Upload
ajaykairi
View
214
Download
0
Embed Size (px)
Citation preview
7/28/2019 Lighting Voltage Supprestion in Gis
1/5
Approaches for Suppressing of Lightning
Overvoltage in the Gas-Insulated Substation (GIS)
AbstractGas-insulated substations (GIS) have different
specifications in proportion to air-insulated substations. Due to
space limitation in the field of the gas-insulated substation (GIS),
it is difficult to install extra arresters near the power
transformers. Voltage magnification is due to reflections oftransient waves in various junctions, low surge impedance and
decrease in the length of conductors in the GIS. These problems
cause to increase the propagation of transmitted and reflected
waves within the conductors in proportion to air-insulated
substation; thereby overvoltages in GIS are more important than
air-insulated substation. In air-insulated substations, probability
of failures across insulator strings or bushings is acceptable since
air insulation is self restoring. In GIS, the entire gas insulated
assembly must be protected because the gas insulated system
must be considered as non-self-restoring. According to
aforementioned reasons, it follows that insulation coordination
design of the GIS has been critically important. This paper
presents practicable and beneficial approaches to the industry to
look for the optimum approaches for lightning incoming surge
mitigation. These approaches are included effects of number of
surge arrester in the each feeder, system configuration and
decreasing of number of surge arrester and as costs, location of
surge arrester and cable, and terminal components. Lightning
overvoltages due to direct lightning stroke with varying intensity
current have been investigated. For accurate calculations,
ATP/EMTP software has been used.
Keywords- Insulation Coordination; lightning; gas insulated
substation (GIS); surge arrester; cable; the terminal component;
switchgear arrangement
I. INTRODUCTIONGas Insulated Substation (GIS) has been developed for
wide range, because of their benefits. These benefits are suchas compactness, protection from pollution, high reliability, a
few maintenance, etc [1]. Gas-Insulated Substations (GIS) are
exposed to the same variety of overvoltages as air-insulated
substations (i.e., lightning. switching, and temporary
overvoltages) [2].
However, in air-insulated stations, primary concern is placed
on the protection of transformers and some risk of failures
across insulator strings or bushings is accepted since air
Insulation is self restoring. In GIS on the other hand, theentire gas insulated assembly (including enclosures, circuit
breakers, disconnect and grounding switches) must be
protected because the gas insulated system must be viewed as
non-self-restoring. In the insulation coordination design of the
GIS, lightning overvoltages are found to be critically
important. Voltage magnification due to reflections of suchlightning surges at various junctions within the GIS is often
the determining criteria for selection of surge arrester rating
and locations [2].Though lightning surges have been reduced to an acceptable
level in modern substation insulation coordination, still
transformer failures related to lightning are often reported.
Two possible transformer failure modes may happen if a
lightning surge appears at the transformer terminals. The
transformer main insulation (the insulation between HV
winding and LV winding, HV winding and core, or HV
windings) will be threatened because of the large magnitude of
the lightning surge. On the other hand, the insulation between
turns at the beginning of the HV winding is oftendisproportionally more stressed because of the large potential
gradient appearing in the initial voltage distribution. Similar to
switching overvoltages and VFT, it is possible that lightning
overvoltage may excite partial winding resonance in the
transformer windings. The distance between the arrester and
the transformer will determine the overvoltage magnitude at
the transformer HV terminals [3],[4].Several factors may contribute to a transformer failure due to
lightning strokes including: 1) very high magnitude of the
overvoltage; 2) nonlinear voltage distribution along the
winding, which could result in high voltage between turns; 3)
Resonance or partial-winding resonance in the HV winding if
they coincide with the excitation frequencies [4],[5].This paper presents beneficial approaches to the industry to
look for the optimum approaches for lightning incoming surge
mitigation, including number of surge arrester, location of
surge arrester/cable, system configuration and decrease
number of surge arrester, the terminal component.
II. LIGHTNINGLightning overvoltage is a phase-to-ground or phase-to-phaseovervoltage produced by one specific lightning discharge. The
Ahmad Tavakoli
Iran University of Science and
Technology, Center of Excellence for
Power System Automation and
Operation, Tehran, Iran
Ahmad Gholami
Iran University of Science and
Technology, Center of Excellence for
Power System Automation and
Operation, Tehran, Iran
Ali Parizad
Iran University of Science and
Technology, Center of Excellence for
Power System Automation and
Operation, Tehran, [email protected]
978-1-4244-4813-5/10/$25.00 2010 IEEE
7/28/2019 Lighting Voltage Supprestion in Gis
2/5
lightning overvoltages have duration bet
microseconds and a wave front between 1 anThe wave shape of the lightning current is
voltage produced at the point of contact
stroke. The lightning condition and
specifications are shown in the table. I. Th
stroke current and its rate of decay were de
the guide lines given in References [2].
