AIR CONDITIONING SYSTEMS FOR ENCLOSURES
COOLING POWER
CE
I N D U S T R I A L D I V I S I O N
www.erdin
cklim
a.com
A conditioned enclosure absorb or dissipate heat through its walls according to its material, dimensions and the difference between internal enclosures and ambient temperature (t). This value is determinate by a simple calculation
2(m x t x5)W, (as assuming the enclosure made in steel, transfer coefficient = 5), see the selection chart below for a quick reference:
First question to ask in order to select the appropriate cooling equipment is: “Can the internal enclosure temperature be higher than the external ambient temperature ?
, we will choose between an air conditioner and a water to air heat exchanger. In this case, the heat absorbed by the enclosure, at specified limit conditions, has to be added to the heat dissipated by the internal components. Using an air conditioner can be maintained constant the internal enclosure temperature, independently from the variation of outside ambient temperature. If an air conditioner is used, it is suggested to keep the internal temperature to a minimum of 30°C to avoid condensate water production when an operator will open the enclosure door. Temperatures lower than 30°C may cause the installed components to be covered of condensate water when warmer external air enter in the enclosure.
, we will choose an air to air heat exchanger or a forced ventilation system, that uses filtered primary air. In this case the heat absorbed by the enclosure, at specified limit conditions, has to be removed from the heat dissipated by the installed components. Air to air heat exchanger cooling capacity is measured in W/K, this value indicates how many Watt the heat exchanger can remove for every degree of temperature difference between internal enclosure temperature and external ambient temperature. For example, a 30 W/K cooling capacity heat exchanger can remove 450W of heat, if ambient temperature is 35°C and internal enclosure temperature is 50°C (i.e. 50-35 = 15 difference of temperature x 30 = 450W).Only as an indication, heat dissipation by components can be calculated using the below table:
transformers drivers, PLC, numerical controls , inverters suppliers moving-coils relay, contactors incandescent lamps heaters
If the answer is NO
If the answer is YES
Help
30
25
20
15
10
0
0 125 250 375 500 625 750 875 1000 1125 1250 1375 1500 1625 1750 1875 2000 2125 2250
∆t °C m²
W
5
2 3 4 5 6 7 8 9 10 11 12 13 14 15
Above table only give approximate values for components. Particular attention should be given to high power components and it is suggested to consult the component's manufacturer in order to obtain an accurate value and to avoid wrong calculations of heat dissipation.
AVAILABLE POWER SUPPLIES
ABCDELTPQRVW
230 1 50230 1 60230 1 50 / 60110 - 115 1 50 / 60440 - 480 3 60415 3 60400 - 415 3 50400 2 50400 2 60440 - 480 2 6024 V DC48 V DC
from 2 to 5%5%
10%3%
100%100%
www.erdin
cklim
a.com
Air conditioners
Air to water heat exchangers
Air to air heat exchangers
Anticondensation heaters
Accessories
From pag. 10 to pag. 29
From pag. 36 to pag. 39
pag. 40
Pag. 42
Index
Ventilation
Pag. 41
LOW MAINTENANCE Units marked with this symbol require only air filter cleaning and no other periodical maintenance.
ANTI-CONDENSATE DEVICEThis device collects condensate and evaporates this off into the ambient atmosphere, thus ensuring that the air left inside the machine is dry and the surfaces are moisture-free.
From pag. 30 to pag. 35
Sales network
Pag. 43
NO MAINTENANCE Units marked with this symbol do not require any periodical maintenance.
ENERGY SAVING This symbol indicates that the product has been designed to optimise its energy consumption according to the provided working conditions. (DIN3168L35L35).
OZON FRIEND Is the symbol that represents Kelvin's permanent commitment in preserving the environment around us. All refrigeration techniques take environmental protection into consideration by using cloro-fluoro-carbon-free (CFC) refrigerants, which are not harmful to the ozone layer.
www.erdin
cklim
a.com
10
KMV
Standard Optionals
he KMV is a very compact air conditioner for vertical installation on the outside face of the door or wall of an enclosure, especially designed for applications where space is limited, like small control panels. It is suitable for low cooling capacities. The condensate drain is positioned on the Tbottom of the air conditioner. Four M6 threaded inserts will enable easy screw-on installation.
CE
MODEL:
Standard power supply (C)Running currentStarting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 self adhesive gasket
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
Internal control thermostat set at 35° C.
