ContentsDescription Page
1. Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . 22. Receiving,Handling,andStorage. . . . . . . . . . 43. EquipmentDescription. . . . . . . . . . . . . . . . . . 54. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . 115. Inspection,Testing,andMaintenance. . . . . . 146. DocumentReferences. . . . . . . . . . . . . . . . . . 14
Effective June 2011Instruction Booklet IB01900002E
Instructions for Magnum DS® Metal-EnclosedLow-Voltage NEMA 3R Assemblies
2
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Readandunderstandtheseinstructionsbeforeattemptingtounpack,assemble,operateormaintainthistypeequipment.
NOTICEALL POSSIBLE CONTINGENCIES WHICH MAY ARISE DURING INSTALLATION, OPERATION OR MAINTENANCE, AND ALL DETAILS AND VARIATIONS OF THIS EQUIPMENT DO NOT PURPORT TO BE COVERED BY THESE INSTRUCTIONS.
Iffurtherinformationisdesiredbypurchaserregardingtheparticularinstallation,operationormaintenanceofparticularequipment,con-tactthelocalEatonrepresentative.
WARNINGMETAL-ENCLOSED LOW-VOLTAGE NEMA 3R ASSEMBLIES COVERED BY THESE INSTRUCTIONS ARE DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERIOUS INJURY AND/OR PROPERTY DAMAGE. ALL RESPONSIBLE PERSONNEL SHOULD LOCATE THE EQUIPMENT RATING NAMEPLATE AND BE FAMILIAR WITH THE INFORMATION PROVIDED THEREON.
Purpose
Thisinstructionmanualisexpresslyintendedtocovertheinstalla-tion,operationandmaintenanceofMagnumDS®Metal-EnclosedLow-VoltageNEMA3RAssembliesusedwithMagnumDS®PowerCircuitBreakersorCM52NetworkProtectors.
NOTICETHIS INSTRUCTION MANUAL IS INTENDED TO EMPHASIZE THE FEATURES AND ENHANCEMENTS UNIQUE TO MAGNUM DS NEMA 3R SWITCHGEAR AND SWITCHBOARDS. IT IS NOT INTENDED TO BE A COMPLETE MANUAL FOR THE INSTALLATION, OPERATION AND MAINTENANCE OF MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE ASSEMBLIES, BUT IS SUPPLEMENTAL IN NATURE; AND APPENDS THE ORIGINAL ONLY AS DESCRIBED HEREIN. FOR COMPLETE INSTRUCTIONS CONCERNING MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE ASSEMBLIES, SEE IB01901001E.
Forapplicationinformationconsultapplicabledescriptivebulletins,applicationpublicationsand/ortheapplicableindustrystandards.Forinstallation,operationandmaintenanceofLow-VoltagePowerCircuitBreakersseeseparateinstructionbooklistedinSection6.
Safety
Allsafetycodes,safetystandardsand/orregulationsMUSTbestrictlyobservedintheinstallation,operationandmaintenanceofthisequipment.
DANGERTHE DANGER, WARNING AND CAUTION MESSAGES INCLUDED AS PART OF THE PROCEDURAL STEPS IN THIS MANUAL ARE FOR PERSONNEL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE THIS PARAGRAPH TO FAMILIARIZE PERSONNEL WITH THE TYPE OF PRESENTATION. THIS WILL HELP TO ASSURE THAT PERSONNEL ARE ALERT TO THESE MESSAGES. IN ADDITION, THESE MESSAGES ARE ALL UPPER CASE AND BOLDFACE.
Section 1: Introduction1.1GeneralInformation
MagnumDSMetal-EnclosedLow-VoltageNEMA3RSwitchgearandSwitchboardAssembliesareuniquelydesignedforuseinoutdoorenvironmentsorotherharshconditions.TheNEMA3REnclosureisa"skin"or"shell"thatcontainsandprotectsthestandardindoorassemblyfromtheelementsassociatedwithoutdoorinstallations,suchasfallingrain,sleetorsnow.Therefore,mostfeaturesandoptionsinherenttothestandardindoorenclosureareavailableintheNEMA3Rversion,aswell.Theseassembliesaretestedtotherig-orsofUL50EandcertifiedasaNEMAType3Renclosure.
TheseassembliescontainthesamedistributionoptionsasstandardindoorassembliesandmayuseMagnumDS,MagnumSBand/orSeriesNRX®PowerCircuitBreakerstocontrolandprotectpowercircuitsuptoandincluding600voltsACandinterruptingcapacitiesuptoandincluding200kA.
Theswitchgearorswitchboardassemblyiscomposedofverticalsectionsthatarearrangedtosuitthecustomer’slayoutrequire-ments.MagnumDSswitchgearandswitchboardsutilizeafour-cellhighstructuredesignconsistingofvariouscombinationsofMagnumDS,MagnumSBand/orSeriesNRXPowerCircuitBreakersandauxiliarycompartments(SeeIB01901001EreferencedinSection6).Busandcablecompartmentsprovidespaceforconnections,mainte-nanceandinspection.Powercableconnectionsarerear-accessibleasastandard,ormaybefront-accessibleasanoption.
Accesstothecircuitbreakersisavailableviaawalk-indesign(42"aisle-way)asastandard,oranon-walk-indesign(aisle-less)asanoption.
Thisinstructionmanualcontainsimportantproceduresandinforma-tionpertinenttothereceiving,handling,storage,installation,opera-tionandmaintenanceofMagnumDSLow-VoltageMetal-EnclosedNEMA3RAssemblies.
