A UTC Fire & Security Company Effective: June 2007 K-84-11 Addressable Manual Pull Station Series 3300 FEATURES Exclusive KIDDE ® Design Unique Field Labeling for either Fire Alarm or Suppression Applications Dual Action Operation Interfaces directly to Kidde Addressable Control Panel SLC FM Approved cULus Listed for US and Canada Other domestic approvals in process Surface and Weatherproof Backboxes Flashing LED Keylock for Reset DESCRIPTION The Kidde ® Addressable Manual Pull Stations is an intel- ligent initiating device that contains its own SmartOne™ Addressable Input (AI) module and interfaces directly to the Kidde PEGAsys™ and ARIES™ control panel. The initiating device circuit is wired as NFPA Class B. The Manual Pull Station is constructed of heavy die-cast aluminum for long life and uses an internal toggle switch for reliable operation. Similiar to othe SmartOne devices, the unit is field pro- grammable using the control panel keypad or Hand-Held Programmer. The owner location message and reporting type can be customized by the use of a programming util- ity utilized with the control panel. A status LED is mounted on the unit and indicates the status by a 2 or 9 second flash interval. A Trouble condition inhibits the sta- tus LED completely. While the Station is designed for quick, efficient emer- gency response, its double action PUSH/PULL levers prevent accidental operation. The Station can be mounted in an indoor or outdoor weatherproof backbox (Model SBG-32S or Model SGB- 32C) or a North American 2-1/2 in. (64 mm) deep 1-gang box. The Station terminal block on the AI module accepts 14, 16 and 18 AWG (1.5 mm 2 , 1.0 mm 2 , and 0.75 mm 2 ) wire. Size #18 is the minimum requirement. FIRE ALARM OR SUPPRESSION RELEASE LABELING The Pull Station has a unique labeling method which pro- vides the installer the greatest amount of flexibility with- out the expense of having to carry extra inventory. Seven heavy-duty Lexan ® self-adhesive labels are shipped with each station: FIRE ALARM FM-200 RELEASE CO 2 RELEASE FE-13 RELEASE FIRE SYSTEMS RELEASE HALON-1301 RELEASE NOVEC 1230 RELEASE

K-84-11 Addressable Pull Station 3300

Embed Size (px)

DESCRIPTION

pull

Citation preview

  • Addressable Manual Pull Station

    A UTC Fire & Security Company

    Effective: June 2007K-84-11

    Series 3300

    FEATURES Exclusive KIDDE Design Unique Field Labeling for either Fire Alarm or

    Suppression Applications Dual Action Operation Interfaces directly to Kidde Addressable Control

    Panel SLC

    FM Approved cULus Listed for US and Canada Other domestic approvals in process Surface and Weatherproof Backboxes Flashing LED Keylock for Reset

    DESCRIPTIONThe Kidde Addressable Manual Pull Stations is an intel-ligent initiating device that contains its own SmartOneAddressable Input (AI) module and interfaces directly tothe Kidde PEGAsys and ARIES control panel. Theinitiating device circuit is wired as NFPA Class B. The Manual Pull Station is constructed of heavy die-castaluminum for long life and uses an internal toggle switchfor reliable operation.Similiar to othe SmartOne devices, the unit is field pro-grammable using the control panel keypad or Hand-HeldProgrammer. The owner location message and reportingtype can be customized by the use of a programming util-ity utilized with the control panel. A status LED ismounted on the unit and indicates the status by a 2 or 9second flash interval. A Trouble condition inhibits the sta-tus LED completely.While the Station is designed for quick, efficient emer-gency response, its double action PUSH/PULL leversprevent accidental operation.The Station can be mounted in an indoor or outdoorweatherproof backbox (Model SBG-32S or Model SGB-32C) or a North American 2-1/2 in. (64 mm) deep 1-gangbox. The Station terminal block on the AI module accepts 14,16 and 18 AWG (1.5 mm2, 1.0 mm2, and 0.75 mm2) wire.Size #18 is the minimum requirement.

    FIRE ALARM OR SUPPRESSION RELEASE

    LABELINGThe Pull Station has a unique labeling method which pro-vides the installer the greatest amount of flexibility with-out the expense of having to carry extra inventory. Sevenheavy-duty Lexan self-adhesive labels are shipped witheach station:

    FIRE ALARM FM-200 RELEASE CO2 RELEASE FE-13 RELEASE

    FIRE SYSTEMS RELEASE HALON-1301 RELEASE NOVEC 1230 RELEASE

  • SPECIFICATIONS ORDERING INFORMATIONThis literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The prod-uct must be properly applied to work correctly.

    SGB-32S INTERIOR SURFACE BACKBOX

    SGB-32C WEATHERPROOF SURFACEBACKBOX

    DIMENSIONS(shown with Fire System Release Label installed)

    Station Type: Double Action, with integral Smart-One Addressable Module

    Initiating Device Circuit:

    EOL Resistor Value:Max. CircuitResistance:Max. Circuit

    Capacitance:

    Style B (Class B) Wiring

    10 K Ohm (06-129025-003)

    50 Ohm (25 ohm per conductor)

    0.1F

    Operating Tempera-ture Range:

    -40F to 150F (-40C to 66C)

    Operating Humidity Range:

    0-95% RH

    Construction: Die-cast metal housing

    Compatible Electrical Boxes:

    Indoor: Sheet metal Model SGB-32SOutdoor: Weatherproof Die-cast Model SGB-32C

    Shipping Weight: 1.12 lbs. (510 g)

    Dimensions: 4-3/4 in. H x 3-1/4 in. W x 2-1/4 in. D

    Construction: Steel sheet metal.

    Conduit: Two knockouts for 1/2 in. conduit connectors, one on top and bottom.

    Mounting: Mounts to the box with (4) 8/32 screws, which ship with each box.

    Dimensions: 4-3/4 in. H x 3-1/4 in. W x 2-1/4 in.D

    Construction: Cast aluminum.

    Conduit: One threaded opening for 1/2 in. conduit connector.

    Mounting: Mounts to the box with (4) 8/32 screws and a foam gasket, which ship with each box.

    Part Number Description

    84-330002-001 Addressable, Double Action Manual Pull Station ships with mounting hard-ware, 2 keys, 1 break rod, and label set.

    70-407008-001 Addressable Input Module (Normally Open Devices)

    84-100009-001 SGB-32S Indoor Backbox

    84-100009-002 SGB-32C Outdoor Waterproof Backbox

    06-129025-003 10 K Ohm Resistor

    84-100008-002 Pkg. of (12) Breakrods

    06-118013-001 Spare Key

    06-231866-930 Label Set

    3-1/4 in.(83 mm)

    1-5/64 in.(27 mm)

    4-3/4 in.(121 mm)

    31/32 in.(24 mm)

    2-1/4 in. MAX.(57 mm)

    PUSH

    PULL

    FIRESYSTEM

    RELEASE

    FIRESYSTEM

    RELEASE

    Kidde is a registered trademark of Kidde-Fenwal, Inc.SmartOne is a trademark of Kidde-Fenwal, Inc.FM-200 is a registered trademark of the Greak Lakes Chemical Corporation.3M and Novec are trademarks of 3M.FE-13 is a trademark of DuPont.Lexan is a registered trademark of the General Electric Company.A UTC Fire & Security Company400 Main StreetAshland, MA 01721Ph: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

    If you need more information on this product, or if you have a particular problem or ques-tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.

    K-84-11 Rev AA 2007 Kidde-Fenwal Inc. Printed in USA

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice