Upload
rindarayna
View
232
Download
0
Embed Size (px)
Citation preview
8/20/2019 L2 V4 02 Datapoints Configuration E 01
1/43
Datapoints Configuration
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
8/20/2019 L2 V4 02 Datapoints Configuration E 01
2/43
Schneider Electric 2- CS&P – Datapoints Configuration – E01
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
8/20/2019 L2 V4 02 Datapoints Configuration E 01
3/43
Schneider Electric 3- CS&P – Datapoints Configuration – E01
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
8/20/2019 L2 V4 02 Datapoints Configuration E 01
4/43
Schneider Electric 4- CS&P – Datapoints Configuration – E01
TYPED DIGITAL INFORMATION
It is an information which is representing a special input regarding theMiCOM C264 inner automations.
Examples :
- Switchgear Position DPS, Locking device status SPS, BayLocal/Remote DPS
• Typed / Generic xPS
GENERIC INFORMATION
It is a standard information which can be configured at any level.
Examples :
- Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
5/43
Schneider Electric 5- CS&P – Datapoints Configuration – E01
Mapping SPS
It is an input which is produced by mapping to another DP. Each state ofthis DP is mapped and corresponds to a state of the mapping SPS.
• Typed / Generic xPS
Day cyclic SPSDay cyclic SPSDay cyclic SPSDay cyclic SPS
It is a transient SPS which is triggered every day at fixed time. (accuracy of+/- 1 minute)(8 max per C264).
8/20/2019 L2 V4 02 Datapoints Configuration E 01
6/43
Schneider Electric 6- CS&P – Datapoints Configuration – E01
• Add / Configure a SPS (1)1) SPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some SPS are System Info .
Short Name :SCE Key + appears in C264 local SOE
Detection Mode :permanent : DI remains ON as far as signal is ON
Time tagging :done at starting/end of signal filtering
2) SPS attributes
Long Name :appears in viewers + printers
Persistence filtering :SPS should remain valid “Set” or “Reset” duringthe configured timer
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :yes = SPS in state list (MSC)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
7/43
Schneider Electric 7- CS&P – Datapoints Configuration – E01
• Add / Configure a SPS (2)3) SPS can be acquired by DIU/CCU board , IED . Some SPS are computed by
C264 application (C264 automation, …)=> Relations under a SPS
Has for IED address :SPS acquired by IED
Wired on : DI Channel
SPS acquired by DIU/CCU board
V4.7 V4.7 V4.7 V4.7
8/20/2019 L2 V4 02 Datapoints Configuration E 01
8/43
Schneider Electric 8- CS&P – Datapoints Configuration – E01
1) DPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some DPS are System Info .
Short Name :SCE Key + appears in C264 local SOE
Time tagging :done at starting/end of motion
2) DPS attributes
Long Name :appears in viewers + printers
Motion & Persistence filtering :Motion : eliminate transients 00 and/or 11 motion
states Persistence : DPS should remain valid “Open” or“Closed” during the configured timer
Forcing Management :
if FSS enabled, auto/manual force
LHMI display :yes = DPS in state list (MSC)
• Add / Configure a DPS (1)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
9/43
Schneider Electric 9- CS&P – Datapoints Configuration – E01
• Add / Configure a DPS (2)3) DPS can be acquired by DIU/CCU board , IED . Some DPS are computed by
C264 application (C264 automation, …)=> Relations under a DPS
Has for IED address :DPS acquired by IED
Wired on :DPS acquired by 2 channels (“open” and“closed”) on DIU/CCU board
DPS computed from 2 SPS :DPS acquired using 2 SPS, 1 for “open” and 1 for“closed”
8/20/2019 L2 V4 02 Datapoints Configuration E 01
10/43
Schneider Electric 10- CS&P – Datapoints Configuration – E01
1) MPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some MPS are System Info .A MPS can have a maximum 16 valid states.
