Upload
bashir-ahmad
View
51
Download
1
Embed Size (px)
DESCRIPTION
power system
Citation preview
9/16/2011
1
Simplified Power System Modeling
• Balanced three phase systems can be analyzed using per phase analysis
• A “per unit” normalization is simplify the analysis of systems with different voltage levels.
Energy Systems Research Laboratory, FIU
• To provide an introduction to power flow analysis we need models for the different system devices:– Transformers and Transmission lines, generators and loads
• Transformers and transmission lines are modeled as a series impedances
Load Models
• Ultimate goal is to supply loads with electricity at constant frequency and voltage
• Electrical characteristics of individual loads matter, but usually they can only be estimated– actual loads are constantly changing consisting of a large
Energy Systems Research Laboratory, FIU
– actual loads are constantly changing, consisting of a large number of individual devices
– only limited network observability of load characteristics
• Aggregate models are typically used for analysis
• Two common models– constant power: Si = Pi + jQi
– constant impedance: Si = |V|2 / Zi
Generator Models
• Engineering models depend upon application
• Generators are usually synchronous machines
• For generators we will use two different models:– a steady-state model, treating the generator as a constant
Energy Systems Research Laboratory, FIU
y , g gpower source operating at a fixed voltage; this model will be used for power flow and economic analysis
– This model works fairly well for type 3 and type 4 wind turbines
– Other models include treating as constant real power with a fixed power factor.
Per Unit Calculations
• A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer
impedances to the different sides of the transformers
Thi bl i id d b li i f ll
Energy Systems Research Laboratory, FIU
• This problem is avoided by a normalization of all variables.
• This normalization is known as per unit analysis.
actual quantityquantity in per unit
base value of quantity
Per Unit Conversion Procedure, 11. Pick a 1 VA base for the entire system, SB
2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral.
3 C l l h i d b Z (V )2/S
Energy Systems Research Laboratory, FIU
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion on affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
Three Phase Per Unit
1. Pick a 3 VA base for the entire system,
2. Pick a voltage base for each different voltage level,
Procedure is very similar to 1 except we use a 3VA base, and use line to line voltage bases
3BS
Energy Systems Research Laboratory, FIU
VB. Voltages are line to line.
3. Calculate the impedance base2 2 2, , ,3 1 1
( 3 )
3B LL B LN B LN
BB B B
V V VZ
S S S
Exactly the same impedance bases as with single phase!
9/16/2011
2
Three Phase Per Unit, cont'd
4. Calculate the current base, IB3 1 1
3 1B B
, , ,
3I I
3 3 3B B B
B LL B LN B LN
S S S
V V V
Energy Systems Research Laboratory, FIU
5. Convert actual values to per unit
Exactly the same current bases as with single phase!
Power Flow Analysis
• We now have the necessary models to start to develop the power system analysis tools
• The most common power system analysis tool is the power flow (also known sometimes as the load flow)
Energy Systems Research Laboratory, FIU
– power flow determines how the power flows in a network
– also used to determine all bus voltages and all currents
– because of constant power models, power flow is a nonlinear analysis technique
– power flow is a steady-state analysis tool
Bus Admittance Matrix or Ybus
• First step in solving the power flow is to create what is known as the bus admittance matrix, often call the Ybus.
• The Ybus gives the relationships between all the bus
Energy Systems Research Laboratory, FIU
bus g pcurrent injections, I, and all the bus voltages, V,
I = Ybus V
• The Ybus is developed by applying KCL at each bus in the system to relate the bus current injections, the bus voltages, and the branch impedances and admittances
Ybus General Form •The diagonal terms, Yii, are the self admittance terms, equal to the sum of the admittances of all devices incident to bus i.
•The off-diagonal terms, Yij, are equal to the negative
Energy Systems Research Laboratory, FIU
of the sum of the admittances joining the two buses.
•With large systems Ybus is a sparse matrix (that is, most entries are zero)
•Shunt terms, such as with the line model, only affect the diagonal terms.
Power Flow Analysis
• When analyzing power systems we know neither the complex bus voltages nor the complex current injections
• Rather, we know the complex power being
Energy Systems Research Laboratory, FIU
p p gconsumed by the load, and the power being injected by the generators plus their voltage magnitudes
• Therefore we can not directly use the Ybus equations, but rather must use the power balance equations
Power Flow Slack Bus
• We can not arbitrarily specify S at all buses because total generation must equal total load + total losses
• We also need an angle reference bus.
• To solve these problems we define one bus as the
Energy Systems Research Laboratory, FIU
To solve these problems we define one bus as the "slack" bus. This bus has a fixed voltage magnitude and angle, and a varying real/reactive power injection.
• A “slack bus” does not exist in the real power system.
