Upload
api-3704641
View
381
Download
10
Embed Size (px)
Citation preview
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
CALCULATION NOTE SHORT-CIRCUIT CURRENTS
C 09-06-06 ABV Issued for Approval AGU RKA
B 29-03-06 SBT Issued for Approval AGU RKA
A 03-02-06 SBT Issued for Comments AGU RKA
REV DATE BY DESCRIPTION CHECK APPR. SPEC. RESP.
CONTRACTOR APPROVAL COMPANY APPROVAL
STATUS CODE : IFC = Issued for comments – IFA = Issued for approval – AFC = Approved – AB = As built
TOTAL OR PARTIAL REPRODUCTION AND/OR UTILIZATION OF THIS DOCUMENT ARE FORBIDDEN WITHOUT PRIOR WRIITEN AUTHORIZATION OF THE OWNER
ACERGY - ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION Département IGP Parc Club des Aygalades - Bât. 6 35, Bd du Capitaine Gèze 13015 Marseille Tél. : 33 4 91 61 58 00 Fax : 33 4 91 61 85 74
663, av. de la 1ère Armée Française Zone portuaire de Brégaillon 83500 La Seyne-Sur-Mer Tél. : 33 4 94 11 54 00 Fax : 33 4 94 06 62 67
Acergy S.A.
1 Quai Marcel Dassault92156 Suresnes Cedex
Tél. : 33 1 40 97 60 00 Fax : 33 1 40 97 63 33 P1916 - 06574004
REVISION C
STATUS IFA
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 2 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
A B C D E F G H A B C D E F G H 1 X X X 51 2 X X X 52 3 X X X 53 4 X X X 54 5 X X X 55 6 X X X 56 7 X X X 57 8 X X X 58 9 X X X 59 10 X X X 60 11 X X X 61 12 X X X 62 13 X X 63 14 X X 64 15 X 65 16 X 66 17 X 67 18 X 68 19 X 69 20 X 70 21 X 71 22 X 72 23 X 73 24 X 74 25 X 75 26 X 76 27 X 77 28 X 78 29 X 79 30 X 80 31 X 81 32 X 82 33 X 83 34 X 84 35 X X X 85 36 X X X 86 37 X X X 87 38 X X X 88 39 X X X 89 40 X X X 90 41 X X X 91 42 X X X 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 50 100
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 3 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
TABLE OF CONTENTS
Page No.
1 FOREWORD .................................................................................................................................. 4
2 REFERENCE DOCUMENTS.......................................................................................................... 4
3 SIMPLIFYING ASSUMPTIONS...................................................................................................... 5
4 FORMULA...................................................................................................................................... 5
4.1 ALTERNATOR IMPEDANCE CALCULATION ..................................................................................... 5 4.2 CABLE IMPEDANCE CALCULATION............................................................................................... 6 4.3 CIRCUIT BREAKER IMPEDANCE ................................................................................................... 6 4.4 ASYNCHRONOUS MOTOR REVERSE CURRENT CALCULATION ........................................................ 6 4.5 SHORT-CIRCUIT CALCULATION ................................................................................................... 8
5 NETWORK MODELLING............................................................................................................... 8
5.1 ELECTRICAL NETWORK DATA ..................................................................................................... 8 5.2 NETWORK CONFIGURATIONS ...................................................................................................... 8
6 EQUIPMENT CHARACTERISTICS.............................................................................................. 10
6.1 DIESEL GENERATORS DATA...................................................................................................... 10 6.2 FEEDERS DATA........................................................................................................................ 11 6.3 PROTECTIVE DEVICES DATA ..................................................................................................... 11
7 RESULTS..................................................................................................................................... 12
7.1 CASE 1 – MAXIMUM FAULT LEVELS .......................................................................................... 12 7.2 CASE 2 – MINIMUM FAULT LEVEL IN NORMAL OPERATION............................................................ 12 7.3 CASE 3 – MINIMUM FAULT LEVEL IN EXCEPTIONAL OPERATION.................................................... 12
ATTACHMENTS
APPENDIX A – General Single Line Diagram
APPENDIX B – G1/G2/G3 Alternators Data Sheet
APPENDIX C – G4 Alternator Data Sheet
APPENDIX D – G5 Alternator Data Sheet
APPENDIX E – GS Alternator Data Sheet
APPENDIX F – BV Information Note BV NI 126A Tables
APPENDIX G – Study Case Report
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 4 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
1 FOREWORD
The purpose of this note is to evaluate the maximum peak short-circuit fault level, the maximum symmetrical short-circuit fault level and the minimum symmetrical short-circuit fault level involved at the bus bar of the new LV switchboards MS1 and MS2 as well as the existing LV switchboards MS3, MS4 and EMS for the Seaway Polaris Upgrade Of Electrical Generation Project. The overall configuration of the electrical network is shown in Appendix A.
