On-line Motor Monitoring
Joe GeimanJoe Geiman
Baker Instrument Co.Baker Instrument Co.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 2/76
What are we really after?
Induction motor and VFD applications
Reduce unscheduled downtimeReduce unscheduled downtime
Indicates root cause analysisIndicates root cause analysis
Save $ $ $Save $ $ $
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 3/76
Motor Failure Areas:
IEEE Study EPRI Study
Motor Failure Areas:
IEEE Study EPRI Study
Bearing
44%
Rotor8%
Other
22%
Stator
26%
Bearing
41%
Other
14% Rotor9%
Stator36%
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 4/76
Motor Failure Causes:
IEEE Study
Motor Failure Causes:
IEEE Study
0%
20%
40%
60%
80%
100%
Bearing Winding
Electrical FaultMechanical Breakage
Insulation Breakdown
Overheating
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 5/76
Safety and Connecting:
Low Voltage (Less than 600V)
Motor
MCC
Load
Breaker
Step one: Running motor
Step two: STOP motor
Step three: Connect Explorer
Step four: Run and test
Step five: STOP motor
Step six: Disconnect Explorer
Explorer
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 6/76
Safety and Connecting:
Medium and High Voltage (Morethan 600V)
Motor
Load
CTs
Breaker
Step one: Motor is running
Step two: Connect Explorer CTsStep three: Connect Explorer PTs
Explorer
PTs
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 7/76
Motor
CTs
Breaker
PTs
EP
Explorer
First Energy
RC Pump
1 of 700+ EPs at one customer
Acquire Data:
Safe, Fast & Easy W/ EP-1
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 8/76
Power Quality Analysis
PQ CapabilitiesPQ Capabilities
Voltage and Current level, unbalanceVoltage and Current level, unbalance
distortionsdistortions
KvarsKvars, KVA, KW’s, Power factor, Crest, KVA, KW’s, Power factor, Crest
factor, Harmonic bar chartfactor, Harmonic bar chart ectect..
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 9/76
Motor Overheating
II22R LossesR Losses Motor CurrentsMotor Currents
100% rated Current100% rated Current 100% rated Temperature100% rated Temperature
110% rated Current110% rated Current 121% rated Temperature121% rated Temperature
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 10/76
Fan 1 hp 1740 rpm
Motor Condition: Broken Rotorbar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 11/76
Rotorbar Frequency:
slip Synchronous rotor bar freq.
% [RPM] [Hz]0.1 1798.2 59.88
0.2 1796.4 59.76
0.3 1794.6 59.64
0.4 1792.8 59.52
0.5 1791 59.4
0.6 1789.2 59.28
0.7 1787.4 59.16
0.8 1785.6 59.04
0.9 1783.8 58.92
1.0 1782 58.8
.
..
.
slip
21
synch
operat synch
fund rotorbar
RPM
RPM RPM s
s f f
Depends on SLIP!
