LIFT APPLICATION GUIDELINES

ACCESSOR I – MODEL VMW-09 ACCESSOR II – MODEL VMX-07

Page 2: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 2

REV F – 11/11

TABLE OF CONTENTS

GENERAL INFORMATION ....................................................................................................... 3

PURPOSE ............................................................................................................................. 3 PRODUCT OVERVIEW ......................................................................................................... 3 SUITABLE LIFT APPLICATIONS........................................................................................... 3

APPLICATION GUIDELINES.................................................................................................... 4

LIFT MODEL SELECTION..................................................................................................... 4 PLATFORM SIZE AND DOOR OPENING LIMITATIONS ...................................................... 4 ACCESSOR SPECIFICATIONS ............................................................................................ 5 COMPONENTS SUPPLIED BY LIFT-U®................................................................................ 5 REGULATORY REQUIREMENTS......................................................................................... 6

RESPONSIBILITY OF OTHERS ............................................................................................... 7

SCOPE OF WORK BY OTHERS ........................................................................................... 7 INTERFACE REQUIREMENTS ............................................................................................. 7 REGULATORY COMPLIANCE BY OTHERS......................................................................... 8

Page 3: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 3

REV F – 11/11

GENERAL INFORMATION PURPOSE LIFT-U® has prepared this document for the purpose of providing building owners and owner representatives such as architects, contractors, and installers with information specific to design planning, special provisions, installation considerations, and regulatory compliance responsibility relevant to the LIFT-U® Accessor I Model VMW and Accessor II Model VMX Vertical Platform Lifts, hereinafter referred to as VMW and VMX respectively. The information presented in this document is fairly generic for VMW and VMX lift applications and not intended to address every detail or special conditions that may be encountered on a project. PRODUCT OVERVIEW By way of introduction, the VMW and VMX lift models are not conventional Vertical Platform Lifts comprised of a car with platform mounted sidewalls, but rather the VMW and VMX are comprised of a platform that raises and lowers within the confines of stationary millwork walls and the closed entrance/exit doors hingedly attached thereto. Subsequently, the lift layout is customized for each application. SUITABLE LIFT APPLICATIONS The VMW and VMX Vertical Platform Lifts are specifically designed for use in courtrooms to facilitate mobility-impaired judges, witnesses, clerks, and jurors, but are also well suited for elevated stage rostrums such as church pulpits and meeting chamber podiums to provide accessibility to mobility-impaired clergy and public speakers.

Page 4: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 4

REV F – 11/11

APPLICATION GUIDELINES LIFT MODEL SELECTION Accessor I Model VMW

1. The four (4) screw jack column design permits the lift to be installed directly on the lower landing floor without the need for a pit.

2. The lift screw columns, base frame, and drive train are encased in millwork walls surrounding the lift platform, thus requiring the coordination of other trades.

3. The drive motor and electronics are located under the upper landing. 4. Refer to exemplar Lift Configuration drawing 910-0091 which is included in this

document. Accessor II Model VMX

1. The lever-screw design requires the lift to be installed in a pit or sub-floor at least 6 inches below the lower landing floor; LIFT-U recommends 7 inches.

2. The lift drive mechanism, motor, and electronics are oriented under the upper landing, thus minimizing the influence on millwork walls surrounding the lift platform.

3. Refer to exemplar Lift Configuration drawing 910-0092 which is included in this document.

For graphic illustration of these design differences and the variables to consider when planning for a particular lift application, as well as LIFT-U’s recommended interface design principles for the lift and optional equipment, refer to exemplar Lift Configuration drawings 910-0091 and 910-0092 along with the following drawings included near the back portion of this document:

1. 910-0026, VMW Lift / Millwork Interface 2. 910-0042, Roll-up Barrier / Millwork Interface 3. 910-0054, Step Module / Millwork Interface 4. 910-0055, Door Set-up Alternatives 5. 910-0056, Strike Latch / Millwork Interface 6. 910-0085, Operable Step / Millwork Interface 7. 910-0088, Roll-Up Barrier Overview 8. 910-0089, Retractable Step Overview 9. 910-0090, Operable Step Overview 10. 910-0093, Electromagnetic Door Holder / Millwork Interface

To further facilitate the architectural design process, design files such as 2D CAD and Revit 3D RFA models are available online at Autodesk® Seek; http://seek.autodesk.com/. Simply type LIFT-U in the search field; then on LIFT-U’s product page select either Accessor I or Accessor II. There you will find several design files as well as additional product information that can be downloaded. The design files may be edited to suit each lift application. PLATFORM SIZE AND DOOR OPENING LIMITATIONS The advantage of using the VMW or VMX is that the platform size and layout can be customized for each application, as well as orientation and placement of the entrance/exit doors.

Page 5: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 5

REV F – 11/11

Be advised, there are certain limitations to be aware of with respect to minimum and maximum dimensions. The minimum platform size and minimum door opening are contingent upon door orientation, i.e., whether the lift provides straight through access or involves a 90 degree turn for the wheelchair-bound passenger. For illustration of available orientations and preferred minimum dimensions refer to template layout drawings 910-0064 thru 910-0071 for the VMW and 910-0072 thru 910-0078 for the VMX near the back portion of this document. Further, the maximum platform size is preferably no greater than 25 sq. ft. However, certain applications may be cause for exception and must be evaluated on a case-by case basis. The best method to prevent exceeding the 25 sq. ft. maximum platform size, particularly for courtroom lift applications where the witness stand or clerk bench footprint may be larger than 25 sq. ft., is to include the LIFT-U® Roll-up Barrier in the witness/clerk landing. Since space in the interior of the witness stand or clerk bench is typically too restrictive for a hinged self-closing door, the LIFT-U® Roll-up Barrier is a practical alternative. The Roll-up Barrier is also practical for non-courtroom lift applications when door swing is an issue. The Roll-up Barrier is illustrated in context on drawing 910-0088, Roll-up Barrier Overview. Additional details are shown on drawing 910-0042, titled Roll-up Barrier/Millwork Interface. Both drawings are included near the back portion of this document. ACCESSOR SPECIFICATIONS

1. Platform dimensions vary for each application. 2. Lift capacity (maximum operating load):

• 750 lbs for platforms less than or equal to 18 ft2.

• 1050 lbs for platforms greater than 18 ft2. 3. Speed is 10 ft./min. maximum. 4. Maximum vertical travel is limited to 24 inches. 5. Manual lowering device is included. 6. Factory finish for all steel framework is black powder-coat. 7. Power source requirements are 115 VAC, 15 amp, 3 wire, single-phase service.

COMPONENTS SUPPLIED BY LIFT-U® The lift package as delivered includes the following:

1. Lift Assembly. 2. Threshold Ramp (if applicable). 3. Electrical Control Panel with Lockable Disconnect. 4. Operator Control Stations (call buttons). 5. Electric Strike Latches. 6. Spring-loaded Latch Bolts. 7. Anchor Bolts. 8. Roll-up Barrier Module (if applicable). 9. Retractable Step Module (if applicable). 10. Hinged Riser – VMW (if applicable). 11. Fixed Riser – VMX (if applicable). 12. Battery Back-up / UPS (if applicable). 13. Operable Step (if applicable). 14. Electromagnetic Door Holder (if applicable)

Page 6: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 6

REV F – 11/11

REGULATORY REQUIREMENTS Vertical Platform Lift design, construction, installation, operation, inspection, testing, maintenance, and repair is specified in Standards developed and published by The American Society of Mechanical Engineers (ASME), entitled ASME A18.1 Safety Standard For Platform Lifts And Stairway Chairlifts. The ASME Standard is intended to serve as the basis for state, municipal, and other jurisdictional authorities in drafting regulations governing Vertical Platform Lifts. With respect to A18.1 effectivity in each jurisdiction, the edition date in effect established by the local jurisdiction may vary; therefore, the local regulations from the authority having jurisdiction (AHJ) must be reviewed prior to each lift installation. For ASME A18.1 references sited in this document, the latest 2008 edition is used. Regarding ASME A18.1, Section 2 categories: 1) Refer to Section 2.1.4 for courtroom lift applications; and 2) For non-courtroom lift applications the Accessor can be characterized in part as having a “Runway Enclosure Provided”, reference para. 2.1.1. Due to architecturally desired features, certain VMW and VMX applications may not comply “to the letter” with all the requirements specified in the A18.1 Standard. In those cases, a variance must be requested for certain specification deviations from the authority having jurisdiction. Typically a variance application for the VMW and VMX will address items such as platform size, stationary millwork walls, millwork wall height and door height, and intermediate landing guard (if applicable). If a variance is necessary LIFT-U® will, on behalf of the building owner, facilitate expediting the variance application. The basis for a variance request is expressly permitted by A18.1 para. 1.2, which states: “The purpose of this Standard is to provide for the safety of life and limb, and to promote the public welfare. The provisions of this Standard are not intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety to those prescribed by this Standard provided that there is technical documentation to demonstrate the equivalency of the system, method, or device. The specific requirements of this Standard shall be permitted to be modified by the authority having jurisdiction based upon technical documentation or physical performance verification to allow alternative arrangements that will assure safety equivalent to that which would be provided by conformance to the corresponding requirements of this Standard.” For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer to the section entitled, Regulatory Compliance by Others, on page 8 of this document.

Page 7: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 7

REV F – 11/11

RESPONSIBILITY OF OTHERS

SCOPE OF WORK BY OTHERS The design, materials, construction, and installation of the following items are the responsibility of others.

1. Lift support structure/foundation. 2. Site preparations, including main electrical power connection to lift power input. 3. Prior to installation, placement of lift must be defined. Chalk lines may be used to outline

exact lift location. 4. Building elements and millwork that encase the lift mechanism adjacent to and

surrounding the lift platform, including but not limited to structural framing and veneered panel finishes.

5. Doors, including self-closing spring hinges. 6. Installation of lift control panels (supplied by LIFT-U®). 7. Installation of door strike latches (supplied by LIFT-U®). 8. Illumination of lift area. 9. Platform floor covering material. 10. Removable step (if applicable).

INTERFACE REQUIREMENTS Space and structural provisions shall be provided in building elements and millwork to accommodate the lift assembly, motor, and electronics. As non-limiting examples, the following features shall be included:

1. Adequate clear space is required under the upper landing for the lift drive mechanism, motor, and electronics.

2. A service hatch is required in the upper landing floor approximate to the motor and electronics. The size of the service hatch shall be sufficient for access to the main power disconnect and to facilitate maintenance.

3. Cutout reliefs in the millwork are required for lift frame clearance and operational lift elements.

4. Interior millwork panels adjacent to the lift platform shall be smooth. 5. With respect to the VMW, the interior millwork panels are to be made removable to

facilitate lift maintenance. 6. Running clearance between platform edges and adjacent millwork surfaces shall be no

less than 0.375 inch nor more than 0.75 inch. Refer to applicable Lift Configuration drawing for layout, orientation, and controlling dimensions for each project.