Short Name :SCE Key + appears in C264 local SOE
2) MPS attributes
Long Name :appears in viewers + printers
Motion & Persistence filtering :Motion : inhibition (cf. next slide) Persistence : MPS should remain in one validstate during the configured timer
Forcing Management :if FSS enabled, auto/manual force
LHMI display :yes = MPS in state list (MSC)
• Add / Configure a MPS (1)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
11/43
Schneider Electric 11- CS&P – Datapoints Configuration – E01
Example : Change State with Filtering “all DI =0 “
During change all DI =0
End of change state
Before change state 0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
During change all DI =1
Example : Change State with Filtering “all DI =1 “
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
1 0
1 1
1 2
1 3
1 4
1 5
1 6
0
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
• Add / Configure a MPS (2)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
12/43
Schneider Electric 12- CS&P – Datapoints Configuration – E01
• Add / Configure a MPS (3)3) MPS can be acquired by DIU/CCU board , IED . Some MPS are computed by
C264 application (C264 automation, …)=> Relations under a MPS
Has for IED address :
MPS acquired by IED
Wired on :MPS acquired by a maximum of 16 channels onDIU/CCU boards
8/20/2019 L2 V4 02 Datapoints Configuration E 01
13/43
Schneider Electric 13- CS&P – Datapoints Configuration – E01
• Content
SPS, DPS, MPS
MV, TPI, Counters
SPC, DPC, SetPoints
Datapoints Quality
8/20/2019 L2 V4 02 Datapoints Configuration E 01
14/43
Schneider Electric 14- CS&P – Datapoints Configuration – E01
• Add / Configure a MV (1)1) MV can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some MV are System Info .
Short Name :SCE Key + appears in C264 local SOE
2) MV attributes in General Tab
Long Name :appears in viewers + printers
Analogue Type :Analogue (AI,CT/VT,IED)
or Digital Measurement
Forcing Management :
if FSS enabled, automatic force to a given value
LHMI display :yes = MV in measurementslist (MSC)
MV transmission :SBUS, LHMI
8/20/2019 L2 V4 02 Datapoints Configuration E 01
15/43
Schneider Electric 15- CS&P – Datapoints Configuration – E01
• Add / Configure a MV (2)
Minimum / Maximum Value :scaled values for SCADA and OI display + FullScale definition
3) MV attributes in Value Features Tab
Thresholds definition :scaled values for LLL, LL, L, H, HH, HHHthresholds + hysteresis
8/20/2019 L2 V4 02 Datapoints Configuration E 01
16/43
Schneider Electric 16- CS&P – Datapoints Configuration – E01
• Add / Configure a MV (3)
Scaling Low :Linear / Quadratic
4) MV attributes in Scaling Tab
Minimum / Maximum acquisition values :- if transducer 0/10 mA :
min=0, max=10 * - if transducer 4/20 mA : min=0, max=16 *
- if voltage of CT/VT with nominal ph-N = 57.7 V min=0, max=57.7 *
- if IED (T103 : min=0, max=1; Modbus : cf. IED
documentation) …* schedule a max value = 120% of expected max max=12, max=20, max=70 ... (transducers canmeasure more and display overflow and
undershoot measurements).
Scaling coefficients :scaled value = A1 x acq. Value + B1
Up to 20 segments
Additional segments :
A2, B2 - A3, B3 - ...
8/20/2019 L2 V4 02 Datapoints Configuration E 01
17/43
Schneider Electric 17- CS&P – Datapoints Configuration – E01
• Add / Configure a MV (4)5) MV can be acquired by AIU/TMU/DIU/CCU board , IED . Some MV arecomputed by C264 application (C264 automation, …)=> Relations under a MV
Has for IED address :
MV acquired by IED
Wired on DI Channels :Digital Measurements acquired by a maximum of64 channels on DIU/CCU boards
Wired on AI Channel :Channel to be configured (cf. next slide)
Computed by CT/VT board :relation to be configured
8/20/2019 L2 V4 02 Datapoints Configuration E 01
18/43
Schneider Electric 18- CS&P – Datapoints Configuration – E01
• Add / Configure a MV (5)6) AI Board channel configuration
Transducer range :
Scanning acquisition period :cf. C264 configuration, Measurements tab
8/20/2019 L2 V4 02 Datapoints Configuration E 01
19/43
Schneider Electric 19- CS&P – Datapoints Configuration – E01
• Add / Configure a TPI (1)1) TPI can ONLY be added under a Tap Changer object belonging to aTransformer module.=> Add / Configure a Tap Changer object :
Built-in function :Tap Changer
Min TAP, Max TAP
Execution timeout :Time allowed for Tap Changing
8/20/2019 L2 V4 02 Datapoints Configuration E 01
20/43
Schneider Electric 20- CS&P – Datapoints Configuration – E01
• Add / Configure a TPI (2)2) TPI attributes :2.1) General Tab