2 REFERENCE DOCUMENTS
Manual calculations were carried out in full compliance with the following documents: Rules
Reference Title NR 467.C2 DTM R02 E Bureau Veritas
Rules for the Classification of Steel Ships - PART C Machinery, Electricity, Automation and Fire Protection Chapters 2 – ELECTRICAL INSTALLATIONS
Standards
Reference Title IEC 61363-1 Electrical installations of ships and mobile and fixed offshore
units - Part 1: procedures for calculating short-circuit currents in three-phase a.c.
IEC 60909 Short-circuit calculation in three phase a.c. system IEC 60909-1 Factor for the calculation of Sc current in 3 phase a.c. systems IEC 60909-2 Electrical equipment-data for Scc calculations Project Document
Reference Title 63772-EL-1004 rev. 14 Seaway POLARIS – General Power Distribution
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 5 of 42
ACERGY POLARIS- UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
3 SIMPLIFYING ASSUMPTIONS
The following assumptions have been taken into account to carry out the calculations: a) Calculations are done within the first half-cycle of the fault condition.
b) All the asynchronous motors have been supposed equivalent to one large (as per IEC 61363-1 definition) motor directly connected to the bus bar of the main switchboard MS1, MS4 and EMS.
c) The impedance of all bus bars is negligible.
d) The maximum peak short-circuit fault level, the maximum symmetrical short-circuit fault level and the minimum symmetrical short-circuit fault level involved at the bus bar of the new LV switchboard MS2 is equal to the one of MS1.
e) The maximum peak short-circuit at EMS is calculated when EMS is fed by MS1, considering the Generators on MS1 have a higher rating than the one connected at MS4 and the interlock between CB40 and CB20 at EMS (see APPENDIX A – General Single Line Diagram).
f) Only the minimum symmetrical short-circuit fault level involved at the bus bar of the new LV switchboards MS1/MS2 is calculated. It is considered that the network configuration upgrade has not impact on the existing LV switchboard MS3, MS4 and EMS regarding this case study (G1, G2 and G3 having a higher power rating than the existing generators).
4 FORMULA 4.1 Alternator Impedance calculation
(1)
(2)
where: XG alternator reactance (Ω) RG alternator resistance (Ω) X”dG alternator direct axis subtransient (%) RaG alternator stator resistance (%) Un alternator rated voltage (V) Sn alternator Rated Power (kVA) If the alternator stator resistance is unknown, it will be calculated as follows:
×=
×=
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 6 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
(3)
4.2 Cable Impedance Calculation
(4)
(5)
where: XCA cable reactance (Ω) RCA cable resistance (Ω) xCA linear reactance for a given section (mΩ/m). Refer to TABLE II of APPENDIX F rCA linear resistance for a given section (mΩ/m). Refer to TABLE II of APPENDIX F LCA cable length (m) nCA number of cables in parallel
4.3 Circuit Breaker Impedance
(6) XCB and RCB are determined according to the TABLE III of APPENDIX F.
