Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 14222 (1995): Impulse Voltage Withstand Levels of Rotating a.c. Machines with Form-wound Stator Coils [ETD 15: Rotating Machinery]

IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 14222 (1995): Impulse Voltage Withstand Levels ofRotating a.c. Machines with Form-wound Stator Coils [ETD15: Rotating Machinery]

Page 2: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained
Page 3: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained
Page 4: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 IEC Pub 34-15 : 1990

Indian Standard

IMPULSE VOLTAGE WITHSTAND LEVELS OF ROTATING A.C.

MACHINES WITH FORM-WOUND STATOR COILS

UDC 621 : 313 : 3.621.317-333-8

@ BIS 1995

BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI 110002

January 1995 Price Group 3

Page 5: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

Rotating Machinery Sectional Committee, ET 15

NATIONAL FOREWORD

This Indian Standard which is identical with IEC Pub 34-15 (1990) ‘Rotating electrical machines Part 15 : Impulse voltage withstand levels of rotating a.c. machines with form-wound stator coils’, issued by the International Electrotechnical Commission was adopted by the Bureau of Indian Standards on the recommendation of the Rotating Machinery Sectional Committee (ET 15) and approval of the Electrotechnicdl Division Council.

The text of IEC standard has been approved as suitable for publication as Indian Standard without deviations. Certain conventions are however not identical to those used in Indian Standards. Wherever the words ‘IEC Standards’ appear in this standard, they should be read as ‘Indian Standards’.

In this adopted standard, reference appears to certain International Standards for which Indian Standards also exist. The corresponding Indian Standards which are to.be substituted in their place are listed below ’ along with their degree of equivalence for the editions indicated :

International Corresponding Indian Degree of Standard Stand&d Equivalence

IEC Pub 34-l (1983) IS325 : 1978Threephase induction motors you&r revision)

IS 996 : 1979 Single phase small ac universal electric motors

IS 7538 : 1975 Three-phase squirrel cage induction motors Not fully for centrifugal pumps for agricultural applications equivalent

IS 4722 : 1985 Rotating electric machine (secorui revision)

IEC 60-2 (1973) IS 2071 (Part 2) : 1974 Methods of high voltage testing: Technically- Part 2 Test procedures (first revision) equivalent

IEC 71-l(l976) IS 2165 (Part 1) : 1977 Insulation coordination: Part 1 Technically Phase to earth insulation coordination equivalent

Only the English language text in the International Standard has been retained while adopting it in this Indian Standard.

For the purpose of deciding whether a particular requirement of this standard is complied with, the final value, observed or calculated, expressing the result of a t est, shall be rounded off in accordance with IS 2 : 1960 ‘Rules for rounding off numerical values (revised)‘. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard.

Page 6: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 IEC Pub 34-15: 1990

Indian Standard

IMPULSE VOLTAGE WITHSTAND LEVELS OF ROTATING A.C.

MACHINES WITH FORM-WOUND STATOR COILS

Introduction

IEC Publication 71~1 specifies general requirements for the phase-to-earth insulation of equipment in

three-phase a.c. systems and states that each Apparatus Committee is responsible for specifying the insula-

tion levels and test procedures for its equipment, taking into consideration the recommendations of Publica-

tion 71-1. The object of this standard is to specify requirements for rotating electrical machines and experi-

ence has shown that the values given in this standard meet the insulation requirements for the essential

stresses in service under usual operating conditions. An explanation of the principles adopted in preparing

these requirements is given in Appendix A.

1 Scope

This standard applies to rotating a.c. machines for rated voltages from 3 kV to 15 kV inclusive and

incorporating form-wound stator coils.

2 Object

This standard specifies the rated phase-to-earth impulse voltage withstand levels and the test pro-

cedures and voltages to be applied to the main and interturn insulation of sample coils to prove the

impulse voltage withstand level of the machine, and gives some guidance for routine tests. The stan-

dard covers surges originating from lightning but consideration is being given to extendhtg the standard

to cover surges originating from switching vacuum and other circuit-breakers.

