Intra-DC & DCI considerations for 100G+ migration

Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October 18th, 2016

Page 2: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

2 © 2015 EXFO Inc. All rights reserved. 2 © 2016 EXFO Inc. All rights reserved.

DC  global  traffic  5  ZB  2016/  10.4  ZB  2019  

10G/40G to 100G/200G/400G Migration

Within  the  DC  

Between  DC  &  users  

Between  Data  Center  

Page 3: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

3 © 2015 EXFO Inc. All rights reserved. 3 © 2016 EXFO Inc. All rights reserved.

10G/40G to 100G/200G/400G Migration

Transceiver  industry  has  developed  2  categories:    §  Parralel  opDcs  (MPO  connector):  2-­‐3  §  WDM  opDcs  (LC  connector):  1-­‐4  

Migra5on  to  100G+  interfaces  means  line  rate  upgrade  of  10Gbps  to  25/50/100Gbps  

Standardized  reach  for  transceivers:    §  MMF:  OM4/  WBMMF  –  150  m  §  SMF:  OS1/  OS2  –  10  km  (2km)  

MTP/MPO  connectors  and  12  or  24  fibers  ribbon  are  used  in  backbone  cables  due  to  installa5on  efficiency  

10G  (LC)  over  12-­‐Fiber  MPO  Cabling  

40G  (MPO)  over  12-­‐Fiber  MPO  Cabling  

2x3 Flip F 2x3 Flip F

100G+  (MPO)  over  12-­‐Fiber  MPO  Cabling  

100G  Switch 100G+  (LC)  over  12-­‐Fiber  MPO  Cabling   100G  Switch

1

2

3

4

Page 4: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

4 © 2015 EXFO Inc. All rights reserved. 4 © 2016 EXFO Inc. All rights reserved.

Data center design rule trend (Leaf-Spine)

Patch  panel   Patch  panel  

Patch  panel   Patch  panel   Patch  panel   Patch  panel  

Patch  panel   Patch  panel   Patch  panel   Patch  panel  

Patch  panel   Patch  panel   Patch  panel   Patch  panel   Patch  panel  Patch  panel   Patch  panel   Patch  panel  

Typical  fiber    distances  

40G-­‐100G  SMF      

Up  to  3,300  W.  1,000  m  

       

Up  to  500-­‐650  W.  150-­‐200  m  

     

Up  to  20  W.  6  m  

CAT-­‐6A/7/8  Twinax  copper  

Spine

Leaf

ToR

Racks

singlemode  

MDA      

HDA      

EDA  DC

I/  Cam

pus  

Page 5: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

5 © 2015 EXFO Inc. All rights reserved. 5 © 2016 EXFO Inc. All rights reserved.

OLTS vs iOLM-OTDR / RL, BR, ORL… Tier-1 & 2

Return  loss  (RL)  is  the  loss  of  power  in  the  signal  returned/reflected  by  a  disconDnuity  in  a  transmission  line  or  op5cal  fiber  (also  called  Reflectance  or  back  reflecDon).  

OpDcal  Return  Loss  (ORL)  is  a  measure  taken  from  one  end  of  the  total  energy  reflected  back  to  the  source  by  all  the  interfaces  (IOR,  breaks,  backscaYer,  etc.)  created  inside  a  component  or  along  a  link.  

LC   LC  

Launch   Receive  

End-­‐to-­‐end  

iOLM  -­‐  OTDR  

OLTS   Simplex  OR  Duplex  

Page 6: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

6 © 2015 EXFO Inc. All rights reserved. 6 © 2016 EXFO Inc. All rights reserved.

What DC operation testing makes sense?

Leaf

Spine Copper  channel  

Fiber  channel  

FIP  

FIP  

FIP  

FIP  

FIP  

FIP  

Move  Add  &  Changes  (MAC)    of  transceiver  (OLTS)  

OLTS

OLTS

Page 7: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

7 © 2015 EXFO Inc. All rights reserved. 7 © 2016 EXFO Inc. All rights reserved.

100G+: Additional DC testing scenarios

Spine

Leaf

Receive  

iOLM-­‐OTDR  posiDons  fault  along  the  fiber.  Measures  back  reflec,on  at  the  patch  panel.  

(If fiber)

OLTS OLTS

OTDR Launch  

Page 8: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

8 © 2015 EXFO Inc. All rights reserved. 8 © 2016 EXFO Inc. All rights reserved.

MTP/MPO - Guiding pins, guiding holes

Adapter

MPO Unpinned (Female)

MPO Pinned (Male)

MPO Guiding holes

MPO Guiding pins

Page 9: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

9 © 2015 EXFO Inc. All rights reserved. 9 © 2016 EXFO Inc. All rights reserved.

MTP/MPO - Physical contact is key… Physical Contact The  Physical  Contact  area  is  the  cri5cal  

joining  point  in  the  fiber  network.    If  no  clean  physical  connec5on,  the  light  path  is  disrupted  and  the  connec5on  is  compromised.  

MulDple  connects-­‐disconnects  can  create  fiber  misalignments  (loose  pin/  hole  or  memory  shape  related  issues)  

Page 10: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

10 © 2015 EXFO Inc. All rights reserved. 10 © 2016 EXFO Inc. All rights reserved.

FIP MTP/ MPO12/24 inspection probe

Low  mag  view  PIP  (100X):  Allows  to  see  which  fiber  is  being  inspected  in  High  magnifica5on  

High  mag  view  (400X):  Highest  Magnifica5on  on  the  market  

Auto-­‐center  +  Auto  Focus  

MTP12  –  MTP24  (MM/SM)  

Page 11: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

11 © 2015 EXFO Inc. All rights reserved. 11 © 2016 EXFO Inc. All rights reserved.

