Major Changes in the 2013 in the 2013 Editions of NFPA 13, 13R NFPA 13, 13R and 13D April 10, 2013 Safer. Smarter. Tyco. TM

LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Embed Size (px)

DESCRIPTION

NFPA 13

Citation preview

Page 1: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Major Changes in the 2013in the 2013 Editions of

NFPA 13, 13RNFPA 13, 13R and 13D

April 10, 2013

Safer. Smarter. Tyco.TM

Page 2: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Meet Your Presenters:Meet Your Presenters:

Terry Victor,

Meet Your Presenters:Meet Your Presenters:

e y cto ,National Manager of Sprinkler Business Processes atSimplexGrinnell.H h 39 f t h i l i i th i kl i d tHe has over 39 years of technical experience in the sprinkler industry and serves on various industry boards, including NFPA technical committees for NFPA 13, NFPA 13D, NFPA 13R, NFPA 20 and NFPA 2525.

Matt Klaus,Senior Fire Protection Engineer for the National Fire Protection gAssociation (NFPA).

He is the staff liaison responsible for many of the NFPA documents related to waterbased systems.

Company Confidential

y

2

Page 3: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

What You’ll Learn From this Webinar:What You’ll Learn From this Webinar:What You ll Learn From this Webinar:What You ll Learn From this Webinar:

How much time and effort goes into the Code Development Cycleg p yHow both new and revised definitions will impact design

approaches and inspection, testing and maintenance requirementsrequirementsWhich systems and components have new requirements and/or

applicationsWhat materials and products used in sprinkler systems must now

be carefully tested and evaluatedWhich design considerations will be more restrictive and whichWhich design considerations will be more restrictive and which

will be less restrictiveHow storage protection is becoming more specialized and what

testing criteria must be met

Company Confidential 3

testing criteria must be met

Page 4: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

What We Won’t Address Today:What We Won’t Address Today:What We Won t Address Today:What We Won t Address Today:

The latest developments on the fire testing and use of p gantifreeze in new and existing systems.The latest changes in the storage protection criteria and

i t i h t 12 th h 21requirements in chapters 12 through 21.

Company Confidential 4

Page 5: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

NFPA 13/13R/13DNFPA 13/13R/13D –– 2013 Code Cycle2013 Code CycleNFPA 13/13R/13D NFPA 13/13R/13D 2013 Code Cycle2013 Code Cycle

A2012 NFPA Code Development Cyclep y•Over 150 Volunteers involved in the 13 Technical Committees•800 + Proposals•500 + Comments

After the Report on Comments•Antifreeze TIAs  (13, 13R, 13D and 25)( , , )•CPVC TIAs (13 and 13R)•Certified Amending Motions (CAMs)•On Doc Info Page

Company Confidential 5

Page 6: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

The 2013The 2013 Edition

Company Confidential 6

Page 7: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

NFPA®NFPA® 1313NFPA® NFPA® 1313Standard for the Standard for the Installation Installation of of

S i kl S tS i kl S tSprinkler SystemsSprinkler Systems

Major Changes

Company Confidential 7

Page 8: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 1Chapter 1 -- AdministrationAdministrationChapter 1 Chapter 1 AdministrationAdministrationChanges include:

New statement on water mist systems

Single fire origin statement

Changes include a scope statement that sprinkler systems are designed based on a single fire 

Company Confidential 8

originating in the building.

Page 9: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 1 - AdministrationChapter 1 Administration(Scope – Water Mist System)

1.1.2 This standard shall not provide i t f th d irequirements for the design or

installation of water mist fire protection systems, which are not considered fire sprinkler systems andconsidered fire sprinkler systems and are addressed by NFPA 750.

This new scope statement clarifies that water mist systems are not considered to be sprinkler 

Company Confidential 9

systems. The same statement is also included in the 2013 editions of NFPA 13R and 13D.

Page 10: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3Chapter 3 -- DefinitionsDefinitionsControl valve

Draft Curtain

Premixed Antifreeze Solution.

Combined Dry Pipe/Pre Action

Chapter 3 Chapter 3 DefinitionsDefinitions

Draft Curtain

Dwelling Unit

High Volume Low Speed Fan

Combined Dry Pipe/Pre Action

Cross Main

System Riser

Continuous Obstruction

Non-Continuous Obstruction

Clearance to Ceiling

Clearance to Storage

General Sprinkler Characteristics

Open Top ContainerClearance to Ceiling

Raw Water Source

Sprinkler System

Open Top Container

Four-Way Bracing

Hanger

Small Room

Antifreeze System

Net Vertical Force

Seismic Separation Assembly

Company Confidential 10

Various new and revised definitions are in the new standard.

Page 11: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Dwelling Unit)

3.3.10 Dwelling Unit (for sprinkler system installations). One or more d f th f i di id l li i t th irooms arranged for the use of one or more individuals living together, as in a

single housekeeping unit normally having cooking, living, sanitary, and sleeping facilities that include, but are not limited to, hotel rooms, dormitory rooms apartments condominiums sleeping rooms in nursing homes androoms, apartments, condominiums, sleeping rooms in nursing homes, and similar living units.

Clarifies where special design criteria for dwelling units may be applied utilizing NFPA 13 for 

Company Confidential 11

criteria

Page 12: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Continuous & Noncontinuous Obstruction)

3.3.18 Obstruction.

3.3.18.1 Continuous Obstruction. An obstruction located at or below the level of sprinkler deflectors that affect the discharge pattern of two or more p g padjacent sprinklers.

3 3 18 2 Noncontinuous Obstruction An obstruction at or below the level of3.3.18.2 Noncontinuous Obstruction. An obstruction at or below the level of the sprinkler deflector that affects the discharge pattern of a single sprinkler.

These terms were used in previous editions but were never specifically defined. These new 

Company Confidential 12

definitions were added to clarify obstruction rules and sprinkler positioning.

