Inverter Air Source Heat Pump

Monobloc system

Product Data & Installation Manual

AXAI-06M & AXAI-09M

AXAI-12M & AXAI-15M

TABLE OF CONTENT

Page 2: Inverter Air Source Heat Pump

INSTRUCTIONS ………………………………………………………………………………………………………………………………1

This manual ……………………………………………………………………………………………………………………………………1

Items inside product box …………………………………………………………………………………………………………….…2

Tools needed to install these products………………………………………………………………………………………..…3

SAFETY PRECAUTIONS ………………………………………………………………………………………………………………….3

Warning ………………………………………………………………………………………………………………………………………..4

Caution ……………………………………………………………………………………………………………………………………….…5

Materials needed to install the heat pump………………………………………………………………………………….…6

Cycle diagram…………………………………………………………………………………………………………………………………6

OVERVIEW OF THE UNIT ………………………………………………………………………………………………………….…...7

The unit (External & Internal): AXAI-06M & AXAI-09M …………………….……………………………………………7

The unit (External & Internal): AXAI-12M & AXAI-15M…………………….………………………………………….…8

Wiring Diagram……………………………………………………………………………………………………………………………...9

Electrical Wiring Diagram for the 6&9KW……………………………………………………………………………………...9

Electrical Wiring Diagram for the 12&15KW….……………………………………………………………………….…….10

Field Wiring……………………………………………………………………………………………………………………………………11

WATER PIPE-WORK…………………….……………………………………………………………………………….…................12

Checking the water circuit……………………………………………………………………………………………………………..12

Charging water………………………………………………………………………………………………………………………….……12

Water Flow Rates….……………………………………………………………………………………………………………………….12

INSTALLATION OF THE MAIN UNIT …………………………………………………………………………………………….…13

Precautions for selecting the location…………………………………………………………………………….……………. 13

Installation space……………………………………………………………………………………………………………………………13

Mounting the unit ………………………………………….……………………………………………………………………………...14

SPECIFICATION …………………………………………..……………………………………………………………………………….…16

Page 3: Inverter Air Source Heat Pump

2

READ THIS MANUAL CAREFULLY BEFORE STARTING THE INSTALLATION OF THIS

PRODUCT. DO NOT THROW IT AWAY.

KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.

BEFORE OPERATING THE UNIT, MAKE SURE THE INSTALLATION HAS BEEN

CARRIED OUT CORRECTLY BY A PROFESSIONAL DEALER. IF YOU FEEL

UNSURE ABOUT OPERATION, CONTACT YOUR DEALER FOR ADVICE AND

INFORMATION.

INTRODUCTION

This manual

This manual includes the necessary information about the unit. Please read this manual

carefully before you install the product.

Domestic hot water tank option

An optional domestic hot water tank with integrated electrical booster heater can be

connected to the unit. The domestic hot water tank is available in different sizes.

Items inside product box

Before starting installation, please make sure that all parts are found inside the product

boxes

The Unit Box

Item Image Quantity

AXAI-06M &

AXAI09M

1

Page 4: Inverter Air Source Heat Pump

AXAI-12M &

AXAI15M

1

Page 5: Inverter Air Source Heat Pump

4

The manual

1

Page 6: Inverter Air Source Heat Pump

5

Tools needed to install these products

1. Hammer Drill

2. Sprit Level

3. Pipe Bending equipment for refrigeration pipe

4. Pipe bending equipment for water pipe

5. Brazing torch

6. Flairing tool

7. Tape measure

8. Torque spanners

9. Pipe cutters

10. Socket set with metric sockets

11. Phillips 2 screwdriver

12. Electrical terminal screwdriver

13. Electrical crimping tool

14. Electrical Side cutters

15. Trimming knife

16. Wire strippers

17. Hack saw

18. Masonry drill bits for fixings 7mm and 10mm are recommended

19. Masonry core bit for interconnecting services 75mm recommended

20. Vacuum pump

21. R410a Gauges

22. Torr gauge

23. Hex keys 4mm

24. Adjustable spanner

25. OFN & Regulator

26. PPE ie gloves, glasses and steal toe protectors

SAFETY INSTRUCTIONS

To prevent injury to the user, other people, or property damage, the following instructions

must be followed. Incorrect operation due to ignoring these instructions may cause harm or

damage.

