    Is Limiter Overview

    INTRODUCTION to Is LIMITERS

    Is Limiters interrupts instantaneous fault currentsame as fuse but the tripping is initiated by an

    external circuit.

    The tripping of Is Limiters limits the prospectivefault current by dividing the fault contributing

    sources.

    It does not clear the fault. The fault is cleared bythe protection device closest to the fault.

  • 7/22/2019 Is Limiter Overview Presentation

    3/23

    Is Limiter Overview

    INTRODUCTION (Cont.)

    Operation of Is Limiter

  • 7/22/2019 Is Limiter Overview Presentation

    4/23

    Fault Current IEC DefinitionsINTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    5/23

    Interrupting Devices

    Circuitbreakers

    Fuses

    Is Limiters

    There are two differences between circuitbreakers and fuses- One is that circuit breaker interrupts currentat current zero while fuse interrupts theinstantaneous current.

    - The second difference is that for operation ofthe circuit breaker it receives a command froman external control circuit.The Is limiter sits in between the two. Is limiterinterrupts instantaneous fault same as fuse butneeds an external circuit to initiate operationsame as circuit breaker.

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    6/23

    Interrupting Device Ratings

    Circuit Breaker Ratings: Breaking :

    Symmetrical Asymmetrical Zero crossing is required to interrupt

    current

    Making Short time rating

    Fuse Ratings: Cut off current Let through energyIs Limiter Ratings: Max short circuit current (initial

    symmetrical)

    Max rate of rise. For ACG limiters it is44.429 kA/ms

    All devices have continuous

    current and voltage rating

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    7/23

    .For higher rated currents

    IS-limiters can be

    connected in parallel.

    Technical data

    Rated

    Voltage

    Rated

    Current

    Switching

    Capability0,75 kV

    12,00 kV

    17,50 kV

    24,00 kV

    36,00 kV40,50 kV

    1250 A - 5000 A

    1250 A - 4000 A

    1250 A - 4000 A

    1250 A - 3000 A

    1250 A - 2500 A1250 A - 2500 A

    140 kA RMS210 kA RMS210 kA RMS140 kA RMS140 kA RMS140 kA RMS

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    8/23

    T2

    T0

    T1

    T3

    Total operating time of the circuit breaker:

    T1: Operating time of the protection relay: 30 - 40 ms

    T2: Operating time of the circuit breaker: 40 - 80 ms

    T3: Arc duration: 10 - 20 ms

    T0: Response time of the protection relay: 30 - 40 ms

    T

    Total operating time of the IS-

    limiter:

    T : 5 - 10 ms

    IS-limiter - Circuit Breaker

    t

    i

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    9/23

    i = i1+ i2without IS-limiter

    i1

    Current curve at the short-circuit location

    Breaking of a short-circuit

    current with IS-limiter

    i2

    u

    t

    i

    126 kA

    63 kA

    Ikperm.= 25 kA=

    IK= 25 kA=

    T1 IK= 25 kA=

    T2

    i1

    Single line diagram ofa busbar systemwith IS-limiter

    i = i1+ i2with IS-limiter

    i2

    i = i1 + i2

    i1 i2

    i = i1 + i2

    i1

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    10/23

    di

    dt( )33di

    dt( )2

    i

    t

    iLimit

    Detection of the Short-circuit current

    2

    4

    1

    1 Short-circuit currentwithout IS-limiter

    2 Short-circuit currentIS-limiter tripped

    3 Over current

    IS-limiter not

    tripped

    4 Peak value of

    service current

    ilimit^(di/dt)

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    11/23

    Schedule for tripping of the Is-limiter

    T1T2

    T0: Reaching time for tripping criteria

    (instantaneous value anddi/dt).

    T4T0t

    i

    T3

    .

    T1: Response time of the electronic approx. 15 s

    T2: Time for opening the bursting bridgeand for commutating the

    current to the fuse element approx. 85 s

    T3: Melting time of the fuse element approx. 500 s

    T4: Arc duration

    iA: Tripping criteria are reached

    (instantaneous value and di/dt).iB: Current at beginning of fuse element's melting

    iC: Let-through current

    iC

    iB

    iA

    INTRODUCTION (Cont.)

    Is Limiter Overview

  • 7/22/2019 Is Limiter Overview Presentation

    12/23

    Is Limiter Overview

    STEP FAULT LIMITING SCHEME

    An integrated scheme consisting of three Is limiters,

    summation CTs, and a logic control panel is provided to

    achieve a reliable operation of Is limiters when requiredand to block its operation to prevent unnecessary and

    spurious tripping.

    Summation CTs are installed in each of the generator

    incomers, the grid incomers and bus sections to monitor

    the actual fault currents.

    Current Limiting Reactor is provided at phase1 & phase2

    Intertie to reduce the fault levels to within the Is Limiters

    and Shah Deniz 11kV fuses breaking capacity.

  • 7/22/2019 Is Limiter Overview Presentation

    13/23

    Is Limiter Overview

    TRIPPING CRITERIA

    Is Limiter must prevent short circuit currents exceeding

    the permissible values as below:

    - Breaking current of 50kA- Peak Short circuit Current of 158kA

    - Initial Symmetrical Short circuit current of 58kA.

    The tripping criteria is based on total summation fault

    current and the current through the Is limiter. If both these

    values exceed the preset value the Is limiter will trip. Tripping

    of the Is Limiter is also dependent on the direction of current.