Polyurethane air filter
Aluminium air filter
User manual in five languages
KMV 03
230 - 50/601,2 / 1,46,2 / 6,2
2330 / 347248 / 257216 / 247
R134a27
20 - 5554346217
C, D
V - HzAAAWWW
bar°CIPIP
dB (A)kg
50
0
170 280
www.erdin
cklim
a.com
KUR
Standard Optionals
CE
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Internal terminal board for wiring
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
User manual in five languages
Protected terminal board IP30
Non standard painting
3 meters power supply cableconnected in therminal board
Aluminium or
polyurethane air filter
Inlet 3 pole connector
Free voltage contact for dirty filter and max temperature alarm
Noise filter for power supply line
he KUR05 and KUR09 are two compact air conditioners designed to be installed on the outside face of the door or wall of an enclosure. These can also be installed internally or semi-concealed using an optional mounting frame. They are made from galvanised steel with an easily removable Tcover with rounded edges. KUR05 and KUR09 are both designed to operate without an air filter, available as an option and recommended if the
working environment is particularly dusty or oily. The condensate drain is positioned at the bottom of the air conditioners. Six M6 threaded inserts will enable easy screw-on installation.
11
KUR 05
2,1 / 2,57,9 / 9,3
4600 / 630450 / 480395 / 461
6728
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KUR 09
2,8 / 3,311,3 / 12,3
4850 / 892637 / 663525 / 611
6829
60
5
215 305
SE
MI-
CO
NC
EA
LE
D A
SS
EM
BLY
INT
ER
NA
L A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
230 - 50/60
R134a27
20 - 555434
C, D
www.erdin
cklim
a.com
12
he KUJ05 and 09 are two air conditioners designed to be installed on the outside face of the door or wall of an enclosure. These can also be installed semi-concealed using an optional frame. The large distance between the inlet and outlet of the internal circuit (enclosure side) helps to keep an even Ttemperature in the cabinet. KUJ models are made from galvanised steel with an easily removable cover with rounded edges. On the front, an
aluminium grid conceals the air filter and gives the air conditioner a pleasant look thanks to its design. The condensate drain is positioned at the bottom. Six M6 threaded inserts will enable easy screw-on installation.
KUJ
Standard Optionals
Protected terminal board IP30
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Non standard painting
Internal terminal board for wiring
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
3 meters power supply cableconnected in therminal board
Aluminium air filter
Inlet 3 pole connector
Free voltage contact for dirty filter and max temperature alarm
Noise filter for power supply line
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
70
0
190 350
CO
VE
R F
OR
IN
TE
RN
AL
AS
SE
MB
LY
SE
MI-
CO
NC
EA
LE
D A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
INT
ER
NA
L A
SS
EM
BLY
KUJ 05
2,2 / 2,78,2 / 9,7
4600 / 630450 / 480445 / 516
6725
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KUJ 09
2,9 / 3,511,6 / 12,7
6850 / 892637 / 663570 / 666
6829
230 - 50/60
C,D
R134a27
20 - 555434
www.erdin
cklim
a.com
KUN
User manual in five languages
Standard
Non standard painting
Optionals
IP54 protected electrical parts
Protection for voltage peaks
CE
Electrical control board
- keeps temperature at set point- visualises temperature inside the control board- provides voltage free contacts for dirty filter and high temperature alarms- protected programming access (within 1' from power-on)
he KUN series of air conditioners are designed to be installed on the outside face of the door or wall of an enclosure.These can be also installed internally or semi-concealed using an optional frame. They are made from galvanised steel with an easily removable cover with rounded edges. On Tthe front, an aluminium grid conceals the air filter and gives the air conditioners a pleasant look thanks to its design.This product line is provided
with a water condensate dissipater and emergency condensate drain at the bottom. Six M6 threaded inserts will enable easy screw-on installation.
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 self adhesive gasket
Polyurethane air filter
Lifting eyebolts
Internal terminal board for wiring
Inlet 3 pole connector
Noise filter for power supply line
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Compressor start delay timer
OPTION: KUN10 and KUN20 230/1/50-60 without electronic diagnostic card are available on cCSAus comply version.
10
00
230 400
VE
RS
ION
WIT
H E
LE
CT
RO
NIC
CO
NT
RO
LL
ER
SE
MI-
CO
NC
EA
LE
D A
SS
EM
BLY
INT
ER
NA
L A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
ON
LY
WIT
H E
LE
CT
RO
NIC
CO
NT
RO
LL
ER
VE
RS
ION
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
13
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KUN 10
2,9 / 3,511,6 / 12,7
41050 / 1102778 / 819570 / 666
45
KUN 15
4,2 / 5,216,6 / 17,2
61360 / 14281020 / 1060830 / 1014
48
KUN 17
5,4 / 6,620,4 / 21,1
101720 / 18061290 / 13421050 / 1278
49
KUN 20
5 / 6,123,6 / 24,2
102000 / 21001500 / 15601045 / 1272
52C,D,E,P,Q,R,T
230 - 50/60
R134a27
20 - 55543470
C,D,P,Q,RC,D,P,Q,R C,D,P,Q,R
www.erdin
cklim
a.com
14
KUN
Optionals
IP54 protected electrical parts
StandardStandard
CE
MODEL:
Standard power supply (A)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Non standard painting
Protection for voltage peaks
Inlet 3 pole connector
Noise filter for power supply line
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Compressor start delay timer
IP54 self adhesive gasket
Polyurethane air filter
Lifting eyebolts
Internal terminal board for wiring
User manual in five languages
OPTION: KUN40 400/3/50 and 440-460/3/60 without electronic diagnostic card are available on cCSAus comply version.
