Lecture 11 Control Loop Interaction 1

Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

Embed Size (px)

Citation preview

Page 1: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

1

Lecture 11

Control Loop Interaction

Page 2: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

2

• Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number of manipulated inputs and controlled outputs.

• The MIMO systems can be controlled by associating one manipulated variable to one controlled variable, hence forming several SISO control loops.

• Unfortunately, there is often interaction between these loops and this may cause the response of one loop to deteriorate once the other loops are closed.

MIMO systems

Page 3: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

3

• The proper choice of input output pairs can minimize the interaction.

• This pairing problem is known as control structure selection.

• After studying this chapter, we should be able to use the relative gain array (RGA) to determine the proper input-output pairings.

MIMO systems

Page 4: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

4

Understanding the Interaction

• Let us consider mixing two streams: alcohol with mass flow rate (u1) and water with mass flow rate (u2). Assume that both the concentration (y1) of Alcohol in the outlet stream and the total flow rate (y2 ) are to be controlled.

• With simple intuition, we know that changes in both u1 and u2 will affect y1 and y2.

Page 5: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

5

Understanding the Interaction

Let us assume that we make a closed-loop to control the composition (y1) using alcohol mass flow rate (u1).

The other loop is open.

The response of the system due to a step set point change in outlet concentration y1.

The interaction is obvious as y2 changes as well.

Page 6: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

6

Understanding the Interaction

Let us assume that we make a closed-loop to control the total flow rate (y2) using water mass flow rate (u2).

The other loop is open.

The response of the system due to a step set point change in outlet total flow rate y2.

The interaction obvious as y1 changes as well.

Page 7: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

7

Understanding the Interaction• Since we desire to control both (y1) and (y2) at the same time, we need to

have both loops closed simultaneously. Consider the system shown below with pairing (y1) with (u1) and (y2) with (u2).

• A set-point change in y1 will cause a change in u1. The change in u1 will also affect (y2, total flow). Once y2 is disturbed, u2 will change. Input u2 will disturb the concentration y1, causing the concentration controller to change u1, and we are back to where we started.

• The effect of one control loop on the other is referred to as control loop interaction.

• Although it is natural to think of these interactions as occurring in a sequential fashion, they actually happen simultaneously.

Page 8: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

8

Understanding the Interaction

• For the system in the previous slide, the response to a set-point change in the outlet concentration with both loops closed is very oscillatory as shown.

• It is interesting to note that, in this example, if we pair (y1) with (u2) and (y2) with (u1), the system will perform better.

• Hence, how should our outputs and inputs be paired?

Page 9: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

9

For simplicity, we will first treat 2x2 systems, for which there is only two pairing choices as shown below.

The Pairing Problem for 2x2 Processes

The process to be controlled

Page 10: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

10

The Pairing Problem for 2x2 Processes

For a 2x2 system, the open-loop input-output relationships are

Which can be rewritten in matrix form as

)(

)(

)()(

)()(

)(

)(

2

1

2221

1211

2

1

su

su

sgsg

sgsg

sy

sy

)()()()()(

)()()()()(

2221212

2121111

susgsusgsy

susgsusgsy

Page 11: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

11

The Pairing Problem for 2x2 Processes

Let us consider the relationship between y1 and u1 under two conditions:

(a) loop 2 is open (b) loop 2 is closed.

What about this case?

)()()( 1111 susgsy

Page 12: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

12

The Pairing Problem for 2x2 Processes

• If the second loop (y2-u2) is closed, there is an additional effect of u1 on y1 through the second controller. This effect can be positive or negative.

• This relationship can be derived as (assuming no set-point change in loop 2, r2 = 0),

• g11,eff(s) is the effective input-output relationship between u1 and y1, with loop 2 closed. This means that g11,eff(s) should be used as the process transfer function to design controller 1 if loop 2 is closed.

)()()(1

)()()()()( 1

)(

222

22112111

,11

susgsg

sgsgsgsgsy

sg

c

c

eff

Page 13: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

13

Steady-State Effective Gain

• Naturally, g11,eff(s) is a function of the controller gc2. What we would really like is a method to determine g11,eff(s) without knowing gc2(s).

• We can easily determine this relationship for a limiting case, the steady state. For the steady state, we simply let s → 0. Assuming integral action is used in the controller, we find that as s → 0, gc2(s) → ∞.

• Where k11, k21, k12, and k22 are the steady state gains.

• We now have a steady-state effective gain relationship between u1 and y1 with the loop between u2 and y2 closed.

effeff kk

kkk

g

gggg ,11

22

211211

22

211211,11 )0(

)0()0()0()0(

Page 14: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

14

The Relative Gain Array

Bristol developed a heuristic technique to predict possible interactive effects between control loops when multiple SISO loops are used. This simple measure of interaction is known as the relative gain array (RGA).

Page 15: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

15

Definition of the Relative Gain

The relative gain (λij) between input (j) and output (i) is defined as

ikk

jkk

yj

i

uj

i

ij

uy

uy

,

,

Gain between input j and output i with all other loops open

Gain between input j and output i with all other loops closed

Page 16: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

16

Relative gain between u1 and y1 for 2x2 System

Based on the results we just obtained about the relationship between y1 and u1 when the other loop is open or closed, we can deduce that

22

211211

11

,11

11

const is 1

1

const is 1

1

11

2

2

kkk

k

k

k

k

uy

uy

eff

y

u

Page 17: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

17

The RGA

• The RGA is simply the matrix whose elements are the individual relative gains.

