Instrument Transformers Presentation2011-2

Embed Size (px)

Citation preview

  • 7/28/2019 Instrument Transformers Presentation2011-2

    1/104

    Instrument Transformers

    For currents greater than 100A and

    voltages higher than 500V, it is difficult to

    construct ammeters and current coils of

    wattmeters, energy meters and relays

    carrying alternating currents greater than

    100A.

    Specially designed transformers knownas instrument transformers are usedfor this purpose.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    2/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    3/104

    Agenda

    Current TransformersVoltage Transformers

    Required Information for Specifying CTs & VTs

    Take Home Rules for CTs & VTs

    Applications

  • 7/28/2019 Instrument Transformers Presentation2011-2

    4/104

    Why use Instrument Transformers?

    Circuit Isolation

    Reduce voltage and currentsto reasonable working levels.

    Phasor combinations for

    summing and measuringpower

  • 7/28/2019 Instrument Transformers Presentation2011-2

    5/104

    CURRENT TRANSFORMERS

    TYPES OF C.T. CONSTRUCTION

    The most common type of C.T. construction is the

    DOUGHNUT type. It is constructed of an iron toroid, which

    forms the core of the transformer, and is wound with secondary

    turns.

    Secondary Winding Primary Conductor

    Iron Core

  • 7/28/2019 Instrument Transformers Presentation2011-2

    6/104

    Transformer ratio (TR)

    Primary Current

    (100 amps)

    Secondary

    Current

    (5 amps)

    Primary Current

    Secondary CurrentTransformer Ratio =___________________

    __

    100

    5___= 100:5 or 20:1

  • 7/28/2019 Instrument Transformers Presentation2011-2

    7/104

    Polarity

    Direction ofPrimary Current

    Direction of

    Secondary Current

    H1

    X1

    Primary current into polarity =

    Secondary current out ofpolarity

    P1

    IEEE

    IEC

    PrimaryPolarity

    Marks

    IEEE

    IECS1

    Secondary

    Polarity

    Marks

    Remember:

  • 7/28/2019 Instrument Transformers Presentation2011-2

    8/104

    Polarity

    Direction of

    Primary Current

    Direction of

    Secondary Current

    H1

    X1

    P1

    IEEE

    IEC

    Primary

    Polarity

    Marks

    IEEE

    IECS1

    Secondary

    Polarity

    Marks

    Primary current into non-polarity =

    Secondary current out ofnon-

    olarity

    Remember:

  • 7/28/2019 Instrument Transformers Presentation2011-2

    9/104

    Generator typical wiring

  • 7/28/2019 Instrument Transformers Presentation2011-2

    10/104

    CT Rating Factor (RF) -- IEEE

    Rated current x (RF) =Maximum continuous current carrying

    capability:

    Without exceeding temperature limits

    Without loss of published accuracy

    class

    Typical rating factors for Metering CTs are:

    1.0, 1.33, 1.5, 2.0, 3.0, 4.0

  • 7/28/2019 Instrument Transformers Presentation2011-2

    11/104

    Short-Time Thermal Current Rating

    One (1) second thermal ratingExpressed as value of RMS primary current

    Main influencing factor:

    CT primary & secondary wire size

    Can be converted to thermal rating for any

    time period (t) up to five (5) seconds:

    (New RF at new Ambient/Stated RF at 30 degrees C)2=

    85-New Ambient/New Ambient

    Example: CT with rating factor of 4 at 30 degrees = rating factor of 2.95 at55 degrees

    X2/42=85-55/55 X=2.95

  • 7/28/2019 Instrument Transformers Presentation2011-2

    12/104

    Instrument Transformers

    The instrument transformers in a sub-

    station are:

    Current transformers:

    Voltage transformer.

    Capacitive voltage transformers (CVTs )

    Voltage Transformers ( IVTS or PTs )

  • 7/28/2019 Instrument Transformers Presentation2011-2

    13/104

    Importance of CTs &PTs

    Many protection systems are required to

    operate during the period of transient

    disturbance in the output of the

    measuring transformers that follows asystem fault.

