- 1 -
Instruction Manual
・This manual covers the handling method of MELSEC BACKUP TOOL.
・Before use, you are kindly requested to read this manual carefully and understand the function and performance of MELSEC BACKUP TOOL for correct handling.
・This software is copyrighted by MITSUBISHI ELECTRIC CONTROL SOFTWARE CORPORATION.
・For this product software, it is required to purchase one cense per computer.
・We assume no responsibility for the results and effect upon operation of this product.
・The content described in this manual is subject to change without notice.
Doc No. : MCO14-13K0007
- 2 -
Sub
No.
Rev. Date Rev. Content
Revision History
- 3 -
CONTENTS
CONTENTS ....................................................................................... 3
1. Introduction .............................................................................. 5
1.1 How to use this manual .................................................................................................... 6 1.2 Confirmation of bundled items .......................................................................................... 7 1.3 Outline ............................................................................................................................... 8
1.3.1 Application of this product 8 1.3.2 Outlined functions 8
1.4 Prior conditions ................................................................................................................. 9
2. Before Handling ..................................................................... 14
2.1 System Requirements .................................................................................................... 15 2.2 Installation ....................................................................................................................... 16
2.2.1 Configuration setting of OS 17 2.2.2 Commercial software installation 26 2.2.3 Installation of MELSEC BACKUP TOOL 27
2.3 Uninstallation .................................................................................................................. 31
3. How to Use ............................................................................ 32
3.1 Operation flow ................................................................................................................. 33 3.2 Cable connection ............................................................................................................ 34 3.3 Editing of setting information .......................................................................................... 35
3.3.1 MELSEC Backup Setting start 35 3.3.2 Configuration setting 36 3.3.3 Group setting 37 3.3.4 MELSEC setting 40 3.3.5 Backup setting 44 3.3.6 Save of Setting Information 48 3.3.7 Import/Export of setting information 49
3.4 Creation of setting information ........................................................................................ 51 3.5 Backup execution ........................................................................................................... 53
3.5.1 Operation of backup schedule 53 3.5.2 Backup Test 56
3.6 Confirmation of execution results ................................................................................... 58 3.6.1 Backup file confirmation 58 3.6.2 Backup execution log 59 3.6.3 In case Backup is not normally completed 61
4. Message ................................................................................ 62
4.1 Backup setting message ................................................................................................. 63 4.1.1 "Import" Menu 63
- 4 -
4.1.2 "Export" Menu 63 4.1.3 "Read" Menu 64 4.1.4 "Setting file create" Menu 65
4.2 Backup Tool message .................................................................................................... 71 4.2.1 Current state 71 4.2.2 Execution error information 73
5. Trouble-Shooting ................................................................... 76
6. Restrictions & Precautions ..................................................... 77
6.1 Restrictions ..................................................................................................................... 78 6.1.1 Common restrictions and precautions 78 6.1.2 Restrictions and precautions for GX Developer 80 6.1.3 Restrictions and precautions for GX Works2 81 6.1.4 Restrictions and precautions for ACPU 83
7. Appendix ............................................................................... 84
7.1 Changing of language selection ..................................................................................... 85
- 5 -
1. Introduction The descriptions in this manual and the features and applications of MELSEC BACKUP TOOL are explained hereunder.
Prior to use, you are kindly requested to read this manual carefully for a full understanding of the product functions and
handle correctly.
- 6 -
1.1 How to use this manual
This manual covers the outline description and installation procedure in "1. Introduction" to "2. Before Handling",
and the function details in "3. How to Use".
For first use of MELSEC BACKUP TOOL, it is recommended to read this manual in order from the first page.
●Meanings of symbols/abbreviated terms used herein
The symbols described herein denote the following meaning:
Denoting the content requiring special care.
Denoting the supplementary content and care-required content.
Denoting the point described the operation-related content.
●Target readers
The target readers of this manual presuppose that they understand the basic operation of the software/hardware shown
below.
・GX Developer 8
・GX Works2
・MELSEC
●Terms and abbreviated names used herein
The terms and abbreviated names used herein are as listed below.
Table 1-1 Names/Abbreviated Names used herein
Name/Abbreviated
Name
Description
Maintenance computer The Computer in which MELSEC BACKUP TOOL is installed Configuration information
Backup target MELSEC information, Group setting and Schedule data
Backup Obtaining program/parameter/device values from MELSEC and saving in computer
Backup data Type GX Developer or Type GX Works2 (work space) MELSEC sequencer project.
GX Developer MELSEC Programming and Maintenance tool (Version8)
GX Works2 MELSEC Programming and Maintenance tool
GPPA Generic term for SW SRXV-GPPA and SW IVD-GPPA
BACKUP TOOL MELSEC BACKUP TOOL
Backup Setting MELSEC Backup Setting
- 7 -
1.2 Confirmation of bundled items
Fig. 1-1 Bundled Items
MELSEC BACKUP TOOL Installation DVD(1pc) ・Software license agreement (1 set)
・For prior reading (1 set)
・Notice of product subject to control by Export
Trade Control Order, etc. (1 sheet) ・Confirmation sheet (1 sheet)
・User registration sheet (1 sheet)
・Inquiry sheet(1 sheet)
- 8 -
1.3 Outline
1.3.1 Application of this product
MELSEC BACKUP TOOL is the software that is to allow the running program with MELSEC used to be automatically saved
in the computer.
In addition, MELSEC BACKUP TOOL is able to set the schedule ensuring the group control of multiple MELSEC and the
time for save execution.
By introducing this software, the recovery work for unexpected occurrence (e.g. MELSEC trouble, etc.) can be carried out
smoothly.
1.3.2 Outlined functions
MELSEC BACKUP TOOL is a system that is intended to automatically back up the MELSEC program connected on the
network according to the schedule. The backup file is saved as a project of GX Developer/GX Works2.
Fig. 1-2 Outline of Backup Function
Ethernet
Maintenance Computer
MELSECNET10/H
Network #1
Network #2
- 9 -
1.4 Prior conditions
(1) Precautions for backup target The MELSEC which MELSEC BACKUP TOOL can back up is able to complete the connection target setting for GX
Developer or GX Works2 from the computer in which it is installed.
"Able to complete connection target setting" for GX Developer means the state of no error when "Communication
Test" button is clicked, after the connection target is specified in the "Specifying the Connection Target" dialogue
that is displayed when the GX Developer "online (O)"-"Specifying the connection target (C)" is clicked.
To fix the setting content, select the "OK".
"Able to complete connection target setting" for GX Works2 means the state of no error when the "Communication
Test" button is clicked in the "Specifying the Connection Target" dialogue. The "dialogue for specifying the
connection target" is displayed when the GX Works2 navigation-frame connection target is clicked.
To fix the setting content, select the "OK".
Please click the "Connection test" button, in order to check that an error does not occur.
1
Click the "OK" button. 2
Please click the "Connection test" button, in order to check that an error does not occur.
1
Click the "OK" button. 2
- 10 -
For MELSEC not completing the GX Developer or GX Works2 connection setting, the connection channel from the
computer to MELSEC shall be built out first, and then ensuring the backup. For the maintenance computer
-MELSEC connection channel, there are two cases, physical connection and GX Developer or GX Works2 setting.
See each of the manual for physical connection method and GX Developer or GX Works2 setting.
(2) Available network channel
MELSEC BACKUP TOOL can be backed up from another MELSEC connected in the MELSECNET by utilizing the
via-connection except for the directly-connected MELSEC.
The MELSECNET that is able to be utilized with MELSEC BACKUP TOOL is a network channel ensuring completion of
connection target setting with MESECNET II/10/H, Ethernet, and GX Developer/GX Works2.
For MELSEC BACKUP TOOL, the Trial package is available, which offers 30 days use free of charge. If the
via-target MELSEC is to be backed up by utilizing the MELSECNET, the Trial package must be used for operation
check.
See the "1.4(5) Precautions for use of trial package".
(3) Installation
MELSEC BACKUP TOOL is intended to be installed in the computer for use.
Then, before use, Configuration setting to OS and installation are required.
Implement the Configuration setting as described in "2.2.1 Configuration setting of OS".
For installation, the commercial software and MELSEC BACKUP TOOL shall be installed.
Implement the installation as described in "2.2.2 Installation of commercial software".
Implement the installation as described in "2.2.3 Installation of Installation of MELSEC BACKUP TOOL".
Configuration setting of OS and installation work of MELSEC BACKUP TOOL, including commercial software, are
mandatory.
- 11 -
(4) MELSEC accepted by MELSEC BACKUP TOOL The PLC that is targeted for backup with MELSEC BACKUP TOOL is listed below.
