Tag #:
PQNFB17C1ACP BACnet® Gateway
Standard Features:
Electrical:
Power Consumption 22 VA
Unit Data:
1.When combined with AC Smart Premium or PDI, 128 max devices per V‐Net. 2.PI‐485 adapter required. Contact Engineering for a list of compa ble systems.
Must follow installation instructions in the applicable LG installation manual.
Notes:
Optional Accessories (sold separately)
Digital Output Kit ‐ PQNFP00T0
Surrounding Conditions:
Operating Temperature ‐4 ‐ 140°F
Storage Temperature ‐4 ‐ 176°F
Dimensions 10‐11/16" W x 6‐3/16" H x 2‐5/8" D
Maximum Number of Outdoor Units 64 (16 per V‐Net)
•Integrates Mul V and select Mini and Mul Split systems² with third party building management systems. •BTL cer fied (ASHRAE 135‐2004) BACnet® Applica on Specific Controller (B‐ASC) •Supports registra on as a foreign device •20 x 4 character LCD •Indoor unit control/monitoring by groups/indoor units •Web access with user access control •Opera on and error history log •Forced off digital input •Nine digital inputs and four digital outputs for device interlockingBasic Unit Functions
Advanced Unit Functions:
Power Supply 24 VAC 60 Hz
Connectivity:
LG Communications 4 Channel/RS‐485 V‐Net
Communications Cabling Specifications (V‐Net):
Type 2‐conductor, stranded, shielded copper cable/PVC or vinyl jacket
Size AWG 18 x 2
Maximum Length 3,280 ft (end to end)
Description:
Humidity 0‐95% (non‐condensing)
For continual product development, LG reserves the right to change specifications without notice.
Page 1 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
AWG ‐ American Wire Gauge
Power Distribution Indicator (PDI) ‐ PQNUD1S41
Maximum Number of Devices 256 (64 per V‐Net¹)
1 Cover
2 RS‐232 Console Port
3 24 VAC Power Terminals
4 Buttons and LCD Display
5 Digital I/O and RS‐485 Expansion Port
6 RS‐485 V‐Net Ports
7 Mini USB Port
8 USB Port
9 SD Card Slot
10 Ethernet Port
11 Power Switch
40 VA transformer recommended. Ethernet 10/100 BASE‐T
•Opera on – On/Off •Mode – Auto/Cool/Dry/Heat/Fan Only •Setpoint •Fan Speed – Auto/Low/Med/High/Power •Louver Swing
•Two Setpoint Auto‐Changeover •Two Setpoint Setback •200 Programmable Schedule Events with control of setpoint, On/Off, Mode, Fan Speed, Controller Lock, and Louver Swing •Temperature Setpoint Range Limit •Remote Controller Lock (All, Setpoint, Mode, Fan Speed) •Run Time Limit (Unoccupied Override) •So ware Device Interlocking •Manual Control and Scheduling of Digital Output Kit •Peak Control •Visual Floorplan Naviga on •Power Distribu on Indicator (PDI) (op onal)
PI‐485 V‐Net Interface Adapter for DFS ‐ PMNFP14A0
BMS Communications BACnet/IP (Annex‐J)
Job Name/Location:
ACP BACnet® Gateway
Tag #:
Date:
PO No.:
PQNFB17C1
For continual product development, LG reserves the right to change specifications without notice.
Page 2 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Job Name/Location:
ACP BACnet® Gateway
Tag #:
Date:
PO No.:
PQNFB17C1
For continual product development, LG reserves the right to change specifications without notice.