    The errors in transformer output may

    abnormally delay the operation of theprotection, or cause unnecessary

    operations.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    14/104

    Importance of CTs &PTs

    Whenever the values of voltage orcurrent in a power circuit are too high topermit convenient direct connection of

    measuring instruments or relays,coupling is made through transformers.

    Such 'measuring transformers arerequired to produce a scaled downreplica of the input quantity to theaccuracy expected for the particularmeasurement

  • 7/28/2019 Instrument Transformers Presentation2011-2

    15/104

    To provide insulation between primaryand secondary circuit for equipment and

    personnel safety

    To change the magnitude (but not thenature) of the quality (voltage or current)

    being measured to a suitable level for

    use with standard instruments (protectiverelays, metering equipment, etc).

    Basic Function of Instrument

    Transformers

  • 7/28/2019 Instrument Transformers Presentation2011-2

    16/104

    Instrument Transformers (DO)

    The quality of instrument transformers

    willaffect directly the overall accuracyand performance of these metering

    and monitoring systems.

    Instrument transformer performance is

    critical in protective relaying, since the

    relays can only be as good as theinstrument transformers.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    17/104

    Basic Function of Instrument

    Transformers

    By using instrument transformers,electrical instruments have beenstandardized to operate on 110V and 5A

    or 1A. They are essential parts of many

    electrical systems, and are used for

    Measuring (metering) andMonitoring (relaying) devices.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    18/104

    Normally both the above functions arecombined in one unit in such apparatusused in power systems. Hence the

    general terminstrument transformers.

    There are occasions where these areused exclusively for commercialmetering and in which case they arecalled Metering Transformers.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    19/104

    Types of Instrument

    Transformers

    Instrument transformers are of twotypes, depending upon whether it is used

    to excite the current or voltage coil of the

    measuring instrument

    Current Transformers- CTs

    Voltage Transformers VTs (also

    referred to as Potential Transformers,

    PTs).

  • 7/28/2019 Instrument Transformers Presentation2011-2

    20/104

    Types of Instrument

    Transformers (Contd)

    Both of these types act as insulatorsbetween high-voltage primary and low-voltage secondary.

    The ratio of primary to secondary voltageis in proportion to the turns of ratio and

    will usually produce 110-120V at thesecondary terminals with rated primaryvoltage applied.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    21/104

    Accuracy of Instrument

    Transformers

    To be a useful part of a measurement system,

    instrument transformers must change the

    magnitude of the quantity being measured

    without introducing any excessive unknownerrors.

    The accuracy of an instrument transformer

    must either be of a known value, so that errors

    may be allowed for, or the accuracy must besufficiently high that errors introduced by the

    instrument transformer may be ignored.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    22/104

    Factors Affecting Accuracy of

    Instrument Transformers

    Design of the instrument transformer

    Circuit conditions such as voltage,current and frequency

    Burden connected to the secondarycircuit of the transformer

  • 7/28/2019 Instrument Transformers Presentation2011-2

    23/104

    Burden of Instrument

    Transformers

    In instrument transformer operations, the

    primary quantities are reduced by the

    turns ratio to provide a secondary current

    or voltage to energize protective relaysand other equipment.

    The totality of the impedances of the

    loads connected to current or voltagetransformers are referred to as burden.