Page 8: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 8

REV F – 11/11

REGULATORY COMPLIANCE BY OTHERS The ASME A18.1 specifies requirements for the design, construction, installation, operation, inspection, testing, maintenance, and repair for Vertical Platform Lifts. With respect to the VMW and VMX installation, while LIFT-U® is required to certify that the lift complies with the A18.1 Standard and any variance decisions granted by the AHJ, there are certain requirements associated with elements necessary for the installation of a complete lift system that are not provided by LIFT-U®, and therefore require the cooperation of other trades contracted by the building owner. Subsequently, these other trades are responsible for compliance with the A18.1 requirements related to their respective work. These elements are itemized in the Scope of Work by Others noted on page 7 of this document. LIFT-U® hereby advises the building owner, or owner’s designated representative, of the owner’s responsibility to communicate the applicable A18.1 requirements to the appropriate trades. To facilitate this effort, LIFT-U® has summarized below the A18.1 requirements that other trades involved with the lift installation must comply with - refer to the A18.1 Standard for complete text. Applicable to Courtroom Lift Installations 2.1.4.1 Upper Landing Entrance

• A door measuring at least 36 inches high shall guard the entrance. Refer to the Lift Configuration drawing and variance decision for allowable door/guard height deviation.

• Door shall be unperforated.

• Door shall be self-closing.

• Door shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation.

• Door shall be located not more than 3 inches from the platform sill. LIFT-U® recommends locating the door flush with the upper landing fascia.

2.1.4.4 Vertical Fascia

• A vertical fascia shall be provided from the upper landing sill and any intermediate landing sill to the lower landing and shall guard the full width of the platform.

• If openings are necessary in the fascia for operation, they shall reject a ball 0.5 inch in diameter.

• Fascia shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation.

• Clearance between the fascia and platform edge shall not be less than 0.375 inch nor more than 0.75 inch.

2.1.4.5 Lower Landing Entrance

• A door measuring at least 36 inches high shall guard the entrance. Refer to the Lift Configuration drawing and variance decision for allowable door/guard height deviation.

• Door shall be unperforated.

• Door shall be self-closing.

Page 9: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 9

REV F – 11/11

• Door shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation.

• Clearance between the door and platform edge shall not be less than 0.375 inch nor more than 0.75 inch.

2.1.4.6 Stationary Runway Guards [millwork sidewalls]

• Sides of the platform not used for entrance or exit shall be guarded by stationary millwork walls that extend to a height of at least 36 inches above the lower landing. Refer to the Lift Configuration drawing and variance decision for allowable wall height deviation.

• Millwork walls shall be unperforated.

• Openings necessary for lift operation shall reject a ball 0.5 inch in diameter.

• Clearance between stationary millwork walls and the platform edge shall not be less than 0.375 inch nor more than 0.75 inch.

2.1.4.7 Doors / Guards

• Doors shall be provided with a combination mechanical lock and electric contact. LIFT-U® furnishes the electric strike latches and associated wiring to interface with the lift control system, which are incorporated by other trades.

Applicable to Non-Courtroom Lift Installations 2.1.1.1 Runway Guards

• Millwork wall height shall extend from the lower landing to at least 42 inches above the uppermost landing. Refer to the Lift Configuration drawing and variance decision for allowable wall height deviations.

• Millwork walls shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation.

• Millwork wall interior surfaces on all sides facing the lift platform shall be smooth.

2.1.1.2 Upper Landing Entrance

• A door measuring at least 42 inches high shall guard the entrance. Refer to the Lift Configuration drawing and variance decision for allowable door/guard height deviation.

• Door shall be unperforated.

• Door shall be self-closing.

• Door surface facing the lift platform shall be smooth.

• Door shall be located not more than 3 inches from the platform sill. LIFT-U® recommends locating the door flush with the upper landing fascia.

2.1.1.3 Lower and Intermediate Landing Entrance

• The entrance opening shall be at least 79 inches high. A door shall guard the entire opening except for space necessary for operation. Space necessary for operation shall reject a 0.5 inch diameter ball. Refer to the Lift Configuration drawing and variance decision for allowable door/guard height deviation.

• Door shall be unperforated.

• Door shall be self-closing.

Page 10: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 10

REV F – 11/11

• Door surface facing the lift platform shall be smooth.

• Door shall be located 0.375 inch to 0.75 inch from the edge of the platform floor.

2.1.1.4 Doors

• Doors shall be provided with a combination mechanical lock and electric contact. LIFT-U® furnishes the electric strike latches and associated wiring to interface with the lift control system, which are incorporated by other trades.

• Doors shall be capable of withstanding 125 lbf applied on any 4 inch by 4 inch area without permanent deformation.

Applicable to Both Courtroom and Non-Courtroom Lift Installations 2.1.1.5 Protrusions

• No hardware shall project beyond the vertical line of travel of the platform. For witness stands that may include a desk or counter top positioned within the vertical line of travel of the platform, LIFT-U® recommends desk and counter tops either be mounted to the lift platform and thus move with the lift, or be hinge mounted to the millwork or removable to prevent a potential hazard to the passenger.

2.1.1.6 Platform Running Clearance

• The running clearance between the entrance and exit sides of the platform floor and the interior of the runway enclosure [millwork walls] shall not be less than 0.375 inch nor more than 0.75 inch.

2.1.5 Pipes in Runway Vicinity

• No piping is permitted in the runway [lift footprint]. 2.1.8 Structural Support

• The structure on which the equipment is installed shall be capable of safely supporting the loads imposed. LIFT-U® provides the building owner, or owner’s representative, with the appropriate load data.

2.1.9 Headroom Clearance

• Headroom clearance throughout the range of travel shall be not less than 79 inches as measured vertically from the platform floor. Refer to the Lift Configuration drawing for lift operational envelope dimensions.

2.2.4.2 Brackets, Fastenings, and Supports

• The guide-rail brackets, their fastenings and supports, such as building beams and walls, shall be capable of resisting the horizontal forces imposed by rated load with a total deflection to the point of support not in excess of 0.125 inch. [Related to millwork walls that encase the VMW screw columns].

2.2.7 Design and Strength of Brackets and Supports

• The building construction forming the supports for the guide rails, and the guide-rail brackets, shall be designed to safely withstand the application of the platform when

Page 11: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

LIFT-U®

Division of Hogan Mfg., Inc. VMW-09 / VMX-07 LIFT APPLICATION GUIDELINES

COPYRIGHT 2011– HOGAN MFG., INC. DOC 599-0006

ALL RIGHTS RESERVED 11

REV F – 11/11

stopping the platform and its rated load; and withstand the forces specified in para. 2.2.4.2 within the deflection limits specified. Where necessary, the building construction shall be reinforced to provide adequate support for the guide rails. [Related to millwork walls that encase the VMW screw columns].

2.3.6 Guiding Member Enclosures

• The guiding members shall be guarded to prevent accidental contact. Any openings necessary in guards for operation, they shall reject a ball 0.75 inch in diameter. [Related to millwork walls that encase the VMW screw columns].

2.5.8 Guarding

• All suspension means shall be guarded against accidental contact. Suspension means, which operate within a guide or track and travel at the same speed and in the same direction as the platform shall be considered suitably guarded. [Related to millwork walls that encase the VMW screw columns or VMX mechanism].

2.6.6 Illumination

2.6.6.1 At the threshold of the floor, with the landing door open, the minimum illumination shall be not less than 5 ftc (50 lx).

2.6.6.2 During operation, the minimum illumination on the floor and controls shall be not less than 5 ftc (50 lx).

2.6.6.3 An auxiliary illumination source to provide general illumination of not less then 0.2 ftc (2.2 lx) on the floor and controls shall be provided. The auxiliary system shall be automatically activated when normal illumination power fails and shall be capable of maintaining the above illumination intensity for a period of not less than 4 hr and shall use no fewer than two lamps of approximately equal wattage.

2.10.1 Operator Control Stations

• Controls shall be located between 48 inches maximum and 15 inches minimum above the platform floor or facility floor or ground level.

Page 12: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A DIVISION OF

REVISIONSHEET NO.DOCUMENT NO.

TITLE

LIFT-U

910-0026 C1 OF 4

VMW LIFT / MILLWORK INTERFACE

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

CUT RELIEF SLOT IN INTERIORPANEL TO ALLOW VERTICALTRAVEL OF PLATFORMCARRIAGE BRACKET

.50

TRAVEL +3"

CONTROL STATIONHT 42" - 48"

(LANDING HT +36"-42")

WALL HT TBD BYMILLWORK DESIGNER

DESIGN PRINCIPLES CAN BE APPLIED TO THE OTHER WALLS BORDERING THE LIFT.

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDED LIFT / MILLWORK INTERFACE.FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERALARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLEDBY OTHERS.

THE VMW LIFT MECHANISM (i.e., SCREW COLUMNS, BASE FRAME, AND DRIVE TRAIN) IS ENCASED IN MILLWORKWALLS SURROUNDING A LIFT PLATFORM THAT TRAVELS UP AND DOWN. SINCE THE MILLWORK IS FURNISHED ANDINSTALLED BY OTHERS THE INTERFACE OF THE MILLWORK TO THE LIFT IS CRITICAL TO A SUCCESSFUL INSTALL-ATION, WHEREIN THE MILLWORK WALL SYSTEM IS NOT ONLY STRUCTURALLY SOUND AND AESTHETCIALLYAPPEALING, BUT JUST AS IMPORTANT SPECIFIC PROVISIONS AND CLEARANCES TO ACCOMMODATE CERTAINLIFT ELEMENTS ARE ALSO INCLUDED IN THE MILLWORK TO ENSURE PROPER LIFT OPERATION AND SERVICABILITY.

ONLY A SMALL SEGMENT OF MILLWORK WALL AND ONE SCREW COLUMN IS SHOWN ON THIS DRAWING. THE SAME

WALL SEGMENT ELEVATION VIEW

LIFT PLATFORM

WALL SEGMENT PLAN VIEW

MILLWORK WALL

THRESHOLDRAMP

.50 NOMINAL PLATFORMRUNNING CLEARANCE

(.38 MIN / .75 MAX)

WITH INTERIOR PANEL REMOVEDENLARGED VIEW OF WALL SEGMENT

12" SHORTER COLUMN AVAILABLE)

AND MOUNTING DETAILS.FOR MORTISE DIMENSIONSREFER TO DRAWING 910-0056ELECTRIC STRIKE LATCH -

(SEE SHEETS 2-4 FOR SECTIONS AND DETAILS)

(TALL COLUMN SHOWN,

MILLWORK STRUCTURALFRAMING

LIFT SCREW COLUMN

C

AA

BB

C

C

D

D

LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE

A RELEASED CAL 6/21/2006

B REVISED STRIKE LATCH NOTE ON SHT 1 CAL 9/7/2007

C UPDATED MODEL PER CURRENT DESIGN BRB 9/21/2011

R E V I S I O N S

Page 13: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A DIVISION OF

REVISIONSHEET NO.DOCUMENT NO.