Install the unit only when it complies with local regulations, by-laws and standards. Check

the main voltage and frequency. This unit is only suitable for earthed sockets. An isolation

switch is required for both indoor and outdoor units.

The following safety precautions should always be taken into account:

- Be sure to read the following WARNING before installing the unit.

- Be sure to observe the cautions specified here as they include important items related to

safety.

- After reading these instructions, be sure to keep it together with the manual in a handy

place for future reference.

Page 7: Inverter Air Source Heat Pump

6

• Ensure the units are securely installed.

If the unit is insufficiently secured or installed, the unit could fall causing injury. The minimum

support weight of 20g/mm² of the installation is required. When installing the unit in an

enclosed area or a confined space please consider the room measurements and sufficient

ventilation to prevent the asphyxia caused by the leakage of refrigerant.

• Use the specified electrical wires and attach the wires firmly to the terminal

board (connection in such a way that the stress of the wires is not applied to the

sections).

Incorrect connection and fixing could cause a fire.

• Be sure to use the correct or specified materials for the installation work. The

use of defective parts / materials could cause an injury due to possible fire, electric

shocks, the unit falling etc.

• Perform the installation securely and please refer to the installation

instructions.

Incorrect installation could cause an injury due to possible fire, electric shocks, the unit

falling, leakage of water etc.

• Perform electrical work according to the installation manual and be sure to use

a dedicated section.

If the capacity of the power circuit is insufficient or there is an incomplete electrical circuit, it

could result in a fire or an electric shock.

• The unit must always have an earthed connection.

If the power supply is not earthed, you may not connect the unit.

• Do not attempt move/repair the unit yourself if you are not a LCP installer.

Improper movement or repair on the unit could lead to water leakage, electrical shock,

injury or fire. Have any repairs and/or maintenance only carried out by a recognized

service engineer.

• Do not plug or unplug the power supply during operation

There is a risk of fire or an electric shock

• Do not touch/operate the unit with wet hands

There is a risk of fire or an electric shock

• Do not place a heater or other appliances near the power cable

There is a risk of fire or an electric shock

Be cautious that water could not be poured to the product directly, do not allow

water to run into electric parts

There is a risk of fire or an electric shock

IF THE PRODUCT IS NOT USED FOR LONG PERIODS OF TIME, WE STRONGLY

RECOMMEND NOT TO SWITCH ‘OFF’ THE POWER SUPPLY TO THE PRODUCT.

IF THE POWER IS NOT SUPPLIED, SOME OF THE PRODUCT-PROTECTING

ACTIONS (SUCH AS WATER PUMP ANTI-LOCKING & CRANK CASE HEATER)

WILL NOT BE OPPERATIONAL

Page 8: Inverter Air Source Heat Pump

7

Do not install the unit in a place where there is a chance of flammable gas leaks. If

there is a gas leak and gas accumulates in the area surrounding the unit, it could cause an

explosion.

Perform the drainage/piping work according to the installation instruction.

If there is a defect in the drainage/piping work, water could leak from the unit and household

goods could get wet and be damaged.

Do not clean the unit when the power is ‘on’.

Always shut ‘off’ the power when cleaning or servicing the unit. If not, it could cause an injury

due to the high speed running fan or an electrical shock.

Do not continue to run the unit when there is something wrong or there is a strange

smell.

The power supply needs to be shut ‘off’ to stop the unit; otherwise this may cause an

electrical shock or fire.

Be cautious when unpacking and installing the product.

Sharp edges could cause injury. Especially watch the edges and the fins on the heat

exchanger of the product.

Always check for gas (refrigerant) leakage after installation or repair of product.

Low refrigerant levels may cause failure of the product.

The installation of the unit must be level and secure.

To avoid vibration and or water leakage

Do not put your fingers or others into the fan, or evaporator. The

fan runs at high speed, this could cause serious injury.

In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this

appliance must not be supplied through an external switching device, such as a timer, or

connected to a circuit that is regularly switched on and off by the utility.