NOTICEINFORMATION PROVIDED IN THIS INSTRUCTION MANUAL AND BY OTHER SUPPLIED DOCUMENTATION AND/OR DRAWINGS SHOULD BE READ AND UNDERSTOOD BY ALL PERSONNEL RESPONSIBLE FOR SUPERVISION, OPERATION OR MAINTENANCE. FAMILIARIZATION SHOULD ALWAYS INCLUDE THE CHARACTERISTICS OF EACH PIECE OF EQUIPMENT CONTAINED IN OR MOUNTED ON THE ASSEMBLY. PROPER INSTALLATION, OPERATION AND MAINTENANCE ARE ESSENTIAL TO ASSURE CONTINUED SATISFACTORY SERVICE FROM THE EQUIPMENT. IT SHOULD NOT BE INSTALLED IN PLACES WHERE IT WILL BE REQUIRED TO OPERATE AT VOLTAGE, CURRENTS OR FAULT CAPACITIES GREATER THAN THOSE FOR WHICH IT WAS DESIGNED, OR WHERE THE ENVIRONMENTAL CONDITIONS ARE DIRTY, CORROSIVE, HUMID OR OTHERWISE HARSH OR UNSUITABLE. (REF. ANSI C37.20.1 FOR ABNORMAL OPERATION CONDITIONS). THE INFORMATION GIVEN IN THIS MANUAL APPLIES TO NEMA 3R LOW-VOLTAGE ASSEMBLIES UTILIZING THE MAGNUM DS FAMILY OF DRAWOUT POWER CIRCUIT BREAKERS UNLESS OTHERWISE NOTED. FOR OTHER OPTIONS, SEE THE DOCUMENTS LISTED IN SECTION 6.
3
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
1.2SafetyFeatures
EachMagnumDSAssemblyismanufacturedwithbuilt-ininterlocksandsafety-relatedfeatures.Theyareprovidedtoreducehazardstooperatingpersonnelandprovideproperoperatingsequences.
DANGERMETAL-ENCLOSED LOW-VOLTAGE ASSEMBLIES ARE PROVIDED WITH MANY SAFETY FEATURES. NEVERTHELESS, WHEN CONNECTED THEY CONTAIN POWER CIRCUITS WITH HIGH FAULT CAPACITY. THE VOLTAGES AND POWER LEVELS AVAILABLE IN THIS EQUIPMENT MAKE CONTACT WITH BARE CONDUCTORS OR TERMINALS EXTREMELY DANGEROUS, AND IS LIKELY TO BE FATAL. ALL POWER SHOULD BE TURNED OFF OR APPROPRIATE PROTECTIVE EQUIPMENT USED WHEN WORKING ON SUCH EQUIPMENT. IN ADDITION TO THE HAZARDS INHERENT TO THE LOW-VOLTAGE ASSEMBLY ITSELF, OPERATION BY UNQUALIFIED PERSONS MAY CAUSE INDIRECT DAMAGE TO CONNECTED EQUIPMENT AND INJURY TO OPERATORS OF CONNECTED EQUIPMENT UNDER NO CIRCUMSTANCE SHOULD THE INTERLOCKS OR OTHER SAFETY FEATURES BE MADE INOPERATIVE OR DISABLED, AS THIS MAY RESULT IN DEATH, BODILY INJURY OR PROPERTY DAMAGE. TO PROTECT PERSONNEL DURING THE INSTALLATION, OPERATION AND MAINTENANCE OF THIS, THE FOLLOWING PRACTICES MUST BE
FOLLOWED:
1.3SafetyPractices
WARNINGMAGNUM DS LOW-VOLTAGE SWITCHGEAR AND SWITCHBOARD ASSEMBLIES ARE COMPLEX, HIGH CURRENT ELECTRICAL EQUIPMENT DESIGNED TO OPERATE WITHIN THE VOLTAGE AND CURRENT LIMITATIONS SHOWN ON THEIR RESPECTIVE NAMEPLATES. DO NOT APPLY THIS EQUIPMENT TO SYSTEMS WITH VOLTAGES AND/OR CURRENTS IN EXCESS OF THESE LIMITS.
1. Onlyqualifiedelectricalpersonnelfamiliarwiththeconstructionandoperationofthisequipmentandtheassociatedhazardsshouldbepermittedtoworkonsuchequipment.Additionally,onlyqualifiedpersonnelshouldbepermittedtoinstalloroperatesuchequipment.
2. Alwaysbecertainthattheprimaryandsecondarycircuitsarede-energizedbeforeattemptinganymaintenance
3. Formaximumsafety,onlyinsertacompletelyassembledbreakerintoanenergizedcell.Frontcoversaresafetyfeaturesandmustbeinplacewhenenergized.
4. Whileintheassembly,alwaysensurethatdrawoutcircuitbea-kersareinoneofthreeintendedpositions:“Connect”,“Test”or“Disconnect”.Acircuitbreakerpermittedtoremaininaninter-mediatepositioncouldresultincontrolcircuitsbeingimproperlyconnectedcausingotherequipmenttomalfunction
5. Donotremoveaccesscoversunlessthecircuitstobeexposedarede-energized.
6. Usecalibratedtestequipmentofknownreliabilitytoconfirmthatallcircuitsarede-energizedbeforeservicing
7. Aftermaintenance,becertaineverycurrenttransformersecond-arycircuitiscompletelyconnectedorshorted.
DANGERIF THE SECONDARY CIRCUIT OF ANY CURRENT TRANSFORMER IS LEFT OPEN WITHOUT LOAD, AND ITS PRIMARY CIRCUIT IS ENERGIZED, A DANGEROUSLY HIGH VOLTAGE IS DEVELOPED ACROSS TRANSFORMER SECONDARY TERMINALS. TO PREVENT DEATH, BODILY INJURY OR ELECTRICAL SHOCK, EITHER DE-ENERGIZE THE CIRCUIT BY OPENING THE BREAKER, OR SHORT CIRCUIT CURRENT TRANSFORMER SECONDARY TERMINALS, BEFORE ENERGIZING THE CIRCUIT AND PROCEEDING WITH MAINTENANCE.