    B d f I

  • 7/28/2019 Instrument Transformers Presentation2011-2

    24/104

    Burden of Instrument

    Transformers (Do)

    The burden consists of the impedances

    of the following:

    Secondary winding of the instrument

    transformer

    Interconnecting leads

    Relay and/or other connected devices.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    25/104

    connections

  • 7/28/2019 Instrument Transformers Presentation2011-2

    26/104

    Current Transformers - CTs

    Current Transformers are used whenever

    the magnitude of the operating current

    has to be reduced to the value for which

    instruments, meters and protectivedevices are designed. At the same time

    current transformers isolate metering and

    protective devices from the systemvoltage.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    27/104

    CTs

    The essential requirement of a currenttransformers is to deliver on its secondarya quantity(current), which truly represents

    the applied quantity on its primary. Thefailure of protective system to perform itsfunction correctly is due to incorrect

    application of this transformers.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    28/104

    CTs

    The requirements of a protective currenttransformer are quite different from thatof a metering C.T. The metering C.T. is

    only required to perform its functionover the normal range of load current,while the protective C.T is required to

    give satisfactory protection over a widerange of fault conditions.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    29/104

    CTs

    Working ranges of CTs

  • 7/28/2019 Instrument Transformers Presentation2011-2

    30/104

    CTs Characteristics

    The curve above describe a characteristic,

    indicating three regions namely:

    (i) Ankle point

    (ii) Linear or straight line region(iii)Knee point

    The working range of a metering C.T., isfrom the Ankle point to the Knee point and

    slightly beyond it.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    31/104

    CTs Characteristics

    Thus the metering C.T., operates between 10%and 120% of the rated current and saturatesbeyond this in order to protect the metering

    instruments.The working range of a protective C.T. extendsover the full range from the ankle point andbeyond. Generally the operating region of aprotective C.T. is beyond the knee point as it isrequired to operate at fault currents, which isseveral times the full load or rated current.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    32/104

    CTs Characteristics

    The knee point voltage of a metering C.T. isgenerally around 60 to 120V and is keptlow so as to protect meters.

    The knee point voltages of protective C.T.saregenerally quite high varying from 200V to1900V depending upon the requirements of therelay. The upper limit of 1900V is specified

    because the secondary cables from a C.T. aregenerally rated to withstand 2KV for about 1 or3 minutes and 660 volts or 1100 voltscontinuously.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    33/104

    CTs Characteristics

    The excitation voltages of metering and protective C.Ts is as follows:

  • 7/28/2019 Instrument Transformers Presentation2011-2

    34/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    35/104

    Theory of Current Transformers

    The current transformer operates likeany other transformer in that the voltage

    ratio and the reciprocal of the current ratio

    are proportional to the turns ratio i.e.Ep = Np

    Es NsWhere: p and s denote primary and secondary.

    E VoltageI Current

    N Number of turns

  • 7/28/2019 Instrument Transformers Presentation2011-2

    36/104

    Theory of Current Transformers

    The primary winding is connected inseries with the load and it is the latter

    which determines the current induced in

    the secondary winding. The secondary is connected to a burden,

    which does not vary, and the primary

    current is not influenced by the magnitudeof the secondary burden.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    37/104

    Theory of Current Transformers

    The current in the secondary isdetermined by the current in the primary

    winding.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    38/104

    Phasor diagram of a C.T.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    39/104

    Phasor diagram of a C.T.

    The secondary currentIs lags behind thesecondary induced voltage, Es by an

    angle . This angle is determined by the

    impedance of the external burden and theimpedance of the secondary winding.

    The primary currentIp is the resultant of -

    Is andIo the exciting current. The exciting

    currentIo consists of two components

    namelyIcthe core-loss component andIm

    the magnetizing component.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    40/104

    Phasor diagram of a C.T.

    The angle between Ip and (-Is) is thephase displacement error between theprimary and secondary currents. This

    angle is expressed in minutes of arc.

    The difference in lengths between Ip and

    (-Is) is called the Ratio Error. When this

    ratio error is expressed as a percentage of

    the primary current Ip, it is calledPercentage Ratio Error.

    Kn = Ip = N2 (the transformation ratio).