where: XCB circuit breaker reactance (Ω) RCB circuit breaker resistance (Ω)
4.4 Asynchronous Motor Reverse Current calculation
As per BV NI-126A note, the following approximate values may be used for the calculation of the rated current of the equivalent asynchronous motor:
(7)
×=
×=
×=
×==
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 7 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
It is considered that the bus bars at MS1, MS4 and EMS have an asynchronous motor connected, respectively MtrEqMS1, MtrEqMS4 and MtrEMS, where:
Furthermore as per IEC 61363-1 chapter 6.3.3, the following approximate values may be used for large asynchronous motors:
Z”M = 0,16 p.u. X”M = 0,15 p.u. RM = 0,055 p.u.
(8)
(9)
(10)
(11)
(12)
(13)
where: Z”M locked rotor impedance (p.u.) X”M reactance (p.u.) RM resistance (p.u.) IrM rated current (r.m.s.) I”M subtransient short-circuit current (r.m.s.)
×≈×
+=
( )
=×≈×−
=
×≈××=
!
×=
!
+×=
!
+×=
×+++
−+×=
=
"#
×+++
+×=
=
"#
×++++
×==
"#"
$
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 8 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
IacM symmetrical short-circuit current (r.m.s.) IpM peak value of the short-circuit current (r.m.s.) n number of alternators simultaneously in service IGi rated current of the alternator No. i running (r.m.s.)
4.5 Short-circuit Calculation
(11)
(12)
where: Xt total reactance of the single-phase circuit up to the fault location Rt total resistance of the single-phase circuit up to the fault location I”k symmetrical short-circuit current (r.m.s.) Ip peak value of the short-circuit current (r.m.s.) IacM symmetrical short-circuit current of the equivalent asynchronous motor (r.m.s.) Un rated voltage (V) c short-circuit current voltage factor according to IEC 60909 Table 1.
The maximum factor is 1.00 for 230 and 400 V, 1.05 for other LV system and 1.10 for MV system
K Impedance corrective factor according to the ratio Xt/Rt (see figure 1 of APPENDIX F).
5 NETWORK MODELLING 5.1 Electrical Network Data
Frequency : 60 Hz Voltage : 460 Vac Phases : 3 ph. Grounding System : IT
5.2 Network configurations
Refer to Appendix A – General Single Line Diagram As per BV document “Rules for the Classification of Steel Ships - PART C Machinery, Electricity, Automation and Fire Protection Chapters 2 – ELECTRICAL INSTALLATIONS” at section 3, the maximum number of generators are to be evaluated without taking into consideration short-term parallel operation (e.g. for load transfer). The 3 new generators G1, G2 and G3 being operated in a 2 of 3 mode, only G1 and G2 are taken into consideration in the calculation.
%
+
××
+=
% & ××=
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 9 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
The following cases have been examined : Case 1 – Calculation of the maximum peak and symmetrical short-circuit currents at MS1, MS4, MS3 and EMS bus bars:
' G1, G2, G4 and G5 running in parallel ' CB1, CB2, CB4 and CB5 closed ' CB10 and CB11 closed ' All continuous / intermittent motor loads are connected to their respective switchboard
(MS1, MS4 and EMS) and represented by an equivalent motor MtrEqMS1, MtrEqMS4 and MtrEqEMS
' EMS switchboard fed by MS1/MS4
Case 2 – Calculation of the minimum symmetrical short-circuit current at MS1 bus bar: ' G4 or G5 running only and respectively CB4 or CB5 closed ' CB10 and CB11 closed
Case 3 - Calculation of the exceptional minimum symmetrical short-circuit current at MS1 bus bar:
' GS running only ' CB1, CB2, CB3 and CB10 opened ' MS1 fed by EMS: CB6, CB20 and CB21 closed
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 10 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
6 EQUIPMENT CHARACTERISTICS 6.1 Diesel Generators data
Refer to APPENDIX B, C, D and E.