he KUN series of air conditioners are designed to be installed on the outside face of the door or wall of an enclosure.These can be also installed internally or semi-concealed using an optional frame. They are made from galvanised steel with an easily removable cover with rounded edges. On Tthe front, an aluminium grid conceals the air filter and gives the air conditioners a pleasant look thanks to its design.This product line is provided
with a water condensate dissipater and emergency condensate drain at the bottom. Six M6 threaded inserts will enable easy screw-on installation.
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KUN 40
6,8 / 33,2 /
3800 / 2850 / 1405 /
87
8,342,6
399029641744
KUN 30
6,7 / 37,2 /
2800 / 2100 / 1155 /
83
8,344,6
294021841444
230 - 50
10
R134a
2720 - 55
543472
A,B,E,T ( )60Hz
12
05
305 500
EX
TE
RN
AL
AS
SE
MB
LY
VE
RS
ION
WIT
HO
UT
EL
EC
TR
ON
IC C
ON
TR
OL
LE
R
SE
MI-
CO
NC
EA
LE
D A
SS
EM
BLY
Electrical control board
- keeps temperature at set point- visualises temperature inside the control board- provides voltage free contacts for dirty filter and high temperature alarms- protected programming access (within 1' from power-on)
www.erdin
cklim
a.com
KUS
Standard
Noise filter for power supply line
Optionals
Internal control thermostat set at 35° C.
Compressor start delay timer
IP54 protected electrical parts
Aluminium air filter
he KUSs are designed for outdoor installations on walls or control board doors. With a depth of only 115mm, a painted cowling with rounded edges and the particular design of the aluminium front grill supporting the air filter, the KUS has all the features that offer an elegant cooling solution. The Tcompressor is positioned in the lower part of the air conditioner and provision must be made behind the door for the extra intrusion of the
compressor body beyond the depth of the KUS. Four M6 threaded inserts are provided for installation. The condensate outlet is positioned on the lower part of the air-conditioner.
Gasket roll
User manual in five languages
CEInternal terminal board for wiring
MODEL:
Standard power supply (C)Running currentStarting currentProtection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Inlet 3 pole connector
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
Protection for voltage peaks
15
15
10
115+60 400
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KUS 10
3,3 / 412,3 / 13,7
41000 / 1050
750 / 780645 / 756
43
KUS 15
4,3 / 5,216,9 / 17,4
61450 / 15221088 / 1131860 / 1014
48
KUS 17
5,5 / 6,720,7 / 21,2
81700 / 17851275 / 13261080 / 1278
49
KUS 20
5,1 / 6,223,9 / 24,4
82000 / 21001500 / 15601075 / 1272
46
230 - 50/60
R134a27
20 - 55
543470
C,D
EX
TE
RN
AL
AS
SE
MB
LY
www.erdin
cklim
a.com
16
KSL
Standard Optionals
CE
he KSL “slim line” air-conditioners are designed to be installed vertically inside and outside the control board. This new product line represents the latest technical innovation from Kelvin's research and development department. All parts are accessible by simply removing the front panel, so Teliminating the need to remove the unit from the control board. This model can be used with or without an air filter. The condensate is collected and
then dissipated into the external ambient. This unit can be installed outdoors without worrying about associated air pollutants.
NEW
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Inlet 3 pole connector
Free voltage contact for dirty filter and max temperature alarm
3 meters power supply cableconnected in therminal board
Aluminium air filter
Noise filter for power supply line
Non standard painting
IP54 protected electrical parts
Internal terminal board for wiring
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
Slim line
15
00
190 400
INT
ER
NA
L A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
VE
RS
ION
WIT
H A
IR F
ILT
ER
V - HzAAAWWW
bar°CIPIP
dB (A)kg
230 - 50/60
R134a27
20 - 55
543469
KSL 10
2,4 / 2,812 / 13
41050 / 1102778 / 819425 / 465
KSL 15
3,6 / 4,215 / 18
61490 / 15451150 / 1200650 / 715
C,D,P,Q,R50
Electrical control board (KUN)
www.erdin
cklim
a.com
KSL Slim line
Standard Optionals
CE
he KSLs are designed for simple installation. The drilling template is common to all models, thus allowing interchangeability of unit sizes if the need to increase cooling power became necessary. In the internal mounted version the air-conditioner's front side, 20 mm thick, is leaned on the Tcontrol board's panel covering so possible aesthetic defects.