9/16/2011
3
Power Balance EquationsFrom KCL we know at each bus i in an n bus system
the current injection, , must be equal to the current
that flows into the network i
n
I
I I I I
Energy Systems Research Laboratory, FIU
1
bus
1
Since = we also know
i Gi Di ikk
n
i Gi Di ik kk
I I I I
I I I Y V
I Y V
*iThe network power injection is then S i iV I
Real Power Balance Equations* *
i1 1
1
S ( )
(cos sin )( )
ikn n
ji i i ik k i k ik ik
k k
n
i k ik ik ik ikk
P jQ V Y V V V e G jB
V V j G jB
Energy Systems Research Laboratory, FIU
i1
i1
Resolving into the real and imaginary parts
P ( cos sin )
Q ( sin cos
n
i k ik ik ik ik Gi Dik
n
i k ik ik ik ik
V V G B P P
V V G B
)k Gi DiQ Q
Newton-Raphson Method (scalar)
( )
( ) ( )
1. For each guess of , , define ˆ
-ˆ
v
v v
x x
x x x
G eneral fo rm of problem : F ind an x such that
( ) 0ˆf x
Energy Systems Research Laboratory, FIU
( )( ) ( )
2 ( ) 2( )2
-
2. Represent ( ) by a Taylor series about ( )ˆ
( )( ) ( )ˆ
1 ( )higher order terms
2
vv v
vv
x x x
f x f x
df xf x f x x
dx
d f xx
dx
Newton-Raphson Method, cont’d
( )( ) ( )
3. Approximate ( ) by neglecting all termsˆ
except the first two
( )( ) 0 ( )ˆ
vv v
f x
df xf x f x x
dx
Energy Systems Research Laboratory, FIU
( )
1( )( ) ( )
4. Use this linear approximation to solve for
( )( )
5. Solve for a new estim
v
vv v
x
df xx f x
dx
( 1) ( ) ( )
ate of x̂v v vx x x
Newton-Raphson Example2
1( )( ) ( )
Use Newton-Raphson to solve ( ) - 2 0
The equation we must iteratively solve is
( )( )
vv v
f x x
df xx f x
d
Energy Systems Research Laboratory, FIU
( ) ( ) 2( )
( 1) ( ) ( )
( 1) ( ) ( ) 2( )
1(( ) - 2)
2
1(( ) - 2)
2
v vv
v v v
v v vv
dx
x xx
x x x
x x xx
Newton-Raphson Example, cont’d
( 1) ( ) ( ) 2( )
(0)
( ) ( ) ( )
1(( ) - 2)
2
Guess x 1. Iteratively solving we get
v ( )
v v vv
v v v
x x xx
x f x x
Energy Systems Research Laboratory, FIU
3 3
6
v ( )
0 1 1 0.5
1 1.5 0.25 0.08333
2 1.41667 6.953 10 2.454 10
3 1.41422 6.024 10
x f x x
9/16/2011
4
Newton-Raphson Comments
• When close to the solution the error decreases quite quickly -- method has quadratic convergence
• f(x(v)) is known as the mismatch, which we would like to drive to zero
Energy Systems Research Laboratory, FIU
• Stopping criteria is when f(x(v)) < • Results are dependent upon the initial guess. What if
we had guessed x(0) = 0, or x (0) = -1?
• A solution’s region of attraction (ROA) is the set of initial guesses that converge to the particular solution. The ROA is often hard to determine
Multi-Variable Newton-Raphson
1 1
2 2
Next we generalize to the case where is an n-
dimension vector, and ( ) is an n-dimension function
( )
( )
x f
x f
x
f x
x
x
Energy Systems Research Laboratory, FIU
2 2( )( )
( )
Again define the solution so ( ) 0 andˆ ˆn n
x f
x f
xx f x
x
x f x
x
ˆ x x
Multi-Variable Case, cont’di
1 11 1 1 2
1 2
1
The Taylor series expansion is written for each f ( )
f ( ) f ( )f ( ) f ( )ˆ
f ( )higher order termsn
x xx x
x
x
x xx x
x
Energy Systems Research Laboratory, FIU
n nn n 1 2
1 2
n
g
f ( ) f ( )f ( ) f ( )ˆ
f ( )higher order terms
nn
nn
x
x xx x
xx
x xx x
x
Multi-Variable Case, cont’d
1 1 1
1 21 1
2 2 2
This can be written more compactly in matrix form
( ) ( ) ( )
( )( ) ( ) ( )
n
f f f
x x xf x
f f f
x x x
xx x x
Energy Systems Research Laboratory, FIU
2 2 22 2
1 2
1 2
( ) ( ) ( )( )
( )ˆ
( )( ) ( ) ( )
n
nn n n
n
f f ff x
x x x
ff f f
x x x
x x xx
f x
xx x x
higher order terms
nx
Jacobian Matrix
1 1 1
1 2
The n by n matrix of partial derivatives is known
as the Jacobian matrix, ( )
( ) ( ) ( )
n
f f fx x x
J x
x x x
Energy Systems Research Laboratory, FIU
1 2
2 2 2
1 2
1 2
( ) ( ) ( )
( )
( ) ( ) ( )
n
n
n n n
n
x x x
f f fx x x
f f f
x x x
x x x
J x
x x x
Multi-Variable N-R Procedure
1
Derivation of N-R method is similar to the scalar case
( ) ( ) ( ) higher order termsˆ
( ) 0 ( ) ( )ˆ
( ) ( )
f x f x J x x
f x f x J x x
x J x f x
Energy Systems Research Laboratory, FIU
( 1) ( ) ( )
( 1) ( ) ( ) 1 ( )
( )
( ) ( )
( ) ( )
Iterate until ( )
v v v
v v v v
v
x J x f x
x x x
x x J x f x
f x
9/16/2011
5
Multi-Variable Example
1
2
2 21 1 2
2 2
xSolve for = such that ( ) 0 where
x
f ( ) 2 8 0x x
x f x
x
Energy Systems Research Laboratory, FIU
2 22 1 2 1 2
1 1
1 2
2 2
1 2
f ( ) 4 0
First symbolically determine the Jacobian
f ( ) f ( )
( ) =f ( ) f ( )
x x x x
x x
x x
x
x x
J xx x
Multi-variable Example, cont’d1 2
1 2 1 2
11 1 2 1
4 2( ) =
2 2
Then
4 2 ( )
x x
x x x x
x x x f
J x
x
Energy Systems Research Laboratory, FIU
1 1 2 1
2 1 2 1 2 2
(0)
1(1)
( )
2 2 ( )
1Arbitrarily guess
1
1 4 2 5 2.1
1 3 1 3 1.3
f
x x x x x f
x
x
x
Multi-variable Example, cont’d
1(2) 2.1 8.40 2.60 2.51 1.8284
1.3 5.50 0.50 1.45 1.2122
Each iteration we check ( ) to see if it is below our
x
f x
Energy Systems Research Laboratory, FIU
(2)
specified tolerance
0.1556( )
0.0900
If = 0.2 then we wou
f x
ld be done. Otherwise we'd
continue iterating.