Page 13: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Sprinkler System)

3.3.22* Sprinkler System. A system that consists of an integrated network of i i d i d i d ith fi t ti i i t d d th tpiping designed in accordance with fire protection engineering standards that

includes a water supply source, a water control valve, a waterflow alarm, and a drain and is commonly activated by heat from a fire, discharging water over the fire area The portion of the sprinkler system above ground is a network ofthe fire area. The portion of the sprinkler system above ground is a network of specifically sized or hydraulically designed piping installed in a building, structure, or area, generally overhead, and to which sprinklers are attached in a systematic pattern The system is commonly activated by heat from a firea systematic pattern. The system is commonly activated by heat from a fire and discharges water over the fire area.

This revised definition will help clarify the limitations of a system as it applies to NFPA 13 and 

Company Confidential 13

25. 

Page 14: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Sprinkler System)

A.3.3.22 Sprinkler System. As applied to the definition of a sprinkler system, each system riser serving a y , y gportion of a single floor of a facility or where individual floor control valves are used in a multistory building should be considered a separate sprinkler system. Multiple sprinkler systems can be supplied by a

l icommon supply main.

Shown here are typical floor control assemblies 

Company Confidential 14

which are considered separate systems.

Page 15: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Premixed Antifreeze Solution)

3.4.1.1 Premixed Antifreeze Solution. A mixture of an antifreeze material ith t th t i d d f t i d b th f t ithwith water that is prepared and factory-mixed by the manufacturer with a

quality control procedure in place that ensures that the antifreeze solution remains homogeneous and that the concentration is as specified.

Sprinkler contractors once mixed their own solutions using pure antifreeze and water. The purity, actual percentage of concentration, and homogeneity of the solution were 

Company Confidential 15

questionable at best.

Page 16: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Clearance to Ceiling)

3.9.1.5 Clearance to Ceiling. Th di t f th t fThe distance from the top of storage to the ceiling above.

This new definition has an impact on the design criteria for storage 

Company Confidential 16

occupancies.

Page 17: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 4CHAPTER 4 -- General RequirementsGeneral RequirementsCHAPTER 4 CHAPTER 4 General RequirementsGeneral Requirements

Changes include:

Air, Nitrogen, or Other Approved Gas

Support of Nonsprinkler System Componentspp p y p

Changes include statements about the use of air in systems and about supporting non‐

Company Confidential 17

sprinkler system components.

Page 18: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 5 CHAPTER 5 –– Classification of Classification of O i d C ditiO i d C ditiOccupancies and CommoditiesOccupancies and CommoditiesChanges include:

Group A plastics subdivided

The only change is the subdivision of group A plastics based on a percentage by volume of 

Company Confidential 18

the expanded plastic.

Page 19: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 6 CHAPTER 6 –– System System C t d H dC t d H dComponents and HardwareComponents and HardwareChanges include:

Nonmetallic pipe and fittings

Sprinklers removedp

Painted, glued, or caulked sprinklers

Limit of underground pipeLimit of underground pipe

Grooved joints

Reserved section for signsReserved section for signs

Several major changes were made in chapter 6 that affects the installation of new sprinkler 

Company Confidential 19

systems, as well as the renovation of existing systems.

Page 20: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 6 – System Components d H dand Hardware

(Removal of Sprinklers)

6.2.1.1 When a i kl h bsprinkler has been

removed for any reason, it shall not be reinstalledreinstalled.

Because even slight damage to a sprinkler during theto a sprinkler during the removal process could cause a premature discharge, the committee decided to 

h b ll

Company Confidential 20

prohibit any re‐installation.

Page 21: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 6 – System Components d H dand Hardware

(Underground Pipe)

6.3.1.1.1* Underground pipe shall be itt d t t d i t th b ildipermitted to extend into the building

through the slab or wall not more than 24 in. (0.6 m).

This change limits the amount of underground pipe that can project into the building. The 24” allows room for the transition to the above 

Company Confidential 21

ground piping system. 

Page 22: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 6 – System Components d H dand Hardware

(Nonmetallic Pipe)

6.3.7* Nonmetallic Pipe. Nonmetallic pipe in accordance with Table 6.3.1.1 shall be investigated for suitability in automatic sprinkler installations and listed for this service.for this service.

--------------------6.3.7.2* When nonmetallic pipe is used in combination systems utilizing steel piping internally coated with corrosion inhibitors and nonmetallic piping thepiping internally coated with corrosion inhibitors and nonmetallic piping, the steel pipe coating shall be investigated for compatibility with the nonmetallic piping by a testing laboratory.

Steel pipe interior coatings must be compatible with any nonmetallic pipe that it can come in 

Company Confidential 22

contact with in a combination system as recognized by a testing laboratory.

Page 23: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 6 – System Components d H dand Hardware

(Nonmetallic Pipe)

6.3.7.4 When nonmetallic pipe is used in combination systems utilizing steel pipe, cutting oils and lubricants used for fabrication of the steel piping shall be compatible with the nonmetallic pipe materials.compatible with the nonmetallic pipe materials.6.3.7.5 Fire-stopping materials intended for use on nonmetallic piping penetrations shall be investigated for compatibility with the nonmetallic pipe materialsmaterials.

Consideration and investigation for compatibility with other system related materials is 

Company Confidential 23

required, including fire stopping materials.

Page 24: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTERCHAPTER 77 –– System RequirementsSystem RequirementsCHAPTER CHAPTER 77 System RequirementsSystem Requirements

Changes include:

Relief valves

Enclosure freeze protectionp

Dry system gauges and sprinklers

Dry system water delivery for dwelling unitsDry system water delivery for dwelling units

Antifreeze solutions

Additives and coatings listedAdditives and coatings listed

Two changes include the need to have solutions or materials that are added to the water 

Company Confidential 24

supply or internal pipe wall listed by a recognized testing laboratory.