Page 3 of 3CTRL‐SB‐CH‐002‐US 014C02© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
CTRL‐IC‐CH‐001‐US 012J07 Page 1 of 3
Date: 2011‐12‐16
Vendor Name: LG Electronics Co. Ltd
Product Name: BNU‐BAC BACnet Gateway
Product Model Number: PQNFB17B0
Application Software Version: 2.00.1 Firmware Revision: 4.0 BACnet Revision: 4.0
Product Description: This gateway converts between BACnet/IP or Modbus TCP protocol and RS‐485 LGAP (LG Aircon protocol) allowing third party control and monitoring of the LG A/C system. It has a built in web server that does not require any additional software.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B‐OWS)
BACnet Building Controller (B‐BC)
BACnet Advanced Application Controller (B‐AAC)
BACnet Application Specific Controller (B‐ASC)
BACnet Smart Senor (B‐SS)
BACnet Actuator (B‐SA)
BACnet Interoperability Building Blocks Supported (BIBBs)
Data Sharing BIBBs
Bibb Type Supported BACnet Service Initiate Execute
DS‐RP‐B Data Sharing‐Read Property‐B ReadProperty ‐
DS‐RPM‐B Data Sharing‐ReadPropertyMultiple‐B ReadPropertyMultiple ‐
DS‐WP‐B Data Sharing‐WriteProperty‐B WriteProperty ‐
DS‐WPM‐B Data Sharing‐WritePropertyMultiple‐B ‐ WritePropertyMultiple ‐
DS‐COV‐B Data Sharing‐COV‐B
SubscribeCOV ‐
ConfirmedCOVNotification ‐
UnconfirmedCOVNotification ‐
Alarm & Event Management BIBBS
Bibb Type Supported BACnet Service Initiate Execute
AE‐NI‐B Alarm and Event‐Notification Internal‐B ConfirmedEventNotification ‐
UnconfirmedEventNotification ‐
BACnet® Protocol Implementation Conformance Statement (PICS)
CTRL‐IC‐CH‐001‐US 012J07 Page 2 of 3
Device Management BIBBs (1)
Bibb Type Supported BACnet Service Initiate Execute
DM‐DDB‐A Device Management – Dynamic Device, Binding‐A
Who‐Is ‐
I‐Am ‐
DM‐DDB‐B Device Management – Dynamic Device, Binding‐B
Who‐Is ‐
I‐Am ‐
DM‐DOB‐B Device Management – Dynamic Object, Binding‐B
Who‐Has ‐
I‐Have ‐
DM‐TS‐B Device Management – TimeSynchronization‐B
TimeSynchronization ‐
DM‐UTC‐B Device Management – UTCTimeSynchronization‐B
UTCTimeSynchronization ‐
DM‐LM‐B Device Management‐List Manipulation‐B AddListElement ‐
RemoveListElement ‐
Segmentation Capability:
Segmented requests supported Window Size ‐ 16
Segmented responses supported Window Size – 16
Standard Object Types Supported:
Object‐Type Dynamically Creatable
Dynamically Deletable
Optional Properties Supported Writable Properties
Analog Input No No
Description, Reliability, Resolution, COV Increment, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps
N/A
Analog Value No No
Description, Reliability, Resolution, COV Increment, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps
Present_Value
Binary Input No No
Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps
N/A
Binary Output No No
Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps
Present_Value
Binary Value No No
Description, Reliability, Time Delay, Notification Class, High Limit, Low Limit, Deadband, Limit Enable, Event Enable, Acked Transitions, Notify type, Event Time Stamps
Present_Value
Device No No
Description, Location, Max Segments Accepted, UTC Offset, Daylight Saving Status, Device Address Binding, APDU Segment Timeout, Database Revision, Active COV Subscriptions
N/A
CTRL‐IC‐CH‐001‐US 012J07 Page 3 of 3
Object‐Type Dynamically Creatable
Dynamically Deletable
Optional Properties Supported Writable Properties
Multi‐State Input No No
Description, Reliability, State Text, Time Delay, Notification Class, Feedback Value, Event Enable, Acked Transitions, Notify type, Event Time Stamps
N/A
Multi‐State Output
No No
Description, Reliability, State Text, Time Delay, Notification Class, Feedback Value, Event Enable, Acked Transitions, Notify type, Event Time Stamps
Present_Value
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802‐3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS‐485 ARCNET (Clause 8), baud rate(s)
MS/TP Master (Clause 9), baud rate(s):
MS/TP Slave (Clause 9), baud rate(s):
Point‐to‐Point, EIA 232 (Clause 10), baud rate(s):
Point‐to‐Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause), medium:
Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two‐way communication with MS/TP slaves and
certain devices)
Yes No
Networking Options:
Router, Clause 6 ‐ List all routing configurations, e.g., ARCNET‐Ethernet, Ethernet‐MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by foreign devices?
Yes No
Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI x 3.4 IBM™ /Microsoft, DBCS ISO 8859‐1
ISO 10646 (USC‐2) ISO 10646 (UCS‐4) JIS C 6226
If this product is a communication gateway, describe the types of non‐BACnet equipment/network(s) that the
gateway supports:
This gateway converts between BACnet IP or Modbus TCP protocol and RS‐485 LGAP (LG Aircon protocol) allowing
third party control and monitoring of the LG A/C system.