Table 1-2 Targets MELSEC for MELSEC BACKUP TOOL
Project Form MELSEC
GX Developer Form ACPU
A2A(S1), A3A
QCPU(Q Mode)
Q02, Q02H, Q02U, Q03UD, Q03UDE,
Q04UDEH, Q04UDH, Q06H, Q06UDEH, Q06UDH,
Q10UDEH, Q10UDH, Q12H, Q13UDEH, Q13UDH,
Q20UDEH, Q20UDH, Q25H, Q26UDEH, Q26UDH
GX Works2 Form QCPU(Q Mode)
Q02, Q02H, Q02U, Q03UD, Q03UDE, Q03UDV,
Q04UDEH, Q04UDH, Q04UDV,
Q06H, Q06UDEH, Q06UDH, Q06UDV,
Q10UDEH, Q10UDH, Q12H, Q13UDEH, Q13UDH, Q13UDV,
Q20UDEH, Q20UDH, Q25H, Q26UDEH,
Q26UDH, Q26UDV, Q50UDEH, Q100UDEH
(a) For MELSEC except for those above, there is a case that MELSEC BACKUP TOOL is able to back up,
however, the program/parameter saved in the computer HDD may not coincide with the program/parameter
inside the MELSEC. Prevent from the backup target.
(b) For ACPU, only the MELSEC implementing « computer Write » with GX Developer must be targeted. In case of
MELSEC BACKUP TOOL, even in case of ACPU implementing « Computer Write » for the program /
parameter created with another engineering tool (e.g. GPPA, etc.), no error is detected when backed up.
See the "6.1.4(1) Target MELSEC & "6.1.4(2) Project form".
(c) For backup in the project form of GX Developer, it is required that the GX Developer isinstalled in the computer.
Unless the GX Developer is installed, the « GX Developer » must not be specified for the backup form.
Otherwise, the actuation is indefinite.
(d) For backup in the project form of GX Works2, it is required that the GX Works2 is installed in the computer.
Unless the GX Works2 is installed, the« GX Works2 » must not be specified for the backup form.
Otherwise,theactuation is indefinite. (e) The MELSEC protected with Password setting/Remote Password setting cannot be backed up.
Before using MELSEC BACKUP TOOL, cancelling the password should be reviewed.
See the "6.1.1(7) Password setting/Remote Password setting".
- 12 -
(f ) For backup of various Configurators including GX Configurator, the IPARAM.QPA saved in the "Program
Memory" in MELSEC is to be backed up. In addition, in various Configurators, the parameter directly set in the
Intelligent memory shall be out of the backup target.
See the "6.1.1(9) Backup of Intelligent Function Module".
(g) The program in MELSEC, as backup target for MELSEC BACKUP TOOL, is a "Ladder program without label
used". Other programs cannot be backed up.
(h) For backup in the GX Developer format, it is a project in the format of "Program type is ladder without label use".
Backing up cannot be done in other formats
See the "6.1.2 (1) Project type/Program language".
(i) For backup in the GX Works2 format, the "Project type is a simple project". Further, it is a project in the format of
"Program type is ladder without label use". Backing up cannot be done in other formats
See the "6.1.3(1) Backup project format". See the "6.1.3(2) Project type/Program language".
- 13 -
(5) Precautions for use of Trial package There is no functional difference between the Trial package and the product package. Then, you can use the Trial package
in the actual environment before purchasing the product package.
The Trial package can be used for 30 days from the first start-up.
After passing 30 days, you cannot use it, therefore purchasing the product package is preferable.
As to the Trial package, when the "Backup Setting" and "Backup Tool" are started, it displays a message notifying of the
remaining number of days usable.
When installing the Trial package, set the Trial package serial No. on the User Information dialogue for installation.
The Trial package serial No. is "MCR101A-00000001234567".
For installation details, see the "2.2.3 Installation of Installation of MELSEC BACKUP TOOL".
The number of usable days is 30 days as maximum and the number of days notified shows the remaining days, not
including the current day.
As an example, it notifies of remaining 15 days as usable days not including this day.
(6) Switching from Trial package to product package
To update to the product package from the Trial package installed, it is required to uninstall the Trial package first and install
the product package.
For uninstallation, see the "2.3 Uninstallation".
For installation, see the "2.2.3 Installation of MELSEC BACKUP TOOL ".
- 14 -
2. Before Handling The installation of MELSEC BACKUP TOOL is described hereunder.
- 15 -
2.1 System Requirements
System Requirements of the computer in which MELSEC BACKUP TOOL is installed is as listed below.
Table 2-1 System Requirements of computer for MELSEC BACKUP TOOL
Item Specification
Computer Main Unit PLC:Core2Duo 2GHz or more Memory 3GB or more
Hard Disk Space 250GB
Basic Software(*2)(*3)(*4) Windows®XP Professional (English ver.) SP3
Windows®7 Professional (English ver.) (*1)(*4)(*5)
Display Resolution 1280 × 1024 dot or more
Required Commercial Software(*6) GX Developer 8 Version 8.109P or newer
GX Works2 Version 1.501X or newer
(*1) Windows XP Professional 64-bit Version cannot be used.
(*2) If the following function is used, there is a possibility that this product is not normally actuated. ・Application start in Windows® compatible mode ・User switching ・Remote desktop
・Large font (Detail setting on screen property) ・Windows® pause and standby
(*3) It cannot be used in case the logon user is subject to Guest authority.
(*4) It cannot be used for the logon users ensuring parent’s restriction valid.
(*5) The following Windows®7 functions cannot be used. ・Windows XP Mode ・Windows Touch
(*6) This software is to be provided by the clients (users). Not included in the package.
- 16 -
2.2 Installation
The flow of MELSEC BACKUP TOOL installation is shown below, and the operating procedure of each item is described on
the next page/thereinafter.
Fig. 2-1 Installation Order of MELSEC BACKUP TOOL
Start
Installation of MELSEC BACKUP TOOL
2.2.3
Configuration setting of OS 2.2.1
End
Commercial software installation 2.2.2
- 17 -
2.2.1 Configuration setting of OS
Setting required for computer OS is to be made. MELSEC BACKUP TOOL is installed in the mentioned computer.
(1) Setting of User Account Control (UAC) If the User Account Control (UAC) is valid inWindows®7, there is a case that MELSEC BACKUP TOOL is not actuated
normally.
Then, allow the User Account Control (UAC) to be invalid according to the following order.
Fig. 2-2 Control Panel
Fig. 2-3 User Accounts
Select the "Start" - "Control Panel". 1
Click the "User Accounts and Family Safety". 2
Click the "User Accounts". 3
- 18 -
Fig. 2-4 Change User Account
Fig. 2-5 User Account Control Settings
Click the "Change User Account Control settings". 4
Move the slider to the position of "Never notify" and click the "OK".
5
Restart the computer to make the change of User Account Control valid.
6
- 19 -
(2) Setting of system standby It is necessary to make the system standby setting invalid for normal backup with MELSEC BACKUP TOOL, even if the
computer is not operated for a certain time.
If a sleep or inactive state occurs during backup, the backup may not be done as scheduled or the backup data may be
incorrect, therefore, this setting must be carried out.
Windows®XP:
Fig. 2-6 Control Panel
Fig. 2-7 Display Properties
Fig. 2-8 Monitor Power Setting
Select the "Start" - "Control Panel" and click the "Screen".
1
Select the Screen Saver Tab on the screen of "Display Properties"
2
Click the "Power" in the "Monitor Power". 3
- 20 -
Fig. 2-9 System Standby
Change to "Never" for the "System Standby" in the "Power Schemes".
4
- 21 -
Windows®7:
Fig. 2-10 Control Panel
Fig. 2-11 System and Security
Fig. 2-12 Power Option
Select the "Start" - "Control Panel". 1
Click the "System and Security" from the "Control Panel".
2
Click the "Power Options" from the "System and Security".
3
Select the "Power saver", and click the "Change plan settings".
4
- 22 -
Fig. 2-13 Editing of Plan Setting
Fig. 2-14 Change of Detailed Power Setting
Click the "Change advanced power settings" from "Edit Plan Settings".
5
Select the "Hard Disk" - "Turn off hard disk after" - "Setting (Minutes):" and input zero on the "Power Option" screen.
6
Click the "OK". 7
- 23 -
(3) Setting of disk defragmenting tool If the disk defragmenting tool is executed during use of MELSEC BACKUP TOOL in Windows®7, there is a case of data
backup failure.
According to the following procedure, it is required to stop the schedule execution of disk defragmenting tool.
Fig. 2-15 Disk Defragmenter
If the "User Account Control" screen is displayed, click the "Yes". Then, carry out the item "2.2.1(1) Setting of User
Account Control (UAC)".
Fig. 2-16 Modify Schedule
Select the "Start" - "Accessory" - "System Tool" - "Disk Defragmenter".
