PRODUCT RANGE QICC – a Nexans Company is committed to deliver the highest standard wires and power cables to the local market, GCC and for export. In order to fit for the customer demand in the Middle East and for export, QICC – a Nexans Company produces a versatile product range covers most of our customer needs: BUILDING SECTION: • Flexible wires and cables up to 16 mm2 to IEC 60227, EN 50525, BS 6004 & BS 6500. • Building wires (NYA) to IEC 60227, EN 50525 and BS 6004, from 1.5 mm2 and above. • Halogen Free Flame Retardant wire (HFFR/LSZH) to BS 7211 and EN 50525, with thermo setting insulation which is alternative to wire type (NYA), where the application requires higher standards of safety against the emission of smoke, fumes and toxic gases. The wires coming mainly single core. LOW VOLTAGE SECTION: • Low Voltage power Cables with PVC and XLPE insulation to IEC 60502-1, BS 5476 and BS 6346. The cables can be single core, and multi core up to 48 cores. MEDIUM VOLTAGE SECTION: • Medium Voltage cables to IEC 60502-2 up to 18/30 (36) kV and to BS 6622 up to 19/33 (36) kV. • LV cables with HFFR, thermosetting insulation. The cables are produced according to BS 6724, IEC 60502-1and tested to IEC 61034, IEC 60754 & IEC 60332. • MV cables with HFFR to BS 7835. The cables can be single core, and three cores cable. HIGH VOLTAGE AND EXTRA HIGH SECTION: • High Voltage and Extra High Voltage cables up to 220 kV to IEC 60840 / IEC 62067, with conductor sizes up to 2500 mm2. The cables are single core only.

Intruduction Final LV

  • Upload
    mealysr

  • View
    29

  • Download
    0

Embed Size (px)

DESCRIPTION

Nexans underground cables

Citation preview

  • PPRROODDUUCCTT RRAANNGGEEQICC a Nexans Company is committed to deliver the highest standard wires and power cables tothe local market, GCC and for export.In order to fit for the customer demand in the Middle East and for export, QICC a Nexans Companyproduces a versatile product range covers most of our customer needs:

    BUILDING SECTION: Flexible wires and cables up to 16 mm2 to IEC 60227, EN 50525, BS 6004 & BS 6500. Building wires (NYA) to IEC 60227, EN 50525 and BS 6004, from 1.5 mm2 and above. Halogen Free Flame Retardant wire (HFFR/LSZH) to BS 7211 and EN 50525, with thermosetting insulation which is alternative to wire type (NYA), where the application requires higherstandards of safety against the emission of smoke, fumes and toxic gases.The wires coming mainly single core.

    LOW VOLTAGE SECTION: Low Voltage power Cables with PVC and XLPE insulation to IEC 60502-1, BS 5476 and BS 6346.The cables can be single core, and multi core up to 48 cores.

    MEDIUM VOLTAGE SECTION: Medium Voltage cables to IEC 60502-2 up to 18/30 (36) kV and to BS 6622 up to 19/33 (36) kV. LV cables with HFFR, thermosetting insulation.The cables are produced according to BS 6724, IEC 60502-1and tested to IEC 61034, IEC 60754 &IEC 60332. MV cables with HFFR to BS 7835.The cables can be single core, and three cores cable.

    HIGH VOLTAGE AND EXTRA HIGH SECTION: High Voltage and Extra High Voltage cables up to 220 kV to IEC 60840 / IEC 62067, withconductor sizes up to 2500 mm2.The cables are single core only.

  • DDEESSIIGGNN CCRRIITTEERRIIAAA power cable is an assembly of one or more electrical conductors, usually held together with anoverall sheath. The assembly is used for transmission of electrical power. Power cables may beinstalled as permanent wiring within buildings, buried in the ground, run overhead, or exposed.Flexible power cables are used for portable devices, mobile tools and machinery.

    1. CONDUCTOR:Is an object or type of material that permits the flow of electrical current in one or more directions.Conductor materials are:- Plain annealed or tin coated copper conductor (to BS EN 1977, ASTM B3, ASTM B49 &ASTM B 33)- Aluminum (to ASTM B233)The conductor structure is complying with the requirements of IEC 60228 class 2 stranded, noncompacted, compacted or compacted sector shaped conductors.

    2. INSULATION:The insulating materials used include:2.1 Polyvinylchloride (PVC): (PVC/A 70 oC) complying with IEC 60502-1 requirements or Types (TI170 oC) & Heat Resistant PVC type TI-3 (90 oC to 105 oC) complying with BS EN 50363-3.2.2 Halogen-Free, Flame Retardant compound (HFFR).2.3 Cross-linked polyethylene (XLPE): complying with IEC 60502 and GP8 as per BS 7655-1.3The insulation of building wires is covered by Ultra-violet (UV) resistant Masterbatch.

    3. Insulated Core Color Codes:

    Number ofcores Colors to IEC 60502-1 Colors to BS 54671 Red or Black Brown or Blue2 Red & Black Brown & Blue3 Red, Yellow and Blue Brown, Black and Grey4 Red, Yellow, Blue and Black Blue, Brown, Black and Grey5 Red, Yellow, Blue, Black and

    Green / YellowGreen / Yellow, Blue, Brown,

    Black and Grey

  • 4. SCREEN DESIGNS:

    The standard range of QICC Medium Voltage XLPE cables rated up to and including 33 kVincorporates copper wire screens based on fault levels of either 3 kA or 10 kA for 1 second. If eitherof the standard screen designs does not suit a particular installation, the screen constructions can betailored in size to meet the specific fault requirements of any operating system.

    5. WIRE SCREEN CROSS SECTIONAL AREAS:In the case of three core cables which have screens around each individual core, the total screencross sectional area is spread evenly over the three cores.There are several other factors which can override the above criteria.Firstly, the screens are designed so that the average gap between the wires does not exceed 4 mm.This result in the screen area being increased above that required for the required fault level incertain cases. Secondly, the screen area is limited to a value so that its fault rating does not exceedthat of the conductor. In some cases, the smaller cables in a range have fault levels of less thaneither 3 kA or 10 kA for 1 second respectively.

    6. CABLE ASSEMBLY:The Insulated cores are assembled together to form the laid up cable cores in case of multi corecables.Extruded suitable polymer compound or non-hygroscopic polypropylene filler is applied (whenrequired) between laid up cores to provide a circular shape to the cable.

    7. JACKETINGS:There are 3 different types of extruded sheaths:7.1 Outer sheath

    It provides protection of the cable from outside.7.2 Inner sheath

    It applies under a metallic protection and - optional - under a lead sheath.7.3 Bedding

    It separate the sheath applied between a lead sheath and a metallic protection (may alsoconsists of plastic tapes).

    The following materials can be used for the sheath:

  • Polyvinylchloride (PVC) Type ST2 compounds as specified in IEC 60502-1, or its equivalentPVC Type 9 to BS 7655-4.2.

    Polyethylene (PE) compound fulfill and exceed the requirements of Type ST7 IEC 60502-1for cables that require being abrasion resistant, protected against water ingress and strongEnvironmental Stress Crack Resistant (ESCR).

    Halogen Free Flame Retardant (HFFR) compounds complying with ST8 to IEC 60502-1or Types LTS 1 & LTS 4 to BS 7655: section 6 for cables installed in intrinsically safe locationsand where the cables require being low smoke, low fume and low toxic gas emitting in case offire. Cables to this category are complying with the requirements of BS 6724.

