P. GOPALA KRISHNAADE/400KV/APTRANSCO
INTERLOCKS
WHY INTERLOCKS
ARE REQUIRED
1. PREVENTS HUMAN MISTAKES
2. INDEPENDENCY OF REQUIREMENT BETWEEN OPERATION OF CIRCUITS AND INTERLOCKING SHOULD BE KEPT IN MIND TO ACHIEVE HIGHEST POSSIBLE RELIABULITY.
INTERLOCKS
ISOLATOR AND
EARTH SWITCH INTERLOCKS
FOR
1. SINGLE MAIN BUS WITH TRANSFER BUS SYSTEM
2. DOUBLE MAIN BUS WITH TRANSFER BUS SYSTEM
3. ONE AND HALF BREAKER SYSTEM
INTERLOCKS
STANDARD PRACTICE1. FOR BUS ISOLATON: EACH BUS HAVING BUS ISOLATOR FOR
EACH BAY.
2. FOR CB ISOLATION: CIRCUIT BREAKER HAVING BOTH SIDES ISOLATORS.
3. FOR LINE/ICT ISOLATION: LINE / ICT HAVING LINE ISOLATOR.
4. FOR BUS MAINTANENCE: EACH BUS HAVING BUS EARTH SWITCH.
5. FOR CB MAINTANENCE: EACH ISOLATOR HAVING EARTH SWITCH TOWARDS CB SIDE.
6. FOR LINE / ICT MAINTANENCE: EACH LINE / ICT HAVING LINE EARTH SWITCH.
INTERLOCKS
1. ISOLATORS ARE NO LOAD SWITCHES. THEY ARE NOT PERMITTED TO BREAK POWER CURRENT OR TO CONNECT DIFFERENT VOLTAGE SYSTEM.
2. MAKING OR BREAKING OF PARALLEL CIRCUITS IS PERMITTED.3. AN ISOLATOR CONNECTED IN SERIES WITH A CB MAY BE OPERATED
WHEN CB IS OPEN AND IF NONE OF ADJACENT EARTH SWITCHES IS CLOSED. EVEN IF ANOTHER ISOLATOR CONNECTED IN SERIES TO THE CB IS OPEN THE ISOLATOR IS NOT ALLOWED TO OPERATED UNLESS THE CB IS OPEN.
4. AN ISOLATOR CONNECTED TO A DUPLICATE BUSBAR OR AUXILIARY BUS MAY BE OPERATED IFi) NO LOAD IS CONNECTED AND NON OF THE EARTH SWITCH IS CLOSED.ii) A PARALLELING CIRCUIT TO THE ISOLATOR IS PRESENT. (ONLY THROUGH THE BUSCOUPLER FOR THE ISOLATORS THAT ARE CONNECTED TO THE TRANSFER BUS.
ISOLATORS
1. OPERATED ONLY IF THE ISOLATORS ON BOTH THE SIDES ARE OPEN.2. EARTH SWITCHES WHICH CAN EARTH AN INCOMING LINE DIRECTLY OR
THROUGH A CB CAN BE OPERATED IF AND ONLY IF THE LINE IS DEAD.
EARTH SWITCH
INTERLOCKS
SINGLE BUS & TRANSFER BUS SYSTEM
FEEDER1
BUS
TRANSFER BUS
FEEDER2
TRA
NSF
ER B
US
CO
UPL
ER
T/F-1 T/F-2
BAY1 BAY2 BAY3 BAY4 BAY5
INTERLOCKS
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-A/BAY ISOLATOR OPERATION:1. 52 CB/BAY IN OPEN CONDITION.2. 89AE/BAY EARTH SWITCH OPEN CONDITION.3. 89LE1/BAY EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.
89-A/BAY
INTERLOCK
CONTACTOR
89-LE1
OPEN
89-AE
OPEN
52 CB
OPEN
BB189E
OPEN
&
BB189EOPEN
OPEN52 CB/BAY
89-AE/BAYOPEN
OPEN
89A/BAYOPERATION
89-LE1/BAY
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-L ISOLATOR OPERATION:1. 52 CB IN OPEN CONDITION.2. 89AE EARTH SWITCH OPEN CONDITION.3. 89LE1 EARTH SWITCH OPEN CONDITION.4. 89LE2 LINE EARTH SWITCH OPEN CONDITION.
89-L
INTERLOCK
CONTACTOR
89-LE1
OPEN
89-AE
OPEN
52 CB
OPEN
&
OPEN
OPEN52 CB
89-AEOPEN
OPEN
89LOPERATION89-LE1
89-LE2
89-LE2
OPEN
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-AE EARTH SWITCH OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.
89-AE
INTERLOCK
CONTACTOR
89-A
OPEN
&OPEN
89-A
OPEN89-AEOPERATION
89-L
89-L
OPEN
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-LE1 EARTH SWITCH OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.
89-LE1
INTERLOCK
CONTACTOR
89-A
OPEN
&OPEN
89-A
OPEN89-LE1OPERATION
89-L
89-L
OPEN
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-LE2 EARTH SWITCH OPERATION:1. 89C BUS ISOLATOR OPEN CONDITION.2. 89L LINE ISOLATOR OPEN CONDITION.3. LINE DEAD CONDITION i.e U/V RELAY
OPERATED.
