© ABB Group May 2, 2012 | Slide 1 MV Primary and Secondary Gas Insulated Switchgear Julius Forrer, MV GIS Sales Support, Abr-2012

Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

  • Upload
    vohanh

  • View
    228

  • Download
    3

Embed Size (px)

Citation preview

Page 1: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 1

MV Primary and SecondaryGas Insulated Switchgear

Julius Forrer, MV GIS Sales Support, Abr-2012

Page 2: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 2

Partes en Media Tensión protegidas en

compartimientos con gas y libres de las

condiciones externas

Nivel de aislación no es influenciado por altitud.

Mantenimiento no requerido para componentes en

MT.

Dimensiones reducidas

Menores costos con obras civiles.

Rápida instalación

Celdas completamente montadas y testadas en

fábrica.

Conexión de barras con tecnología plug-in, sin

manejo de gas en terreno.

Tecnología GIS

Page 3: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 3

Plantas de Generación eléctrica

Eólica

Hidroeléctrica

Industria

Química

Petroquímica

Minería

Acero

Cemento

Transporte

Puertos, aeropuertos, estaciones de

tren

Servicios

Clínicas, shopping centers

Aplicaciones

Page 4: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 4

Fábrica

• Ubicada en Ratingen, Alemania (10km de

Düsseldorf).

• Producción de:

• Botellas al vacío

• Interruptores

• Medium Voltage GIS

• Is-Limiter

• Laboratorio para ensayos de tipo.

Page 5: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 5

Key data

• Primera GIS producida en 1965.

• >30.000 celdas entregadas.

• Empleados: 779

Page 6: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 6

GIS Producción y Pruebas

• Procesos automatizados de corte y soldatura

de los compartimientos de gas.

• Pruebas de Rutina según IEC 62271-200.

Ejemplos:

• Hermeticidad de compartimiento de gas

• Pruebas de alta tensión

• Chequeo automatico de todo cableado de

control.

Page 7: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 7

Sistema de Gas

Compartimientos son llenados en fabrica con la presión de

operación (1,3 bar).

Tasa de pérdida <0,1% por año.

Sensores de densidad en cada compartimiento para indicación de

presión baja (1,2 bar).

Hasta la presión mínima (1,0 bar) BIL no es afectado.

1 bar

1.2 bar

1.3 bar

10 years 20 years 30 years

1) Normal leakage

zone < 0.1% /

annum

7 years 14 years

Atmosphere pressure.

Under SF6, panel can be

operated

Pressure

at 20 °C

timeDate of original filling

Page 8: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Ciclo de vida

© ABB Group May 2, 2012 | Slide 8

Page 9: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 9

Gas-insulated switchgearFamilia ZX

Page 10: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 10

Características Generales

Diseño IEC

Gas aislante SF6

Interruptores fijos

Metal Clad o Metal Enclosed

Arc Resistant (AFL o AFLR)

MT comp.- IP65, BT comp. – IP4X

Certificación Sísmica IEEE693-1997.

Page 11: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 11

Switching por botella en vacío.

Polos imersos en SF6.

Fijo

Mecanismo de operación fuera del módulo de

gas.

Enclavamiento mecánico con el desconectador

para prevenir una mala operación.

Interruptor VD4x

Page 12: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 12

Puesta a Tierra

SF6

Puesta a tierra por la acción combinada

del interruptor y del seccionador de 3

posiciones.

Interruptor es un aparato de mejor

calidad que cualquier llave de puesta a

tierra.

Page 13: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Secuencia de Aterrizaje

© ABB Group May 2, 2012 | Slide 13

x x xxx

Page 14: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 14

Aterrizaje de la barra Por Celda Acopladora

Page 15: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 15

Aterrizaje de la barra Por Earthing Set

Page 16: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 16

Pruebas de gas son hechas en fábrica.

Herramientas especiales no son

requeridas.

Rápida instalación sin manejo de gas.

Espiras

Tubo de

contacto

Capa

aislante

Conexión de barras

Page 17: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 17

Conexión de barras

Page 18: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 18

Conexión de barras

Page 19: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

SF6

Conexión de Barras

Page 20: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

SF6

Conexión de Barras

Page 21: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

SF6 SF6

Compartimientos de gas separados.

Conexión de Barras

Page 22: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Protección y Control Familia Relion

© ABB•Gas-insulated switchgear type ZX1.2 | 22

Protección y control integrados:

REF630: Feeder

REM630: Motor

RET630: Transformer

Nativo en protocolo IEC61850

Page 23: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Protección y Control Familia Relion

© ABB•Gas-insulated switchgear type ZX1.2 | 23

Operación del

interruptorSelector Local/

Remoto

Mímico

Alarmas

Luces Indicadoras

Page 24: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 24

Control Convencional Panel control Unit, PCU100/200

PCU100 (SBB) PCU200 (DBB)

Solucción moderna para control convencional.

