Power Protection for Business Critical Continuity
Liebert GXT-MT +
Trouble is Coming Down The Line And You Must Be Prepared
Every operation in your business depends upon the instant, around-the clock availability of computers, servers and other electronic systems. If they aren’t working, neither is your company. Every piece of this equipment your company possesses is subject to the whims of the electricity that powers it.
The first step in taking control of this situation is to understand the threats to your system reliability — and exactly what you can
do about them.
The Liebert GXT-MT + True Online Double Conversion UPS With Extended Runtime Capabilities
Liebert GXT-MT + features a comprehensive specification, satisfies safety criteria and electromagnetic compatibility standards, and offers intelligent monitoring and network management functions.
Liebert GXT-MT + satisfies your requirements for high reliability and high availability of the AC
power supply.
Liebert GXT-MT + is available in a compact Tower configuration making it easily deployed in an office or a light industrial application.
Liebert GXT-MT + long run model (L) deploys adaptive battery architecture to maximise your valuable rack space utilisation. Application specific battery configuration and placement ensures optimal performance.
NOTE:- Liebert GXT-MT + standard model is provided complete with internal battery.
Liebert GXTL-MT + (long back up model) application specific battery and cabinet available through your local Emerson
Network Power representative.
Applications
Small Size Data Center Telecommunication, VoIP Small Office Network Data Warehouses Medical Diagnostics Process Automation Equipments
Features
0.8 o/p p.f with LCD Display Option Extended Runtime Capabilities Flexible (Site Specific) Battery Configuration Compact Tower design. Generator Compatible Class B Electromagnetic interference (EMC) compatible Ultra wide input voltage range High capacity Battery Charger for GXTL High input power factor & low THDi
Liebert GXT - MT +
True Online Double Conversion
Flexible Configuration
Extended Run Time ready facilitated through a simple process of building up additional battery resources.
Multiple AC output interfaces via IEC standard sockets
Convenient maintenance
Fault type is clearly displayed for fast troubleshooting.
LCD display provides maximum operational convenience when managing the UPS.
Intelligent Management functions
Stronger Battery charger on the GXT L model for quick recharge
Remote Monitoring is available through RS232, and optional via dry contacts and SNMP. The monitoring option software supports TCP/IP with event log and analysis function.
Self-diagnosis and protection enable the auto shutdown of the client terminal or server under abnormal mains supply or when battery is over discharged.
True On-Line Double Conversion
Technology: When “Adequate” protection is not enough
Technical Specifications Model 1 kVA 2 kVA 3 kVA
OUTPUT PARAMETERS
Capacity 1kVA / 800W 2kVA / 1600W 3kVA / 2400W
Power Factor 0.8 0.8 0.8
Configuration 1 phase, L-N = PE 1 phase, L-N = PE 1 phase, L-N = PE
Nominal Voltage 220 / 230 / 240 Vac 220 / 230 / 240 Vac 220 / 230 / 240 Vac
Voltage Regulation + / - 3% + / - 3% + / - 3%
Voltage THD <=3% - Linear Load <=6% - Non Linear load
<=4% - Linear Load <=7% - Non Linear load
<=4% - Linear Load <=7% - Non Linear load
Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Frequency Regulation - Free Run (Unsynchronised with bypass)
+ / - 0.5 Hz + / - 0.5 Hz + / - 0.5 Hz
Frequency Regulation (Synchronised with bypass)
47.5 to 52.5 HZ / 57.5 to 62.5 HZ 47.5 to 52.5 HZ / 57.5 to 62.5 HZ 47.5 to 52.5 HZ / 57.5 to 62.5 HZ
Slew Rate 1 Hz per second maximum 1 Hz per second maximum 1 Hz per second maximum
Creast Factor 3:1 max. 3:1 max. 3:1 max.