    All cables produced at QICC a Nexans Company with PVC or HFFR jackets are complyingwith the flame retardant test to IEC 60332-1 and Ultra-violet (UV) resistant Masterbatch.

    Whenever a requirement for more severe tests as IEC 60332-3 is needed, Oil resistant andHydrocarbon resistant for Oil and Gas projects.

    8. ARMOUR:There are 3 different types of armouring are listed below:

    Galvanized round steel wire armour SWA:(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).

    Single or double layer of steel STA :(The minimum thickness of a tape shall be 0.2 mm).

    Aluminum or copper wire armour AWA / CWA:(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).

    9. JACKETING MARKETING:

    Standard engraving outerJacketMarking consisting of:

    1. Type designation, size of conductor, rated voltage, standard.2. Name of manufacturer QICC-Nexans.3. Year, continuous length marking every meter.4. Any special part no. on request.

    10. INSTALLATION

  • Inform

    ation

    Data

    LowV

    oltag

    eCon

    trolca

    bleHig

    hVoltag

    eDistr

    ibution

    LowV

    oltag

    eSign

    alcable

    LowV

    oltag

    eDistr

    ibution

    Low voltage cables with both PVC and XLPE insulation are suitable for indoor and outdoorapplications. The methods are based on IEC 60364-5-52 or BS 7671 IEE wiring regulationseventeenth edition.Below are the recommendations to be followed in order to get the optimal cable service:1. Unarmoured cables are not recommended for direct buried applications, except if thequoted cables are designed and produced to pass direct burial test requirements (example, directburial tests described in UL 1277 and UL 1581).2. Armoured cables are not recommended for tray applications, as they are heavy in weightand extra loads are exerted on the tray.3. A PVC jacket is a very stable material against a wide range of chemicals, while HDPEjacketed cables can serve better in wet locations.4. A recommended minimum bending radius as per the technical data sheet of each group.5. HFFR cables are not recommended for direct buried applications, as the material is soft andits mainly for building proposes.

    10.1 CABLE PULLING-IN FORCE:Care should be taken to prevent damage to insulation or distortion of cable during installation.The pulling force in Newtons should not exceed 0.036 times the circular mil area of the coppercross-sectional area times the number of conductors in the cable when pulling on the conductorsutilizing pulling eyes and bolts. Pulling force for multi core cables when utilizing eyes or bolts shouldnot include drain or ground conductors in the copper cross-sectional area. When pulling with abasket weave grip, maximum pulling tension (per grip) should not exceed 4.5kN, or the valuecalculated for eyes or bolts, whichever is greater.The sidewall pressure should not exceed a maximum of 7.3kN per meter of the inside radius of thebend.Cables should not be pulled in freezing conditions. If conditions are below 0C, consult themanufacturer.If it is necessary to pull in these conditions, cables should be stored at a temperature above 10C for24 h prior to installation, if the cable has been previously stored in an area under 0C.When installing low smoke cables, additional consideration should be given to handling andlubrication due to their possible lower tear strength and higher coefficient of friction than othermarine cable.For more guidance concerning this subject, refer to IEEE Std 576-2001

    10.2 Single-conductor ac cables:To avoid an undesirable inductive effect in ac installations, the following precautions should beobserved.

  • Closed magnetic circuits around single-conductor ac cable should be avoided, and no magneticmaterial should be permitted between cables of different phases of a circuit.1. Single-conductor ac cables should not be located closer than 76mm from parallel magneticmaterial.2. Single-conductor ac cable should be supported on insulators. Armor, if used, should begrounded only at approximately the midpoint of the cable run.3. Where single-conductor ac cables penetrate the bulkhead, conductors of each phase of thesame circuit should pass through a common nonferrous bulkhead plate to prevent heating of thebulkhead.4. Single-conductor cables in-groups should be arranged to minimize their inductive effect. Thismay be accomplished by the transposition of cables in groups of three (one each phase) to give theeffect of triplexed cable. This transposition should be made at intervals of not over 15m and need notbe made in cable runs of less than 30m.

    10.3 Cable continuity and grounding:All cable should be continuous between terminations; however, splicing is permitted under certainconditions. For cable provided with armor, the armor should be electrically continuous betweenterminations and should be grounded at each end (multi conductor cables only); except that for finalsub circuits, the armor may be grounded at the supply end only.

    10.4 Cable locations:Cable installation should avoid spaces where excessive heat and gases may be encountered such asgalleys, boiler rooms and pump rooms, and spaces where cables may be exposed to damage suchas cargo spaces and exposed sides of deck houses. Cables should not be located in cargo tanks,ballast tanks, fuel tanks, or water tanks except to supply equipment and instrumentation specificallydesigned for such locations and whose functions require it to be installed on the tank. Suchequipment may include submerged cargo pumps and associated control devices, cargo monitoring,and underwater navigation systems.Unless unavoidable, cables should not be located behind or embedded in structural heat insulation.Where cables are installed behind paneling, all connections should be readily accessible and thelocation of concealed connection boxes should be indicated. Cables should preferably not be runthrough refrigerated cargo spaces.Cables should not be located below the faceplate of the vessel s main bottom structural members orwithin .6m above any double bottom tank top.

    10.5 Cable protection:Cables should be adequately protected where exposed to mechanical damage. Cables should besecured against chafing or displacement due to vibration. Cables in bunkers, and where particularlyliable to damage, such as locations in way of cargo ports, hatches, tank tops, and where passing

  • through decks, should be protected by removable metal coverings, angle irons, or other equivalentmeans.Where cables pass through insulation, they should be protected by a continuous pipe. For wiringentering refrigerated compartments, the pipe should be of heat-insulating material (fiber or phenolictubing) joined to the bulkhead-stuffing tube, or a section of such material should be inserted betweenthe bulkhead-stuffing tube and the metallic pipe.Where cables are installed in pipes, the space factor (ratio of the sum of the cross-sectional areascorresponding to the external diameter of the cables to the internal cross-sectional areas of the pipe)shall not be greater than 0.41, except for two cables, where the space factor shall not exceed 0.31,Pipes shall be so arranged or designed to prevent the accumulation of internal condensation.

  • MMAANNUUFFAACCTTUURRIINNGG CCHHAARRTTMMAANNUUFFAACCTTUURRIINNGG CCHHAARRTTMMAANNUUFFAACCTTUURRIINNGG CCHHAARRTT

  • EELLEECCTTRRIICCAALL CCHHAARRAACCTTEERRIISSTTIICCSSSSTTAANNDDAARRDDSS RREELLAATTEEDD TTOO PPOOWWEERR CCAABBLLEESS1. THE INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)DOCUMENT NO. DOCUMENT NAME

    IEC 60038 IEC standard voltages - Edition 7.0IEC 60050-121 AMENDMENT 2 International Electro technical Vocabulary Part 121:

    Electromagnetism - Edition 2.0IEC 60060-1 High-Voltage Test Techniques Part 1: General Definitions and Test

    Requirements - Edition 2.0; The contents of the corrigendum of March 1992have been included in this copy

    IEC 60183 AMD Guide to the Selection of High-Voltage Cables - Edition 2.0IEC 60227-1 Polyvinyl chloride insulated cables of rated voltages up to and including

    450/750 V Part 1: General requirements - Edition 3.0IEC 60227-2 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including

    450/750 V - Part 2: Test Methods - Edition 2.1; Edition 2: 1997 Consolidatedwith Amendment 1: 2003

    IEC 60227-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including450/750 V - Part 3: Non-Sheathed Cables for Fixed Wiring - Edition 2.1

