On-line Motor Monitoring

Joe GeimanJoe Geiman

Baker Instrument Co.Baker Instrument Co.

Page 2: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 2/76

What are we really after?

Induction motor and VFD applications

Reduce unscheduled downtimeReduce unscheduled downtime

Indicates root cause analysisIndicates root cause analysis

Save $ $ $Save $ $ $

Page 3: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 3/76

Motor Failure Areas:

IEEE Study EPRI Study

Motor Failure Areas:

IEEE Study EPRI Study

Bearing

44%

Rotor8%

Other

22%

Stator

26%

Bearing

41%

Other

14% Rotor9%

Stator36%

Page 4: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 4/76

Motor Failure Causes:

IEEE Study

Motor Failure Causes:

IEEE Study

0%

20%

40%

60%

80%

100%

Bearing Winding

Electrical FaultMechanical Breakage

Insulation Breakdown

Overheating

Page 5: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 5/76

Safety and Connecting:

Low Voltage (Less than 600V)

Motor

MCC

Load

Breaker

Step one: Running motor

Step two: STOP motor

Step three: Connect Explorer

Step four: Run and test

Step five: STOP motor

Step six: Disconnect Explorer

Explorer 

Page 6: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 6/76

Safety and Connecting:

Medium and High Voltage (Morethan 600V)

Motor

Load

CTs

Breaker

Step one: Motor is running

Step two: Connect Explorer CTsStep three: Connect Explorer PTs

Explorer 

PTs

Page 7: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 7/76

Motor

CTs

Breaker

PTs

EP

Explorer 

First Energy

RC Pump

1 of 700+ EPs at one customer

Acquire Data:

Safe, Fast & Easy W/ EP-1

Page 8: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 8/76

Power Quality Analysis

PQ CapabilitiesPQ Capabilities

Voltage and Current level, unbalanceVoltage and Current level, unbalance

distortionsdistortions

KvarsKvars, KVA, KW’s, Power factor, Crest, KVA, KW’s, Power factor, Crest

factor, Harmonic bar chartfactor, Harmonic bar chart ectect..

Page 9: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 9/76

Motor Overheating

II22R LossesR Losses Motor CurrentsMotor Currents

100% rated Current100% rated Current 100% rated Temperature100% rated Temperature

110% rated Current110% rated Current 121% rated Temperature121% rated Temperature

Page 10: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 10/76

Fan 1 hp 1740 rpm

Motor Condition: Broken Rotorbar

Page 11: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 11/76

Rotorbar Frequency:

slip Synchronous rotor bar freq.

% [RPM] [Hz]0.1 1798.2 59.88

0.2 1796.4 59.76

0.3 1794.6 59.64

0.4 1792.8 59.52

0.5 1791 59.4

0.6 1789.2 59.28

0.7 1787.4 59.16

0.8 1785.6 59.04

0.9 1783.8 58.92

1.0 1782 58.8

.

..

.

slip

21

synch

operat synch

 fund rotorbar 

 RPM 

 RPM  RPM s

s f  f 

Depends on SLIP!

•Harder to assess with lesser load

•Harder to assess with bigger motor

•Harder to assess with more efficient motor

Page 12: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 12/76

Increasing Lines of Resolution:Increasing Lines of Resolution:

Page 13: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 13/76

New Rotorbar y-axis Scale

 

  

 

 

  

 

 A

mAdB

l fundamenta

signaldBres

300

42log105.38

log10].[down'dB'

Page 14: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 14/76

Good Rotor Bar

Page 15: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 15/76

Bad Rotor Bar

Page 16: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 16/76

Case Study 1

2A High Pressure Pump2A High Pressure Pump

ProblemProblem

Serious vibrationSerious vibration Vibration ReadingVibration Reading

•• High 7200High 7200

•• Turn off motor 7200 peek disappearsTurn off motor 7200 peek disappears

Electricians do not believe it could be a rotor barElectricians do not believe it could be a rotor bar•• They have never seen a rotor problemThey have never seen a rotor problem