This appliance has not been designed for use by persons (including children) with reduced

physical, sensorial or mental faculties or by persons without any experience or knowledge of

heating systems, unless they act under the safety and supervision of a responsible person

or have received prior training concerning the use of the appliance. Children should be

supervised to ensure that they do not play with the appliance.

If the supply cord is damaged, it must be replaced by the manufacturer or its service agent

or a similarly qualified person in order to avoid a hazard. The means for disconnection must

be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in

each active(phase)conductors.

Page 9: Inverter Air Source Heat Pump

8

Materials needed to install the heat pump

Water connection on the indoor unit is 1-1/4” female connection for both flow and return.

3 way Valve when requiring a hot water & heating system.

2 way Valve when requiring zone heating NB each zone requires a 2 way valve

NB The water connection can be reduced using a male to female bush

Power cable to the unit :6KW&9kw used 3 core 4mm2 shielded heat resistance cables,

12KW&15kw used 3 core 6mm2 shielded heat resistance cables An

isolator is required as part of the field wiring.

Power cable to the indoor unit 3 core 2.5mm2 shielded heat resistance cable. An isolator is

required as part of the field wiring.

Low voltage inter connecting cable .75mm shielded twisted pair.

NB all controls cable must be installed 300mm away from mains cables

The required insolation for the field pipe installation is Class ‘0’.

Heating operation range

The Unit

Dry bulb Wet

Bulb Inlet Outlet

Heating Max. 35 26 50 55

Min. -15 / 15 20

Page 10: Inverter Air Source Heat Pump

9

Cycle diagram(AXAI-06M / AXAI-09M/ AXAI-12M/AXAI-15M)

OVERVIEW OF THE UNIT

External: AXAI-06M & AXAI-09M

Page 11: Inverter Air Source Heat Pump

10

Internal: AXAI-06M & AXAI-09M

Page 12: Inverter Air Source Heat Pump

11

External: AXAI-12M&AXAI-15M

Internal: AXAI-12M&AXAI-15M

Page 13: Inverter Air Source Heat Pump

12

Wiring Diagram

Electrical Wiring Diagram for the 6&9KW

Page 14: Inverter Air Source Heat Pump

13

Electrical Wiring Diagram for the 12&15KW

NB cable entry either top or bottom of the unit The

unit Separated Power supply

Model Separated Power supply / Rated Current

AXAI-06M 2200W / 9.6A

AXAI-09M 2500W /11.9A

AXAI-12M 4200W / 14A

AXAI-15M 4400W /19A

Page 15: Inverter Air Source Heat Pump

14

WARNING

• A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local and national legislation.

• Switch ‘off’ the power supply before making any connections.

• All field wiring and components must be installed by a licensed electrician and must

comply with relevant European and national regulations.

• The field wiring must be carried out in accordance with the wiring diagram supplied

with the unit and the instructions given below.

• Be sure to use a dedicated power supply. Never use a power supply shared by

another appliance.

• Be sure to establish an earth. Do not earth the unit to a utility pipe, surge absorber, or

telephone earth. Incomplete earth may cause electrical shock.

• Be sure to install an earth leakage protector.

Failure to do so may cause electrical shock.

Wiring overview

The table below gives a wiring overview of required field wiring.

AXAI-06M AXAI-09M AXAI-12M AXAI-15M

United Power supply

(outdoor power supply

must fuse down the

indoor power supply to

20 amps)

AWG9(6.63m

m2

)*3

AWG9(6.63mm

2 )*3

AWG8(8.37m

m2

)*3

AWG8(8.37m

m2

)*3

Separated

Power supply

Outdoor AWG13(4mm

2 )*3

AWG13(4mm2

)*3

AWG11(4.mm

2 )*3

AWG11(4.mm

2 )*3

Communication cable Twin-core twisted pair shielding (0.75mm

2 )*2

Page 16: Inverter Air Source Heat Pump

15

WATER PIPE-WORK

Checking the water circuit

NB: The 3-way valve is not supplied with this system

Before continuing the installation of the unit, check the following points:

• The maximum water pressure is 10 bar.

• Shut-off valves are not included with the unit. To facilitate service and maintenance, please install one at each water inlet/outlet. Mind position of the shut-off valves. Orientation of the integrated drain and fill valves is important for servicing.