•Harder to assess with lesser load
•Harder to assess with bigger motor
•Harder to assess with more efficient motor
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 12/76
Increasing Lines of Resolution:Increasing Lines of Resolution:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 13/76
New Rotorbar y-axis Scale
A
mAdB
l fundamenta
signaldBres
300
42log105.38
log10].[down'dB'
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 14/76
Good Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 15/76
Bad Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 16/76
Case Study 1
2A High Pressure Pump2A High Pressure Pump
ProblemProblem
Serious vibrationSerious vibration Vibration ReadingVibration Reading
•• High 7200High 7200
•• Turn off motor 7200 peek disappearsTurn off motor 7200 peek disappears
Electricians do not believe it could be a rotor barElectricians do not believe it could be a rotor bar•• They have never seen a rotor problemThey have never seen a rotor problem
•• Electricians have no way to confirm or deny theElectricians have no way to confirm or deny the
allegations of the mechanicsallegations of the mechanics
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 17/76
Show Data
2A high Pressure Pump2A high Pressure Pump
Broken Rotor BarBroken Rotor Bar
1C high Pressure Pump1C high Pressure Pump
Good Rotor BarGood Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 18/76
2A High Pressure Pump
Broken Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 19/76
2A High Pressure Pump
Broken Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 20/76
1C High Pressure Pump
Good Rotor Bar (comparison)
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 21/76
1C High Pressure Pump
Good Rotor Bar (comparison)
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 22/76
Conclusion
2A High Pressure Pump
Recommendation to customerRecommendation to customer
It appeared to be a brokenIt appeared to be a broken
All thought, only slightly into the cautionAll thought, only slightly into the caution
we questioned how saver the problemwe questioned how saver the problem
waswas
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 23/76
Results
2A High Pressure Pump3 Broken Rotor Bars
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 24/76
Results
2A High Pressure Pump3 Broken Rotor Bars
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 25/76
Case Study 2
4a PA Fan
Problem Slight vibrationProblem Slight vibration
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 26/76
Broken Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 27/76
Broken Rotor Bar
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 28/76
Case Study 3
Rotor IssueRotor Issue
Show need for higher acquisitionShow need for higher acquisition
Show other places in spectrum toShow other places in spectrum to
represent or confirm rotor issuesrepresent or confirm rotor issues
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 29/76
Low Resolution Data
No Assessment Can Be Made
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 30/76
Low Resolution Data
No Assessment Can Be Made
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 31/76
High Resolution Data
Assessment Can Be Made
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 32/76
High Resolution Data
Assessment Can Be Made
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 33/76
Results
Inspection found brazing issues at theInspection found brazing issues at the
end ring causing high resistance joints.end ring causing high resistance joints.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 34/76
Epoxy Melting Off Rotor Bars
Representing Excessive Heat
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 35/76
Cracked End Ring (Case Study 4)
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 36/76
Motor Current Signature Analysis
Values From Technical Associates. 54 – 60 dB Excellent54 – 60 dB Excellent
48 – 54 dB Good condition48 – 54 dB Good condition
42 – 48 dB Moderate condition42 – 48 dB Moderate condition
36 – 42 dB Rotor bar crack 36 – 42 dB Rotor bar crack developing ordeveloping or highhighresistance joints.resistance joints.
30 – 36 dB multiple cracked / broken30 – 36 dB multiple cracked / brokenbars or end – ringsbars or end – rings
indicatedindicated < 30 dB multiple cracked /< 30 dB multiple cracked /
broken bars orbroken bars orend-rings very likelyend-rings very likely
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 37/76
Current signature: FFT vs. DFLL
Amplitude: 20dB
Amplitude: 60dB
Resolution: 0.13Hz Resolution: 0.005Hz
FFT DFLL
Need: High Amplitude and Frequency Resolution
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 38/76
• Requires constant torque level
• Torque ripple
• Next one breaks sooner
• Current increases
• Temperature increases
• Insulation life shortens
• Typically non-immediate death
Motor Condition:
Broken Rotorbar issues
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 39/76
Motor
MCC
Load
1. frequency 2. speed
3. Torque4. Power
5. Voltage
6. Current
Chain of events:
Cause and effect
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 40/76
N
SF
F
I
I
F : Force
I : Current
: Flux
Calculating Torque:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 41/76
Flux: Generated by stator Voltage
Rotor Current: Monitored with Stator Current
T
T(t) = f( V(t), I(t) )According to Park’s theory, 1920.
RotorStator
Calculating Torque:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 42/76
Explorer showed that not all motors run at constantExplorer showed that not all motors run at constant
operating condition. The 4 motors at the center displayoperating condition. The 4 motors at the center display
a larger variability to their operation. These are thea larger variability to their operation. These are the
locations which’ motors break with unusually highlocations which’ motors break with unusually high
frequency.frequency.
• The maintenance supervisor noted that some stirringpool motors (decontamination and recycling process)break with unusually high frequency.
Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 43/76
Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 44/76
• The maintenance supervisor noted that some stirringpool motors (decontamination and recycling process)break with unusually high frequency.