8. Alwaysbecertainthatallassemblyhardwareisinplaceandboltedtightlybeforeinsertingadrawoutcircuitbreakerintoitscompartment.
WARNINGFAILURE TO FOLLOW THESE DIRECTIONS MAY RESULT IN DEATH, SERIOUS BODILY INJURY OR PROPERTY DAMAGE.
1.4QualifiedPersonnel
Forthepurposeofoperatingswitchgearandswitchboardassem-blies,apersonwhohasbeenthoroughlytrainedintheoperationofcircuitbreakersandanyincludedinstrumentationandwhohascom-pleteknowledgeoftheloadsconnectedtotheassemblymaybeconsideredtobeaqualifiedperson.
Forthepurposeofinstalling,inspectingandmaintainingswitchgearandswitchboardassemblies,aqualifiedpersonMUSTalsobeaqualifiedelectrician,whoisthoroughlytrainedinregardtorecogniz-ingandavoidingthehazardsinherenttoworkingwithelectricityandintheproperwaytoperformsuchwork.Theindividualmustbeabletode-energize,clearandlockout/tagoutcircuitsinaccordancewithestablishedsafetypractices.Inaddition,theindividualmustbeequippedwith,andtrainedintheuseof,PersonalProtectiveEquipment(PPE)(rubbergloves,arc-flashclothes,etc.)forthoseoccasionswhenitisnotpossibletode-energizeallcircuitsbeforedoingmaintenanceworkinthearea.
1.5Precautions
1. Ifrelaysareincluded,removeallblocking.Checkcontrolcircuits(exceptvoltageandcurrenttransformercircuits)forgroundsandshortcircuitsbeforeapplyingcontrolpower.
2. Connecttheassemblytothestationgroundbeforeapplyinganypower
3. Incaseoffire,donotuseliquidfireextinguisheruntilallcircuitshavebeendisconnected.
4. Ifanassemblyistobestoredforanextendedperiodpriortoinstallation,provisionsmustbemadeforenergizingthespaceheaterstopreventcondensationofmoistureinsidetheassem-bly.
1.6OtherPublicationsandDocumentation
Inadditiontothisinstructionmanual,otherprintedinformationanddocumentationissuppliedwitheachassembly.Thisadditionalinfor-mationwillinclude,butnotnecessarilybelimitedto,aMagnumDSLow-VoltagePowerCircuitBreakerinstructionmanual,arrangementdrawings,andconnectiondiagrams.ForadditionalreferencesseeSection6.
4
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Section 2: Receiving, Handling & Storage
NOTICEFOR COMPLETE RECEIVING, HANDLING AND STORAGE INSTRUCTIONS, SEE SECTION 2 OF THE PRIMARY INSTRUCTION BOOK IB01901001E, REFERENCED ELSEWHERE IN THIS PUBLICATION. INSTRUCTIONS WHICH FOLLOW EMPHASIZE THE UNIQUE FEATURES ASSOCIATED WITH MAGNUM DS LOW-VOLTAGE NEMA 3R ASSEMBLIES.
2.1GeneralInformation
MagnumDSMetal-EnclosedLow-Voltageassembliesareshippedinoneormoreshippinggroups,dependingonthenumberofverti-calsections,orthelimitationsofhandlingfacilitiesattheinstalla-tionsite.Thiscouldtypicallyresultinthreeorfoursectionsforacompleteassembly.MaximumlengthofapreassembledNEMA3Rshippingsectionis108”(2743mm)includingatransformerconnec-tionthroat,ifapplicable.
Allshippingsectionsareshippedsoastobeprotectedfromtheweatherduringshipmentbutarenotsuitableforstorageoutdoorsasshipped.NEMA3Rassembliesarenotweatherproofuntilcom-pletelyassembled.Treatthemthesameasindoorequipmentuntilfullyassembled.
2.2Receiving
WhenaMagnumDSLow-Voltageassemblyreachesitsdestination,thepurchasershouldcheckthematerialreceivedagainsttheship-pinglisttobecertainthatallitemshavearrived.Noteaccuratelyanydiscrepancies.Eachshippinggroupisplainlymarkedwithoraccom-paniedbyanidentifyingshopordernumber,generalordernumberandshippingweight.Eachshipmentincludesacontentslistwhichisapartoftheoverallpackageofshippingpapers.Toavoidthelossofanyparts,thecontentsofeachcontainershouldbecarefullycheckedagainstthepackinglist.Donotdiscardanypackingmate-rialuntilitiscertainthateveryitemhasbeenreceivedintheproperconditionandthatcertainpackingmaterialwillnotberequiredlaterforequipmentstorage.Largeritems,suchasportabletravelinglift-ers,areshippedinseparatecartons.Otherlooseandunmounteditemsmaybepackedinadditionalcartons.Theseitems,suchasshippingsplithardware,shouldbeloggedinandsetasideinasafelocationuntiltheassemblyhasbeensetinitsfinalposition.
Equipmentshippedfromthefactoryiscarefullypackedandinspect-edpriortoitsdeparture.Onoccasion,however,equipmentdamageisincurredduringtransportation.Ifanydamageisfound,fileadam-ageclaimimmediatelywiththetransportationcarrierandnotifyanEatonrepresentative.Allclaimsshouldbefiledassoonaspossibleandincludeapplicablepartnumbers,shopordernumbersand/orgeneralordernumbers
2.3Precautions
Itispreferabletouseanoverheadcranewhenmovingtheassem-bly.Circumstancesattheinstallationlocationmaypreventtheuseofanoverheadcraneforallmovement.Insuchinstances,thecarefuluseofrollerscanbeemployed.AlthoughthemethodsformovingNEMA1andNEMA3Rassembliesaresimilar,thetechniquesvaryslightly.Thedifferencesarehighlightedinthissection.