ELECTRICAL
CHARACTERISTICS
G1 G2 G3 G4 G5 GS
Rated voltage [v] V 460 460 460 460 460 460
Frequency [Hz] F 60 60 60 60 60 60
Rated Power [kVA] S 1 987 1 987 1 987 1 800 1 800 800
Rated Mechanical Power [kW] P 1 665 1 665 1 665 - - -
Rated Electrical Power [kW] P 1 590 1 590 1 590 - - -
Rated power factor [%] Pf 0.8 0.8 0.8 0.8 0.8 0.8
Rated current [A] In 2 390 2 390 2 390 2 165 2 165 1004
Rated speed [rpm] N 900 900 900 1 800 1 800 1 200
Engine Type - Diesel Diesel Diesel Diesel Diesel Diesel
Phase Number φ 3 3 3 3 3 3
Efficiency η
at 0.8 PF
Load at 100 % [%] 95.5 95.5 95.5 94.8 95.2 -
Load at 75 % [%] 95.7 95.7 95.7 94.9 95 -
Load at 50 % [%] 95.5 95.5 95.5 94.4 - -
Load at 25 % [%] 93.5 93.5 93.5 91.6 - -
at 1.0 PF
Load at 100 % [%] 96.7 96.7 96.7 96 96.3 -
Load at 75 % [%] 96.7 96.7 96.7 95.8 95.9 -
Load at 50 % [%] 96.2 96.2 96.2 95.1 - -
Load at 25 % [%] 94 94 94 91.9 - -
Direct axis reactance ( % ) [%] Xd 154 154 154 315 351 174
Direct axis transient ( % ) [%] X’d 19.5 19.5 19.5 24.5 29 13
Direct axis sub-transient ( % ) [%] X”d 16.5 16.5 16.5 14.5 16 9
Quad. axis synchronous ( % ) [%] Xq 65.7 65.7 65.7 190 - 111
Quad. axis sub-transient ( % ) [%] X”q 19.6 19.6 19.6 19.5 - 28
Negative Sequence ( % ) [%] X2 18.1 18.1 18.1 17 - 16
Zero Sequence ( % ) [%] Xo 13 13 13 2.9 - 2
R / X"d - 0.084 0.084 0.084 0.08 0.08
Grounding - Open Open Open Open Open Open
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 11 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
6.2 Feeders data
6.3 Protective Devices data
Nota : NWxx H2 circuit breaker: Icu = 85kA at 500/690V NS100L circuit breaker: Icu = 100kA at 500/525V
ELECTRICAL
CHARACTERISTICS
Type Section
mm² Nb.
cables length
m CABLE1 Three-core 120 12 30
CABLE2 Three-core 120 12 30
CABLE3 Three-core 120 12 30
CABLE4 Three-core 120 11 25
CABLE5 Three-core 120 11 25
CABLE6 Three-core 120 5 25
CABLE10 Three-core 120 20 70
CABLE20 Three-core 120 5 60
CABLE30 Three-core 120 14 70
CABLE40 Three-core 120 5 20
ELECTRICAL
CHARACTERISTICS
Type Model Rated current A
Nb. poles
CB1 Circuit breaker
NW25H2 2 500 3
CB2 Circuit breaker
NW25H2 2 500 3
CB3 Circuit breaker
NW25H2 2 500 3
CB4 Circuit breaker
NW25H2 2 500 3
CB5 Circuit breaker
NW25H2 2 500 3
CB6 Circuit breaker
NW10H2 1 000 3
CB10 Circuit breaker
NW40H2 4 000 3
CB11 Circuit breaker
NW40H2 4 000 3
CB20 Circuit breaker
NS1000L 1 000 3
CB21 Circuit breaker
NS1000L 1 000 3
CB30 Circuit breaker
NW32H2 3 200 3
CB40 Circuit breaker
NS1000L 1 000 3
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 12 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
7 RESULTS 7.1 Case 1 – Maximum Fault Levels
According to IEC 60909 Table 1, the maximum short-circuit current voltage factor is 1.00 for 230 and 400 V, 1.05 for other LV system and 1.10 for MV system.
