Is Limiters Introduction to Is Limiters STEP Fault Limiting Scheme Tripping Criteria Blocking Logic Inter-tripping to Bus Section
Breakers Interlocking Control Supply Is Limiter LV Compartment Alarm
and Status Signals Testing Is Limiter Control Panel Is Limiter Simulation
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
2/23
Is Limiter Overview
INTRODUCTION to Is LIMITERS
Is Limiters interrupts instantaneous fault currentsame as fuse but the tripping is initiated by an
external circuit.
The tripping of Is Limiters limits the prospectivefault current by dividing the fault contributing
sources.
It does not clear the fault. The fault is cleared bythe protection device closest to the fault.
7/22/2019 Is Limiter Overview Presentation
3/23
Is Limiter Overview
INTRODUCTION (Cont.)
Operation of Is Limiter
7/22/2019 Is Limiter Overview Presentation
4/23
Fault Current IEC DefinitionsINTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
5/23
Interrupting Devices
Circuitbreakers
Fuses
Is Limiters
There are two differences between circuitbreakers and fuses- One is that circuit breaker interrupts currentat current zero while fuse interrupts theinstantaneous current.
- The second difference is that for operation ofthe circuit breaker it receives a command froman external control circuit.The Is limiter sits in between the two. Is limiterinterrupts instantaneous fault same as fuse butneeds an external circuit to initiate operationsame as circuit breaker.
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
6/23
Interrupting Device Ratings
Circuit Breaker Ratings: Breaking :
Symmetrical Asymmetrical Zero crossing is required to interrupt
current
Making Short time rating
Fuse Ratings: Cut off current Let through energyIs Limiter Ratings: Max short circuit current (initial
symmetrical)
Max rate of rise. For ACG limiters it is44.429 kA/ms
All devices have continuous
current and voltage rating
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
7/23
.For higher rated currents
IS-limiters can be
connected in parallel.
Technical data
Rated
Voltage
Rated
Current
Switching
Capability0,75 kV
12,00 kV
17,50 kV
24,00 kV
36,00 kV40,50 kV
1250 A - 5000 A
1250 A - 4000 A
1250 A - 4000 A
1250 A - 3000 A
1250 A - 2500 A1250 A - 2500 A
140 kA RMS210 kA RMS210 kA RMS140 kA RMS140 kA RMS140 kA RMS
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
8/23
T2
T0
T1
T3
Total operating time of the circuit breaker:
T1: Operating time of the protection relay: 30 - 40 ms
T2: Operating time of the circuit breaker: 40 - 80 ms
T3: Arc duration: 10 - 20 ms
T0: Response time of the protection relay: 30 - 40 ms
T
Total operating time of the IS-
limiter:
T : 5 - 10 ms
IS-limiter - Circuit Breaker
t
i
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
9/23
i = i1+ i2without IS-limiter
i1
Current curve at the short-circuit location
Breaking of a short-circuit
current with IS-limiter
i2
u
t
i
126 kA
63 kA
Ikperm.= 25 kA=
IK= 25 kA=
T1 IK= 25 kA=
T2
i1
Single line diagram ofa busbar systemwith IS-limiter
i = i1+ i2with IS-limiter
i2
i = i1 + i2
i1 i2
i = i1 + i2
i1
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
10/23
di
dt( )33di
dt( )2
i
t
iLimit
Detection of the Short-circuit current
2
4
1
1 Short-circuit currentwithout IS-limiter
2 Short-circuit currentIS-limiter tripped
3 Over current
IS-limiter not
tripped
4 Peak value of
service current
ilimit^(di/dt)
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
11/23
Schedule for tripping of the Is-limiter
T1T2
T0: Reaching time for tripping criteria
(instantaneous value anddi/dt).
T4T0t
i
T3
.
T1: Response time of the electronic approx. 15 s
T2: Time for opening the bursting bridgeand for commutating the
current to the fuse element approx. 85 s
T3: Melting time of the fuse element approx. 500 s
T4: Arc duration
iA: Tripping criteria are reached
(instantaneous value and di/dt).iB: Current at beginning of fuse element's melting
iC: Let-through current
iC
iB
iA
INTRODUCTION (Cont.)
Is Limiter Overview
7/22/2019 Is Limiter Overview Presentation
12/23
Is Limiter Overview
STEP FAULT LIMITING SCHEME
An integrated scheme consisting of three Is limiters,
summation CTs, and a logic control panel is provided to
achieve a reliable operation of Is limiters when requiredand to block its operation to prevent unnecessary and
spurious tripping.
Summation CTs are installed in each of the generator
incomers, the grid incomers and bus sections to monitor
the actual fault currents.
Current Limiting Reactor is provided at phase1 & phase2
Intertie to reduce the fault levels to within the Is Limiters
and Shah Deniz 11kV fuses breaking capacity.
7/22/2019 Is Limiter Overview Presentation
13/23
Is Limiter Overview
TRIPPING CRITERIA
Is Limiter must prevent short circuit currents exceeding
the permissible values as below:
- Breaking current of 50kA- Peak Short circuit Current of 158kA
- Initial Symmetrical Short circuit current of 58kA.