NEW
MODEL:
Standard power supply Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 protected electrical parts
Internal terminal board for wiring
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
Inlet 3 pole connector
Free voltage contact for dirty filter and max temperature alarm
Electrical control board (KUN)
3 meters power supply cableconnected in therminal board
Aluminium air filter
Noise filter for power supply line
Non standard painting
15
00
220 400
VE
RS
ION
E S
EN
ZA
FIL
TR
O A
RIA
INT
ER
NA
L A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
17
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KSL 20
230 - 50/60 (C)4,7 / 5,622 / 24,2
82100 / 22001500 / 1560870 / 1050
20 -55
56C,D,E,P,Q,R,T
KSL 40
230 - 50 (A)8,5 / 29 /
103300 / 2450 / 1220 /
20 - 50
65A,B,E,T ( )
9,334,8
349025201464
60Hz
KSL 30
230 - 50 (A)5,6 / 26 /
102900 / 2190 / 1055 /
R134a27
20 - 5554347065
A,B,E,T ( )
6,231
302022651344
60Hz
www.erdin
cklim
a.com
KZM
18
Standard Optionals
Compressor start delay timer
IP54 protected electrical parts Protection for voltage peaks
Lifting eyeboltsElectric module (KUN)
he KZM60 and 80 air conditioners are designed for side panel mounting. They are made from steel and painted and measure 2000mm high by either 600mm or 800mm wide respectively. These units are designed so that one unit can provide conditioned air to up to 6 cabinet modules in a Trow, supplying the air via a channel in the floor. Particular care has been taken when designing the KZM range of products to give the optimum
performance/consumption ratio. The water condensate drain is positioned at the bottom. Eight M6 threaded inserts will enable easy screw-on installation.
Gasket roll
CE
Internal terminal board for wiring
MODEL:
Standard power supply (T)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Polyurethane air filter
Internal control thermostat set at 35° C.
User manual in five languages
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
Aluminium air filter
KZM 60
6 / 21,4 /
85700 / 4275 /2340 /
150
6,923,2
5985 44462928
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KZM 80
7,6 / 30,4 /
107500 / 5625 / 3140 /
160
8,532,2
78755850 3828
20
00
380600 KZM60
800 KZM80
400 - 3 - 50
3454
20 - 5527
R407C
72
E,L,T ( )60Hz
EX
TE
RN
AL
AS
SE
MB
LY
EX
TE
RN
AL
AS
SE
MB
LY
KZM60 KZM80
www.erdin
cklim
a.com
19
KB
Standard
Inlet 3 pole connector
noise filter for power supply line
Optionals
he KB 04 is a very compact air-conditioner and is particularly suitable for fitting on the top of small control boards which require minimal cooling within limited room conditions. The internal recycled cooled air is parallel to KB04s longitudinal axis. Four M6 threaded inserts are provided for Tinstallation. The condensate outlet is positioned on the unit's rear side.
CE
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 self adhesive gasket
Polyurethane air filter
Internal control thermostat set at 35° C.
User manual in five languages
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
KB 04
230 - 50/601,9 / 2,26,8 / 6,9
4490 / 515368 / 382360 / 419
R134a27
20 - 5554346722
C,D
V - HzAAAWWW
bar°CIPIP
dB (A)kg
25
0
500350
www.erdin
cklim
a.com
20
KBhe KBs are air-conditioners designed to be fitted on the roof of control boards requiring a transverse cooled air path when compared to the KBs longitudinal axis. The supporting structure is made from galvanised steel sheet and an elegant aluminium grid supports the standard polyurethane Tair filter. Four M6 threaded inserts are provided for installation. The condensate outlet is positioned laterally on its right side.