TPI type :- Analogue Tap Position acquired byAIU or IED,- Coded Digital Measurement (1/N,
decimal, gray, BCD) acquired by DIU
Note : Tabs are not the same - Value Features is common to Analogue and Digital TPI - Scaling & Tap Position for Analogue
- Tap Position for Digital
8/20/2019 L2 V4 02 Datapoints Configuration E 01
21/43
Schneider Electric 21- CS&P – Datapoints Configuration – E01
• Add / Configure a TPI (3)2) TPI attributes :2.2) Value Features Tab
Minimum / Maximum Value :Should comply with Tap Changer objectconfiguration
Thresholds definition :scaled values for LLL, LL, L, H, HH, HHHthresholds
8/20/2019 L2 V4 02 Datapoints Configuration E 01
22/43
Schneider Electric 22- CS&P – Datapoints Configuration – E01
• Add / Configure a TPI (4)2) TPI attributes :2.3) Scaling Tab (for Analogue TPI only)
Minimum / Maximum Acquisition Value :
Same as for a MV
2.4) Tap Position Tab
For Analogue TPI :
filtering => transient “intertap” filtering current valid range => gives validity DC inputrange for each tap
For Digital TPI :filtering => signal validation inhibition => transient “intertap” filtering
8/20/2019 L2 V4 02 Datapoints Configuration E 01
23/43
Schneider Electric 23- CS&P – Datapoints Configuration – E01
• Add / Configure a TPI (5)3) TPI can be acquired by AIU/DIU/CCU board , IED .=> Relations under a TPI
Has for IED address :TPI acquired by IED
Wired on DI Channels :Digital TPI acquired by a maximum of 64 channelson DIU/CCU boards
Wired on AI Channel :Channel to be configured
8/20/2019 L2 V4 02 Datapoints Configuration E 01
24/43
Schneider Electric 24- CS&P – Datapoints Configuration – E01
• Add / Configure a Counter (1)1) Counter can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy.
Short Name :SCE Key + appears in C264 local SOE
2) Counter attributes in General Tab
Long Name :appears in viewers + printers
Counter Type :Standard (standard DI counting)
Energy import / Energy export
Counter Acquisition :
validation => min pulse length to be counted invalidity => for double, non complementarity
LHMI display :yes = Counter inmeasurements list (MSC)
Counter Management :cf. next slide
8/20/2019 L2 V4 02 Datapoints Configuration E 01
25/43
Schneider Electric 25- CS&P – Datapoints Configuration – E01
• Add / Configure a Counter (2)2) Counter attributes in General Tab
Counter cumulative period :- configure a period at the end of which the counter value is transmitted (SBUS,LHMI) - possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, … 24h -at the end of this period, counter value can be reset (C264 re-start counting from
0)
Counter Total for IED counters :Yes => IED is sending real counter
value No => IED is sending non-scaledvalue
8/20/2019 L2 V4 02 Datapoints Configuration E 01
26/43
Schneider Electric 26- CS&P – Datapoints Configuration – E01
• Add / Configure a Counter (3)3) Counter can be acquired by DIU/CCU board , IED . Some Counters arecomputed by C264 application (C264 automation, …)=> Relations under a Counter
Has for IED address :
Counter acquired by IED
Wired on :Single counter => 1 DI Channel Double counter => 2 DI Channels
integrate :Counter computed by MV integration (example : P) Counter type is not “Standard” but “Energy import” or “Energy export”
Integration of P or Q :In case the scale and unit is to big ( In case the scale and unit is to big ( In case the scale and unit is to big ( In case the scale and unit is to big (MVarh MVarh MVarh MVarh for ex.), iffor ex.), iffor ex.), iffor ex.), ifenergy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,the value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isequal to 0).equal to 0).equal to 0).equal to 0).
!
8/20/2019 L2 V4 02 Datapoints Configuration E 01
27/43
Schneider Electric 27- CS&P – Datapoints Configuration – E01
• Content
SPS, DPS, MPS
MV, TPI, CountersSPC, DPC, SetPoints
Datapoints Quality
8/20/2019 L2 V4 02 Datapoints Configuration E 01
28/43
Schneider Electric 28- CS&P – Datapoints Configuration – E01
TYPED CONTROL
It is an information which is representing a special functionality regardingthe MiCOM C264 inner automations.
Examples :
- Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC,Sync CB Close
• Typed / Generic xPC
GENERIC CONTROL
It is a standard control which can be configured at any level.
Examples :
- Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)
8/20/2019 L2 V4 02 Datapoints Configuration E 01
29/43
Schneider Electric 29- CS&P – Datapoints Configuration – E01
• Add / Configure a SPC (1)1) SPC can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some SPC are System Info .