Real Power Balance Equations* *
i1 1
1
S ( )
(cos sin )( )
ikn n
ji i i ik k i k ik ik
k k
n
i k ik ik ik ikk
P jQ V Y V V V e G jB
V V j G jB
Energy Systems Research Laboratory, FIU
i1
i1
Resolving into the real and imaginary parts
P ( cos sin )
Q ( sin cos
n
i k ik ik ik ik Gi Dik
n
i k ik ik ik ik
V V G B P P
V V G B
)k Gi DiQ Q
Newton-Raphson Power Flow
In the Newton-Raphson power flow we use Newton's
method to determine the voltage magnitude and angle
at each bus in the power system.
We need to solve the power balance equations
Energy Systems Research Laboratory, FIU
i1
We need to solve the power balance equations
P ( cosn
i k ik ikk
V V G
i1
sin )
Q ( sin cos )
ik ik Gi Di
n
i k ik ik ik ik Gi Dik
B P P
V V G B Q Q
Power Flow Variables
2 2 2
Assume the slack bus is the first bus (with a fixed
voltage angle/magnitude). We then need to determine
the voltage angle/magnitude at the other buses.
( ) GP P x 2DP
Energy Systems Research Laboratory, FIU
2 2 2
n
2
( )
( )
G
n
P P
V
V
x
x f x
2
2 2 2
( )
( )
( )
D
n Gn Dn
G D
n Gn Dn
P
P P P
Q Q Q
Q Q Q
x
x
x
9/16/2011
6
N-R Power Flow Solution
( )
( )
The power flow is solved using the same procedure
discussed last time:
Set 0; make an initial guess of , vv x x
Energy Systems Research Laboratory, FIU
( )
( 1) ( ) ( ) 1 ( )
While ( ) Do
( ) ( )
1
End While
v
v v v v
v v
f x
x x J x f x
Power Flow Jacobian Matrix
1 1 1
1 2
The most difficult part of the algorithm is determining
and inverting the n by n Jacobian matrix, ( )
( ) ( ) ( )
n
f f fx x x
J x
x x x
Energy Systems Research Laboratory, FIU
1 2
2 2 2
1 2
1 2
( ) ( ) ( )
( )
( ) ( ) ( )
n
n
n n n
n
x x x
f f fx x x
f f fx x x
x x x
J x
x x x
Power Flow Jacobian Matrix, cont’d
i
i
Jacobian elements are calculated by differentiating
each function, f ( ), with respect to each variable.
For example, if f ( ) is the bus i real power equationn
x
x
Energy Systems Research Laboratory, FIU
i1
f ( ) ( cos sin )i k ik ik ik ik Gik
x V V G B P P
i
1
i
f ( )( sin cos )
f ( )( sin cos ) ( )
Di
n
i k ik ik ik iki k
k i
i j ik ik ik ikj
xV V G B
xV V G B j i
Two Bus Newton-Raphson Example
Line Z = 0 1j
For the two bus power system shown below, use the Newton-Raphson power flow to determine the voltage magnitude and angle at bus two. Assumethat bus one is the slack and SBase = 100 MVA.