1
Un-check the "Run on a schedule". 3
Click the "OK". 4
Click the "Configure schedule". 2
- 24 -
(4) Making Network card power saving setting invalid When the power saving setting function of the network card mounted from Windows® 7 is made valid, there is a case of
communication failure with MELSEC. For this reason, the power saving setting of network card should be invalid.
(In addition, the following screen is different depending on the network card manufacturers. If the screen is different, the
similar setting is required.)
Fig. 2-17 Network Connections
Fig. 2-18 Local Area Connection Properties
Right-click the "Local Area Connection" and click the "Properties".
Click the "Configure".
2
3
Select [Control Panel]-[Network], and Click [Adapter setting] from left menu.
1
- 25 -
Fig. 2-19 System Idle Power Save
Fig. 2-20 Power Management
Click the "OK".
Un-check property.
Click the "System Idle Power Saver", and select the value "Disabled".
Click the "Advanced" Tab.
Click the "Power Management".
4
5
6
7
7
- 26 -
2.2.2 Commercial software installation
The commercial software required for actuation of MELSEC BACKUP TOOL is as listed below.
Then, the commercial software shall be provided separately and installed in accordance with the manual attached to the
commercial software.
If the version required for actuation is not included, it is necessary to get the update ver. for updating.
Table 2-2 Commercial Software List
Item Version
Commercial software required GX Developer 8 Version 8.109P or newer
GX Works2 Version 1.501X or newer
To install the GX Developer, see the "GX Developer Version 8 Operating Manual (Startup)" attached to
GX Developer.
To install the GX Works2, see the "Installation Procedure for GX Works2" attached to GX Works2.
For save in the project form of GX Developer, installing the GX Developer is mandatory.
For save in the project form of GX Works2, installing the GX Works2 is mandatory.
It is recommended to install both of the GX Developer/GX Works2.
- 27 -
Exit all of the Windows® program.
If a different version of MELSEC BACKUP TOOL is installed, uninstalling is required.
(See "2.3 Uninstallation")
Click the "Next" on the screen of "Welcome to the InstallShield Wizard for MELSEC BACKUP TOOL".
Double-click the "setup.exe".
Start the Windows Explorer and click the Drive with disk inserted.
Insert the installation DVD into the DVD-ROM Drive.
2.2.3 Installation of MELSEC BACKUP TOOL
(1) MELSEC BACKUP TOOL Installation Use the "MELSEC BACKUP TOOL DVD with label (hereinafter mentioned "Installation DVD") to install the MELSEC
BACKUP TOOL.
Fig. 2-21 Windows Explorer Start
Fig. 2-22 MELSEC BACKUP TOOL Installation Start
Fig. 2-23 Installation Initial Screen
1
2
3
4
5
6
- 28 -
Click the "Next"
Click the "Next"
On the "Customer Information" screen, input the "User Name", "Organization " and "Serial Number"
Confirm the License Agreement content first, and then select "I accept the terms in the license agreement"
Fig. 2-24 License Agreement Confirmation Screen
Fig. 2-25 User Information Setting Screen
・For Serial No., you can confirm in the Software License Agreement. ・When 30 days pass after Trial package installation, the message is displayed as shown, then not allowing MELSEC BACKUP
TOOL to be started.
7
8
9
10
- 29 -
Set the installation folder and click the "Next" on the "Destination Folder" screen.
Select the "Language" on the screen of "The language used for Backup Tool.
The set language can be changed after installation.
Click the "Install" on the screen of "Ready to Install the Program ".
Click the "Next"
Click the "Next"
Fig. 2-26 Installation Target Folder Screen
Fig. 2-27 Setting Screen of Language Used
Fig. 2-28 Installation Ready Screen
11
13
12
14
15
- 30 -
Click the "Yes" on the restart confirmation screen.
Click the "Finish" on the "InstallShield Wizard Completed" screen..
Fig. 2-29 Completion Screen of InstallShield Wizard
Fig. 2-30 Restart Confirmation Screen
16
17
- 31 -
2.3 Uninstallation
MELSEC BACKUP TOOL shall be uninstalled in the following procedure:
(1) Case of Windows®XP
(2) Case of Windows®7
Even if MELSEC BACKUP TOOL is uninstalled, the created setting information and backup data are not deleted.
To delete these files, delete the folder in which MELSEC BACKUP TOOL is installed and others by operating the
Windows® Explorer.
Select the "Start" - "Control Panel", and select the "Program Addition and Deletion". 1
Select the "MELSEC BACKUP TOOL" from the installed program list, and click the "Delete". 2
Select the "Start" - "Control Panel", and select the "Program Uninstall". 1
Select the "MELSEC BACKUP TOOL" from the program list, and select the "Uninstall". 2
Click the "Permit" on the "User Account Control" screen. 3
- 32 -
3. How to Use The usage of MELSEC BACKUP TOOL is described below.
- 33 -
3.1 Operation flow
In this section, the operation flow from connection with MELSEC sequencer to confirmation of backup data is described.
Fig. 3-1 Operating Order up to Backup
Start
Editing of Setting Information 3.3
Creation of Setting Information 3.4
Confirmation of Execution Results
3.6
Exit
Cable Connection 3.2
Backup Execution
3.5
- 34 -
3.2 Cable connection
The connection-target MELSEC sequencer shall be connected with the computer in which MELSEC BACKUP TOOL is
installed. In case of Windows7, the AC power shall be connected, if the Computer is to be used as maintenance computer.
If the power supply is from the battery in Windows7, the backup schedule is not executed.
- 35 -
3.3 Editing of setting information
MELSEC BACKUP TOOL actuation shall be set. The setting procedure is described below.
3.3.1 MELSEC Backup Setting start
Fig. 3-2 Backup Setting Screen (Initial state after installation)
Select the "Start" - "Program" - "MCR TOOLS" - "MELSEC BACKUP TOOL" - " Backup Setting". Or, click the shortcut icon for Backup Setting on the desktop.
1
- 36 -
3.3.2 Configuration setting
With the "Configuration setting" Tab, set MELSEC BACKUP TOOL actuation.
Fig. 3-3 "Configuration setting" Tab
The following items can be set with the "Configuration setting" Tab.
Table 3-1 Setting Items of Configuration setting
No. Setting Items Description Remarks
A Save folder Specifying the folder to save the backup data.
In the save folder, the GX Developer format or GX Works2
(workspace) format project file is backed up.
For backup data
save target, see
"3.6.1
Backup file
confirmation".
B Retry time Specifying the retry time, if not connected to MELSEC at
the time of backup execution. (Unit: sec.)
Setting value
Range able to specify:1 to 3600
For precautions
for retry time, see
"6.1.1 (1)
Retry".
C Retry count Specifying the retry count, if not connected to MELSEC at
the time of backup execution.
Setting value
Range able to specify:0 to 86400
(No retry in case of 0)
For precautions
for retry count,
see "6.1.1 (1)
Retry".
If necessary to change, change the "Save Folder", Retry Time" and "Retry Count".
2
A
B
C
Click the "Config" tab title. 1
Change column width by drag operation as needed.
- 37 -
3.3.3 Group setting
To back up the multiple MELSEC at the same timing, it is required to prepare the group of MELSEC to be backed up by the
"Group setting" Tab.
Unless the backup file is controlled in the group, this setting is not required.
Fig. 3-4 "Group setting" Tab
A
When the Able/Disable is made "Able", set the backup schedule
4
B C
Click the "Group" tab title. 1
D E F
Input the Group name. 2
To be Able if the backup schedule is to be set in the group i
3
Change column width by drag operation as needed.
- 38 -
With the "Group setting" Tab, the following items can be set as shown.
Table 3-2 Setting Items of Group setting
No. Setting Items Description Remarks
A Group Name Setting the group name.
Setting value
Setting the character usable as folder name.
The group able to be set
is 32 groups as Max.
B Able/Disable
Specifying if backup is executed or not in the group
unit.
Setting value
Able Backup execution
Blank No backup
(Note 1)
C Backup Schedule Mode Setting the backup cycle.
Setting is required in case of "Able".
Setting value
Daily :Daily backing up
Weekly :Weekly backing up with day of the week.
Monthly :Monthly backing up on day of the week.
(Note 2)
D Day of the week
(Specifying weekly)
Specifying the day of the week for backup when the
mode is weekly set.
Setting value
The day of the week to be set is from Sunday to
Saturday.
(Note 2)
E Day of the month
(Specifying monthly)
Specifying the day for backup when the mode is
monthly set.
Setting value
The number from1 to 28 is to be set.
(Note 2)/(Note 3)
F Specifying the start time Specifying the backup starting time.
Setting is required even in case the backup schedule
mode is any of day/week/month.
Setting value
hh:mm Specifying the format.
hh Specifying the hour. Numbers from 00 to 23.
mm Specifying the minute. Numbers from 00 to 59.
(Note 2)/(Note 4)
- 39 -
Note 1: The relationship between the combination of Group setting (ON/OFF) with MELSEC setting (ON/OFF) and the backup
operation to be executed is as listed below.