89-LE2
INTERLOCK
CONTACTOR
89-L
OPEN
89-C
OPEN
U/V RELAY
OPTD
&
U/V RELAYOPTD
89-COPEN
OPEN
89-LE2OPERATION
89-L
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 52 CB CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA HSTR/MTR RESET CONDITION.2. 86-GB HSTR/MTR RESET CONDITION.3. 96-BB TBC HSTR/MTR RESET CONDITION.
52-CB
INTERLOCK
CONTACTOR
96-BB
RESET
86-GB
RESET
86-GA
RESET
&
86-GARESET
86-GBRESET
RESET
52-CBREMOTEOPERATION
96-BB
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 52 CB CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.4. 89-LE1 EARTH SWITCH CLOSED CONDITION.
52CB
INTERLOCK
CONTACTOR
89-LE1
CLOSE
89-AE
CLOSE
89L
OPEN
89A
OPEN
&
89-A OPEN
OPEN89-L
89-AE CLOSE
CLOSE
52-CBLOCALOPERATION
89-LE1
LINE BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR 89-C ISOLATOR OPERATION:1. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C2. BB389E EARTH SWITCH OPEN CONDITION.3. 89LE2 EARTH SWITCH OPEN CONDITION.4. 52 TBC CB IN OPEN CONDITION.
OR1. 52 CB IN CLOSED POSITION.2. 89-A ISOLATOR CLOSED CONDITION.3. 89-L ISOLATOR CLOSED POSITION.4. 89-A/TBC BAY BUS-A ISOLATOR CLOSED POSITION.5. 89-C/TBC BAY BUS-C ISOLATOR CLOSED POSITION.6. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C7. ADDITIONAL INTERLOCK PROTECTION TRANSFERRED
MAY ALSO PUT THROUGH PROTECTION TRANSFER SWITCH.
89-A
89-C
89-AE
52-CB
89-CE
TRANSFER BUS COUPLER
LINE BAY
INTERLOCKS
FOR LINE-1
89-C/ LINE-1
FOR LINE-2
89-C/ LINE-2
FOR ICT-1
89-C/ ICT-1
FOR ICT-2
89-C/ ICT-2
FUTU
RE
BA
YS
+ VE
+ VE
TO OBTAIN A CONTACT FOR NO OTHER ISOLATOR CLOSED TO BUSBAR’C’
1. TO OBTAIN CONTACTS OF TRANSFER BUS COUPLER CIRCUIT CLOSSED IT IS PREFERED TO USE CONTACTS OF AUXILIARY RELAY ENERGISED UNDER THESE CONDITIONS.
2. TO MAKE SURE THE PROTECTION IS TRANSFERRED TO TBC CIRCUIT BREAKER BEFORE THE ISOLATOR IS CLOSSED, CONTACT OF TRIP TRANSFER SWITCH MAY BE UTILISED.
LINE BAY
89-C/ LINE-1 89-C/ LINE2 89-C/ ICT-1 89-C/ ICT-2
89-LE2LINE-1
89-LE2LINE-2
89-TE2ICT-1
89-TE2ICT-2
INTERLOCKS
89-C/BAY
INTERLOCK
CONTACTOR
NO OTHER ISOLATOR CLOSED TOBUSBAR-C
CLOSE
BB389E
OPEN
89LE2
OPEN
52CB/TBC
OPEN
NO OTHER ISOLATOR CLOSED TOBUSBAR-C
CLOSE
52CB/BAY
CLOSE CLOSE
89L/BAY
CLOSE
89A/BAY89-A/TBC
CLOSE CLOSE
89C/TBC
&
52CB/TBC OPEN
OPEN89-LE2
BB389E OPEN
CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C
&52CB/BAY CLOSE
CLOSE89-A
89L CLOSE
CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C
89-A/TBC
89-C/TBC CLOSE
CLOSETTS TRANSFER OR
OPERATION 89-C/BAY
LINE BAY
.N TTTS
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 89-A / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.
89-A/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
OPEN
89-AE/TBC
OPEN
52 CB/TBC
OPEN
BB189E
OPEN
&
BB189EOPEN
OPEN52 CB / TBC
89-AE / TBCOPEN
OPEN
89A / TBCOPERATION
89-CE / TBC
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 89-C / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB389E BUSEARTH SWITCH OPEN CONDITION.
89-C/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
OPEN
89-AE/TBC
OPEN
52 CB/TBC
OPEN
BB389E
OPEN
&
BB389EOPEN
OPEN52 CB / TBC
89-AE / TBCOPEN
OPEN
89C / TBCOPERATION
89-CE / TBC
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 89-AE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.
89-AE/TBC
INTERLOCK
CONTACTOR
89-A/TBC
OPEN
&OPEN
89-A / TBC
OPEN89-AE / TBCOPERATION
89-C/TBC
89-C/TBC
OPEN
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 89-CE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.
89-CE/TBC
INTERLOCK
CONTACTOR
89-A/TBC
OPEN
&OPEN
89-A / TBC
OPEN89-CE / TBCOPERATION
89-C/TBC
89-C/TBC
OPEN
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / TBC HSTR/MTR RESET CONDITION.2. 86-GB / TBC HSTR/MTR RESET CONDITION.3. 96-BB / TBC HSTR/MTR RESET CONDITION.