Energy Systems Research Laboratory, FIU
Line Z = 0.1j
One Two 1.000 pu 1.000 pu
200 MW 100 MVR
0 MW 0 MVR
2
2
10 10
10 10bus
j j
V j j
x Y
Two Bus Example, cont’d
i1
General power balance equations
P ( cos sin )
Q ( i )
n
i k ik ik ik ik Gi Dik
n
V V G B P P
V V G B Q Q
Energy Systems Research Laboratory, FIU
i1
2 1 2
22 1 2 2
Q ( sin cos )
Bus two power balance equations
(10sin ) 2.0 0
( 10cos ) (10) 1.0 0
i k ik ik ik ik Gi Dik
V V G B Q Q
V V
V V V
Two Bus Example, cont’d2 2 2
22 2 2 2
2 2
P ( ) (10sin ) 2.0 0
( ) ( 10cos ) (10) 1.0 0
Now calculate the power flow Jacobian
P ( ) P ( )
V
Q V V
x
x
x x
Energy Systems Research Laboratory, FIU
2 2
2 2
2 2
2 2
2 2 2
2 2 2 2
P ( ) P ( )
( )Q ( ) Q ( )
10 cos 10sin
10 sin 10cos 20
VJ
V
V
V V
x x
xx x
9/16/2011
7
Two Bus Example, First Iteration(0)
2 2(0)
0Set 0, guess
1
Calculate
(10sin ) 2.0 2.0f( )
v
V
x
Energy Systems Research Laboratory, FIU
(0)2
2 2 2
2 2 2(0)
2 2 2 2
(1)
f( )1.0( 10cos ) (10) 1.0
10 cos 10sin 10 0( )
10 sin 10cos 20 0 10
0 10 0Solve
1 0 10
V V
V
V V
x
J x
x1 2.0 0.2
1.0 0.9
Two Bus Example, Next Iterations(1)
2
(1)
0.9(10sin( 0.2)) 2.0 0.212f( )
0.2790.9( 10cos( 0.2)) 0.9 10 1.0
8.82 1.986( )
1.788 8.199
x
J x
Energy Systems Research Laboratory, FIU
1(2) 0.2 8.82 1.986 0.212 0.233
0.9 1.788 8.199 0.279 0.8586
f(
x
(2) (3)
(3)2
0.0145 0.236)
0.0190 0.8554
0.0000906f( ) Done! V 0.8554 13.52
0.0001175
x x
x
Two Bus Solved ValuesOnce the voltage angle and magnitude at bus 2 are known we can calculate all the other system values, such as the line flows and the generator reactive power output
Energy Systems Research Laboratory, FIU
Line Z = 0.1j
One Two 1.000 pu 0.855 pu
200 MW 100 MVR
200.0 MW168.3 MVR
-13.522 Deg
200.0 MW 168.3 MVR
-200.0 MW-100.0 MVR
PV Buses
• Since the voltage magnitude at PV buses is fixed there is no need to explicitly include these voltages in x or write the reactive power balance equations– the reactive power output of the generator varies to
i t i th fi d t i l lt ( ithi li it )
Energy Systems Research Laboratory, FIU
maintain the fixed terminal voltage (within limits)
– optionally these variations/equations can be included by just writing the explicit voltage constraint for the generator bus
|Vi | – Vi setpoint = 0
Three Bus PV Case Example
Line Z = 0 1j
2 2 2 2
3 3 3 3
2 2 2
For this three bus case we have
( )
( ) ( ) 0
V ( )
G D
G D
D
P P P
P P P
Q Q
x
x f x x
x
Energy Systems Research Laboratory, FIU
Line Z = 0.1j
Line Z = 0.1j Line Z = 0.1j
One Two 1.000 pu 0.941 pu
200 MW 100 MVR
170.0 MW 68.2 MVR
-7.469 Deg
Three 1.000 pu
30 MW 63 MVR
Solving Large Power Systems
• The most difficult computational task is inverting the Jacobian matrix– inverting a full matrix is an order n3 operation, meaning
the amount of computation increases with the cube of the size size
Energy Systems Research Laboratory, FIU
size size
– this amount of computation can be decreased substantially by recognizing that since the Ybus is a sparse matrix, the Jacobian is also a sparse matrix
– using sparse matrix methods results in a computational order of about n1.5.
– this is a substantial savings when solving systems with tens of thousands of buses
9/16/2011
8
“DC” Power Flow
• The “DC” power flow makes some approximations to the power balance equations to simplify the problem– completely ignore reactive power, assume all the voltages
are always 1.0 per unit, ignore line conductance, assumes l th li ll
Energy Systems Research Laboratory, FIU
angles across the lines are small.
– Line flow is then approximated as (i – j)/Xij
• This makes the power flow a linear set of equations, which can be solved directly = B-1P
• While the DC power flow is approximate, it is widely used to get a feel for power system MW flows.
400 MVA15 kV
T1
T2800 MVA345/15 kV
800 MVA15 kV
520 MVALine 3 345 kV
50 mi
1 4 35
Five Bus Power Flow Example
Energy Systems Research Laboratory, FIU
400 MVA15/345 kV
80 MW40 Mvar
280 Mvar 800 MW
Lin
e 2
Lin
e 1345 kV
100 mi345 kV 200 mi
2
Single-line diagram
DC Power Flow Example
• For the system shown in the previous slide with bus 1 as the system slack and with the below B matrix (100 MVA base) numbered from buses 2 to 5, determine the bus angles using the DC power flow approximation the and the flow on the line between bus 1 and 5 which has a pu
Energy Systems Research Laboratory, FIU
the flow on the line between bus 1 and 5, which has a puX of 0.02.