TITLE

LIFT-U

910-0026 C2 OF 4

VMW LIFT / MILLWORK INTERFACE

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

ELECTRICAL CABLES

PROVIDE OPENING IN STRINGER

SECTION A-A

BEARING FASTENERSAT SCREW COLUMN TO ACCESS

PROVIDE HOLES FOR ROUTING

DOOR JAM IS SHOWN CUT INTO INTERIORPANEL. JAM CONFIGURATION MAY VARYTO SUIT DOOR AND MILLWORK DESIGN.

E

SECTION B-B

TO SCREW COLUMN ANGLESINTERIOR PANEL TO BE FASTENED

EXTERIOR PANEL OR BLOCKINGMATERIAL MAY BE FASTENED TOSCREW COLUMN ANGLES

LIFT PLATFORM

1.25.50

F

G

SECTION C-C

PANELSOF MILLWORK FRAMING AND VENEERED

TO BASE FRAMENAILER MAY BE FASTENED

CABLES

SHEET METAL ANGLES ON SCREW JACKCOLUMNS FACILITATE THE ATTACHMENT

MILLWORK FINISH TREATMENTSUCH AS TOP CAP AND EXTERIORTRIM DETAILS TBD BY MILLWORKDESIGNER

PROVIDE HOLES FORROUTING ELECTRICAL

LIFT PLATFORM 11.30

MIN

.75

5.50

.50

.75

(TALL COLUMN)25.69

7.00

(SHORT COLUMN)13.69

C

SECTION D-D

CABLERACEWAY

LIFT BASEFRAME

FRAME STRINGERS

BRACKETPLATFORM CARRIAGE

INTERIOR SURFACES WITHIN THERANGE OF LIFT MOTION MUST BESMOOTH

C

Page 14: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A DIVISION OF

REVISIONSHEET NO.DOCUMENT NO.

TITLE

LIFT-U

910-0026 C3 OF 4

VMW LIFT / MILLWORK INTERFACE

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

DETAIL E

FRAME STRINGER

SCREW COLUMN ANGLES

SCREW COLUMN ANGLES

LIFT PLATFORM

COLUMNSCREW

1.25.50

5.50

5.75SCREW COLUMN

FRAME

NAILER

DETAIL F

LIFT BASE

FRAME STRINGER

CABLE RACEWAY

SCREW COLUMN ANGLES

DRIVE SHAFT

TBD BY MILLWORK DESIGNER

1.95

1.59 3.91

SHOWN - THK SUBJECT TO

SCREW COLUMN5.50

INTERIOR AND EXT PANEL THK -

PLATFORM EDGESCREW COLUMN TO

1.25

OVERALL WALL THK

PLATFORM RUNNING CLEARANCETO COMPLY WITH ALLOWABLE

SHOWN - .50 MIN / .88 MAX INTERIOR PANEL THK

MILLWORK DESIGNERSHOWN - THK TBD BY

EXT PANEL THK.75.75

7.00

1.125

DETAIL G

SCREW COLUMN ANGLES

FRAME STRINGER

Page 15: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A DIVISION OF

REVISIONSHEET NO.DOCUMENT NO.

TITLE

LIFT-U

910-0026 C4 OF 4

VMW LIFT / MILLWORK INTERFACE

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.PERSPECTIVE VIEW OF WALL SEGMENT

BRACKET

ADJACENT TO THE STRIKECUT RELIEF IN FRAMING

CABLESSTATIONS AND ROUTING

LATCH FOR WIRE CLEARANCE

GEARBOXES, AND DRIVE SHAFTS.OR REPLACEMENT OF SCREW JACKS,

STATIONCONTROLLEVEL 1

STATIONCONTROLPLATFORM

STRIKEELECTRIC

LEVEL SWITCHES AND ENABLE SERVICE

LATCH

12" SHORTER COLUMN AVAILABLE)

DRIVE SHAFT

(TALL COLUMN SHOWN,LIFT SCREW COLUMN

LIFT PLATFORM

REMOVABLE TO PROVIDE ACCESS TOTHE INTERIOR PANELS SHOULD BE MADE

CABLESELECTRICAL

PROVIDE OPENINGS FORMOUNTING CONTROL

MILLWORK STRUCTURALFRAMING

PLATFORM CARRIAGE

C

Page 16: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A

PLAN VIEW

WITNESS LANDING

JUDGE LANDING

LIFT PLATFORM

ROLL-UP BARRIERMODULE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDROLL-UP BARRIER / MILLWORK INTERFACE.

THE ROLL-UP BARRIER PORTAL WIDTH, VERTICAL GUIDES, AND EXTENDED BARRIER HEIGHTWILL VARY FOR EACH APPLICATION. THEREFORE, FOR EACH PROJECT APPLICATION REFERTO ITS CORRESPONDING LIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENTLAYOUT, LIFT ENVELOPE DIMENSIONS, AND ROLL-UP BARRIER MODULE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

PW = PORTAL WIDTH

C

C

B B

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

ROLL-UP BARRIER / MILLWORK INTERFACE

1 OF 3 B910-0042

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

DETAIL AFLOOR OPENING AND PREP TO

ACCOMMODATE ROLL-UP BARRIER MODULE

PW + 2.00

PW + 3.00

1.25 ROUTERx .12 DEEP2 - PLACES

1.50 ROUTERx .12 DEEP

26.25

.50

VARIES

LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE

A RELEASED CAL 7/7/2006

B UPDATED PER CURRENT DESIGN WAC 10/14/2011

R E V I S I O N S

Page 17: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

ROLL-UP BARRIER / MILLWORK INTERFACE

2 OF 3 B910-0042

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

DETAIL D

.50 1.25

.12 ROUTERDEPTH (TYP)

INSTALLATIONSHIM AT

4.50

DETAIL E

1.50

4.50

1.53FLNG

E

F

FASCIA

SECTION C-C

VERTICALGUIDE

6.00 MIN.

25.97

26.25

VARIES

VARIES

1.91.62

D

SECTION B-B

PW = PORTAL WIDTH

PW + 2.00

PW + 3.00

DETAIL F

INSTALL FLUSHWITH FASCIA

4.50

Page 18: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

ROLL-UP BARRIER MODULEINSTALLATION SEQUENCE

1) PAN INSTALLS FIRST. USE FLAT HEAD WOOD SCREW TO ATTACH PAN TO WITNESS FLOOR.

2) REMOVE COVER TO INSTALL FASTENERS THAT MATE THE ROLL-UP BARRIER MODULE TO PAN. RE-ASSEMBLE COVER.

3) SECURE VERTICAL GUIDES TO ADJACENT MILLWORK WALLS WITH FLAT HEAD WOOD SCREWS. SHIM GAP AS REQUIRED.

PERSPECTIVE VIEW

FLOOR COVERINGMATERIAL(BY OTHERS)

BARRIER VERTICAL GUIDESMAY BE DRESSED OUT WITHTRIM (BY OTHERS)

ROLL-UP BARRIERMODULE

ROLL-UP BARRIERPAN

ALL MILLWORK, INCLUDING STRUCTURALFRAMING AND VENEERED PANEL FINISHES,ARE BY OTHERS.

MILLWORK FLOOR AND FRAMING TOBE CONSTRUCTED TO SUPPORT ANDACCOMMODATE ROLL-UP BARRIERMODULE.

LIFT PLATFORM

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

ROLL-UP BARRIER / MILLWORK INTERFACE

3 OF 3 B910-0042

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

Page 19: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

PLAN VIEW

A A

C

C

B

B

PERSPECTIVE VIEW

PROVIDE ACCESS HATCH TO ENABLESERVICE OR REPLACEMENT OF STEPMODULE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDRETRACTABLE STEP MODULE / MILLWORK INTERFACE.

THE RETRACTABLE STEP MODULE HEIGHT AND WIDTH WILL VARY FOR EACHAPPLICATION. THEREFORE, FOR EACH PROJECT REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFTENVELOPE DIMENSIONS, AND STEP MODULE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT, ANDFLOOR JOIST FRAMING USED TO FASTEN AND SUPPORT THE STEP MODULE AREFURNISHED AND INSTALLED BY OTHERS. REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STEP MODULE / MILLWORK INTERFACE

1 OF 4 B910-0054

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE

A RELEASED CAL 8/28/2007

B UPDATED PER CURRENT STEP DESIGN BSA 9/20/2011

R E V I S I O N S

Page 20: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

D

BRACKET (IF APPLICABLE) SECTION A-A

STEP MODULEENCLOSURE

RETRACTABLE STEP

PLATFORM CARRIAGE BRACKETSTO ALLOW VERTICAL TRAVEL OFRELIEF SLOTS IN INTERIOR PANEL

STEP MODULEHANGER PLATES

STEP MODULE SUPPORT

LIFT PLATFORM

MAX 7" EACH3 EQ RISERS

VARIES

24.88 11.00

FINISHED MILLWORKINTERIOR PANEL

DETAIL D

OR REPLACEMENT OF STEP MODULEREMOVABLE TO ENABLE SERVICE

PLATFORMTOP OF LIFT

RISER FASCIA SHOULD BE MADE

LIFT BASECHANNEL

= SR -.50"RISER FASCIA

= SR +.63FASCIA OPNG

.13

.50 NOMINALCLEARANCE

SR

RISESR = STEP

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STEP MODULE / MILLWORK INTERFACE

2 OF 4 B910-0054

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

Page 21: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

E

SECTION B-B

COLUMN

RISER FASCIA

STEP MODULE

SCREW JACK

LIFT PLATFORM

= SW +1.00MIN FASCIA OPNG

.50.50 SW = STEP WIDTH

F

SECTION C-C

STEP MODULE SUPPORT BRACKETS(IF APPLICABLE) MAY BE REMOVEDAFTER THE HANGER PLATES AREFASTENED TO FLOOR JOISTS

VARIES

SW +1.38

DETAIL F

LAG SCREW OR CARRIAGEBOLT STEP MODULE HANGERPLATE TO FLOOR JOIST

INTERIOR PANEL

DETAIL E

FINISHED MILLWORK

PLATFORM CARRIAGE BRACKET

.50 NOMINALCLEARANCE

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STEP MODULE / MILLWORK INTERFACE

3 OF 4 B910-0054

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

Page 22: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

DETAIL G

PREFERRED ATTACHMENT:LAG SCREW OR CARRIAGE BOLTSTEP MODULE HANGER PLATESTO FLOOR JOIST. FASTENERSARE SUPPLIED AND INSTALLEDBY OTHERS.