3 Defmitions

For the purpose of this standard the following definitions apply:

3.1 Random Sample test: A test carried out on coils which adequately represent the configuration of the

finished item to be used in the machine, for the purpose of evaluating the basic design, type of

materials, manufacturing procedures and processes incorporated in the insulation system.

3.2 Routine fest: A test carried out on all coils of the machine.

3.3 Form-wound staror coil: A coil which is preformed to shape ,before insertion in the stator.

4 Impulse voltage withstand levels

The rated lightning impulse voltage withstand levels for certain rated voltages are given in column 2

of Table 1.

1

Page 7: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 EC Pub 34-15 : 1990

Table 1 - Rated insulation le<els for rotating machines

1 Rated voltage

2 Rated lightning impulse withstand voltage (peak)

3 Rated power-frequency

withstand voltage (r.m.s.) according to

IEC Publication 34-l

kV kV kV

3 17 7

3.3 I8 7.6 4 21 9.0 6 29 13 696 31 14.2

. 10 45 21 II 49 23 13.2 58 27,4 13.x 60 28,6 1.5 65 31

.NOTES

I The levels in column 2 are based on a standard lightning impulse having a front time of 1.2 ps and a time to half-value of 50 vs as specified in IEC Publication 60-2.

2 The levels in column 2 are obtained by application of the formula:

u,= 4 lJ,+s

where :

U,, = rated lightning impulse withstand voltage (peak) in kilovolts U,- rated voltage in kiloyolts

3 The levejs in co!umn 2 have been deemed appropriate by taking into consideration both the average characteristics of machines and “usual” operating conditions.

The above-mentioned levels, thereford; may not be adequate for “special” operating conditions (e.g. machines directly connected to overhead lines) or “abnormal events” (e.g. multiple re-ignition of the switchgear) and in such cases the windings should either be designed to withstand other impulse levels or be protected in an appropriate way.

Rated lightning imp&e voltage withstand levels for other rated voltages between 3 kV and 15 kV

can be obtained by application of the formula given in note 2 of Table 1, the values obtained being

rounded off to the nearest whole number.

5 Tests

5.1 Random sample tests

These tests are performed as an indirect proof as explained in Sub-clause A.3.2 of AppendikA. The

test coils shall be finally processed, including corona protection, if provided, and shall be either

embedded in slots or fitted with the slot portion wrapped in earthed conducting tape or foil. The

number of sample coils shall be two, unless agreed otherwise between the manufacturer and the

purchaser;

All tested coils shall fulfill the requirements given below and, in the case of a failure, investigations

shall be carried out to determine the cause.

5.1.1 Impulse test of the interturn insulation

5.1 .l.i The impulse test of the interturn insulation shall be performed by applying a voltage between the

two terminals of the sample coils.

2

Page 8: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 IEC: Pub 34-15 : 1990

5.1.1.2 The’interturn test voltage shall be generated by the damped oscillatory discharge of a capacitor. The

number of capacitor discharges shall be five, unless agreed otherwise between the manufacturer and

the purchaser. In order to obtain even distribution of the surge between coil turns, the front time of the

first voltage peak should not be shorter than 0,5 p.

5.1.1.3 The voltage peaks between the terminals of the sample coil shall be 50% of the values given in

5.1.2

Table 1, column 2 or 50% of the values obtained by application of the formula U,, = 4 UN ; 5 (see

Clause 4). This is in accordance with the 50% presumption mentioned in Sub-clause A.3.2.3 of

Appendix A. Where calculations or tests show that less than 40% or more than 60% of the input

impulse voltage appears across the entrance cbil, the test voltage should be subject to agreement be-

tween the manufacturer and the purchaser.