Page 25: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – System RequirementsChapter 7 System Requirements(Antifreeze Systems)

7.6.2* Antifreeze Solutions.7.6.2.1* Except as permitted in 7.6.2.2, antifreeze solutions shall be listed for use in sprinkler systems.7.6.2.2 Premixed antifreeze solutions of propylene glycol shall be permitted to p py g y pbe used with ESFR sprinklers where the ESFR sprinklers are listed for such use in a specific application.

This statement anticipates that there could be a listed antifreeze solution at some point in 

Company Confidential 25

time, and would allow for it’s immediate use.

Page 26: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – System RequirementsChapter 7 System Requirements(Additives and Coatings)

7.11 Additives and Coatings.7.11.1 Additives to the water supply intended for control of microbiological or other corrosion shall be listed for use within fire sprinkler systems.7.11.2 Internal pipe coatings, excluding galvanizing, intended for control of p p g g g gmicrobiological or other corrosion shall be listed for use within fire sprinkler systems.

Compatibility of sprinkler system piping, fittings and components with corrosion inhibiting 

Company Confidential 26

solutions, coatings, and additives have been a problem for many years now.

Page 27: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8Chapter 8 –– Installation RequirementsInstallation RequirementsChapter 8 Chapter 8 Installation RequirementsInstallation Requirements

Changes include:

Sprinklers in equipment

Sprinklers in light hazard and residential compartmentsp g p

ESFR and CMSA sprinkler limitations and obstructions

Dry sprinkler barrel lengthsDry sprinkler barrel lengths

Sprinklers in small closets

The use of bafflesThe use of baffles

Sprinklers and soffits

Company Confidential 27

These changes that are checked are major ones that will impact design considerations.

Page 28: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8Chapter 8 –– Installation RequirementsInstallation RequirementsChapter 8 Chapter 8 Installation RequirementsInstallation Requirements

Changes include:

Sprinklers and various obstructions

Allowances to omit sprinklersp

Exterior Projections

Bathrooms in dwelling unitsBathrooms in dwelling units

Hospital Clothes Closets

Floor control assembliesFloor control assemblies

Freeze protectionChanges on this slide will impact the number of sprinklers required and how systems are 

Company Confidential 28

installed in multi‐story buildings.

Page 29: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8.1* Basic Requirements.

Chapter 8 Installation Requirements(Sprinklers in Equipment)

8.1.1* The requirements for spacing, location, and position of sprinklers shall be based on the following principles:

--------------------(8)*Sprinklers shall not be required(8) Sprinklers shall not be required to be installed within electrical equipment, mechanical equipment, or air handling units not intended gfor occupancy.

Some of this equipment can get extremely large, to the point where it becomes close to the 

Company Confidential 29

size of a room

Page 30: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8.3.3.4 When existing light hazard

Chapter 8 Installation Requirements(Sprinklers in LH and Residential Compartments)

8.3.3.4 When existing light hazard systems are converted to use quick-response or residential sprinklers, all sprinklers in a compartment shall be h dchanged.

--------------------8.4.5.3 Where residential sprinklers are installed in a compartment asare installed in a compartment as defined in 3.3.6, all sprinklers within the compartment shall be residential sprinklers.p

The sprinklers must be all QR or all residential 

Company Confidential 30

in a compartment.

Page 31: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation RequirementsChapter 8 Installation Requirements(Sprinklers in Small Closets)

8.5.5.4 Closets. In all closets and compartments, including those closets housing mechanical equipment, that are not larger than 400 ft3 (11.33 m3) in size, a single sprinkler at the highest ceiling space h ll b ffi i t ith t d tshall be sufficient without regard to

obstructions or minimum distance to the wall.

This change allows that the sprinkler may be located without regard to a shelf or multiple 

Company Confidential 31

shelves or other equipment in the closet.

Page 32: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8 6 3 4 Minimum Distances

Chapter 8 Installation Requirements(Allowance for Baffles Between Sprinklers)

8.6.3.4 Minimum Distances Between Sprinklers.8.6.3.4.1 Unless the requirements of 8 6 3 4 2requirements of 8.6.3.4.2, 8.6.3.4.3, or 8.6.3.4.4 are met, sprinklers shall be spaced not less than 6 ft (1 8 m) on centerless than 6 ft (1.8 m) on center.

--------------------8.6.3.4.3 In-rack sprinklers shall be permitted to be placed lessbe permitted to be placed less than 6 ft (1.8 m) on center.

This change provides additional rules for baffles used 

Company Confidential 32

for closely spaced sprinklers.

Page 33: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8.6.3.4 Minimum Distances Between Sprinklers.

Chapter 8 Installation Requirements(Allowance for Baffles Between Sprinklers)

--------------------8.6.3.4.2 Sprinklers shall be permitted to be placed less than 6 ft (1.8 m) on center where the following conditions are satisfied:center where the following conditions are satisfied:(1) Baffles shall be arranged to protect the actuating elements.(2) Baffles shall be of solid and rigid material that will stay in place before and during sprinkler operationduring sprinkler operation.(3) Baffles shall be not less than 8 in. (203 mm) long and 6 in. (152 mm) high.(4) The tops of baffles shall extend between 2 in. and 3 in. (51 mm and 76 mm) above the deflectors of upright sprinklers.(5) The bottoms of baffles shall extend downward to a level at least even with the deflectors of pendent sprinklers.

Company Confidential 33

Page 34: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation RequirementsChapter 8 Installation Requirements(Allowance for Baffles Between Sprinklers)

Sprinkler Type Minimum Distance  w/o Baffles

BafflesAllowed

Chapter 8 Reference

Standard Upright & Pendent 6’‐0 Yes 8.6.3.4.2p g

Standard Sidewall 6’‐0 Yes 8.7.3.4

EC Upright & Pendent 8’‐0 Yes 8.8.3.4.2

EC Sidewall Not in Protection Area Yes 8 9 3 4EC Sidewall Not in Protection Area Yes 8.9.3.4

Residential 8’‐0 Yes 8.10.3.3

Residential Sidewall Not in Protection Area Yes 8.10.3.4

Previous editions of NFPA 13 didn’t provide this much detail on the construction and 

Company Confidential 34

placement of baffles.