    IEC 60227-4 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including450/750 V - Part 4: Sheathed Cables for Fixed Wiring - Edition 2.1; Edition2: 1992 Consolidated with Amendment 1: 1997

    IEC 60227-5 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including450/750 V - Part 5: Flexible Cables (Cords) - Edition 2.2; Edition 2:Consolidated with Amendments 1:1997 and 2:2003

    IEC 60227-6 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including450/750 V - Part 6: Lift Cables and Cables for Flexible Connections - ThirdEdition

    IEC 60227-7 Polyvinyl chloride insulated cables of rated voltages up to and including450/750 V Part 7: Flexible cables screened and unscreened with two or moreconductors - Edition 1.1; Edition 1: 1995 Consolidated with Amendment 1:2003

    IEC 60229 Electric cables Tests on extruded over sheaths with a special protectivefunction - Edition 3.0

    IEC 60230 Impulse Tests on Cables and Their Accessories - First EditionIEC 60270 High-Voltage Test Techniques - Partial Discharge Measurements - Third

    Edition; Corrigendum 1, 10/2001IEC 60287-1-3 Electric Cables - Calculation of the Current Rating - Part 1-3: Current Rating

    Equations (100% Load Factor) and Calculation of Losses - Current Sharingbetween Parallel Single-Core Cables and Calculation of Circulating CurrentLosses - First Edition

    IEC 60287-2-1 Electric cables Calculation of the current rating Part 2-1: Thermalresistance Calculation of the thermal resistance CORRIGENDUM 1 -Edition1.2

  • IEC 60332-3-10 Tests on electric and optical fibre cables under fire conditions Part 3-10:Test for vertical flame spread of vertically-mounted bunched wires or cables Apparatus - Edition 1.1; Consolidated Reprint

    IEC 60332-3-21 Tests on Electric Cables Under Fire Conditions - Part 3-21: Test for VerticalFlame Spread of Vertically-Mounted Bunched Wires or Cables - Category AF/RFirst Edition

    IEC 60332-3-22 Tests on electric and optical fiber cables under fire conditions Part 3-22:Test for vertical flame spread of vertically-mounted bunched wires or cables Category A - Edition 1.1; Consolidated Reprint

    IEC 60332-3-23 Tests on electric and optical fiber cables under fire conditions Part 3-23:Test for vertical flame spread of vertically-mounted bunched wires or cables Category B - Edition 1.1; Consolidated Reprint

    IEC 60332-3-24 Tests on electric and optical fiber cables under fire conditions Part 3-24:Test for vertical flame spread of vertically-mounted bunched wires or cables Category C - Edition 1.1; Consolidated Reprint

    IEC 60332-3-25 Tests on electric and optical fiber cables under fire conditions Part 3-25:Test for vertical flame spread of vertically-mounted bunched wires or cables Category D - Edition 1.1; Consolidated Reprint

    IEC 60364-5-52 Low-voltage electrical installations Part 5-52: Selection and erection ofelectrical equipment Wiring systems - Edition 3.0

    IEC 60446 Basic and safety principles for man-machine interface, marking andidentification Identification of conductors by colours or alphanumerics -Edition 4.0

    IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltagesfrom 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) Part 1: Cables forrated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV) - Edition 2.1;Consolidated Reprint

    IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for RatedVoltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2:Cables for Rated Voltages from 6 kV (Um = 7,2 kV) and up to 30 kV (Um =36 kV) - Edition 2

    IEC 60719 Calculation of the Lower and Upper Limits for the Average Outer Dimensionsof Cables with Circular Copper Conductors and of Rated Voltages up to andIncluding 450/750 V - Edition 2; CENELEC EN 60719: 1993

    IEC 60724 Short-circuit temperature limits of electric cables with rated voltages of 1 kV(Um = 1,2 kV) and 3 kV (Um = 3,6 kV) - Edition 3.1; Consolidated Reprint

    IEC 60826 Design criteria of overhead transmission lines - Third EditionIEC 60840 Power cables with extruded insulation and their accessories for rated voltages

    above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) Test methods andrequirements - Third Edition

    IEC 60853-3 Calculation of the Cyclic and Emergency Current Rating of Cables Part 3:Cyclic Rating Factor for Cables of all Voltages, with Partial Drying of the Soil -First Edition

    IEC 60865-1 Short-circuit currents - Calculation of effects - Part 1: Definitions andcalculation methods - Second Edition; Corrigendum 1: 03/1995

    IEC 60885-1 Electrical test methods for electric cables Part 1: Electrical tests for cables,cords and wires for voltages up to and including 450/750 V - First Edition

  • IEC 60885-3 Electrical Test Methods for Electric Cables Part 3: Test Methods for PartialDischarge Measurements on Lengths of Extruded Power Cable First Edition -First Edition

    IEC 60889 Hard-Drawn Aluminum Wire for Overhead Line Conductors - First EditionIEC 60949 AMD 1 AMENDMENT 1 Calculation of thermally permissible short-circuit currents,

    taking into account non-adiabatic heating effects - Edition 1.0IEC 60986 Short-circuit temperature limits of electric cables with rated voltages from 6

    kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV) - Edition 2.1; ConsolidatedReprint

    IEC 61089 Round Wire Concentric Lay Overhead Electrical Stranded Conductors - FirstEdition; Amendment 1-1997; Replaces 60207 thru 60210: 1966

    IEC 62067 Power cables with extruded insulation and their accessories for rated voltagesabove 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV) Testmethods and requirements - Edition 1.1 * Consolidated Reprint

    IEC GUIDE 104 Preparation of Safety Publications and the Use of Basic Safety Publicationsand Group Safety Publications - Third Edition

    IEC TR 61597 Overhead Electrical Conductors - Calculation Methods for Stranded BareConductors - Edition 1

    IEC TS 61394 Overhead Lines - Characteristics of Greases for Aluminium, Aluminium Alloyand Steel Bare Conductors - Edition 1.0; Includes Access to AdditionalContent

  • 2. THE BRITISH STANDARD (BS)

    DOCUMENT NO. DOCUMENT NAME

    BS 5099 Electric cables - Voltage levels for spark testingBS 5467 Electrical cables - Thermosetting insulated, armoured cables for voltages of

    600/1 000 V and 1 900/3 300 VBS 6004 Electric cables - PVC insulated, non-armoured cables for voltage up to and

    including 450/750 V, for electric power, lighting and internal wiring.BS 6469-99.1 Insulating and sheathing materials of electric cablesBS6724 Electric cables - Thermosetting insulated, armoured cables for voltages of

    600/1 000 V and 1 900/3 300 V, having low emission of smoke andcorrosive gases when affected by fire

    BS 7211 Electric cables - Thermosetting, insulated, non-armoured cables for voltagesup to and including 450/750V, for electric power, lighting and internalwiring, and having low emission of smoke and corrosive gases when affectedby fire

    BS 7655 Specification for Insulating and sheathing materials for cables.Section 6. General application thermoplastic types.

    BS 7655 Specification for Insulating and sheathing materials for cables. Section 1.2General 90C application

    BS 7655-0 Specification for insulating and sheathing materials for cablesBS 7655-1.3 Specification for Insulating and sheathing materials for cables.BS 7655-4.2 Specification for Insulating and sheathing materials for cables - Part 4. PVC

    sheathing compounds - Section 4.2: General applicationBS 7835 Electric cables - Armoured cables with thermosetting insulation for rated

    voltage from 3.8/6.6kv to 19/33kv having low emission of smoke andcorrosive gases when affected by fire - requirements and test methods.