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STEP MODULE / MILLWORK INTERFACE

4 OF 4 B910-0054

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

G

PARTIAL PERSPECTIVE VIEWw/ MILLWORK CUT AWAY AND SUB-FLOOR

HIDDEN TO ILLUSTRATE FRAMING CONCEPT

FLOOR JOIST SPACING TOCORRESPOND WITH STEPMODULE HANGER PLATES

JOISTS ABOVE STEP MODULE USED TOFRAME THE ACCESS HATCH OPENINGSHOULD BE REMOVABLE TO ENABLESERVICE AND REPLACEMENT OFSTEP MODULE

THE STEP MODULE IS SUSPENDED BELOW THE UPPERLANDING FLOOR BY FASTENING THE HANGER PLATES(INCLUDED WITH THE STEP MODULE) TO FLOOR JOISTS.ALTERNATIVELY, SUPPORT BRACKETS (INCLUDED WITHMOST APPLICATIONS), WHICH ARE INTENDED TO FACILITATEINSTALLATION OF THE STEP MODULE BEFORE THE MILLWORKIS COMPLETE, MAY BE MADE PERMANENT BY ANCHORING TOTHE FLOOR, BUT MUST ALSO BE SECURED LATERALLY FORSTABILITY; i.e., BRACE TO ADJACENT STRUCTURE OR UTILIZEHANGER CONNECTION TO FLOOR JOISTS. LIFT-U FURNISHESTHE ANCHOR BOLTS TO EXERCISE THIS OPTION.

Page 23: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S

RECOMMENDED DOOR / MILLWORK INTERFACE ALTERNATIVES. FOR

EACH PROJECT APPLICATION REFER TO ITS CORRESPONDING LIFT

CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT AND

LIFT ENVELOPE DIMENSIONS.

REFER TO DRAWING 910-0056 FOR THE RECOMMENDED JAM STYLES

NOTED ON THIS DRAWING, AND FOR STRIKE LATCH / MILLWORK

INTERFACE.

THE LIFT PLATFORM REQUIRES 3/8" MINIMUM TO 3/4" MAXIMUM RUNNING

CLEARANCE WITH ALL ADJACENT SURFACES; i.e., CLOSED DOORS AND

MILLWORK FINISHED SURFACES.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING

THE LIFT, AS WELL AS DOORS / GATES AND JAMS ARE FURNISHED

AND INSTALLED BY OTHERS.

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

THIS DOCUMENT IS LOANED FOR THE LIMITED

PURPOSES STATED HEREIN ONLY, AND REMAINS

THE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

DOOR SET-UP ALTERNATIVES

1 OF 1 A910-0055

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

32.00MIN

32.00MIN

UPPER LANDING

LIFT PLATFORMUPPER LANDING DOOR

MUST CLOSE FLUSH WITH

MILLWORK INTERIOR

LOWER LANDING DOOR CLOSES FLUSHWITH MILLWORK EXTERIOR - HINGES 180

PLATFORM EXTENDS

INTO OPENING NEAR

CLOSED DOOR TO

COMPLY WITH GAP

REQUIREMENTS

JAM STYLE D

JAM STYLE

A OR B

32.00MIN

32.00MIN

UPPER LANDING

LIFT PLATFORM

UPPER LANDING DOOR

MUST CLOSE FLUSH WITH

MILLWORK INTERIOR

LOWER LANDING DOOR CLOSES FLUSHWITH MILLWORK INTERIOR - HINGES 90

HINGE

PLATE

JAM STYLE D

JAM STYLE D

36.00 MIN

34.00MIN

34.00

MIN

UPPER LANDING

LIFT PLATFORM

UPPER LANDING DOOR

MUST CLOSE FLUSH WITH

MILLWORK INTERIOR

LOWER LANDING DOOR CLOSES FLUSHWITH MILLWORK EXTERIOR - HINGES 90

JAM STYLE

A OR B

JAM STYLE

A OR B

32.00

MIN

LIFT PLATFORM

LOWER LANDING DOOR CLOSES FLUSHWITH MILLWORK INTERIOR - HINGES 90

JAM STYLE D

32.00MIN

LIFT PLATFORM

LOWER LANDING DOOR CLOSES FLUSHWITH MILLWORK EXTERIOR - HINGES 90

PLATFORM EXTENDS

INTO OPENING NEAR

CLOSED DOOR TO

COMPLY WITH GAP

REQUIREMENTS

JAM STYLE C

OR SIMILAR TO B

LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE

A RELEASED CAL 9/5/2007

R E V I S I O N S

Page 24: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

JAM STYLE D

DWG, 1.25 MIN

SEE CONFIG

2.00 PREFERRED

SEE CONFIG DWG

FOR DOOR THK,

JAM STYLE C

A

DOOR JAM

ELECTRIC STRIKE

LATCH, SEE SHT 2

JAM STYLE AABOVE UPPER LANDING

HOLD JAM 3.00

2.00 PREFERRED

SEE CONFIG DWG

FOR DOOR THK,

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE

LIFT-U'S RECOMMENDED JAM STYLES AND STRIKE LATCH /

MILLWORK INTERFACE.

CLEARANCE AND/OR OPENINGS INSIDE THE MILLWORK WALLS

MUST BE PROVIDED FOR ROUTING OF ELECTRIC STRIKE LATCH

WIRING.

REFER TO DRAWING 910-0026 FOR ADDITIONAL RECOMMENDED

MILLWORK WALL INTERFACE DESIGN PRINCIPLES.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES

ENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMS

ARE FURNISHED AND INSTALLED BY OTHERS.

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

THIS DOCUMENT IS LOANED FOR THE LIMITED

PURPOSES STATED HEREIN ONLY, AND REMAINS

THE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STRIKE LATCH / MILLWORK INTERFACE

1 OF 2 B910-0056

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

JAM STYLE B

JAM

RECESSED

2.00 PREFERRED

SEE CONFIG DWG

FOR DOOR THK,

DETAIL A

DRILL FOR #12

WOOD SCREW

4.13

1.25

1.85

1.19

.12

3.35

4.88

.63

LTR ECO APPD DATE DESCRIPTION DFTR DATE CHKR DATE

A RELEASED CAL 9/6/2007

B ADDED STRIKE LATCH DIMENSIONS ON SHEET 2 BSA 11/15/2011

R E V I S I O N S

Page 25: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

2.442.06

1.68

1.231.00 MIN

1.19

2.00 PREFERRED

SEE CONFIG DWG

FOR DOOR THK,1.68MIN

.13 MAX

SECTION B-B

4.88

1.85

1.25

.63

1.23

3.35

2X, .275

PERSPECTIVE VIEWOF LOCKSET

ELECTRIC STRIKE LATCH

SPRING LATCH BOLT

1.00

2.251.63

2X, .196

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

THIS DOCUMENT IS LOANED FOR THE LIMITED

PURPOSES STATED HEREIN ONLY, AND REMAINS

THE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

STRIKE LATCH / MILLWORK INTERFACE

2 OF 2 B910-0056

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

MILLWORK

WALLDOOR

STRIKE LATCH DIMENSIONS

B

.165 1.43

.83

1.59

STRIKE INSERT MAY BE

ADJUSTED FOR PROPER

ALIGNMENT WITH SPRING

LATCH BOLT

1.96MAX

ELEVATION VIEWOF LOCKSET INTERFACE

SPRING LATCH

BOLT

ELECTRIC STRIKE

LATCH

B

B

Page 26: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

37.00(TALL COLUMN)

7.45

10.818.84

3.19

GEARBOXES

CENTERBETWEEN

18.00

18.00

8.78COLUMN

5.47COLUMN

1.25

6.72 (TYP)

3.88BASE FRAME

47.00 MINPLATFORMSEE NOTE 1

35.00 MINPLATFORMSEE NOTE 1

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT A

1 OF 1 B910-0064

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

32.00 MINCLEAR DOOR

OPENING

36.00 MINMILLWORKSEE NOTE 1

48.00 MINMILLWORK

SEE NOTE 1

7.00MILLWORK WALL

ENCASING COLUMN

.50 RUNNINGCLEARANCE

2.00 DOORBY OTHERS

VMW DETAILED LIFT TEMPLATE

PERSPECTIVE VIEW

VMW LIFT

MILLWORKBY OTHERS

UPPERLANDING

NOTES:1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

B

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

Page 27: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT B

1 OF 1 B910-0065

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

BASE FRAME

10.81

SEE TABLE MINUS 1"PLATFORM WIDTH

SEE TABLE MINUS 1"PLATFORM LENGTH

18.00

8.78COLUMN

1.25

8.84

3.19

5.47COLUMN

6.72 (TYP)

3.88BASE FRAME

5.003.81

GEARBOXES

CENTERBETWEEN

18.00

PERSPECTIVE VIEW

VMW LIFT

MILLWORKBY OTHERS

UPPERLANDING

TABLE

NOTES:1. SPECIFIC TO THIS CONFIGURATION, THE MINIMUM PLATFORM WIDTH CORRESPONDS TO THE MINIMUM PLATFORM LENGTH - REFER TO TABLE. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

B

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

32.00 MINCLEAR DOOR

OPENING

SEE TABLEMILLWORK WIDTH

SEE TABLEMILLWORK LENGTH

.50 RUNNINGCLEARANCE

7.00MILLWORK WALL

ENCASING COLUMN

42.00 MINCLEAR DOOR

OPENING

2.00 DOORBY OTHERS

VMW DETAILED LIFT TEMPLATE

DRIVEMOTOR

7.45

37.00(TALL COLUMN)

WIDTH LENGTH

42" 60"

43" 59"

44" 58"

45" 57"

46" 56"

VMW 90 DEG EGRESS

Page 28: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

B

7.45

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT C

1 OF 1 B910-0066

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

PERSPECTIVE VIEW

VMW LIFT

MILLWORKBY OTHERS

UPPERLANDING

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

54.00 MINMILLWORKSEE NOTE 1

48.00 MINMILLWORKSEE NOTE 1

32.00 MINCLEAR DOOR

OPENING

.50 RUNNINGCLEARANCE

2.00 DOORBY OTHERS

7.00MILLWORK WALL

ENCASING COLUMN

18.00

53.00 MINPLATFORMSEE NOTE 1

GEARBOXES

CENTERBETWEEN

47.00 MINPLATFORMSEE NOTE 1

3.19

3.19

8.84 10.81

18.00

3.19

1.255.47

COLUMN

3.88BASE FRAME

7.00

8.78COLUMN

6.72(TYP)

VMW DETAILED LIFT TEMPLATE

B

37.00(TALL COLUMN)

NOTES:1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

Page 29: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

PERSPECTIVE VIEW

VMW LIFTMILLWORKBY OTHERS

UPPERLANDING

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

B7.45

37.00(TALL COLUMN)

NOTES:1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT D

1 OF 1 B910-0067

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

VMW DETAILED LIFT TEMPLATE

18.00

53.00 MINPLATFORMSEE NOTE 1

47.00 MINPLATFORMSEE NOTE 11.25

3.19

3.88BASE FRAME

8.84 10.81

5.47COLUMN

18.00

GEARBOXES

CENTERBETWEEN

8.78COLUMN

6.72(TYP)

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

54.00 MINMILLWORKSEE NOTE 1

48.00 MINMILLWORKSEE NOTE 1

7.00MILLWORK WALL

ENCASING COLUMN

.50 RUNNINGCLEARANCE

32.00 MINCLEAR DOOR

OPENING

2.00 DOORBY OTHERS

Page 30: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

NOTES:1. MINIMUM PLATFORM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUBSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM PLATFORM DIMENSIONS. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT E

1 OF 1 B910-0068

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

18.00

45.00 MINPLATFORMSEE NOTE 1

GEARBOXES

CENTERBETWEEN

47.00 MINPLATFORMSEE NOTE 1

3.19

3.19

8.84 10.81

18.00

3.19

1.255.47

COLUMN

6.72(TYP)

3.88BASE FRAME

7.00

8.78COLUMN

33.22

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

7.45

VMW DETAILED LIFT TEMPLATE

B

B

37.00(TALL COLUMN)

PERSPECTIVE VIEW

VMW LIFTMILLWORKBY OTHERS

UPPERLANDING

INTERMEDIATELANDING

ROLL-UP BARRIER

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

ROLL-UP BARRIER MODULE INSTALLS INTHE INTERMEDIATE LANDING.BASE FRAME AND DRIVE SHAFTS ROUTEAROUND THE ROLL-UP BARRIER MODULEWHEN THE INTERMEDIATE LANDING ELEVIS LESS THAN 10", BUT THE LANDING MUSTBE AT LEAST 6" ABOVE THE LOWER LANDING.