• The Explorer showed that not all motors run atconstant operating condition. The 4 motors at thecenter display a larger variability to their operation.These are the locations which’ motors break withunusually high frequency.
• The Torque Ripple graphs clarified the source of theoperation’s variability.
Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 45/76
Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.
Corrective action:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 46/76
4160V submersible pump
Torque Signature:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 47/76
Torque Ripple vs. Time
Hzss period time
soccurrence
frequency 2.311.073.0
2
_
#
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 48/76
Torque Ripple vs. Time
Hzss period time
soccurrence frequency 2.3
11.073.0
2
_
#
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 49/76
Torque vs. Frequency:Mechanical Imbalance
• Investigating vibration and torque forinaccessible loads:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 50/76
Comparison of Duct-Mounted Vibration and Instantaneous
Airgap Torque Signals for Predictive Maintenance of Vane Axial
Fans .
Comparison of Duct-Mounted Vibration and Instantaneous
Airgap Torque Signals for Predictive Maintenance of Vane Axial
Fans .
Don DoanTexas Utilities
Ernesto WiedenbrugBaker Instrument Company
Don DoanDon DoanTexas UtilitiesTexas Utilities
Ernesto WiedenbrugErnesto WiedenbrugBaker Instrument CompanyBaker Instrument Company
Presented in IEEE CMD / 2005
Ulsan, Korea
Presented in IEEE CMD / 2005
Ulsan, Korea
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 51/76
Problem Application:Problem Application:
A Vane Axial Fan’s failure can result inunplanned outages, health and safety costs, and
extensive damage to surrounding equipment.
A Vane Axial Fan’s failure can result inA Vane Axial Fan’s failure can result inunplanned outages, health and safety costs, andunplanned outages, health and safety costs, and
extensive damage to surrounding equipment.extensive damage to surrounding equipment.
• Vane Axial Fans are common
in nuclear environments
• It is almost impossible to
predict bearing faults for
Vane Axial Fans.
• Vane Axial Fans are common
in nuclear environments
• It is almost impossible to
predict bearing faults forVane Axial Fans.
Nuclear Comanche Peak Station
TXU Electric
Horizontal
Application
Vertical
Application
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 52/76
Vane-axial Fan Maintenance Challenge:Vane-axial Fan Maintenance Challenge:
Application frequently called: “Fan-in-a-can”
Impossible to monitor with preferred technology
(vibration on bearing housing) Cost prohibitive to issue a “change in design”
for all Vane axial Fans for this Nuclear Power
Plant. (Nuclear Industry in U.S. average cost permeter of retrofitted wire > U$ 5,000)
Application frequently called: “Fan-in-a-can”Application frequently called: “Fan-in-a-can”
Impossible to monitor with preferred technologyImpossible to monitor with preferred technology
(vibration on bearing housing)(vibration on bearing housing) Cost prohibitive to issue a “change in design”Cost prohibitive to issue a “change in design”
for all Vane axial Fans for this Nuclear Powerfor all Vane axial Fans for this Nuclear Power
Plant. (Nuclear Industry in U.S. average cost perPlant. (Nuclear Industry in U.S. average cost permeter of retrofitted wire > U$ 5,000)meter of retrofitted wire > U$ 5,000)
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 53/76
Laboratory Investigation:Laboratory Investigation:
Set up a Vane Axial Fan in a Laboratory, and create:
• Healthy operation (baseline data)
• Advanced Bearing fault (Stage III)
Gathering Data:
• Vibration data obtained from the bearing housing – preferreddiagnostic method – (used as benchmark of planted faults).
• Accelerometers connected to the outside of the duct.
• Calculated Instantaneous Airgap Torque using Park’s theory.
Statistical Data Analysis:
• Statistical evaluation using “single sided experiment design”.
• 9 samples needed for certainties exceeding 95% and 90% for
errors type I, and type II, respectively.