The tripping criteria is based on total summation fault
current and the current through the Is limiter. If both these
values exceed the preset value the Is limiter will trip. Tripping
of the Is Limiter is also dependent on the direction of current.
The tripping values for the summation current and the
current through the Is limiter are 7kA and 42kA respectively.
These values are factory set and cannot be changed by the
operator on site.
7/22/2019 Is Limiter Overview Presentation
14/23
Is Limiter Overview
BLOCKING LOGIC
The operation of the Is limiters is not activated for the
following:
-To prevent unnecessary operation of more than one Is
limiter for the same fault.
-To prevent operation of Is limiters for external gridfault.
- To prevent operation if the summation current does
not exceed the tripping value.
7/22/2019 Is Limiter Overview Presentation
15/23
Is Limiter Overview
INTER-TRIPPING TO BUS SECTION BREAKERS
The Is Limiter operates independently for each
phase. If the tripping values for one phase are
exceeded the Is Limiter for that phase only will trip.
If the tripping values for two phases are exceeded
the Is Limiters for those phases will trip.
For three phase isolation intertripping is providedsuch that tripping of the Is Limiter will trip the
associated bus section breaker.
The tripping values of the Is Limiters are set such
the circuit breaker interrupting capacity is not
exceeded.
7/22/2019 Is Limiter Overview Presentation
16/23
Is Limiter Overview
INTERLOCKING
A solenoid operated Interlocking is provided
such that the Is Limiter truck cannot be insertedor withdrawn unless both sides of the Is limiter
are de-energised.
In addition interlocking is provided such thatthe associated bus section breaker cannot be
closed unless the Is Limiter is ready for
operation.
7/22/2019 Is Limiter Overview Presentation
17/23
Is Limiter Overview
CONTROL SUPPLY
For high reliability two 110V AC supplies:
- The main power supply via voltage transformer (VT)- The Secondary power supply from UPS
These two power supplies are provided with an auto
changeover scheme. Normal operation will be with the
power supply from the voltage transformer. Upon loss
of mains power the auxiliary supply will be switched to
UPS. Similarly upon restoration of main power the
auxiliary supply will be switched back the voltage
transformer.
7/22/2019 Is Limiter Overview Presentation
18/23
Is Limiter Overview
IS LIMITER LV COMPARTMENT ALARM AND STATUSSIGNALS
Alarm and status signals are sent to PMS, logic control
panel and to the associated bus section breaker.
The followings are the interface between LV
Compartment and Logic Control Panel:
- Is Limiter Blocking
- Is Limiter Deactivation of Tripping Criteria
- Tripping Criteria Status
- Is Limiter Blocked
- Is Limiter Tripped- Is Limiter Ready
7/22/2019 Is Limiter Overview Presentation
19/23
Is Limiter Overview
TESTING
The testing of the trip values will normally becarried out by specialist engineer using vendor
supplied test inserts and testing equipment. Refer
to acceptance test procedure, vendor document
reference PTCS01A-H0191.
7/22/2019 Is Limiter Overview Presentation
20/23
Is Limiter Overview
IS LIMITER CONTROL PANEL
A logic control panel is provided to implement thematrix logic. In order to achieve high reliability the
matrix logic is implemented both by using hard wired
control relay and a PLC. If there is any discrepancy
between the hard wired logic and the PLC logic an alarmis raised.
The control panel consists of hard wired logic and the
supervisory PLC. The PLC has dual redundant processors
running in synchronism with bumpless transfer from the
primary processor to the secondary processor.
7/22/2019 Is Limiter Overview Presentation
21/23
Is Limiter Overview
In-Service/Overide Selection:
- For a fault on each Is limiter an alarm is received from
the Is Limiter cubicle to the control panel. The operator
can take the faulty Is Limiter out of service without
affecting the operation of other Is Limiters. A key
operated in-service/over-ride switch is provided for this
for each Is Limiter.
Alarms:
- PLC Watchdog Fault
- Incorrect activation/blocking criteria outputs from
hardwired control section
IS LIMITER CONTROL PANEL (Cont)
7/22/2019 Is Limiter Overview Presentation
22/23
Is Limiter Overview
- Discrepancy check of main generator/grid circuit breaker
status signals- Discrepancy between verified IS Limiter
activation/blocking status and outputs from the hardwired
relay logic
- Common fault including control supply fault of Is Limiterfault to PMS
- Is Limiter Control Panel fault to PMS
-Common alarm to the ICSS for any alarm present in the
logic control panel including the Is Limiter fault alarms.
Control Supply
- Dual UPS supplies with auto changeover.
IS LIMITER CONTROL PANEL (Cont)
7/22/2019 Is Limiter Overview Presentation
23/23
Is Limiter Overview
IS LIMITER SIMULATION
The IS limiters is simulated in a spreadsheet for a 3-
phase fault at any 11kV busbar, with the system in any
operating configuration. This will also check the Is limiter
blocking or activation of selectivity criteria, dependent on
the number of main generators/grids supplies connected
to the 11kV system. The fault currents are calculated withIS limiter operation and also ignoring Is limiter operation
in accordance with BS-EN 60909-0:2001.