Ground fault protector/earth leakage protector for Series G E-Frame circuit breakers and HMCPE motor circuit protectors El protector de fallas a tierra/protector de fugas a tierra para interruptores de circuito Serie G Marco-E y protectores de motores HMCPE Effective October 2010 Instructional Leaflet IL01202012E WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. Figure 1. Figure 2. ADVERTENCIA NO INTENTE INSTALAR O LLEVAR A CABO TRABAJOS DE MANTENIMIENTO EN EL EQUIPOMIENTRAS TENGA ENERGIA. EL CONTACTO CON EQUIPO CON ENERGIA PUEDE PROVOCAR LA MUERTE O LESIONES PERSONALES SEVERAS. ANTES DE PROCEDER, VERIFIQUE SIEMPRE QUE NO HAYA VOLTAJE PRESENTE. Figure 3. Figure 4. Attach Endcap. Maximum Breaker Rating 125A Continuous. Coloque la tapa en el extremo. Denominación máxima del interruptor 125A continuo. Insert Screws and Washers. Inserte los tornillos y arandelas dentro de los retenedores. A_1 A_1 A_1 A_1 Insert Unit Into Breaker. Coloque la unidad en el interruptor. Reset Unit Tighten Breaker Screws. Apriete los tornillos del interruptor. 0.156 in (3.97mm) 0.156 pulg. 34–38 in lb (3.8–4.3 Nm) 34–38 pulg./lb.

Instructional Leaflet IL01202012E Effective October 2010 ... · Reajustar el interruptor de circuito. 3. Prueba de operación (el voltaje de línea debe de estar presente) a. Presione

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • Ground fault protector/earth leakage protector for Series G E-Frame circuit breakers and HMCPE motor circuit protectorsEl protector de fallas a tierra/protector de fugas a tierra para interruptores de circuito Serie G Marco-E y protectores de motores HMCPE

    Effective October 2010Instructional Leaflet IL01202012E

    WARNINGDO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.

    Figure 1.

    Figure 2.

    ADVERTENCIA NO INTENTE INSTALAR O LLEVAR A CABO TRABAJOS DE MANTENIMIENTO EN EL EQUIPOMIENTRAS TENGA ENERGIA. EL CONTACTO CON EQUIPO CON ENERGIA PUEDE PROVOCAR LA MUERTE O LESIONES PERSONALES SEVERAS. ANTES DE PROCEDER, VERIFIQUE SIEMPRE QUE NO HAYA VOLTAJE PRESENTE.

    Figure 3.

    Figure 4.

    Attach Endcap. Maximum Breaker Rating 125A Continuous.

    Coloque la tapa en el extremo.Denominación máxima del interruptor 125A continuo.

    Insert Screws and Washers.

    Inserte los tornillos y arandelas dentro de los retenedores.

    A_1

    A_1

    A_1

    A_1

    Insert Unit Into Breaker.

    Coloque la unidad en el interruptor.

    Reset Unit

    Tighten Breaker Screws.

    Apriete los tornillos del interruptor.

    0.156 in(3.97mm)0.156 pulg.

    34–38 in lb(3.8–4.3 Nm)34–38 pulg./lb.

  • 2

    Instructional Leaflet IL01202012EEffective October 2010

    Ground fault protector/earth leakage protector for Series G E-Frame circuit breakers and

    HMCPE motor circuit protectors

    eaton corporation www.eaton.com

    Figure 5.

    Figure 6.

    Figure 7.

    Figure 8.

    Figure 9.

    Figure 10.

    Figure 11.

    Figure 12.

    Remove Secondary Cover.

    Remueva la tapa secundaria.

    Insert Push Bar into Mechanical Accessory.

    Inserte la barra en el accesorio mecánico.

    Insert Push Bar into RCD Window and Rotate Mechanical Accessory into Pocket.

    Inserte la barra en la ventana del RCD y rote el accesorio dentro de la cavidad (abertura).

    Torque Secondary Cover Mounting Screws 10–13 in lb (1.1–1.5 Nm).

    Apriete los tornillos de la tapa secundaria a un torque de 10–13 pulg. lb. (1.1–1.5 Nm).