    Is NI

    Common definition of terms used

  • 7/28/2019 Instrument Transformers Presentation2011-2

    41/104

    Common definition of terms usedwith Current Transformers

    Composite error C Composite error C is the difference

    between the ideal secondary current and

    the actual secondary current under steady-state conditions. It includes amplitude

    (Ratio) and phase errors and also the

    effects of any possible harmonics in theexciting current

  • 7/28/2019 Instrument Transformers Presentation2011-2

    42/104

    Common definitionThusEc= 1001o

    t[(Kn is - ip)2dt]Ip T

    Where

    Ec is the composite errorT the time of one periodIp the rms value of the primary current in Ampsip the instantaneous value of the primary current in Amps.is the instantaneous value of the secondary current in

    Amps.Kn the transformation ratio = Ip

    Is

  • 7/28/2019 Instrument Transformers Presentation2011-2

    43/104

    Common definition

    At rated frequency and with rated burden connected, theamplitude error and phase error and composite error of a CT shall

    not exceed the values given in the following table.

    Marking: The accuracy class of a CT is written after the rated power. E.g.

    10 VA 5P10, 15 VA 10P10, 30 VA 5P20

  • 7/28/2019 Instrument Transformers Presentation2011-2

    44/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    45/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    46/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    47/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    48/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    49/104

    Common definition

    Rated BurdenThis is the apparent resistance of the secondary circuit

    expressed in ohms together with the power factor for

    which the specified accuracy limits are valid.

    Burden Zb = rb + jXb

    Secondary winding impedance Zs = rs + jXs

    Total secondary impedance Zt = Zb + Zs

    = (rb + rs) + j(Xb+Xs)

    Es =Is (Zb + Zs)

  • 7/28/2019 Instrument Transformers Presentation2011-2

    50/104

    Common definition

    Rated OutputThe rated output of a current transformer is theapparent power expressed in VA together with thepower factor, which the C.T. can deliver to thesecondary circuit at rated current and burden while stillmaintaining its accuracy in the specified class.

    The rated output is equal to the product of the ratedsecondary current and the voltage drop in the

    external secondary circuit due to this current.The standardised values of rated outputs are 2.5, 5, 7.5,10, 15, 30, 45, 60, 90, & 120 in VA.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    51/104

    Common definition

    In BSS, the VA output is specified along

    with the accuracy class. For example

    30 5P 10 means a protection C.T. of

    accuracy class s having a total error of5% with a VA of 30. The number 10 is

    the ALF defined later However in IEC,

    the VA is specified separately.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    52/104

    Common definition

    Accuracy Limit Factor (ALF) The accuracy limit current is the highest

    primary current at which a current

    transformer still meets the specifiedrequirements as regards total error. Theaccuracy limit factor is the ratio of theaccuracy limit current to the rated

    primary current. The standardized accuracy limit factors

    are 5, 10, 15, 20 and 30.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    53/104

    Common definition

    For example, as per IEC 5 p 20 means aC.T. for protection having maximumtotal error of 5% at 20 times the rated

    current. Marking: Accuracy limit factor is written

    after the accuracy class.

    E.g. 10 VA 5P10, 15 VA 10P10, 30 VA5P20.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    54/104

    Common definition

    Instrument Security Factor (ISF)The rated instrument security factor is thesmallest primary current at which an

    instrumentation core exhibits a currenterror of 10%.The Instrument Security Factor ISF is the

    ratio of the rated instrument safety currentto rated primary current.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    55/104

    Common definition

    The instrument security factor defines thebehavior of a metering C.T. core underover-current conditions. The ISF is

    specified to protect instruments connectedto the metering C.T. core from systemshort circuit currents. The ISF to bechosen should be as low as possible.It is expressed as a number n 5 or n10.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    56/104

    Common definition

    Knee point voltage (Vk)This is the sinusoidal e.m.f of ratedfrequency applied to the secondary

    terminals of the C.T., with all otherwindings being open circuited, which whenincreased by 10% causes the exciting

    current to increase by 50% or more. Thisis illustrated below:

    f

  • 7/28/2019 Instrument Transformers Presentation2011-2

    57/104

    Common definition

  • 7/28/2019 Instrument Transformers Presentation2011-2

    58/104

    Common definition

    ExampleV1= 100 VV2= 110 V

    Percentage Increase = 10%

    Corresponding currents C1= 0.35AC2= 0.7A

    Percentage increase = 50%V is the knee point voltage Vk.