SWITCHBOARD I" k (kA r.m.s) IP (kA peak)
MS1 81 183 MS2 81 183 MS4 81 183 MS3 70 134 EMS 76 124
7.2 Case 2 – Minimum fault level in normal operation
According to IEC 60909 Table 1, the maximum short-circuit current voltage factor is 1.00 for 230 and 400 V, 1.05 for other LV system and 1.10 for MV system.
SWITCHBOARD I" k (kA r.m.s) IP (kA peak)
MS1 21 48
7.3 Case 3 – Minimum fault level in exceptional operation
According to IEC 60909 Table 1, the maximum short-circuit current voltage factor is 1.00 for 230 and 400 V, 1.05 for other LV system and 1.10 for MV system.
SWITCHBOARD I" k (kA r.m.s) IP (kA peak)
MS1 12 24
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 13 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : B Date : 29/03/06
APPENDIX A GENERAL SINGLE LINE DIAGRAM
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 14 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : B Date : 29/03/06
MtrEqMS1
MS4 MS1
CABLE2
G2 1987 kVA
CB2
CABLE3
G3 1987 kVA
CB3
CABLE4
G4 1800 kVA
CB4
CABLE5
G5 1800 kVA
CB5
CB30
CABLE30
MS3MS2
M
CB11 CB10
CABLE10
CB20 CB21
CABLE20
EMS
CABLE6
GS 800 kVA
CB6
CABLE1
G1 1987 kVA
CB1
Existing installation New installation Upgrade of Electrical Generation Project
MtrEqEMS
M
MtrEqMS4
M
CB40
CABLE40
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 15 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : A Date : 03/02/06
APPENDIX B
G1, G2 AND G3 DATA SHEET
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 20 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : A Date : 03/02/06
APPENDIX C
G4 DATA SHEET
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 22 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : A Date : 03/02/06
APPENDIX D
G5 DATA SHEET
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 24 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : A Date : 03/02/06
APPENDIX E
GS DATA SHEET
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 32 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : A Date : 03/02/06
APPENDIX F
BV NI-126 A TABLES
' Impedance Correction Factor K
' Approximate Minimal Impedances of Protective Devices
' Approximate Minimal Impedance of cables
Approximate minimal impedances of cables
Section mm²
Resistance mΩ/m
Reactance mΩ/m
: The values above correspond to three-core cables. For the single-core cables, the reactances vary according to the conditions of installation, one will be able to take as approximate value 1.5 times the value given for the three-core cables.
Approximate minimal impedances of protective devices
Rated Current
Devices with direct relay
switches or devices with indirect relay
Reactance mΩ/phase
Switches
Devices with relay and
blow-out coil
Resist-ance mΩ/
phase
Reactance mΩ/phase
Resistance mΩ/
phase
values to determine
in each particular
case
values to determine
in each particular
case
ACERGY
ACERGY POLARIS UPGRADE OF ELECTRICAL GENERATION
Doc. Title : SHORT-CIRCUIT CURRENTS - CALCULATION NOTE Page 35 of 42
ACERGY POLARIS - UPGRADE OF ELECTRICAL GENERATION Document : P1916 - 06574004 Revision : C Date : 31/05/06