MELSEC Setting Group setting
Target
ON OFF
Able/Disable
Able Backup execution in
Group setting Backup execution in
Group setting
Disable Backup execution in
MELSEC setting Out of backup target
Even if the backup is not executed in Group unit, the backup file is to be saved in the Group folder.
Note 2: Even for backup target in MELSEC setting, when the Group-unit backup is executed (ON), the Group schedule is given
high priority.
Note 3: The 31-day month and intercalary month (29 days in Feb.) are not considered. Specify the compatible day in every
month.
Note 4: The summer time is not considered.
- 40 -
3.3.4 MELSEC setting
With the "MELSEC Setting" Tab, the backup target MELSEC shall be set.
Fig. 3-5 "MELSEC Setting" Tab
Fig. 3-6 Connection Setting – "Read" Menu
Fig. 3-7 Specifying the Connection Target
A
Click the "MELSEC" tab title. 1
Input the MELSEC name for registration. 2
Select the "Transfer setup" - "Read" Menu. Connect with MELSEC and read the connection parameter and PLC parameter in the MELSEC.
3
Select the "Backup Format"/"PLC series" of the MELSEC to be read. 4
Click the "OK" button. 5
Change column width by drag operation as needed.
- 41 -
Fig. 3-8 Specifying the Connection Target
Fig. 3-9 "MELSEC Setting" Tab Schedule setting
B C D E F G
Execute the communication test, and confirm that the connection channel is correct.
If the PLC type name is correctly obtained, press the "OK" button. (PLC parameter is to be obtained.)
Specify the connection channel of the MELSEC to be backed up and maintenance computer.
6
7
8
Specify the group or set the target. To back up in the group unit, set the No. of the group to be attached to specifying the group. In addition, for backup in the MELSEC unit, the target should be "ON".
9
When the target is made "ON", set the backup schedule.
10
- 42 -
With the "MELSEC Setting" Tab, the following items can be set as shown.
Table 3-3 Setting Items of MELSEC Setting
No. Setting Items Description Remarks
A MELSEC Information
MELSEC name
MELSEC name for backup target MELSEC. To be
named optionally.
Setting value
Setting the character usable as folder name.
The MELSEC nameable
to be set is 64 PLC as
Max.
B Setting Group
(Group No.)
To be set in case the multiple MELSECs are to be
backed up at the same timing.
Setting value
The setting content is Group No. of the Group
setting.
(See "3.3.3 Group setting".)
C Target
(ON Execution)
Specifying if backup is practically executed or not.
Setting value
ON Backup execution
Blank No backup
D Backup Schedule Mode Setting the backup cycle.
Setting is required in case of backup target (ON).
Setting value
Daily Daily backing up
Weekly Weekly backing up with day of the week.
Monthly Monthly backing up on day of the week.
(Note 1)
E Day of the week
(Specifying weekly)
Specifying the day of the week for backup when the
mode is weekly set.
Setting value
The day of the week to be set is from Sunday to
Saturday.
(Note 1)
F Day of the month
(Specifying monthly)
Specifying the day for backup when the mode is
monthly set.
Setting value
The number from1 to 28 is to be set.
(Note 1)/(Note 2)
G Specifying the start time Specifying the backup starting time.
Setting is required even in case the backup schedule
mode is any of day/week/month.
Setting value
hh:mm Specify in the format.
hh Specifying the hour Numbers from 0 to 23.
mm Specifying the minute. Numbers from 00 to 59
(Note 1)/(Note 3)
- 43 -
Note 1: The relationship between the combination of Group setting (Enable/Disable) with MELSEC setting
(ON/OFF) and the backup operation to be executed is as listed below. MELSEC Setting
Group setting Target
ON OFF
Able/Disable Able
Backup execution in Group setting
Backup execution in Group setting
Disable Backup execution in MELSEC setting
Out of backup target
Even if the backup is not executed in Group unit, the backup file is to be saved in the Group folder.
Note 2: Even for backup target in MELSEC setting, when the Group-unit backup is executed (ON), the Group
schedule is given high priority.
Note 3: The 31-day month and intercalary month (as February 29) are not considered. Specify the compatible day
in every month.
Note 4: The daylight saving time is not considered.
- 44 -
3.3.5 Backup setting
With the "Backup Setting" Tab, the backup target is to be set.
Fig. 3-10 "Backup Setting" Tab
Click the "Backup" tab title. 1
Change the display to the PLC parameter of target PLC series
2
Change column width by drag operation as needed.
A B C D E
Specify the backup target. 4
Confirm the backup-target setting value. 3
- 45 -
With the "Backup Setting" tab, the listed items can be set for the MELSEC that "Transfer setup-"Read" Menu is successful.
Table 3-4 Setting Items of Backup Setting
No. Setting Items Description Remarks
A Program/Parameter To be specified for backup of program/parameter.
Setting value
Target Backup execution
Blank No backup
(Note 1)
B Comment File To be specified for backup of comment file.
Select the Drive (Memory) saving the comment file.
Setting value
Drive (Memory) Backing up the comment file on
the target drive (memory).
Blank No backup
(Note 2)
C Device Initial Value To be specified for backup of device initial value file.
Setting value
Target Backup execution
Blank No backup
(Note 3)
D File Register To be specified for backup of file register.
Setting value
Target Backup execution
Blank No backup
(Note 4)
E Device memory File To be specified in case the device current value
(latch-set) is to be backed up as device memory file.
Setting value
Target Backup execution
Blank No backup
(Note 5)
- 46 -
For QCPU (Q Mode): Note 1:For program/parameter, the following files are to be backed up.
・All the program file existing on the program memory. (Even if not specified for PLC parameter "Program Setting", the backup is to be done, if existing on the program memory.)
・Parameter file existing on the program memory (PLC parameter and network parameter)
・Boot file setting file (If the PLC parameter "Boot File Setting" is default, this file does not exist.)
・Intelligent function unit parameter file) (If there is no parameter created with intelligent function unit utility, this file does not exist.)
In addition, unless the program/parameter backup is specified, the parameter file of default value (computer parameter and network parameter) is to be created for GPPW.
Note 2: For comment files, all the comment file existing in the specified drive (memory) is to be backed up.
Target Setting Target Memory in GX Developer Format
Target Memory in GX Works2 Format
"Program Memory" Program Memory/Device Memory Program Memory/Device Memory
"Standard RAM" Not allowed to specify Standard RAM(However, the high-speed Universal model type QCPU only allowed to specify.)
"Standard ROM" Standard ROM Standard ROM
"Card(RAM)" Memory Card(RAM) Memory Card(RAM)
"Card(ROM)(SD)" Memory Card(ROM) Memory Card(ROM)or Memory Card (SD)
Note 3: For device initial value, the initial value file set in the "computer File Setting" (device initial value) of the read PLC
parameter is to be backed up. By the "Computer File Setting" (device initial value), to following files are to be backed up.
・"Not used" is set. : No backing up ・In case the "Use the same file name as the program." is set. : All device initial value files existing on the target ・In case "Use the following file." is set. : Initial value file of specified target file name existing on
the target memory In addition, the read PLC parameter can be confirmed in the "PLC Parameter (QCPU)" field of "Backup Setting" tab.
Note 4: For file register, the file register set in the "PLC File Setting" (file register) of the read PLC parameter is to be backed
up. By the " File Setting" (file register), the following files are to be backed up. ・In case "Not used" is set. : No backing up ・In case the "Use the same file name as the program." is set. : All file registers existing on the target memory ・In case " Use the following file." is set. : File register of specified target file name existing on the
target memory In addition, the read PLC parameter can be confirmed in the "PLC Parameter (QCPU)" field of "Backup Setting" tab.
Note 5: For device memory file, the device data (current value) in the latch set range of the read PLC parameter "Device
Setting" is to be backed up. If there is no device latch-set in the PLC parameter "Device Setting", backing up is not done. The backed-up device data name is "EZLCHBUP".
In addition, the read PLC parameter can be confirmed in the "PLC parameter (QCPU)" field of "Backup Setting" tab.
(For others, see "6.1 Restrictions" also.)
- 47 -
For ACPU: Note 1: For program/parameter, the following memory is to be backed up according to the current "Memory Capacity Setting".
・Sequence "Main" is more than 1K step : "MAIN" Program ・Sub-sequence "Sub 1" is more than 1K step : "SUB1" Program
The range exceeding the program capacity is to be deleted at reading. In addition, the read PLC parameter can be confirmed in the "PLC parameter (ACPU)" field of the "Backup Setting" tab.
Note 2: For comment file, the following memory is to be backed up according to the current "Memory Capacity Setting".
