44
Rick Aguilar, Director of Job Training & Safety KMU SUBSTATION WORKSHOP JUNE 29-30, 2016 OTTAWA, KS

KMU SUBSTATION WORKSHOP

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: KMU SUBSTATION WORKSHOP

Rick Aguilar, Director of Job Training & Safety

KMU SUBSTATION WORKSHOP

JUNE 29-30, 2016 OTTAWA, KS

Page 2: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Hazards & Safety Rules

• Qualified Personnel & Task-Based Hazard Mitigation

• Worksite Applications & Considerations

• Electric Arc Protection

• FACE Reports & Lessons Learned

• Electrical Principles

Ohm’s Law

Circuit review

Page 3: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

HAZARDS & SAFETY RULES

Page 4: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Re-energized line(s)

• Induced voltages & currents

Magnetic induction

Capacitive induction

• Step potential

• Touch potential

Page 5: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Magnetic voltages

• Capacitive induction

Page 6: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Equal to the difference in voltage, given by the

voltage distribution curve, between two points at

different distances from the electrode

Page 7: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Voltage resulting from

touching a conductive

object that is connected

to a remote energized

component

Page 8: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• OSHA Regulations

1910.269(n)(2)

• General. For any employee to work transmission and distribution

lines or equipment as deenergized, the lines or equipment shall

be deenergized under the provisions of paragraph (m) of this

section and shall ensure proper grounding of the lines or

equipment as specified in paragraphs (n)(3) through (n)(9) of this

section.

1910.269(n)(3)

• Equipotential zone. Temporary protective grounds shall be

placed at such locations and arranged in such a manner that

the employer can demonstrate will prevent each employee

from being exposed to hazardous differences in electric

potential.

Page 9: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Standards

IEEE Std. 1048-2003

NESC C2-2012

• Placement of grounding

sets for employee

protection

Page 10: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 512 Substations

512.1 General Rules

512.2 Working in an Energized Substation

512.3 Hazardous Energy Control (LOTO)

512.4 Batteries

512.8 Circuit Breaker Maintenance & Repair

512.9 Working in Transformer Tanks & Vessels

512.10 Work in Manholes & Vaults

512.11 Splicing & Terminating

512.12 Vault/Manhole Rescue

*Rev. 15, 2012

Page 11: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 507 Overhead Lines and Equipment

507.6 Working on De-energized Lines and Equipment

507.11 Stringing or Removing De-energized Conductors

507.12 Stringing Adjacent to Energized Lines

507.13 Grounding – General

507.14 Equal Potential Grounding

• 509 Underground Lines and Equipment

509.5 Work on De-energized Cables

509.7 Grounding – URD Circuits

*Rev. 15, 2012

Page 12: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Nominal voltage to ground

Minimum Clear Distance for Condition 1,2

Condition A Condition B Condition C

m ft m ft m ft

601-2500 V 0.9 3.0 1.2 4.0 1.5 5.0

2501-9000 V 1.2 4.0 1.5 5.0 1.8 6.0

9001 V-25 kV 1.5 5.0 1.8 6.0 2.8 9.0

Over 25-75 kV3 1.8 6.0 2.5 8.0 3.0 10.0

Above 75 kV3 2.5 8.0 3.0 10.0 3.7 12.0

*Table 512.1. Minimum Depth of Clear Working Space

at Electric Equipment, Over 600 V

APPA Safety Manual 15th Ed. pg. 233

Page 13: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Nominal voltage (kV)

Phase-to-Phase

Distance

Phase-to-Ground Phase-to-Phase

m ft m ft

0.050 to 0.300 2 Avoid Contact Avoid Contact

0.301 to 0.750 0.33 1.09 0.33 1.09

0.751 to 5.0 0.63 2.07 0.63 2.07

5.1 to 15.0 0.65 2.14 0.68 2.24

15.1 to 36.0 0.77 2.53 0.89 2.92

36.1 to 46.0 0.84 2.76 0.98 3.22

46.1 to 72.5 1.00 3.29 1.20 3.94

Table R-6

Alternative Minimum Approach Distances for Voltages of 72.5 kV and less 1

Page 14: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Altitude above

sea level (m)

Correction

Factor

0 to 900 1.00

901 to 1,200 1.02

1,201 to 1,500 1.05

1,501 to 1,800 1.08

1,801 to 2,100 1.11

2,101 to 2,400 1.14

2,401 to 2,700 1.17

2,701 to 3,000 1.20

3,001 to 3,600 1.25

3,601 to 4,200 1.30

4,201 to 4,800 1.35

4,801 to 5,400 1.39

5,401 to 6,000 1.44

Table R-5 Altitude

Correction Factor

Multiply distances from

Table R-6 with correction

factor corresponding to

altitude of work

Page 15: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

QUALIFIED PERSONNEL & TASK-

BASED HAZARD MITIGATION

Page 16: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• One who has received training in and has

demonstrated skills and knowledge in the construction

and operation of electrical equipment and installation

and the hazards involved.

Page 17: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• One who has the skill and knowledge related

to the construction and operation of the

electrical equipment and installations and has

received safety training to recognize and

avoid the hazards involved.