Short Name :SCE Key + appears in C264 local SOE
Activation Mode :- transient => configure pulse duration - permanent
- permanent until feedback
2) SPC attributes General Tab
Long Name :appears in viewers + printers
LHMI display :yes = SPC in control list
(MSC)
Inter Control timeout :no possibility to execute 2 consecutive ordersduring this timer
8/20/2019 L2 V4 02 Datapoints Configuration E 01
30/43
Schneider Electric 30- CS&P – Datapoints Configuration – E01
• Add / Configure a SPC (2)3) SPC execution may be dependant on Local/Remote status ofSubstation/Bay, on SBMC and/or on control uniqueness=> SPC attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed,from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMIallowed, from OI & SCADA notallowed
SBMC :advised not to use SBMC (put No)
if needed, local transfer when SS is inRemote
Note : This is internal automation existing and configurable for all xPC.
8/20/2019 L2 V4 02 Datapoints Configuration E 01
31/43
Schneider Electric 31- CS&P – Datapoints Configuration – E01
• Add / Configure a SPC (3)4) SPC can be executed on DOU/CCU board , IED . Some SPC are computedby C264 application (C264 automation, …)=> Relations under a SPC
Has for IED address :
SPC executed by IED
Wired on : DO ChannelSPC executed on DOU/CCU board
Interlock SPS :holds a logic allowing/blocking the control
Associated DO channel status SPS :for hardwired SPC only
Auto/Manu dependency :
blocks the operator control if an automation is inprogress => connect to SPS/DPS givingautomation status
Feedback definition :for C264 acknowledgement cf. slide “§3.4”
8/20/2019 L2 V4 02 Datapoints Configuration E 01
32/43
Schneider Electric 32- CS&P – Datapoints Configuration – E01
• Add / Configure a DPC (1)1) DPC can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some DPC are System Info .
Short Name :SCE Key + appears in C264 local SOE
Activation Mode :- transient => configure pulse duration (2channels “open” / “close”)
- permanent - permanent until feedback
2) DPC attributes
Long Name :appears in viewers + printers
LHMI display :yes = DPC in control list
(MSC)
Inter Control timeout :no possibility to execute 2 consecutive ordersduring this timer
8/20/2019 L2 V4 02 Datapoints Configuration E 01
33/43
Schneider Electric 33- CS&P – Datapoints Configuration – E01
• Add / Configure a DPC (2)3) DPC execution is dependant on one hand from Local/Remote status ofSubstation/Bay and on the other hand from control uniqueness=> DPC attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed,from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMIallowed, from OI & SCADA notallowed
SBMC :advised not to use SBMC (put No)
if needed, local transfer when SS is inRemote
Note : This is internal automation existing and configurable for all xPC.
8/20/2019 L2 V4 02 Datapoints Configuration E 01
34/43
Schneider Electric 34- CS&P – Datapoints Configuration – E01
• Add / Configure a DPC (2)4) DPC can be executed on DOU/CCU board , IED . Some DPC are computedby C264 application (C264 automation, …)=> Relations under a DPC
Has for IED address :
DPC executed by IED
Wired on : DO ChannelDPC executed on DOU/CCU board
2 Interlock SPS (open/close):holds a logic allowing/blocking the controls
2 Associated DO channel status SPS :for hardwired DPC only
Auto/Manu dependency :
blocks the operator control if an automation is inprogress => connect to SPS/DPS givingautomation status
Feedback definition :for C264 acknowledgement cf. slide “§3.4”
8/20/2019 L2 V4 02 Datapoints Configuration E 01
35/43
Schneider Electric 35- CS&P – Datapoints Configuration – E01
• Configure a xPC feedback1) SPC/DPC can have for feedback a SPS/DPS=> C264 checks if control success (ex: CB control, feedback CB position)=> Example given for DPC with DPS feedback
Relation “has for feedback”with 2 attributes :- execution timeout : maximumtime allowed to get feedback - status check : C264 will checkstatus before performing control
DPC
DPS
8/20/2019 L2 V4 02 Datapoints Configuration E 01
36/43
Schneider Electric 36- CS&P – Datapoints Configuration – E01
• Add / Configure a SetPoint (1)1) SetPoints can be added at Substation , Voltage Level , Bay , Module ,ISaGRAF automation level in Electric hierarchy.
Short Name :SCE Key + appears in C264 local SOE
SetPoint type :
2) SetPoint attributes
Long Name :appears in viewers + printers
LHMI display :yes = SetPoint in control list(MSC)
Minimum / Maximum value :
raw values for SetPoint validity
For Digital SetPoint :increment value pulse duration
8/20/2019 L2 V4 02 Datapoints Configuration E 01
37/43
Schneider Electric 37- CS&P – Datapoints Configuration – E01
• Add / Configure a SetPoint (2)3) SetPoint execution is dependant on one hand from Local/Remote status ofSubstation/Bay and on the other hand from control uniqueness=> SetPoint attributes Dependencies tab
Substation Local/Remote :
SS Local => control from OI allowed,from SCADA forbidden
Control Uniqueness
Bay Local/Remote :
Bay Local => control from LHMIallowed, from OI & SCADA notallowed
SBMC :advised not to use SBMC (put No)
if needed, local transfer when SS is inRemote
Note : This is internal automation existing and configurable for allSetpoints.
