TTE Hydraulic Schemes
Intelligent TopTronic control and Hoval system solutions A professional integrated approach
BioLyt > 50 TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
BioLyt >50 BioLyt with
Buffer vessel (no buffer control)
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BCDE010
BioLyt with
Twin buffer vessel with buffer control
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BCDE030
CompactGas TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
CompactGas CompactGas with
Low loss header
Boiler circuit pump with return protection
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BDGE020
TopGas > 30 TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
TopGas >30
TopGas with
1 x Direct circuit
Optional room station
BDDE010
TopGas with
1 x Direct circuit
Calorifier
Optional room station
BDDE020
TopGas with
Low loss header
Boiler circuit pump
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BDDE030
UltraGas TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraGas
UltraGas with
1 x Direct circuit
Optional gateway
Optional room station
BDEE005
UltraGas with
1 x mixed circuit
Optional gateway
Optional room station
BDEE020
UltraGas with
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BDEE030
UltraGas with
1 x Direct circuit
1 x Mixed circuit
Calorifier with separate flow/return
Optional extra mixed circuit
Optional gateway
Optional room station
BDEE040
UltraGas with
1 x Direct circuit
1 x Mixed circuit
Calorifier
High and low temperature returns
Optional extra mixed circuit
Optional gateway
Optional room station
BDEE050
UltraGas 3-8 Boiler Cascade TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraGas 3-8 Boiler Cascade
UltraGas 3-8 boiler cascade
Low loss header
3 x mixed circuits
Calorifier
KBCE010
UltraGas 3-8 boiler cascade
Low loss header
BMS control
Total flow sensor
KBCE020
UltraGas 3-8 boiler
Low loss header
Individual BMS controls
KBCE030
UltraGas Twin TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraGas Twin
2 boiler cascade
2 x mixed circuits
Calorifier
KBAE010
2 boiler cascade
BMS control
KBAE020
2 boiler cascade
Low loss header
2 x mixed circuits
Calorifier
KBBE010
2 boiler cascade
Low loss header
BMS control
Total flow sensor
KBBE020
2 boiler
Individual BMS control
KBAE030
2 boiler
Low loss header
Individual BMS controls
KBBE030
UltraOil TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraOil UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier
High and low temperature returns
Optional extra mixed circuit
Optional gateway
Optional room station
BEBE050
UltraOil (16-80) TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraOil (16-80) UltraOil with
1 x direct circuit
Optional gateway
Optional room station
BEBE005
UltraOil with
1 x mixed circuit
Optional gateway
Optional room station
BEBE010
UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier with separate flow/return
Optional extra mixed circuit
Optional gateway
Optional room station
BEBE020
UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEBE030
UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEBE040
UltraOil > 110 TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraOil >110 UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BECE020
UltraOil with
1 x Direct circuit
1 x Mixed circuit
Calorifier
High and low temperature returns
Optional extra mixed circuit
Optional gateway
Optional room station
BECE030
UltraOil Twin TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
UltraOil Twin Boiler 2 boiler cascade
2 x mixed circuits
Calorifier
KAE010
Uno-3 TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
Uno-3 Uno-3 with
Low loss header
Boiler circuit pump with return protection
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEEE030
Uno-3 with
Low loss header
Boiler circuit pump
1 x Direct circuit
1 x Mixed circuit
Calorifier with separate flow/return
Optional extra mixed circuit
Optional gateway
Optional room station
BEEE050
Uno-3 with
Low loss header
Boiler circuit pump with return protection
1 x Direct circuit
1 x Mixed circuit
Calorifier with separate flow/return
Optional extra mixed circuit
Optional gateway
Optional room station
BEEE060
Max-3 plus, SR-plus & ST-plus
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with local regulations.
Note – Optional items are shown in yellow.
Max-3 plus, SR-plus &ST-plus
- Max-3 plus, SR-plus & ST-plus� Low loss header� Boiler circuit pump� 1 x Direct circuit� 1 x Mixed circuit� Calorifier� Optional extra mixed circuit� Optional gateway� Optional room station
BEFE010
Max-3 plus, SR-plus & ST-plus� Low loss header� Boiler circuit pump with return protection� 1 x Direct circuit� 1 x Mixed circuit� Calorifier� Optional extra mixed circuit� Optional gateway� Optional room station
BEFE020
ThermoCondenser TCAF TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
ThermoCondenser TCAF Boiler with
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEGE010
Boiler with
Low loss header
Boiler circuit pumps with separate low and high temperature returns
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEGE020
Boiler with
Low loss header
Boiler circuit pumps with low return water protection and separate low and high temperature returns
1 x Direct circuit
1 x Mixed circuit
Calorifier
Optional extra mixed circuit
Optional gateway
Optional room station
BEGE040
Solar TTE Hydraulic Schemes
Attention! These hydraulic schematics only show the basic principles and do not show all the items of the installation. The installation must be in accordance with
local regulations.
Note – Optional items are shown in yellow.