2.3.1 Overhead Lifting
WARNINGFAILURE TO FOLLOW LIFTING INSTRUCTIONS MAY RESULT IN DEATH OR SERIOUS BODILY INJURY. READ INSTRUCTIONS FOR LIFTING SWITCHGEAR PRIOR TO ATTACHING CABLES, CHAINS OR SPREADER BARS.
Liftingplatesareattachedalongtheassemblybaseatthefrontandrearforcranecableattachment.Suitablysizedspreaderbars(notprovided)mustbeplacedbetweenliftcablestopreventequipmentdamage(Figure1).Ifitappearsthatthecableswilltouchtheassem-blyduringtheliftingprocess,placeappropriatelysizedlumberalongthesideswherecontactcouldbemadebetweenthecableandtheequipment.Thiswillpreventdamagecausedbytheliftingcables.
Figure1.NEMA3RAssemblyLiftingMethod.
5
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
2.3.2 Rolling
Ifduringthemovingandpositioningprocessitisnotfeasibletouseanoverheadcrane,theequipmentcanbemovedonconstructionrollers.TheheavysteelbaseonanNEMA3Rassemblyissuitableforusedirectlywhenrolling.Usenolessthanfourevenlyspacedrollersforassemblymovement.Sinceequipmentlengthcanvary,each1.5to2.0feet(457to610mm)ofequipmentlengthrequiresaroller.Astheequipmentiscarefullymoved,therollersthatbecomefreeattheendoppositethemovementdirectionshouldonceagainbeplacedatthefrontforcontinuedmovement.
2.3.3 Lifting Plate Removal
Theliftingplatesattachedatthebaseperformthedualpurposeofprovidingaconvenientandrobustmethodofsecuringtheunittothefoundation.Aseparatechannelbaseisnotrequired.Onceanassemblyisinitspermanentlocationremovetheliftingeyesfromtheangles(Figure2).Rotatetheangles180degreesandreinstall.Usetheholesintheanglestobolttheassemblytothefoundation.
Figure2.Figure2LiftingAngleinPlaceAsReceivedPriortoReversingforSecuringtoFoundation.
2.4Storage
Afullyassembledassemblyrequiresaminimumofcareduringoutdoorstorage.Theareashouldbereasonablyfreeofdirtandcorrosivegases.Thespaceheaters,whicharestandardwithweath-erproofassemblies,mustbeenergizedtopreventcondensation.NEMA3Rassemblieswhicharenotfullyassembledmustbetreat-edinthesamemannerasindoorequipment.
CAUTIONWHEN SPACE HEATERS ARE ENENERGIZED, CARE MUST BE TAKEN THAT INTEGRAL CONTROL POWER TRANSFORMERS ARE NOT BACK-FED. DISCONNECT PRIMARY AND SECONDARY FUSES.
Duringstorage,allassemblies,whetherindoorsoroutdoors,shouldbeplacedonafirm,levelsurface.Thiswillpreventanyunneces-sarystrainorpossibledistortion.Storeallotherseparatelypackagedaccessoryequipmentinaclean,drylocation.Itisrecommendedthatawaterproofcoverbeplacedovercircuitbreakercartonsandthecartonskeptinanindoorstoragelocationwhenthecircuitbreak-ersarestoredseparatelyfromtheassembly.
Section 3: Equipment Description3.1GeneralDescription
Thefollowingdescriptionsapplytostandardmetal-enclosedcon-structionandwiring.Specialfeaturesandcontrolschemesareoftenincorporatedpercustomerspecifications.Thesespecialfeaturesareevidentandportrayedonthedrawingsanddiagramsforthespecificassembly.Instructionsonincludedapparatussuchasrelays,instru-ments,controlswitchesandcircuitbreakersareincludedelsewhereinseparateinstructionbooksorsheets.
Eachlow-voltage(600voltsandbelow)indoorandoutdoormetal-enclosedassemblyisfactoryassembledandtested.Itisdesignedtorequireaminimumamountoflaborforinstallation.
Eachmetal-enclosedassemblyconsistsofastationarystructurethatincludesoneormorefree-standingverticalsectionsmechanicallyandelectricallyjoinedtomakeasinglecoordinatedinstallation.
Inenclosuresidentifiedasrear-accessible,averticalsectionconsistsofthreemajordivisions:thefrontcompartment(breakers),buscompartment,andcablecompartment,whereinthepowercablesareaccessedthroughdoorslocatedintherearoftheenclosure.Inaddition,personnelingress(andaccesstothecircuitbreakers)isaffectedeitherthroughawalk-inaisleway(Figure3)ordirectlythroughthefrontoftheenclosure(Figure4).
Inenclosuresidentifiedasfront-accessible,thethreedivisionsareredistributedbetweenapairofverticalsections:frontcompartment/buscompartmentinonehalf;cablecompartment/buscompart-mentintheremaininghalf,whereinthepowercablesareaccessedthroughdoorslocatedinthefrontoftheenclosure.Inaddition,per-sonnelingress(andaccesstothecircuitbreakers)isaffectedeitherthroughawalk-inaisleway(Figure5)ordirectlythroughthefrontoftheenclosure(Figure6).
AllMagnumDSMetal-EnclosedLow-VoltageNEMA3RAssembliesareapredetermineddepthbasedononeofthefourconfigurationschosen.Directtransformerconnectionsareeasilymanagedwithrear-accessibleunits.However,duetotheforeshorteneddesignoffront-accessibleassemblies,directtransformerconnectionisnotpossiblewithouttheaidofaspecialtransitionenclosure.Ifthisisanessentialpartofaninstallation,contactanEatonsalesandser-vicerepresentativeforassistance.
NOTICEFOR SPECIFIC INFORMATION REGARDING THE INTERNAL CONSTRUCTION OF MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE ASSEMBLIES, INCLUDING BUT NOT LIMITED TO CIRCUIT BREAKER INSTALLATION, BUS CONSTRUCTION AND CABLE/CONDUIT SPACES, REFER TO SECTION 3 OF IB01901001E, REFERENCED IN SECTION 6 OF THIS MANUAL.