52-CB/TBC
INTERLOCK
CONTACTOR
96-BB/TBC
RESET
86-GB/TBC
RESET
86-GA/TBC
RESET
&
86-GA/TBCRESET
86-GB/TBCRESET
RESET
52-CB/TBCREMOTEOPERATION
96-BB/TBC
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE52-CB89-CE
BB389E
BB189E
TRANSFER BUS COUPLER
FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.3. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.4. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.
52CB/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
CLOSE
89-AE/TBC
CLOSE
89C/TBC
OPEN
89A/TBC
OPEN
&
89-A/TBC OPEN
OPEN89-C/ TBC
89-AE / TBC CLOSE
CLOSE
52-CB / TBCLOCALOPERATION
89-CE / TBC
TBC BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR BB189E EARTH SWITCH OPERATION:1. ALL BAYS BUS-A ISOLATORS OPEN CONDITION
89-A
89-C
89-AE
52-CB
89-CE
TRANSFER BUS COUPLER
&
89-A/BAY1 OPEN
OPEN
OPEN
BB189EOPERATION89-A/BAY2
89-A/BAYn
UP TO NO OF BAYS
BB189E
INTERLOCK
CONTACTOR
89-A / BAY n
OPEN
89-A/BAY2
OPEN
89-A /BAY1
OPENUP TO NO OF BAYS
BUS BAY
MAIN BUS(A)
TRANSFER BUS( C )
INTERLOCKS
89-A89-C
89-AE
89-L
52-CB
89-LE1
89-LE2
BB389E
BB189E
FEEDER OR
ICT OR
REACTOR
FOR BB389E EARTH SWITCH OPERATION:1. ALL BAYS BUS-C ISOLATORS OPEN CONDITION
89-A
89-C
89-AE
52-CB
89-CE
TRANSFER BUS COUPLER
&
89-C/BAY1 OPEN
OPEN
OPEN
BB389EOPERATION89-C/BAY2
89-C/BAYn
UP TO NO OF BAYS
BB389E
INTERLOCK
CONTACTOR
89-C / BAY n
OPEN
89-C/BAY2
OPEN
89-C /BAY1
OPENUP TO NO OF BAYS
BUS BAY
INTERLOCKS
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
FEEDER1
BUS-2
BUS-1
FEEDER2
TRA
NSF
ER B
US
CO
UPL
ER
T/F-1 T/F-2
BU
S C
OU
PLER
TRANSFER BUS
FEEDER3 FEEDER4
BAY1 BAY2BAY3 BAY4 BAY5
BAY6 BAY7 BAY8
INTERLOCKS
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
89-A/BAY
INTERLOCK
CONTACTOR
BB189E
OPEN
89-AE/BAY
OPEN
89LE1/BAY
OPEN
52CB/BAY
OPEN
89-A/BC
CLOSE
52 CB/BC
CLOSE
89-B/BC
CLOSE
89-B/BAY
OPEN
52CB/BAY
CLOSE
89-B/BAY
CLOSE
&
52CB/BAY OPEN
OPEN89-LE1/BAY
89-AE/BAY OPEN
OPEN
&52CB/BAY CLOSE
CLOSE89-A/BC
89-B/BC CLOSE
CLOSE
89-B/BAY CLOSE
OR &
52CB/TBC
89-B/BAY
BB189EOPEN
89-A/BAYOPERATION
FOR 89-A/BAY ISOLATOR OPERATION:
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
89-B/BAY
INTERLOCK
CONTACTOR
BB289E
OPEN
89-AE/BAY
OPEN
89LE1/BAY
OPEN
52CB/BAY
OPEN
89-A/BAY
CLOSE
52 CB/BC
CLOSE
89-B/BC
CLOSE
89-A/BAY
OPEN
52CB/BAY
CLOSE
89-A/BC
CLOSE
&
52CB/BAY OPEN
OPEN89-LE1/BAY
89-AE/BAY OPEN
OPEN
&52CB/BAY CLOSE
CLOSE89-A/BC
89-B/BC CLOSE
CLOSE
89-A/BAY CLOSE
OR &
52CB/TBC
89-A/BAY
BB289EOPEN
89-B/BAYOPERATION
FOR 89-B/BAY ISOLATOR OPERATION:
INTERLOCKS
89-C/BAY
INTERLOCK
CONTACTOR
NO OTHER ISOLATOR CLOSED TOBUSBAR-C
CLOSE
BB389E
OPEN
89LE2
OPEN
52CB/TBC
OPEN
NO OTHER ISOLATOR CLOSED TOBUSBAR-C
CLOSE
52CB/BAY
CLOSE CLOSE
89L/BAY
CLOSE
89A/BAY89-A/TBC
CLOSE CLOSE
89C/TBC
&
52CB/TBC OPEN
OPEN89-LE2/BAY
BB389E OPEN
CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C
&52CB/BAY CLOSE
89L/BAY CLOSE
CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C
89-C/TBC CLOSETTS TRANSFER OR
OPERATION 89-C/BAY
FEEDER BAY
&
CLOSE
89B/BAY
CLOSE
89B/TBC
CLOSE89-B/TBC
89-B/BAY CLOSE
&CLOSE89-A/TBC
89-A/BAY CLOSE
OR
.N TTTS
FOR 89-C/BAY ISOLATOR OPERATION:
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 89-L/BAY ISOLATOR OPERATION:
&
OPEN
OPEN52 CB/BAY
OPEN
OPEN
89L/BAYOPERATION89-LE1/BAY
89-LE2/BAY
89-L
INTERLOCK
CONTACTOR
89-LE1/BAY
OPEN
89-AE/BAY
OPEN
ICT HV TE
OPEN
89-LE2/BAY
OPEN
89-AE/BAYOPENICT HV TE
(FOR ICT ONLY)
52 CB/BAY
OPEN(FOR ICT ONLY)
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 89-AE/BAY ISOLATOR OPERATION:
&
OPEN89-L/BAY