APPENDIX G
STUDY CASE REPORT
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 1
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
PROJECT INPUT DATA
Synchronous Generator Input Data
(2) (1)
Generator Type Voltage Power Ra X"d R X Z
ID V kVA % % Ω Ω Ω
G1 Diesel 460 1 987 1,39 16,5 0,0014802 0,0175712 0,0176335
G2 Diesel 460 1 987 1,39 16,5 0,0014802 0,0175712 0,0176335
G3 Diesel 460 1 987 1,39 16,5 0,0014802 0,0175712 0,0176335
G4 Diesel 460 1 800 1,16 14,5 0,0013636 0,0170456 0,0171000
G5 Diesel 460 1 800 1,28 16 0,0015047 0,0188089 0,0188690
GS Diesel 460 800 0,72 9 0,0019044 0,0238050 0,0238811
Line / Cable Input Data
(5) (4)
Line / Cable Section #/phase Length Mat. R X Z
ID mm² m Ω Ω Ω
CABLE1 3 x 120 12 30 copper 0,0003925 0,0001900 0,0004361
CABLE2 3 x 120 12 30 copper 0,0003925 0,0001900 0,0004361
CABLE3 3 x 120 12 30 copper 0,0003925 0,0001900 0,0004361
CABLE4 3 x 120 11 25 copper 0,0003568 0,0001727 0,0003964
CABLE5 3 x 120 11 25 copper 0,0003568 0,0001727 0,0003964
CABLE6 3 x 120 5 25 copper 0,0007850 0,0003800 0,0008721
CABLE10 3 x 120 20 70 copper 0,0005495 0,0002660 0,0006105
CABLE20 3 x 120 5 60 copper 0,0018840 0,0009120 0,0020931
CABLE30 3 x 120 14 70 copper 0,0007850 0,0003800 0,0008721
CABLE40 3 x 120 5 20 copper 0,0006280 0,0003040 0,0006977
Protective Device Input Data
(6) (6)
Prot. Device Type Rating r x R X Z
ID A mΩ/phase mΩ/phase Ω Ω Ω
CB1 Circ. Break. 2 500 0,015 0,025 0,0000150 0,0000250 0,0000292
CB2 Circ. Break. 2 500 0,015 0,025 0,0000150 0,0000250 0,0000292
CB3 Circ. Break. 2 500 0,015 0,025 0,0000150 0,0000250 0,0000292
CB4 Circ. Break. 2 500 0,015 0,025 0,0000150 0,0000250 0,0000292
CB5 Circ. Break. 2 500 0,015 0,025 0,0000150 0,0000250 0,0000292
CB6 Circ. Break. 1 000 0,03 0,04 0,0000300 0,0000400 0,0000500
CB10 Circ. Break. 4 000 0,01 0,02 0,0000100 0,0000200 0,0000224
CB11 Circ. Break. 4 000 0,01 0,02 0,0000100 0,0000200 0,0000224
CB20 Circ. Break. 1 000 0,03 0,04 0,0000300 0,0000400 0,0000500
CB21 Circ. Break. 1 000 0,03 0,04 0,0000300 0,0000400 0,0000500
CB30 Circ. Break. 3 200 0,015 0,025 0,0000150 0,0000250 0,0000292
CB40 Circ. Break. 1 000 0,03 0,04 0,0000300 0,0000400 0,0000500
Nota:
' Sign “ + ” = parallel ' Sign “ . “ = series
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 2
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 1
SHORT-CIRCUIT REPORT
3-phase fault at bus: : MS1 / MS2
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 81 kA rms
X/R = 6,4
K = 2,26 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 183 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 1 992 460 1 587 0,0114746 0,0312936 0,033330964
MtrEqMS4 2 259 460 1 800 0,0101184 0,0275948 0,029391448
MtrEqEMS 502 460 400 0,0455327 0,1241768 0,132261516
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L40 CB40 CABLE40 0,0000300 0,0000400 0,0000500
CABLE40 CB21 0,0006280 0,0003040 0,0006977
CB21 EMS 0,0000300 0,0000400 0,0000500
0,0006880 0,0003840 0,0007879
L1 + L2 + MtrEqMS1 0,0008721 0,0069251 0,0069798
MtrEqEMS . L20 0,0474767 0,1251688 0,1338703
(L4 + L5 + MtrEqMS4) . L10 0,0013974 0,0071159 0,0072518