48.00 MINMILLWORK

SEE NOTE 1

42.00MIN

46.00 MINMILLWORK

SEE NOTE 130.00 MIN

7.00MILLWORK WALL

ENCASING COLUMN.50 RUNNINGCLEARANCE

32.00 MINCLEAR DOOR

OPENING

2.00 DOORBY OTHERS

Page 31: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

7.45

NOTES:1. MINIMUM PLATFORM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUBSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM PLATFORM DIMENSIONS. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

PERSPECTIVE VIEW

VMW LIFT MILLWORKBY OTHERS

UPPERLANDING

INTERMEDIATELANDING

ROLL-UP BARRIER

VMW DETAILED LIFT TEMPLATE

B

B

37.00(TALL COLUMN)

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT F

1 OF 1 B910-0069

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

18.00

45.00 MINPLATFORMSEE NOTE 1

GEARBOXES

CENTERBETWEEN

47.00 MINPLATFORMSEE NOTE 1

3.19

3.19

8.84 10.81

18.00

3.19

1.255.47

COLUMN

3.88BASE FRAME

7.00

8.78COLUMN

6.72(TYP)

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

ROLL-UP BARRIER MODULEINSTALLS IN THE INTERMEDIATELANDING.FOR THE MODULE TO CLEAR DRIVESHAFT, THE INTERMEDIATE LANDINGELEV MUST BE NO LESS THAN 10"ABOVE THE LOWER LANDING.

48.00 MINMILLWORK

SEE NOTE 1

32.00 MINCLEAR DOOR

OPENING

42.00MIN

46.00 MINMILLWORK

SEE NOTE 130.00 MIN

7.00MILLWORK WALL

ENCASING COLUMN.50 RUNNINGCLEARANCE

2.00 DOORBY OTHERS

Page 32: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

PERSPECTIVE VIEW

VMW LIFT

MILLWORKBY OTHERS

UPPERLANDING

INTERMEDIATELANDING

ROLL-UP BARRIER

18.00

35.00 MINPLATFORMSEE NOTE 1

63.00 MINPLATFORMSEE NOTE 1

1.25

GEARBOXES

CENTERBETWEEN

10.818.84

3.81 5.00

5.47COLUMN

3.88BASE FRAME

8.78COLUMN

3.19

6.72(TYP)

18.00

VMW DETAILED LIFT TEMPLATE

B

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

B 7.45

37.00(TALL COLUMN)

NOTES:1. MINIMUM PLATFORM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUBSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM PLATFORM DIMENSIONS. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

ROLL-UP BARRIER MODULEINSTALLS IN THE INTERMEDIATELANDING.FOR THE MODULE TO CLEAR DRIVESHAFT, THE INTERMEDIATE LANDINGELEV MUST BE NO LESS THAN 10"ABOVE THE LOWER LANDING.

42.00MIN

36.00 MINMILLWORKSEE NOTE 1

30.00 MIN

.50 RUNNINGCLEARANCE

2.00 DOORBY OTHERS

32.00 MINCLEAR DOOR

OPENING

64.00 MINMILLWORK

SEE NOTE 1

11.00

7.00MILLWORK WALL

ENCASING COLUMN

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT G

1 OF 1 B910-0070

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

Page 33: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

25.00(SHORT COLUMN)

PERSPECTIVE VIEW

VMW LIFT

MILLWORKBY OTHERS

UPPERLANDING

INTERMEDIATELANDING

ROLL-UP BARRIER

VMW SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPERLANDING

LOWERLANDING

ROLL-UP BARRIER MODULEINSTALLS IN THE INTERMEDIATELANDING.FOR THE MODULE TO CLEAR DRIVESHAFT, THE INTERMEDIATE LANDINGELEV MUST BE NO LESS THAN 10"ABOVE THE LOWER LANDING.

56.00 MINMILLWORK

SEE NOTE 1

32.00 MINCLEAR DOOR

OPENING

42.00MIN

46.00 MINMILLWORKSEE NOTE 1

30.00 MIN

7.00MILLWORK WALL

ENCASING COLUMN.50 RUNNINGCLEARANCE

10.00

2.00 DOORBY OTHERS

18.00

45.00 MINPLATFORMSEE NOTE 1

GEARBOXES

CENTERBETWEEN

55.00 MINPLATFORMSEE NOTE 1

3.19

8.84 10.81

18.00

3.19

1.255.47

COLUMN

6.72(TYP)

3.88BASE FRAME

8.78COLUMN

7.81

7.00

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

VMW TEMPLATE, LAYOUT H

1 OF 1 B910-0071

LIFT-U

A DIVISION OF

HOGAN MFG., INC.

NOTES:1. MINIMUM PLATFORM DIMENSIONS CORRESPOND WITH MINIMUM DOOR OPENINGS AND SCREW COLUMN ORIENTATION. SUBSEQUENTLY, INCREASING THE DOOR OPENINGS ALSO INCREASES THE MINIMUM PLATFORM DIMENSIONS. PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED, 74" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE VMW.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK INTERFACE DETAILS, REFER TO VMW LIFT APPLICATION GUIDELINES.

B

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

B UPDATED PER CURRENT DESIGNS WAC 10-18-11

VMW DETAILED LIFT TEMPLATE

B

SCREW COLUMN(TALL COLUMN SHOWN, 12"SHORTER COLUMN AVAILABLE)

DRIVEMOTOR

BASE FRAME

B 7.45

37.00(TALL COLUMN)

Page 34: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

6.00 MINPIT DEPTH

MIN PIT LENGTH

12.09

.50 45.00

MIN PIT WIDTH

.50.50

910-0072

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT A

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES.

DRIVE

BASE FRAME

MOTORLOWER

LANDING

78.88

31.38

12.25

PLATFORM

MILLWORK

PERSPECTIVE VIEW

VMX LIFTBY OTHERS

UPPER

LANDING

SEE NOTE 1

38.52

SEE NOTE 1

35.00

PLATFORM

MIN

48.00 MINPLATFORM

33.00

VMX DETAILED LIFT TEMPLATE

PLATFORM

MILLWORK FOOTPRINT SHOWNVMX SIMPLE TEMPLATE

UPPER

LANDING

LOWER

LANDING

MIN

2.00 DOOR

MILLWORK WALL

BY VMX LIFT

MILLWORK49.00

BY OTHERS

36.00 MIN

MILLWORKSEE NOTE 1

SEE NOTE 1

CLEARANCE RUNNING.50

THK UNAFFECTED

32.00 MIN

CLEAR DOOROPENING

Page 35: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

12.09

MIN PIT LENGTH

6.00 MIN

PIT DEPTH

.50 45.00

MIN PIT WIDTH

.50.50

DRIVE

BASE FRAME

MOTORLOWER

LANDING

12.25

78.88

PLATFORM

31.38

MILLWORK

PERSPECTIVE VIEW

VMX LIFT

BY OTHERS

UPPER

LANDING

VMX DETAILED LIFT TEMPLATE

PLATFORM

UPPER

LANDING

VMX SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

LOWER

LANDING

32.00

CLEARANCE

OPENING

OPENING

SEE TABLELENGTH

CLEAR DOOR

BY OTHERS DOOR

.50

THK UNAFFECTED

MIN

RUNNING

CLEAR DOOR

2.00

MILLWORK

42.00 MIN

BY VMX LIFT

MILLWORK WALL

SEE TABLE

MILLWORK WIDTH

SEE TABLE MINUS 1"PLATFORM LENGTH

PLATFORM WIDTH

38.52

SEE TABLE MINUS 1"

33.00

TABLE

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. SPECIFIC TO THIS CONFIGURATION, THE MINIMUM

PLATFORM WIDTH CORRESPONDS TO THE MINIMUM

PLATFORM LENGTH - REFER TO TABLE. PLATFORMS

MEASURING AT LEAST 18 SQ. FT. ARE PREFERRED;

BUT SHOULD NOT EXCEED 25 SQ. FT. BE ADVISED,

72" IN THE LONG DIRECTION IS LIFT-U'S ABSOLUTE

"DO NOT EXCEED" DIMENSION FOR THE VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES. 910-0073

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT B

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

WIDTH LENGTH

42" 60"

43" 59"

44" 58"

45" 57"

46" 56"

47" 55"

48" 54"

49" 53"

VMX 90 DEG EGRESS

Page 36: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

MIN PIT WIDTH

.50 .50

MIN PIT LENGTH

6.00 MINPIT DEPTH

12.09

.50 45.00

BY OTHERS

PERSPECTIVE VIEW

VMX LIFT

MILLWORK

UPPER

LANDING

VMX DETAILED LIFT TEMPLATE

PLATFORMDRIVE

BASE FRAME

MOTOR

LOWER

LANDING

PLATFORM

78.88

31.38

12.25

UPPER

LANDING

VMX SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

LOWER

LANDING

BY VMX LIFT

MILLWORK WALL

MIN

MILLWORK

SEE NOTE 1

THK UNAFFECTED

MIN

CLEAR DOOR

RUNNINGCLEARANCE

DOORBY OTHERS

49.00

OPENING

.50

32.00

2.00

54.00 MIN

MILLWORKSEE NOTE 1

38.52

48.00

SEE NOTE 1

PLATFORM MIN

SEE NOTE 1

53.00 MINPLATFORM

33.00

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES. 910-0074

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT C

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

Page 37: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

MIN PIT WIDTH

.50.50

MIN PIT LENGTH

12.096.00 MIN

PIT DEPTH

45.00.50

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES.