TABLE . THE LIGHTNING CONDITION AND THE APP
Peak Current (kA) 50 75 100
Time to Crest (s) 1.5 1.75 2.0
III. MODELING OF GIS COMTo model GIS components, lumped elemeparameters can be used, that is defined by
wave velocity and lengths of GIS section.
The surge arresters model recommended b
(IEEE Working Group 3.4.11, 1992) is sho
model the non-linear V-I characteristic is rep
sections of non-linear resistances designate
two non-linear resistances A0 and A1 are s
filter. For currents discharge in arrester witthe influence of the filter is negligible; th
essentially in parallel and characterize the
the MOSA. For the fast rising of su
impedance of the filter becomes more signi
inductance L1 derives more current into the
A0. Since A0 has a higher voltage for a givethe model generates a higher voltage b
terminals, what matches the dynamic
MOSAs. The inductance L0 represents
associated with the magnetic fields in the i
of the arrester. The resistor R0 is used tooscillations when running the model with
The capacitance C0 represents the ext
associated to the height of the arrester [8], [9
Figure 1. The IEEE Frequency-Dependant
Table.II shows the electrical equivalent circof GIS component [6]. Fig.2 shows the sing
a 420 kV GIS. Characteristics of the trans
and the electric power line and the ground
the table.III and Fig.3.
een 1 and 100
d 5 microseconds.different from the
of the lightning
the apparatus
e steepness of the
ermined based on
RATUS SPECIFICATION
150 200
2.25 2.5
ONENTS
ts and distributedurge impedances,
IEEE W.G3.4.11
n in Fig.1. In this
resented with two
d A0 and A1. The
parated by a R-L
slow rising time,s A0 and A1 are
static behavior of
ge currents, the
ficant, indeed the
non-linear branch
n current than A1,etween its input
characteristics of
the inductance
mmediate vicinity
avoid numericaldigital program.
rnal capacitance
], [10].
Model [8]
uits for mode lingle-line diagram of
ission line tower
ire are shown in
Figure 2. Single-line d
Figure 3. Transmissi
TABLE I. ELECTRICAL
Component
GIS Bus Bar
CB, DS, and Earthing Switch
Potential Transformer (PT)
Current Transformer (CT)
Capacitive Voltage Transformer
(CCVT)
Bushing
Power Transformer
Arrester
cable
CT
LA
T1
LA
PT
PT
CT
CT
PT
Transmi
Ca
iagram of a 420 kV GIS
n Line and Substation
QUIVALENT CIRCUIT[5],[6],[7]
Notes
z0 = 90 ohm
v = 270 m/us
In the closed position: impedance
(42 ohm)
In the open position: capacitance
(4pF)
300pF
300pF
5 nF
100pF
2 nF
Discharge Voltage (10kA):870kV
R0 = 0.0010679 ohm/m
z0 = 30 ohmv = 165m/us
CT
LA
LA
CT
T2
PT
PT
sion Line
ble
7/28/2019 Lighting Voltage Supprestion in Gis
3/5
TABLE II. SPECIFICATION OF TRANS
Conductor resistance at DC (with skin
effect) ohm/km
Power
Ground
Outer radius of one conductor
Power
Ground
Inner radius of one conductor. Only
available with skin effect
Power
Ground
Vertical bundle height at tower PowerGround
Vertical bundle height at mid-spanPower
Ground
Distance between conductors in a
bundle
Power
Ground
Angular position of one of the
conductors in a bundle
Power
Ground
Number of conductors in a bundlePower
Ground
The time step for simulation is 2.5 ns and
100s. Computer simulation has been
alternative transients program (ATP), a wide
EMTP. For simulation of surge arrester c
exponential current-dependent resistor
ATP/EMTP.
IV. EFFECT OF VARIOUS FACTDIRECT LIGHTNING S
In this section, lightning overvoltages
lightning that directly striking the transmissi
is corresponding to the situation where
opened and lightning is struck on the tower
(Fig. 3). Also, in order to simulation
condition, it is considered that lightning waphase A in tower No.2 and at the crest of
Table.IV describes the lightning overvoltage
intensity current at the power transformer,
near the lightning struck.