• For a 2 x 2 system, the RGA is

2221

1211

Page 18: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

18

The RGA• Below is a general relative gain array for n x n

system.• Different columns represent the different manipulated

(input) variables

nnnn

n

n

RGA

21

22221

11211

Page 19: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

19

The RGA

• Different rows represent the different controlled (output) variables

• Note that in the RGA, the elements of any row or column sum to 1.0.

nnnn

n

n

RGA

21

22221

11211

Page 20: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

20

How to calculate the RGA for n x n process?

• Given the steady-state gain matrix Kss = G(0), the relative gain array can be calculated using the following relationship:

where:• “ ” denotes element-wise multiplication (not matrix multiplication!!).• “T ” denotes the transpose of a matrix.

Tssss

T

KK

GG

)(

))0(()0(1

1

Page 21: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

21

Example

• Given the following steady state gain matrix

• The RGA is then

11

075.0025.0K

25.075.0

75.025.0

Page 22: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

22

Significance of the RGA• Think of it this way: if we want to use a u1-y1 pairing for a

SISO controller, we do not want it to matter whether the other loops in the system are closed or not. This tells us that we desire a relative gain close to 1.0.

• A value of 1 indicates that specific input variable is the only influence on that output variable.

• A value of 0 indicates no relationship between u1 and y1.

• Negative values indicate an unstable relationship. Why?

Page 23: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

23

Negative relative gain

• If λ11 is negative, this means that the gain between u1 and y1 with loop 2 closed (k11,eff) has the opposite sign compared with the gain between them (k11) with loop 2 open.

• For open-loop stable processes, the controller gain must have the same sign as the process gain. Hence, a controller for loop 1 designed based on g11 (loop 2 open) will be destabilized when loop 2 is closed and vice versa.

• This is unacceptable in practice. Hence, avoid input-output pairings based on a negative relative gain.

Page 24: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

24

Input-output Pairing Guidelines

• Try to pair on relative gains close to 1.

• Do not pair on a negative or zero relative gain

• The higher the value of λij, the greater the interaction. Therefore try not to pair yi with uj if the value of λij is large.

Page 25: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

25

Example 2

• Consider a 2x2 system having the following RGA.

The recommended pairings are y1-u1 & y2-u2

• However, for the case

The recommended pairings are y1-u2 & y2-u1

95.005.0

05.095.0

05.095.0

95.005.0

Page 26: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

26

043

243

111

Example 3Consider the following RGA for a system with three inputs and three outputs:

How would you choose input-output pairings for this process?

Solution

1- First of all, we know that we do not want to pair on a negative relative gain.

2- Second, we do not want to pair with a relative gain of 0 because that means that the particular input does not have an effect on the particular output, when all of the other loops are open.

Applying these guidelines, we get the following pairings y1-u1, y2-u3, y3-u2.

Page 27: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

27

7309.04761.09017.01087.3

3974.10396.06749.40327.5

5212.05507.10544.00839.0

8546.00349.08276.20078.3

Λ

• Given the following RGA for a 4x4 distillation column, suggest the input-output pairing.

• Looking at column 3, we see only one relative gain that is not negative, therefore, we must pair y2 with u3.

• Looking at row 4, we notice that there is only one relative gain that is not negative, therefore, we must pair y4 with u1.

• Looking at column 2, there are two nonnegative gains, but we have already used output 2, so we must pair y3 with u2.

• This leaves y1 and u4, which, fortunately, has a favorable relative gain (0.8546). If the y1-u4 relative gain had not been favorable, we would have been forced to drop output 1 and input 4 and simply have three control loops for our system.

Example 4

Page 28: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

28

RGA & Controller Tuning

• When tuning a set of SISO controllers in a MIMO system, the RGA gives a valuable insight on how to tune the controller to avoid any failure in the control loops.

• When a control loop fails, it becomes open. This may happen in a number of ways:

– The most obvious way is for an operator to put loop 2 on manual control (i.e., open loop).

– Another way is if the second manipulated variable hits a constraint, say if the valve goes all the way open or closed—this means that the second input can no longer affect the second output, which is equivalent to being open loop.

Page 29: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

29

Relative Gains Between 0 and 1

• If a relative gain is less than 1, this means that

k11,eff (other loops closed) > k11 (other loops open).

• If a controller for loop 1 is based on k11 (implicitly assuming that loop 2 is open), then when loop 2 is closed, the control system will respond too rapidly and there will be a chance of instability.

• For safety purposes, if the relative gain is less than 1, then loop 1 should be tuned based on loop 2 closed.

Page 30: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

30

Relative gains greater than 1

• If a relative gain is greater than 1, this means that

k11,eff < k11.

• If a controller for loop 1 is based on k11,eff (implicitly assuming that loop 2 is closed), then if loop 2 is opened, the control system will respond too rapidly and there will be a chance of instability.

• For safety purposes, if the relative gain is greater than 1, then loop 1 should be tuned based on loop 2 open.

Page 31: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

Dynamic Considerations in pairing I/O

• Note that the RGA gives recommendations to pair I/O variables taking into account the steady-state effects only. If dynamic considerations are taken into account, the recommended pairing may differ.

• For example, consider transfer function matrix

• Pairings based on RGA: (u1-y1), (u2-y2)

• Pairings based on time constants: (u1-y2), (u2-y1).

64.036.0

36.064.0

25.1

5.12

110

2

1

5.11

5.1

110

2

)( KG

s

e

s

es

e

s

e

s ss

ss

p

Page 32: Lecture 11 Control Loop Interaction 1. Thus far in the course, we have focused on SISO control systems. However, most process unit operations have a number

32

Reference

Bequette, B. W. Process control Modeling, Design, and Simulation. Prentice Hall PTR, 2002, Chapter 13.