    The tripping values for the summation current and the

    current through the Is limiter are 7kA and 42kA respectively.

    These values are factory set and cannot be changed by the

    operator on site.

  • 7/22/2019 Is Limiter Overview Presentation

    14/23

    Is Limiter Overview

    BLOCKING LOGIC

    The operation of the Is limiters is not activated for the

    following:

    -To prevent unnecessary operation of more than one Is

    limiter for the same fault.

    -To prevent operation of Is limiters for external gridfault.

    - To prevent operation if the summation current does

    not exceed the tripping value.

  • 7/22/2019 Is Limiter Overview Presentation

    15/23

    Is Limiter Overview

    INTER-TRIPPING TO BUS SECTION BREAKERS

    The Is Limiter operates independently for each

    phase. If the tripping values for one phase are

    exceeded the Is Limiter for that phase only will trip.

    If the tripping values for two phases are exceeded

    the Is Limiters for those phases will trip.

    For three phase isolation intertripping is providedsuch that tripping of the Is Limiter will trip the

    associated bus section breaker.

    The tripping values of the Is Limiters are set such

    the circuit breaker interrupting capacity is not

    exceeded.

  • 7/22/2019 Is Limiter Overview Presentation

    16/23

    Is Limiter Overview

    INTERLOCKING

    A solenoid operated Interlocking is provided

    such that the Is Limiter truck cannot be insertedor withdrawn unless both sides of the Is limiter

    are de-energised.

    In addition interlocking is provided such thatthe associated bus section breaker cannot be

    closed unless the Is Limiter is ready for

    operation.

  • 7/22/2019 Is Limiter Overview Presentation

    17/23

    Is Limiter Overview

    CONTROL SUPPLY

    For high reliability two 110V AC supplies:

    - The main power supply via voltage transformer (VT)- The Secondary power supply from UPS

    These two power supplies are provided with an auto

    changeover scheme. Normal operation will be with the

    power supply from the voltage transformer. Upon loss

    of mains power the auxiliary supply will be switched to

    UPS. Similarly upon restoration of main power the

    auxiliary supply will be switched back the voltage

    transformer.

  • 7/22/2019 Is Limiter Overview Presentation

    18/23

    Is Limiter Overview

    IS LIMITER LV COMPARTMENT ALARM AND STATUSSIGNALS

    Alarm and status signals are sent to PMS, logic control

    panel and to the associated bus section breaker.

    The followings are the interface between LV

    Compartment and Logic Control Panel:

    - Is Limiter Blocking

    - Is Limiter Deactivation of Tripping Criteria

    - Tripping Criteria Status

    - Is Limiter Blocked

    - Is Limiter Tripped- Is Limiter Ready

  • 7/22/2019 Is Limiter Overview Presentation

    19/23

    Is Limiter Overview

    TESTING

    The testing of the trip values will normally becarried out by specialist engineer using vendor

    supplied test inserts and testing equipment. Refer

    to acceptance test procedure, vendor document

    reference PTCS01A-H0191.

  • 7/22/2019 Is Limiter Overview Presentation

    20/23

    Is Limiter Overview

    IS LIMITER CONTROL PANEL

    A logic control panel is provided to implement thematrix logic. In order to achieve high reliability the

    matrix logic is implemented both by using hard wired

    control relay and a PLC. If there is any discrepancy

    between the hard wired logic and the PLC logic an alarmis raised.

    The control panel consists of hard wired logic and the

    supervisory PLC. The PLC has dual redundant processors

    running in synchronism with bumpless transfer from the

    primary processor to the secondary processor.

  • 7/22/2019 Is Limiter Overview Presentation

    21/23

    Is Limiter Overview

    In-Service/Overide Selection:

    - For a fault on each Is limiter an alarm is received from

    the Is Limiter cubicle to the control panel. The operator

    can take the faulty Is Limiter out of service without

    affecting the operation of other Is Limiters. A key

    operated in-service/over-ride switch is provided for this

    for each Is Limiter.

    Alarms:

    - PLC Watchdog Fault

    - Incorrect activation/blocking criteria outputs from

    hardwired control section

    IS LIMITER CONTROL PANEL (Cont)

  • 7/22/2019 Is Limiter Overview Presentation

    22/23

    Is Limiter Overview

    - Discrepancy check of main generator/grid circuit breaker

    status signals- Discrepancy between verified IS Limiter

    activation/blocking status and outputs from the hardwired

    relay logic

    - Common fault including control supply fault of Is Limiterfault to PMS

    - Is Limiter Control Panel fault to PMS

    -Common alarm to the ICSS for any alarm present in the

    logic control panel including the Is Limiter fault alarms.

    Control Supply

    - Dual UPS supplies with auto changeover.

    IS LIMITER CONTROL PANEL (Cont)

  • 7/22/2019 Is Limiter Overview Presentation

    23/23

    Is Limiter Overview

    IS LIMITER SIMULATION

    The IS limiters is simulated in a spreadsheet for a 3-

    phase fault at any 11kV busbar, with the system in any

    operating configuration. This will also check the Is limiter

    blocking or activation of selectivity criteria, dependent on

    the number of main generators/grids supplies connected

    to the 11kV system. The fault currents are calculated withIS limiter operation and also ignoring Is limiter operation

    in accordance with BS-EN 60909-0:2001.