•• Electricians have no way to confirm or deny theElectricians have no way to confirm or deny the

allegations of the mechanicsallegations of the mechanics

Page 17: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 17/76

Show Data

2A high Pressure Pump2A high Pressure Pump

Broken Rotor BarBroken Rotor Bar

1C high Pressure Pump1C high Pressure Pump

Good Rotor BarGood Rotor Bar

Page 18: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 18/76

2A High Pressure Pump

Broken Rotor Bar

Page 19: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 19/76

2A High Pressure Pump

Broken Rotor Bar

Page 20: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 20/76

1C High Pressure Pump

Good Rotor Bar (comparison)

Page 21: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 21/76

1C High Pressure Pump

Good Rotor Bar (comparison)

Page 22: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 22/76

Conclusion

2A High Pressure Pump

Recommendation to customerRecommendation to customer

It appeared to be a brokenIt appeared to be a broken

All thought, only slightly into the cautionAll thought, only slightly into the caution

we questioned how saver the problemwe questioned how saver the problem

waswas

Page 23: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 23/76

Results

2A High Pressure Pump3 Broken Rotor Bars

Page 24: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 24/76

Results

2A High Pressure Pump3 Broken Rotor Bars

Page 25: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 25/76

Case Study 2

4a PA Fan

Problem Slight vibrationProblem Slight vibration

Page 26: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 26/76

Broken Rotor Bar

Page 27: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 27/76

Broken Rotor Bar

Page 28: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 28/76

Case Study 3

Rotor IssueRotor Issue

Show need for higher acquisitionShow need for higher acquisition

Show other places in spectrum toShow other places in spectrum to

represent or confirm rotor issuesrepresent or confirm rotor issues

Page 29: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 29/76

Low Resolution Data

No Assessment Can Be Made

Page 30: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 30/76

Low Resolution Data

No Assessment Can Be Made

Page 31: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 31/76

High Resolution Data

Assessment Can Be Made

Page 32: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 32/76

High Resolution Data

Assessment Can Be Made

Page 33: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 33/76

Results

Inspection found brazing issues at theInspection found brazing issues at the

end ring causing high resistance joints.end ring causing high resistance joints.

Page 34: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 34/76

Epoxy Melting Off Rotor Bars

Representing Excessive Heat

Page 35: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 35/76

Cracked End Ring (Case Study 4)

Page 36: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 36/76

Motor Current Signature Analysis

Values From Technical Associates. 54 – 60 dB Excellent54 – 60 dB Excellent

48 – 54 dB Good condition48 – 54 dB Good condition

42 – 48 dB Moderate condition42 – 48 dB Moderate condition

36 – 42 dB Rotor bar crack 36 – 42 dB Rotor bar crack developing ordeveloping or highhighresistance joints.resistance joints.

30 – 36 dB multiple cracked / broken30 – 36 dB multiple cracked / brokenbars or end – ringsbars or end – rings

indicatedindicated < 30 dB multiple cracked /< 30 dB multiple cracked /

broken bars orbroken bars orend-rings very likelyend-rings very likely

Page 37: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 37/76

Current signature: FFT vs. DFLL

Amplitude: 20dB

Amplitude: 60dB

Resolution: 0.13Hz Resolution: 0.005Hz

FFT DFLL

Need: High Amplitude and Frequency Resolution

Page 38: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 38/76

• Requires constant torque level

• Torque ripple

• Next one breaks sooner

• Current increases

• Temperature increases

• Insulation life shortens

• Typically non-immediate death

Motor Condition:

Broken Rotorbar issues

Page 39: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 39/76

Motor

MCC

Load

1. frequency 2. speed

3. Torque4. Power

5. Voltage

6. Current

Chain of events:

Cause and effect

Page 40: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 40/76

N

SF

F

I

I

F : Force

I : Current

: Flux

Calculating Torque:

Page 41: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 41/76

Flux: Generated by stator Voltage

Rotor Current: Monitored with Stator Current

T

T(t) = f( V(t), I(t) )According to Park’s theory, 1920.

RotorStator

Calculating Torque:

Page 42: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 42/76

Explorer showed that not all motors run at constantExplorer showed that not all motors run at constant

operating condition. The 4 motors at the center displayoperating condition. The 4 motors at the center display

a larger variability to their operation. These are thea larger variability to their operation. These are the

locations which’ motors break with unusually highlocations which’ motors break with unusually high

frequency.frequency.