38.52

48.00

SEE NOTE 1PLATFORM

MIN

SEE NOTE 1

53.00 MIN

PLATFORM

33.00

VMX DETAILED LIFT TEMPLATE

BASE FRAME

MOTOR

DRIVE

LOWER

LANDING

PLATFORM

78.88

31.38

12.25

910-0075

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT D

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

MILLWORK FOOTPRINT SHOWNVMX SIMPLE TEMPLATE

UPPER

LANDING

LOWER

LANDING

BY VMX LIFT

MILLWORK

MIN

.50 RUNNING

CLEARANCE

49.00 MIN

MILLWORK

SEE NOTE 1

2.00 DOOR

BY OTHERS

SEE NOTE 1

54.00

THK UNAFFECTED

MILLWORK WALL

32.00 MIN

CLEAR DOOR

OPENING

BY OTHERS

PERSPECTIVE VIEW

VMX LIFT

MILLWORK

UPPER

LANDING

Page 38: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

MIN PIT WIDTH

.50 .50

MIN PIT LENGTH

12.096.00 MIN

PIT DEPTH

.50 45.00

VMX DETAILED LIFT TEMPLATE

PLATFORM

DRIVE

BASE FRAME

MOTORLOWER

LANDING

PLATFORM

78.88

31.38

12.25

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES. 910-0076

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT E

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

VMX SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

LANDING

LOWER

UPPER

LANDING

ROLL-UP BARRIER MODULE

INSTALLS IN THE INTERMEDIATE

LANDING.

THE INTERMEDIATE LANDING

ELEV MUST BE NO LESS THAN 6"

ABOVE THE LOWER LANDING.

RUNNING

49.00

CLEARANCE

OPENING

2.00

BY VMX LIFT

MILLWORK WALLTHK UNAFFECTED

CLEAR DOOR

.50

DOOR

BY OTHERS

SEE NOTE 1

MILLWORK MIN

MIN

42.00

MIN30.00

32.00 MIN

42.00 MINMILLWORK

SEE NOTE 1

38.52

48.00

33.00

MIN

PLATFORM

SEE NOTE 1

41.00 MIN

PLATFORMSEE NOTE 1

BY OTHERS

UPPER

LANDING

LANDING

PERSPECTIVE VIEW

VMX LIFTMILLWORK

INTERMEDIATE

ROLL-UP BARRIER

Page 39: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

MIN PIT WIDTH

.50.50

MIN PIT LENGTH

12.096.00 MIN

PIT DEPTH

.50 45.00

910-0077

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT F

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES.

VMX SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

LANDING

LOWER

UPPER

LANDING

ROLL-UP BARRIER MODULE

INSTALLS IN THE INTERMEDIATE

LANDING.

THE INTERMEDIATE LANDING

ELEV MUST BE NO LESS THAN 6"

ABOVE THE LOWER LANDING.

MILLWORK

49.00

MIN42.00

SEE NOTE 1

.50 RUNNING

CLEARANCE

OPENING

MINCLEAR DOOR

SEE NOTE 1MILLWORK

MIN

MIN30.00

MIN

42.00

BY VMX LIFT

MILLWORK WALLTHK UNAFFECTED

32.00

2.00 DOORBY OTHERS

BY OTHERS

UPPER

LANDING

LANDING

PERSPECTIVE VIEW

VMX LIFTMILLWORK

INTERMEDIATE

ROLL-UP BARRIER

38.52

33.00

48.00 MINPLATFORM

SEE NOTE 1

41.00 MIN

PLATFORM

SEE NOTE 1

VMX DETAILED LIFT TEMPLATE

PLATFORM

BASE FRAME

MOTOR

DRIVELOWER

LANDING

PLATFORM

78.88

31.38

12.25

Page 40: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

MIN PIT WIDTH

.50.50

MIN PIT LENGTH

12.096.00 MIN

PIT DEPTH

45.00.50

910-0078

LIFT-U

A DIVISION OF

REVISIONSHEET NO.

A1 OF 1

VMX TEMPLATE, LAYOUT G

209-838-2400

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

PURPOSES STATED HEREIN ONLY, AND REMAINS

DOCUMENT NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL

TRADE SECRET INFORMATION OF THE COMPANY. NO

PART OF IT MAY BE REPRODUCED, STORED IN A

RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM

OR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,

RECORDING OR OTHERWISE, WITHOUT THE PRIOR

WRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED CAL 3/4/09

NOTES:

1. MINIMUM PLATFORM DIMENSIONS ARE SHOWN.

PLATFORMS MEASURING AT LEAST 18 SQ. FT. ARE

PREFERRED; BUT SHOULD NOT EXCEED 25 SQ. FT.

BE ADVISED, 72" IN THE LONG DIRECTION IS LIFT-U'S

ABSOLUTE "DO NOT EXCEED" DIMENSION FOR THE

VMX.

2. MAXIMUM VERTICAL TRAVEL IS 24".

3. FOR LIFT APPLICATIONS THAT DO NOT CORRESPOND

WITH LIFT-U'S STANDARD TEMPLATES, CONTACT LIFT-U

FOR EVALUATION.

4. FOR ADDITIONAL INFORMATION, INCLUDING MILLWORK

INTERFACE DETAILS, REFER TO VMX LIFT APPLICATION

GUIDELINES.

LOWER

LANDING

VMX SIMPLE TEMPLATEMILLWORK FOOTPRINT SHOWN

UPPER

LANDING

ROLL-UP BARRIER MODULE

INSTALLS IN THE INTERMEDIATE

LANDING.

THE INTERMEDIATE LANDING

ELEV MUST BE NO LESS THAN 6"

ABOVE THE LOWER LANDING.

MIN36.00

SEE NOTE 1MILLWORK

2.00 DOOR

.50

BY OTHERS

32.00 MIN

MIN30.00

MIN

MILLWORK WALL

BY VMX LIFT

42.00

CLEARANCE

RUNNING

CLEAR DOOR

OPENING

THK UNAFFECTED

54.00 MIN

MILLWORKSEE NOTE 1

33.00

38.52

53.00 MIN

PLATFORMSEE NOTE 1

35.00 MINPLATFORM

SEE NOTE 1

VMX DETAILED LIFT TEMPLATE

DRIVE

BASE FRAME

MOTORLOWER

LANDING

PLATFORM

78.88

31.38

12.25

BY OTHERS

UPPER

LANDING

LANDING

PERSPECTIVE VIEW

VMX LIFT

MILLWORK

INTERMEDIATE

ROLL-UP BARRIER

Page 41: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDOPERABLE STEP / MILLWORK INTERFACE.

THE OPERABLE STEP HEIGHT AND WIDTH WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT, LIFT ENVELOPEDIMENSIONS, AND OPERABLE STEP MODULE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

CUT MILLWORK FOR1/4" TO 1/2" CLEARANCE

ALL-AROUND

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED

OPERABLE STEPIN "STEP" POSITION

OPERABLE STEPIN "RAMP" POSITION

OPERABLE STEP

WIDTH

OVERALLSTEP

HEIGHTSTEP

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

OPERABLE STEP / MILLWORK INTERFACE

1 OF 1 A910-0085

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

OPERABLE STEPINSTALL WITH ANCHOR BOLTS

(SUPPLIED BY LIFT-U)PRIOR TO MILLWORK

PLAN VIEW WITH OPERABLE STEP IN "STEP" POSITION

.50 RUNNINGCLEARANCE

Page 42: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

ROLL-UP BARRIER (STOWED) ROLL-UP BARRIER (DEPLOYED)

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

ROLL-UP BARRIER OVERVIEW

1 OF 1 A910-0088

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

ACCESSOR LIFT WITH ROLL-UP BARRIER

LIFT AT PARK LEVEL; BARRIER IS STOWED

BARRIER DEPLOYS DURING LIFT OPERATION

Page 43: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

ACCESSOR LIFT WITH RETRACTABLE STEP

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

RETRACTABLE STEP OVERVIEW

1 OF 1 A910-0089

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

RETRACTABLE STEP IS DEPLOYED WHILE LIFT IS IN PARK POSITION

RETRACTABLE STEP (DEPLOYED)

RETRACTABLE STEP IS STOWED DURING LIFT OPERATION

RETRACTABLE STEP (STOWED)

Page 44: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

OPERABLE STEP IS IN "STEP" POSITION DURING LIFT OPERATION

OPERABLE STEP IS IN "STEP" POSITION WHILE LIFT IS PARKED

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

OPERABLE STEP OVERVIEW

1 OF 1 A910-0090

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

ACCESSOR LIFT WITH OPERABLE STEP

OPERABLE STEP IS IN "RAMP" POSITION AT LOWER LEVEL FOR PASSENGER INGRESS/EGRESS

OPERABLE STEP (STEP POSITION) OPERABLE STEP (RAMP POSITION)

Page 45: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

44.00DOORFRAME

42.00CLEARDOOR

OPENING

36.00DOORFRAME

34.00CLEARDOOR

OPENING

4.00

APPROVAL SIGNIFIES THAT ALL DIMENSIONS ARE CORRECT

5. SEE SHEET 5 OF 5 FOR LIFT SPECIFICATIONS.TO THEIR SPECIFICATIONS.

DRAWING MUST BE SIGNED BY CUSTOMER AND RETURNED 4.TO LIFT-U PRIOR TO PRODUCTION RELEASE. CUSTOMER

REQUIRED TO OBTAIN A VAIRANCE FROM THE PRESIDING AUTHORITY FOR NON-COMPLIANT FEATURES.

PRIOR TO INSTALLATION, THE CUSTOMER MAY BE 3.

ELECTRICAL CONTROL PANEL BY OTHERS. FURNISH 115 BUILDING POWER TO BE SUPPLIED AND ROUTED TO

POWER NOTE:

VAC, 3 WIRE, 15 AMP, SINGLE PHASE SOURCE POWER.

ADVISORY NOTES:

THIS DRAWING IS SUBJECT TO CHANGE PENDING 1.APPLICABLE STATE AND LOCAL CODES, AND CUSTOMER APPROVAL.CUSTOMER MUST PROVIDE APPLICABLE STATE AND LOCAL 2.CODES TO LIFT-U PRIOR TO DESIGN.

THIS DRAWING ILLUSTRATES A LIFT PLATFORM ANDOPERATING MECHANISM WITHIN THE PARAMETERS OFMILLWORK WALLS. THE LIFT PLATFORM REQUIRES 3/8"MINIMUM TO 3/4" MAXIMUM RUNNING CLEARANCE WITHADJACENT MILLWORK FINISHED SURFACES. THE MILL-WORK SHOWN IS FOR ILLUSTRATIVE REFERENCE ONLY.DIMENSIONAL EXTENTS OF THE MILLWORK IS THERESPONSIBILITY OF OTHERS.

