6
Date: Job Name/Location: PO No.: Architect: Engr: GC: Rep: For: File Approval Mech: Resubmit Other (Company) (Project Manager) Tag #: PQNFB17C1 ACP BACnet® Gateway Standard Features: Electrical: Power Consumption 22 VA Unit Data: 1.When combined with AC Smart Premium or PDI, 128 max devices per VNet. 2.PI485 adapter required. Contact Engineering for a list of compaƟble systems. Must follow installation instructions in the applicable LG installation manual. Notes: Optional Accessories (sold separately) Digital Output Kit PQNFP00T0 Surrounding Conditions: Operating Temperature 4 140°F Storage Temperature 4 176°F Dimensions 1011/16" W x 63/16" H x 25/8" D Maximum Number of Outdoor Units 64 (16 per VNet) •Integrates MulƟ V and select Mini and MulƟ Split systems² with third party building management systems. •BTL cerƟed (ASHRAE 1352004) BACnet® ApplicaƟon Specic Controller (BASC) •Supports registraƟon as a foreign device •20 x 4 character LCD •Indoor unit control/monitoring by groups/indoor units •Web access with user access control •OperaƟon and error history log •Forced odigital input •Nine digital inputs and four digital outputs for device interlocking Basic Unit Functions Advanced Unit Functions: Power Supply 24 VAC 60 Hz Connectivity: LG Communications 4 Channel/RS485 VNet Communications Cabling Specifications (VNet): Type 2conductor, stranded, shielded copper cable/PVC or vinyl jacket Size AWG 18 x 2 Maximum Length 3,280 ft (end to end) Description: Humidity 095% (noncondensing) For continual product development, LG reserves the right to change specifications without notice. Page 1 of 3 CTRLSBCH002US 014C02 © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com AWG American Wire Gauge Power Distribution Indicator (PDI) PQNUD1S41 Maximum Number of Devices 256 (64 per VNet¹) 1 Cover 2 RS232 Console Port 3 24 VAC Power Terminals 4 Buttons and LCD Display 5 Digital I/O and RS485 Expansion Port 6 RS485 VNet Ports 7 Mini USB Port 8 USB Port 9 SD Card Slot 10 Ethernet Port 11 Power Switch 40 VA transformer recommended. Ethernet 10/100 BASET •OperaƟon – On/O•Mode – Auto/Cool/Dry/Heat/Fan Only •Setpoint •Fan Speed – Auto/Low/Med/High/Power •Louver Swing •Two Setpoint AutoChangeover •Two Setpoint Setback •200 Programmable Schedule Events with control of setpoint, On/O, Mode, Fan Speed, Controller Lock, and Louver Swing •Temperature Setpoint Range Limit •Remote Controller Lock (All, Setpoint, Mode, Fan Speed) •Run Time Limit (Unoccupied Override) •SoŌware Device Interlocking •Manual Control and Scheduling of Digital Output Kit •Peak Control •Visual Floorplan NavigaƟon •Power DistribuƟon Indicator (PDI) (opƟonal) PI485 VNet Interface Adapter for DFS PMNFP14A0 BMS Communications BACnet/IP (AnnexJ)

Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

Date:

Job Name/Location:

PO No.:

Architect:

Engr:

GC:

Rep:

For: File

Approval

Mech:

Resubmit

Other

(Company) (Project Manager)

Tag #:

PQNFB17C1ACP BACnet® Gateway

Standard Features:

Electrical:

Power Consumption 22 VA

Unit Data:

1.When combined with AC Smart Premium or PDI, 128 max devices per V‐Net. 2.PI‐485 adapter required. Contact Engineering for a list of compa ble systems.

Must follow installation instructions in the applicable LG installation manual.

Notes:

Optional Accessories (sold separately)

Digital Output Kit ‐ PQNFP00T0

Surrounding Conditions:

Operating Temperature ‐4 ‐ 140°F

Storage Temperature ‐4 ‐ 176°F

Dimensions 10‐11/16" W x 6‐3/16" H x 2‐5/8" D

Maximum Number of Outdoor Units 64 (16 per V‐Net)

•Integrates Mul  V and select Mini and Mul  Split systems² with third party building management systems. •BTL cer fied (ASHRAE 135‐2004) BACnet® Applica on Specific Controller (B‐ASC) •Supports registra on as a foreign device •20 x 4 character LCD •Indoor unit control/monitoring by groups/indoor units •Web access with user access control •Opera on and error history log •Forced off digital input •Nine digital inputs and four digital outputs for device interlockingBasic Unit Functions

Advanced Unit Functions:

Power Supply 24 VAC 60 Hz

Connectivity:

LG Communications 4 Channel/RS‐485 V‐Net

Communications Cabling Specifications (V‐Net):

Type 2‐conductor, stranded, shielded copper cable/PVC or vinyl jacket

Size AWG 18 x 2

Maximum Length 3,280 ft (end to end)

Description:

Humidity  0‐95% (non‐condensing)

For continual product development, LG reserves the right to change specifications without notice.