Page 35: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8.15.1.2* Concealed Spaces

Chapter 8 Installation Requirements(Allowance to Omit Sprinklers)

Not Requiring Sprinkler Protection.

--------------------8.15.1.2.7 Concealed spaces filled with noncombustible insulation shall not require qsprinkler protection.8.15.1.2.7.1 A maximum 2 in. (50 mm) air gap at the top of the ( ) g p pspace shall be permitted.

Since it’s virtually impossible to eliminate an air gap as insulation settles, this new text allows 

Company Confidential 35

for up to a 2” air gap between top of insulation and bottom of deck above

Page 36: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation RequirementsChapter 8 Installation Requirements(Allowance to Omit Sprinklers)

8.15.5 Elevator Hoistways and Machine Rooms.--------------------8.15.5.3 Automatic fire sprinklers shall not be required in elevator machine rooms, elevator machinery spaces, control spaces, or hoistways of traction elevators installed in accordance with the applicable provisions in NFPA 101, pp p ,or the applicable building code, where all of the following conditions are met:(1) The elevator machine room, machinery space, control room, control space, or hoistway of traction elevator is dedicated to elevator equipment only.y q p y

This allowance to not require sprinklers in elevator hoistways and machine rooms was 

Company Confidential 36

debated by the technical committee. 

Page 37: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

(2) The elevator machine room, machine room, machinery space, control

Chapter 8 Installation Requirements(Allowance to Omit Sprinklers)

room, control space, or hoistway of traction elevators are protected by smoke detectors, or other automatic fire detection, installed in accordance with NFPA72.(3) The elevator machinery space, control room, control space, or hoistway of traction elevators is separated from the remainder of the building by walls and floor/ceiling or roof/ ceiling assemblies having a fire resistance rating of not less than that specified by the applicable building code.(4) No materials unrelated to elevator equipment are permitted to be stored in elevator machine rooms, machinery spaces, control rooms, control spaces, or hoistways of traction elevators.(5) The elevator machinery is not of the hydraulic type.

Company Confidential 37

When all of the conditions are met sprinklers can be omitted.

Page 38: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation RequirementsChapter 8 Installation Requirements(Bathrooms in Dwelling Units)

8.15.8 Dwelling Units.8.15.8.1 Bathrooms.8.15.8.1.1* Sprinklers shall not be required in bathrooms that are located within dwelling units of hotels and motels, that do not exceed 55 ft2 (5.1 m2) in area, and that have walls and ceilings of noncombustible or limited-, gcombustible materials with a 15-minute thermal barrier rating, including the walls and ceilings behind any shower enclosure or tub.

This change adds sprinklers in bathrooms of apartments, condos, dorms and other building 

Company Confidential 38

with residential dwelling units protected in accordance with NFPA 13.

Page 39: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation Requirements

8.16.1.5 Floor Control Valve Assemblies.

Chapter 8 Installation Requirements(Floor Control Assemblies)

8.16.1.5.1* Multistory buildings exceeding two stories in height shall be provided with a floor control valve, check valve, main drain valve, and flow switch for isolation, control, and annunciation of water flow on each floor level.

41

2

4

3

Company Confidential 39

This change compliments the new definition of a sprinkler system. 

Page 40: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Installation RequirementsChapter 8 Installation Requirements(Floor Control Assemblies)

8.16.1.5 Floor Control Valve Assemblies.--------------------8.16.1.5.2 The floor control valve, check valve, main drain valve, and flow switch required by 8.16.1.6.3 shall not be required where sprinklers on the top level of a multistory building are supplied by piping on the floor below.y g pp y p p g8.16.1.5.3 The floor control valve, check valve, main drain valve, and flow switch required by 8.16.1.6.3 shall not be required where the total area of all floors combined does not exceed the system protection area limitations of y p8.2.1.

Company Confidential 40

There are two exceptions for the requirement of floor control assemblies

Page 41: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter Chapter 99 –– Hanging, Bracing and Hanging, Bracing and R t i t f S t Pi iR t i t f S t Pi iRestraint of System PipingRestraint of System PipingChanges include:

Minimum Number of Hangers

Unsupported lengths of pipepp g p p

Securing pipe stands

Earthquake protectionEarthquake protection

Sway bracing requirements

Company Confidential 41

We will not be addressing any changes in this chapter during the webinar

Page 42: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 10Chapter 10 –– Underground PipingUnderground PipingChapter 10 Chapter 10 Underground PipingUnderground Piping

Changes include:

Steel pipe for FDCs

Buried Fittingsg

Coated bolts

Pipe run under buildingsPipe run under buildings

Flushing flow rates

Material and Test CertificateMaterial and Test Certificate

Company Confidential 42

We will not be addressing any changes in this chapter during the webinar

Page 43: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 11Chapter 11 –– Design ApproachesDesign ApproachesChapter 11 Chapter 11 Design ApproachesDesign Approaches

Changes include:

Designers discretion

High Volume Low Speed (HVLS) Fansg p ( )

Adjacent unsprinklered concealed spaces

Residential sprinklers with unsprinklered combustibleResidential sprinklers with unsprinklered combustible concealed spaces

One change has a huge impact on design areas for residential sprinklers in a NFPA 13 

Company Confidential 43

application.

Page 44: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 11 – Design Approaches

11.3 Special Design Approaches.

Chapter 11 Design Approaches(Residential Unsprinklered Combustible Concealed Spaces )

11.3.1 Residential Sprinklers.----------------------11.3.1.2* Unless the requirements of 11.2.3.1.4(4) are met for buildings having unsprinklered combustible concealed spaces, as described in 8.15.1.2 and 8.15.6, the minimum design area of sprinkler operation for that portion of the building shall be eight sprinklers.11 3 1 2 1* The design area of eight sprinklers shall be applied only to the portion11.3.1.2.1 The design area of eight sprinklers shall be applied only to the portion of the residential sprinklers that are adjacent to the qualifying combustible concealed space.11.3.1.2.2 The term adjacent shall apply to any sprinkler system protecting a space above, below, or next to the qualifying concealed space except where a barrier with a fire resistance rating at least equivalent to the water supply duration completely separates the concealed space from the sprinklered area.