89-A/BAY OPEN
OPEN
89-AE/BAYOPERATION
89-B/BAY
89-AE/BAY
INTERLOCK
CONTACTOR
89A/BAY
OPEN
89-L/BAY
OPEN
89-B/BAY
OPEN
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 89-LE1/BAY ISOLATOR OPERATION:
&
OPEN89-L/BAY
89-A/BAY OPEN
OPEN
89-LE1/BAYOPERATION
89-B/BAY
89-LE1/BAY
INTERLOCK
CONTACTOR
89A/BAY
OPEN
89-L/BAY
OPEN
89-B/BAY
OPEN
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 89-LE2/BAY ISOLATOR OPERATION:
&89-L/BAY OPEN
OPEN89-C/BAY
LINE U/V OPTD
OPEN
1-89LE2OPERATION
LV-89T
89-LE2
INTERLOCK
CONTACTOR
LINE U/V
OPTD
LV-89T
OPEN
89-L/BAY
OPEN
89-C/BAY
OPEN
(FOR ICT)
(FOR LINE)
(FOR ICT) (FOR LINE)
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 52 CB/BAY CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA HSTR/MTR RESET CONDITION.2. 86-GB HSTR/MTR RESET CONDITION.3. 96-BB TBC HSTR/MTR RESET CONDITION.
52-CB/BAY
INTERLOCK
CONTACTOR
96-BB
RESET
86-GB
RESET
86-GA
RESET
&
86-GARESET
86-GBRESET
RESET
52-CB/BAYREMOTEOPERATION
96-BB
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
FEEDER BAY
FOR 52 CB /BAYCIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.4. 89-LE1 EARTH SWITCH CLOSED CONDITION.
52-CB/BAY
INTERLOCK
CONTACTOR
89-LE1
CLOSE
89-AE
CLOSE
89L
OPEN
89A
OPEN
&
89-A OPEN
OPEN89-L
89-AE CLOSE
CLOSE
52-CB/BAYLOCALOPERATION
89-LE1
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 89-A / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.5. 89-B/TBC ISOLATOR OPEN CONDITION
89-A/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
OPEN
89-AE/TBC
OPEN
52 CB/TBC
OPEN
BB189E
OPEN
&
BB189EOPEN
OPEN52 CB / TBC
89-AE / TBCOPEN
OPEN89A / TBCOPERATION
89-CE / TBCOPEN89-B / TBC
89-B/TBC
OPEN
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 89-B / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB289E BUSEARTH SWITCH OPEN CONDITION.5. 89-A/TBC ISOLATOR OPEN CONDITION
89-B/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
OPEN
89-AE/TBC
OPEN
52 CB/TBC
OPEN
BB289E
OPEN
&
BB289EOPEN
OPEN52 CB / TBC
89-AE / TBCOPEN
OPEN89B / TBCOPERATION
89-CE / TBCOPEN89-A / TBC
89-A/TBC
OPEN
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 89-C / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB389E BUSEARTH SWITCH OPEN CONDITION.
89-C/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
OPEN
89-AE/TBC
OPEN
52 CB/TBC
OPEN
BB389E
OPEN
&
BB389EOPEN
OPEN52 CB / TBC
89-AE / TBCOPEN
OPEN
89C / TBCOPERATION
89-CE / TBC
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 89-AE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.
89-AE/TBC
INTERLOCK
CONTACTOR
89-B/TBC
OPEN
&OPEN
89-A / TBC
OPEN89-AE / TBCOPERATION
89-C/TBC
89-C/TBC
OPEN
OPEN89-B / TBC
OPEN
89-A/TBC
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 89-CE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.
89-CE/TBC
INTERLOCK
CONTACTOR
89-B/TBC
OPEN
&OPEN
89-A / TBC
OPEN89-CE / TBCOPERATION
89-C/TBC
89-C/TBC
OPEN
OPEN89-B / TBC
OPEN
89-A/TBC
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / TBC HSTR/MTR RESET CONDITION.2. 86-GB / TBC HSTR/MTR RESET CONDITION.3. 96-BB / TBC HSTR/MTR RESET CONDITION.
52-CB/TBC
INTERLOCK
CONTACTOR
96-BB/TBC
RESET
86-GB/TBC
RESET
86-GA/TBC
RESET
&
86-GA/TBCRESET
86-GB/TBCRESET
RESET
52-CB/TBCREMOTEOPERATION
96-BB/TBC
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
52-CB
89-CE
BB289E
BB189E
TRANSFER BUS
COUPLER
BB389E
MAIN BUS-2(B)
89-A
TBC BAY
FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.4. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.5. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.