[L1 + L2 + MtrEqMS1] + [MtrEqEMS . L20 ] + [(L4 + L5 + MtrEqMS4) . L10]
0,0005310 0,0034139 0,0034549
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 3
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 1
SHORT-CIRCUIT REPORT
3-phase fault at bus: : MS4
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 81 kA rms
X/R = 6,6
K = 2,26 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 183 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 1 992 460 1 587 0,0114746 0,0312936 0,033330964
MtrEqMS4 2 259 460 1 800 0,0101184 0,0275948 0,029391448
MtrEqEMS 502 460 400 0,0455327 0,1241768 0,132261516
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L40 CB40 CABLE40 0,0000300 0,0000400 0,0000500
CABLE40 CB21 0,0006280 0,0003040 0,0006977
CB21 EMS 0,0000300 0,0000400 0,0000500
0,0006880 0,0003840 0,0007879
L4 + L5 + MtrEqMS4 0,0008279 0,0068099 0,0068600
MtrEqEMS . L40 0,0462207 0,1245608 0,1328599
(L1 + L2 + MtrEqMS1) . L10 0,0014416 0,0072311 0,0073734
[L4 + L5 + MtrEqMS4] + [MtrEqEMS . L40] + [(L1 + L2 + MtrEqMS1) . L10] 0,0005200 0,0034110 0,0034504
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 4
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 1
SHORT-CIRCUIT REPORT
3-phase fault at bus: : MS3
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 70 kA rms
X/R = 2,9
K = 1,91 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 134 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 1 992 460 1 587 0,0114746 0,0312936 0,033330964
MtrEqMS4 2 259 460 1 800 0,0101184 0,0275948 0,029391448
MtrEqEMS 502 460 400 0,0455327 0,1241768 0,132261516
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L30 CB30 CABLE30 0,0000150 0,0000250 0,0000292
CABLE30 MS3 0,0007850 0,0003800 0,0008721
0,0008000 0,0004050 0,0008967
L40 CB40 CABLE40 0,0000300 0,0000400 0,0000500
CABLE40 CB21 0,0006280 0,0003040 0,0006977
CB21 EMS 0,0000300 0,0000400 0,0000500
0,0006880 0,0003840 0,0007879
L4 + L5 + MtrEqMS4 0,0008279 0,0068099 0,0068600
MtrEqEMS . L40 0,0462207 0,1245608 0,1328599
(L1 + L2 + MtrEqMS1) . L10 0,0014416 0,0072311 0,0073734
[[L4 + L5 + MtrEqMS4] + [MtrEqEMS . L40] + [(L1 + L2 + MtrEqMS1) . L10]] .L30 0,0013200 0,0038160 0,0040379
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 5
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 1
SHORT-CIRCUIT REPORT
3-phase fault at bus: : EMS
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 76 kA rms
X/R = 3,9
K = 1,63 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 124 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 1 992 460 1 587 0,0114746 0,0312936 0,033330964
MtrEqMS4 2 259 460 1 800 0,0101184 0,0275948 0,029391448
MtrEqEMS 502 460 400 0,0455327 0,1241768 0,132261516
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L40 CB40 CABLE40 0,0000300 0,0000400 0,0000500
CABLE40 CB21 0,0006280 0,0003040 0,0006977
CB21 EMS 0,0000300 0,0000400 0,0000500
0,0006880 0,0003840 0,0007879
L1 + L2 + MtrEqMS1 0,0008721 0,0069251 0,0069798
L4 + L5 + MtrEqMS4 0,0008279 0,0068099 0,0068600
L20 + L40 0,0005082 0,0002768 0,0005787