    BS 7846 Electric cables - Thermosetting insulated, armoured, fire resistance cables ofrated 600/1 000 V, having low emission of smoke and corrosive gases whenaffected by fire - Specification.

    BS 7870-4.10 LV and MV polymeric insulated cables for use by distribution and generationutilities - Part 4: Specification for distribution cables with extruded insulationfor rated voltage of 11kV and 33 kV - Section 4.10: Single -core 11kV and33kV cables.

    BS 7870-4.11 LV and MV polymeric insulated cables for use by distribution and generationutilities - Part 4: Specification for distribution cables with extruded insulationfor rated voltage of 11kV and 33 kV - Section 4.11: Single -core 33kV leadsheathed cables.

    BS 7870-4.20 LV and MV polymeric insulated cables for use by distribution and generationutilities - Part 4: Specification for distribution cables with extruded insulationfor rated voltage of 11kV and 33 kV - Section 4.20: Three -core 11kV cables.

    BS 7889 Electric cables - Thermosetting insulated, unarmored cables for a voltage of600/1 000 V

    BS 7970 Electric cables - metallic wire foil sheat constructions of power cables havingXLPE insulation for rated voltage from 66 kv (Um = 72.5 kv) to132 kv (Um = 145 kv)

  • BS EN 10257-1: Zinc or Zinc alloy coated non-alloy steel wire for armoring either powercables or telecommunication cables

    BS EN 50267-2-1 Common test methods for cables under fire conditions - Test on gasesevolved during combustion of materials from cables.

    EN50525-2-31 Electric cables -Low voltage energy cables of rated voltages up to and including 450/750 V(U0/U) -Part 2-31: Cables for general applications -Single core non-sheathed cables with thermoplastic PVC insulation

    EN50525-3-41 Electric cables -Low voltage energy cables of rated voltages up to and including 450/750 V(U0/U) -Part 3-41: Cables with special fire performance -Single core non-sheathed cables with halogen-free cross linked insulationand low emission of smoke

    BS EN 50363-3 Insulating, sheathing and covering materials for low voltage energy cables -Part 3: PVC insulating compounds

    BS EN 50363-4-1 Insulating, sheathing and covering materials for low voltage energy cablesBS EN 50363-5 Insulating, sheathing and covering materials for low voltage energy cablesBS EN 60230 Impulse test on cables and their accessoriesBS EN 60332-1-2 Test on electric and optical fiber cables under fire conditions - Part 1-2: Test

    for vertical flame propagation for a single insulated wire or cable - Procedurefor 1kW pre-mixed flame

    BS EN 60332-2-2 Test on electric and optical fiber cables under fire conditions - Part 1-2: Testfor vertical flame propagation for a single small insulated wire or cable -Procedure for diffusion flame

    BS EN 60332-3-24 Test on electric and optical fiber cables under fire conditionsBS EN 60811-1-1 Insulating and sheathing materials of electric and optical cables - Common

    Test methods - Part 1-1: General application - Measurement of thinness andoverall dimensions - Test for determining the mechanical properties

    BS EN 60811-1-2 Common test methods for insulating and sheathing materials of electric andoptical cables

    BS EN 60811-1-3 Insulating and sheathing materials of electric and optical cables - CommonTest methods

    BS EN 60885-3 Electrical test methods for electric cablesBS EN 61034-2 Measurement of smoke density of cables burning under defined condition -

    Part 2: Test procedure and requirements.BS EN 62230 Electric cables - Spark-test methodBS EN ISO 14001 Environmental management systems - Requirements with guidance for useBS EN ISO 6892-1 Metallic materials - Tensile testing Part 1: Method of test at ambient

    temperature.BS EN ISO 9001 Quality management system - RequirementsBS OSHAS 18001 Occupational health and safety management system - requirementsBS 7655: Section 6.1 Specification for Insulating and sheathing materials for cables

  • SELECTION OF CABLES:It is essential to consider the specific system and installation conditions to be able to select the rightcable.The following criteria should be taken into account to choose the suitable cable.

    1. Cable Laying:Depending on the nature of the cable system (fixed or mobile) a rigid or flexible cable should beselected. The appropriate protection of a cable will be determined taking into account themechanical stress and presence of chemical, oils or hydrocarbons.

    2. Ambient and ground TemperatureThe quality of the material used to manufacture a cable shall be determined according to themaximum and minimum temperatures to which the cable will be submitted.

    3. Nature of ConductorsCopper or aluminum conductors can be used.

    For equal current rating aluminum cross-section= 1.28 copper cross-section

    For equal ohmic resistance aluminum cross-section= 1.65 copper cross-section

    For copper, sector shaped conductors are availableOn request from 70 mm2 and above

    4. Maximum operating voltage.5. Insulation level.6. Load to be carried.7. Frequency.8. Magnitude and duration of possible overload Emergency current.9. Magnitude and duration of short-circuit current for conductor and screen.10.Length of line.11.Voltage drop.12.Chemical and physical properties of soil.13.Min. and Max. ambient air temperatures and soil temperature.14.Specification and requirements to be follow.

  • MetalCopper (annealed)

    Relative ConductivityCopper 100%

    100

    Electrical Resistivityat 20 C ohm. m (10-8)

    1.7241

    Temperature Coefficient ofResistance per C

    0.00393Copper (hard drawn) 97 1.777 0.00393Tinned copper 95 - 97 1.741 - 1.814 0.00393Aluminium 61 2.8264 0.00403

    VOLTAGE:The VOLTAGE Is the electric potential difference between two points, or the difference in electricpotential energy of a unit charge transported between two points, The standard rate voltage aredefined by three values Uo / U (Um), where :Uo = rated rms power frequency voltage, core to screen or sheath.U = rated rms power frequency voltage, core to core.Um = max. rms power frequency voltage, core to core.

    Uo / U(kV)

    0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 38/66 76/132 127/220Um(kV)

    1.2 3.6 7.2 12 17.5 24 36 72.5 145 245Cable design for 6/10, 12/20 and 18/30 kV is applicable for 6.35/11, 12.7/22 and 19/33 kV respectively.

    METALS USED FOR CABLES:

    Electrical Properties:

    MetalRelative

    ConductivityElectrical Resistivityat 20 C ohm. m

    (10-8)TemperatureCoefficient of

    Resistance per CCopper (annealed) 100 1.7241 0.00393Copper (hard drawn) 97 1.777 0.00393Tin copper 95 - 97 1.741 - 1.814 0.00393Aluminum 61 2.8264 0.00403Lead 8 21.4 0.0040

    Physical Properties:

    Property Unit Copper Aluminum LeadDensity at 20 C kg / m3 8890.00 2703.00 11340.00Coeff. thermal expansion Per C x 10-6 17.00 23.00 29.00Melting point C 1083.00 659.00 327.00Thermal conductivity W/cm C 3.80 2.40 0.34Ultimate tensile strength Mn/m2 225.00 70-90 -

  • EELLEECCTTRRIICCAALL CCAALLCCUULLAATTIIOONN GGUUIIDDEE1. NOMINAL VOLTAGE

    The Nominal voltage is to be expressed with twovalues of alternative current Uo/U in V (volt)Uo/U : Phase to earth voltageUo : Voltage between conductor and earthU : Voltage between phases (conductors)

    2. RESISTANCEThe Values of conductor DC resistance aredependent on temperature as given by :Rt=R20x[l+20(t-20)] /kmRt : conductor DC resistance at t C /kmR20 : conductor DC resistance at 20 C /kmt : operating temperature C : resistance temperature coefficient