52CB/TBC
INTERLOCK
CONTACTOR
89-CE/TBC
CLOSE
89-AE/TBC
CLOSE
89C/TBC
OPEN
89B/TBC
OPEN
&
89-A/TBC OPEN
OPEN89-C/ TBC
89-AE / TBC CLOSE
CLOSE
52-CB / TBCLOCALOPERATION
89-CE / TBC
89-B/TBCOPEN
89A/TBC
OPEN
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 89-A / BC ISOLATOR OPERATION:1. 52 CB / BC IN OPEN CONDITION.2. 89AE / BC EARTH SWITCH OPEN CONDITION.3. 89BE / BC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.
89-A/BC
INTERLOCK
CONTACTOR
89-BE/BC
OPEN
89-AE/BC
OPEN
52 CB/BC
OPEN
BB189E
OPEN
&
BB189EOPEN
OPEN52 CB / BC
89-AE / BCOPEN
OPEN
89A / BCOPERATION
89-BE / BC
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 89-B / BC ISOLATOR OPERATION:1. 52 CB / BC IN OPEN CONDITION.2. 89AE / BC EARTH SWITCH OPEN CONDITION.3. 89BE / BC EARTH SWITCH OPEN CONDITION.4. BB289E BUSEARTH SWITCH OPEN CONDITION.
89-B/BC
INTERLOCK
CONTACTOR
89-BE/BC
OPEN
89-AE/BC
OPEN
52 CB/BC
OPEN
BB289E
OPEN
&
BB289EOPEN
OPEN52 CB / BC
89-AE / BCOPEN
OPEN
89B / BCOPERATION
89-BE / BC
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 89-AE / BC EARTH SWITCH OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.
89-AE/BC
INTERLOCK
CONTACTOR
89-A/BC
OPEN
&OPEN
89-A / TBC
OPEN89-AE / BCOPERATION
89-B/TBC
89-B/BC
OPEN
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 89-BE / BC EARTH SWITCH OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.
89-BE/BC
INTERLOCK
CONTACTOR
89-A/BC
OPEN
&OPEN
89-A / BC
OPEN89-BE / BCOPERATION
89-B/BC
89-B/BC
OPEN
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 52 CB / BC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / BC HSTR/MTR RESET CONDITION.2. 86-GB / BC HSTR/MTR RESET CONDITION.3. 96-BB / BC HSTR/MTR RESET CONDITION.
52-CB/BC
INTERLOCK
CONTACTOR
96-BB/BC
RESET
86-GB/BC
RESET
86-GA/BC
RESET
&
86-GA/BCRESET
86-GB/BCRESET
RESET
52-CB/BCREMOTEOPERATION
96-BB/BC
MAIN BUS-1(A)
INTERLOCKS
89-A 89-B
89-AE 52-CB 89-BE
BB289E
BB189E
BUS COUPLER
BC BAY
MAIN BUS-2(B)
FOR 52 CB / BC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.3. 89-AE / BC EARTH SWITCH CLOSED CONDITION.4. 89-BE / BC EARTH SWITCH CLOSED CONDITION.
52CB/BC
INTERLOCK
CONTACTOR
89-BE/BC
CLOSE
89-AE/BC
CLOSE
89B/BC
OPEN
&
89-A/BC OPEN
89-AE/BC CLOSE
CLOSE
52-CB / BCLOCALOPERATION
89-BE/BC
89-B/BCOPEN
89A/BC
OPEN
MAIN BUS-1(A)
TRANSFER BUS( C )
INTERLOCKS
89-B 89-C89-AE
89-L
52-CB
89-LE1
89-LE2
BB289E
BB189E
FEEDER OR
ICT OR
REACTOROF BAY
BB389E
MAIN BUS-2(B)
89-A
BUS ES
89-B
89-AE 52-CB 89-BE
BUS COUPLER
89-A89-B 89-C
52-CB
89-CE
TRANSFER BUS
COUPLER
89-A89-AE
INTERLOCKS BUS EARTH SWITCH
&
89-A/BAY1 OPEN
OPEN
OPEN
BB189EOPERATION
89-A/BAY2
89-A/BAYn
UP TO NO OF BAYS &
89-B/BAY1 OPEN
OPEN
OPEN
BB289EOPERATION
89-B/BAY2
89-B/BAYn
UP TO NO OF BAYS &
89-C/BAY1 OPEN
OPEN
OPEN
BB389EOPERATION
89-C/BAY2
89-C/BAYn
UP TO NO OF BAYS
BB189E BB289E BB389E
BB189E
INTERLOCK
CONTACTOR
89-A / BAY n
OPEN
89-A/BAY2
OPEN
89-A /BAY1
OPENUP TO NO OF BAYS
BB289E
INTERLOCK
CONTACTOR
89-B / BAY n
OPEN
89-B/BAY2
OPEN
89-B /BAY1
OPENUP TO NO OF BAYS
BB389E
INTERLOCK
CONTACTOR
89-C / BAY n
OPEN
89-C/BAY2
OPEN
89-C /BAY1
OPENUP TO NO OF BAYS
FOR BUS EARTH SWITCH OPERATION, ALL ISOLATORS CONNECTED TO CONCERNED BUS ARE TO BE OPENED.