• The maintenance supervisor noted that some stirringpool motors (decontamination and recycling process)break with unusually high frequency.

Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.

Page 43: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 43/76

Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.

Page 44: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 44/76

• The maintenance supervisor noted that some stirringpool motors (decontamination and recycling process)break with unusually high frequency.

• The Explorer showed that not all motors run atconstant operating condition. The 4 motors at thecenter display a larger variability to their operation.These are the locations which’ motors break withunusually high frequency.

• The Torque Ripple graphs clarified the source of theoperation’s variability.

Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.

Page 45: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 45/76

Case study I: Hydro-mechanical resonance. Brewery.Case study I: Hydro-mechanical resonance. Brewery.

Corrective action:

Page 46: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 46/76

4160V submersible pump

Torque Signature:

Page 47: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 47/76

Torque Ripple vs. Time

 Hzss period time

soccurrence

 frequency 2.311.073.0

2

_

#

Page 48: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 48/76

Torque Ripple vs. Time

 Hzss period time

soccurrence frequency 2.3

11.073.0

2

_

#

Page 49: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 49/76

Torque vs. Frequency:Mechanical Imbalance

• Investigating vibration and torque forinaccessible loads:

Page 50: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 50/76

Comparison of Duct-Mounted Vibration and Instantaneous

Airgap Torque Signals for Predictive Maintenance of Vane Axial

Fans .

Comparison of Duct-Mounted Vibration and Instantaneous

Airgap Torque Signals for Predictive Maintenance of Vane Axial

Fans .

Don DoanTexas Utilities

Ernesto WiedenbrugBaker Instrument Company

Don DoanDon DoanTexas UtilitiesTexas Utilities

Ernesto WiedenbrugErnesto WiedenbrugBaker Instrument CompanyBaker Instrument Company

Presented in IEEE CMD / 2005

Ulsan, Korea

Presented in IEEE CMD / 2005

Ulsan, Korea

Page 51: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 51/76

Problem Application:Problem Application:

A Vane Axial Fan’s failure can result inunplanned outages, health and safety costs, and

extensive damage to surrounding equipment.

A Vane Axial Fan’s failure can result inA Vane Axial Fan’s failure can result inunplanned outages, health and safety costs, andunplanned outages, health and safety costs, and

extensive damage to surrounding equipment.extensive damage to surrounding equipment.

• Vane Axial Fans are common

in nuclear environments

• It is almost impossible to

predict bearing faults for

Vane Axial Fans.

• Vane Axial Fans are common

in nuclear environments

• It is almost impossible to

predict bearing faults forVane Axial Fans.

Nuclear Comanche Peak Station

TXU Electric

Horizontal

Application

Vertical

Application

Page 52: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 52/76

Vane-axial Fan Maintenance Challenge:Vane-axial Fan Maintenance Challenge:

Application frequently called: “Fan-in-a-can”

Impossible to monitor with preferred technology

(vibration on bearing housing) Cost prohibitive to issue a “change in design”

for all Vane axial Fans for this Nuclear Power

Plant. (Nuclear Industry in U.S. average cost permeter of retrofitted wire > U$ 5,000)

Application frequently called: “Fan-in-a-can”Application frequently called: “Fan-in-a-can”

Impossible to monitor with preferred technologyImpossible to monitor with preferred technology

(vibration on bearing housing)(vibration on bearing housing) Cost prohibitive to issue a “change in design”Cost prohibitive to issue a “change in design”

for all Vane axial Fans for this Nuclear Powerfor all Vane axial Fans for this Nuclear Power

Plant. (Nuclear Industry in U.S. average cost perPlant. (Nuclear Industry in U.S. average cost permeter of retrofitted wire > U$ 5,000)meter of retrofitted wire > U$ 5,000)

Page 53: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 53/76

Laboratory Investigation:Laboratory Investigation:

Set up a Vane Axial Fan in a Laboratory, and create:

• Healthy operation (baseline data)

• Advanced Bearing fault (Stage III)

Gathering Data:

• Vibration data obtained from the bearing housing – preferreddiagnostic method – (used as benchmark of planted faults).

• Accelerometers connected to the outside of the duct.

• Calculated Instantaneous Airgap Torque using Park’s theory.