MILLWORK WALLS ARE SHOWN IN SHADED /TRANSPARENT MODE ON SHEET 1 OF 5 TO VIEWENCASED LIFT ASSEMBLY.

REFERENCE ONLY

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

THE PROPERTY OF THE COMPANY.

THIS DOCUMENT IS LOANED FOR THE LIMITEDA DIVISION OF

209-838-2400

LIFT CONFIGURATION, 7"-14" RISETITLE

DOCUMENT NO. SHEET NO. REVISION

1 OF 5

LIFT-U

910-0091

PURPOSES STATED HEREIN ONLY, AND REMAINS

A

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

D

INSTALLED BY OTHERS.

BARRIER

PLAN VIEW

OPERATING

PLATFORM SHOWN AT LOWER LEVEL (1)

WITNESS LEVEL

COURTROOM LEVEL 1

PANEL W/DISCONNECT(BELOW)

(BELOW)

MANUAL

+1.6" ELEV

AS ADJACENT AREAS. FLOOR

+15.5" ELEV

COVERING TO BE SUPPLIED AND

DEVICE

JUDGE LEVEL 3

+8.5" ELEV

ELECTRICAL CONTROL

+8.5" ELEV

(BELOW)

LIFT PARKS AT

DRIVE MOTOR

WITNESS LEVEL 2

MODULE

PLATFORM TO BE COVERED WITH THE SAME FLOORING MATERIAL

ROLL-UP

BATTERY BACK-UP(BELOW)

26.00

48.00

.50

7.00

DOOR

PLATFORM

DOOR

WIDTH

59.00

7.00

2.00 2.00

2.00

47.00

4.00

MILLWORK

67.00

18.13

MILLWORK INTERIOR

PLATFORMLENGTH

2.00

4.00

15.44

48.00

INTERIOR

CLEARANCE RUNNING

60.00

17.06

4.00

AA

B

B

CC

SCREW JACK

DETAIL D

COLUMN

LIFTPLATFORM

7.00

.50

PANEL THK.

CLEARANCE RUNNING

.75 MIN.

5.47

Page 46: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

36.00 DOOR FRAME

REFERENCE ONLY

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

LIFT-U

2 OF 5REVISIONSHEET NO.DOCUMENT NO.

910-0091 A

LIFT CONFIGURATION, 7"-14" RISE

209-838-2400

A DIVISION OF THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

BRACKET

DETAIL E

PLATFORM SUPPORT

LIFT PLATFORM

.50

COLUMN THK

CLEARANCE RUNNING

6.22

.75 MINPANEL THK.

5.47 SCREW

1.60

EDOOR MUST CLOSE FLUSH

LIFT IS INSTALLED.

SUPPORT

SIDES FACING THE PLATFORMTO BE COMPLETED AFTER THE

SECTION B-B

WITH FASCIA BELOW UPPERLANDING SILL BRACKET

LIFT SCREW JACK COLUMNS TOBE ENCASED IN MILLWORK.MILLWORK IS SUPPLIED ANDINSTALLED BY OTHERS.

PLATFORM

DOORJAMB

1.60

8.50

60.00 MILLWORK INTERIOR4.00

36.10

4.00

F

PRIOR TO LIFT INSTALLATION

STATION

FLOOR MUST BE LEVEL (BY OTHERS)

FLOOR

PLATFORMCONTROL

SECTION A-A

TO ALLOW VERTICAL MOVEMENT OF THELIFT PLATFORM SUPPORT BRACKETS.

RAISED

PROVIDE RELIEF CUTS IN VENEER PANELS

PANEL TO BE REMOVABLETO ALLOW ACCESS TO SCREW COLUMNS BEHIND

WALL

.50

18.50

2.00

9.76

MAX

1.60

44.60

48.00DOOR

15.50

MILLWORK INTERIOR

40.00

7.00

51.60

DETAIL F

PROVIDE RELIEF CUTS IN VENEER FOR HINGED RISER CONTROL PIN AND GUIDE BLOCK

2.13

6.8013.13

.38

7.64

Page 47: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

SECTION C-C

ROLL-UP BARRIER:REFER TO DRAWING 910-0042 FOR RECOMMENDED MILLWORK INTERFACE

15.50

8.50

7.00

2.002.00

42.00

7.00 48.00

PORTAL OPENING

MILLWORK INTERIOR

51.60

44.60

1.60RAISED FLOOR

21.00

REFERENCE ONLY

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

A DIVISION OF

THE PROPERTY OF THE COMPANY.

REVISIONSHEET NO.DOCUMENT NO.

209-838-2400THIS DOCUMENT IS LOANED FOR THE LIMITED

HOGAN MFG., INC.PURPOSES STATED HEREIN ONLY, AND REMAINS

RR

910-0091 A

R

TITLE

LIFT CONFIGURATION, 7"-14" RISE

3 OF 5

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

LIFT-U

Page 48: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

PLATFORM SHOWN AT UPPER LEVEL (3)READY FOR PASSENGER INGRESS OR EGRESS

DETAIL F

ELECTRIC STRICK LATCHCUT INTO DOOR JAMB

F

REVERSE ISOMETRIC VIEWBACK WALL AND DOORS NOT SHOWN FOR CLARITY

PROVIDE AN ACCESS HATCH TO ENABLESERVICE ON MOTOR AND ELECTRONICSLOCATED BELOW UPPER LANDING.HATCH SHOULD BE NO LESS THAN 30" x 36".A REMOVABLE JOIST WITHIN THE FRAMEDHATCH OPENING SHOULD BE POSITIONEDTO REINFORCE THE HATCH COVER.

MANUALLY OPERATED, SELF-CLOSING DOORS i.e. w/SPRING HINGES. DOORS, SELF-CLOSING SPRING HINGES,AND JAMBS ARE FURNISHED

AND INSTALLED BY OTHERS.ELECTRIC STRIKE LATCHES, SPRING-LOADED LATCH BOLTS,

AND ELECTRICAL INTERLOCK WIRING FURNISHED BY LIFT-U AND INSTALLED BY

OTHERS.

LEVEL (2) FOR USE BY ABLE-BODIED PERSONS

REFERENCE ONLY

PLATFORM SHOWN PARKED AT WITNESS

TYPICAL 2 PLACES

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

LIFT-U

4 OF 5REVISIONSHEET NO.DOCUMENT NO.

910-0091 A

LIFT CONFIGURATION, 7"-14" RISE

209-838-2400

A DIVISION OF THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHED AND INSTALLED BY OTHERS. BE ADVISED - ALL INTERIOR SURFACES MUST BE SMOOTH, i.e. NO PROTRUSIONS AND NO OPENINGS, OTHER THAN THOSE NECESSARY FOR THE OPERATION OF THE LIFT. INTERIOR PANELS SHOULD BE MADE REMOVABLE TO PROVIDE ACCESS TO LEVEL SWITCHES AND ENABLE SERVICE OR REPLACEMENT OF SCREW JACKS, GEARBOXES, AND DRIVE SHAFTS.

DOORS ARE CLOSED AND LOCKED WHENPLATFORM RAISES AND LOWERS

PLATFORM SHOWN AT LOWER LEVEL (1)READY FOR PASSENGER INGRESS OR EGRESS

THREE CONTROL STATIONS SUPPLIED BY LIFT-U.LOCATION AND WALL CUT IN BY OTHERS.ELECTRICAL WIRING FURNISHED BY LIFT-U.

Page 49: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

32.41

10.25

3.19

REFERENCE ONLY

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

A910-0091

LIFT-U

5 OF 5REVISION

LIFT CONFIGURATION, 7"-14" RISE

209-838-2400

A DIVISION OF THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

DOCUMENT NO.

PURPOSES STATED HEREIN ONLY, AND REMAINS

SHEET NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

60.44

19.88

FRAME

47.00

98.94

FRAME36.41

3.19

BASE

BASE

52.91 BASE FRAME

70.91

33.22

10.009.91

BASE FRAME

59.00

41.41

1.25

36.41

33.00

10.81

5.00

6.72TYP.

LIFT ENVELOPE DIMENSIONS

36.99

8.507.65

1.60

15.50

FURNISHED BY LIFT-U.

LEVEL 1 - TOP

DRIVEDEVICEOPERATINGMANUAL

DRIVE SHAFTS CONNECTING

PLATE AT +1.60"OF LIFT PLATFORM

ISOMETRIC VIEW

THIS TIME.

PLATE AT +8.50"

RACEWAYS NOT SHOWN AT

TO FLOOR. ANCHOR BOLTS LIFT BASE FRAME ANCHORS

GEARBOXES, AND CABLE

MOTOR

LEVEL 2 - TOPOF LIFT PLATFORM

HINGED RISER

SHEET METAL FLANGES ON SCREW JACKCOLUMNS FACILITATE THE ATTACHMENTOF MILLWORK FRAMING AND VENEERED

PANELS (MILLWORK BY OTHERS).

LEVEL 3 - TOPOF LIFT PLATFORMPLATE AT +15.50"

8.78 5.47

5.75

48.00 HINGED RISER WIDTH

Page 50: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

2X, 34.00CLEAR DOOR

OPENING

2X, 36.00DOORFRAME

5. SEE SHEET 5 OF 5 FOR LIFT SPECIFICATIONS.

DIMENSIONAL EXTENTS OF THE MILLWORK IS THE

POWER NOTE:

BUILDING POWER TO BE SUPPLIED AND ROUTED TO ELECTRICAL CONTROL PANEL BY OTHERS. FURNISH 115

MILLWORK WALLS. THE LIFT PLATFORM REQUIRES 3/8"OPERATING MECHANISM WITHIN THE PARAMETERS OFTHIS DRAWING ILLUSTRATES A LIFT PLATFORM AND

TO LIFT-U PRIOR TO PRODUCTION RELEASE. CUSTOMER

ADJACENT MILLWORK FINISHED SURFACES. THE MILL-WORK SHOWN IS FOR ILLUSTRATIVE REFERENCE ONLY.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT AREFURNISHED AND INSTALLED BY OTHERS.

RESPONSIBILITY OF OTHERS.

VAC, 3 WIRE, 15 AMP, SINGLE PHASE SOURCE POWER.

AUTHORITY FOR NON-COMPLIANT FEATURES.

APPROVAL SIGNIFIES THAT ALL DIMENSIONS ARE CORRECT TO THEIR SPECIFICATIONS.

MILLWORK WALLS ARE SHOWN IN SHADED /TRANSPARENT MODE ON SHEET 1 OF 5 TO VIEWENCASED LIFT ASSEMBLY.