P15 = (1 – 5)/X15 = 0.072/0.02 = 3.6 pu = 360 MW
37 Bus Power Flow Example
slack
Metropolis Light and Power Electric Design Case 2SLA CK3 45
SLA CK1 38
RA Y34 5
RA Y1 38
RA Y69
FERNA 69
A
MVA
BOB1 38
WOLEN69
PET E69HISKY69
T IM6 9
T IM1 38
TIM3 45
PA I69
GROSS69
MORO13 8
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
1.03 pu
1.02 pu
1.03 pu
1.03 pu
1.01 pu
1 .0 0 pu1.01 pu
1 .0 1 pu
1 .0 1 pu
1 .0 2 pu
1 .0 0 pu
1.02 pu
1.02 pu
A
MVA
A
MVA
A
MVA
System Losses: 10.70 MW
22 0 MW 5 2 Mvar
12 MW 3 Mvar
3 7 MW
1 3 Mvar
12 MW
2 3 MW 7 Mvar
3 3 MW 1 3 Mvar
15 .9 Mvar 1 8 MW 5 Mvar
58 MW 40 Mvar
4.9 Mvar
39 MW 13 Mvar
1 7 MW 3 Mvar
Energy Systems Research Laboratory, FIU
DEMA R6 9
BLT 69
BLT1 38
BOB6 9
SHIMKO6 9
ROGER6 9
UIUC6 9
HA NNA H69
A MA NDA 69
HOMER69
LA UF6 9
LA UF1 38
HA LE69
PA T TEN6 9
WEBER69
BUCKY1 38
SA VOY69
SA VOY138
JO1 38 JO34 5
A
MVA
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
1 .00 pu
1.02 pu
1.01 pu
1.00 pu
1 .0 1 pu
1 .0 1 pu
1.00 pu0 .9 9 pu
0 .99 pu
1.00 pu
1.0 2 pu
1 .00 pu1 .0 1 pu
1.01 pu
1 .0 0 pu 1.00 pu
1 .01 pu
1 .0 2 pu 1.02 pu
1.02 pu 1.0 3 pu
A
MVA
LYNN1 38
1.02 pu
A
MVA
1.00 pu
A
MVA
2 0 MW 1 2 Mvar
124 MW 4 5 Mvar
12 MW 5 Mvar
1 50 MW 0 Mvar
56 MW
13 Mvar
1 5 MW 5 Mvar
1 4 MW
2 Mvar
3 8 MW 3 Mvar
4 5 MW 0 Mvar
25 MW 36 Mvar
36 MW 10 Mvar
1 0 MW 5 Mvar
22 MW 15 Mvar
6 0 MW 1 2 Mvar
2 0 MW 2 8 Mvar
60 MW 19 Mvar
1 4.2 Mvar
2 5 MW 1 0 Mvar
20 MW 3 Mvar
23 MW 6 Mvar 1 4 MW
3 Mvar
7.3 Mvar
12 .8 Mvar
28 .9 Mvar
7.4 Mvar
0.0 Mvar
5 5 MW 2 5 Mvar
1 50 MW 0 Mvar
16 MW -1 4 Mvar
1 4 MW 4 Mvar
KYLE69A
MVA
Good Power System Operation
• Good power system operation requires that there be no reliability violations for either the current condition or in the event of statistically likely contingencies• Reliability requires as a minimum that there be no transmission
line/transformer limit violations and that bus voltages be within acceptable limits (perhaps 0 95 to 1 08)
Energy Systems Research Laboratory, FIU
limits (perhaps 0.95 to 1.08)
• Example contingencies are the loss of any single device. This is known as n-1 reliability.
• North American Electric Reliability Corporation now has legal authority to enforce reliability standards (and there are now lots of them). See http://www.nerc.com for details (click on Standards)
Looking at the Impact of Line Outages
slack
Metropolis Light and Power Electric Design Case 2SLA CK345
SLA CK138
RA Y345
RA Y138
RA Y69
FERNA 69
A
MVA
DEMA R69BOB138
WOLEN69
PET E6 9HISKY6 9
T IM69
T IM138
T IM345
PA I69
GROSS69
HA NNA H69
MORO138
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
1.03 pu
1 .0 2 pu
1 .0 3 pu
1.03 pu
1.01 pu
1.00 pu1.01 pu
1.01 pu
1.01 pu
1.02 pu
1.01 pu
1.02 pu
A
MVA
1.02 pu
A
MVA
A
MVA
A
MVA
System Losses: 17.61 MW
227 MW 4 3 Mvar
12 MW 3 Mvar
37 MW
13 Mvar
12 MW 5 Mvar
23 MW 7 Mvar
33 MW 13 Mvar
16.0 Mvar 18 MW 5 Mvar
58 MW 40 Mvar
60 MW19 Mvar
4 .9 Mvar
2 8.9 Mvar
3 9 MW 1 3 Mvar
17 MW 3 Mvar
Energy Systems Research Laboratory, FIU
BLT 69
BLT 138
BOB69
SHIMKO69
ROGER69
UIUC69
A MA NDA 69
HOMER6 9
LA UF69
LA UF138
HA LE69
P A T T EN69
WEBER69
BUCKY138
SA VOY69
SA VOY138
JO138 JO345
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
1.00 pu
1.02 pu
1.01 pu
1.00 pu
1.01 pu
1.01 pu
1.00 pu0.90 pu
0.90 pu
0.94 pu
1 .0 1 pu
0.99 pu1.00 pu
1.00 pu
1 .0 0 pu 1.00 pu
1.01 pu
1.01 pu 1.02 pu
1.02 pu 1.03 pu
LYNN1 38
1.02 pu
A
MVA
1.00 pu
A
MVA
20 MW 12 Mvar
124 MW 45 Mvar
150 MW 4 Mvar
5 6 MW
1 3 Mvar
15 MW 5 Mvar
14 MW
2 Mvar
3 8 MW 9 Mvar
45 MW 0 Mvar
25 MW 36 Mvar
3 6 MW 1 0 Mvar
10 MW 5 Mvar
22 MW 15 Mvar
60 MW 12 Mvar
20 MW 40 Mvar
19 Mvar
11.6 Mvar
25 MW 10 Mvar
20 MW 3 Mvar
23 MW 6 Mvar 14 MW
3 Mvar
7 .2 Mvar
1 2.8 Mvar
7 .3 Mvar
0 .0 Mvar
55 MW 32 Mvar
150 MW 4 Mvar
16 MW -14 Mvar
14 MW 4 Mvar
KYLE69A
MVA
80%A
MVA
135%A
MVA
110%A
MVA
Opening one line (Tim69-Hannah69) causes an overload. This would not be allowed (i.e., we can’t operate this way when line is in.