Statistical Data Analysis:

• Statistical evaluation using “single sided experiment design”.

• 9 samples needed for certainties exceeding 95% and 90% for

errors type I, and type II, respectively.

Set up a Vane Axial Fan in a Laboratory, and create:Set up a Vane Axial Fan in a Laboratory, and create:

•• Healthy operation (baseline data)Healthy operation (baseline data)

•• Advanced Bearing fault (Stage III)Advanced Bearing fault (Stage III)

Gathering Data:Gathering Data:

•• Vibration data obtained from the bearing housing – preferredVibration data obtained from the bearing housing – preferreddiagnostic method – (used as benchmark of planted faults).diagnostic method – (used as benchmark of planted faults).

•• Accelerometers connected to the outside of the duct.Accelerometers connected to the outside of the duct.

•• Calculated Instantaneous Airgap Torque using Park’s theory.Calculated Instantaneous Airgap Torque using Park’s theory.

Statistical Data Analysis:Statistical Data Analysis:

•• Statistical evaluation using “single sided experiment design”.Statistical evaluation using “single sided experiment design”.•• 9 samples needed for certainties exceeding 95% and 90% for9 samples needed for certainties exceeding 95% and 90% for

errors type I, and type II, respectively.errors type I, and type II, respectively.

Page 54: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 54/76

Chosen Fan / Motor:Chosen Fan / Motor:

Motor: Baldor 3.7kW (5hp),

4-pole, 480V.

Fan: Aerovent 304 mm (24 in).

System used in the Exhaust of 

the Electrical Control Room.

Motor: Motor:  Baldor Baldor  3.7kW (5hp),3.7kW (5hp),

4-pole, 480V.4-pole, 480V.

Fan: Fan:  Aerovent Aerovent  304 mm (24 in).304 mm (24 in).

System used in the Exhaust of System used in the Exhaust of 

the Electrical Control Room.the Electrical Control Room.

Note: The support system of this motor/fan has a long transmission path – which may dampen 

mechanical signals on their way to the duct.

Note: The support system of this motor/fan has a long transmission path – which may dampen 

mechanical signals on their way to the duct.

Page 55: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 55/76

The “known good” Signals:The “known good” Signals:

Redundant verification:  Accelerometers: 100mV/g ICP

Cognitive Systems CV395B Analyzer

Bentley Nevada ADRE 208P SWANTECH stress wave analysis

Redundant verification: Redundant verification:  Accelerometers: 100mV/g ICPAccelerometers: 100mV/g ICP

Cognitive Systems CV395B AnalyzerCognitive Systems CV395B Analyzer

Bentley Nevada ADRE 208PBentley Nevada ADRE 208P SWANTECH stress wave analysisSWANTECH stress wave analysis

Additional Instrumentation 

ensuring constant operating condition: Airfolow Meters Humidity Meter ThermocouplesCurrent Meters Laser tachometers

Additional Instrumentation 

ensuring constant operating condition: Airfolow Meters Humidity Meter ThermocouplesCurrent Meters Laser tachometers

Page 56: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 56/76

Field-friendly alternative #1:Duct-mounted Accelerometers

Field-friendly alternative #1:Duct-mounted Accelerometers

Vibration Transducers 100mV/g ICP.

Cognitive Systems Spectrum Analyzer 

Accelerometers mounted directly at Mounting Rod on the Duct.

Vibration Transducers 100mV/g ICP.Vibration Transducers 100mV/g ICP.

Cognitive Systems Spectrum Analyzer Cognitive Systems Spectrum Analyzer 

Accelerometers mounted directly at Mounting Rod on the Duct.Accelerometers mounted directly at Mounting Rod on the Duct.

Page 57: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 57/76

Field-friendly alternative #2:Torque Signature Analyzer

Field-friendly alternative #2:Torque Signature Analyzer

Explorer II (Baker Instrument Company)

Measures 3 currents and 3 voltages at MCC.

Calculates airgap torque (Park 1929).

Obtains operating speed from current and torquesignatures.

Monitoring Imbalances: 1x mechanical frequencies inairgap torque spectrum.

Explorer II (Baker Instrument Company)Explorer II (Baker Instrument Company)

Measures 3 currents and 3 voltages at MCC.Measures 3 currents and 3 voltages at MCC.