    = 0.00393 for copper= 0.00403 for aluminum

    Generally DC resistance is based on IEC 60228To calculate AC resistance of the conductorat the operating temperature as the following:RAC = Rt x[ 1+ ys + yp ]ys : skin effect factoryp : proximity effectGenerally AC resistance is based on IEC 60287

    3. CAPACITANCE

    F/km

    C : Operating capacitance F/kmD : Diameter over insulation mmd : Conductor diameter mmr :Relative permittivity of insulation material

    r = 4.8 for PVCr = 2.3 for XLPE

    4. INDUCTANCEL=K+0.2 ln ( 2s/d) mH/kmL : Inductance mH/kmK :Constant depends on number of wires of conductord: Conductor diameterS : Axial spacing between cables (Trefoil formation )S : 1.26 x axial spacing between cables ( Flat formation)

    5. REACTANCEThe inductive reactance per phase of a cable may beobtained by the formula:X = 2 f L x 10-3 /kmX: Reactance /kmf : Frequency HzL : Inductance mH/km

    6. IMPEDANCE

    Z = /kmZ :Phase impedance of cable /kmRac : AC resistance at operating temperature /kmX : Reactance /km

    7. INSULATION RESISTANCE

    R =

    R : Insulation resistance at 20 C M.kmD : Insulated conductor diameter mmd : Conductor diameter mm

    1000 * LN (D/d)2 *

    EELLEECCTTRRIICCAALL CCAALLCCUULLAATTIIOONN GGUUIIDDEE1. NOMINAL VOLTAGE

    The Nominal voltage is to be expressed with twovalues of alternative current Uo/U in V (volt)Uo/U : Phase to earth voltageUo : Voltage between conductor and earthU : Voltage between phases (conductors)

    2. RESISTANCEThe Values of conductor DC resistance aredependent on temperature as given by :Rt=R20x[l+20(t-20)] /kmRt : conductor DC resistance at t C /kmR20 : conductor DC resistance at 20 C /kmt : operating temperature C : resistance temperature coefficient

    = 0.00393 for copper= 0.00403 for aluminum

    Generally DC resistance is based on IEC 60228To calculate AC resistance of the conductorat the operating temperature as the following:RAC = Rt x[ 1+ ys + yp ]ys : skin effect factoryp : proximity effectGenerally AC resistance is based on IEC 60287

    3. CAPACITANCE

    F/km

    C : Operating capacitance F/kmD : Diameter over insulation mmd : Conductor diameter mmr :Relative permittivity of insulation material

    r = 4.8 for PVCr = 2.3 for XLPE

    4. INDUCTANCEL=K+0.2 ln ( 2s/d) mH/kmL : Inductance mH/kmK :Constant depends on number of wires of conductord: Conductor diameterS : Axial spacing between cables (Trefoil formation )S : 1.26 x axial spacing between cables ( Flat formation)

    5. REACTANCEThe inductive reactance per phase of a cable may beobtained by the formula:X = 2 f L x 10-3 /kmX: Reactance /kmf : Frequency HzL : Inductance mH/km

    6. IMPEDANCE

    Z = /kmZ :Phase impedance of cable /kmRac : AC resistance at operating temperature /kmX : Reactance /km

    7. INSULATION RESISTANCE

    R =

    R : Insulation resistance at 20 C M.kmD : Insulated conductor diameter mmd : Conductor diameter mm

    1000 * LN (D/d)2 *

    22 XR ac

    EELLEECCTTRRIICCAALL CCAALLCCUULLAATTIIOONN GGUUIIDDEE1. NOMINAL VOLTAGE

    The Nominal voltage is to be expressed with twovalues of alternative current Uo/U in V (volt)Uo/U : Phase to earth voltageUo : Voltage between conductor and earthU : Voltage between phases (conductors)

    2. RESISTANCEThe Values of conductor DC resistance aredependent on temperature as given by :Rt=R20x[l+20(t-20)] /kmRt : conductor DC resistance at t C /kmR20 : conductor DC resistance at 20 C /kmt : operating temperature C : resistance temperature coefficient

    = 0.00393 for copper= 0.00403 for aluminum

    Generally DC resistance is based on IEC 60228To calculate AC resistance of the conductorat the operating temperature as the following:RAC = Rt x[ 1+ ys + yp ]ys : skin effect factoryp : proximity effectGenerally AC resistance is based on IEC 60287

    3. CAPACITANCE

    F/km

    C : Operating capacitance F/kmD : Diameter over insulation mmd : Conductor diameter mmr :Relative permittivity of insulation material

    r = 4.8 for PVCr = 2.3 for XLPE

    4. INDUCTANCEL=K+0.2 ln ( 2s/d) mH/kmL : Inductance mH/kmK :Constant depends on number of wires of conductord: Conductor diameterS : Axial spacing between cables (Trefoil formation )S : 1.26 x axial spacing between cables ( Flat formation)

    5. REACTANCEThe inductive reactance per phase of a cable may beobtained by the formula:X = 2 f L x 10-3 /kmX: Reactance /kmf : Frequency HzL : Inductance mH/km

    6. IMPEDANCE

    Z = /kmZ :Phase impedance of cable /kmRac : AC resistance at operating temperature /kmX : Reactance /km

    7. INSULATION RESISTANCE

    R =

    R : Insulation resistance at 20 C M.kmD : Insulated conductor diameter mmd : Conductor diameter mm

    1000 * LN (D/d)2 *

  • 8.CHARGING CURRENT

    I = Uo x 2 f x C x 10-6I : Charging current A/kmUo : voltage between phase and earth VC : Capacitance to neutral F/km

    9. DIELECTRIC LOSSES

    D = 2 f C 2Uo tan 10-6 watt/km/phaseD : Dielectric losses watt/km/phaseUo : Voltage between phase and earth VC : Capacitance to neutral F/kmtan : Dielectric power factor

    10. CABLE SHORT CIRCUIT CAPACITY

    ISC(t) = ISC(1) / t kAISC(t): Short circuit for t second kAISC(1): Short circuit for 1 second kA

    Data about short circuit are tabulated from table 9 to table11

    11. VOLTAGE DROP

    When the current flows in conductor, there is a voltagedrop between the ends of the conductor. For low voltagecable network of normal operation.

    We recommend voltage drops not to exceed: 3 % for lighting wire systems 5 % for driving force wire systems 10 % on starting time for motors

    To calculate voltage drop as the following:

    1. In DC =2. For single phase circuit AC: = ( + )3. For three phase circuit AC: = ( + )

    u : Voltage drop VRc : conductor resistance in D.C. at operating

    temperature (/km)Ra : conductor resistance in A.C. at operating

    temperature (/km)L : core inductance (H/km) : pulsation equal to 2 f (314 for f= 50 Hz)I : Load current AX : Reactance /km : Length kmcos : Power factor

    - Relation between cos and sin as following: 1.0 0.9 0.8 0.71 0.6 0.5 0.0 0.44 0.6 0.71 0.8 0.87

  • CCUURRRREENNTT RRAATTIINNGG AASSSSUUMMPPTTIIOONNSS::

    THE ELECTRIC CURRENT: is a flow of electric charge. In electric circuits this charge is often carriedby moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions andelectrons such as in a plasma.