6
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
3.2NEMA3REnclosureConstructionOptions(Figures3-6)
MagnumDSMetal-EnclosedLow-VoltageNEMA3RAssembliesareofferedinfourvarietiestomeetthelimitationsofspaceandcustomerpreferences.Theoptionsincludelocationofpowercableconnectionsaswellaspresenceorabsenceofapersonnelingressaisle-way.
3.2.1 Rear-Access with Aisle-way
Powercableconnectionsareaccessiblefromtherearoftheassem-bly.Therearaccessdoorsarehingedandprovidedwithdoorstops.Thesebraceskeepthedoorsopenata90degreeangle.Powercablesandconduitscanexitthroughthefloororthroughtheroofiftheproperroof-exitflangeisinstalled(bycustomerorderrequest).Connectiontolineand/orloadbreakerconnectionsisthesameasdescribedinIB01901001E,theindoorassemblyliteratureforrear-accessibleenclosures.
Afrontoperatingandmaintenanceaisleextendsthroughallunitsoftheassembly.Alargereinforceddoorwithpanichardwareisstan-dardateachendoftheaisle.Thesedoorscanbeopenedfromtheinside,evenwhenpadlockedfromtheoutside.
Thestructurealsoincludes,asstandard,filteredventilationopen-ings(filterscanbechangedwithoutopeningaisleorrearcompart-mentdoors),aislelighting,GFIprotectedconveniencereceptaclesandspaceheaters.Whenspecified,athermostatismountedinthecablecompartment.Spaceheatersarelocatedinthe“D”positionbreakercell,buscompartmentandcablecompartmentofeachverti-calsection
3.2.2 Rear-Access without Aisle-way (Non walk-in)
Powercableconnectionsarethesameasdescribedabove.Connectiontolineand/orloadbreakerconnectionsisthesameasdescribedinIB01901001E,theindoorassemblyliteratureforrear-accessibleenclosures.
Thefrontaisle-wayisabsentinthenon-walk-indesign,permittinganassemblydepthreductionofapproximately32inches(812mm)overthestandardrear-accesswalk-inassembly.Accesstothebreakercompartmentisaffectedthroughfull-heightdoorsonthefrontoftheenclosure.Thesedoorscontainthesamebracingfeaturespresentonthereardoorsdescribedabove.Ventilatedfilters,lighting,recep-taclesandheatersarestandardasdescribedabove.
Theworkspacebetweentheexternalshellandtheinternalbreakerenclosureisapproximately7.5inches(190mm),thereforetheneedforameansofemergencyexitisnotprovided.
otee:N Auniquefeatureofthenon-walk-inassemblyistheinternalbreakerdoorshingeontheright-handsideasnormalconvention,ratherthantheleft.
3.2.3 Front-Access with Aisle-way
Frontaccessibleassembliesprovidefurtherfootprintreductionswhenrequiredbycustomerinstallations.
Powercableconnectionsareaccessiblefromthefrontoftheassem-blythroughthemaintenanceaisle-wayasdescribedbelow.Powercablesandconduitscanexitthroughthefloororthroughtheroofiftheproperroof-exitflangeisinstalled(bycustomerorderrequest).Connectiontolineand/orloadbreakerconnectionsisthesameasdescribedinIB01901001E,theindoorassemblyliteratureforfront-accessibleenclosures.
Afrontoperatingandmaintenanceaisleextendsthroughallunitsoftheassembly.Alargereinforceddoorwithpanichardwareisstan-dardateachendoftheaisle.Thesedoorscanbeopenedfromtheinside,evenwhenpadlockedfromtheoutside.
Thestructurealsoincludes,asstandard,filteredventilationopen-ings(filterscanbechangedwithoutopeningaisleorrearcompart-mentdoors),aislelighting,GFIprotectedconveniencereceptaclesandspaceheaters.Whenspecified,athermostatismountedinthecablecompartment.Spaceheatersarelocatedinthe“D”positionbreakercell,buscompartmentandcablecompartmentofeachverti-calsection.
3.2.4 Front-Acess without Aisle-way (Non walk-in)
Powercableconnectionsarethesameasdescribedabove.Connectiontolineand/orloadbreakerconnectionsisthesameasdescribedinIB01901001E,theindoorassemblyliteratureforfront-accessibleenclosures.
Thefrontaisle-wayisabsentinthenon-walk-indesign,permittinganassemblydepthreductionofapproximately31inches(784mm)overthestandardfront-accesswalk-inassembly.Accesstothebreakercompartmentandpowercableconnectionsisaffectedthroughfull-heightdoorsonthefrontoftheenclosure.Thesedoorscontainthesamebracingfeaturespresentonthereardoorsdescribedabove.Ventilatedfilters,lighting,receptaclesandheatersarestandardasdescribedabove.
Theworkspacebetweentheexternalshellandtheinternalbreakerenclosureisapproximately7.5inches(190mm),thereforetheneedforameansofemergencyexitisnotprovided.
otee:N Auniquefeatureofthenon-walk-inassemblyistheinternalbreakerdoorshingeontheright-handsideasnormalconvention,ratherthantheleft.
7
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
C
C
9255C35
120.0[3047]
OVERALL DEPTH
18.4[468]
BUS OPENING(FROM BASE)
109.1[2772]
105.1[2668]
51.2[1301]
2.0[51]
4.0[102]
3.9[99]
2.3[58]
28.6[726]
(FROMBASE)
26.0[660]
43.4[1102]
AISLE WIDTH117.1[2974](BASE)
30.2[767]
(OPENINGWIDTH)
0.6[15]
33.5[850]
(DOORWIDTH)
5.8[146]
5.8[146]
111.5[2832]
OVERALLHEIGHT
Figure3.SideElevationNEMA3RAssemblyRear-AccessiblewithWalk-inAisleWay.