MTP/MPO cable configurations (polarity, types)

Page 12: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

12 © 2015 EXFO Inc. All rights reserved. 12 © 2016 EXFO Inc. All rights reserved.

100G+ migration (base 8) MTP/ MPO parallel

1 2 3

OTDR

Page 13: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

13 © 2015 EXFO Inc. All rights reserved. 13 © 2016 EXFO Inc. All rights reserved.

iOLM – MTP switch kit: software interface

1.  Link Length 2.  Total link loss 3.  Link ORL 4.  Connection Insertion

Loss 5.  Connection Return

Loss 6.  Pass/ Fail diagnostic

OTDR

Page 14: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

14 © 2015 EXFO Inc. All rights reserved. 14 © 2016 EXFO Inc. All rights reserved.

Any back reflection issues at the patch panel?

Source: EXFO Application Note 327 – Touching on Failure: Sources of Singlemode Fiber Issues in the Data Center, December 2015

10-­‐12  dB  average  change  (clean  vs.  oil)  

Strict  correla5on  (clean  vs.  oil)  0.7

0.6

0.5

0.4

0.3

0.2

0.1

0

70

60

50

40

30

20

10

0

Reflectance   ISO/IEC  11801  (2010)   TIA-­‐568.3-­‐D  (2013)   ISO-­‐IEC  14763-­‐3  (2014)*  

MMF   20  dB   20  dB   35  dB  

SMF   35  dB  UPC   35dB  UPC  55  dB  analog  video  

45  dB  UPC  60  dB  APC  

*  Reference  test  cords;  should  have  the  same  or  beger  performance  specificaDon  as  the  hardware  

terminaDng  the  cabling  under  test;    

Coherent-­‐based:  -­‐30dB  =  EDFA  APR  mode  issue  Direct  modulaDon:  -­‐40  to  -­‐45dB  CRC  issues    

What  about  back  reflecDon?  

Finger  oil  

Page 15: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

15 © 2015 EXFO Inc. All rights reserved. 15 © 2016 EXFO Inc. All rights reserved.

Do you face pluggables quality issues? Quick  quality  check  for  next-­‐gen  High  Speed  pluggables  with  quick  pass/  fail  verdict  

Supports  all  popular    high-­‐speed  pluggables  

Customer  CFP  

Fiber  Jumper  

Page 16: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

16 © 2015 EXFO Inc. All rights reserved. 16 © 2016 EXFO Inc. All rights reserved.

Network Latency is not always created equal…

Data  Center  1  

Data  Center  2  

DCI  

Page 17: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

17 © 2015 EXFO Inc. All rights reserved. 17 © 2016 EXFO Inc. All rights reserved.

What DCI testing considerations make sense?

CD/PMD  In-­‐band  OSNR  

Data  Center  1   Data  Center  2  

Data  Center  3  

OSA+100G test

VoIP  IPTV  Video  /  OTT  

Premium  IP  /  VPN  Service  High  Speed  Internet  

Key  Performance  Indicator  (KPIs),  per  Class  of  Services  (CoS)  Network  latency  /  Packet  loss  /  Bandwidth  /  QoS  /  BER  es5ma5on  

QoS QoS

QoS

MPLS  /  CORE  

Page 18: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

18 © 2016 EXFO Inc. All rights reserved.

DCI- Bit Error Rate (BER) evaluation

100G Through mode testing Simplified BER test setup view

Summary and detailed views of alarms and errors

• Ethernet Layer 2: traffic validation • During the construction phase, it is essential to test the traffic shaping using different profiles

• Validate the traffic protection with service disruption measurement

• Establish: • Testing period • Threshold values

Page 19: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

19 © 2016 EXFO Inc. All rights reserved.

DCI- Service Performance Evaluation

Multi-Service SAM (Y.1564) test TCP Throughput Test (RFC 6349)

Packet synchronization (SyncE and 1588 PTP)

ü Op,on:  Test  against  latest  cumng-­‐edge  MEF  standards  and  thresholds,  and  configurable  performance  criteria  (stringent  requirements)  

 ü Best  prac,ce:  Test  from  10M  to  100G  

Page 20: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

20 © 2016 EXFO Inc. All rights reserved.

Data Center – Intra + DCI assurance

Intra-DC

Inter-POD

Inter-DC

Intra-POD

Performance Report

Dashboard

Data Center Deployment:

•  Measure mesh performance

across all probes using L2 or L3 techniques

•  Complete transport layer performance analysis with unidirectional and round trip results

•  Using protocols with low

utilization to avoid impacting services (OAM or TWAMP)

External OSS/BSS

External Big Data

Integrate with external Systems

Page 21: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

21 © 2016 EXFO Inc. All rights reserved.

OSS

E2E IP Transport – DCI assurance

VoIP IPTV Video

Premium IP / VPN Service HSI

MPLS / CORE

Monitor performance between data centers •  Continuous core SLA and availability across multiple CoS simultaneously •  Combination of L3 Standards based approach •  Emulate Voice/Video/Web transaction and capture QoE performance •  Integration with OSS through Toolkit API

Monitor  Service  /  Network  and  Customer  QoE  Real-­‐Time  with  ReporDng  and  Dashboard  

Page 22: Intra-DC & DCI considerations for 100G+ migration · 2016. 10. 17. · Intra-DC & DCI considerations for 100G+ migration Nicholas Gagnon, BDM Data Center NANOG 68 Dallas - October

22 © 2015 EXFO Inc. All rights reserved. 22 © 2016 EXFO Inc. All rights reserved.

DATA CENTER FIBER It’s a vendor agnostic forum