INTERLOCKS
I-CONFIGUARATION
FEEDER2 FEEDER4 FEEDER6 FEEDER8 FEEDER10 FEEDER12
FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11
BUS-2
BUS-1
BA
Y1B
AY2
BA
Y3
BA
Y4B
AY5
BA
Y6
BA
Y7B
AY8
BA
Y9
BA
Y10
BA
Y11
BA
Y12
BA
Y13
BA
Y14
BA
Y15
BA
Y16
BA
Y17
BA
Y18
DIA1 DIA2 DIA3 DIA4 DIA5 DIA6
INTERLOCKS
D-CONFIGUARATION
BUS-2
BUS-1
FEEDER3 FEEDER4 FEEDER7 FEEDER8 FEEDER11 FEEDER12
FEEDER1 FEEDER2 FEEDER5 FEEDER6 FEEDER9 FEEDER10
BA
Y1
BAY2
BA
Y3
BA
Y4
BAY5
BA
Y6
BA
Y7
BAY8
BA
Y9
BA
Y10
BAY11B
AY1
2
BA
Y13
BAY14
BA
Y15
BA
Y16
BAY17
BA
Y18
DIA1
DIA2
DIA3
DIA4
DIA5
DIA6
INTERLOCKS
ONE & HALF BREAKER SYSTEM
LINE 1
1-89
1-89A
1-52CB
3-89
3-89A
3-52CB
2-52CB
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
UUUU UU
LINESHUNT
REACTOR .1-PH NEUTRAL GROUNDING
REACTOR
INTERLOCKS
BB1-89E BB2-89E
1-89E
1-89AE 3-89AE
2-89AE 2-89BE
3-89E
1-89LE 3-89TE
1-89R1-89RE
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&BB189E OPEN
OPEN1-89AE
1-89E OPENOPEN
1-89OPERATION
1-52CB
1-89
INTERLOCK
CONTACTOR
1-89AE
OPEN
BB189E
OPEN
1-52 CB
OPEN
1-89E
OPEN
FOR 1-89 ISOLATOR OPERATION:
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&OPEN
1-89A
1-89 OPEN1-89E
OPERATION
1-89E
INTERLOCK
CONTACTOR
1-89A
OPEN
1-89
OPEN
FOR 1-89E ISOLATOR OPERATION:
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&
OPEN1-89AE
1-89E OPEN
OPEN
1-89AOPERATION
1-52CB
1-89A
INTERLOCK
CONTACTOR
1-89AE
OPEN
1-52 CB
OPEN
1-89E
OPEN
FOR 1-89A ISOLATOR OPERATION:
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
FOR 1-89AE EARTH SWITCH OPERATION:
&OPEN
1-89A
1-89 OPEN1-89AE
OPERATION
1-89AE
INTERLOCK
CONTACTOR
1-89A
OPEN
1-89
OPEN
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&OPEN2-52CB
1-89LE OPENOPEN
1-89LOPERATION
1-52CB
1-89L
INTERLOCK
CONTACTOR
2-52 CB
OPEN
1-89R
CLOSE
1-52 CB
OPEN
1-89LE
OPEN
FOR 1-89L ISOLATOR OPERATION:
1-89R CLOSEPUSHDC
INTERLOCK BYPASS
PB
OR
IL
INTER LOCK FACILITY:WHEN 1-89R CLOSES ONLY
PERMIT TO CLOSE 1-89L AND1-89L OPENS ONLY
PERMIT TO OPEN 1-89R.
DC INTERLOCK BYPASS PB
PUSH
IL
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&OPEN
1-89L
LINE U/V RELAY OPTD1-89LE
OPERATION
1-89LE
INTERLOCK
CONTACTOR
LINE U/V RELAY
OPTD
1-89L
OPEN
FOR 1-89LE EARTH SWITCH OPERATION:
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
&OPEN2-52CB
1-89L OPENOPEN
1-89LOPERATION
1-52CB
1-89L
INTERLOCK
CONTACTOR
2-52 CB
OPEN
1-52 CB
OPEN
1-89LE
OPEN
FOR 1-89R ISOLATOR OPERATION:
1-89RE OPEN
IL
1-89RE
OPEN
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
U UULI
NE
SHU
NT
REA
CTO
R
.
INTERLOCKS
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
BAY 1
OPEN1-89R 1-89RE
OPERATION
1-89RE
INTERLOCK
CONTACTOR
1-89R
OPEN
FOR 1-89RE EARTH SWITCH OPERATION:
INTERLOCKS BAY1
REMOTE
1-52 CB
LOCAL
1-52 CB
INTERLOCK
CONTACTOR
1-89 E
CLOSE
1-89 AE
CLOSE
&1-89E
CLOSE
CLOSE
1-52 CBLOCALOPERATION
1-89AE
LINE 1
1-89
1-89A
1-52CB
1-89L
BUS-1UUU
UUULI
NE
SHU
NT
REA
CTO
R
.