Company Confidential 44

The normal four sprinkler design area is doubled and must include eight sprinklers.

Page 45: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 12 Chapter 12 –– General Requirements General Requirements f Stf Stfor Storagefor Storage

Through and Including

.Chapter 21 Chapter 21 –– Alternative Sprinkler Alternative Sprinkler System Designs for Chapters 12System Designs for Chapters 12System Designs for Chapters 12 System Designs for Chapters 12 Through 20Through 20

We do want to point out that Chapter 21 is new to the 2013 edition of NFPA 13. The purpose of this new chapter is to provide an alternative to Chapters 12 through 20 using the results of 

Company Confidential 45

full‐scale fire tests to establish the discharge criteria. 

Page 46: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 22 Chapter 22 –– Special Occupancy Special Occupancy R i tR i tRequirementsRequirementsChanges include:

Nitrite Film (NFPA 40)

Protection of Information Technology Equipment (NFPA 75)gy q p ( )

Water Cooling Towers (NFPA 214)

Hydroelectric Generating Plants (NFPA 851)Hydroelectric Generating Plants (NFPA 851)

Cultural Resource Properties - Museums, Libraries, and Places of Worship (NFPA 909)

Metal/Nonmetal Mining and Metal Mineral Processing Facilities (NFPA 122)

C ( )

Company Confidential 46

Hazardous Materials Code (NFPA 400)

Page 47: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 23Chapter 23 –– Plans and CalculationsPlans and CalculationsChapter 23 Chapter 23 Plans and CalculationsPlans and Calculations

Through and Including

Chapter 27Chapter 27 –– System InspectionSystem Inspection.Chapter 27 Chapter 27 System Inspection, System Inspection, Testing, and MaintenanceTesting, and Maintenance

Company Confidential 47

We will not be addressing any changes in these chapters during the webinar

Page 48: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

NFPA®NFPA® 13R13RNFPA® NFPA® 13R13RStandard for the Standard for the Installation Installation of of

S i klS i kl S tS t i Li LSprinkler Sprinkler Systems Systems in Lowin Low--Rise Residential OccupanciesRise Residential Occupancies

Major Changes

Company Confidential 48

Page 49: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

The 2013The 2013 Edition

Company Confidential 49

Page 50: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

New TitleNew TitleNew TitleNew TitleNFPA 13R Standard for the Installation of Sprinkler Systems in Low-rise Residential p y

Occupancies

Company Confidential50

Page 51: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 1Chapter 1 -- AdministrationAdministrationChapter 1 Chapter 1 AdministrationAdministration

Changes include:

Height above grade plane statement

Water mist system statementy

To go with the revised scope is an extensive explanation on the appropriate use and intent of 

Company Confidential 51

the standard.

Page 52: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3Chapter 3 -- DefinitionsDefinitionsChapter 3 Chapter 3 DefinitionsDefinitions

Changes include:

Grade Plane (new)

Raw Water Source (new)( )

Shadow Area (new)

New definitions have been added and others revised to support new or existing terms used in 

Company Confidential 52

the standard.

Page 53: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 4Chapter 4 –– General RequirementsGeneral RequirementsChapter 4 Chapter 4 General RequirementsGeneral Requirements

Company Confidential 53

No changes were made to chapter 4.

Page 54: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 5CHAPTER 5 –– System ComponentsSystem ComponentsCHAPTER 5 CHAPTER 5 System ComponentsSystem Components

Changes include:

Combined water meters & PRVs

Nonmetallic pipe compatibilityp p p y

Nonmetallic fitting compatibility

Use of brass pipe and fittingsUse of brass pipe and fittings

Use of antifreeze

Freeze protection options expandedFreeze protection options expanded

The changes in chapter 5 include the same requirements as NFPA 13 on the compatibility of 

Company Confidential 54

nonmetallic pipe and antifreeze.

Page 55: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTERCHAPTER 66 –– InstallationInstallationCHAPTER CHAPTER 66 InstallationInstallationChanges include:

Sprinklers outside the dwelling unitSprinklers outside the dwelling unit

Exposed barrel lengths for dry type sprinklers

S i kl i l tSprinkler coverage in closets

Shadow areas

P t ti f i t i t i llProtection of interior stairwells

Areas to omit sprinklers

Freeze protection options

Control valve location

Company Confidential 55

Some of the other changes in this chapter that we won’t be covering are significant

Page 56: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – InstallationChapter 6 Installation(Sprinklers in Small Closets)

6.4.6.3.2* Within Closets. In all closets and compartments, including those closets housing mechanical equipment,closets housing mechanical equipment, that are not larger than 400 ft3 (11.33 m3) in size, a single sprinkler at the highest ceiling space shall be sufficient without g pregard to obstructions or minimum distance to the wall.

The position of the sprinkler isn’t important because of the amount of water being discharged under 

Company Confidential 56

pressure in such a small space.

Page 57: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – Installation

6.4.6.3.3.1* Shadow Areas. Shadow areas shall be permitted in the

Chapter 6 Installation(Shadow Areas)

protection area of a sprinkler as long as the cumulative dry areas do not exceed 15 ft2 (1.4 m2) per sprinkler.

--------------------6.4.6.3.3.3 Small areas created by architectural features such as planter box windows, bay windows, and similar features shall be evaluated as follows:(1) Where no additional floor area is created by the architectural feature no(1) Where no additional floor area is created by the architectural feature, no additional sprinkler protection is required.

--------------------(3) The hydraulic design is not required to consider the area created by the(3) The hydraulic design is not required to consider the area created by the architectural feature.