May be considered qualified with respect to

certain equipment & method but still

unqualified for others.

Page 18: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Employer must provide the employee in charge with

all available information that relates to the

determination of existing characteristics and conditions under §§1910.269(a)(4) and 1926.950(d):

• Employer shall ensure employee in charge conducts

a job briefing

Information on existing characteristics

Information about existing conditions

§§1910.269(c)(1)(i) & 1926.952(a)(1)

Page 19: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Employer to employee in charge, employee in

charge to coworkers

• Hazards associated with

the job

• Work procedures involved

• Special precautions

• Energy-source controls

• Personal protective equipment requirements

§§1910.269(c)(1)(ii) & 1926.952(a)(2)(b)

Page 20: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Number of briefings

• At least one before

each day or shift

• When there

significant changes

§§1910.269(c)(3) & 1926.952(a)(2)(c)

Page 21: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Short discussion

• Satisfactory if the work involved is routine

Detailed discussion

• If work is particularly hazardous, or

• If employees cannot be expected to recognize and

avoid the hazards involved

Page 22: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Isolate – not able to

contact energized part

• Insulate – same

principle used with

energized work

Page 23: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Magnetic voltages

• Capacitive induction

Page 24: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Key is to place worker in parallel with low resistance path to shunt dangerous current & limit voltage across worker.

• Return path considerations System neutral

Ground rod

• Approved ground clams, jumpers ≥ #2 copper, clean surfaces

Page 25: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

ELECTRIC ARC PROTECTION

Subtitle

Page 26: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Outer layer of clothing must be arc-rated for

incident energy exceeding 2.0 cal/cm2

• Arc-rated protection must cover entire body,

with certain exceptions:

Protection for hands (rubber gloves with protectors

or, for exposures ≤ 14 cal/cm2, heavy-duty (12oz)

leather work gloves)

Protection for feet (heavy work shoes or boots)

Protection for the head under certain conditions

§1910.269(l)(8) & §1926.960(g)

Page 27: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Federal Register pg. 20489

§1910.269(l)(8) & §1926.960(g)

Page 28: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Head when incident

energy is < 9 cal/cm2

(single phase), or < 5

cal/cm2 for other

exposures

• Hands when wearing

rubber gloves and

protectors

• Feet when wearing

heavy leather boots

Page 29: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Hazard Risk

Category 0Hazard Risk

Category 2

Hazard Risk

Category 3Hazard Risk

Category 4Hazard Risk

Category 1

Page 30: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 100% cotton long sleeve shirt

• Long pants

• Safety glasses

• Hearing protection

• Leather and insulated gloves (as required)

• Leather work boots

Page 31: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 4+ cal long sleeve shirt & long pants (or) coveralls

• Hardhat

• Safety glasses

• Arc rated face shield

• Hearing protection (inserts)

• VR gloves

• Leather gloves

• Leather work boots

Page 32: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 8+ cal long sleeve shirt & long pants (or) coveralls

• Hardhat

• Safety glasses

• Arc rated face shield

• Hearing protection (inserts)

• VR gloves

• Leather gloves

• Leather work boots

Page 33: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 25+ flashsuit w/ hood over long sleeve shirt and long pants

• Safety glasses

• Arc rated face shield

• Hearing protection (inserts)

• VR gloves

• Leather gloves

• Leather work boots

Page 34: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• 40+ flashsuit w/ hood over arc-rated FR long sleeve shirt and long pants

• Safety glasses

• Arc rated face shield

• Hearing protection (inserts)

• VR gloves

• Leather gloves

• Leather work boots

Page 35: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Layering Outer layers must be flame resistant

Under layers must be non-melting

• Fit – Clothing shall fit properly (loose), w/ least interference

• Coverage – Clothing must cover potentially exposed areas (wrist, neck)

• Care & Maintenance Inspect before use

Launder according to mfg’s instructions

*Photo courtesy of Salisbury

Page 36: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Equipment exposed to electric arcs must

pass drop test post-exposure

• No requirement to pass an arc rating test

Page 37: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Assess worksite for hazards

• Determine appropriate

controls

• May use isolation,

insulation, and

equipotential zones

• Ensure no contact with

equipment and ground

rod

Page 38: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Stringing adjacent to

energized lines and equipment

• Placement of tools and

materials

• Worksite access control

• Ensure no contact with

equipment and ground rod

Page 39: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

FACE REPORTS & LESSONS

LEARNED

Page 40: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Page 41: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Page 42: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Page 43: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

• Inspections and P.M. need to be completed and

are critical safety element for personnel and facilities

• Control access and ensure personnel are qualified

for tasks

• Communicate PPE & MAD requirements with

exposed workers

Page 44: KMU SUBSTATION WORKSHOP

Energized & De-Energized Work Procedures in Substations

KMU Substation WorkshopJune 29-30, 2016

Rick Aguilar, CUSP, PHR

Director of Job Training & Safety

Kansas Municipal Utilities

101 ½ N. Main

McPherson, KS 67460

(316) 293-6933

[email protected]

Serving municipal utilities for 85 years