    The knee point voltage indicates the voltage above which

    the C.T. enters into saturation and exciting current

    increases rapidly with a very little increase in voltage

  • 7/28/2019 Instrument Transformers Presentation2011-2

    59/104

    Common definition

    The Vk is also limited by practicaldesign and manufacturing considerationas:

    Vk = Rated output in VA x ALFSecondary rated current

    d fi i i

  • 7/28/2019 Instrument Transformers Presentation2011-2

    60/104

    Common definition

    Rated Short Time Thermal Current (Ith)This is the rms value of the primary current,which the C.T. will withstand for one secondwithout suffering any internal damage or otherharmful effects with the secondary being short-circuited.

    This rating is for a very short time and it is

    usually assumed that the entire heat generatedis stored in the primary winding itself.

    C d fi i i

  • 7/28/2019 Instrument Transformers Presentation2011-2

    61/104

    Common definition

    Rated short time thermal current isexpressed in KA. It is related to themaximum short circuit current at the

    point of installation of the C.T., and alsoon the duration of the breaking time ofthe short circuit current

    C d fi i i

  • 7/28/2019 Instrument Transformers Presentation2011-2

    62/104

    Common definition

    The following condition should be met with

    Ith Iscx[t + 0.05 x 50] KA rms.f

    WhereIth- Rated short time thermal current for 1 sec.Isc- Short circuit current at C.T. location in KA rmst - short circuit duration in sec.f - Rated system frequency.

    For system frequency of 50 Hertz

    Ith Isc[t + 0.05] KA rms.

    C d fi iti

  • 7/28/2019 Instrument Transformers Presentation2011-2

    63/104

    Common definition

    Rated Dynamic Current (I dyn)It is the peak value of the primary current, whichthe transformer will withstand without

    being damaged electrically or mechanically by theresulting electromagnetic forces, the secondarywinding being short- circuited.The maximum value of this current can be 2.5times the rated short time thermal current(Ith)

    I dyn = 2.5 Ith

    C d fi iti

  • 7/28/2019 Instrument Transformers Presentation2011-2

    64/104

    Common definition

    Rated Primary and Secondary CurrentThese are the values of the primary and secondarycurrent on which the performance of the currenttransformer is based.

    Standard values of primary currents are:5, 10, 15, 20, 30, 60, 75, 50, 100, 150, 200, 300, 400,600, 800, 1000, 1500, 2000, 3000, 4000 and above.

    Standard values of secondary currents as per BS 3938are 5A, 2A and 1A and as per IEC, 5A or 1A. Howeverthere are cases where occasionally ratings of 0.577A,0.866A or 2.87A have been used.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    65/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    66/104

    Tips on CT selection

    The selection of the primary current of a C.T. shall always beadopted as closely as possible to the full load or rated current of theinstallation by rounding off to the next higher standard. However theC.T must be capable of continuously carrying the maximum expectedcurrent in service. It is advisable to consider a permitted overload of20% of the full load current while deciding the rated current.

    Another factor to be considered is also the load growth and theincrease in capacity of an installation. It is for this reasonthat multi ratio primary currents are adopted like 800- 400 - 200 - 100 A.

    The selection of the secondary current depends upon the secondarycurrent of the equipment already in service where interchangeability isa consideration.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    67/104

    The following are the advantages and disadvantages ofCTs with 5A and 1A secondary currents.

    The number of turns required on the secondary side is less

    for a 5A C.T. than for a 1A C.T. for a given primary current.

    A thicker gauge wire is required for a 5A C.T than for a 1AC.T.

    Both the above factors contribute to the cost reduction of a

    5A C.T. when compared to a 1A C.T.

