHU No.
Room
Note: Resisdence time, s
No.Scanning
counts
Stationary
counts
Leaked
(Yes/No)No.
Scanning
counts
Stationary
counts
Leaked
(Yes/No)
Scanning
limit,
counts
Stationary
limit,
counts
Filter material scanning Filter frame scanning
FILTER PASSED LEAKAGE TEST (YES/NO)
INSTALLED FILTER LEAKAGE TEST REPORT
TEST RESULTS
Challenging
particles
concentration
(particles/cm3)Location
Filter
Testing criteria
Scanning
rate, cm/s