Set up a Vane Axial Fan in a Laboratory, and create:Set up a Vane Axial Fan in a Laboratory, and create:
•• Healthy operation (baseline data)Healthy operation (baseline data)
•• Advanced Bearing fault (Stage III)Advanced Bearing fault (Stage III)
Gathering Data:Gathering Data:
•• Vibration data obtained from the bearing housing – preferredVibration data obtained from the bearing housing – preferreddiagnostic method – (used as benchmark of planted faults).diagnostic method – (used as benchmark of planted faults).
•• Accelerometers connected to the outside of the duct.Accelerometers connected to the outside of the duct.
•• Calculated Instantaneous Airgap Torque using Park’s theory.Calculated Instantaneous Airgap Torque using Park’s theory.
Statistical Data Analysis:Statistical Data Analysis:
•• Statistical evaluation using “single sided experiment design”.Statistical evaluation using “single sided experiment design”.•• 9 samples needed for certainties exceeding 95% and 90% for9 samples needed for certainties exceeding 95% and 90% for
errors type I, and type II, respectively.errors type I, and type II, respectively.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 54/76
Chosen Fan / Motor:Chosen Fan / Motor:
Motor: Baldor 3.7kW (5hp),
4-pole, 480V.
Fan: Aerovent 304 mm (24 in).
System used in the Exhaust of
the Electrical Control Room.
Motor: Motor: Baldor Baldor 3.7kW (5hp),3.7kW (5hp),
4-pole, 480V.4-pole, 480V.
Fan: Fan: Aerovent Aerovent 304 mm (24 in).304 mm (24 in).
System used in the Exhaust of System used in the Exhaust of
the Electrical Control Room.the Electrical Control Room.
Note: The support system of this motor/fan has a long transmission path – which may dampen
mechanical signals on their way to the duct.
Note: The support system of this motor/fan has a long transmission path – which may dampen
mechanical signals on their way to the duct.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 55/76
The “known good” Signals:The “known good” Signals:
Redundant verification: Accelerometers: 100mV/g ICP
Cognitive Systems CV395B Analyzer
Bentley Nevada ADRE 208P SWANTECH stress wave analysis
Redundant verification: Redundant verification: Accelerometers: 100mV/g ICPAccelerometers: 100mV/g ICP
Cognitive Systems CV395B AnalyzerCognitive Systems CV395B Analyzer
Bentley Nevada ADRE 208PBentley Nevada ADRE 208P SWANTECH stress wave analysisSWANTECH stress wave analysis
Additional Instrumentation
ensuring constant operating condition: Airfolow Meters Humidity Meter ThermocouplesCurrent Meters Laser tachometers
Additional Instrumentation
ensuring constant operating condition: Airfolow Meters Humidity Meter ThermocouplesCurrent Meters Laser tachometers
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 56/76
Field-friendly alternative #1:Duct-mounted Accelerometers
Field-friendly alternative #1:Duct-mounted Accelerometers
Vibration Transducers 100mV/g ICP.
Cognitive Systems Spectrum Analyzer
Accelerometers mounted directly at Mounting Rod on the Duct.
Vibration Transducers 100mV/g ICP.Vibration Transducers 100mV/g ICP.
Cognitive Systems Spectrum Analyzer Cognitive Systems Spectrum Analyzer
Accelerometers mounted directly at Mounting Rod on the Duct.Accelerometers mounted directly at Mounting Rod on the Duct.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 57/76
Field-friendly alternative #2:Torque Signature Analyzer
Field-friendly alternative #2:Torque Signature Analyzer
Explorer II (Baker Instrument Company)
Measures 3 currents and 3 voltages at MCC.
Calculates airgap torque (Park 1929).
Obtains operating speed from current and torquesignatures.
Monitoring Imbalances: 1x mechanical frequencies inairgap torque spectrum.
Explorer II (Baker Instrument Company)Explorer II (Baker Instrument Company)
Measures 3 currents and 3 voltages at MCC.Measures 3 currents and 3 voltages at MCC.
Calculates airgap torqueCalculates airgap torque (Park 1929)(Park 1929)..
