PERIODIC SERVICE MAINTENANCE 1st
RUMAH SAKIT UNHAS
Attn : Bpk. Adi
Bpk Andi Iqbal Sinrang
PSA/01/RSU/XI/13/JCS
2
� Informasi Data Unit
� Performance Unit
� Data Hasil Pemeriksaan
� Saran
� Pekerjaan Lanjutan yang Diperlukan
REPORT CONTENTS
Periodic Service Maintenance ke 1 tanggal 21 – 25 October 2013
INFORMASI DATA UNIT
3
RUMAH SAKIT UNHAS
4
Informasi Data Unit
Chiller 1
YORK - Air Cooled Screw Chiller
Model : YGAS090SAE
Serial No. : 50531M10595909
Chiller Capacity : 316.4 kWr = 90 Ton
Power Input : 105.8 Kw
Evaporator water flow : 240 Gpm
Pressure drop water : 62.4 Kpa = 0.62 Kg/cm2
5
Informasi Data Unit
Chiller 2
YORK - Air Cooled Screw Chiller
Model : YGAS090SAE
Serial No. : 50531M10595910
Chiller Capacity : 316.4 kWr = 90 Ton
Power Input : 105.8 Kw
Evaporator water flow : 240 Gpm
Pressure drop water : 62.4 Kpa = 0.62 Kg/cm2
6
PERFORMANCE UNIT
RUMAH SAKIT UNHAS
7
Performance Unit – Chiller 1
Secara general chiller beroperasi dengan baik, semua parameter sesuai dengan design unit.
� Saat ini STD evaporator masih bagus yaitu 0.7 ° C. untuk mendapatkan STD ini dilakukan
pengurangan selisih pembacaan antara leaving evaporator (LCHLT) dengan saturated
refrigerant temperature.
� Level refrigerant di sight glass evaporator terlihat pada sigth glass ¾
� Oil level di sight glass saat unit beroperasi : Full
� Telah dilakukan service annual Shutdown
� Saat kunjungan chiller beroperasi pada persentase RLA antara 35.3 – 37.0 %.
� Pressure drop evaporator yang terbaca saat ini 1.5 Kg/cm2. dengan pressure inlet 4 bar,
pressure outlet 2.5 Bar.
8
Performance Unit – Chiller II
Secara general chiller beroperasi dengan baik, semua parameter sesuai dengan design unit.
� Saat ini STD evaporator masih dalam range yaitu 2.5 ° C. untuk mendapatkan STD ini dilakukan
pengurangan selisih pembacaan antara leaving evaporator (LCHLT) dengan saturated
refrigerant temperature.
� Level refrigerant di sight glass evaporator terlihat pada sigth glass ¾
� Oil level di sight glass saat unit beroperasi : Full
� Telah dilakukan service annual Shutdown
� Saat kunjungan chiller beroperasi pada persentase RLA antara 46 – 48 %.
� Pressure drop evaporator yang terbaca saat ini 1.5 Kg/cm2. dengan pressure inlet 4 bar,
pressure outlet 2.5 Bar.
9
DATA HASIL PEMERIKSAAN
RUMAH SAKIT UNHASS
10
Data Hasil PemeriksaanLog Sheet Chiller#1
No Desc Before AftetKondisi
System
1 Leaving water temperature C 14.1 15.7 Normal
2 Return water temperature C 17.1 18.2 Normal
3 Ambient Temperature C 26.7 26.8 Normal
4 Saturated Discharge Temp C 44.1 40.6 Normal
5 Discharge Superheat C 20.6 13.1 Normal
6 Liquid Line Temperature C 33.4 37.9 Normal
7 Discharge Temperature C 64.5 43.7 Normal
8 Oil Temperature C 61.3 52.8 Normal
9 Oil Sink Temperature C 52.0 41.9 Normal
10 Compressor Running Hour 7062 7128 Normal
11 Compressor Start 1849 1858 Normal
12 Evaporator Pressure Kpag 354 384 Normal
13 Discharge Pressure Kpag 1033 931 Normal
14 Oil Pressure Kpag 952 836 Normal
15 Ampere 88.3 73.6 Normal
16 Incoming Voltage 380 380 Normal
17 Total Consumption KW 46.4 38.70 Normal
20 Control Voltage 115 115 Normal
21 Evaporator water pressure drop 1.5 Bar 1.5 Bar Normal
Analisa Data Log Sheet dan Hasil pemeriksaan Chiller #1
� Berdasarkan hasil logsheet yang ada, semua parameter berada pada range normal.
� Condenser pressure cenderung menurun antara sebelum dan sesudah cleaning,
� Saat ini flow yang mengalir pada Evaporator melebihi dari design unit chiller. Hal itu dapat kita lihat
dengan membandingkan antara pressure drop yang ada saat ini.
Saat ini pressure drop unit chiller 1.5 Bar, seharusnya sesuai dengan design 6.2 Bar.
� Halamana berikut terlampir dash board, dari dash board tersebut kita dapat melihat perkembangan dan
perubahan dari chiller selama kunjungan/periodic maintenance.
� Dilakukan perhitungan tonase chiller tonase menggunakan rumus berikut
TR =��������������� �� �∆���������������������&������(℉)
��
Untuk mengetahui flow yang mengalir saat ini, dapat dilakukan dengan 2 metode :
1. menggunakan flow meter
2. menggunakan perbandingan antara pressure drop dan flow yang mengalir, terlampir tabel dihalaman
berikutnya.