Page 1 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

AWG ‐ American Wire Gauge

Power Distribution Indicator (PDI) ‐ PQNUD1S41

Maximum Number of Devices 256 (64 per V‐Net¹)

1 Cover

2 RS‐232 Console Port

3 24 VAC Power Terminals

4 Buttons and LCD Display

5 Digital I/O and RS‐485 Expansion Port

6 RS‐485 V‐Net Ports

7 Mini USB Port

8 USB Port

9 SD Card Slot

10 Ethernet Port

11 Power Switch

40 VA transformer recommended. Ethernet 10/100 BASE‐T

•Opera on – On/Off •Mode – Auto/Cool/Dry/Heat/Fan Only •Setpoint •Fan Speed – Auto/Low/Med/High/Power •Louver Swing

•Two Setpoint Auto‐Changeover •Two Setpoint Setback •200 Programmable Schedule Events with control of setpoint, On/Off, Mode, Fan Speed, Controller Lock, and Louver Swing •Temperature Setpoint Range Limit •Remote Controller Lock (All, Setpoint, Mode, Fan Speed) •Run Time Limit (Unoccupied Override) •So ware Device Interlocking •Manual Control and Scheduling of Digital Output Kit •Peak Control •Visual Floorplan Naviga on •Power Distribu on Indicator (PDI) (op onal)

PI‐485 V‐Net Interface Adapter for DFS ‐ PMNFP14A0

BMS Communications BACnet/IP (Annex‐J)

Page 2: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

Job Name/Location:

ACP BACnet® Gateway

Tag #:

Date:

PO No.:

PQNFB17C1

For continual product development, LG reserves the right to change specifications without notice.

Page 2 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

Page 3: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

Job Name/Location:

ACP BACnet® Gateway

Tag #:

Date:

PO No.:

PQNFB17C1

For continual product development, LG reserves the right to change specifications without notice.

Page 3 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

Page 4: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

CTRL‐IC‐CH‐001‐US 012J07                         Page 1 of 3  

 

 

Date: 2011‐12‐16 

Vendor Name: LG Electronics Co. Ltd 

Product Name: BNU‐BAC BACnet Gateway 

Product Model Number: PQNFB17B0 

Application Software Version: 2.00.1     Firmware Revision: 4.0     BACnet Revision: 4.0 

Product Description: This gateway converts between BACnet/IP or Modbus TCP protocol and RS‐485 LGAP (LG Aircon protocol) allowing third party control and monitoring of the LG A/C system. It has a built in web server that does not require any additional software. 

 

BACnet Standardized Device Profile (Annex L): 

 BACnet Operator Workstation (B‐OWS) 

 BACnet Building Controller (B‐BC) 

 BACnet Advanced Application Controller (B‐AAC) 

 BACnet Application Specific Controller (B‐ASC) 

 BACnet Smart Senor (B‐SS) 

 BACnet Actuator (B‐SA) 

 

BACnet Interoperability Building Blocks Supported (BIBBs) 

Data Sharing BIBBs 

Bibb Type  Supported BACnet Service  Initiate Execute

DS‐RP‐B  Data Sharing‐Read Property‐B    ReadProperty    ‐ 

DS‐RPM‐B  Data Sharing‐ReadPropertyMultiple‐B    ReadPropertyMultiple    ‐ 

DS‐WP‐B  Data Sharing‐WriteProperty‐B    WriteProperty    ‐ 

DS‐WPM‐B  Data Sharing‐WritePropertyMultiple‐B  ‐  WritePropertyMultiple    ‐ 

DS‐COV‐B  Data Sharing‐COV‐B   

SubscribeCOV    ‐ 

ConfirmedCOVNotification  ‐   

UnconfirmedCOVNotification  ‐   

 

Alarm & Event Management BIBBS 

Bibb Type  Supported BACnet Service  Initiate Execute

AE‐NI‐B  Alarm and Event‐Notification Internal‐B   ConfirmedEventNotification  ‐   

UnconfirmedEventNotification  ‐   

                                                                                                                           