Calculates airgap torqueCalculates airgap torque (Park 1929)(Park 1929)..

Obtains operating speed from current and torqueObtains operating speed from current and torque

signatures.signatures.

Monitoring Imbalances: 1x mechanical frequencies inMonitoring Imbalances: 1x mechanical frequencies inairgap torque spectrum.airgap torque spectrum.

Page 58: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 58/76

• 7.6 grams create 0.39 gm (0.54 oz in) imbalance.

• Comparing amplitudes of 1 x mechanical frequenciesfor “unfaulted” vs. “faulted” data.

• 7.6 grams create 0.39 gm (0.54 oz in) imbalance.

• Comparing amplitudes of 1 x mechanical frequenciesfor “unfaulted” vs. “faulted” data.

• Start: Precision balancedfan (baseline).

• Planted Fault: 7.6 gramsimbalance.

• Start: Precision balancedfan (baseline).

• Planted Fault: 7.6 gramsimbalance.

Fault 1: Mechanical ImbalanceFault 1: Mechanical Imbalance

Page 59: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 59/76

Comparison of the amplitudes of 29.9Hz (1x mechanical)frequencies for 1 set of balanced data, with one set ofimbalanced operation:

Comparison of the amplitudes of 29.9Hz (1x mechanical)Comparison of the amplitudes of 29.9Hz (1x mechanical)frequencies for 1 set of balanced data, with one set offrequencies for 1 set of balanced data, with one set of

imbalanced operation:imbalanced operation:

Fault 1: Mechanical ImbalanceFault 1: Mechanical ImbalanceResults:

Duct Accelerometer:Duct Accelerometer:

-- 99% certain that imbalanced data has higher99% certain that imbalanced data has higheramplitude.amplitude.

-- Amplitude is only 6.7% higher. Amplitude is only 6.7% higher.

Conclusion:Conclusion:This methodThis method “could” “could” be used, but the very low amplitudebe used, but the very low amplitude

gain renders it unfeasible for maintenance.gain renders it unfeasible for maintenance.

Page 60: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 60/76

Airgap Torque Method: Airg ap Torque Method: 

99% certain that imbalanced data has higher amplitude.99% certain that imbalanced data has higher amplitude.

Amplitude is 150 times higher ( >40dB ).Amplitude is 150 times higher ( >40dB ).

Conclusion:Conclusion:

According to this experiment, this methodAccording to this experiment, this method CAN CAN bebe

used for maintenance.used for maintenance.

The large amplitude gain makes it very robust andThe large amplitude gain makes it very robust andeasy to interpret.easy to interpret.

Fault 1: Mechanical ImbalanceFault 1: Mechanical ImbalanceResults:

Page 61: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 61/76

Bearing Signature Analysis•• Mechanical world:Mechanical world:

Stage II:Stage II:

nnmm = Mechanical (shaft) speed= Mechanical (shaft) speed i,k i,k = 1,2,3,…= 1,2,3,…

•• Electrical world:Electrical world:

Stage II:Stage II:

nnfundfund = fundamental electrical frequency= fundamental electrical frequency i,k i,k 

= 1,2,3,…= 1,2,3,…

mn2k BPFOisFrequencieFault

fund.n2k BPFOisFrequencieFault

Page 62: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 62/76

Motor Failure Areas:Bearings

Motor Failure Areas:Bearings

harm. * BPFO 2 * RPM

Page 63: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 63/76

Known Good Bearing Known Outer Race Defect

Torque Spectra

BPFO Controlled Lab Test… how it works

Electrical Frequencies Removed Electrical Frequencies RemovedMarking 1 * BPFOAdding Electrical Harmonic Sidebands

Page 64: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 64/76

Signal Quality:Signal Quality:

harm. * BPFO 2 * RPM Torque (Nm) Current (A)

RMS 0.5 5

Signal 0.025 0.0022

Noise 0.0012 0.0005

Torque S/N = 4.8 * betterTorque S/RMS = 125 * better

“It can be found”“It is in your face”

4 pole 5hp

Page 65: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 65/76

Eccentricity in Spectrum:

•• Location:Location:

•• “1x” types:“1x” types:

•• Current signals:Current signals: f  f  fund. fund. ±± f  f mech.mech.