    Since the number of turns is less for a 5A C.T, the voltage

    induced on the secondary side during secondary saturation

    or secondary open circuit is less when compared to a 1A

    C.T.

  • 7/28/2019 Instrument Transformers Presentation2011-2

    68/104

    The lead burden, however, becomes excessive for a 5A C.Tsince the same is proportional to the product of the square

    of the current and resistance of the lead wire. The lead

    burden in a 1A CT. will be very low.

    In view of the reduced number of secondary turns in a 5AC.T., it is difficult to provide for turns compensation to

    design and manufacture low current higher accuracy class

    CTs. However in a 1A C.T. it is possible to achieve

    the desired accuracy class because of the increased

    number of turns and by providing compensating turns. The internal resistance of a 5A C.T. is comparatively less (

    1 ohm) when compared to that of 1A C.T. (Generally 3 to

    12 ohms)

    E l

  • 7/28/2019 Instrument Transformers Presentation2011-2

    69/104

    Examples

    A case study of Estimation of Burden, Knee PointVoltage, Accuracy Class etc of a Protective CurrentTransformer

    Requirement of a C.T. to protect a 15 MVA, 132/33 KVDelta/Star connected transformer.

    Data available

    % Impedance of Transformer = 10Fault level at 132KV side = 1400 MVA

    E l

  • 7/28/2019 Instrument Transformers Presentation2011-2

    70/104

    Examples

    Transformer full load current per phase= 15 x 106_____

    3 x 132 x 103= 65.61 A

    Hence select primary current = 100 A

    i.e. Ip = 100 A

    Select secondary current Is as 5A. A 5A C.T secondary

    has a winding resistant of less than 1.0 ohm. A typical

    value may be chosen as 0.601 ohms.

    E l

  • 7/28/2019 Instrument Transformers Presentation2011-2

    71/104

    Examples

    Assume(a)Distance from C.T to Relay control panel as 100 metres and

    C.T. secondary leads of 10 sq mm. (RL = 0.1627 ohms for 100

    metres)

    (b)Connected relays are GEC CDG 11 over-current and earthfault relays with VA burden of 1.8 and 4 respectively.

    E l

  • 7/28/2019 Instrument Transformers Presentation2011-2

    72/104

    Examples

    Relay burden =IS2RS + 2IS

    2RL + VA of (OCR + EFR)

    =(5) 20.601 + 2(5) 20.1627 + (1.8 + 4)

    = 15.0 + 8.135 + 5.8= 28.935 VA

    Hence select relay burden or output as 30 VA

    Select Accuracyclass 5 P 20

    Examples

  • 7/28/2019 Instrument Transformers Presentation2011-2

    73/104

    Examples

    Knee point voltage

    Vk = VA x ALF__

    Sec. current

    = 30 x 20

    5

    = 6005

    = 120 V

    Examples

  • 7/28/2019 Instrument Transformers Presentation2011-2

    74/104

    Examples

    Fault current at C.T. installation = 1400 x 106

    ___3 x 132 x 103

    = 6123.6 A

    or 6.124 KA = Isc

    IthIsc[t + 0.05] KA rms for 1 sec

    Assume operating time of breakers, relays etc = 1 sec

    Ith6.124[1.05]6.275 KA rms

    Select Ithas 10 KA rms for 1 sec

    Examples

  • 7/28/2019 Instrument Transformers Presentation2011-2

    75/104

    Examples

    Ith short time rating = 10 KA rms for 1 sec.

    Idyn = 2.5 Ith =2.5 x 10 = 25 KA for 1 sec.

    Hence complete specifications for this protection C T will be:

    Voltage class: 132 KVPrimary current: 100 A

    Highest System Voltage: 145 KV

    Secondary current: 5 A

    Accuracy class: 5 P 20

    Vk: 120 V.Ith: 10 KA rms for 1 sec.

    Idyn: 25 KA for 1 sec.