Solar Single solar system BAAE020
Twin solar system BABE010
SolKit BAAE040
ZH-HLE:NE ednegeL: adoC / edoC Control voltage electric heating element SH Main switch with min. 3mm distance between
(R)BM
moorreliob eht fo edistuo gnitnuom ,tcatnoc)gnitaeh moor(
,stinu lareves fi( eludom lortnoRoom station / Cplease connect in line)
ELH-WW Control voltage electric heating element SLP Calorifier - loading pumpAAT
)reifirolac(
noitcartxe hsA
SM(A) Alarm (230V)ADR. Address switch
EW/EVU Power cut by power company SOP Solarpump 1,2…AF Outside sensor
FA Automatic Firing device (FA) SST Control power supply ~230V/50 HzAGF Flue gas sensor
FVT-F Flow rate sensor (F=flow rate) STB Safety temperature limiterASHB Ashbox switch
FVT-T Flow rate sensor (T=temperature) STW Flow switchAST-SV Extraction storage room (vacuum)
GB Internal device bus T1, T2,… difference control sensor 1,2…AST-V Extraction storage room (screw)
GWF Ground water sensor T1O, T2O, … Storage tank sensor 1,2... topATB Flue gas - temperature limiter (remove bridge)
GWP Ground water pump T1U, T2U, … Storage tank sensor 1,2... bottomAUE Automatic change-over device (storage room)
GW-STW Ground water flow switch TKO 1,2 Solar panel flow sensor 1,2…AVF Plant flow sensor (AVR control)
HST Main current power supply 3~400V/50 Hz TKR 1,2 Collector return sensorAV 1, 2 … Shut-off valve
IMP Pulse input TKSV Door touch sensit. switch stor. room (remove bridge)AVP Pump, plant flow control
KKP 1,2,… Boiler circuit pump 1,2… TTE-BM Control moduleB1 * Flow temperature switch - on demand
M5.1, M5.2,… Boiler circuit pump 1,2… TTE-FE Extension module B11 / XE6 Condesate - pumping station
M-BUS M-BUS TTE-GLT BMS module 0-10VB12 Fire alarm safety switch
MK1,2,… Pump mixing circuit 1, 2, … TTE-GW GatewayB13 Low gas pressure switch
MWQ heat source pump TTE-HK/WW Heating circuit/DHW moduleB15 Return thermostat
OT Data bus heat generator (OpenTherm) TTE-PS Buffer moduleB2 Flue gas - temperature limiter (remove bridge)
PBL Pump charging TTE-RBM Room control moduleB5 *) Emergency off - burner, to be mounted outside
PBSo Fill level pellets box top TTE-SOL Solar moduleof the boiler room (remove bridge)
PBSu Fill level pellets box bottom TTE-WEZ Base module heat generator*) If Y6 main gas valve
PEF Buffer discharging sensor TWVz Temperature heat exchanger supply centralexists, to be connected serial with Y6
PEL Pump discharging U12 Change-over unit storageB7 Low water pressure switch
PF 1, 2, … Buffer sensor UPA Change-over unit buffer start load reliefBFSV Storage room fill level switch
PF-A )lortnoc eriw-elgnis()AF( rosnes reffuBBK1,2,… Heat generator sensor 1,2…
PLF Buffer charging sensor UPE Change-over unit buffer load reliefBP / PW Water pressure sensor
PLP )lortnoc eriw-elgnis(pmup gnigrahc reffuBBUS-CAN Control bus connection
Pmax Max. pressure relief valve VA1,2,... Variable output 1, 2BZ (1,2) Operating signal (Stage1,2)
PS 1, 2, .. Solarpump 1,2… VA10V/PWM Variable output 0-10V/PWMCP Condenser pump
PWM Pulse-width modulation VE1,2,… Variable input 1, 2…CRF Condenser return sensor
PWTz Pump heat exchanger central VE10V Variable input 0-10VCVF condenser flow sensor
QF Heat source sensor VE230V Variable input 230VDKP Pump for heating cycle without mixer
RAS Low pressure switch extraction turbine- VF1,2,… Flow sensor 1,2…E1-ST
)egdirb evomer(-
tnemele gnitaeh cirtcele rof ylppus rewoP
WF Water meter (impulse)3~400V/50 Hz
R-CAN CAN terminating resistor
WF Heat generator sensorE1-WW Electric heating element - calorifier (external
RLF Return sensor
X… Plug connectiontemperature control)
RLP By-pass pump return
Y10.1,2,… Valve or zone valve 1,2...-E2 Heating tape condensate drain
RS485
)metsys eriw elgnis(-
rotareneg taeh sub ataD
E6 Condensate drip tray heater external
SF 1,2, … Calorifier heater sensor 1, 2, …
Y4 Exhaust gas damper or secondary airdevice (remove bridge)
Y6 Oil magnetic valve / main gas valveY6.1, Y6.2 Oil magnetic valve (Y6.1 single tube supply
Y6.2 double tube supply)Y7 Water deflector valve for calorifier
(single wire system)YAV Actuator plant flow mixerYK1,2,… Actuator mixer 1,2…YKR 1, 2, … Actuator low temperature protection 1,2…YPEL Actuator discharging mixerYPL Actuator charging mixerZKP Calorifier - circulation pumpZUP Feed pump
Automatic air vent