BB1-89E
1-89E
1-89AE
1-89LE
1-89R1-89RE
1-52 CB
INTERLOCK
CONTACTOR
96-BB/BAY1
RESET
86-GB/BAY1
RESET
86-GA/BAY1
RESET
&
86-GA/BAY1RESET
86-GB/BAY1RESET
RESET
1-52 CBREMOTEOPERATION
96-BB/BAY1
2-52CB
2-89A 2-89B
INTERLOCKS
2-89AE 2-89BE
BAY 2
2-89A
INTERLOCK
CONTACTOR
289-BE
OPEN
289-AE
OPEN
2-52 CB
OPEN
&
OPEN2-52 CB
289-AEOPEN
OPEN
2-89AOPERATION
289-BE
FOR 2-89A ISOLATOR OPERATION:
2-52CB
2-89A 2-89B
INTERLOCKS
2-89AE 2-89BE
BAY 2
2-89B
INTERLOCK
CONTACTOR
289-BE
OPEN
289-AE
OPEN
2-52 CB
OPEN
&
OPEN2-52 CB
289-AEOPEN
OPEN
2-89BOPERATION
289-BE
FOR 2-89B ISOLATOR OPERATION:
2-52CB
2-89A 2-89B
INTERLOCKS
2-89AE 2-89BE
BAY 2
2-89AE
INTERLOCK
CONTACTOR
289-B
OPEN
289-A
OPEN
&289-A
OPEN
OPEN2-89AEOPERATION
289-B
FOR 2-89AE EARTH SWITCH OPERATION:
2-52CB
2-89A 2-89B
INTERLOCKS
2-89AE 2-89BE
BAY 2
2-89BE
INTERLOCK
CONTACTOR
289-B
OPEN
289-A
OPEN
&289-A
OPEN
OPEN2-89BEOPERATION
289-B
FOR 2-89BE EARTH SWITCH OPERATION:
INTERLOCKS BAY2
REMOTE
2-52 CB
LOCAL
2-52 CB
INTERLOCK
CONTACTOR
2-89 BE
CLOSE
2-89 AE
CLOSE
&2-89BE
CLOSE
CLOSE
2-52 CBLOCALOPERATION
2-89AE
2-52 CB
INTERLOCK
CONTACTOR
96-BB/BAY2
RESET
86-GB/BAY2
RESET
86-GA/BAY2
RESET
&
86-GA/BAY2RESET
86-GB/BAY2RESET
RESET
2-52 CBREMOTEOPERATION
96-BB/BAY2
2-52CB
2-89A 2-89B
2-89AE 2-89BE
FOR HALF DIA ONLY
FOR HALF DIA ONLY
3-89
3-89A
3-52CB
3-89T
BUS-2
INTERLOCKSBB2-89E
3-89E
3-89AE
3-89TE
&BB289E OPEN
OPEN3-89AE
3-89E OPENOPEN
3-89OPERATION
3-52CB
3-89
INTERLOCK
CONTACTOR
3-89AE
OPEN
BB289E
OPEN
3-52 CB
OPEN
3-89E
OPEN
FOR 3-89 ISOLATOR OPERATION:
BAY 3
ICT
INTERLOCKS BAY 3
&OPEN
3-89A
3-89 OPEN3-89E
OPERATION
3-89E
INTERLOCK
CONTACTOR
3-89A
OPEN
3-89
OPEN
FOR 3-89E EARTH SWITCH OPERATION:
3-89
3-89A
3-52CB
3-89T
BUS-2BB2-89E
3-89E
3-89AE
3-89TE
ICT
3-89
3-89A
3-52CB
3-89T
BUS-2
INTERLOCKSBB2-89E
3-89E
3-89AE
3-89TE
&OPEN
3-89AE
3-89E OPENOPEN
3-89AOPERATION
3-52CB
3-89A
INTERLOCK
CONTACTOR
3-89AE
OPEN
3-52 CB
OPEN
3-89E
OPEN
FOR 3-89A ISOLATOR OPERATION:
BAY 3
ICT
INTERLOCKS BAY 3
&OPEN
3-89A
3-89 OPEN3-89AE
OPERATION
3-89AE
INTERLOCK
CONTACTOR
3-89A
OPEN
3-89
OPEN
FOR 3-89AE EARTH SWITCH OPERATION:
3-89
3-89A
3-52CB
3-89T
BUS-2BB2-89E
3-89E
3-89AE
3-89TE
ICT
3-89
3-89A
3-52CB
3-89T
BUS-2
INTERLOCKSBB2-89E
3-89E
3-89AE
3-89TE
&LV89TE2 OPEN
OPEN2-52 CB
3-89TE OPENOPEN
3-89TOPERATION
3-52CB
3-89T
INTERLOCK
CONTACTOR
2-52CB
OPEN
LV89TE2
OPEN
3-52 CB
OPEN
3-89TE
OPEN
FOR 3-89T ISOLATOR OPERATION:
BAY 3
ICT
INTERLOCKS BAY 3
&OPEN
3-89T
LV89T OPEN3-89TE
OPERATION
3-89TE
INTERLOCK
CONTACTOR
3-89T
OPEN
LV89T
OPEN
FOR 3-89TE EARTH SWITCH OPERATION:
3-89
3-89A
3-52CB
3-89T
BUS-2BB2-89E
3-89E
3-89AE
3-89TE
ICT
INTERLOCKS BAY3
REMOTE
3-52 CB
LOCAL
3-52 CB
INTERLOCK
CONTACTOR
3-89 E
CLOSE
3-89 AE
CLOSE
&3-89E
CLOSE
CLOSE
3-52 CBLOCALOPERATION
3-89AE
3-52 CB
INTERLOCK
CONTACTOR
96-BB/BAY3
RESET
86-GB/BAY3
RESET
86-GA/BAY3
RESET
&
86-GA/BAY3RESET
86-GB/BAY3RESET
RESET
3-52 CBREMOTEOPERATION
96-BB/BAY3
3-89
3-89A
3-52CB
3-89T
BUS-2BB2-89E
3-89E
3-89AE
3-89TE
ICT
INTERLOCKS BUS EARTH SWITCH
FOR BUS EARTH SWITCH OPERATION, ALL ISOLATORS
CONNECTED TO CONCERNED BUS ARE TO BE OPENED.