TABLE V. LIGHTNING OVERVOLT
Peak Current
(kA)
Transformer
(MV)
Tower
(kV)
50 1.1221 67.17
75 1.1401 101.19
100 1.2841 142.98
150 1.3573 208.61200 1.3635 274.96
These factors are included effects of the
arrester in the each feeder, system c
decreasing of number of surge arrester and
surge arrester and cable, terminal compon
resistance of tower. The impact of various
discussed above, were investigated undcurrent levels.
ISSION LINE
ine 0.069
Wire 0.44
ine 1.45cm
Wire 0.77cm
ine 0.7cm
Wire 0.5cm
ine 25.1mWire 39.7m
ine 10.1m
Wire 24.7m
ine 60cm
Wire 0cm
ine 45deg
Wire 0deg
ine 4
Wire 1
alculating time is
done using the
ly used version of
n be using ZnO-
(TYPE 92) in
ORS UNDER
ROKE
re simulated for
on line. This part
bus coupler was
o.2 from the GIS
under the worst
s happened on thenegative polarity.
s with the various
T, PT and tower
AGES
CT
(MV)
PT
(MV)
1.1361 1.3044
1.1584 1.3731
1.3208 1.4442
1.3544 1.56851.4049 1.6158
number of surge
onfiguration and
costs, location of
nt and grounding
odeling details as
r various stroke
A.Effect of Number of SurgeThis part is corresponding towas opened and lightning stru
the GIS (Fig. 3).The lightning
six cases.
Case(A-1): the arreste Case(A-2): the arr
transformer feeder, Case (A-3) : original
as Shown in Fig. 2
Case (A-4): an extrtransformer feeder ba
Case (A-5): an extrafeeder based on case (
Case (A-6): an extrtransformer feeder a
case (A-3).
Fig.4 shows the effect of nu
overvoltage at the power tran
lightning stroke. Its clear that
cause decreasing of the overvobserved that peak magnitude
power transformer terminal
current is fixed. Fig.5 shows cthe lightning overvoltage at t
The observed overvoltage at
can reach up much more than t
when the arresters are disabl
feeder. But disabled arresters
than disabled arresters in thexistence of arrester at the i
Fig.5, case (A-3) shows clearl
transformer terminal is still v
and can be up to 4.21 Pu. It isarrester installed, the lightnin
transformer terminal is still hithe studied case. Hence, ins
necessary for suppressing har
Figure 4. Effects of number of surge
transformer due to direct lightning stro
the line feeder, case (A-2): the arrestercase (A-3): original arrester configura
(A-4): an extra arrester is installed in t
3), case (A-5: an extra arrester is insta3) and case (A-6) is that an extra arres
and in the line feeder based on case (A
Arrester
he situation where bus couplerk on the tower No.2 away from
overvoltages are investigated in
rs are disabled in the line feeder
sters are disabled in the
arrester configuration is applied
a arrester is installed in the
ed on case (A-3),
arrester is installed in the line
A-3)
a arrester is installed in the
d in the line feeder based on
mber of surge arrester on the
sformer terminal due to direct
existence of extra arrester can
oltage. In the cases 4, 5, 6 areof overvoltage variation at the
with increasing of lightning
learly effect of extra arrester one power transformer terminal.
he power transformer terminal
he transformer BIL of 1230 kV,
ed in the line and transformer
in the line feeder can be worse
transformer feeder. Howevercoming feeder is emphasized.
y that the voltage at the power
ery high because of reflection,
orth noting, that even with theovervoltage seen at the power
her than the transformer BIL inalling extra surge arresters is
ful lightning overvoltages.
rrester on the overvoltage at the power
ke. Case (A-1): arresters are disabled in
s are disabled in the transformer feeder,ion is applied as Shown in Fig. 2, case
e transformer feeder based on case (A-
led in the line feeder based on case (A-ter is installed in the transformer feeder
-3).
7/28/2019 Lighting Voltage Supprestion in Gis
4/5
Figure 5. Effects of extra arrester on the lightni
B.Effect of System ConfigurationInstalling extra surge arresters is necessar
harmful lightning overvoltages. But it is
extra arresters near transformers due to spac
site.