・Comment is more than 2K byte : Comment ・Extended comment is more than 2K byte : Extended comment The backed-up comment is saved as the comment file shown below. ・Comment "Common(X,Y, Special M, Special D)": Extended comment : "COMMENT" File ・Extended comment "Program-classified (For Main)" : "MAIN" File ・Extended comment "Program-classified (For Sub 1)" : "SUB1" File
In addition, the read PLC parameter can be confirmed in the "PLC parameter (ACPU)" field of "Backup Setting" tab.
Note 3: There is no device initial value in the ACPU. Note 4: For file register, the file register (Block No. 0) memory is to be backed up according to the current "Memory Capacity
Setting". (For the Extension file register, the Block No.1 and afterward (from Block No. 1) are not backed up.) ・File register is more than 1K point. : "MAIN" File In addition, the read PLC parameter can be confirmed in the "PLC parameter (ACPU)" field of "Backup Setting" tab.
Note 5: For device memory file, the device data (current value) in the latch-set range of the read PLC parameter "Device
Setting" is to be backed up. Unless there is the device latch-set in the "Device Setting" of PLC parameter, the backup is not done. The backed-up device data name is "EZLCHBUP".
In addition, the read PLC parameter can be confirmed in the "PLC parameter (ACPU)" field of "Backup Setting" tab.
(For others, see "6.1 Restrictions" also.)
- 48 -
3.3.6 Save of Setting Information
The setting information in editing can be saved.
Fig. 3-11 "File"-"Save" Menu and Save Button (1)
Fig. 3-12 "File" - "Save" Menu and Save Button (2)
Select the “File”-"Save" Menu or click the "Save" button. 1
When "Save" is completed, the "Save" button is invalid. 2
- 49 -
3.3.7 Import/Export of setting information
In preparation to control the setting information in multiple patterns or so, the Import/Export functions are ready.
(1) Import procedure
The Import can be edited by reading the exported setting file and text file.
Fig. 3-13 "File"-"Import" Menu
Fig. 3-14 Reference to Folder (Import)
Select the “File”- "Import" - "Setting file" or “File”- "Import"-"Text file" Menu.
1
Specify the folder with Setting File to be Imported or Text file 2
Click the "OK" button. 3
- 50 -
(2) Export procedure
The Export can be prepared in the folder specified for the setting file and text file.
Fig. 3-15 "File"-"Export" Menu
Fig. 3-16 Reference to Folder (Export)
Select the “File” - "Export"-"Setting file" or “File” - "Export" - "Text file" Menu.
1
Specify the folder to which the setting file or text file is desired to be exported. Also, it can be prepared by "Make New Folder".
2
Click the "OK" button. 3
- 51 -
3.4 Creation of setting information
If editing of setting information is completed, the setting information for backup schedule execution is to be created.
The procedure for setting information creation is as shown below.
Fig. 3-17 Confirmation of Schedule Stopped State
Fig. 3-18 "Transfer Setting"-"Setting file Create" Menu
Select the “Transfer setup”-"Setting file Create" Menu. 3
Confirm that the Backup Tool is "Schedule stopped".
Allow the Backup Tool to be displayed, and click the "MELSEC Backup Schedule Stop".
1
2
- 52 -
In the left example, the MELSEC №, 2, 3 and 4, are backup target. The MELSEC No.1 is backup target execution OFF. The MELSEC No.2 is for backup in MELSEC unit without group registration. The MELSEC Nos. 3 and 4 are for backup in Group unit of Group No.1.
The MELSEC No. 5 and afterward are without MELSEC setting.
Fig. 3-19 Creation Confirmation Screen
(Before creation)
(After creation)
Fig. 3-20 Display of Setting file Create State
Confirm the registered schedule.
4
When the setting file is created, the display will be changed from "Not created" to "Created", then confirmation is needed.
5
- 53 -
3.5 Backup execution
3.5.1 Operation of backup schedule
For Backup Tool, the schedule is to be executed on the basis of the setting information created in the Backup setting.
Fig. 3-21 Backup Tool Screen (Under schedule Stopped)
Fig. 3-22 Backup Tool Screen (Schedule started)
Fig. 3-23 Backup Tool Screen (Under Backup)
Click the "MELSEC Backup Schedule Start". Then, the backup schedule is started.
1
To stop the schedule, click the "MELSEC Backup Schedule Stop".
2
When the scheduled time comes, the communication with MELSEC is started, thereby executing the backup.
3
- 54 -
Fig. 3-24 Backup Tool Screen (Error detected)
The schedule start/stopped state is held even if the maintenance computer is shut down. For example, When shut
down under schedule started, when the maintenance computer is turned ON next, it will come to "Under started"
automatically.
Even if an error is detected under execution, the backup processing is continued, however, the [Execution Error
Information:] display is not updated until the [Error clear] button is pressed. After that, even if an error is newly
detected, the screen holds the first error content. For errors after such an error detection, confirm with the execution
log (See "3.6.2 Backup execution log".).
Also, when the icon color display is red (error detected), there is no change until the [Error clear] button is pressed.
However, if the MELSEC maintenance system computer is turned OFF->ON or if this application is exited ->
started, the error display is also cleared by pressing the [Error clear] button.
Clear the error state. 5
When an error is detected under backup, it comes to Error Detected.
4
- 55 -
During starting of this application, the icon is displayed on the task bar. The icon on the task bar displays the current
operating state with the color of part "B".
Fig. 3-25 Backup Tool Icon
Table 3-5 Backup Tool Icon and Operating State
Color Icon Operating State Description
White
Under schedule
stopped
The backup schedule is stopped.
Green
Under schedule
starting
Under backup schedule started. When the backup scheduled time is
reached, the backup is started.
Yellow
Under backup running Connected with MELSEC, the backup is executed.
Red
Error detected When an error is detected under backup running, the first error content is
displayed on the [Execution Error Information:]. Then, for errors after this,
confirm the execution log. (note 1)
Note 1: When an error is detected, the displayed content of execution error information is not changed.
When the [Error clear] button is pressed, the execution error information display mentioned above is cleared.
The icon color Is any of the "White", "Green" and "Yellow" displaying an operating state at the time of Error
Clear.
For example, a communication defect is detected in a MELSEC under backup running, and when the error is
cleared, if another MELSEC backup is under execution, the mentioned color is yellow, and in case of next
schedule wait, the color is green. In addition, when the error is cleared after schedule stopped, the color is
white.
Fig. 3-26 Backup Tool Exit Menu
To exit Backup Tool, right-click the icon, thereby the "Exit" Menu appears. Then, click it adequately.
6
- 56 -
3.5.2 Backup Test
For Backup Test, the schedule of the setting information created in Backup setting can be executed at an arbitrary timing.
Then, it can be used for confirmation of the setting information, etc.
The procedure for specifying the group No. and its execution is described below.
Fig. 3-27 Backup Test (Group No. Specified)
The procedure for specifying the MELSEC No. and its execution is described below.
Fig. 3-28 Backup Test (MELSEC No. Specified)
When the radio button of the group No. is selected, the group No. can be inputted in the state. Input the group No. set in the "Group setting".
1
When the Execution button is clicked, the specified group schedule can be executed.
2
When the radio button of the MELSEC No. is selected, the MELSEC No. can be inputted in the state. Input the MELSEC No. set in the "MELSEC Setting".
1
When the Execution button is clicked, the schedule of the specified MELSEC No. can be executed.
2
- 57 -
The precautions for backup test execution are described as below.
Note 1: The Group No. and MELSEC No. input can be switched many times. Even if the No. input is left at the
input-unable side, it will be neglected, therefore there is no effect to such a test execution.
Note 2: If the mentioned test is executed with the number that the Group No. and MELSEC No. are not
schedule-registered (the target is not "ON"), an error message is displayed on the MELSEC Backup
execution screen.
Note 3: If the BACKUP TOOL is during schedule stopped or is not started, the backup test is not executed.
Note4: If there is a request, Schedule started, for the BACKUP TOOL, after backup completion, the backup test
schedule is executed.
Note 5: Unless connected with MELSEC, retry is not done. However, However, "Retry Over" is displayed for the
execution error information.
Note 6: The save folder is a folder of the current day of backup test execution. If the same-name backup project
exists below the current-day folder, see the "3.6 Confirmation of execution results" for operation.
- 58 -
3.6 Confirmation of execution results
The backup execution results can be confirmed with the backup file and the execution log.
3.6.1 Backup file confirmation
The backup data is to be controlled by the date folder showing the backup date and each MELSEC No. folder.
The following is an example of the operation result dated February 24, 2014, when the
"C:\MelsecBackupTool\BackupGppw" was specified for the "Save Folder".
Fig. 3-29 Save Folder Examples
Table 3-6 Setting Items of Group setting
No. Folder Description Remarks
A Save Folder Save folder specified by "Configuration setting" Tab.
B Date Folder Folder of backed-up date.
"yyyyMMdd" format
C Group Folder Folder of the group name set in the "Setting Group".