8
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Figure4.SideElevationNEMA3RAssemblyRear-AccessiblewithoutWalk-inAisleWay.
C
C
9259C06
86.0[2185]
(BASE)
26.0[660]
28.6[726]
(FROMBASE)
51.2[1301]
2.0[51]
4.0[102]
109.8[2789]
OVERALLHEIGHT
105.1[2669]
109.1[2770]
4.2[107]
18.4[468]
88.0[2236]
OVERALL DEPTH
BUS OPENING(FROM BASE)
9
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Figure5.SideElevationNEMA3RAssemblyFront-AccessiblewithWalk-InAisleWay.
8652C19
87.1[2211]
OVERALL DEPTH
29.1[740]
111.4[2830]
107.9[2740]
2.0[51]
3.9[99]
111.5[2832]
OVERALLHEIGHT
4.0[102]
30.2[767]
(OPENINGWIDTH)33.5
[850](DOORWIDTH) 5.8
[146]
43.4[1102]
AISLE WIDTH85.3
[2166](BASE)
BUS OPENING(FROM BASE)
10
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Figure6.SideElevationNEMA3RAssemblyFront-AccessiblewithoutWalk-InAisleWay.
8652C25
54.2[1378](BASE)
105.1[2669]
110.3[2800]
109.8[2789]
OVERALLHEIGHT
2.0[51]
4.0[102]
3.9[99]
30[766]
56.2[1428]
OVERALL DEPTHBUS OPENING(FROM BASE)
11
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Section 4: Installation
WARNINGBEFORE PROCEEDING WITH ANY INSTALLATION, TESTING, START-UP OR MAINTENANCE, REVIEW ALL OF SECTION 1 FOR SAFETY PRACTICES AND RECOMMENDATIONS. FAILURE TO DO SO MAY RESULT IN DEATH, SERIOUS BODILY INJURY OR PROPERTY DAMAGE.
4.1GeneralInformation
ThissectioncontainsinstructionsforinstallingMagnumDSMetal-EnclosedLow-VoltageAssemblies.ProperinstallationofMagnumDSMetal-EnclosedLow-VoltageAssembliesisofprimeimportance.Toomuchemphasiscannotbeplacedonthisphaseofthework.Studytheassociatedinstructionmanualsanddrawingscarefully.
CAUTIONPERSONNEL INSTALLING THIS EQUIPMENT MUST BE THOROUGHLY FAMILIAR WITH ALL ASSOCIATED INSTRUCTION MANUALS AND APPLICABLE GOVERNING CODES. ADDITIONALLY, ALL DRAWINGS, WHETHER MECHANICAL OR ELECTRICAL, MUST BE UNDERSTOOD AND STRICTLY FOLLOWED TO PREVENT POSSIBLE DAMAGE TO THE SWITCHGEAR OR EQUIPMENT BEING PROTECTED.
4.2LocationandFoundation
MagnumDSMetal-EnclosedLow-Voltageassembliesarecon-structedatthefactoryonsmoothlevelsurfacestoassurecorrectalignmentofallparts.Extracarebythepurchaserinselectingthelocationandpreparingthefoundationwillresultinreducedinstalla-tioncosts,aswellasgoodequipmentperformance.
4.2.1 Location
Ingeneral,thelocationwillhavebeendeterminedduringthespeci-ficationand/orprocurementphases.Certainlocationsmayimposerequirementswhichmustbemetsothattheswitchgearassemblymayoperateefficientlywiththeleastamountofmaintenance.Considerationmustbegiventotheopenspacerequiredatthefrontandrearoftheequipment,spaceattheendsofthelineup,andthecharacteristicsoftheenvironment.
Thespaceatthefrontmustbesufficienttomeetapplicablecodes,permittheopeningofdoors,theinsertionandwithdrawalofcircuitbreakers,andthetransferofcircuitbreakerstoothercompartmentsbymeansofanoverheadlifterorportableliftingdevice.Inrear-accessibleenclosures,thespaceattherearmustbesufficienttomeetlocalcodes,permitventilation,openreardoors,installcables,inspectequipmentandperformmaintenance.
4.2.2 Foundation
Thesitefoundationshouldbesmoothandlevel(within1/8inchperthreefeet[3.5mm/meter]inanydirection)toavoiddistortionofthestructure.Theliftingplatesattachedatthebaseperformthedualpurposeofprovidingaconvenientandrobustmethodofsecuringtheunittothefoundation.Aseparatechannelbaseisnotrequired.Oncetheassemblyisinitspermanentlocationremovetheliftingeyesfromtheangles(Figure2).Rotatetheangles180degreesandreinstall.Usetheholesintheanglestobolttheassemblytothefoundation.Forfurtherdetailsseethefoundationplansprovidedwiththeequipment.
4.2.3 Conduits
Provisionsmustbemadeinthesitefoundationforallconduitsenteringfrombelow.Specificfloorplandetailsprovidedwiththeequipmentmustbeusedtodeterminethefinalconduitlayoutandfootprintrequiredforeachlineup(SeeBasePlanreferencedrawing4A37896).
Powerconduitsshouldprojectabovethefinishedfloornotmorethanteninches(254mm)foroneoftheseassemblies.Controlwireconduitsshouldnotextendhigherthannineinches(228mm).Itwillsimplifymovingtheshippingsectiongroupsintoplaceifthecon-duitsareflushwiththeconcretesurfaceandappropriateextensionsleevesaddedaftertheunitsareintheirfinallocation.SeeBasePlanreferencedrawing4A37896suppliedwiththeassemblyforbot-tomentryconduitspaceandlocation.
4.3ShippingSectionGroupAssembly
Beforeconnectingtheseparateshippingsectionsoftheassembly,allcomponentsshouldbeavailableatthesitelocation.Thepreparedfoundationshouldbereadyandallembeddedconduitsinstalledandcapped.