Impulse withstand test of the main insulation

The impulse withstand level of the main insulation is tested by applying either a power-frequency

voltage (see Sub-clause 5.1.2.1) or an impulse voltage (see Sub-clause 5.1.2.2).

5.1.2.1 Power-frequency voltage test

The r.m.s. voltage (2&+1) kV shall be applied for 1 min between coil terminals and earth, shall

then be increased at the rate of 1 kV/s up to 2(2UN+ 1) kV and shall then immediately be reduced at

a rate of at least 1 kV/s to zero, without failure. The corresponding impulse withstand level of the

main insulation and the overhang corona protection are then considered to fulfill at least the require-

ments of Table 1, column 2.

NOTES

1 The rated impulse level in Table 1, column 2, is lower than the peak value 2\/2(2U,+ I) kV dcrivcd from this tcht

because the impulse level of a machine is determined by the interturn voltage due to longitudinal voltage distribution (WC

Sub-clauses A.I. I and A. 1.2). The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more

nearly equivalent to that obtained by the impulse test.

2 In some countries it is common practice to apply a d.c. test voltage instead of.thc power-frcqucncy volt;~gc spccificd

above. This is permitted by this standard when agreed between the manufacturer and the purchaser. The d.c. voltage level

shall he included in such an agreement and should he at least as high as 1.7 times the power-frequency routine ICSI voltqc.

i.e. at least 1.7(2U,+ I) kV.

5.1.2.2 Impulse vollage test

5.1.2.2.1 The impulse test of the main insulation shall be performed by applying a voltage between the coil

terminals and earth.

5.1.2.2.2 The main insulation test voltage shall be generated by an impulse generator applying approxi-

mately the standard lightning impulse specified in.1 EC Publication 60-2. The number of impulses shall

be five, unless agreed otherwise between the manufacturer and the purchaser.

5.1.2.2.3 The voltage peaks between the coil terminals and earth shall be 100% of the values given in

Table 1, column 2 or 100% of the values obtained by application of the formula U,, = 4 UN + 5 (see

Clause 4).

5.2 Routine tests

Routine tests shall be carried out for all coils after insertion in the stator core’, bul bcforc the

connections have been made.

Due to the various technologies involved (c.g. resin rich insulation, vacuunl prcssurc in~uliltion). no

general requircmcnts can Ix spccifictl for the test values.

Page 9: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 IEC Pub 34-15 : 1990

APPENDIX A

PRINCIPLES INVOLVED IN THE SPECIFICATION OF IMPULSE VOLTAGE

WITHSTAND LEVELS AND TEST PROCEDURES

A.1 Impulse voltage stress of a machine winding

A. I. 1 When a steep voltage surge occurs between one machine terminal and earth, the corresponding phase

cannot “suddenly” (i.e. during the impulse rise-time) adopt the same potential on all its points. Hence,

two types of voltage arise in the winding: the voltage between the copper and earth (transverse voltage)

and the voltage along the copper (longitudinal voltage).

A.1.2 Whilst the transverse @age stresses the main wall insulation, the longitudinal voltage also stresses

the interturn insulation. The highest voltage components of both kinds normally appear on the first or

entrance coil of the,winding.

A. 1.3 In practice, voltage surges can be of various shapes and may even extend to wave-front times down to

about 0,2 us. The’following explanations and the requirements in this standard only refer to the

standard lightning impulse defined in IEC Publication 60-2, since this is the wave shape of the rated

A.2

lightning impulse withstand voltage given in IEC Publication 71-1. This wave

and a time to half-value of 50 ns.

Impulse withstand level of a machine winding

A.2.1 A machine winding should have a certain impulse withstand level within

co-ordination.

A.2.2 Impulse withstand levels specified in this standard are based on the

has a front time of 1,2 us

the system of insulation

formula Up = 4UN+‘5

A.3

A.3.1

(see Clause 4).