For MELSEC backup without Group specified, this folder is
not included in the path.
D MELSEC Folder Folder of MELSEC name specified in the "MELSEC
Setting".
In case of GX Developer format, the GX Developer project
is saved below this folder.
In case of GX Works2 format, the work space is prepared
below this folder.
In setting, the total number of characters of the folders A to D is to be within 150 characters.
A
B
C D
- 59 -
3.6.2 Backup execution log
The backup execution results of MELSEC BACKUP TOOL, according to schedule information, can be confirmed by
opening the execution log file with text editor such as notepad, etc.
The execution log file is to be created as "backup log" for the "Save Folder" set in the "3.3.2 Configuration setting".
For the execution log file, when 200KB is reached, its name is to be changed to "backup.bak", then ensuring log output to
the new "backup.log" file.
Then, when the new file reaches 200KB, the old "backup.bak" content is overwritten with "backup.log" content.
For backup, only up to one generation before remains at any time.
2013-07-16 16:05:20.038 Backup execution [The schedule started by pressing the button.]
2013-07-16 16:05:31.210 Backup execution [Backup is started.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:06:01.741 Backup execution [MELSEC connection setting not correct.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:06:11.757 Backup execution [Backup is started.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:06:42.241 Backup execution [MELSEC is not correct.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:06:52.257 Backup execution [Backup started.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:06:52.319 Backup execution [MELSEC is not correct.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:07:02.335 Backup execution [Backup started.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:07:10.944 Backup execution [Backup completed.] 20130716 GROUP01 GPPW001 Q06H
2013-07-16 16:56:14.116 Backup execution [The schedule is stopped by pressing the button.]
Fig. 3-30 Execution Log Output Examples
- 60 -
Table 3-7 Execution Log Message Content
*1.Group No.:XX or MELSEC No.:XXX
No. Message Content
(First line: Message title Second line/afterward: Message detail)
Description
1 Backup is started.
YYYYMMDD GROUPXX GPPWXXX MELSEC name
Backup execution start
2 Backup is completed.
YYYYMMDD GROUPXX GPPWXXX MELSEC name
Backup execution completed
3 Backup is started.
YYYYMMDD GROUPXX GPPWXXX MELSEC name (Manual)
Backup execution start (Manual)
4 Backup is completed.
YYYYMMDD GROUPXX GPPWXXX MELSEC name (Manual)
Backup execution completed
(Manual)
5 MELSEC connection setting is not correct.
YYYYMMDD GROUPXX GPPWXXX MELSEC name
Connection error
6 MELSEC configure file does not exist.
YYYYMMDD GROUPXX GPPWXXX MELSEC name [PRO/PAR/COM/INI/REG]
No MELSEC file
7 Backup is stopped because the remaining disk capacity is less than 1GB.
YYYYMMDD GROUPXX GPPWXXX MELSEC name
Remaining disk capacity
Less than1GB
8 The schedule not registered is requested (*1). Start parameter error
9 Not connected to MELSEC (Retry over).
YYYYMMDD GROUPXX GPPWXXX MELSEC name
Retry over
10 The schedule is stopped by pressing the button. Pressing Stop button.
11 The schedule is started by pressing the button. Pressing Start button.
12 The execution error information is cleared by pressing the Error Clear button. Error clear
13 The memory capacity setting is changed.(ACPU) Memory capacity setting
parameter at the time execution is
different from the time of creation.
14 The temporary work space cannot be ensured.(Works2)
YYYYMMDD GROUPXX GPPWXXX MELSEC name
GX Works2 Project backup
execution failure
15 The temporary work space cannot be ensured.(Retry over) GX Works2 Project backup
execution failure (Retry over)
16 The schedule is stopped because of application error. Error stopping
- 61 -
3.6.3 In case Backup is not normally completed
If the backup is interrupted due to defect detected, such as maintenance computer going down during backup, the backup
project is not saved.
When a check tool is maintenance computer start-up, the data which did not carry out normal completion is deleted.
When the data which did not carry out normal completion is deleted, the result eliminated in the dialog of the following figure
is displayed.
Fig. 3-31 Defect Detection during Backup
Click the "OK" button and it closes this dialog. 2
The contents displayed now can perform cut & paste to text editor.
1
- 62 -
4. Message Various messages to be outputted for operation are described hereinafter.
- 63 -
4.1 Backup setting message
Listed below describes the messages to be displayed when each menu of Backup Setting is executed.
4.1.1 "Import" Menu
Table 4-1 Messages displayed on "Import" Menu
No. Message Description/Countermeasures
1
Description
There was no file for import target in the selected
folder.
Countermeasure
Select the folder executed from the "Export" Menu.
In case of setting file, the files ,
"EZBackup.def","EZMelsec.def" and
"EZSchedule.def", are required.
In case of text file, the files, "Config.txt","Melsec.txt",
"Group.txt" and "Backup.txt" are required.
2
Description
The content in the setting file for import target in the
selected folder is not perfect.
(Message format)
File in trouble "Error content"
Countermeasure
Investigate if there is no problem in the import-target
setting file according to the message content.
・General configuration file :"EZBackup.def"
・MELSEC file :"EZMelsec.def"
・Schedule configure file :"EZSchedule.def"
4.1.2 "Export" Menu
Table 4-2 Message displayed on "Export" Menu
No. Message Description/Countermeasures
1
Description
The folder for MELSEC BACKUP TOOL was selected.
Countermeasure
Re-select another folder.
- 64 -
4.1.3 "Read" Menu
Table 4-3 Message displayed on "Read" Menu
No. Message Description/Countermeasures
1
Description
Communication with MELSEC could not be done in
the connection channel set on the transfer setup
screen.
Countermeasure
Confirm the connection channel.
2
Description
Because the PLC parameter does not exist in
MELSEC, it could not be obtained.
Countermeasure
Confirm the target MELSEC PLC parameter with
GX Developer / GX Works2.
- 65 -
4.1.4 "Setting file create" Menu
Table 4-4 Message commonly displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
During backup schedule starting, the setting
information was to be created.
Countermeasure
Stop the schedule with the Backup tool.
If the screen is closed, double-click the icon to display
the screen, and if under backup, stop the schedule
after its completion.
If the Backup Tool is exited, start it first, and then click
the Schedule Stop button on the screen.
2
Description
For the setting items "Save Folder" of "Configuration
setting" tab, the total of "Group setting" tab setting
items "Group Name" and "MELSEC Setting" tab
setting items "MELSEC Name" exceeds 150
characters.
Countermeasure
In setting, the total should not exceed 150 characters.
- 66 -
Table 4-5 Message of "Configuration setting" as Cause, displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
The input content of the "Configuration setting" tab
setting items "Save Folder" is not correct.
In the left example, the folder does not exist.
For others, if the file, instead of folder, is specified or in
case of no input, it is the same as above.
(Please check the "content")
Countermeasure
Input the backup folder correctly in full path.
2
Description
The "Value" of the "Configuration setting" tab setting
items "Retry Time" is blank.
Countermeasure
Input the numbers from 1 to 3600.
3
Description
The "Value" of the "Configuration setting" tab setting
items "Retry Count" is blank.
Countermeasure
Input the numbers from 0 to 86400.
(If retry is not required, input zero (0).
- 67 -
Table 4-6 Message of "MELSEC Setting" as Cause, displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
The "MELSEC Setting" tab setting items "Target" is
set ON, however, the "Mode" is blank.
Countermeasure
Select the mode.
2
Description
The "MELSEC Setting" tab setting items "Mode" is
selected as Weekly, however, the "Day of the week" is
blank.
Countermeasure
Select the day of the week.
3
Description
The "MELSEC Setting" tab setting items "Mode" is
selected as Monthly, however, the "Day of the month"
is blank.
Countermeasure
Input the numbers from 1 to 28.
4
Description
The "MELSEC Setting" tab setting items "Target" is
set ON, however, the "Start time" is blank.
Even if any mode is selected, the "Start time" is a
mandatory item.
Countermeasure
Input the start time.
- 68 -
Table 4-7 Message of "Group setting" as Cause, displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
The "Group setting" tab setting item "Able/Disable" is
set Able, however, the "Mode" is blank.
Countermeasure
Select the mode.
2
Description
The "Group setting" tab setting item "Mode" is
selected as Weekly, however, the "Day of the week" is
blank.
Countermeasure
Select the day of the week.
3
Description
The "Group setting" tab setting item "Mode" is
selected as Monthly, however, the "Day of the month"
is blank.
Countermeasure
Input the numbers from 1 to 28.
4
Description
The "Group setting" tab setting item "Able/Disable" is
set Able, however, the "Start time" is blank.
Even if any mode is selected, the "Start time" is a
mandatory item.
Countermeasure
Input the start time.