CAUTIONPRIOR TO INSTALLATION AND ASSEMBLY, BE CERTAIN THE FOUNDATION IS LEVEL AND FREE OF ANY DEBRIS TO PREVENT EQUIPMENT DAMAGE.
4.3.1 Preparation of the Unit for Assembly
MagnumDSNEMA3RAssembliesareshippedwithexternalship-pingbracesattachedtopreventdistortionoftheunitduringtrans-port.Thesebracesmaybealengthofaluminumangle,asteelsupportasshowninFigure7,orbothdependingupontheenclosuretype.Anysuchbraceattachedistemporaryandshouldberemovedanddiscardedpriortoconnectingtheshippingsections.
Roofseamsarecoveredbyaweldedseamcover.Theseareshippedattachedtotheenclosureroofforconvenience.Priortojoiningshippingsections,removetheseamcoverfromanyshippingsectionwhereitoverhangs,similartoasshowninFigure8.Removethesecuringhardwareandretainforreinstallationaftertheunitsareconnectedandsecuredpertheinstructionsbelow.
Alsoremoveanypackingcardboard,includingcardboardonaisle-wayfloors,priortoinstallation.
Figure7.TemporaryShippingBraceonWalk-inAisleway.
12
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Figure8.RoofSeamCover.
4.3.2 Assembly Procedures
Whencorrectlyinstalled,bothrearandfront-accessibleassembliesshouldconformtothefollowingrequirements:
1. Frontpanelsshouldformastraightline.Whentransformersand/orothergearareincluded,equipmentshouldbelocatedinkeep-ingwiththeplandrawingssuppliedwiththeequipment.
2. Verticalsectionsmustbecorrectlyspacedfromcentertocenterandplumb.Asuggestionforlininguptheshippinggroupsistoestablishabaselineafewinchesinfrontoftheassemblyandparalleltothefinallocation.Equalizethedistancesfromthefrontoftheshippinggroupstothebaseline,thusmakingthefaceoftheassemblyparalleltothebaseline.Checkeachverticalsec-tionbydroppingaplumblinefromthetopcornerofeachverticalsection.Itshouldalignwiththebottomcorner.
3. Theentireassemblyofverticalsectionsshouldbesecurelyfas-tenedtofloorchannelsorbasepad.
4. Shippinggroupsmustbesecurelyboltedtogetherandallbusandcontrolwiringconnectionsproperlymade.
Afterthefirstshippinggrouphasbeenlocated,thesecondship-pinggroupshouldbemovedintopositionandsimilarlychecked.Theshippinggroupsarefastenedtogetherinaccordancewiththeinstructionsgivenindrawing9253C18.Thisdrawingisincludedintheinformationpacketattachedtothesideoftheswitchgearassem-bly.Shouldadditionalcopiesofthisdrawingbeneeded,contactyourEatonsalesoffice.
4.4Bus,CableandControlConnections
RefertoSection4.4.1thru4.4.6ofreferenceIB01901001Eforcom-pleteinstructionsandguidelinesonvariousbusconnections,installa-tionofpowercables,andconnectionofcontrolwiring.
4.5TravelingCircuitBreakerLifter
Thetravelingoverheadcircuitbreakerlifterisastandarddeviceinstalledontheseassemblieswhereanaisle-wayispresent.Forconveniencethehoistassemblyisshippedcontainedwithinoneoftheendshippingsectionsofanymulti-sectionshippinggroup.Removetheretainingstrapssecuringthebreakerlifterhoistpriortouse.Aready-touseoverheadlifterisshowninFigure9.
Figure9.OverheadCircuitBreakerLifter.
DANGERDO NOT STAND UNDER THE CIRCUIT BREAKER DURING HOISTING OPERATIONS. THE CIRCUIT BREAKER MIGHT SLIP AND CAUSE PERSONAL INJURY. KEEP HANDS AND TOOLS AWAY FROM SPREADER BAR, LIFTING HOOKS AND BREAKER. SEVERE INJURY MAY RESULT. SUDDEN MOTIONS ARE COMMON IN A CABLE UNDER TENSION AS IT WINDS AROUND A WINCH DRUM.
Spreaderbarsthatattachtothetravelinghoistforpurposesofattachingtothecircuitbreakerwillbeshippedseparately.
Inassemblieswhereanaisle-wayisnotpresent(non-walk-in),orbycustomerrequest,aseparateportablebreakerliftermaybespeci-fied.Portableliftingdevicesarerecommendedtoonlybeutilizedonsmoothlevelsurfaces.SeeFigure10below.
4.6MovingParts
TherearefewmovingpartsinthestationarystructuresofMagnumDSLow-VoltageAssemblies.Itisrecommendedthatallmov-ingpartsbecarefullyoperatedbyhand.Thiswillensurethatnobindingordamagehasoccurredduringshipmentorhandling.Insomecases,accessoriesmaybeblockedorbracedforshipment.Thoroughlycheckapparatus,suchasmetersandrelays,forformsofblockingorbracingwhichmustberemoved.
13
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Fig
ure
10.
Cir
cuit
Bre
aker
Inst
alla
tio
nw
ith
Po
rtab
leB
reak
erL
ifter
wit
ho
utW
alk-
inA
isle
Way
.
14
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Section 5: Inspection, Testing and MaintenanceForcompleteinstructionsregardinginspectionandtestingofMagnumDSswitchgearandswitchboardspriortostart-upandoper-ation,seeSection5ofIB01901001E.Readandfollowallinstructionsregardingsafetypracticesdescribedtherein.