    The calculation of the current ratings, Current rating equations(100% load factor) andcalculation of losses are based on IEC 60287 series , and the values of Current ratings forunderground applications (In Duct or Direct Buried) are derived from the latest issue of ERAReport Current Rating Standards 69.30 Part V. and the values of current ratings are verified withthe tabulated value in IEC 60364-5-52.The Current Carry Capacity calculated based on one circuit installed thermally isolated from othercircuits or any other heat source.Ambient Air Temperature : 30 CAmbient Ground Temperature : 20C Depthof laying in ground : 0.70 mSoil Thermal Resistivity :2.5 K.m/W

    For other installation conditions or any value of different air/ ground temperature, depth of laying,different soil thermal resistivity the customer is divided to multiply the tabulated current rating by thede-rating factor values as in tables 1 to 8.

    CCUURRRREENNTT RRAATTIINNGG AASSSSUUMMPPTTIIOONNSS::

    THE ELECTRIC CURRENT: is a flow of electric charge. In electric circuits this charge is often carriedby moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions andelectrons such as in a plasma.

    The calculation of the current ratings, Current rating equations(100% load factor) andcalculation of losses are based on IEC 60287 series , and the values of Current ratings forunderground applications (In Duct or Direct Buried) are derived from the latest issue of ERAReport Current Rating Standards 69.30 Part V. and the values of current ratings are verified withthe tabulated value in IEC 60364-5-52.The Current Carry Capacity calculated based on one circuit installed thermally isolated from othercircuits or any other heat source.Ambient Air Temperature : 30 CAmbient Ground Temperature : 20C Depthof laying in ground : 0.70 mSoil Thermal Resistivity :2.5 K.m/W

    For other installation conditions or any value of different air/ ground temperature, depth of laying,different soil thermal resistivity the customer is divided to multiply the tabulated current rating by thede-rating factor values as in tables 1 to 8.

    CCUURRRREENNTT RRAATTIINNGG AASSSSUUMMPPTTIIOONNSS::

    THE ELECTRIC CURRENT: is a flow of electric charge. In electric circuits this charge is often carriedby moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions andelectrons such as in a plasma.

    The calculation of the current ratings, Current rating equations(100% load factor) andcalculation of losses are based on IEC 60287 series , and the values of Current ratings forunderground applications (In Duct or Direct Buried) are derived from the latest issue of ERAReport Current Rating Standards 69.30 Part V. and the values of current ratings are verified withthe tabulated value in IEC 60364-5-52.The Current Carry Capacity calculated based on one circuit installed thermally isolated from othercircuits or any other heat source.Ambient Air Temperature : 30 CAmbient Ground Temperature : 20C Depthof laying in ground : 0.70 mSoil Thermal Resistivity :2.5 K.m/W

    For other installation conditions or any value of different air/ ground temperature, depth of laying,different soil thermal resistivity the customer is divided to multiply the tabulated current rating by thede-rating factor values as in tables 1 to 8.

  • DDEERRAATTIINNGG FFAACCTTOORRSS1. INSTALLATION CONDITIONS FOR CABLES IN AIR

    Table 1: Rating factors for ambient air temperatures other than 30 C to be applied to thecurrent-carrying capacities for cables in the air:

    Ambienttemperature

    a CInsulation

    PVC XLPEandEPR

    Mineral a

    PVC coveredor bare andexposed totouch 70 C

    Bare notexposed totouch 105C

    10 1,22 1,15 1,26 1,1415 1,17 1,12 1,20 1,1120 1,12 1,08 1,14 1,0725 1,06 1,04 1,07 1,0430 1,00 1,00 1,00 1,0035 0,94 0,96 0,93 0,9640 0,87 0,91 0,85 0,9245 0,79 0,87 0,78 0,8850 0,71 0,82 0,67 0,8455 0,61 0,76 0,57 0,8060 0,50 0,71 0,45 0,7565 0,65 0,7070 0,58 0,6575 0,50 0,6080 0,41 0,5485 0,4790 0,4095 0,32

    a For higher ambient temperatures, consult the manufacturer.

  • 2. INSTALLATION CONDITIONS FOR DIRECT BURIAL CABLESFor a cable installed direct buried, the following tables will be used to calculate the current ratesbased on the actual soil thermal resistivity, Ground ambient temperature and the Depth of Laying.

    Table 2: Rating factors for ambient ground temperatures other than 20 C to be applied to thecurrent-carrying capacities for cables in ducts in the ground:

    Groundtemperature

    CInsulation

    PVC XLPE and EPR10 1,10 1,0715 1,05 1,0420 1,00 1,0025 0,95 0,9630 0,89 0,9335 0,84 0,8940 0,77 0,8545 0,71 0,8050 0,63 0,7655 0,55 0,7160 0,45 0,6565 0,6070 0,5375 0,4680 0,38

    Table 3: Rating factors for cables buried direct in the ground or in buried ducts for soil thermalresistivities other than 2,5 Km/W to be applied to the current-carrying capacities for referencemethod D:

    Thermal resistivity, Km/W 0,5 0,7 1 1,5 2 2,5 3Correction factor for cables inburied ducts

    1,28

    1,20

    1,18

    1,1 1,05

    1 0,96Correction factor for direct

    buried cabl es1,88

    1,62

    1,5 1,28

    1,12

    1 0,90NOTE 1 The correction factors given have been averaged over the range of conductor sizes and types of

    installation included in Tables B.52.2 to B.52.5. The overall accuracy of correction factors is within 5 %.NOTE 2 The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in theground the correction f actors for thermal resistivities less than 2, 5 Km/W will be higher. W here more precisevalues are required they may be calculated by methods given in the IEC 60287 series.NOTE 3 The correction factors are applicable to ducts buried at depths of up to 0,8 m.NOTE 4 It is assumed that the soil properties are uniform. No allowance had been made for the possibilityy ofmoisture migration which can lead to a region of high thermal resistivity around the cable. If partial drying out ofthe soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287series.

  • 3. INSTALLATION CONDITIONS FOR CIRCUIT GROUPSTable 4: Rating factors for one circuit or one multi-core cable or for a group of more than onecircuit:

    To beused withcurrent-carryingcapacities,reference

    Arrangement Number of circuits or multi-core cables

    Item (cables

    touching)1 2 3 4 5 6 7 8 9 12 16 20

    1 Bunched in air,on a surface,embedded orenclosed

    1,00 0,80 0,70 0,65 0,60 0,57 0,54 0,52 0,50 0,45 0,41 0,38 B.52.2to B.52.13Methods A

    to F

    2 Single layer onwall, floor orunperforatedcable traysystems

    1,00 0,85 0,79 0,75 0,73 0,72 0,72 0,71 0,70

    B.52.2 toB.52.7

    3 Single layerfixed directlyunder awooden ceiling

    0,95 0,81 0,72 0,68 0,66 0,64 0,63 0,62 0,61 No furtherreduction factor formore than nine

    circuits or multicorecables

    Method C

    4 Single layer ona perforatedhorizontal orvertical cabletray systems

    1,00 0,88 0,82 0,77 0,75 0,73 0,73 0,72 0,72

    B.52.8to B.52.13

    5 Single layer oncable laddersystems orcleats etc.,

    1,00 0,87 0,82 0,80 0,80 0,79 0,79 0,78 0,78 Methods Eand F

    NOTE 1 These factors are applicable to uniform groups of cables, equally loaded.NOTE 2 W here horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction factor need be applied.NOTE 3 The same factors are applied to:

    groups of two or three single-core cables; multi-core cables.

    NOTE 4 If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and thecorresponding f actor is applied to the tables for two loaded conductors for the two-core cables, and to the tables f or three loadedconductors for the three-core cables.NOTE 5 If a group consists of n single-core cables it m ay either be considered as n/2 circuits of two loaded conductors or n/ 3 circuits ofthree loaded conductors.