Standard Optionals
CE
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Lifting eyebolts
Internal terminal board for wiring
Antifreeze thermostat
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
Inlet 3 pole connector
Noise filter for power supply line
Non standard painting
Condensate overflow safety
device (Acquablock)
Electrical control board (KUN)
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Compressor start delay timer
Protection for voltage peaks
IP54 protected electrical parts
30
0
600400
KB 10
2,9 / 3,511,6 / 12,7
61000 / 1050
750 / 780570 / 666
37
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KB 17
5,2 / 6,220 / 20
81650 / 17321237 / 12871005 / 1188
41
KB 15
230 - 50/604 / 4,8
16,2 / 16,46
1450 / 1522 1087 / 1131
785 / 924R134a
2720 - 55
54347041
C,D,P,Q,R
www.erdin
cklim
a.com
KB
Standard
Lifting eyebolts
Inlet 3 pole connector
Noise filter for power supply line
Non standard painting
Optionals
Condensate overflow safety
device (Acquablock)
IP54 protected electrical parts
CE
Internal terminal board for wiring
Antifreeze thermostat
MODEL:
Standard power supply Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Compressor start delay timer
Protection for voltage peaks
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
21
KB 20
230 - 50/60 (C)5 / 6,1
23,7 / 24,28
2000 / 21001500 / 15601050 / 1272
54C,D,E,P,Q,R,T
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KB 40
230 - 50 (A)6,8 /
33,2 / 10
3800 / 2850 / 1405 /
63A,B,T,E ( )
8,342,6
399029641744
60Hz
KB 30
230 - 50 (A)6,9 /
37,6 / 10
2800 / 2100 / 1115 /
R134a27
20 - 5554346560
A,B,T,E ( )
8,945,8
294021841370
60Hz
40
0
800400
Electrical control board (KUN)
www.erdin
cklim
a.com
22
KT
Standard Optionals
CE
he KTs are a range of air-conditioners designed to be fitted on the roof of a cabinet with a cold air recycle path parallel to its longitudinal axis. Its supporting structure is made from galvanised steel sheet and an elegant aluminium grid supports the standard polyurethane air filter. Four M6 Tthreaded inserts are provided for installation. The condensate outlet is positioned on the unit's rear side.
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Lifting eyebolts
IP54 protected electrical parts
Internal terminal board for wiring
Antifreeze thermostat
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
Inlet 3 pole connector
Noise filter for power supply line
Non standard painting
Condensate overflow safety
device (Acquablock)
Electrical control board (KUN)
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
Compressor start delay timer
Protection for voltage peaks
35
0
400 600
KT 10
2,9 / 3,511,6 / 12,7
61000 / 1050
750 / 780570 / 666
37C,D,P,Q,R
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KT 17
5,2 / 6,220 / 20,2
81700 / 17851275 / 13261005 / 1188
41C,D,E,P,Q,R,T
230 - 50/60
R134a27
20 - 55543467
www.erdin
cklim
a.com
KT
Standard
Noise filter for power supply line
Non standard painting
Optionals
Compressor start delay timer
Protection for voltage peaks
Electrical control board (KUN)
Condensate overflow safety device (Acquablock)
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 protected electrical parts
Internal terminal board for wiring
Antifreeze thermostat
IP54 self adhesive gasket
Internal control thermostat set at 35° C.
Polyurethane air filter
User manual in five languages
Inlet 3 pole connector
3 meters power supply cableconnected in therminal board
Aluminium air filter
Free voltage contact for dirty filter and max temperature alarm
23
MODEL:
Standard power supply (A)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
KT 35
230 - 506,8 /
33,2 / 10
3500 / 2625 / 1350 /
R134a27
20 - 5554347264
A,B,E,T ( )
8,342,6
365027301700
60Hz
V - HzAAAWWW
bar°CIPIP
dB (A)kg
45
0
460 800
Lifting eyebolds
www.erdin
cklim
a.com
KCN
24
Standard
Inlet 3 pole connector
Optionals
he KCN is an air conditioner for 19” rack cabinets. It has an aluminium front panel 6U high. Two handles on the front provide easy installation into an enclosure. Both the air intake and outlet of the external circuit are located on the front of the unit and so there is no need for cutouts through the Tenclosure side panels. The condensate drain is positioned on the front side of the unit.
Compressor start delay timer
IP54 protected electrical parts
Washable aluminium air filter
CE
Antifreeze thermostat
MODEL:
Standard power supply (C)Running current Starting current Protection fuses Cooling capacity L35 L35Cooling capacity L35 L50 Power absorbed L35 L35 Refrigerant Maximum pressureTemperature rangeInternal circuit protection degreeExternal circuit protection degree Noise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Internal control thermostat set at 35° C.
User manual in five languagesNon standard painting
Internal terminal board for wiring
Protection for voltage peaks
Noise filter for power supply line
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
26
6
545 445
KCN 05
2,2 / 2,78,2 / 9,7
4600 / 630450 / 480445 / 516
25
V - HzAAAWWW
bar°CIPIP
dB (A)kg
KCN 10
230 - 50/602,9 / 3,5
11,6 / 12,76
850 / 892637 / 663570 / 666
R134a27
20 - 5554346737
KCN 15
4 / 4,816,2 / 16,4
61450 / 1522 1087 / 1131
785 / 924
41
483
C,D
www.erdin
cklim
a.com
KWS
30
Standard Optionals
he air-water heat exchanger KWS20 KELVIN is unique in representing the best in compactness and design. It is silent, long lasting and totally free of ordinary maintenance. It represents an optimised product designed to reach elevated performances. This offers the best choice when it comes to Tprohibitive working temperatures. Four M6 threaded inserts are provided for fixing onto the cabinet.