… there may be “dry floor area within the protection area of a sprinkler created by the portion 

Company Confidential 57

of sprinkler discharge that is blocked by a wall or partition.”

Page 58: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – Installation

6.4.6.3.3.3 Small areas created by architectural features such as planter box i d b i d d i il f h ll b l d f ll

Chapter 6 Installation(Shadow Areas)

windows, bay windows, and similar features shall be evaluated as follows:---------------------------(2) Where additional floor area is created by an architectural feature, no dditi l i kl t ti i i d id d ll f th f ll iadditional sprinkler protection is required, provided all of the following

conditions are met:(a) The floor area shall not exceed 18 ft2 (1.7 m2).(b) Th fl h ll t b t th 2 ft (0 61 ) i d th t th d t(b) The floor area shall not be greater than 2 ft (0.61 m) in depth at the deepest point of the architectural feature to the plane of the primary wall where measured along the finished floor.(c) The floor shall not be greater than 9 ft (2 7 m) in length where measured(c) The floor shall not be greater than 9 ft (2.7 m) in length where measured along the plane of the primary wall.(d) Measurement from the deepest point of the architectural feature to the sprinkler shall not exceed the maximum listed spacing of the sprinkler.

Company Confidential

sprinkler shall not exceed the maximum listed spacing of the sprinkler.

58

Page 59: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – InstallationChapter 6 Installation(Shadow Areas)

These figures have been added in the annex to illustrate the use of the rules in 6.4.6.3.3.3 (2) 

Company Confidential 59

(a) through (d). 

Page 60: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – Installation

6.4.6.3.3.2 Shadow areas in corridors up to 2 ft (0.61 m) in depth and up to 9 ft

Chapter 6 Installation(Shadow Areas)

(2.7 m) in length behind sidewall sprinklers shall be permitted as shown in Figure 6.4.6.3.3.2.

Company Confidential 60

This is a good illustration of the intent of allowing some dry floor area

Page 61: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – InstallationChapter 6 Installation(Control Valve Location)

6.8.8 The control valve for a system ti f t t tior portion of a system protecting a

dwelling unit shall not be located in a different dwelling unit than the unit it servesserves.

If a control valves serves several units it must be in a separate valve room because it can’t 

Company Confidential 61

be in one unit and serve another.

Page 62: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 7CHAPTER 7 –– Discharge CriteriaDischarge CriteriaCHAPTER 7 CHAPTER 7 Discharge CriteriaDischarge Criteria

Changes include:

Discharge density

Listed flows

Number of design sprinklers

Design criteria outside the dwelling unitDesign criteria outside the dwelling unit

Increase for unsprinklered combustible concealed spaces

We will focus on two changes that will resolve many problems typically encountered when 

Company Confidential 62

designing sprinkler systems per NFPA 13R.

Page 63: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – Discharge Criteria

7.1.1.3* Number of Design Sprinklers.

Chapter 7 Discharge Criteria(Sprinklers Under Sloped Ceilings)

7.1.1.3.1 For each of the following situations, the number of sprinklers in the design area shall be all of the sprinklers within a compartment, up to a maximum of four sprinklers, that require the greatest hydraulic demand:g y(1) A flat, smooth, horizontal ceiling with no beams up to a maximum of 24 ft (7.3 m) above the floor.(2) A flat horizontal beamed ceiling with a maximum ceiling height of 24 ft(2) A flat, horizontal, beamed ceiling, with a maximum ceiling height of 24 ft (7.3 m), with beams up to 14 in. (355 mm) deep with pendent sprinklers under the beams. The compartment containing the beamed ceiling shall be a maximum of 600 ft2 (55m2) in area. The highest sprinkler in the compartment ( ) g p pshall be above all openings from the compartment into any communicating spaces.This new text … incorporates the findings of the Fire Protection Research Foundation’s project 

Company Confidential 63

on residential sprinklers and sloped and beamed ceilings 

Page 64: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – Discharge Criteria

(3) A smooth, flat, sloped ceiling with no beams up to a maximum slope of 8 in

Chapter 7 Discharge Criteria(Sprinklers Under Sloped Ceilings)

12. The highest portion of the ceiling shall not be more than 24 ft (7.3 m) above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from the compartment containing the sloped ceiling into

i tiany communicating spaces.(4) A sloped ceiling with beams up to 14 in. (355 mm) deep with pendent sprinklers under the beams. The compartment containing the sloped, beamed ceiling shall be a maximum of 600 ft2 (55 m2) in area. The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of the ceiling shall not be more than 24 ft (7.3 m) above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from the compartmentsloped portion of the ceiling shall be above all openings from the compartment containing the sloped ceiling into any communicating spaces.Sprinklers installed on smooth sloped ceilings up to a maximum slope of 8/12 will adequately provide the prescribed level of safety if calculated using the Listed flows of the residential flat

Company Confidential 64

provide the prescribed level of safety if calculated using the Listed flows of the residential flat (up to 2/12 slope) sprinklers. 

Page 65: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – Discharge Criteria

(5) A sloped ceiling with beams of any depth with sidewall or pendent

Chapter 7 Discharge Criteria(Sprinklers Under Sloped Ceilings)

sprinklers in each pocket formed by the beams. The compartment containing the sloped, beamed ceiling shall be a maximum of 600 ft2 (55 m2) in area. The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of th ili h ll t b th 24 ft (7 3 ) b th flthe ceiling shall not be more than 24 ft (7.3 m) above the floor.7.1.1.3.2 For situations not meeting one of the conditions in 7.1.1.3.1, residential sprinklers listed for use in specific ceiling configurations shall be permitted to be used in accordance with their listing.7.1.1.3.3* For situations not meeting one of the conditions in 7.1.1.3.1 and 7.1.1.3.2, the number of sprinklers in the design area shall be determined in consultation with the authority having jurisdiction as appropriate for the conditions.If the ceiling configuration doesn’t meet one of those described the manufacturer and/or the 

Company Confidential 65

AHJ must be consulted for a resolution. 