  • a a

    Table 5: Rating factors for more than one circuit, cables laid directly in the ground Single-core ormulti-core cables:

    Numbe

    r of

    circuits

    Cable to cable clearanceaNil One

    cablediameter(cablestouching)

    0,125 m 0,25 m 0,5 m

    2 0,75 0,80 0,85 0,90 0,903 0,65 0,70 0,75 0,80 0,854 0,60 0,60 0,70 0,75 0,805 0,55 0,55 0,65 0,70 0,806 0,50 0,55 0,60 0,70 0,807 0,45 0,51 0,59 0,67 0,768 0,43 0,48 0,57 0,65 0,759 0,41 0,46 0,55 0,63 0,7412 0,36 0,42 0,51 0,59 0,7116 0,32 0,38 0,47 0,56 0,3820 0,29 0,35 0,44 0,53 0,66

    a Multi-core cables

    a Single-core cables

    NOTE 1 Values given apply to an installation depth of 0,7 m and a soil thermalresistivity of 2,5 Km /W . They are average values for the range of cable sizes andtypes quoted for Tables B.52.2 to B.52.5. The process of averaging, together withrounding off, can result in some cases in errors up to 10 %. (W here m ore precisevalues are required they may be calculated by methods given in IEC 60287-2-1.)NOTE 2 In case of a thermal resistivity lower than 2, 5 Km /W the corrections factorscan, in general, be increased and can be calculated by the methods given in IEC60287-2-1.NOTE 3 If a circuit consists of m parallel conductors per phase, then fordetermining the reduction factor, this circuit should be considered as m circuits.

  • Table 6: Rating factors for more than one circuit, cables laid in ducts in the ground:

    A) Multi-core cables in single-w a y ductsNumber

    of cablesDuct to duct clearance a

    Nil(ducts

    touching)0,25 m 0,5 m 1,0 m

    2 0,85 0,90 0,95 0,953 0,75 0,85 0,90 0,954 0,70 0,80 0,85 0,905 0,65 0,80 0,85 0,906 0,60 0,80 0,80 0,907 0,57 0,76 0,80 0,888 0,54 0,74 0,78 0,889 0,52 0,73 0,77 0,8710 0,49 0,72 0,76 0,8611 0,47 0,70 0,75 0,8612 0,45 0,69 0,74 0,8513 0,44 0,68 0,73 0,8514 0,42 0,68 0,72 0,8415 0,41 0,67 0,72 0,8416 0,39 0,66 0,71 0,8317 0,38 0,65 0,70 0,8318 0,37 0,65 0,70 0,8319 0,35 0,64 0,69 0,8220 0,34 0,63 0,68 0,82

  • B) Single-core cables in non-magnetic single-w a y ductsNumber ofsingle- corecircuits oftwo or threecables

    Duct to duct clearance b

    Nil(ducts

    touching)0,25 m 0,5 m 1,0 m

    2 0,80 0,90 0,90 0,953 0,70 0,80 0,85 0,904 0,65 0,75 0,80 0,905 0,60 0,70 0,80 0,906 0,60 0,70 0,80 0,907 0,53 0,66 0,76 0,878 0,50 0,63 0,74 0,879 0,47 0,61 0,73 0,8610 0,45 0,59 0,72 0,8511 0,43 0,57 0,70 0,8512 0,41 0,56 0,69 0,8413 0,39 0,54 0,68 0,8414 0,37 0,53 0,68 0,8315 0,35 0,52 0,67 0,8316 0,34 0,51 0,66 0,8317 0,33 0,50 0,65 0,8218 0,31 0,49 0,65 0,8219 0,30 0,48 0,64 0,8220 0,29 0,47 0,63 0,81

    a Multi-c ore cables

    b Single-core cables

    NOTE 1 Values given apply t o an installation depth of 0,7 m and a soil t herm alresistivity of 2,5 Km/W . They are average values for the range of cable sizes andtypes quoted for Tables B.52.2 to B.52.5. The process of averaging, togetherwith rounding off, can result in some cases in errors up to 10 %. W here more precise values are required they may be calculated by methods given in the IEC60287series.NOTE 2 In case of a thermal resistivity lower than 2, 5 Km/W the corrections factorscan, in general, be increased and can be calculated by the methods given in IEC60287-2-1.NOTE 3 If a circuit consists of n parallel conductors per phase, then for determiningthe reduction factor this circuit shall be considered as n circuits

  • Table 7: Rating factors for group of more than one multi-core cable to be applied to referencecurrent-carrying capacities for multi-core cables in free air:

    Method of installation in Table A.52.3IEC 60364-5-52

    Number oftraysor

    ladders

    Number of cables per tray or ladder

    1 2 3 4 6 9

    Perforated cabletraysystems(note 3)

    31

    Touching 1236

    1,001,001,001,00

    0,880,870,860,84

    0,820,800,790,77

    0,790,770,760,73

    0,760,730,710,68

    0,730,680,660,64

    Spaced 123

    1,001,001,00

    1,000,990,98

    0,980,960,95

    0,950,920,91

    0,910,870,85

    Verticalperforatedcable traysystems(note4)

    31

    Touching12

    1,001,00

    0,880,88

    0,820,81

    0,780,76

    0,730,71

    0,720,70

    Spaced

    12

    1,001,00

    0,910,91

    0,890,88

    0,880,87

    0,870,85

    Unperforat edcable traysystems

    31

    Touching1236

    0,970,970,970,97

    0,840,830,820,81

    0,780,760,750,73

    0,750,720,710,69

    0,710,680,660,63

    0,680,630,610,58

    Cableladdersystems,cleats, etc.

    (note3)

    323334

    Touching1236

    1,001,001,001,00

    0,870,860,850,84

    0,820,800,790,77

    0,800,780,760,73

    0,790,760,730,68

    0,780,730,700,64

  • Spaced123

    1,001,001,00

    1,000,990,98

    1,000,980,97

    1,000,970,96

    1,000,960,93

    NOTE 1 Values given are averages for the cable types and range of conductor sizes considered in Tables A.52.8 toA.52.13. The spread of values is generally less than 5 %.NOTE 2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed inmore than one layer touching each other. Values for such installations may be significantly lower and has to bedetermined by an appropriate method.NOTE 3 Values are given for vertical spacing between cable t rays of 300 mm and at least 20 mm between cabletrays and wall. For closer spacing the factors should be reduced.NOTE 4 Values are given for horizontal spacing between cable t rays of 225 mm with cable trays mounted back t oback. For closer spacing the factors should be reduced.