In order to suppressing harmful lightning otransformer terminals, it can be used an
installation of extra arresters. In this waycircuit breaker of bus coupler; on the other h
associated with together and more tran
connected to the substation. In this sectovervoltages are investigated in three cases.
Case (B-1): the arresters are disfeeder and bus coupler is closed
Case (B-2): the arresters aretransformer feeder and bus coupler
Case (B-3): original arrester conand bus coupler is closed.
Fig.6 shows effect of system configuration
at the power transformer terminal when bus
If bus coupler is closed, the lightnintransformer terminals can be reduced to a le
in the studied case. Fig.7 compares effects onew configuration (bus coupler is closed
associated with together). Its clear that c
than case (A-4) and case (A-5). H
configuration is better than even extra arrest
With more transformers connected to tharresters must be also connected to the GI
absorbing more lightning energy by the a
cause to reduce the maximum overv
transformer terminal.
g overvoltage.
for suppressing
ifficult to install
e limitation in the
vervoltages at theapproach without
ne can be closedand, all of feeders
sformers can be
ion the lightning
abled in the line
disabled in the
is closed
iguration applied
nthe overvoltagecoupler is closed.
overvoltage atel below the BIL
extra arrester andor all of feeders
se (B-3) is lower
nce, appropriate
r in the feeder.
e network, more, it is helpful for
rresters; hence, it
oltages at each
Figure 6. Effects of System Configutransformer terminal when bus couple
disabled in the line feeder and bus co
are disabled in the transformer feederoriginal arrester configuration is appl
(A-3) is that original arrester configura
Figure 7. Compares etween effect
configuration (bus coupler is closed or
C.Effect of Location of SurgeDue to absorbing more lightni
negative reflection of cable,ef
and cable is imported. This
situation where bus coupler
on the tower No.2 away fro
arrester configuration is app
lightning overvoltages are inve
Case(C-1): the surgincoming cable
Case(C-2): the surgeincoming cable.
Case(C-3): the surgeincoming cable
Case(C-4): the surgeincoming cable
Case (C-5): the surincoming cable.
Fig.8 shows effect of location
the overvoltage at the powerwhen the surge arrester is pl
lightning overvoltages are
reflection.
Figure 8. Effects of location of surge
power transformer terminal. Case (C-
incoming cable, Case (C-2): the surge
ation on the overvoltage at the poweris closed. Case (B-1): the arresters are
pler is closed, Case (B-2): the arresters
and bus coupler is closed, Case (B-3):ed and bus coupler is closed and case
tion applied as Shown in Fig.2.
of extra arrester and effect of new
all of feeders associated with together)
Arrester and Cable
ng energy by the arresters and
fect of location of surge arrester
ection is corresponding to the
as opened and lightning struck
m the GIS (Fig. 3). Original
lied as shown in Fig.2. The
stigated in five following cases.
arrester situated in next of
arrester situated in 3/4 after
arrester situated in 2/4 after
arrester situated in 1/4 after
ge arrester situated in before
of surge arrester and cable ontransformer terminal. Its clearced before of incoming cable,
decreased due to negative
rrester and cable onovervoltage at the): the surge arrester situated innext ofarrester situated in3/4 after incoming
7/28/2019 Lighting Voltage Supprestion in Gis
5/5
cable Case (C-3): the surge arrester situated in2/4 afte(C-4): the surge arrester situated in1/4 after incomingsurge arrester situated inafter incoming cable.
D.Effect of the Terminal ComponentThe peak magnitude of lightning overvolta
terminals depends on the terminal compone
GIS. The terminal component can be an
overhead transmission line or a gas-insulate
(GITL). To understand the effect of differe
the peak magnitude of the lightning ovesubstation layouts have been considered and
V. The attenuation of the lightning overv
with time is found to depend on the switc
and the terminal component connected to the
Fig.9 shows variation in peak magnitudes
overvoltages for various substation layouts.
The attenuation rate is high if the GIS is teimpedance systems, such as XLPE cable, a
rate is low if the GIS is terminated with hig
elements such as an overhead line. Similar
terminated with a long length of GITL, ther
the transient currents for longer time durati
be noted that effect of the cable is more effeovervoltage peak than adding more arresters.
Figure 9. variation in peak magnitudes of the lightvarious substation layouts.