&
3-89/ DIA1 OPEN
BB289EOPERATION
UP TO NO OF DIAS
BB289E
6-89/ DIA2 OPEN
9-89/ DIA3 OPEN
DIA N OPEN
&
1-89/ DIA1 OPEN
BB189EOPERATION
UP TO NO OF DIAS
BB189E
4-89/ DIA2 OPEN
7-89/ DIA3 OPEN
DIA N OPEN
BB189E
INTERLOCK
CONTACTOR
DIA N
OPEN
7-89/DIA3
OPEN
4-89/DIA2
OPENUP TO NO OF DIAS
BB289E
INTERLOCK
CONTACTOR
DIA N
OPEN
9-89/DIA3
OPEN
6-89/DIA2
OPENUP TO NO OF BAYS
1-89/DIA1
OPEN
3-89/DIA1
OPEN
ISOLATOR INTERLOCKS INTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSE
BAY - 2
BAY - 3
O152 CBO189 EO189 AEOBB189 EISO1 - 891BAY - 1
EQUIPMENT-4EQUIPMENT-3EQUIPMENT-2EQUIPMENT-1ISOLATOROPEN/CLOSES.NO
------O189O189 AES1 – 89 AE4---O152 CBO189 EO189 AEISO1 – 89 A3------O189O189 AES1 – 89 E2
------AUV RELAYO189 LES1 – 89 LE6---O252 CBO152 CBO189 LEISO1 – 89 L5
------O289 AO289 BES2 – 89 AE8---O252 CBO289 AEO289 BEISO2 – 89 A7
------O289 AO289 BES2 – 89 BE10---O252 CBO289 AEO289 BEISO2 – 89 B9
O352 CBO389 EO389 AEOBB289 EISO3 – 89 11------O389O389 AES3 – 89 E12---O352 CBO389 EO389 AEISO3 – 89 A13------O389O389 AES3 – 89 AE14
------OLV89 TO389 TES3 – 89 TE16O352 CBO252 CBO389 TEOLV89 E2ISO3 – 89 T15
NOTE: All Earth Switches in the Bay are towards Circuit Breaker side only. The Line and Transformer Earth Switches are towards Line & Transformer.
O: OPENC: CLOSEA: ACTED
BB189E : BUSBAR-1 EARTH SWITCH .BB289E : BUSBAR-2EARTH SWITCH . UV RELAY: UNDER VOLTAGE RELAY.
ISOLATOR & CB INTERLOCKS
1-52CB&
OPENOPEN
OPEN
OPERATION1-89LE
2-52CB
1-89L
1-52CB
&OPENOPEN
OPENOPERATION1-89AE
1-89E
1-89A
&BB189E OPEN
OPEN1-89AE
1-89E OPENOPEN
1-89OPERATION
1-52CB
&1-89 OPENOPEN
1-89A1-89EOPERATION
2-52CB&
OPENOPEN
OPENOPERATION2-89AE
2-89BE2-89A
OPEN
&1-89OPEN
1-89A1-89AEOPERATION
&1-89L OPENACTED
U/V RLY1-89LEOPERATION
&OPERATION
OPENOPEN
OPENOPEN
BB289E
3-89AE
3-89E3-52CB
3-89
3-52CB
3-89AE&
OPENOPEN
OPEN3-89E
OPERATION3-89A
2-52CB&
OPENOPEN
OPEN
3-52CB
3-89TEOPERATION3-89T
OPEN LV89E2
OPENOPEN& 3-89
3-89AOPERATION3-89E
OPENOPEN& 3-89
3-89AOPERATION3-89AE
OPENOPEN&OPERATION3-89TE
3-89T
LV89T
OPEN &OPEN2-89A
2-89BOPERATION
2-89AEOPENOPEN &2-89A
2-89BOPERATION
2-89BE
2-52CB&
OPENOPEN
OPENOPERATION2-89AE
2-89BE2-89B
CLOSE &CLOSE1-89E
1-89AE
LOCAL CLOSE
1-52CB
CLOSE &CLOSE2-89AE
2-89BE
LOCAL CLOSE
2-52CB
CLOSE &CLOSE3-89E
3-89AE
LOCAL CLOSE
3-52CB
RESET &RESET86GR-A
86GR-BREMOTE CLOSE
1-52CBRESET96BB
RESET &RESET
86GR-A86GR-B
REMOTE CLOSE
2-52CB
RESET &RESET86GR-A
86GR-BREMOTE CLOSE
3-52CBRESET96BB