CE
NEW
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
Internal control thermostat set at 35° C.
Internal terminal board for wiring
User manual in five languages
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
IP54 self adhesive gasket
MODEL:
Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies
V - HzWW AA
m³/hbar°CIP
dB (A)kg
KWS 20
230 - 50/6029 / 28
635 - 250 lit/h0,2 / 0,4
1330
5-5 +70IP551/2”5012
C,D,V,W
60
0
110250
www.erdin
cklim
a.com
KWS
31
Optionals
he KWS air to water heat exchangers can reach high cooling capacities with small dimensions. They represent the best choice if the working environment is particularly dusty, oily or hot. KWS offer IP55 protection rating and are very silent and reliable, with almost no maintenance Trequired. Six M6 threaded inserts will enable easy screw-on installation.
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
MODEL:
Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies
Standard
Internal control thermostat set at 35° C.
Internal terminal board for wiring
User manual in five languages
IP54 self adhesive gasket
V - HzWWAA
m³/hbar°CIP
dB (A)kg
KWS 30
230 - 50/6080 / 98
1600 - 200 lit/h0,36 / 0,44
2550
5-5 +70IP551/2”6015
C,D,W
60
0
160300
www.erdin
cklim
a.com
KWS
32
Optionals
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
MODEL:
Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies
Standard
Internal control thermostat set at 35° C.
Internal terminal board for wiring
User manual in five languages
IP54 self adhesive gasket
V - HzWWAA
m³/hbar°CIP
dB (A)kg
10
00
200400
KWS 70
230 - 50/6085 / 90
3400 - 400 lit/h0,38 / 0,4
2850
5-5 +70IP551/2”6529
C,D,W
he KWS air to water heat exchangers can reach high cooling capacities with small dimensions. They represent the best choice if the working environment is particularly dusty, oily or hot. KWS offer IP55 protection rating and are very silent and reliable, with almost no maintenance Trequired. Six M6 threaded inserts will enable easy screw-on installation.
www.erdin
cklim
a.com
KWS
Optionals
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard painting
MODEL:
Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies
Standard
Internal control thermostat set at 35° C.
Internal terminal board for wiring
User manual in five languages
IP54 self adhesive gasket
33
V - HzWWAA
m³/hbar°CIP
dB (A)kg
12
00
250450
KWS 90
230 - 50/60130 / 180
5400 - 600 lit/h0,57 / 0,80
21230
5-5 +70IP551/2”6834
C,D,W
www.erdin
cklim
a.com
KWS
34
Standard Optionals
Internal control thermostat set at 35° C.
he air-water heat exchangers KWS 100 and 120 are designed to reach elevated cooling performances. They are realized inside carpentry modules planned on purpose to be placed side by side to the cabinets, obtaining so an optimal aesthetic integration. Due to their functional characteristics Tthese products are very simple, silent, long lasting and completely free of ordinary maintenance and represent the best choice in cases of prohibitive
working temperatures. Eight M6 threaded inserts are provided for fixing on the control board.
Internal terminal board for wiring
Gasket roll
NEW
MODEL:
Power supply (C)Power absorptionCooling capacity L35/W10°CNominal currentProtection fuses Air flow rangeMaximum pressureTemperature range (ambient)Internal circuit protection degree ConnectionsNoise levelWeightAvailable power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
Free voltage contact for dirty filter and max temperature alarm
Non standard paintingUser manual in five languages
V - HzWWAA
m³/hbar°CIP
dB (A)kg
KWS 100
15012500 - 2000 lit/h
0,66
125
380600 KWS100
20
00
800 KWS120
KWS 120
30014000 - 2000 lit/h
1,3
135
230 - 50/60
42340
5-5 +70IP55
1”69
C,P,T
KWS100 KWS120
CE
www.erdin
cklim
a.com
36
MODEL:
Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies
KSAhe KSAs 18-19 are air-air heat exchangers, which are particularly suitable for side or door installations on small control boards and other small enclosures which require minimal cooling within limited room conditions. These two models use four axial fans, which provide improved air Tcirculation and temperature distribution. The external circuit fans can be controlled by a DIN bar thermostat, saving energy and reducing noise.
The control board circuit fans have to run permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.