    Table 8: Rating factors for groups of one or more circuits of single-core cables to be applied toreference current-carrying capacity for one circuit of single- core cables in free air

    Method of installation in TableA.52.3 IEC 60364-5-52

    Numberof traysorladders

    Number of three-phase circuits per trayor ladder

    Use as amultiplierto current-carryingcapacity

    for1 2 3

    Perforated cable

    traysystems

    (note 3)

    31

    Touching

    123

    0,980,960,95

    0,910,870,85

    0,870,810,78

    Three cablesinhorizontalformation

    Verticalperforated cable

    traysystems(note4)

    31

    Touching

    12

    0,960,95

    0,860,84

    Three cablesin verticalformation

    Cableladdersystems,cleats, etc.(note 3)

    323334

    Touching

    123

    1,000,980,97

    0,970,930,90

    0,960,890,86

    Three cablesinhorizontal

    Touching

  • Perforated cable

    traysystems

    (note 3)31

    123

    1,000,970,96

    0,980,930,92

    0,960,890,86

    Three cablesin trefoilformation

    Verticalperforated cable

    traysystems(note4)

    31

    Spaced

    12

    1,001,00

    0,910,90

    0,890,86

    Cableladdersystems,cleats, etc.(note 3)

    323334

    123

    1,000,970,96

    1,000,950,94

    1,000,930,90

    NOTE 1 Values given are averages for the cable types and range of conductor sizes considered in Table B.52.8to B.52.13. The spread of values is generally less than 5 %.NOTE 2 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not applywhen cables are installed in more than one layer touching each other. Values f or such installations may besignificantly lower and should be determined by an appropriate method.NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cabletrays and wall. For closer spacing the factors should be reduced.NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted backto back. For closer spacing the factors should be reduced.NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductorsshould be considered as a circuit for the purpose of this table.NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor this circuitshould be considered as m circuits.

  • SSHHOORRTT CCIIRRCCUUIITT RRAATTIINNGG CCOONNDDUUCCTTOORRSSThe permissible short-circuit currents as presented in figures 1 to 6 are calculated in accordance withIEC 60724:2008.The calculation method neglects heat loss and is accurate enough for the majority of practicalcases. Any error is on the safe side. However, caution should be exercised when using large sizeconductors and an installation radius less than 8 x cable diameter where high deforming forcesmay occur. Where such conditions cannot be avoided, it is recommended to reduce the shortcircuit rating by 15% or contact SCC technical department.

    The following formulae have been derived from 60724:2008Figure 1

    Figure 2

    Figure 3

    Figure 4

    Figure 5

    Figure 6

    I : Short-circuit current (kA)k : Duration of short-circuit current t (sec.)S : Cross-sectional area of conductor (mm2)

    Maximum Short circuit temperature for cable components:

    Material Item Temp. C

    Insulation PVC insulation140 For C.S.A.

  • PVC (based on 70C type TI-1 or 90C type TI-3) cables copper and aluminumconductor:

    Short Circuit Ratings for 1 second in k AmpConductor

    SizeCopper Conductor Aluminum Conductor

    10 1.2 0.8616 1.8 1.125 2.85 1.835 3.55 2.5550 5 3.470 6.9 4.995 10.9 6.8120 11.8 8.5150 15.3 11185 18.7 13240 23.6 16.5300 30.1 22.5400 41.2 29.5500 51.5 36630 64.9 45.5800 82.4 621000 103 78

  • XLPE cables copper and aluminum conductor:

    Short Circuit Ratings for 1 second in k ampConductor

    SizeCopper Conductor Aluminum Conductor

    10 1.43 0.9416 2.29 1.525 3.58 2.3535 5 3.2950 7.15 4.770 10.01 6.5895 13.59 8.93120 17.16 11.28150 21.45 14.1185 26.46 17.39240 34.32 22.56300 42.9 28.2400 57.2 37.6500 71.5 46.09630 90.09 59.22800 114.4 75.21000 143 94

  • Graph 1 : PVC (90 C type) insulated cables short circuit (Copper Conductor):

    Duration of short circuit in seconds t(sec.)

    Fault

    Curre

    nt Kilo

    ampe

    re-I(kA)

  • Graph 2 : PVC (90 C type) insulated cables short circuit (Aluminum Conductor):

    Duration of short circuit in seconds t(sec.)

    Fault

    Curre

    nt Kilo

    ampe

    re-I(kA)

  • Graph 3 : XLPE (90 C type) insulated cables short circuit (Copper Conductor):

    Duration of short circuit in seconds t(sec.)

    Fault

    Curre

    nt Kilo

    ampe

    re-I(kA)

  • Graph 4 : XLPE (90 C type) insulated cables short circuit (Aluminum Conductor)

    Duration of short circuit in seconds t(sec.)

    Fault

    Curre

    nt Kilo

    ampe

    re-I(kA)

  • IINNSSTTAALLLLAATTIIOONN RREECCOOMMMMEENNDDAATTIIOONNSS

    Instructions for transport, handling, storage of drums and laying of the cables.

    The cables, whether they are armoured or unarmoured, are manufactured with high quality materialsallowing long storage, handling, transport and unreeling subject to the following recommendations.Before acceptance of a shipment, all reels must be inspected. Any sign of damage should be noticedto the carrier (broken flanges, damaged wrapping or or lagging, interlocked flanges, broken reels)

    I. Transport & Handling:The wooden drums must be always carried vertically. They must be fixed and properly chocked withcare on the vehicle, on the wagon and on the ship, in order to avoid any exterior damages.

    Correct Incorrect

    The unloading and the different handling will be done carefully with liftingequipments.

    In case of handling with a crane, an axle is used in crossing the drum centre, lifted from both ends bytwo slings. It must have length equal, at least, to the width of the drum. It prevents the lifting cable orchain from pressing against the reel flanges.

    Correct Incorrect

    In case of handling with a forklift truck, the drum is laid vertically with care on the forks.

    Correct Incorrect

  • II. Rolling directionsWhen a reel is rolled from one point to another, it must be rolled only in the direction shown byarrows as printed on the reel.

    Correct Incorrect

    III. StorageCables can be stored, with site temperature limits: -15 + 60 degrees celcius. For Outdoor location themaximum relative humidity is 90% at all temperatures. The cables drums must be appropriatelywedged, transported and stored in a vertical position (never laid on flange) on a flat, dry and solidground that is not liable to settlement.They must be protected to avoid any mechanical risk and exterior shocks.

    The original wooden lags have to be kept until the cable unreeling to ensure a good protection of thecable. The both ends of the cable (inner & outer ends) have to be watertight in order to avoidpenetration of water or humidity inside the cable. Thermo retractable polyethylene caps must be fixedon both ends.

    IV. Loading, Unloading and Movement of Cable Drums:Lifting, loading & unloading of cable drums should be performed using slings fitted to shafts insertedthrough the cable drum hubs. Spreader bars shall be used where required to avoid pressure on thedrum flanges.If Forklifts are used, both cable drum flanges must sit on the forks of the fork liftCable drums may only be moved short distances by Drum rolling and drums must always be rolledin the direction as indicated on the drum flanges.

    V. Ultraviolet ProtectionCable drums with cable that is not UV resistant shall at times be covered to protect the cable fromUV damage.

    VI. Laying of the cables:

    Laying temperature:Installation shall be postponed if the temperature is lower than- 5 degrees celcius. Below this temp.cables shall be stored in a room where temp. is higher than 10 degrees celcius at least 24hoursbefore unreeling. Cables shall be unreeled as soon as they are removed from the room and the usualbending radius should be increased as possible.

  • Pulling strength:The pulling strengths applied directly to the copper or aluminum cores of the cables should notexceed:- 5daN/mm2 of cross section for copper conductors-3daN/mm2 of cross section for aluminum conductors.The pulling must be regular without shock and continuously checked by a dynamometer (esp. in caseof using a winch).

    Bending radius:During the unreeling, the bending radius shall be, at least, twice the static bending radius (asspecified in our technical data sheets).

    Cables Unreeling:The drum shall be settled on jacks by using a spindle through the central hole of the drum.The unreeling speed shall be monitored at any moment.The cables must be reeled only in the opposite direction indicated by the arrow printed on theflange of the drum (do not unreel the cable in the same direction of the arrow).

    Correct Incorrect

    Cable Wind direction and end mark shall be indicated on both the flanges. While unreeling, thecables shall not be twisted, waved or buckled.