8/20/2019 L2 V4 02 Datapoints Configuration E 01
38/43
Schneider Electric 38- CS&P – Datapoints Configuration – E01
• Add / Configure a SetPoint (3)4) SetPoints can be executed on DOU/CCU board , IED . Some SetPoints arecomputed by C264 application (C264 automation, …)=> Relations under a SetPoints
Has for IED address :SP executed by IED
DO Channels :
C264 will close DO channels using configuredcode (BCD, binary, …)
Auto/Manu dependency :blocks the operator control if an automation is in
progress => connect to SPS/DPS givingautomation status
AO Channels :C264 will set AO channel
8/20/2019 L2 V4 02 Datapoints Configuration E 01
39/43
Schneider Electric 39- CS&P – Datapoints Configuration – E01
• Content
SPS, DPS, MPS
MV, TPI, CountersSPC, DPC, SetPoints
Datapoints Quality
8/20/2019 L2 V4 02 Datapoints Configuration E 01
40/43
Schneider Electric 40- CS&P – Datapoints Configuration – E01
• SPS Status
SPS STATUS
RESET
SET
SELF CHECK FAULTY
MEANING
Electric status 0
Electric status 1
Faulty DI Channel on board
TOGGLING Toggling filtering has detected behaviour
UNKNOWN IED acquiring DP is disconnected from C264
FORCED SET * SPS is Forced Set by C264 (FSS enable)
SUBSTITUTED SET * SPS is Substituted Set by Oper. (FSS enable)
SUPPRESSED SPS is Suppressed by Oper. (FSS enable)
* => Same for RESET
Quality => gives the nature of invalidity
8/20/2019 L2 V4 02 Datapoints Configuration E 01
41/43
Schneider Electric 41- CS&P – Datapoints Configuration – E01
• DPS Status
DPS STATUS
OPEN
CLOSED
SELF CHECK FAULTY
MEANING
Electric status 01
Electric status 10
Faulty DI Channel on board
TOGGLING Toggling filtering has detected behaviour
UNKNOWN IED acquiring DP is disconnected from C264
FORCED OPEN * DPS is Forced Open by C264 (FSS enable)
SUBSTITUTED OPEN * DPS is Substituted Open by Op. (FSS enable)
SUPPRESSED DPS is Suppressed by Oper. (FSS enable)
* => Same for CLOSED
Quality => gives the nature of invalidity
JAMMED Electric status 00
UNDEFINED Electric status 11
8/20/2019 L2 V4 02 Datapoints Configuration E 01
42/43
Schneider Electric 42- CS&P – Datapoints Configuration – E01
• MPS Status
MPS STATUS
STATE 1 -> STATE 16
SELF CHECK FAULTY
MEANING
Only one channel activated
Faulty DI Channel on board
TOGGLING Toggling filtering has detected behaviour
UNKNOWN IED acquiring DP is disconnected from C264
FORCED STATE N * MPS is Forced St. N by C264 (FSS enable)
SUBSTITUTED STATE N * MPS is Substituted St. N by Op. (FSS enable)
SUPPRESSED MPS is Suppressed by Oper. (FSS enable)
Quality => gives the nature of invalidity
UNDEFINED No channel or more than one activated
8/20/2019 L2 V4 02 Datapoints Configuration E 01
43/43
Schneider Electric 43- CS&P – Datapoints Configuration – E01
• MV Status
MV STATUS
VALID
SELF CHECK FAULTY
MEANING
MV in between min/MAX and/or L/H threshold
Faulty DI/AI Channel on board
TOGGLING Toggling filtering has detected behaviour
UNKNOWN IED acquiring DP is disconnected from C264
FORCED MV is Forced C264 (FSS enable)
SUBSTITUTED STATE N * MV is Substituted by Op. (FSS enable)
SUPPRESSED MV is Suppressed by Oper. (FSS enable)
Quality => gives the nature of invalidity
UNDEFINED No DI channel or more than one activated DM
OVERRANGE Acquisition out of range
OPEN CIRCUIT No current on AI channel (mA)
OVERSHOOT [1,2,3] Over H, HH, HHH Threshold
UNDERSHOOT [1,2,3] Under L, LL, LLL Threshold