Standard
Adjustable DIN bar thermostat to control external circuit fans
3 meters power supply cableconnected in therminal board
Optionals
External air path deflector
Inlet 3 pole connector
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP54 self adhesive gasket
User manual in five languages
Internal air path deflector
Non standard painting
38
0
134 316
INT
ER
NA
L A
SS
EM
BLY
EX
TE
RN
AL
AS
SE
MB
LY
KSA 18
12360,21
24024036
-10 +55IP54
8
V - HzW/KWAA
m³/hm³/h
dB(A)°CIPkg
KSA 19
23570,31
38038048
-10 +55IP54
8C,D,V,W
230 - 50/60www.erdin
cklim
a.com
KSAhe KSAs 20-23 are air air heat exchangers designed to be fitted on the side, the door or the roof of control boards. The reduced depth to high performance ratio makes this one of the best product lines that the market can offer. Thanks to their high flow rate and head pressure , the radial fans Tensure a correct air circulation and an unvarying temperature distribution. The external circuit fan can be controlled by a DIN bar thermostat,
saving energy and reducing noise. The inside circuit fan runs permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.
Standard Optionals
IP55 protection degreeIP55
CE
MODEL:
Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
3 meters power supply cableconnected in therminal board
External air path deflector
IP54 self adhesive gasket
User manual in five languages
Adjustable DIN bar thermostat to control external circuit fans
Inlet 3 pole connector
Internal air path deflector
Non standard painting
86 3187
82
EX
TE
RN
AL
AS
SE
MB
LY
INT
ER
NA
L A
SS
EM
BLY
37
KSA 20
371600,71
55055065
-5 +55IP5410
V - HzW/KWAA
m³/hm³/h
dB(A)°CIPkg
KSA 23
471600,71
55055065
-5 +55IP5411
C,D,V,W
230 - 50/60www.erdin
cklim
a.com
38
KSA
Standard Optionals
IP55
CE
MODEL:
Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP55 protection degree
3 meters power supply cableconnected in therminal board
External air path deflector
IP54 self adhesive gasket
User manual in five languages
Adjustable DIN bar thermostat to control external circuit fans
Inlet 3 pole connector
Internal air path deflector
Non standard painting
86 3187
82
DIM
A M
ON
TA
GG
IO E
ST
ER
NO
DIM
A M
ON
TA
GG
IO IN
CA
SS
O
V - HzW/KWAA
m³/hm³/h
dB(A)°CIPkg
KSA 42
371600,71
55055065
-5 +55IP5410
KSA 43
471600,71
55055065
-5 +55IP5411
C,D,V,W
230 - 50/60
he KSAs 42-43 and 21 are air air heat exchangers designed to be fitted on the side, the door or the roof of control boards. The reduced depth to high performance ratio makes this one of the best product lines that the market can offer. Thanks to their high flow rate and head pressure , the radial fans Tensure a correct air circulation and an unvarying temperature distribution. The external circuit fan can be controlled by a DIN bar thermostat,
saving energy and reducing noise. The inside circuit fan runs permanently to avoid heat-pockets from forming. Four M6 threaded inserts are provided for fixing onto the cabinet.
www.erdin
cklim
a.com
KSA
Standard Optionals
IP55
CE
MODEL:
Power supply (C)Cooling capacityAbsorptionRunning current 50/60 HzProtection fuses Internal circuit flow rateExternal circuit flow rateNoise levelTemperature range (ambient)Internal circuit protection degreeWeight Available power supplies
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
IP55 protection degree
3 meters power supply cableconnected in therminal board
External air path deflector
IP54 self adhesive gasket
User manual in five languages
Adjustable DIN bar thermostat to control external circuit fans
Inlet 3 pole connector
Internal air path deflector
Non standard painting
107 318
12
50
EX
TE
RN
AL
AS
SE
MB
LY
INT
ER
NA
L A
SS
EM
BLY
39
KSA 21
230 - 50/6080
1700,75
185085073
-5 +55IP5418
C,D,V,W
V - HzW/KWAA
m³/hm³/h
dB(A)°CIPkg
www.erdin
cklim
a.com
40
MODELLO:
Power supply (C)Air flow rateDissipation powerFrontal air speedAbsorption Current absorptionProtection degreeNoise levelColorsPower supply cableDimension W D HWeight Available power supplies
KEA 60 / 100
KEA 200
VENTILATORShe KEA ventilation systems offer a wide range of functional solutions to cool control boards with primary air. There are two types available: the wall mounted version and the mini-tower for roof mount installations on control boards. They have a particularly high air flow rate. Ventilation Twith filtration represents an efficient solution in those cases in which the working ambient air is clean and the temperature inside the cabinet can
be higher than the external one. KELVIN offers with the KEA product line a solution panoramic suitable to satisfy any applicative, aesthetic and technical need. The new and exclusive KEA200 has a wide filtering area. This highly efficient design practically eliminates the need to clean the filters and represents a perfect example of KELVIN's continual commitment to developing new and innovative designs for the future.