Control via botoneras y selector local / remoto.

Mimico con LEDs de distintos colores para indicación de posición (mismo en

salas con poca iluminación se puede ver sin dificuldad la posición de cada

elemento).

Page 25: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 25

Control Convencional Panel control Unit, PCU100/200

Alambrado con PCU Alambrado convencional

Page 26: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 26

Familia ZX

Metal Enclosed Metal Clad

Page 27: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 27

Celdas Metal Enclosed

ZX0 block design ZX0.2

Page 28: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 28

Celdas Metal Clad

ZX1.2 SBB ZX2 SBB ZX2 DBB

Page 29: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 29

A – Compartimiento de gas

B – Compartimiento de cables

C – Compartimiento de baja tensión

A

B

C

Gas-insulated switchgear ZX0 Estructura

Page 30: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 30

Gas-insulated switchgear ZX0 Alimentadores

SF6

850 mm 1000 mm400 mm 600 mm

Page 31: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 31

Gas-insulated switchgear ZX1.2 Celda cable-in cable-out

SF6

2400 mm

1600 mm (1 cable/fase)

1900 mm (2 cables/fase)

…36 kV

…1250 A

…31.5 kA

Page 32: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 32

Gas-insulated switchgear ZX2 Estructura

Barra simple

A

B

C

D

E

F

A

B B

C

D

E E

F

Barra dupla

A – Compartimiento del interruptor

B – Compartimiento de barras

C – Compartimiento de cables

D – Ducto de alivio de presión para

interruptor y cables

E – Ducto de alivio de presión para

compartimiento de barras

F – Compartimiento de baja tensión

Page 33: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 33

Gas-insulated switchgear ZX2 Componentes externos Plug-in

Surge arresters

Voltage transformers

Test plugsBB extension

Cable plugs

Blind plugs

Secondary

equipment

Page 34: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 34

Gas-insulated switchgear ZX2 I/O feeder panel 800 A y 1250 A

Ir = 800 A

W = 600 mm

12 kV …31,5 kA

24 kV …25 kA

SF6

1860 mm

Ir = 1250 A

W = 600 mm

12 kV …40 kA

24 kV …31,5 kA

36 kV …31,5 kA

W = 800 mm

24 kV …40 kA

36 kV …40 kA1860 mm

Page 35: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 35

Gas-insulated switchgear ZX2 I/O feeder panel 2000 A

Ir = 2000 A

W = 800 mm

12 kV …40 kA

24 kV …40 kA

36 kV …40 kA

SF6

2300 mm

1860 mm

Page 36: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 36

Gas-insulated switchgear ZX2 I/O feeder panel 2500 A / passive cooling

Ir = 2500 A

W = 800 mm

12 kV …40 kA

24 kV …40 kA

36 kV …40 kA

SF6

2870 mm

2090 mm

Page 37: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 37

Gas-insulated switchgear ZX2 Double feeder panel 630 A

Ur: …24kV

Ik: …25kA

Ir (feeder): …630A

Ir (busbar): …2500A

Page 38: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 38

Gas-insulated switchgear ZX2 I/O feeder panel 4000 A

Ir = 4000 A

W = 2x 800 mm

12 kV …40 kA

24 kV …40 kA

36 kV …40 kA

SF6

2300 mm

2090 mm

Page 39: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 39

Gas-insulated switchgear ZX2 Alivio de presión

Dentro de la sala pasando por

filtro de absorción Para fuera de la sala con

extensión del ducto de gas

Cada compartimiento tiene un disco de ruptura para alivio de gases cuando

presión >2,2 bar. Los gases son liberados según una de las alternativas:

Page 40: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 40

Gas-insulated switchgear ZX2 Espacio requerido

> 100 mm

>1860

+300 mm

1860 mm

> 800 mm

250 mm B

> 800 mm

Panel width

+ 200 mm

50 mm A

Pasillo de servicio

Pasillo de operación

Recomendaciones según IEC 61936 y IEC 62271-200.

Pasillo de operación considera la posibilidad de sacar una celda en el medio del

switchgear.

Espacios pueden ser reducidos de acuerdo con la forma de alivio de presión

elegida.

Page 41: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Condiciones de Operación No-Estándar

Instalación >1000 msnm.

De-rateo en la capacidad de corriente por la diminución de la

capacidad de disipación térmica (menos aire).

Refuerzo en la fijación de los discos de ruptura.

Reducción de la presión de gas SF6. No hay impacto en el BIL.

Corriente de barra >2500A.

Posible si la temperatura ambiente <40oC.

Cambiadores de calor adicionales requeridos.

© ABB Group May 2, 2012 | Slide 41

Page 42: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 42

Entrega e instalación

• Celdas completas y pruebadas.

• 1 celda = 1 unidad de transporte.

