INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Embed Size (px)

Citation preview

Page 1: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

INTRODUCTION TO T&T ELECTRICAL WIRING CODE

TTS 171: PART 1: 2002

By GEORGE SAMPSON

ELECTRICAL INSPECTOR III

GOVERNMENT ELECTRICAL INSPECTORATE

Page 2: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

What is the T&T Wiring Code?

• Revised edition of TTS: 26 20 505-1978

• REQUIREMENTS FOR THE ELECTRICAL WIRING OF BUILDINGS AND EQUIPMENT

• More Comprehensive

• Additional technical information.

Page 3: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

WHO BENEFITS?• Electrical Fraternity members

and clients

AREAS• Designing

• Planning

• The actual installation of a wiring system

Page 4: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

SCOPE• COVERS: Installations up to 600 volts

• NOT COVERED:Installations operated by Authorities

forthe Generation & Distribution of electrical power such as:

Powergen InnCogen T&TEC

Page 5: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

ENFORCEMENT

HOW?

• The CEI is the authority with jurisdiction

• Interpretation

• Enforcement of this standard

Page 6: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

CONFLICT

• If ever, any conflict arises between TTS 171 and any other standard, the CEI shall be the sole arbitrator and his decision shall be final

Page 7: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

WHAT’S NEW?

The terminologies are in harmony with international standards

Examples

2002 1978

•Ground •Earth

•Grounding Conductor •Earth Continuity Conductor

•Grounding Electrode Conductor

•Earthing Lead (MEC)

•Receptacle Outlet •Socket Outlet

Page 8: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

WHAT’S NEW ? ( Cont’d )

• Ground Fault Circuit Interrupter & Ground Fault Protection of equipment are also new to the list of definitions.

Page 9: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

ANNEX C

• Revision of TTS 1978 ( Table 21 )

• Guidelines on sub-circuit requirements for:• Residential

• Commercial

• Industrial Installations

Page 10: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

• Simple Formulae and Worked Example for voltage drop calculation ( section D.1.7.3)

• New to this standard

• It was included to assist with the application of the Voltage Drop Tables

Page 11: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

ANNEX EMaximum conductor fill for Conduits

& Boxes

Consider a practical case:

Install the following conductors within a common raceway:

• 6 x 1.5mm sq.

• 8 x 2.5mm sq.

• 4 x 6.0mm sq.

• 6 x 4.0mm sq.

Page 12: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Comply with section 6.2.7

• A space factor of 40% is not to be exceeded.

• The cables are not to be damaged.

• No more than two ( 2 ) 90 degrees bends are allowed along the conduit work.

Page 13: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

DISTRIBUTION AND PROTECTION (Section 4.1.1)

• Every consumer’s installation shall be adequately controlled by a service disconnect. i.e. Main Switch or Circuit Breaker

• Does this requirement apply to systems utilizing standby power from a Generator?

Page 14: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

• The CEI requires that all wiring

systems are to comply with section 4.1.1 whether they utilize a standby Generator or not.

• In addition, those with standby power must incorporate suitable Transfer Equipment.

Page 15: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Why Transfer Equipment?

• This is to prevent the inadvertent or accidental interconnection of the normal (T&TEC) and the standby ( Generator) sources of power.

Page 16: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

HIGHLIGHTS FROM OTHER SECTIONS

OF THE CODE

Page 17: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

MARKINGS

• Section 3.10.1 requires each piece of electrical apparatus and material to bear such markings to identify it

• To ensure its suitability for the particular application

Page 18: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Examples of Markings• Manufacturers’ name, trademark, or other

recognized symbols of identification

• Rated load in amperes

• Rated frequency or frequency ranges in hertz

• Whether for continuous load or intermittent

Page 19: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Consequences of failure to conform to technical data

• Persons could receive a severe electric shock

• Explosion or fire may occur

• Serious injury may occur from a fall or flying objects

• Electrocution is also a very, very real possibility

Page 20: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

The foregoing are sufficient reasons to be

meticulous when selecting equipment and materials.