• Take care that the components installed in the field piping can withstand the water

pressure.

NEVER USE UN-COATED PARTS IN THE WATER CIRCUIT. EXCESSIVE

CORROSION OF THESE PARTS MAY OCCUR AS COPPER PIPING IS USED IN THE

INTERNAL WATER CIRCUIT OF THE UNIT.

WHEN USING A 3-WAY VALVE OR A 2-WAY VALVE IN THE WATER CIRCUIT. THE RECOMMENDED MAXIMUM CHANGEOVER TIME OF THE VALVE SHOULD BE LESS THAN 60 SECONDS.

Charging water

1. Connect the water supply to a drain and fill valve.

2. Make sure the automatic air purge valve is open (at least 2 turns).

3. Fill with water until the water manometer indicates a pressure of approximately 2.0 bar.

Remove air in the circuit as much as possible using the air-purge valves. Air present in

the water circuit might cause malfunctioning of the optional backup heater.

4. Backup heater:

Check that the backup heater vessel is filled with water by opening the pressure relief

valve. Water must flow out of the valve.

NOTE

• During filling, it might not be possible to remove all the air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required.

• The water pressure indicated on the water manometer will vary depending on the

water-temperature (higher pressure at higher water temperature).

• However, at all times water pressure should remain above 0.3 bar to avoid air

entering the circuit.

• The unit might dispose some excessive water through the pressure relief valve.

• Water quality must be according to EN directive 98/83 EC.

Water Flow Rates

6 kw 1.03m³ /h

9kw 1.55m³ /h

Page 17: Inverter Air Source Heat Pump

16

12kw 2.06m³ /h

15kw 2.6m³ /h

INSTALLATION OF THE MAIN UNIT Installation guidelines Precautions for selecting the

location

WARNING

MAKE SURE TO PROVIDE FOR ADEQUATE MEASURES IN ORDER TO PREVENT

THAT THE OUTDOOR UNIT WILL BE USED AS A SHELTER BY SMALL ANIMALS.

SMALL ANIMALS MAKING CONTACT WITH ELECTRICAL PARTS CAN CAUSE

POSSIBLE MALFUNCTIONS, SMOKE OR FIRE. PLEASE KEEP THE AREA AROUND

THE UNIT CLEAN.

1. Choose a place solid enough to bear the weight and vibration of the unit, where the

operation noise will not be amplified.

2. Choose a location where the hot air discharged from the unit or the operation noise will

not cause a nuisance to the neighbors of the user.

3. Avoid places near a bedroom and the like, so that the operation noise will cause no

trouble.

4. There must be sufficient space for carrying the unit into and out of the site.

5. There must be sufficient space for air passage and no obstructions around the air inlet

and the air outlet.

6. The site must be free from the possibility of flammable gas leakage in a nearby place.

7. Install units, power cords and inter-unit cables at least 3m away from television and radio

sets. This is to prevent interference to images and sounds.

8. Depending on radio wave conditions, electromagnetic interference can still occur even if

installed more that 3m away.

9. In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may

shorten the life of the outdoor unit.

10. The water will flows out of the unit when in defrost, do not place anything under the unit

which must be kept dry.

Installation space

Page 18: Inverter Air Source Heat Pump

17

Installation procedure

Mounting the unit

When installing the unit, please refer to “Installation guidelines” to select an appropriate

location.

1. Check the strength and level of the installation ground so that the unit will not cause any

operating vibration or noise after installation.

2. Prepare 4 sets of M8 foundation bolts, nuts and washers each (filed supply).

3. Fix the unit securely by means of the foundation bolts in accordance with the foundation drawing. It is best to screw in the foundation bolts until their length remains 20mm above the foundation surface.

NB; Wall brackets are not supplied with the unit unless specified an installation guide

is supplied within the wall brackets packaging

Check before running

Check before initial startup

Turn off the power before connecting

After installation, before accessing circuit breaker, please check the contents:

1. Field Wiring

Make sure the wiring of instrument panel and the host, the wiring between the unit and the

tank is in accordance with instructions guide, schematics is followed European and national

laws.