9/16/2011
9
Contingency Analysis
Contingencyanalysis providesan automaticway of lookingat all the
i i ll
Energy Systems Research Laboratory, FIU
statisticallylikely contingencies. Inthis example thecontingency setIs all the single line/transformeroutages
Generation Changes and The Slack Bus
• The power flow is a steady-state analysis tool, so the assumption is total load plus losses is always equal to total generation• Generation mismatch is made up at the slack bus
• When doing generation change power flow studies
Energy Systems Research Laboratory, FIU
When doing generation change power flow studies one always needs to be cognizant of where the generation is being made up• Common options include system slack, distributed across
multiple generators by participation factors or by economics
Generation Change Example 1slack
SLA CK345
SLA CK138
RA Y345
RA Y138
RA Y69
FERNA 69
A
MVA
DEMA R69BOB138
BOB69
WOLEN69
UIUC6 9
PET E69
HISKY69
T IM69
T IM138
T IM345
PA I69
GROSS6 9
HA NNA H6 9
MORO138
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVAA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
0.00 pu
-0.01 pu
0.00 pu
0.00 pu
0.00 pu
-0.03 pu-0.01 pu
0.00 pu
0.00 pu
0.0 0 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu
A
MVA
-0 .01 pu
A
MVA
A
MVA
LYNN138
A
MVA
0.00 pu
162 MW 35 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
-157 MW -45 Mvar
0 MW
0 Mvar
0 MW 0 Mvar
0 MW
0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
-0 .1 Mvar 0 MW 0 Mvar
0 MW 0 Mvar 0 MW
0 Mvar
-0 .1 Mvar
-0 .1 Mvar
-0 .1 Mvar
-0 .2 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW
Energy Systems Research Laboratory, FIU
BLT 69
BLT 138
SHIMKO69
ROGER6 9
A MA NDA 6 9
HOMER69
LA UF69
LA UF138
HA LE69
PA T T EN69
WEBER69
BUCKY138
SA VOY69
SA VOY138
JO138 JO345
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
0.00 pu
-0.03 pu
-0.0 1 pu0.0 0 pu
-0.002 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu0.0 0 pu
0.00 pu
0.00 pu 0.00 pu
0.00 pu
0.00 pu 0.00 pu
0.00 pu0.00 pu
0.00 pu
A
MVA
A
MVA
0 MW 2 Mvar
0 MW 0 Mvar
0 MW
0 Mvar
0 MW 3 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 4 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar 0 MW
0 Mvar
0 .0 Mvar
0 .0 Mvar
0 .0 Mvar
0 MW 51 Mvar
0 MW 2 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
Display shows “Difference Flows” between original 37 bus case, and case with a BLT138 generation outage; note all the power change is picked up at the slack
Generation Change Example 2
slack
SLA CK345
SLA CK138
RA Y345
RA Y138
RA Y69
FERNA 69
A
MVA
DEMA R69BOB138
BOB69
WOLEN69
UIUC6 9
PET E69
HISKY69
T IM69
T IM138
T IM345
PA I69
GROSS6 9
HA NNA H6 9
MORO138
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVAA
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
A
A
MVA
A
MVA
0.00 pu
-0.01 pu
0.00 pu
0.00 pu
0.00 pu
-0.03 pu0.00 pu
0.00 pu
0.00 pu
0.0 0 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu
A
MVA
0.00 pu
A
MVA
A
MVA
LYNN138
A
MVA
0.00 pu
0 MW 37 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
-157 MW -45 Mvar
0 MW
0 Mvar
0 MW 0 Mvar
0 MW
0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
-0 .1 Mvar 0 MW 0 Mvar
0 MW 0 Mvar 0 MW
0 Mvar
-0 .1 Mvar
0 .0 Mvar
-0 .1 Mvar
-0 .2 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
Energy Systems Research Laboratory, FIU
BLT 69
BLT 138
SHIMKO69
ROGER6 9
A MA NDA 6 9
HOMER69
LA UF69
LA UF138
HA LE69
PA T T EN69
WEBER69
BUCKY138
SA VOY69
SA VOY138
JO138 JO345
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
MVA
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
0.00 pu
-0.03 pu
-0.0 1 pu-0.01 pu
-0.003 pu
0.00 pu
0.00 pu
0.00 pu
0.00 pu0.0 0 pu
0.00 pu
0.00 pu 0.00 pu
0.00 pu
0.00 pu 0.00 pu
0.00 pu0.00 pu
0.00 pu
A
MVA
A
MVA
0 MW 0 Mvar
0 MW 0 Mvar
0 MW