Transient response at 100% step load + / - 6% On line mode; + / - 6% On line mode; + / - 6% On line mode;
Recovery time <150ms <150ms <150ms
Over load capacity 110% - 130% - 12 sec; >130 - 1.5 sec 110% - 130% - 12 sec; >130 - 1.5 sec 110% - 130% - 12 sec; >130 - 1.5 sec
AC - AC Efficiency 88% R-Load, 87% RCD - Load 88% R-Load, 87% RCD - Load 88% R-Load, 87% RCD - Load
Transfer time - Mains to battery 0 millisec 0 millisec 0 millisec
Transfer time - Inverter to bypass - Synchronisation mode
4 msec 4 msec 4 msec
INPUT PARAMETERS
Configuration 1 phase, L-N + PE 1 phase, L-N + PE 1 phase, L-N + PE
Nominal Voltage 230 Vac 230 Vac 230 Vac
Voltage range 160V to 300V at 100% Load, At 60% Load 110V to 300 Vac
160V to 300V at 100% Load, At 60% Load 110V to 300 Vac
160V to 300V at 100% Load, At 60% Load 110V to 300 Vac
Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Frequency range - Hz 40 - 70 Hz 40 - 70 Hz 40 - 70 Hz
Power Factor >=0.95 >=0.95 >=0.95
Current Distortion (I-THD) 12% linear, 13% nonlinear 12% linear, 13% nonlinear 12% linear, 13% nonlinear
BYPASS
Voltage 220 / 230 / 240 Vac 220 / 230 / 240 Vac 220 / 230 / 240 Vac
198V - 242V For 220V 198V - 242V For 220V 198V - 242V For 220V
207V - 253V For 230V 207V - 253V For 230V 207V - 253V For 230V
216V - 264V For 240V 216V - 264V For 240V 216V - 264V For 240V
Frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Frequency Range 47.5 to 52.5 Hz / 57.5 to 62.5 Hz 47.5 to 52.5 Hz / 57.5 to 62.5 Hz 47.5 to 52.5 Hz / 57.5 to 62.5 Hz
Technical Specifications Model 1 kVA 2 kVA 3 kVA
BATTERY CHARGER
Nominal Voltage - Float 41 Vdc 108 Vdc 82.1 Vdc
Maximum charging current - STD. / LB. 1A - STD and 4 / 8 A - LB 1A - STD and 4 / 8 A - LB 1A - STD and 4 / 8 A - LB
Better Connector 5 pin Wago 770-750 5 pin Wago 770-750 5 pin Wago 770-750
BATTERY PARAMETERS
Type SMF SMF SMF
No. of battery blocks 3 8 8
Battery Voltage 36 VDC 96 V 96V
Maximum Back up time at full load STD. 7 minutes / 7 AH STD. 6.5 minutes / 7 AH STD. 5 minutes / 7 AH
ENVIRONMENTAL PARAMETERS
Operating temperature 0 to 40 deg. centigrade 0 to 40 deg. centigrade 0 to 40 deg. centigrade
Storage temperature -20 to 50 deg. centigrade -20 to 50 deg. centigrade -20 to 50 deg. centigrade
Relative Humidity 90% RH 90% RH 90% RH
Altitude
Noise level <45db <45db <45db
MECHANICAL PARAMETERS
Height X Width X Depth (MM) 220 X 145 X 388.5 318 X 190 X 387 318 X 190 X 387
Weight 13 kg. - STD., 7 kg. - LB 26 kg. - STD., 13 kg. - LB 28 kg. - STD., 13 kg. - LB
Ventilation Forced - Air cooled Forced - Air cooled Forced - Air cooled
Cable Entry Backside Backside Backside
Colour / Panel finish RAL 7016 dark grey RAL 7016 dark grey RAL 7016 dark grey
Protection IP20 IP20 IP20
Communication Port RS232, USB RS232, USB RS232, USB
EPO Yes Yes Yes
MONITORING SOFTWARE SNMP, dry contact card, UPSilon 2000
SNMP, dry contact card, UPSilon 2000
SNMP, dry contact card, UPSilon 2000
STANDARDS
EMI EN 62040-2: 2006 EN 62040-2: 2006 EN 62040-2: 2006
SAFETY EN 62040-1-1: 2003 EN 62040-1-1: 2003 EN 62040-1-1: 2003
PERFORMANCE (technical feature) IEC / EN 62040 - 3 IEC / EN 62040 - 3 IEC / EN 62040 - 3
Transportation IEC 600068-2-32 - DROP TEST IEC 600068-2-32 - DROP TEST IEC 600068-2-32 - DROP TEST
IEC 60068-2-64 - VIBRATION TEST IEC 60068-2-64 - VIBRATION TEST IEC 60068-2-64 - VIBRATION TEST
IEC 60068-2-27 - SHOCK TEST IEC 60068-2-27 - SHOCK TEST IEC 60068-2-27 - SHOCK TEST
Miscellaneous EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD
EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD
EN 50272 - VOLUME / AIR FLOW / DEGASSING STANDARD
CE MARK CE MARK CE MARK
Country Office
Emerson Network Power (India) Private Ltd.
Plot No. C-20, Road No. 19, Wagle Estate,
Thane (w), Maharashtra - 400 604. India.
Tel.: 91-22-67208000
Fax: 91-22-25828358
Toll Free No 18002096070
Email: [email protected]
Voice of Customers UPS Awards 2004-05 for Product Line
& Customer Service Awards in IT, Telecom, Large Enterprise & Hospitals and
Customer Service Leadership Award in BFSI
2007 R
Best IT Hardware Company Maharashtra IT Award 2006-07
www.emersonnetworkpower.co.in
Emerson Network Power.
The global leader in enabling Business-Critical Continuit yTM.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection While every precaution has been taken to ensure accuracy and completeness in this brochure, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions.
For disposal of Batteries Please visit the below link: http://www.cpcb.nic.in/divisionsofheadoffice/hwmd/lead.pdf
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. © 2009 Emerson Electric Co.