• Llenadas en fábrica a la presión de operación.

• Montaje sobre bases para ajuste de nivelación.

• Instalación rápida y sencilla con conexión plug-in.

• Mano de obra capacitada en Chile para instalación

y mantenimiento.

Page 43: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Positioning panel 1

Plug-in connection

Fastening

Finished!

Simple

Safe

Fast

Entrega e instalación

Page 44: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 44

• >1600 celdas en Latinoamerica.

• >300 celdas en Chile.

Proyectos:

• Codelco Mina Ministro Hales (@2800msnm)

• 39 celdas ZX2 24kV-3000A-40kA

• 11 celdas ZX2 24kV-1250A-40kA

• Minera Esperanza (<1000msnm)

• 8 celdas ZX2 36kV-2000A-25kA

• Chilectra (<1000msnm)

• 15 celdas ZX2 24kV-2500A-25kA

• Collahuasi (@2800msnm)

• 18 celdas ZX2 24kV-2500A-31.5kA

Referencias en LatinoAmerica

Page 45: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Instalación de 39 celdas en 11 dias!

Referencias Proyecto Minero Perú

Page 46: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Referencias Salas Eléctricas Pre-fabricadas

© ABB Group May 2, 2012 | Slide 46

Page 47: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Referencias Salas Eléctricas Pre-fabricadas

© ABB Group May 2, 2012 | Slide 47

Page 48: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 48

Gas-insulated Secundary switchgearSafeRing / SafePlus

Page 49: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 49

Distribución primaria y secundariaDesde el punto de vista de Tableros Eléctricos y Consumidores

Distribución Primaria Distribución Secundaria

Nivel de Tensión 36kV ≥ Un ≥ 1kV

Corriente Nominal

BusbarHasta 4000A

400A y 630A

(eventualmente 1250A)

Corriente de

Cortocircuito de

breve duración

Hasta 50kA Hasta 25kA

Corriente de Arco

Interno soportada

Hasta 40kA 1s

Hasta 50kA 0,5sHasta 20kA 1s

Aparato principal

Interruptor en SF6 ó

Vacío, ejecución

extraíble

Seccionador bajo carga en

SF6, interruptor en SF6 ó

Vacío, ambos en ejecución

fija

Principales

aplicaciones:

Distribución Publica

Subestaciones

Transformadores

AT/MT o MT/MT

Centros de

Transformación MT/BT

Distribución Privada

Industria Pesada o

Electrointensiva –

Aplicaciones Marítimas

Edificios - Industria de

Manufactura -

Infraestructura

G G

Transmisión

Distribución

S.E.T. Elevadora

M.T. / A.T.

S.E.T. Reductora

A.T. / M.T.

L. A.T.

Distribución

Primaria (M.T.)

Distribución

Secundaria (M.T.)

Distribución (B.T.)

Consumidores

Generación

Page 50: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 50

Características Generales

Diseño IEC

Gas aislante SF6

Interruptores fijos

Metal Clad

Conexión de barras tipo plug-in y externas

MV comp.- IP67, LV comp. – IP2X.

Tensiones 12,15,17.5,24,36 y 40.5 kV

Corrientes de Barra 630 A

Corrientes de Cortocircuito 16 y 21 kA.

Page 51: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

© ABB Group May 2, 2012 | Slide 51

Aplicaciones SafeRing – Soluciones Compactas

SafeRing

SafeRing SafeRing

SafeRing

SS/EE secundarias

Plantas de energía eólica

Minería

Aeropuertos

Bóvedas

Page 52: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Aplicaciones SafePlus – Soluciones a Medida

© ABB Group May 2, 2012 | Slide 52

Módulos tipo:

C :Interruptor de Línea (Cable)

D :Conexión Directa de Cable

F :Interruptor-Fusibles

V :Interruptor Automático de Vacío

CB :Circuit Breaker

Be :Puesta a Tierra de Barras

De :Conexión Directa de Cable con Seccionador de Tierra

Sl :Seccionamiento de Barras, Interruptor-Seccionador

Sv :Seccionamiento de Barras, Interruptor Automático de Vacío

M :Módulo de Medida

Page 53: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Conexión de Barras

© ABB Group May 2, 2012 | Slide 53

Semimodular Fullymodular

Extensión lateral

Page 54: Julius Forrer, MV GIS Sales Support, Abr-2012 MV Primary ...€¦ · Gas-insulated switchgear ZX2 Espacio requerido > 100 mm >1860 +300 mm 1860 mm > 800 mm 250 mm B > 800 mm Panel

Contacto

Julius Forrer

GIS MV Switchgear Product Manager

Fone: (2) 471 4096

Email: [email protected]

Carolina Sepúlveda

MV Switchgear Product Manager

Fone: (2) 471 4606

Email: [email protected]

© ABB Group May 2, 2012 | Slide 54