Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
IL01222027E
Effective Date 11/07
1
Instruction Leaflet for Series G L - Frame Motor Operator
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.
CONTENTS: Motor operator 1x Mounting screws (100 mm) 2x Mounting screws (35 mm) 2x Mounting screws (14 mm) 2x
WARNING
Page 2 IL01222027E
Effective Date 11/07
2
Remove existing two screws from primary cover of breaker.
3
Assemble support onto the breaker with four mounting screws supplied. Torque to 0.44 to 0.6 N.m or 4 to 5 in. lb.
4
• Turn breaker to the “OFF” position first. • Line up breaker handle and molded trigger of
motor operator, and position motor operator on the breaker.
5
Mount motor operator to breaker using mounting screws. Torque to 0.44 to 0.6 N.m or 4 to 5 in. lb.
Support
Molded Trigger
Mounting Screws (14 mm length)
Breaker Handle
Mounting Screws (35 mm length)
Mounting Screws (100 mm length)
Page 3 IL01222027E
Effective Date 11/07
6
Manual Operations • Move the slide knob to the MANUAL position to expose the manual operating shaft located under
the slide knob. The control power supply is cut off automatically. • Insert the operating key into shaft slot. Turn the key clockwise to verify the breaker can be closed
and opened. • Leave breaker in the ON position. Press the manual PUSH-TO-TRIP button on the breaker to trip
the breaker. Check that the display indicates the TRIP position. • Turn the operating key clockwise (approximately 180°) again. This should reset the breaker. • Status window indicates Green / OFF, Red / ON and White / Tripped. • Always remove the operating key and move the slide knob to the AUTO position before operating
electrically.
Turn the key
(Clockwise only)
Slide knob
Status
Indication
PUSH-TO TRIP Button
Opetating key
Page 4 IL01222027E
Effective Date 11/07
7
Motor Operator Wire Connection Diagram
Motor Operator Electrical Data
Voltage Frequency Inrush Current
208-240 VAC 110-127 VAC
50/60 Hz
220-250 VDC 110-125 VDC
DC 2 A
24 VDC DC 6 A 48 VDC DC 4 A
1) A minimum 300VA power source is recommended. 2) Maximum rate of operation: 2 operations per minute.
208-240VAC/220-250VDC Application
24VDC Application
110-127VAC/110-125VDC Application
48VDC Application
Page 5 IL01222027E
Effective Date 11/07
9
LOCK-OFF Move slide knob to AUTO position. Pull out the Lock-Off lever when breaker is in OFF position, insert one to three padlock shackles up to 6mm (.25 inch) in diameter. CAUTION The motor operator cannot be locked off while it is in the ON position.
8
Electrical Operation • Make sure the slide knob is located in the AUTO position. • Operating the OFF remote control switch will cause the breaker to go to its OFF position. • Operating the ON remote control switch will cause the breaker to go to its ON position. • Press the manual PUSH-TO-TRIP button on the breaker to verify that the breaker moves to the trip
position. Operating the OFF remote control switch again will reset the breaker. • Status window indicates Green / OFF, Red / ON and White / Tripped. • Always remove the operating key and move the slide knob to the AUTO position before operating
electrically.
Lock-Off Lever
Page 6 IL01222027E
Effective Date 11/07
Page 7 IL01222027E
Effective Date 11/07
10 Motor Operator Outline Dimensions – mm / [inch]
Page 8 IL01222027E
Effective Date 11/07
Printed in TQC