- 69 -
Table 4-8 Message of "Backup Setting" as Cause in Q Series displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
"File Selection"-"Device Initial Value" of the "Backup
Setting" tab is "Target", however, the device initial
value of the read PLC parameter is set "Not used".
Countermeasure
Allow the "Device Initial Value" to be blank (no backing
up).
2
Description
"File Selection"-"File Register" of the "Backup Setting"
tab is "Target", however, the file register of the read
PLC parameter is set "Not used".
Countermeasure
Allow the "File Register" to be blank (no backing up).
3
Description
"File Selection"-"Device memory File" of the "Backup
Setting" tab is "Target", however, there is no latch
device for device setting of the read PLC parameter.
Countermeasure
Allow the "Device memory File" to be blank (no
backing up).
4
Description
"File Selection"-"Comment File" of the "Backup
Setting" tab is "Standard RAM ", however, there is no
comment file in the target PLC standard RAM. (The
high-speed Universal model type QCPU is only
specified by the standard RAM.)
Countermeasure
Allow the "Comment File" to be except for "Standard
RAM" or blank (no backing up).
- 70 -
Table 4-9 Message of "Backup Setting" as Cause in A Series displayed on "Setting file create" Menu
No. Message Description/Countermeasures
1
Description
"File Selection"-"Device Initial Value" of the "Backup
Setting" tab is "Target", however, the ACPU has no
device initial value.
Countermeasure
Allow the "Device Initial Value" to be blank (no backing
up).
2
Description
"File Selection"-"Comment File" of the "Backup
Setting" tab is "Target", however, both of the comment
and extension comment setting are OK byte in the
PLC parameter.
Countermeasure
Allow the "Comment File" to be blank (no backing up).
3
Description
In the PLC parameter, the file register setting is zero
(0), however, the "File Register" of "File Selection" of
the "Backup Setting" tab is selected.
"File Selection"-"File Register" of the "Backup Setting"
tab is "Target", however, the file register setting is OK
point in the PLC parameter.
Countermeasure
Allow the "File Register" to be blank (no backing up).
- 71 -
4.2 Backup Tool message
4.2.1 Current state
The status displayed on the Backup Tool "Status" is described hereinafter.
Fig. 4-1 Current State Display Position
- 72 -
Table 4-10 Current State Display Status
No. Status Description/Countermeasures
1 The backup schedule is stopped. Description
When the "MELSEC Backup Schedule Start" is pressed, the schedule is
started. The "Setting file create" can be executed.
2 Standby for the next schedule. Description
When the "MELSEC Backup Schedule Stop" is pressed, the schedule
can be stopped. The "Setting file create" cannot be executed. After
stopping, carry it out.
3 Backup under execution
(MELSEC No:50).
Description
Backup is under execution, based on the schedule.
The displayed MELSEC No. (the left example is No. 50) is currently
backed up. Until the backup execution is completed, the schedule Start
and Stop cannot be pressed. The application can be exited, however, it
will exit after the currently-displayed MELSEC No. is backed up
(completed).
4 The execution schedule
configure is not correct.
Description
After installation, the "Setting file create" of the "Backup Setting" is never
executed.
Countermeasure
・After executing "Setting file create", press the "MELSEC Backup
Schedule Start".
5 The save folder configure is not
correct.
Description
There is no existence of "Save Folder" specified at the time of "Setting file
create" of "Backup Setting".
Countermeasure
・Prepare the save folder specified.
・Change to a correct save folder, and re-execute the "Setting file create".
6 Backup is skipped (Remaining
disk capacity : less than 1GB.)
Description
The spare capacity of the whole backup drive set in the "Save Folder" is
less than 1GB.
Countermeasure
・Ensure the drive spare capacity by more than 1GB.
7 Schedule configure is under use
in other process.
Description
On the "Backup Setting", the "Setting file create" is under execution.
Countermeasure
・After completion of setting file creation, press the "MELSEC Backup
Schedule Start".
8 An exceptional error detected
(Contact the develop.
destination.)
Description
Unexpected error is detected.
Countermeasure
・Contact the developer, attaching the execution log and error log.
- 73 -
4.2.2 Execution error information
The status displayed on the "Execution Error Information" of Backup Tool is described hereinafter.
Fig. 4-2 Display Position of Execution Error Information
- 74 -
Table 4-11 Display Content of Execution Error Information
No. Content of Execution Error Information
Description/Countermeasures
1 Not connected to MELSEC
(Retry over).
Description
Failed at the time of MELSEC connection. After retry time specified with
"Configuration setting" tab, retry was executed, however, coming to retry
over.
If failed to connect to MELSEC, executing from the backup test, retry is
not executed, despite specifying with "Configuration setting" tab,
however, the same message is displayed.
Countermeasure
・Confirm if the connection MELSEC power is not OFF.
・Confirm if there is no problem in cable connection such as Ethernet,
MELSECNET, etc.
・Confirm if there is no change of maintenance computer network
address, compared with the time of "Transfer setup"-"Read".
・For others, confirm if there is no difference in configuration, compared
with the time of "Transfer setup"-"Read".
2 Backup is stopped because the
remaining disk capacity is less
than 1GB.
Description
The spare capacity of the whole backup drive set in the "Save Folder" is
less than 1GB.
Countermeasure
・Ensure the drive spare capacity by more than 1GB.
3 MELSEC configure file does not
exist.[XXX]
Description
The backup target specified at the time of backup setting "Setting file
create" did not exist in the MELSEC for execution.
[XXX] : Showing the following backup target.
[Program] Program file
[Parameter] Parameter file
[Comment file] Device comment file
[Device initial] Device initial value file
[File register] File register
Countermeasure
・Re-execute "Transfer setup"-"Read" to create the setting information or
confirm the MELSEC.
4
The memory capacity setting is
changed. (ACPU)
Description
This warning message is displayed when the PLC parameter memory
capacity setting content (A Series) is different between the time of
backup setting "Setting file create" and the time of backup execution.
Based on information on the current PLC parameter memory capacity
setting, backing up was executed.
Countermeasure
・Confirm the MELSEC for creation of setting information by re-executing
the "Transfer setup"-"Read".
- 75 -
No. Content of Execution Error Information
Description/Countermeasures
5 The temporary work space could
not be ensured. (Retry over)
Description
Failed to ensure the space temporarily, when the GX Works2 format
backup is executed.
After retry time specified with "Configuration setting" tab, retry was
executed, but coming to retry over.
If backup is failed executing from the backup test, retry will not be
executed, despite specifying with the "Configuration setting" tab,
however, the same message is displayed.
Countermeasure
Make sure that there is no application accessing to the workspace folder
below the Install Folder.
6 The execution error information
cleared by pressing the Error
Clear button.
Description
[Error clear] button was pressed.
7 The schedule not registered is
requested. (Group No.:XX)
Description
In the backup test, the group No. that schedule registration is not ON was
specified.
8 The schedule not registered is
requested. (MELSEC No.:XX)
Description
In the backup test, the MELSEC No. that schedule registration is not ON
was specified.
9 The schedule is stopped
because of application error.
Description
Unexpected error is detected.
Countermeasure
Contact the developer, attaching the execution log and error log.
・Execution log:"backup.log" below the save folder
・Error log :"log" folder lower file below the save folder
- 76 -
5. Trouble-Shooting When you are in trouble, it is required to review the usage and confirm the message, including restrictions/precautions.
Then, if there is still any unknown point, you can confirm the listed below before contacting us.
Table 5-1 Trouble-Shooting
No Situation Countermeasures
1 Not backed up. ・Confirm that it is the schedule start state.
・If the "Setting file create" is not executed in Backup Setting, its
execution is required.
・In Windows7, if the notebook computer (laptop) is used with
battery, it is not executed. Use the AC power without fail.
・Once the backup is carried out at a specified time, it is not
executed even if the maintenance computer time is turn back.
You are obliged to wait for the next backup schedule or
re-execute the "Transfer Setup"-"Setting file create".
2 There is a device memory file "EZLCHBUP" in
backup project.
・For device memory file, the latch data is only to be backed up.
The target file name is "EZLCHBUP". (See "3.3.5 Backup
setting" also.)
3 Comment file is not backed up. Confirm if the comment file target memory of the MELSEC
Backup Setting "Backup Setting" tab is not specified correctly.
4 Message as shown is displayed in the Trial
package.
Start the "Install Folder ¥exe¥EZBkupAuto.bat".
5 Application error pop-up is displayed. Inform the developer of the ID and content displayed on the
pop-up.
- 77 -
6. Restrictions & Precautions The restrictions and precautions for use of this product are described hereinafter.
- 78 -
6.1 Restrictions
6.1.1 Common restrictions and precautions
The common restrictions and precautions are described hereinafter.