DANGERENERGIZING THE SWITCHGEAR FOR THE FIRST TIME IS POTENTIALLY DANGEROUS. THEREFORE, ONLY QUALIFIED PERSONNEL SHOULD BE PRESENT WHEN THE EQUIPMENT IS ENERGIZED. IF PROBLEMS CAUSED BY DAMAGE OR POOR INSTALLATION PRACTICES HAVE NOT BEEN DETECTED IN THE CHECKOUT PROCEDURE (PREVIOUSLY DESCRIBED), DEATH, PERSONAL INJURY OR SERIOUS DAMAGE MAY RESULT WHEN POWER IS APPLIED.
Forinstructionsregardingperiodicmaintenanceofswitchgear/switchboarddevices,busandconnections,aswellasreplacementparts,seeSection6ofIB01901001E.Readandfollowallinstructionsregardingsafetypracticesdescribedtherein.
DANGERWHEN ENERGIZED, A CIRCUIT BREAKER IS PART OF A HIGH POWER SYSTEM. BEFORE ATTEMPTING ANY INSPECTION OR MAINTENANCE, BE SURE THAT ALL PRIMARY AND CONTROL CIRCUITS HAVE BEEN DE-ENERGIZED AND GROUNDED AS REQUIRED. ALSO MAKE CERTAIN THAT PROPER STEPS HAVE BEEN TAKEN TO BE SURE THAT THEY WILL REMAIN DE-ENERGIZED UNTIL ALL WORK IS COMPLETED. FAILURE TO DO SO MAY RESULT IN DEATH, BODILY INJURY OR ELECTRICAL SHOCK.
Section 6: Document ReferencesInadditiontothisInstructionBook,thefollowingInstructionBooksanddrawingsarecommonlyincludedinanylow-voltageassemblyshipment.Pleaseinspectthepacketattachedtotheoutside,orwithinanemptycell,forallpertinentdocumentationbeforecontact-inganEatonservicerepresentativeforreplacements.
2A97855 MagnumDSStructureSectionViewTypeDS Low-VoltageMetal-EnclosedSwitchgear
4A37896 MagnumDSStructureBasePlan
9253C18 ShippingSplitBusInformation
9253C21 InstallationSpaceRequirements
Inaddition,thefollowingdocumentsmaybeincludeddependinguponoptionalequipmentcontainedwithintheassembly:
4A37898 InstallationGuidelinesforUsersofMagnumDS Low-VoltageRear/FrontAccessSwitchgear AssembliesforSeismicApplications
IB2C12060H08 InstructionsforInstallation,Operationand MaintenanceofMagnumDS,DSXandDSLLow VoltagePowerCircuitBreakers
IB2C12063H02 InstructionsforInstallation,Operationand MaintenanceofMagnumSBInsulatedCaseLow VoltagePowerCircuitBreakers
IB32-693A InstructionsforFieldTestingofGroundFault SystemsUtilizingEatonMagnumDSCircuit Breakers
IB32-698C InstructionsforC-HRG“Safe-Ground”Low- VoltageHighResistancePulsingGroundSystem
IB52-01-TE InstructionsforEatonTypeCM52Network Protectors800to4500Amperes
MN01301001E InstructionsforInstallation,Operationand MaintenanceofSeriesNRXLowVoltagePower (Air)CircuitBreakers
Also,supportingdocumentationandinstructionsforauxiliarycompo-nentsanddevicescontainedwithintheassemblywillbeforwardedwithanyshipment.TheaccuracyofclaimsmadewithindocumentsbyothermanufacturersisnottheresponsibilityofEatonbutthedevicemanufacturer.
Therearenumeroussupportingdocumentswhicharenotlistedhereduetothewidevarietyofcomponentscontainedwithinanygivenassembly.Forafullselectionofavailabledocuments,seetheTechnicalDocumentssectionofwww.Eaton.com.
15
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
EATON CORPORATION www.eaton.com
Notese:
EatonCorporationElectricalSector1111SuperiorAve.Cleveland,OH44114UnitedStates877-ETN-CARE(877-386-2273)Eaton.com
©2011EatonCorporationAllRightsReservedPrintedinUSAPublicationNo.IB01900002E/TBG000585June2011
EatonisaregisteredtrademarkofEatonCorporation.
Allothertrademarksarepropertyoftheirrespectiveowners.
InstructionBookletIB01900002EEffective June 2011
Instructions for Magnum DS Metal-EnclosedLow-Voltage NEMA 3R Assemblies
ThisInstructionBookletispublishedsolelyforinformationpurposesandshouldnotbeconsideredall-inclusive.Iffurtherinformationisrequired,youshouldconsultanauthorizedEatonsalesrepresenta-tive.
ThesaleoftheproductshowninthisliteratureissubjecttothetermsandconditionsoutlinedinappropriateEatonsellingpoliciesorothercontractualagreementbetweentheparties.Thisliteratureisnotintendedtoanddoesnotenlargeoraddtoanysuchcontract.ThesolesourcegoverningtherightsandremediesofanypurchaserofthisequipmentisthecontractbetweenthepurchaserandEaton.
NOWARRANTIES,EXPRESSEDORIMPLIED,INCLUDINGWARRANTIESOFFITNESSFORAPARTICULARPURPOSEORMERCHANTABILITY,ORWARRANTIESARISINGFROMCOURSEOFDEALINGORUSAGEOFTRADE,AREMADEREGARDINGTHEINFORMATION,RECOMMENDATIONS,ANDDESCRIPTIONSCONTAINEDHEREIN.
InnoeventwillEatonberesponsibletothepurchaseroruserincontract,intort(includingnegligence),strictliabilityorotherwiseforanyspecial,indirect,incidentalorconsequentialdamageorlosswhatsoever,includingbutnotlimitedtodamageorlossofuseofequipment,plantorpowersystem,costofcapital,lossofpower,additionalexpensesintheuseofexistingpowerfacilities,orclaimsagainstthepurchaseroruserbyitscustomersresultingfromtheuseoftheinformation,recommendationsanddescriptioncontainedherein.