 

BACnet® Protocol Implementation Conformance Statement (PICS) 

Page 5: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

CTRL‐IC‐CH‐001‐US 012J07                         Page 2 of 3  

Device Management BIBBs (1) 

Bibb Type  Supported BACnet Service  Initiate Execute

DM‐DDB‐A Device Management – Dynamic Device, Binding‐A 

 Who‐Is  ‐   

I‐Am    ‐ 

DM‐DDB‐B Device Management – Dynamic Device, Binding‐B 

 Who‐Is    ‐ 

I‐Am  ‐   

DM‐DOB‐B Device Management – Dynamic Object, Binding‐B 

 Who‐Has    ‐ 

I‐Have  ‐   

DM‐TS‐B Device Management – TimeSynchronization‐B 

  TimeSynchronization    ‐ 

DM‐UTC‐B Device Management – UTCTimeSynchronization‐B 

  UTCTimeSynchronization    ‐ 

DM‐LM‐B  Device Management‐List Manipulation‐B   AddListElement ‐

RemoveListElement ‐

 

Segmentation Capability: 

 Segmented requests supported    Window Size ‐ 16 

 Segmented responses supported    Window Size – 16 

 

Standard Object Types Supported: 

Object‐Type Dynamically Creatable 

Dynamically Deletable 

Optional Properties Supported Writable Properties 

Analog Input  No  No 

Description, Reliability, Resolution, COV Increment, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps  

N/A 

Analog Value  No  No 

Description, Reliability, Resolution, COV Increment, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps  

Present_Value 

Binary Input  No  No 

Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps  

N/A 

Binary Output  No  No 

Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps  

Present_Value 

Binary Value  No  No 

Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps  

Present_Value 

Device  No  No 

Description, Location, Max Segments Accepted, UTC Offset, Daylight Saving Status, Device Address Binding, APDU Segment Timeout, Database Revision, Active COV Subscriptions  

N/A 

Page 6: Job Name/Location: Tag - RJI Salesrji-sales.com/.../03/LG_BacNet_Submittal_PointsList... · Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0 Product

CTRL‐IC‐CH‐001‐US 012J07                         Page 3 of 3  

Object‐Type Dynamically Creatable 

Dynamically Deletable 

Optional Properties Supported Writable Properties 

Multi‐State Input  No  No 

Description, Reliability, State Text, Time Delay, Notification Class, Feedback Value,  Event Enable, Acked Transitions, Notify type, Event Time Stamps  

N/A 

Multi‐State Output 

No  No 

Description, Reliability, State Text, Time Delay, Notification Class, Feedback Value,  Event Enable, Acked Transitions, Notify type, Event Time Stamps  

Present_Value 

 

Data Link Layer Options: 

 BACnet IP, (Annex J) 

 BACnet IP, (Annex J), Foreign Device 

 ISO 8802‐3, Ethernet (Clause 7) 

 ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) 

 ANSI/ATA 878.1, RS‐485 ARCNET (Clause 8), baud rate(s) 

 MS/TP Master (Clause 9), baud rate(s): 

 MS/TP Slave (Clause 9), baud rate(s): 

 Point‐to‐Point, EIA 232 (Clause 10), baud rate(s): 

 Point‐to‐Point, modem, (Clause 10), baud rate(s): 

 LonTalk, (Clause), medium: 

 Other: 

 

Device Address Binding: 

Is static device binding supported? (This is currently necessary for two‐way communication with MS/TP slaves and 

certain devices)  

 Yes   No 

 

Networking Options: 

 Router, Clause 6 ‐ List all routing configurations, e.g., ARCNET‐Ethernet, Ethernet‐MS/TP, etc.  Annex H, BACnet Tunneling Router over IP  BACnet/IP Broadcast Management Device (BBMD) 

 Does the BBMD support registrations by foreign devices? 

 Yes   No 

 Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. 

 ANSI x 3.4     IBM™ /Microsoft, DBCS     ISO 8859‐1 

 ISO 10646 (USC‐2)   ISO 10646 (UCS‐4)       JIS C 6226 

 

If this product is a communication gateway, describe the types of non‐BACnet equipment/network(s) that the 

gateway supports: 

This gateway converts between BACnet IP or Modbus TCP protocol and RS‐485 LGAP (LG Aircon protocol) allowing 

third party control and monitoring of the LG A/C system.