11
Data Hasil Pemeriksaan
12
Data Hasil Pemeriksaan
13
Data Hasil PemeriksaanDashboard monitoring Log Sheet Chiller#1
0
10
20
30
40
50
60
Discharge Temperature
Oil Temperature
Oil Sink Temperature
Liquid Line Temperature
0
5
10
15
20
25
30
Leaving Evaporator
Entering Evaporator
Ambient temperature
0
20
40
60
80
100
120
140
160
Evaporator Pressure
Discharge Pressure
Oil Pressure
Start CounterCompressor Run Time
0
1000
2000
3000
4000
5000
6000
7000
1858
6909
Start Counter
Compressor RunTime
14
Data Hasil PemeriksaanDashboard monitoring Log Sheet Chiller#1
kW/TR
0.00
0.20
0.40
0.60
0.80
kW/TR
kW/TR
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
Power Consuption
TR
15
Data Hasil PemeriksaanLog Sheet Chiller#2
No Desc Before AftetrKondisi
System
1 Leaving water temperature C 14.4 10.5 Normal
2 Return water temperature C 17.3 13.6 Normal
3 Ambient Temperature C 16.1 15.3 Normal
4 Saturated Discharge Temp C 43.4 42.7 Normal
5 Discharge Superheat C 14.2 16.3 Normal
6 Liquid Line Temperature C 36.1 35.7 Normal
7 Discharge Temperature C 57.5 58.4 Normal
8 Oil Temperature C 56.1 57.5 Normal
9 Oil Sink Temperature C 48.3 47.5 Normal
10 Compressor Running Hour 6115 6121 Normal
11 Compressor Start 618 621 Normal
12 Evaporator Pressure Kpag 500 282 Normal
13 Discharge Pressure Kpag 985 979 Normal
14 Oil Pressure Kpag 915 909 Normal
15 Ampere 90.1 99.9 Normal
16 Incoming Voltage 380 380 Normal
17 Total Consumption KW 47.38 52.53 Normal
20 Control Voltage 115 115 Normal
21 Evaporator water pressure drop 1.5 Bar 1.5 Bar Normal
16
Data Hasil Pemeriksaan
Analisa Data Log Sheet dan Hasil pemeriksaan Chiller #2
� Berdasarkan hasil logsheet yang ada, semua parameter berada pada range normal.
� Terjadi peningkatan condenser pressure, hal ini dikarena chiller sedang kondisi loading. Untuk mencapai
target temperature yang ditentukan.
� Saat ini flow yang mengalir pada Evaporator melebihi dari design unit chiller. Hal itu dapat kita lihat
dengan membandingkan antara pressure drop yang ada saat ini.
Saat ini pressure drop unit chiller 1.5 Bar, seharusnya sesuai dengan design 6.2 Bar.
� Ambient transducer tidak akurat, pembacaan ambient 15 -16 °C, seharusnya ambient antara 26 – 29 °C
� Evaporator transducer tidak akurat. sehingga apabila dilakukan penggantian chiller yang beroperasi, harus
memindah transducer evaporator dari chiller lainnya.
� Halaman berikut terlampir dash board, dari dash board tersebut kita dapat melihat kinerja dan perubahan
yang terjadi pada chiller selama kunjungan/periodic maintenance.
17
Data Hasil PemeriksaanDashboard monitoring Log Sheet Chiller#2
0
2
4
6
8
10
12
14
16
18
Leaving Evaporator
Entering Evaporator
Ambient temperature
0
10
20
30
40
50
60
70
Discharge Temperature
Oil Temperature
Oil Sink Temperature
Liquid Line Temperature
0
20
40
60
80
100
120
140
160
Evaporator Pressure
Discharge Pressure
Oil Pressure
Start CounterCompressor Run Time
0
1000
2000
3000
4000
5000
6000
7000
623
6121 Start Counter
Compressor RunTime
18
Data Hasil PemeriksaanDashboard monitoring Log Sheet Chiller#2
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
Power Consuption
Tonnage
kW/TR
0.00
0.20
0.40
0.60
0.800.73
kW/TR
kW/TR
19
PEKERJAAN KETIKA KUNJUNGAN
RUMAH SAKIT UNHAS
Pekerjaan Ketika Kunjungan
� Pekerjaan sesuai dengan lingkup pekerjaan periodic maintenance ke 1
20
� Monitoring dan ambil data chiller saat running
� Pemeriksaan tekanan refrigerant (log Sheet Chiller)
� Pemeriksaan tekanan air dan flow water
� Pemeriksaan kebocoran
� Pemeriksaan control dan setpoints
� Pemeriksaan panel starter
� Pemeriksaan kekencangan baut dan koneksi
� Pemeriksaan data akurasi sensor dan tranducer.
� membersihkan panel control chiller.
� membersihkan body chiller.
� membersihkan coil condenser.
� Mengukur dan mencatat ampere kompresor dan fan motor.
� Mencatat level oli dan kondisi sight glass liquid line
� Memeriksa dan memastikan semua proteksi chiller bekerja dengan baik.
� Melakukan penggantian oli dan filter dehydrator.
21
KESIMPULAN & SARAN
RUMAH SAKIT UNHAS
Kesimpulan dan Saran
– Disarankan untuk melakukan pengambilan logsheet minimal 3 kali sehari, untuk memepermudah analisa
apabila terjadi permasalahan pada unit.
– Disarankan melakukan cleaning condenser sebulan sekali.
– Disarankan untuk melakukan penggantian ambient temperature sensor chiller 2
– Disarankan untuk melakukan penggantian evaporator transducer chiller 2.
22
Pekerjaan Lanjutan
- Penggantian sensor ambient temperature
- Penggantian transducer evaporator
23
24
Operation Team
Terima Kasih
Mochammad Safi’i
Service Engineer