0 Mvar
42 MW -14 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
99 MW -20 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
0 MW 0 Mvar 0 MW
0 Mvar
0 .0 Mvar
-0 .1 Mvar
0 .0 Mvar
19 MW 51 Mvar
0 MW 0 Mvar
0 MW 0 Mvar
Display repeats previous case except now the change in generation is picked up by other generators using a participation factor approach
Sitting New Wind Generation Examplesl
SLACK138
RAY345
RAY138
RAY69
FERNA69
A
MVA
DEMAR69BOB138
PETE69HISKY69
TIM69
TIM138
TIM345
PAI69
GROSS69
HANNAH69
MORO138
A
MVA
A
MVA
MVA
A
MVA
A
MVA
A
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
1.02 pu
1.01 pu
1.02 pu
1.03 pu
1.00 pu
0.99 pu1.01 pu
1.01 pu
1.01 pu
1.02 pu
1.00 pu
1.02 pu
A
1.02 pu
A
MVA
A
MVA
System Losses: 8.73 MW
12 MW 3 Mvar
12 MW5 Mvar
Energy Systems Research Laboratory, FIU
BLT69
BLT138
BOB69
SHIMKO69
ROGER69
UIUC69
AMANDA69
HOMER69
LAUF69
HALE69
PATTEN69
WEBER69
A
MVA
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A
MVA
A A
A
MVA
A
MVA
A
MVA
1.00 pu
1.01 pu
1.01 pu
0.99 pu
1.01 pu
1.00 pu
1.00 pu1.00 pu
1.00 pu
1.01 pu
1.02 pu1.01 pu
1.00 pu 1.00 pu
MVA
1.00 pu
A
MVA
20 MW 12 Mvar
0 MW 0 Mvar
5 Mvar
56 MW
13 Mvar
14 MW
2 Mvar
Wind69
50 MW
-2 Mvar
What does the Future Hold for Wind?
• Wind has experienced rapid growth over the last decade; but with a large drop in installations expected for 2010.
• Nuclear and renewal generation are running into strong “head winds”
d b l
Energy Systems Research Laboratory, FIU
caused by lownatural gas prices.
• Expiring tax credits is acontinual concern.
• State renewable portfolio standards willhelp with growth.
9/16/2011
10
Hurricanes Impact Energy Prices
• Many oil refineries and natural gas pipelines off the coast
• Need to be shut down
Hurricane Ike, Sept. 2008
Energy Systems Research Laboratory, FIU
Need to be shut down and evacuated
• Takes time to get the systems back up and running afterwards http://tonto.eia.doe.gov/oog/special/hurricanes/
gustav_091308.html
Hurricanes Impact Energy Prices
Energy Systems Research Laboratory, FIUhttp://www.eia.doe.gov/emeu/steo/pub/special/pdf/2008_sp_03.pdf
What does the Future Hold for Wind?Vestas to Cut 3000 Jobs (14%) (10/26/10)
Vestas Stock Price Over Last Five Years
Closedat 176 onWednesday and 169.4 on Thursday!
Energy Systems Research Laboratory, FIU
Long-term the outlook for wind is probably good. On 9/1/10 EIA reduced their 2010 forecast for US capacity additions to 4.3 GW in 2010 and 6.5 GW in 2011; the totals for 2007 were 5.2 GW, 2008 8.4 GW and 2009 10.0GW
Distributed Generation (DG)
• Small-scale, up to about 50 MW
• Includes renewable and non-renewable sources
M b i l t d f th id id
Energy Systems Research Laboratory, FIU
• May be isolated from the grid or grid-connected
• Usually near the end user
Integrated Generation, Transmission, Buildings, Vehicles
kWh
Renewables
Grid
Energy Systems Research Laboratory, FIU
PHEV
N. Gas
Heat kWh
kWh
Smartmeters
Vehicle-to-Grid
CombinedHeat andPower (CHP)
Source: Masters
Pluggable Hybrid Electric Vehicles (PHEVs) as Distributed Generation
• Can charge at night when electricity is cheap
Energy Systems Research Laboratory, FIU
• Can provide services back to the grid
Source: www.calcars.org
Source: http://www.popularmechanics.com/automotive/new_cars/4215489.html
9/16/2011
11
San Francisco charging stations, 2009
Energy Systems Research Laboratory, FIUhttp://en.wikipedia.org/wiki/File:Charging_stations_in_SF_City_Hall_02_2009_02.jpg
DG Technologies, Excepting Solar
• Microturbines
• Reciprocating Internal Combustion Engines
• Biomass
• Micro-Hydro
Energy Systems Research Laboratory, FIU
y
• Fuel Cells (we’ll be skipping)
• Concentrated solar power is talked about in Chapter 4, but we’ll skip until after we cover Chapter 7.