Proof of impulse voltage withstand levels

It is not recommended that an impulse test should be performed on a complete machine, because, in

this case. any interturn failure is very difficult to detect with the present state of knowledge. The

impulse voltage withstand levels can therefore only be proved indirectly by random sample tests on

individual coils.

A.3.2 Itldirect proof by random ‘sample test on coils

A.3.2.1 The impulse voltage withstand level of a complete machine winding can be proved indirectly by

tests on a sample coil. based on the principle that the sample coil during this random sample test should

be stressed, as near as practicable, in the same manner as that coil (or those coils) within the complete

winding with fhe maximum stressesbetween turns and/or to earth, i.e. normally the entrance coil of the

winding.

4

Page 10: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

IS 14222 : 1995 IEC Pub 34-15 : 1990

A.3.2.2 The peak value of the transverse voltage (between copper and earth) appearing on the entrance coil

(and therefore on the sample coil for the random sample test) is equal to the peak value of the impulse

voltage on the complete winding. This peak value can be higher than the power-frequency routine test

peak voltage a(2 UN 4 1) kV but generally not higher than the figure derived from the test in Sub-

clause 5.1.2.1.

A.3.2.3 The peak value of the longitudinal voltage appearing on the entrance coil varies widely due; at

least, to the following factors:

- rise time t, of the voltage impulse ;

- copper length of the entrance coil;

- number and arrangement of the turns.

The actual value may be investigated by applying a “model impulse voltage” with for example a few

hundred volts peak on the terminal of the complete machine.

Corresponding investigations have been made in several countries and results have been published.

but, as expected, no simple law has been found for pre-calculating this peak value from a given machine

configuration.

It is considered, therefore, that the three factors mentioned above are too complicated to be used as

a basis for practical specifications. For easier practice in most cases it is considered that 50% of the total

longitudinal voltage on the complete winding for the standard impulse (see Sub-clause’ A.1.3) should be

adopted as a rough guideline for the longitudinal voltage on the entrance coil. The sample test coil

should, therefore, be tested by applying high frequency voltage between its terminals with 50% of the

specified impulse withstand voltage of the total winding.

Page 11: IS 14222 (1995): Impulse Voltage Withstand Levels of ...The purpose of the higher a,c. test level is to product a voltage gradient iit the slot end more nearly equivalent to that obtained

Bureau of Indian Standards

BlS is a statutor? institution established under the Bureau of Indian Standards dct, 1986 to Promote harmonious development of the activities of standardization, marking and quality certification of goods and attending to connected matters in the country.

Copyright

BIS has a copyright of all its publications. No part of these publications may be reproduced in any form without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed periodically; a standard along with amendments is reaffirmed when such a review indicates that no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of ‘BIS Handbook’ and ‘Standards Monthly Addition’.

This Indian Standard has been developed from Dot : No. ET 15 (3634).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected _~

BUREAU OF INDIAN STANDARDS

Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002

Telephones : 3310131,331 13 75 Telegrams : Manaksanstha ( Common to all Offices )

Regional Offices:

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg NEW DELHI 110002

Eastern : l/14 C.I.T. Scheme VII M, V.I.P. Road, Maniktola CALCUTTA 700054

Northern : SC0 445-446, Sector 35-C, CHANDIGARH 160036

Southern : C.I.T. Campus, IV Cross Road, MADRAS 600113

Western : Manakalaya, E9 MIDC, Marol, Andheri ( East ) BOMBAY 430093

Telephones

t

33101 31 331 13 75

(

37 84 99, 37 85 61 37 86 26, 37 86 62

{

53 38 43, 53 16 40 53 23 84

{

235 02 16, 235 04 42 235 15 19, 235 23 15

632 92 95, 632 78 58 632 78 91, 632 78 92

Branches : AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR. CGIMBATGRE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. , JAIPUR. KANPUR. LUCKNOW. PATNA. THIRUVANANTHAPURAM.

Reprography Unit, BIS, New Delhi, India