KEA 200
230 - 50/60700210
185 / 90
0,38 / 0,4IP3368
RAL70323
30090
150014
C,D,V,W
KEA 100
230 - 50/60700210
85 / 900,38 / 0,4
IP3368
RAL 70323
375295915,9
C,D,V,W
KEA 60
230 - 50/60450135
80 / 980,36 / 0,44
IP3360
RAL70323
375295915,6
C,D,V,W
V - Hzm³/hW/KMsWAIP
dB (A)
mmmmmmmKg
CE
All drilling templates on outside view Noise level measured at 1 meter from the unit, 1,6 meter from the ground level, in free space
www.erdin
cklim
a.com
nti-condensate heaters are indispensable to avoid condensate from forming inside the cabinet during a unit's standstill and in instances of very low ambient temperatures or very high humidity. Since hot air tends to rise they have to be positioned in the lower part and possibly beneath Athose components that require protection. Maximum efficiency is reached installing the heater in a vertical position and orientating the supply
cable downwards. In case of large cabinets it is advisable to use multiple low rate heaters to obtain an unvarying temperature distribution. All KELVIN heaters are provided with a snapping fitment for the DIN EN 5002 conform 35 mm bar.
ANTICONDENSATIONHEATINGS
MAXI VENTILATED
Power supply
Heating capacity (W)
Maximum amperage (A)
Superficial temperature (°C)
Protection class
Protection degree
Approvals
Mounting
Dimensions (mm)
K5R035
250
1,5
75
I
20
VDE, UL
80 x 80 x178
K5R036
400
2,2
75
I
20
VDE, UL
80 x 80 x252
MINI
Power supply
Heating capacity(W)
Maximum amperage (A)
Superficial temperature (°C)
Protection class
Protection degree
Mounting
Approvals
K5R037
10
0,8
70
II
54
VDE, UL
AC/DC 110 - 250 max. 265V
CR TERM. + VENTIL.
Power supply
Air flow rate (m³/h)
Heating capacity (W)
Maximum amperage (A)
Protection class
Protection degree
Approvals
Mounting
Range of regulation (C°)
Dimensions (mm)
K5R040
35
350
7,5
20
UL
0 - 60
K5R041
35
350
11
20
UL
0 - 60
K5R042
45
550
8,5
20
UL
0 - 60
Bar 35mm. DIN EN 50022
K5R043
45
550
12
20
UL
0 - 60
II ( double isolation)
AC 220-230 / 50-60Hz
MIDI
Power supply
Heating capacity (W)
Maximum amperage (A)
Superficial temperature (°C)
Protection class
Protection degree
Approvals
Mounting
K5R028
15
0,5
165
I test 1600V
20
-
AC/DC 110-250V max. 265V
AC 110-120 / 50-60Hz
K5R029
30
1
190
I test 1600V
20
-
K5R030
45
1
105
I test 1600V
20
-
K5R031
60
1,5
110
I test 1600V
20
-
K5R032
75
1,8
110
I test 1600V
20
-
K5R033
100
2,4
130
I test 1600V
20
-
K5R034
150
4,5
140
I test 1600V
20
-
K5R038
20
1
110
II
54
VDE, UL
K5R039
30
1,5
120
II
54
VDE, UL
41
AC 220-230 / 50-60Hz
100 x 128 x 165
Bar 35mm. DIN EN 50022
Bar 35mm. DIN EN 50022
Bar 35mm. DIN EN 50022
www.erdin
cklim
a.com
MODEL:
Range of regulationContact capacityPrecisionProtection degreeAmbient temperatureDimensions (HxWxD)
K9S.022
from 50 to 100% UR5 A to 230V
+/- 3%IP20
from 0° to 60°67x50x38 mm
MODEL:
Range of regulationContact capacityAssemblyDifferential commutationProtection degreeApprovationBoxDimensions (HxWxD)
K7H.020 - K7H.021
from 0° to +60°C6A (1) 250 V ACDIN bar 35 mm
7KIP30
VDE, ULPlastic (UL94V0)
60x33x35 mm
7H.020 and K7H.021 are two electro-mechanical bimetal thermostats with contactors, which are normally open (with a blue regulation screw) and normally closed (with a red regulation screw) respectively. The former is suitable in controlling cooling devices (air-conditioners, air-water Kheat exchangers, air-air heat exchangers, and fans) or to provide high temperature alarms. The latter is suitable in controlling heating or
anticondensate devices (anticondensate heaters) K9S.022 is a humidistat with a 35 mm DIN bar (EN 5002) mount and generally used to control the anticondensate heaters.
K7H.020 K7H.021 K9S.022
Functional scheme of K7H.021 e del K9S.022.
Functional scheme of K7H.020.
42
ACCESSORIES
www.erdin
cklim
a.com