2. Fuse or protective device

Page 19: Inverter Air Source Heat Pump

18

Checking fuses and installed protective equipment is ok. Make sure fuses and protection

devices have not been overlooked.

3. The grounding wire

Properly connect the ground terminals then tighten

4. Internal wiring

Check whether the switch box is loose or electrical components is damaged

5. Fixed

Check whether the machine fixed, to avoid abnormal noises and vibrations when starting.

6. The damage to the equipment

Check whether there is damage to the internal components of the machine or tube is

squeezed

7. The refrigerant leak

Check whether the machine refrigerant leakage, if there is a leak, contact your local dealer

8. Power voltage

Check the power supply voltage on the screen, the supply voltage must be consistent with

the nameplate on the machine.

9. Air vent valve

Make sure the air vent valve is open (at least 2 turns)

10. The atmospheric valve

After checking the atmospheric valve is opened, whether the backup heater vessel filled with

water. It is purified water instead of air.

Running the system when backup heater vessel is unfilled with water will damage

the heater

11. Shut-off valve

Properly install shut-off valves, and open.

Running the system when the valve closing will damage the pump!

Page 20: Inverter Air Source Heat Pump

19

Specification - DC Inverter - Monobloc type

TECHNICAL DATA AXAI- S06M

AXAI- S09M

AXAI-S12M AXAI-S15M

Heating

Nominal

capacity KW 6(2.1-6.5) 9(2.3-9.8) 12(4-13) 15(5-16)

Power input KW 1.39 2.1 2.82 3.57

COP W/W 4.3 4.3 4.25 4.2

Cooling

Nominal

capacity KW 5(1.9-5.33) 7(2.1-8.3) 10(2.2-10.5) 12(3-12.2)

Power input KW 1.34 2 3 3.75

EER W/W 3.73 3.5 3.3 3.2

DHW

Nominal

capacity KW 5(2.0-5.8) 8(2.2-8.8) 10(2.2-11) 12.5(2.2-14)

Power input KW 1.34 2.2 2.8 3.52

COP W/W 3.74 3.63 3.57 3.55

Power supply V/Ph/Hz

220-240/1/50

Max. power input KW

2.2 3.2 4 4.8

Max. current A

9.6 14 18 21

Max. leaving water

temperature (without using

backup heater) ℃ 58

Working temperature range ℃ -20 - 43

Refrigerant

circuit

Refrigerant Type R410A

Compressor Brand*Q'ty/Type TOSHIBA*1/Inverter

Rotary TOSHIBA*1/Inverter Twin

Rotary

Heat exchanger Type High efficiency hydrophilic fin-tube heat exchanger

EEV Brand SAGInoMIYA

Fan motor Quantity 1 1 2 2

Power input (W) 65 70 140 140

Size of fan mm 420*153 500*145 508*145 508*145

Liquid pipe inch(mm) 1/4(6.35) 3/8(9.52) 3/8(9.52) 3/8(9.52)

Page 21: Inverter Air Source Heat Pump

20

Gas pipe inch(mm) 1/2(12.7) 5/8(15.88) 5/8(15.88) 5/8(15.88)

Water

circuit

Heat exchanger Type Stainless steel plate heat exchanger

Rated water

flow m3/h 1 1.5 2.1 2.6

Inlet/outlet pipe inch(mm) 5/4(31.75)

Net Dimension (H*W*D) mm 860*900*325 1330*900*340

Packing Dimension (H*W*D) mm 1000*1000*400 1460*990*415

Net weight Kg 86 102 125 145

Gross weight Kg 98 118 135 160

Noise level dB(A) 50 53 60 62

NOTES:

Capacities and power inputs based on the following conditions:

Heating: Water Inlet/Outlet temperature 30℃/35℃. Outdoor air dry bulb/wet bulb temperature 7℃/6℃

Cooling: Water Inlet/Outlet temperature 23℃/18℃. Outdoor air dry bulb temperature 35℃

Domestic Hot Water: Water temperature in the tank 40℃. Outdoor air dry bulb/wet bulb temperature 7℃/6℃

-The related data is subject to adjustment periodically because of technical improvement without further notice.

Please refer to heat pump nameplate.