Reasons for Distributed Generation
• Good for remote locations
• Renewable resources
• Reduced emissions
Energy Systems Research Laboratory, FIU
• Can use the waste heat
• Can sell power back to the grid
Terminology
• Cogeneration and Combined Heat and Power (CHP) – capturing and using waste heat while generating electricity
• When fuel is burned one product is water; if water vapor exits stack then its energy is lost (about 1060 Btu per pound of water vapor)
Energy Systems Research Laboratory, FIU
p p )
• Heat of Combustion for fuels– Higher Heating Value (HHV) – gross heat, accounts for latent
heat in water vapor
– Lower Heating Value (LHV) – net heat, assumes latent heat in water vapor is not recovered
– Both are used - Conversion factors (LHV/HHV) in Table 4.2
HHV and LHV Efficiency
• Find LHV efficiency or HHV efficiency from the heat rate:
HHV( )HHV( )
3412 Btu/kWh (3.16)
Heat Rate (Btu/kWh)LHVLHV
Energy Systems Research Laboratory, FIU
• Convert to get the other efficiency:
HHV( )LHV
HHV LHV
LHV (4.1)
HHV
Note the LHV is less than the HHV
Microturbines
• Small natural gas turbines, 500 W to 100s kW
• Only one moving part
• Combined heat and power
230 kW fuel
120 kW hot water output
Energy Systems Research Laboratory, FIU
Combined heat and power
• High overall efficiency
Source: http://www.capstoneturbine.com
Capstone 65 kW Microturbine
80% CHPEfficiency
65 kW electrical output
45 kW waste heat
9/16/2011
12
Microturbines
1. Incoming air is compressed
2. Moves into cool side of recuperator & is heated
3. Mixes with fuel in
Energy Systems Research Laboratory, FIU
combustion chamber
4. Expansion of hot gases spins shaft
5. Exhaust leaves
Figure 4.1
Microturbines and Renewable Energy
• Microturbines are not a renewable energy source since they ultimately use natural gas as their fuel. But when used for combined heat and electricity they can be quite efficient and emit significantly less CO2 than coal.
• A possible scenario: If natural gas prices remain low,
Energy Systems Research Laboratory, FIU
commercial/industrial entities will increasingly go “off grid.” Hence they will not be subject to state renewable portfolio standards or utility taxes. This will mean renewable energy subsidies will increasingly be born by residential customers. Average residential price per therm is $0.57 in October in Illinois; with a heat rate of 8.5 this gives electricity at 4.8 cents/kWh.
Biomass – Current Conditions
• Biomass, including waster, currently provides about 4% of the US total energy, a value that is projected to grow to about 7% by 2030.
• In 2008 the 3.85 quad of biomass was split between biofuels such as ethanol (1.37 quad), waste such as landfill gas (0.436 quad)
Energy Systems Research Laboratory, FIU
and wood (2.04 quad). – About 1/10 of the wood was used to produce electricity, primarily by the
paper industry; total generation capacity in US is about 11.3 GW
– We are not considering liquid fuels for non-electricity use in ECE 333; ethanol usage was growing at 30% per year
• Little to no fuel cost for wood waste but little growth
Biomass – Future Possibilities for Electricity
• Newer crops are being considered for future biomass, including various grasses (such as Miscanthus and Switch Grass) along with algae
• Potential uses include both fuel to t l t i it ( i il th
Energy Systems Research Laboratory, FIU
create electricity (primarily the grasses), and conversion to liquid fuels such as ethanol.– On campus 320 acres in the South
Farms are devoted to biofuel research
Biomass – Future Possibilities for Electricity
• A full consideration of biomass is beyond our scope of since it gets into agricultural economics issues
• Miscanthus can be harvested at rates of about 15 tons per acre in Illinois Once established it does not need to be replanted This
Energy Systems Research Laboratory, FIU
Illinois. Once established it does not need to be replanted. This allows the energy potential of about 225 Mbtu per acre; income depends on energy price, say $2/Mbtu = $450 per acre. For comparison corn can yield up to 200 bushels per acre at say $5.50/bushel = $1100 per acre– Energy yield is about 225/15 = 15 Mbtu/ton which is similar to coal
– Not a native species so containment could be an issue
Cofiring
• Burn biomass and coal
• Modified conventional steam-cycle plants
• Allows use of biomass in plants with higher ffi i i
Energy Systems Research Laboratory, FIU
efficiencies
• Reduces overall emissions
9/16/2011
13
Gas Turbines and Biomass
• Cannot run directly on biomass without causing damage
• Gassify the fuel first and clean the gas before combustion
Energy Systems Research Laboratory, FIU
combustion
• Coal-integrated gasifier/gas turbine (CIG/GT) systems
• Biomass-integrated gasifier/gas turbine (BIG/GT) systems
Biomass and Transportation
• A key issue associated with biomass is the transportation costs – these grasses are quite bulky.
• A rough estimate of the cost per ton for transportation is about $1 + 0.1 * round trip distance in miles + h ti t f b t $22 t S if th
Energy Systems Research Laboratory, FIU
harvesting costs of about $22 per ton. So if the power plant is 50 miles distant, total cost would be $33 per ton, or about $33/ton/($15 Mbtu/ton) = $2.2 per Mbtu
• Total US corn planting is about 87 million acres, which if planted in grass could yield about 20 quad of energy.– Won’t meet all our needs but could play a major role
A Biomass plant
Energy Systems Research Laboratory, FIU