    Polarity and Markings

  • 7/28/2019 Instrument Transformers Presentation2011-2

    76/104

    Polarity and Markings

    Polarity and Markings

  • 7/28/2019 Instrument Transformers Presentation2011-2

    77/104

    Polarity and Markings

  • 7/28/2019 Instrument Transformers Presentation2011-2

    78/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    79/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    80/104

    Voltage Transformers

  • 7/28/2019 Instrument Transformers Presentation2011-2

    81/104

    Voltage Transformers

    Types of VTs

    Electromagnetic VT

    Capacitive VT

    Types of VTs for Protective

  • 7/28/2019 Instrument Transformers Presentation2011-2

    82/104

    Relaying.

    Voltage transformers have woundprimaries that are

    Either connected directly to the power

    systems (VTs)

    Or across a selection of capacitor string

    connected between phase and ground,

    that is, coupling-capacitor voltagetransformers (CCVTs)

    VTs For Relay Applications

  • 7/28/2019 Instrument Transformers Presentation2011-2

    83/104

    VTs For Relay Applications

    Voltage transformers, which step downsystem voltages to sufficiently low, safer,

    measurable values, are required for

    Indication of the voltage conditions. Energy meters and watt meters (kWh

    and kW meters)

    Protective relays Synchronizing

    Points To Note About VTs

  • 7/28/2019 Instrument Transformers Presentation2011-2

    84/104

    Points To Note About VTs

    VTs are used at all power system voltages,andare usually connected to the bus.

    Usually the CCTVs are connected to the line,

    rather than to the bus, because the couplingcapacitor devices may also be used to couple

    radio frequencies to the line for use in pilot

    relaying

    At about 115kV, the CCVT types becomesapplicable and generally more economical

    than VTs at the higher voltages.

    Points to Note About VTs (Do)

  • 7/28/2019 Instrument Transformers Presentation2011-2

    85/104

    Points to Note About VTs (Do)

    Either type of voltage transformer (VT orCCVT) provides excellent reproduction ofprimary voltage, both transient and steady-state, for protection functions.

    Saturation is not a problem because powersystems should not be operated above normalvoltage, and faults result in a collapse orreduction in voltage.

    VTs are normally installed with primary fuses,which are not necessary with CCTVs. Fusesare also used in the secondary.

    Voltage Transformers

  • 7/28/2019 Instrument Transformers Presentation2011-2

    86/104

    Voltage Transformers

    HV and EHV Capacitor-coupled VT (CVT)

    C1 & C2 are adjusted, so that a few kVs of voltage is obtains

    across C2

    Then, stepped down by T

  • 7/28/2019 Instrument Transformers Presentation2011-2

    87/104

    Example: To calculate the capacitance requirements for aCVT to be used on a 132KV system.

    Let (1) Total capacitance of capacitor be 20,000pF

    (2) Burden requirement 100 VA

    (3) Magnetic transformer designed for a standard primary

    voltage of 10/3 KV

  • 7/28/2019 Instrument Transformers Presentation2011-2

    88/104

    C1 = E2C2 E1

    = 10/3_________

    132/3 10/3

    C1 = _10____ x C2 = 10_ x C2

    132 10 122

    or C2 = 122 C1

    10

    Also 1_ + 1 = 1C1 C2 C

    Or C = C1C2_

    C1 + C2

  • 7/28/2019 Instrument Transformers Presentation2011-2

    89/104

    Substituting for C2 in the above eqn.

    C = C1 x 122 C1

    10____

    C1 + 122 C1

    10

    = C12 x 122

    10____10C1 + 122C1

    10

    = 122 C1

    132

    C1 = 132 C

    122= 132 x 20000 = 21639.34pF

    122

    C2 = 122 x 21639.34 = 264000pF

    10

  • 7/28/2019 Instrument Transformers Presentation2011-2

    90/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    91/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    92/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    93/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    94/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    95/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    96/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    97/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    98/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    99/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    100/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    101/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    102/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    103/104

  • 7/28/2019 Instrument Transformers Presentation2011-2

    104/104