2© 2016 EXFO Inc. All rights reserved.
INTRA–DC TRANSCEIVERS FORECASTS
Information from Informa PLC
25G server ports begin to ramp in 2016
40G sustains in 2016, continues with rest of market as web-scales jump to 100G
3© 2016 EXFO Inc. All rights reserved.
COMING TO THE RESCUE: WBMMF
Wide Band Multimode Fiber
8 fibers at 850 nm
2 fibers at 850 nm
880 nm
910 nm
940 nm
4© 2016 EXFO Inc. All rights reserved.
40G-100G REQUIREMENTS: IEEE 802.3BA
OM4 fiber IL max. requirement and reach performance
will be the same for WBMMF
5© 2016 EXFO Inc. All rights reserved.
ORL IS IMPORTANT TOO
-30 dB is a more realistic target for 25G+ line rate. Bad
reflection close to active equipment can be bad
-20dB won’t allow you to detect any potential Optical
Return Loss problem
6© 2016 EXFO Inc. All rights reserved.
TIGHT BUDGET AND MM IS CHALLENGING
Core diameter differences
Numerical Aperture differences
Core/Cladding concentricity errorFiber Mismatch
Light source/light coupled into the
fiber
7© 2016 EXFO Inc. All rights reserved.
OM4 PERFORMANCES REQUIREMENTS
TIA-492AAAD specifications for OM4 Fiber, September 2009
A core concentricity of 2 microns for a 50 micron
core fiber produces an attenuation of 0.47 dB
8© 2016 EXFO Inc. All rights reserved.
LAUNCH CONDITIONS: CONNECTOR OFF-SET
LED
VCSEL
FP-LaserModCon
© 2016 EXFO Inc. All rights reserved. 9
THE MANDREL WRAP AS A MODE CONDITIONERPrevious technique used before Encircled Flux
On the LS side wrap the TC
around 5 times
Measurement variability due to:
#1 Mode power distribution
#2 MM fiber characteristics
10© 2016 EXFO Inc. All rights reserved.
ENCIRCLED FLUX (EF) TEMPLATE
IEC 61280-4-1 Ed 2.0, Fibre-optic communication subsystem test procedure –
Part 4-1:Installed cable plant – Multimode attenuation measurement (Belden)
10GbE fiber-optic testing, requires Encircled Flux (EF) metric, slightly under-filled, launching conditions to satisfy the required
REPEATABILITY, REPRODUCIBILITY and UNCERTAINTYand provides good correlation between the loss and connector lateral off-set
11© 2016 EXFO Inc. All rights reserved.
LSPM – EF compliant
OTDR – EF compliant
ATTENUATION MEASUREMENTS METHODS
MMF Link
MLC
850 nm -
1300 nm
Laser
Variable Mode
Conditioner
Speckle
Scrambler
Launching
CableModal
interference
noise reduction
850 nm -
1300 nm
Power meter
MMF Link
MLC
850 nm - 1300 nm
OTDR
Variable Mode
Conditioner
Speckle
Scrambler
Launching
CableModal
interference
noise reduction
MLC: Mode Launch Conditions
12© 2016 EXFO Inc. All rights reserved.
1- OFL/ Mandrel Wrap per TIA-426- 14-A, Method B
2- Encircled Flux TIA-426-14-B, Annex A
COMPARATIVE OLTS MEASUREMENTS
Source: Optical loss testing in the field is not as simple as it seems, Belden (2011)
13© 2016 EXFO Inc. All rights reserved.
IT’S A WRAP.
1. Wide Band Multimode Fiber (WBMMF) and SWDM4
transceivers shall develop a competitive and affordable 40G-
100G proposition on both CAPEX and OPEX sides
2. Using a Mandrel can result in a large measurement variability
3. Encircled Flux (EF) metric for MMF insures the required
testing REPEATABILITY, REPRODUCIBILITY and
UNCERTAINTY in tighter budget situation such as IEEE
802.3ah 40G-100G requirements
14© 2016 EXFO Inc. All rights reserved.