4. DRAWING MUST BE SIGNED BY CUSTOMER AND RETURNED

MINIMUM TO 3/4" MAXIMUM RUNNING CLEARANCE WITH

ADVISORY NOTES:

THIS DRAWING IS SUBJECT TO CHANGE PENDING 1.APPLICABLE STATE AND LOCAL CODES, AND CYSTOMER APPROVAL.CUSTOMER MUST PROVIDE APPLICABLE STATE AND LOCAL 2.CODES TO LIFT-U PRIOR TO DESIGN.PRIOR TO INSTALLATION, THE CUSTOMER MAY BE 3.REQUIRED TO OBTAIN A VAIRANCE FROM THE PRESIDING

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

REFERENCE ONLY

FLOOR COVERING TO BE SUPPLIED AND

PANEL w/DISCONNECT

(BELOW)

COURTROOM FLOOR

BATTERY BACK-UP

+18" ELEVJUDGE LEVEL (3)

+12" ELEV

PLAN VIEWPLATFORM SHOWN AT JUDGE LEVEL (3)

(BELOW)

WITNESS LEVEL (2)

ELECTRICAL CONTROL INSTALLED BY OTHERS.

LEVEL (1) +0" ELEV

PLATFORM TO BE COVERED WITH THE SAMEFLOORING MATERIAL AS ADJACENT AREAS.

ROLL-UP BARRIERMOULE

2.00

4.00

INTERIOR

62.00 2.00

4.00

DOOR

RUNNING

MILLWORK INTERIOR

.50CLEARANCE

18.13

PLATFORMWIDTH

PLATFORM LENGTH

37.00

61.00

27.87

30.00

62.00

DOOR

MILLWORK INTERIOR

36.00

15.44

17.06

38.00MILLWORK

4.00

B

B

A

A

C C

A910-0092

LIFT-U

LIFT CONFIGURATION, 6" - 18" RISEREVISION

A DIVISION OF

209-838-2400

1 OF 5

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.

TITLE

DOCUMENT NO.

PURPOSES STATED HEREIN ONLY, AND REMAINS

SHEET NO.

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

Page 51: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

(42.00)MAX

6.0012.00

36.00 DOORFRAME

PLATFORM

COURTROOM

LEVEL (BY OTHERS) PRIOR TO LIFT INSTALLATION.

WITNESSLEVEL (2)

SECTION A-A

CONTROL

LEVEL (3)

PARK

FLOOR LEVEL (1)

JUDGELEVEL

STATION

RECESSED SLAB MUST BE

DOORJAMB

DOOR2.00

18.00

6.00PIT DEPTH

12.2512.09

86.02

DOOR

36.00

38.02

62.00 MILLWORK INTERIOR2.00

9.76

106.50 MIN RECESSED SLAB LENGTH

LIFT-U

209-838-2400

REVISIONSHEET NO.DOCUMENT NO.

910-0092 A

LIFT CONFIGURATION, 6" - 18" RISE

A DIVISION OF

2 OF 5

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

FURNISHED AND INSTALLED BY OTHERS.ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

REFERENCE ONLY

SECTION B-B

DOOR MUST CLOSE FLUSHWITH FASCIA BELOW UPPERLANDING SILL DOOR JAMB

CUTOUTFASCIA

INTERIOR

36.00

12.0018.00

MIN34.00

36.00

FLOOR

MILLWORK38.00

RECESSED6.00

FASCIA CUTOUT

4.75 MIN

38.00 MIN RECESSEDSLAB WIDTH

Page 52: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

FURNISHED AND INSTALLED BY OTHERS.ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

REFERENCE ONLY

LIFT-U

209-838-2400

REVISIONSHEET NO.DOCUMENT NO.

910-0092 A

A DIVISION OF

3 OF 5

LIFT CONFIGURATION, 6" - 18" RISE

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

SECTION C-C

ROLL-UP BARRIER:REFER TO DRAWING 910-0042FOR RECOMMENDED MILLWORKINTERFACE.

MILLWORK INTERIOR

PORTAL OPENING

36.00

4.00

12.00

21.0048.00

52.00

6.00

62.00

4.00

Page 53: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

D

PROVIDE AN ACCESS HATCH TO ENABLESERVICE ON MOTOR AND ELECTRONICSLOCATED BELOW UPPER LANDING.HATCH SHOULD BE NO LESS THAN 30" x 36".A REMOVABLE JOIST WITHIN THE FRAMEDHATCH OPENING SHOULD BE POSITIONEDTO REINFORCE THE HATCH COVER.

REVERSE ISOMETRIC VIEWBACK WALL AND DOORS NOT SHOWN FOR CLARITY

DETAIL D

ELECTRIC STRIKELATCH CUT INTODOOR JAMB

2 PLACES

WITNESS LEVEL 2+12" ELEV

THE LIFT. THOSE NECESSARY FOR THE OPERATION OF

ROLL-UP BARRIER IS STOWEDLEVEL FOR USE BY ABLE-BODIED PERSONS

PLATFORM SHOWN AT PARK

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE FURNISHEDAND INSTALLED BY OTHERS. BE ADVISED - ALLINTERIOR SURFACES MUST BE SMOOTH, i.e. NOPROTRUSIONS AND NO OPENINGS, OTHER THAN

PARK LEVEL+6" ELEV

PLATFORM SHOWN AT JUDGE LEVEL (3)READY FOR PASSENGER INGRESS OR EGRESS

ROLL-UP BARRIERMODULE

LIFT-U

209-838-2400

REVISIONSHEET NO.DOCUMENT NO.

910-0092 A

LIFT CONFIGURATION, 6" - 18" RISE

A DIVISION OF

4 OF 5

THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

DOORS ARE CLOSED AND LOCKED WHENPLATFORM RAISES AND LOWERS

MANUALLY OPERATED, SELF-CLOSING DOORS, i.e. w/SPRING HINGES.DOORS, SELF-CLOSING SPRING HINGES, ANDJAMBS ARE FURNISHED AND INSTALLED BY OTHERS.ELECTRIC STRIKE LATCHES, SPRING-LOADED LATCHBOLTS, AND ELECTRICAL INTERLOCK WIRING FURN-ISHED BY LIFT-U AND INSTALLED BY OTHERS.

FURNISHED AND INSTALLED BY OTHERS.ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

REFERENCE ONLY

THREE CONTROL STATIONS SUPPLIED BY LIFT-U.LOCATION AND WALL CUT INBY OTHERS. ELECTRICAL WIRINGFURNISHED BY LIFT-U.

PLATFORM SHOWN AT LOWER LEVEL (1)READY FOR PASSENGER INGRESS OR EGRESS

Page 54: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

61.00

2.00

31.38

33.00

99.52

2.00

37.00

DRIVE MOTOR

BY LIFT-U.

LIFT BASE FRAME ANCHORS TO PITFLOOR. ANCHOR BOLTS FURNISHED

JUDGE LEVEL (3) - TOPOF LIFT PLATFORMPLATE AT +18" ABOVECOURTROOM FLOOR

PERSPECTIVE VIEW

LIFT-U

LIFT CONFIGURATION, 6" - 18" RISEREVISIONSHEET NO.DOCUMENT NO.

910-0092 A

209-838-2400

5 OF 5

A DIVISION OF THIS DOCUMENT IS LOANED FOR THE LIMITED

THE PROPERTY OF THE COMPANY.PURPOSES STATED HEREIN ONLY, AND REMAINS

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.

P.O. BOX 398

ESCALON, CA. 95320

HOGAN MFG., INC.

FURNISHED AND INSTALLED BY OTHERS.ALL MILLWORK FRAMING AND VENEERED PANEL FINISHES ENCASING THE LIFT ARE

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATE LIFT-U'S RECOMMENDEDVMW LIFT / MILLWORK INTERFACE.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION.THEREFORE, FOR EACH PROJECT APPLICATION REFER TO ITS CORRESPONDINGLIFT CONFIGURATION DRAWING FOR GENERAL ARRANGEMENT LAYOUT AND LIFT ENVELOPE DIMENSIONS.

REFERENCE ONLY

LIFT ENVELOPE DIMENSIONS

COURTROOM FLOORLEVEL (1) +0" ELEV

18.00

12.00

2.33

12.25

24.00

12.09

6.00

6.00

Page 55: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

A

ELECTROMAGNETICDOOR HOLDER

COVER PLATE

CATCH PLATE

LOCATION OF DOOR HOLDER IS FOR ILLUSTRATION PURPOSES ONLY.

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

DOOR HOLDER / MILLWORK INTERFACE

1 OF 2 A910-0093

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

NOTES:

THIS DRAWING IS GENERIC AND PROVIDED TO ILLUSTRATELIFT-U'S RECOMMENDED ELECTROMAGNETIC DOOR HOLDER /MILLWORK INTERFACE. SEE SHEET 2 AND MANUFACTURER'SINSTRUCTIONS FOR INSTALLATION.

THE DIMENSIONS AND DETAILS WILL VARY FOR EACH APPLICATION,REFER TO ITS CORRESPONDING LIFT CONFIGURATION.

CLEARANCE AND/OR OPENINGS INSIDE THE MILLWORK WALLSMUST BE PROVIDED FOR ROUTING OF ELECTROMAGNETIC DOOR HOLDER WIRING.

REFER TO DRAWING 910-0026 FOR ADDITIONAL RECOMMENDEDMILLWORK WALL INTERFACE DESIGN PRINCIPLES.

ALL MILLWORK FRAMING AND VENEERED PANEL FINISHESENCASING THE LIFT, AS WELL AS DOORS / GATES AND JAMSARE FURNISHED AND INSTALLED BY OTHERS.

REVISIONS

REV ECO DESCRIPTION CREATED DATE APPROVED DATE

A RELEASED WAC 10-27-11

INSTALL PER MANUFACTURERE'SINSTRUCTIONS

DETAIL A

SINGLE GANG OUTLET BOX(SUPPLIED BY OTHERS)

ELECTROMAGNETICDOOR HOLDER

Page 56: LIFT APPLICATION GUIDELINES - Discover My Mobility · 2019-05-13 · For A18.1 regulations applicable to the other trades involved with either the VMW or VMX lift installation, refer

.69.69

1.97

1.80

1.79

2.16

REVISIONSHEET NO.DOCUMENT NO.

TITLE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIALTRADE SECRET INFORMATION OF THE COMPANY. NOPART OF IT MAY BE REPRODUCED, STORED IN ARETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORMOR BY ANY MEANS ELECTRONICALLY, PHOTOCOPYING,RECORDING OR OTHERWISE, WITHOUT THE PRIORWRITTEN PERMISSION OF HOGAN MFG, INC.THIS DOCUMENT IS LOANED FOR THE LIMITEDPURPOSES STATED HEREIN ONLY, AND REMAINSTHE PROPERTY OF THE COMPANY.

DOOR HOLDER / MILLWORK INTERFACE

2 OF 2 A910-0093

RR

HOGAN MFG., INC.

P.O. BOX 398

ESCALON, CA. 95320

209-838-2400

A DIVISION OF

R

LIFT-U

PERSPECTIVE VIEW OFELECTRIOMAGNETIC DOOR HOLDER

ELECTROMAGNETICDOOR HOLDER

CATCH PLATE

COVER PLATE

3.282.56 4.15