Page 66: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – Discharge CriteriaChapter 7 Discharge Criteria(Sprinklers in Design Area)

7.5 Combustible Concealed Spaces. Where unsprinklered combustible concealed spaces are present in a building, the design area shall not be required to be increased to 3000 ft2 (279m2) or any other value due to the existence of the unsprinklered concealed spaces, regardless of the type of sprinklers used and whether the area is inside or outside of a dwelling unit.

Even when there are unsprinklered combustible concealed spaces in a building, the design 

Company Confidential 66

area does NOT have to be increased as it does in NFPA 13.

Page 67: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 8CHAPTER 8 –– Plans & CalculationsPlans & CalculationsCHAPTER 8 CHAPTER 8 Plans & CalculationsPlans & Calculations

Changes include:

Typical floor plans allowed

Full height cross section clarifiedg

Sprinkler characteristics clarified

Company Confidential 67

There were no major changes in chapter 8.

Page 68: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 9CHAPTER 9 –– Water SupplyWater SupplyCHAPTER 9 CHAPTER 9 Water SupplyWater Supply

Changes include:

Sources clarified

Tanks per NFPA 22p

Domestic demand addressed

Company Confidential 68

There were no major changes in chapter 9.

Page 69: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 10CHAPTER 10 –– System AcceptanceSystem AcceptanceCHAPTER 10 CHAPTER 10 System AcceptanceSystem Acceptance

Changes include:

Test Certificate added

Company Confidential 69

There were no major changes in chapter 10.

Page 70: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

CHAPTER 11CHAPTER 11 –– Care & MaintenanceCare & MaintenanceCHAPTER 11 CHAPTER 11 Care & MaintenanceCare & Maintenance

Changes include:

Spare sprinklers correlated

List of sprinklers p

Common spare sprinkler cabinet

Changes in chapter 11 include clarification on the number, a list, and the location of spare 

Company Confidential 70

sprinklers.

Page 71: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

NFPA® 13DNFPA® 13DNFPA® 13DNFPA® 13DStandard for the Installation of Standard for the Installation of S i kl S t i OS i kl S t i O ddSprinkler Systems in OneSprinkler Systems in One-- and and TwoTwo--Family Dwellings and Family Dwellings and Manufactured HomesManufactured Homes

Major Changes

Company Confidential 71

Page 72: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

The 2013The 2013 Edition

Company Confidential 72

Page 73: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 1Chapter 1 -- AdministrationAdministrationChapter 1 Chapter 1 AdministrationAdministration

Changes include:

New statement on water mist systems

Reorganized section on equivalency

Company Confidential 73

NFPA 13D includes the same statement made in NFPA 13 and 13R on water mist systems

Page 74: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3Chapter 3 -- DefinitionsDefinitionsChapter 3 Chapter 3 DefinitionsDefinitions

Changes include:

Premixed Antifreeze Solution (new)

Shadow Area (new)

Antifreeze Sprinkler System

Multipurpose Piping Sprinkler System (new)

P i P S i kl S t ( )Passive Purge Sprinkler System (new)

Stand-Alone Sprinkler System (new)

Definitions were revised and several new added, primarily addressing antifreeze and different 

Company Confidential 74

residential system types as used only in NFPA 13D.

Page 75: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Multipurpose Piping Sprinkler System)

3.3.11.3* Multipurpose Piping Sprinkler System. A piping system p y p p g yintended to serve both domestic needs in excess of a single fixture and fire protection needs from one common piping system throughout the dwelling unit(s).

This new language will clarify that a multipurpose system is one system throughout the 

Company Confidential75

dwelling unit that feeds both fire protection and domestic fixtures. 

Page 76: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Passive Purge Sprinkler System)

3.3.11.5* Passive Purge Sprinkler System. A type of sprinkler system that i l t il t i dditi t th fi i klserves a single toilet in addition to the fire sprinklers.

A.3.3.11.5 Passive Purge Sprinkler System. The domestic plumbing fixture should be on a remote portion of the system or the system should be designed

l th t t th h j it f th t h thas a loop so that water moves through a majority of the system when the fixture is used. This type of system is also called a “flow through system” in much of North America.

Company Confidential76

This type of system is also called a “flow through system” in much of North America.

Page 77: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 3 – DefinitionsChapter 3 Definitions(Stand-Alone Sprinkler System)

3.3.11.9* Stand-Alone Sprinkler System. A sprinkler system where the b d i i l fi i klaboveground piping serves only fire sprinklers.

A.3.3.11.9 Stand-Alone Sprinkler System. Underground piping is permitted to serve domestic use as well as sprinkler system use, but once the split is made between systems, the piping serving fire sprinklers only serves the fire sprinklers.

Company Confidential77

Standalone is a commonly used term and this new definition will provide a specific meaning.

Page 78: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 4Chapter 4 –– General RequirementsGeneral RequirementsChapter 4 Chapter 4 General RequirementsGeneral Requirements

Changes include:

Some requirements relocated

Some of the requirements of chapter 4 in the 2010 edition were relocated to some of the new 

Company Confidential

chapters in the 2013 edition.

Page 79: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 5Chapter 5 –– System ComponentsSystem ComponentsChapter 5 Chapter 5 System ComponentsSystem Components

Changes include:

Spare sprinklers not required

Lower sprinkler pressure ratingsp p g

Special piping allowances

Pressure reliefPressure relief

Special fitting allowances

Most of the changes are related to lower pressures being allowed for the materials and 

Company Confidential

components being installed in certain systems.

Page 80: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 5 – System Components(Sprinkler Pressure Rating)

Chapter 5 System Components

5.2.1 Listed residential sprinklers installed in systems complying with 5.2.2.3, 5.2.2.4, 5.2.5.3, or 5.2.5.4 shall be permitted to have a minimum pressure rating of 130 psi (8.9 bar).rating of 130 psi (8.9 bar).