[[ L1 + L2 + MtrEqMS1 ] + [ L4 + L5 + MtrEqMS4 ]] . [ L20 + L40 ] 0,0009329 0,0037103 0,0038258
MtrEqEMS + [ [[L1 + L2 + MtrEqMS1] + [L4 + L5 + MtrEqMS4]] . [L20 + L40] ] 0,0009141 0,0036027 0,0037169
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 6
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 2
SHORT-CIRCUIT REPORT
3-phase fault at bus: : MS1 / MS2
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 21 kA rms
X/R = 6,3
K = 2,26 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 48 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 473 460 377 0,0483244 0,1317902 0,140370573
MtrEqMS4 537 460 428 0,0425650 0,1160834 0,123641119
MtrEqEMS 119 460 95 0,1920792 0,5238383 0,557943537
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L30 CB30 CABLE30 0,0000150 0,0000250 0,0000292
CABLE30 MS3 0,0007850 0,0003800 0,0008721
0,0008000 0,0004050 0,0008967
MtrEqEMS . L20 0,1940232 0,5248303 0,5595461
(L4 + MtrEqMS4) . L10 0,0022370 0,0153192 0,0154817
[ [MtrEqMS1] + [MtrEqEMS . L20] + [(L4 + MtrEqMS4) . L10] 0,0021147 0,0133742 0,0135404
Project: SEAWAY POLARIS - UPGRADE OF ELECTRICAL GENERATION Page: 7
Location: SEAWAY POLARIS Date: 31-mai-06
Contract: 57-5E-0230 Revision: C
Study Case: Case 3
SHORT-CIRCUIT REPORT
3-phase fault at bus: : MS1 / MS2
Nominal kV = 0,460 kV
Voltage c Factor = 1,05
(14) Symmetrical short-circuit current = 12 kA rms
X/R = 5,1
K = 1,98 (APPENDIX F - Impedance Correction Factor K)
(15) Peak short-circuit current = 24 kA rms
Equivalent Asynchronous Motors Contribution
(7) (13) (12) (11)
Motor Current Voltage Power R X Z
ID A V kVA Ω Ω Ω
MtrEqMS1 210 460 167 0,1088449 0,2968417 0,316168005
MtrEqMS4 239 460 190 0,0956377 0,2608233 0,277804523
MtrEqEMS 53 460 42 0,4312721 1,1761653 1,25274115
ID From ID To ID R X Z
Ω Ω Ω
L1 G1 CABLE1 0,0014802 0,0175712 0,0176335
CABLE1 CB1 0,0003925 0,0001900 0,0004361
CB1 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L2 G2 CABLE2 0,0014802 0,0175712 0,0176335
CABLE2 CB2 0,0003925 0,0001900 0,0004361
CB2 MS1 0,0000150 0,0000250 0,0000292
0,0018877 0,0177862 0,0178861
L4 G4 CABLE4 0,0013636 0,0170456 0,0171000
CABLE4 CB4 0,0003568 0,0001727 0,0003964
CB4 MS4 0,0000150 0,0000250 0,0000292
0,0017355 0,0172433 0,0173304
L5 G5 CABLE5 0,0015047 0,0188089 0,0188690
CABLE5 CB5 0,0003568 0,0001727 0,0003964
CB5 MS4 0,0000150 0,0000250 0,0000292
0,0018765 0,0190066 0,0190990
L10 CB11 CABLE10 0,0000100 0,0000200 0,0000224
CABLE10 CB10 0,0005495 0,0002660 0,0006105
CB10 MS1 0,0000100 0,0000200 0,0000224
0,0005695 0,0003060 0,0006465
L6 GS CABLE6 0,0019044 0,0238050 0,0238811
CABLE6 CB6 0,0007850 0,0003800 0,0008721
CB6 EMS 0,0000300 0,0000400 0,0000500
0,0027194 0,0242250 0,0243772
L20 CB21 CABLE20 0,0000300 0,0000400 0,0000500
CABLE20 CB20 0,0018840 0,0009120 0,0020931
CB20 MS1 0,0000300 0,0000400 0,0000500
0,0019440 0,0009920 0,0021825
L30 CB30 CABLE30 0,0000150 0,0000250 0,0000292
CABLE30 MS3 0,0007850 0,0003800 0,0008721
0,0008000 0,0004050 0,0008967
(MtrEqEMS + L6) . L20 0,0046464 0,0247281 0,0251609
[MtrEqMS1] + [(MtrEqEMS + L6) . L20] 0,0044561 0,0228266 0,0232575