Obtains operating speed from current and torqueObtains operating speed from current and torque
signatures.signatures.
Monitoring Imbalances: 1x mechanical frequencies inMonitoring Imbalances: 1x mechanical frequencies inairgap torque spectrum.airgap torque spectrum.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 58/76
• 7.6 grams create 0.39 gm (0.54 oz in) imbalance.
• Comparing amplitudes of 1 x mechanical frequenciesfor “unfaulted” vs. “faulted” data.
• 7.6 grams create 0.39 gm (0.54 oz in) imbalance.
• Comparing amplitudes of 1 x mechanical frequenciesfor “unfaulted” vs. “faulted” data.
• Start: Precision balancedfan (baseline).
• Planted Fault: 7.6 gramsimbalance.
• Start: Precision balancedfan (baseline).
• Planted Fault: 7.6 gramsimbalance.
Fault 1: Mechanical ImbalanceFault 1: Mechanical Imbalance
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 59/76
Comparison of the amplitudes of 29.9Hz (1x mechanical)frequencies for 1 set of balanced data, with one set ofimbalanced operation:
Comparison of the amplitudes of 29.9Hz (1x mechanical)Comparison of the amplitudes of 29.9Hz (1x mechanical)frequencies for 1 set of balanced data, with one set offrequencies for 1 set of balanced data, with one set of
imbalanced operation:imbalanced operation:
Fault 1: Mechanical ImbalanceFault 1: Mechanical ImbalanceResults:
Duct Accelerometer:Duct Accelerometer:
-- 99% certain that imbalanced data has higher99% certain that imbalanced data has higheramplitude.amplitude.
-- Amplitude is only 6.7% higher. Amplitude is only 6.7% higher.
Conclusion:Conclusion:This methodThis method “could” “could” be used, but the very low amplitudebe used, but the very low amplitude
gain renders it unfeasible for maintenance.gain renders it unfeasible for maintenance.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 60/76
Airgap Torque Method: Airg ap Torque Method:
99% certain that imbalanced data has higher amplitude.99% certain that imbalanced data has higher amplitude.
Amplitude is 150 times higher ( >40dB ).Amplitude is 150 times higher ( >40dB ).
Conclusion:Conclusion:
According to this experiment, this methodAccording to this experiment, this method CAN CAN bebe
used for maintenance.used for maintenance.
The large amplitude gain makes it very robust andThe large amplitude gain makes it very robust andeasy to interpret.easy to interpret.
Fault 1: Mechanical ImbalanceFault 1: Mechanical ImbalanceResults:
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 61/76
Bearing Signature Analysis•• Mechanical world:Mechanical world:
Stage II:Stage II:
nnmm = Mechanical (shaft) speed= Mechanical (shaft) speed i,k i,k = 1,2,3,…= 1,2,3,…
•• Electrical world:Electrical world:
Stage II:Stage II:
nnfundfund = fundamental electrical frequency= fundamental electrical frequency i,k i,k
= 1,2,3,…= 1,2,3,…
mn2k BPFOisFrequencieFault
fund.n2k BPFOisFrequencieFault
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 62/76
Motor Failure Areas:Bearings
Motor Failure Areas:Bearings
harm. * BPFO 2 * RPM
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 63/76
Known Good Bearing Known Outer Race Defect
Torque Spectra
BPFO Controlled Lab Test… how it works
Electrical Frequencies Removed Electrical Frequencies RemovedMarking 1 * BPFOAdding Electrical Harmonic Sidebands
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 64/76
Signal Quality:Signal Quality:
harm. * BPFO 2 * RPM Torque (Nm) Current (A)
RMS 0.5 5
Signal 0.025 0.0022
Noise 0.0012 0.0005
Torque S/N = 4.8 * betterTorque S/RMS = 125 * better
“It can be found”“It is in your face”
4 pole 5hp
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 65/76
Eccentricity in Spectrum:
•• Location:Location:
•• “1x” types:“1x” types:
•• Current signals:Current signals: f f fund. fund. ±± f f mech.mech.