TABLE V. VARIOUSSUBSTATIONLAYOUTSFOR
Substation
Layouts
The Terminal Co
D-1 Overhead Li
D-2 GITL
D-3 XLPE Cab
D-4 Two XLPE Cable i
IV. CONCLUSION
Installing extra surge arresters isuppressing harmful lightning overv
difficult to install extra arresters near t
space limitation in the site.
In order to suppressing harmful lightnithe transformer terminals, it can be
without installation of extra arresters. I
be closed circuit breaker of bus co
incoming cable, Casecable, Case (C-5): the
es at transformer
t connected to the
LPE cable or an
transmission line
t terminations on
voltages, variousare listed in table
oltages amplitude
ing configuration
GIS.
of the lightning
minated with lownd the attenuation
surge impedance
ly, if the GIS are
is a possibility of
on [11]. It should
ctive to reduce the
ning overvoltages for
IFFERENTTERMINALS
mponent
ne
le
n Parallel
necessary for
ltages. But it is
ansformers due to
g overvoltages at
sed an approach
this way one can
pler; With more
transformers connected
must be also connectedabsorbing more lightning
it reduce to a level below
When the surge arrestercable, lightning overvo
negative reflection.
It should be noted thateffective to reduce the
more arresters. When
impedance becomes sm
overvoltage appearing a
reduced dramatically due
The attenuation rate is hilow impedance systems,
attenuation rate is low if
surge impedance eleme
Similarly, if the GIS are t
GITL, there is a possibil
longer time duration.
REFE
[1] C.Y. Lui J. Hiley Computatiowith special reference to effecovervoltage amplitude IEEETr1994.
[2] H. Elahi, M. Sublich, M.E.overvoltage protection of thesubstation, IEEE Transactions50, Jan. 1990.
[3] A. Greenwood, Electrical TransYork: Wiley, 1991, pp. 548554.
[4] Xuzhu Dong,Sebastian RosadoLine, Tzong-Yih Guo, "StudyEffects on GSU Transformers"vol. 18, NO. 3, JULY 2003
[5] J. P. Bickford and A. G. Heatsystems, Proc. Inst. Elect. En1986.
[6] Task Force on Very Fast Transifor very fast transients, IEEEpp.20282035, Oct. 1996.
[7] Z. Haznadar, S.CarSimamoviModeling of Gas Insulated Substof Very Fast ElectromagneticDelivery, Vol. 7 No.1, January 1
[8] IEEE working group 3.4.11, MIEEE Trans. Power Delivery, vol
[9] F. Fernndez, R. Daz, Metatransient simulations paper 14system transients, IPST01, 20 -2
[10] A. BAYADI1, N. HARID 2, K.of metal oxide surge arrester dThe international Conference onin New Orleans, USA
[11] M. Mohana Rao, M. Joy TCharacteristics of Very Fast TraTransactions on Power Delivery,
o the network, more arresters
to the GIS, it is helpful forenergy by the arresters; hence,
the BIL in the studied case.
is placed before of incoming
ltages are decreased due to
effect of the cable is moreovervoltage peak than adding
the equivalent cable surge
aller, the peak value of the
t the transformer terminals is
to negative reflection.
h if the GIS is terminated with
such as XLPE cable, and the
the GIS is terminated with high
ts such as an overhead line.
erminated with a long length of
ity of the transient currents for
ENCES
al study of very fast transients in GISts of trapped charge and risetime onns. Distrib, Vol. 141, No. 5, September
Anderson, B.D. Nelson, LightningPaddock 362-145 kV gas-insulated
n Power Delivery, vol.5, no.1, pp.144-
ients in Power Systems, 2nd ed. New
, Yilu Liu,Nien-Chung Wang,E-Lenyof Abnormal Electrical Phenomena
EEE Transactions on Power Delivery,
n, Transients overvoltages on power., pt. C, vol. 133, pp. 201225, May
nts, Modeling and analysis guidelinesTrans. Power Delivery, vol. 11, no. 4,
, R. Mahmutkehajif ,"More Accurateation Component in Digital Simulations
Transients" Transactions on Power92.
odeling of metal oxide surge arresters,. 7, pp. 302309, Jan. 1992.
l-oxide surge arrester model for fast4, International conference on power4 June 2001.
EHAR 1, S. BELKHIAT, Simulationnamic behavior under fast transientsPower Systems Transients - IPST 2003
omas, and B. P. Singh Frequencysient Currents in a 245-kV GIS IEEEvol. 20, NO. 4, OCTOBER 2005.