    Replace Secondary Cover, Reset Unit and Latch Breaker.

    Reemplace la tapa secundaria y opere el interruptor.

    2

    13

    Test by Pushing Push-To-Trip Button.

    Pruebe la unidad presionado el boton de disparo.

    1

    2

    3

    Reset Unit and Latch Breaker.

    Reinicie la unidad y cierre el interruptor.

    12

    3

    Attach Accessories.

    Coloque los accesorios.

    Accessory Wires

    Customer Provided Contact.

    Contacto provisto por el cliente.

    Gre

    en

    Blu

    e

    Ora

    ng

    e

    Bell Alarm(3A–250V~)

    50% IG(0.1A–250V~)

    Bla

    ck

    Bla

    ck

    Wh

    ite

    Wh

    ite

    Remote Trip(0.1A–250V~)

    ON

    ON

    TRIP

    Off/Reset

    On

    Tripped

    State of bell alarm contacts as a function of circuit breaker and protector.Estado de los contactos de la alarma de timbre como una función de interruptor de circuito y protector.

    Position of the Toggle Handle

    Position of the Protector Reset Button (Yellow)

    Position of the Protector Bell AlarmOrange Blue Green

    Orange Blue Green

    Orange Blue Green

  • 3

    Instructional Leaflet IL01202012EEffective October 2010

    Ground fault protector/earth leakage protector for Series G E-Frame circuit breakers and HMCPE motor circuit protectors

    eaton corporation www.eaton.com

    Figure 13.

    product operation

    1. Earth leakage detected

    a. 50% Earth Leakage setting detected, LED and contacts change state.

    b. 100% Earth Leakage setting detected, the module trips the circuit breaker via mechanical interlock.

    c. Reset button on earth leakage module extends, indicating trip due to earth leakage current.

    d. Bell Alarm Auxiliary NO/NC contact in module changes state.

    2. Reset

    a. Depress Reset button on module (if tripped on earth leakage). This will reset the mechanical interlock allowing the circuit breaker to be reset.

    b. Reset circuit breaker.

    3. Test operation (line voltage must be present)

    a. Depress test button to test earth leakage circuit.

    b. The module trips circuit breaker via mechanical interlock.

    c. Reset button on earth leakage module extends.

    d. Bell Alarm Auxiliary NO/NC contact in module changes state.

    4. Remote tripping of breaker (line voltage must be present)

    a. Customer-supplied signal energized (dry contact closer).

    b. The module trips the circuit breaker via mechanical interlock.

    c. Reset button on earth leakage module extends.

    d. Bell Alarm Auxiliary NO/NC contact in module changes state.

    operación del producto

    1. Falla a tierra detectada

    a. Se detecta 50% de Falla a Tierra, el LED y contactos cambian de estado.

    b. Se detecta 100% de Falla a Tierra, el modulo dispara el interruptor de circuito por medio del enlace mecánico.

    c. El botón de reajuste en el modulo de fallo a tierra se extiende, indicando que hubo un disparo debido a un fallo de corriente a tierra.

    d. El contacto en el modulo Alarma de Campana Auxiliar NO/NC cambia de estado.

    2. Reajustar

    a. Presione el botón de reajuste en el modulo (si se disparo debido a falla a tierra). Esto reajustara el enlace mecánico lo que permitirá que el interruptor de circuito pueda ser reajustado.

    b. Reajustar el interruptor de circuito.

    3. Prueba de operación (el voltaje de línea debe de estar presente)

    a. Presione el botón de prueba para probar el circuito de fallo a tierra.

    b. El modulo dispara el interruptor de circuito por medio del enlace mecánico.

    c. El botón de reajuste en el modulo de fallo a tierra se extiende.

    d. El contacto en el modulo Alarma de Campana Auxiliar NO/NC cambia de estado.

    4. Disparo remoto del interruptor de circuito

    a. Señal energizada suplida por el cliente (contacto seco cercano).

    b. El modulo dispara el interruptor de circuito por medio del enlace mecánico.

    c. El botón de reajuste en el modulo de fallo a tierra se extiende.

    d. El contacto en el modulo Alarma de Campana Auxiliar NO/NC cambia de estado.