Sprinklers listed with a lower pressure rating can used in certain  types of residential piping 

Company Confidential

systems.

Page 81: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 5 – System Components(Residential Sprinkler Piping)

Chapter 5 System Components

5.2.2.2* Pipe used in sprinkler systems other than those addressed in 5.2.2.3 or 5.2.2.4 shall be designed to withstand a working pressure of not lessdesigned to withstand a working pressure of not less than 175 psi (12.1 bar).5.2.2.3 Nonmetallic pipe used in multipurpose piping systems and passive purge systems not equippedsystems and passive purge systems not equipped with a fire department connection shall be designed to withstand a working pressure of not less than 130 psi (8.9 bar) at 120 F (49 C).( ) ( )

Nonmetallic piping with lower pressure ratings than normally used in NFPA 13 and 13R 

Company Confidential

systems are allowed in NFPA 13D

Page 82: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 5 – System Components(Residential Sprinkler Piping)

Chapter 5 System Components

5.2.2.4 Nonmetallic pipe used in wet pipe sprinkler systems not equipped with a fire department connection and provided with a pressure-reducing valve set no higher than 80 psi (5.5 bar) shall be designed to withstand a workingno higher than 80 psi (5.5 bar) shall be designed to withstand a working pressure of not less than 130 psi (8.9 bar) at 120 F (49 C) and 100 psi (6.9 bar) at 180 F (82.2 C).

The use of a pressure reducing valve with a setting of 80 psi, provides a level of assurance 

Company Confidential

that the pressure rating of the pipe and fittings will not be exceeded. 

Page 83: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 5 – System Components(Residential Sprinkler Piping)

Chapter 5 System Components

5.2.2.4.1 If the maximum static pressure from the water supply is less than or equal to 80 psi (5.5 bar), pipe designed to withstand a working pressure of not less than 130 psi (8.9 bar) at 120 F (49 C) and 100 psi (6.9 bar) at 180 Fless than 130 psi (8.9 bar) at 120 F (49 C) and 100 psi (6.9 bar) at 180 F (82.2 C) shall be permitted to be used without a pressure-reducing valve.5.2.2.4.2 If a pressure-reducing valve is used to comply with 5.2.2.4, an automatic means of pressure relief shall be installed on the sprinkler systemautomatic means of pressure relief shall be installed on the sprinkler system side of the pressure-reducing valve.

For situations where the water supply is not going to reach 80 psi, such as a water supply off a pump and tank for the sprinkler system where the churn pressure for the pump is less than 

Company Confidential

80 psi, there is no need for the pressure reducing valve.

Page 84: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 6 – Water SupplyChapter 6 Water Supply

Changes include:

Residential pumps

Company Confidential

The requirements for pumps and tanks were clarified.

Page 85: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 7 – InstallationChapter 7 Installation

Changes include:

Backflow assembly shut-off valve

Drain requirement and sizeq

Test connections for water flow alarms and PRVs

QR sprinklers in saunasQR sprinklers in saunas

Company Confidential

Although some of these changes are significant, we aren’t considering them major changes

Page 86: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 8 – Sprinkler Position and L tiLocationChanges include:

A new chapter title

Residential horizontal sidewall sprinkler placementp p

Sprinkler and obstructions rules for closets

Shadow area rule and examplesShadow area rule and examples

Exposed dry sprinkler barrel lengths

Fuel-fired equipmentFuel fired equipment

Ceiling pocket criteriaMany of the requirements and allowances are the same or similar to those in NFPA 13R 

Company Confidential

including the small closet rule and slightly different shadow area allowances. 

Page 87: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 9 – Protection from FreezingChapter 9 Protection from Freezing

Changes include:

New chapter

Wet system required above 40 Fy q

Freeze protection required below 40 F

Methods of freeze protection describedMethods of freeze protection described

Antifreeze criteria

Dry Pipe and Preaction System criteriaDry Pipe and Preaction System criteria

NFPA 13D is the only document to allow the installation of new antifreeze systems, using 

Company Confidential

currently available solutions in limited areas of systems

Page 88: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 10 – Discharge and Hydraulic C l l tiCalculationsChanges include:

New chapter

Number of design sprinklers – including slope ceiling criteriag p g p g

Acceptable piping configurations

Pipe sizing criteria – prescriptive and hydraulic calc methodsPipe sizing criteria prescriptive and hydraulic calc methods

The sloped ceiling criteria is the same as we reviewed in NFPA 13R, except that a maximum of 

Company Confidential

two sprinklers is to be flowed instead of four. 

Page 89: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 11 – System AcceptanceChapter 11 System Acceptance

Changes include:

New Chapter

Acceptance testsp

Pump tests

Hydrostatic testHydrostatic test

Operational tests

Acceptance test criteria that the installer must perform, including a hydrostatic test, a pump test when a pump is installed, and operational tests for specific components and system 

Company Confidential

types. 

Page 90: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Chapter 12 – Inspection, Testing, and M i tMaintenanceChanges include:

New chapter

Installer requirementsq

Inspections, tests, and maintenance requirements

Painted sprinklersPainted sprinklers

Freeze protection

Antifreeze system maintenance

There are many “shall” statements in this new chapter including ones for periodic system inspections and tests, system maintenance, painted sprinklers, maintaining proper 

Antifreeze system maintenance

Company Confidential

temperature, and antifreeze solution testing and maintenance.  

Page 91: LFTL - Major Changes in the 2013 Editions of NFPA 13 13R and 13D

Questions?Questions?

Terry Victor,

Questions?Questions?

e y cto ,National Manager of Sprinkler Business Processes at SimplexGrinnell.Tel: 410-401-2245 / Mobile: 443-286-4038705 Digital Drive, Suite N / Linthicum, MD 21090 / USA705 Digital Drive, Suite N / Linthicum, MD 21090 / USA

[email protected] / www.simplexgrinnell.com

Matt Klaus,,Senior Fire Protection Engineer for the National Fire Protection Association (NFPA).

Company Confidential 91