•• Torque signals:Torque signals: f  f mech.mech.

•• - “Bar-pass” types:- “Bar-pass” types:

•• Current signals:Current signals: nn ·· f  f mech.mech. ±±11 ·· f  f  fund. fund. (hopefully there)(hopefully there)•• Torque signals:Torque signals: nn ·· f  f mech.mech. (many times not(many times not

there)there)

Page 66: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 66/76

• 4-pole motor.

• 1x = just below 30Hz.

rpm Hz s 8.17686048.29min

Eccentricity, Torque Signature:“1 x” location

Page 67: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 67/76

Eccentricity, Current Signature:Eccentricity, Current Signature:“1 x” location“1 x” location

rpm Hz s 2.17656058.3060min

• 4-pole motor.

• 1x = just above 30Hz.

E i i T SiE i i

T Si

Page 68: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 68/76

Eccentricity, Torque Signature:Eccentricity, Torque Signature:“Rotorbar Pass Frequency” location“Rotorbar Pass Frequency” location

• 2-pole motor. 2nd peak @ freq. just below Harmonic.

• 1920Hz / 60Hz = 32bars (1920Hz is synchronous rotorbar pass frequency)

rpm Hz

 f  Hzbars

 Hz

s

mech

5.35936089.59

89.5932

56.1916

min

.

Page 69: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 69/76

Eccentricity, Current Signature:“Rotorbar Pass Frequency” location

• 2-pole motor.

•1860Hz / 60Hz + 1 = 32bars

rpm Hz

 f  Hzbars

 Hz Hz

s

mech

5.35936089.59

89.5932

6051.1856

min

.

Page 70: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 70/76

“1x” locations

# of Poles Synchronous 1% slip "1x" Torque "1x" Current

[RPM] [RPM] [Hz] [Hz]2 3600 3564 59.4 0.6

4 1800 1782 29.7 30.3

6 1200 1188 19.8 40.2

8 900 891 14.85 45.15

10 720 712.8 11.88 48.12

12 600 594 9.9 50.1

.elec.1 mech fund  x f  f  f  .trq.1 mech x f  f 

Page 71: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 71/76

Comparing Ieccent.

with T eccent.

•• T  T  eccent.eccent. at “expected” frequencyat “expected” frequency

•• I I eccent.eccent. at “expected” frequency – 60Hz.at “expected” frequency – 60Hz.

•• T  T  eccent.eccent. -28.43 dB relative amplitude.-28.43 dB relative amplitude.

•• I I eccent.eccent. -34.9 dB relative amplitude.-34.9 dB relative amplitude.

T eccent. is at the understandable location.

T eccent. has a 4.5 times larger signal.

Page 72: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 72/76

Demodulated Signals:Torque vs. Current

Demodulated Signals:Torque vs. Current

Demodulated Torque Demodulated Current1* RPM 2* RPM 1* RPM 2* RPM

Bad Motor #1

Bad Motor #2

Good Motor #1

Good Motor #2

3.47E-05 7.94E-05 0.00324 0.03150

4.26E-05 7.96E-05 0.00398 0.03091

2.96E-05 1.35E-05 0.00245 0.03109

3.46E-05 1.42E-05 0.00308 0.03057

Factor 1.20 5.90 1.31 1.01

Conclusions:

• Demodulated Current method does not agree with vibration’s methods.

• Demodulated Torque reacts like vibration’s methods.

• This method is independent of Motor design.

• This method does not disagree with IEEE motor scientist’s research.

Page 73: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 73/76

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

Page 74: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 74/76

Input Shaft Freq.Intermediate Shaft Freq.

Output Shaft Freq.

Blade Pass Freq.

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

C C

Page 75: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 75/76

1st  Mesh Frequency 2 nd  Mesh Frequency 

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

C d II C li f d i

Page 76: Joe Geiman - Baker Instruments

8/2/2019 Joe Geiman - Baker Instruments

http://slidepdf.com/reader/full/joe-geiman-baker-instruments 76/76

BPFO 

BPFI + - 2 x Electrical 

+ - 2 x Electrical 

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

Case study II: Cooling tower fan and gear signatures.

Coal-fired power plant.

SKF 22310c