    Table 1a. EG-Frame Line and Load Terminations

    Wire Size torque

    Frame type

    Wire type aWG mm2

    terminal Materials

    catalog number Lb in nm

    EG-Frame Cu/Al 14–10 2.5–6 Aluminum TA125EF a 35 4.0

    EG-Frame Cu/Al 6–3/0 16–95 Aluminum TA150EF 80 9.0aStandard collars mounted on ground fault/earth leakage.

    Table 1b. Terminaciones de línea y carga del marco EG

    tamano de alambre torosion

    tipo de Marco

    tipo de alambre aWG mm2

    Material de la terminal

    numero de catalogo

    Lb in nm

    Marco EG Cu/Al 14–10 2.5–6 Aluminio TA125EF a 35 4.0

    Marco EG Cu/Al 6–3/0 16–95 Aluminio TA150EF 80 9.0aConectores estándares montados en el dispositivo falla a tierra/fuga a tierra.

    Reset ButtonBoton de reinicio

    IG (or In) Adjustment

    Adjuste del IG (o I n)

    t(s)

    1

    0.5

    0.3

    0.06

    0.15

    Inst.

    IG (A)

    10

    3

    10.3

    0.1

    0.03

    50% IG STATUS

    68

    C37

    33

    H04

    Ground Fault Protector

    WARNING

    C.B. Acc.560U

    0.03 Inst.

    Cat. ELEBN4125WS# 68D3907G03

    In 125A4 POLE120–480 VΣ 50/60 HzClass 1

    CU-AL

    TEST

    RESET

    Hazardous voltage – can cause severeinjury or death. In reverse-feed applicationsGFP (Ground Fault Protector) is energizedwhen breaker handle is in any position.

    Disconnect all power before installingor removing GFP.Do not remove cover from GFP.

    NOTICES:- Terminals if used must be aluminum TA125EF or TA150EF (Al/Cu). - See breaker for terminal torque.- See instrction sheet for high voltage tests.- For use on Seres G, E-Frame Circuit Breaker, Switch, Motor Circuit Protector.

    Push to

    Trip

    50% IG (or 50% I n)(Indicates 50% of Leakage Value has Been Reached)

    50% IG (o 50% I n)Indica que 50% del valor defuga fue alcanzado)

    Status Light (Flashes to indicate proper operation)

    Luz para indicacion del estado (Parpadea para indicar operacion apropiada)

    t(s) (o t) Adjustment

    Adjuste det(seg.) (o t)

    Terminal Block Access (4-Pole Only)Acceso al bloque de terminal (4 polos solamente)

    Push-to-Trip ButtonBoton de disparo

    Test ButtonBoton de prueba

  • Eaton CorporationElectrical Sector1111 Superior Ave.Cleveland, OH 44114United States877-ETN-CARE (877-386-2273)Eaton.com

    © 2010 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. IL01202012E H01 / Z10486October 2010

    PowerChain Management is a registered trademark of Eaton Corporation.

    All other trademarks are property of their respective owners.

    Instructional Leaflet IL01202012EEffective October 2010

    Ground fault protector/earth leakage protector for Series G E-Frame circuit breakers and

    HMCPE motor circuit protectors

    Figure 14.

    10.26(260.6)

    1.49(37.8)

    3.98 (101.1) Four-Pole2.98 (75.7) Three-Pole

    8.59(218.2)

    3.81(96.8)

    0.97(24.6)

    2.00(50.8)

    0.50(12.7)

    1.00(25.4)

    2.75(69.9)

    3.01(76.5)

    3.54(89.9)

    3.58(90.9)

    2.96(75.2)

    2.90(73.7)

    2.74(69.6)

    10.26(260.6)

    5.50(139.7)

    1.00(25.4)

    2.00(50.8)

    3.00(76.2)

    1.49(37.8)

    3.98 (101.1) Four-Pole2.98 (75.7) Three-Pole

    8.59(218.2)

    3.81(96.8)

    0.97(24.6)