(1) Retry The timer start timing of the retry time that is set with "Configuration setting" tab is not from the backup start time, but from
the point of connection error. (Note 1)
For example, if the transfer setup time check =30(sec.) and the retry time of "Configuration setting" tab =60(sec.), the actual
retry time in case a connection error is detected starting backup from 23:50:00 is not 23:51:00, but 23:51:30.
Even if not connected to the MELSEC at the time of backup, when the MELSEC maintenance computer is turned OFF->ON
before reaching the retry time, retry is not executed. The setting information (retry time/count) is re-read, and backing up is
not executed until the next schedule time.
This operation is the same in case "Backup Tool" is exited->started from the icon and also in case the schedule is
stopped->started by the button operation.
Note 1: The time up to connection error detected is the time set in the "Time Check (sec.)" of the Transfer setup
screen (See " Fig. 3-7 Transfer setup".)
(2) Time of save folder The save folder date is the "schedule execution scheduled date" even the backup completion time is the next day.
For example, though the time with date, Feb. 17, 2014, 23:50, is specified, if the obtaining completion is Feb. 18, 2014,
00:20, the date folder is "20140217".
However, if 24 hours are passed, it is the backup implement action day.
For example, if the obtaining completion is Feb. 18, 2014, 23:51, though the time with date, Feb. 17, 2014, 23:50, is
specified, the date folder is "20140218".
- 79 -
(3) Backup target memory The relationship between the MELSEC real machine drive (memory) and the save-possible file is as shown below. In
addition, the relationship between the backup target and non-target, in the save folder, is as listed below. The device
comment can be specified by the user, on the backup setting.
Drive
File
Program
Memory Standard ROM Standard RAM
Card(RAM)
Note 1:
Card(ROM)
Note 2:
Program/Parameter O X X X X
Device comment O O X O O
Device initial value O O X O O
File register X X O O O
Device memory O X X X X
O:Backup target X:Out of backup target
Note 1:For Card(RAM), it is described as "Memory Card (RAM)" on the GX Developer/GX Works2.
Note 2:For Card(ROM), it is described as "Memory Card (ROM)" (or "Memory Card (SD)")
on the GX Developer/GX Works2.
(4) Data retention period The data retention period and capacity are not especially limited. It depends on the disk capacity.
However, in deleting the file due to disk capacity problem, etc., it can be deleted through the Windows Explorer.
(When the disk remaining quantity is less than 1GB, the file is not saved.)
(5) Maintenance computer shutdown Do not carry out shutdown during backup running. (Otherwise, the backup data is indefinite.)
In order to shut down the maintenance system computer, stop the schedule, or confirm that the current state displays
"Next Schedule Wait" in advance.
(6) Device setting change If the PLC parameter "Device Setting" of the backup target MELSEC is changed, re-implement the "Connection
Setting"-"Read" in backup setting and re-create the setting information. (See "3.3.4 MELSEC setting".)
(7) Password setting/Remote password setting The MELSEC memory with password setting or remote password setting made cannot be backed up.
- 80 -
(8) Bit device backup range If the latch specified range of the bit device is not 16 point unit, the latch-specified range back and forth part is to be backed
up in 16 point unit.
For example, if the latch specified is from B1000 to B1099, the backup range is from B992 to B1103.
(9) Backup of intelligent function module The intelligent function module parameter IPARAMQPA saved in the MELSEC memory "Program Memory" is only backed
up. The data set in each intelligent card itself is out of backup target.
(10)Connection channel The MELSEC not connection-set with GX Developer or GX Works2 cannot be backed up.
6.1.2 Restrictions and precautions for GX Developer
The following is the GX Developer format project and the restrictions and precautions for backing up.
(1) Project type/Program language The corresponding project type and program language are limited as follows:
Label setting : Only the project not used is supported. Label-used project is not supported.
Program type : Only ladder is supported. SFC,ST is not supported.
- 81 -
6.1.3 Restrictions and precautions for GX Works2
The following is the restrictions and precautions for backup in the project of GX Works2 format.
(1) Backup project format The backup project format is the work-space format project.
Saving in Single File Format project is not supported.
Even if the project written in MELSEC is Single File Format, it is work-space format project.
(2) Project type/Program language The corresponding project type and program language are limited as follows:
Project type : Simple project is only correspondent. The structured project is not correspondent.
Label : Only the project not used is correspondent. Label-used project is not correspondent.
Program language : Only ladder is supported. SFC is not supported.
(3) Work space name/Project name In the save folder mentioned in "3.6.1 Backup file confirmation", the work space is prepared, and in the workspace, the
project is backed up.
The workspace format folder structure is as shown below:
\\Backup top folder \ Date folder \ Group name \MELSEC name \Workspace name \ Project name
Workspace name : wsHHMMSS
Project name :"project" fixed
Example: C:\EZBackup\BackupGppw\20130626\GROUP1\MELSEC1\ws155112\project
(4) Same day save If the MELSEC with the same MELSEC No. is backed up on the same day, such as in backup test, etc., the work space is to be newly prepared, instead of overwrite. (Multiple "wsHHMMSS" is created below the same"\Date folder\Group
name\MELSEC name" folder.)
- 82 -
(5) Copy and move of backup file For GX Works2 project completing backup, copying and moving all in the MELSEC name folder are required to open the
GX Works2.
As recommended, open the GX Works2 project completing backup and execute saving as single file format project by the
"Save under a new file name", and then move a single file.
Fig. 6-11 Save as a Single File Format Project
Do not save the Single File Format project in the same folder as the GX Works2 project in the backed-up work
space format. In addition, do not replace the work space format project with the Single File Format project.
(6) Backup of device initial value only/device memory file only The PLC parameter is backed up also in case the backup target is "Device initial value only" and "Device memory file only".
(7) Backup range of C,T,ST device If the latch specified range of C,T,ST device is not 16-point unit, the latch specified range back/forth part is also backed up
in 16-point unit.
For example, if the latch specified range is from C1000 to C1099, the backup range is from C992 to C1103.
For GX Developer, the latch specified range is only backed up.
Click the "Save as a Single File Format Project", then saving in Single File Format
1
- 83 -
6.1.4 Restrictions and precautions for ACPU
The following is the restrictions and precautions for ACPU backup.
(1) Target MELSEC Only the MELSEC with project-written in GX Developer is able to be backed up. Then, even if the MELSEC with
project-written in GPPA is backed up, there is a possibility of difference being made between the GPPA format and the
program code, etc.
(2) Project format The backup project format is the GX Developer format only. The GPPA format is out of target.
(3) Program The program able to be backed up is the sequence/sub-sequence only.
SFC and microcomputer are out of backup target.
(4) File register For file register, the block No. 0 is only to be backed up. The Extension file register (Block No.1 to) is not to be backed up.
(5) Device comment The device comment is to be backed up as COMMENT(common), MAIN (for main program) and SUB1(for sub1 program).
(6) Change of memory capacity setting If the PLC parameter "Memory Capacity Setting" of the backup target ACPU is changed, re-implement the "Transfer
setup"-"Read" with backup setting, and re-create the setting information. (See "3.3.4 MELSEC setting".)
- 84 -
7. Appendix
- 85 -
7.1 Changing of language selection
The display language of MELSEC BACKUP TOOL is to be determined when installed. However, the screen can partly
change the display language by the following operation.
Fig. 7-1 Help-"Language" Menu
Fig. 7-2 Language Selection
The language change will be valid from the next start-up. For immediate change, exit the tool once, and re-start up.
The language can be changed for the "Backup Tool ", "Backup Setting", "Backup Test" and the Help File to be displayed
from Help Menu. The Start Menu, Desktop Icon and the transfer setup screen cannot be changed.
Select the "Help"-"Language" Menu. 1
Select the language to be changed, and click the OK". 2
- 86 -
MELSEC BACKUP TOOL Instruction Manual
July 10, 2014 Issued First Edition
Contact Information:
MITSUBISHI ELECTRIC CONTROL SOFTWARE CORPORATION / Total Solution Div. Works
Tokyo: 4F, Sumitomo Oimachi Building North 1-20-6, Oi, Shinagawa-ku, Tokyo 140-0014, Japan
Phone: +81-3-5718-3350
Kansai: 11F, Nihon Seimei Kobe Building 2-1-18, Nakamachidori, Chuo-ku, Kobe 650-0027, Japan
Phone: +81-78-360-3650
Nagoya: 7F, Ozone Front Building 3-15-58, Ozone, Kita-ku, Nagoya 462-0825, Japan
Phone: +81-52-910-1671
Microsoft, Windows, Windows XP & Windows 7 are the registered trademarks of Microsoft Corporation in the USA and other countries.
MELSEC, MELSECNET, GX Developer & GX Works2 are the trademarks of MITSUBISHI ELECTRIC CORPORATION.
Ethernet is the registered trademark of Xerox.co.ltd, USA.
For others, the company name and product name herein are each company’s trademarks or registered trademarks.