•• Torque signals:Torque signals: f f mech.mech.
•• - “Bar-pass” types:- “Bar-pass” types:
•• Current signals:Current signals: nn ·· f f mech.mech. ±±11 ·· f f fund. fund. (hopefully there)(hopefully there)•• Torque signals:Torque signals: nn ·· f f mech.mech. (many times not(many times not
there)there)
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 66/76
• 4-pole motor.
• 1x = just below 30Hz.
rpm Hz s 8.17686048.29min
Eccentricity, Torque Signature:“1 x” location
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 67/76
Eccentricity, Current Signature:Eccentricity, Current Signature:“1 x” location“1 x” location
rpm Hz s 2.17656058.3060min
• 4-pole motor.
• 1x = just above 30Hz.
E i i T SiE i i
T Si
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 68/76
Eccentricity, Torque Signature:Eccentricity, Torque Signature:“Rotorbar Pass Frequency” location“Rotorbar Pass Frequency” location
• 2-pole motor. 2nd peak @ freq. just below Harmonic.
• 1920Hz / 60Hz = 32bars (1920Hz is synchronous rotorbar pass frequency)
rpm Hz
f Hzbars
Hz
s
mech
5.35936089.59
89.5932
56.1916
min
.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 69/76
Eccentricity, Current Signature:“Rotorbar Pass Frequency” location
• 2-pole motor.
•1860Hz / 60Hz + 1 = 32bars
rpm Hz
f Hzbars
Hz Hz
s
mech
5.35936089.59
89.5932
6051.1856
min
.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 70/76
“1x” locations
# of Poles Synchronous 1% slip "1x" Torque "1x" Current
[RPM] [RPM] [Hz] [Hz]2 3600 3564 59.4 0.6
4 1800 1782 29.7 30.3
6 1200 1188 19.8 40.2
8 900 891 14.85 45.15
10 720 712.8 11.88 48.12
12 600 594 9.9 50.1
.elec.1 mech fund x f f f .trq.1 mech x f f
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 71/76
Comparing Ieccent.
with T eccent.
•• T T eccent.eccent. at “expected” frequencyat “expected” frequency
•• I I eccent.eccent. at “expected” frequency – 60Hz.at “expected” frequency – 60Hz.
•• T T eccent.eccent. -28.43 dB relative amplitude.-28.43 dB relative amplitude.
•• I I eccent.eccent. -34.9 dB relative amplitude.-34.9 dB relative amplitude.
T eccent. is at the understandable location.
T eccent. has a 4.5 times larger signal.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 72/76
Demodulated Signals:Torque vs. Current
Demodulated Signals:Torque vs. Current
Demodulated Torque Demodulated Current1* RPM 2* RPM 1* RPM 2* RPM
Bad Motor #1
Bad Motor #2
Good Motor #1
Good Motor #2
3.47E-05 7.94E-05 0.00324 0.03150
4.26E-05 7.96E-05 0.00398 0.03091
2.96E-05 1.35E-05 0.00245 0.03109
3.46E-05 1.42E-05 0.00308 0.03057
Factor 1.20 5.90 1.31 1.01
Conclusions:
• Demodulated Current method does not agree with vibration’s methods.
• Demodulated Torque reacts like vibration’s methods.
• This method is independent of Motor design.
• This method does not disagree with IEEE motor scientist’s research.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 73/76
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 74/76
Input Shaft Freq.Intermediate Shaft Freq.
Output Shaft Freq.
Blade Pass Freq.
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
C C
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 75/76
1st Mesh Frequency 2 nd Mesh Frequency
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
C d II C li f d i
8/2/2019 Joe Geiman - Baker Instruments
http://slidepdf.com/reader/full/joe-geiman-baker-instruments 76/76
BPFO
BPFI + - 2 x Electrical
+ - 2 x Electrical
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
Case study II: Cooling tower fan and gear signatures.
Coal-fired power plant.
SKF 22310c