Page 21: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

GROUNDING ELECTRODE CONDUCTOR &

GROUNDING CONDUCTOR

Page 22: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Why should we give the Grounding Electrode

Conductor and the Grounding Conductor the respect they

deserve?

Page 23: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Three basic reasons for grounding• Limits the voltage caused by lightning, or by

accidental contact with conductors of higher voltages.

• Stabilizes the voltage under normal operating conditions - to maintain the voltage at one level relative to ground so equipment connected to the system is subjected only to that potential difference.

• Facilitates the operation of over current devices such as fuses, circuit breakers or relays under ground fault conditions.

Page 24: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Selection and application of:

• The Grounding Electrode Conductor and the Grounding Conductor deserves our keenness attention

• Sizes of grounding conductors

( Sec 9.5 )

See Current Ed. Of NFPA 70 Tables

250-66 and 250-122

Page 25: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

APPARATUS IN GARAGES (Section 8.5)

Where motor-driven vehicles are:• Stored• Serviced• Repaired

• All apparatus shall, unless of a totally enclosed or flameproof type, be installed at a minimum height of 1200mm ( 4ft ) above the general floor level.

Page 26: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

SEGREGATION OF CIRCUITS (Section 5.23 )

• Lighting and power cables operating at voltages above extra-low ( i.e.exceeding 50 V a.c. or

120 V d.c. whether between conductor or to ground).

• Shall not be drawn into the same conduit or duct as cables of extra-low voltage or of radio systems.

• Unless the latter are insulated for the higher voltage present.

Page 27: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Note:

Failure to observe these guidelines

may result in Electromagnetic

Induction (EMI ) and disruption of

the extra-low voltage equipment.

Page 28: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

RACEWAY INSTALLATIONS (section 6.1.1)

• Conduit works shall be completed before any cables are drawn in.

• Ends shall be reamed and bushed to avoid abrasion.

• Inspection boxes shall remain accessible throughout the life of the installation.

Page 29: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

TESTING AND INSPECTION(Section 10 )

• To determine what malfunctions are possible

• To determine what protection is necessary and sufficient

• To minimize the ill-effects of such malfunctions

Page 30: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Section 10.1.1

• Requires that every new installation and

any alteration to an existing installation

shall be inspected and tested to ensure

compliance with TTS 171

Page 31: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Inspection and Testing

Involves:

• Visual examination of workmanship• Verification of polarity (I.R.test)• Effectiveness of grounding• Continuity• A verification of polarity shall be made

to ensure that all fuses, circuit breakers and single pole control devices, are connected to live conductors only.

Page 32: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Since ground fault protection relies on operation of fuses or circuit breakers,

the resistance or impedance between the electrode and the remote end of every

grounding conductor, shall not exceed 1 ohm.

• Where metal conduit forms part or whole of the grounding conductor, the

above shall also apply.

Page 33: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Electrical Metallic Tubing ( EMT )

• Shall be protected against any risk of mechanical damage.

• Not to be exposed to rain, dripping water, condensation, oil, corrosive substances and hazardous location.

• Not bend, as to damage the tubing or to effectively reduce its internal diameter.

• Not be buried directly in the ground.

Page 34: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

CONTROL OF MOTORS

(Section 8.12.2) • Each motor and its control equipment shall

have a disconnecting means.

For remote disconnecting means:• an additional means of isolation adjacent to the

motor shall be installed OR• a lockout device shall be installed adjacent to

the motor

• The remote means of isolation shall be able to be locked in the off-position.

Page 35: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

Conclusion

Section 3.1.2 reads in part:

• This standard contains minimum provision considered necessary for safety, but is not to be regarded as a design specification or an instruction manual for untrained persons.

Page 36: INTRODUCTION TO T&T ELECTRICAL WIRING CODE TTS 171: PART 1: 2002 By GEORGE SAMPSON ELECTRICAL INSPECTOR III GOVERNMENT ELECTRICAL INSPECTORATE

THE END