Lightning overvoltage protection of combined overhead line and underground cable distribution network Božidar Filipović-Grčić, PhD Prof. Ivo Uglešić Faculty of Electrical Engineering and Computing University of Zagreb, Croatia 9 th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas 1

Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

Lightning overvoltage protection of combined overhead line and

underground cable distribution network

Božidar Filipović-Grčić, PhD

Prof. Ivo Uglešić

Faculty of Electrical Engineering and Computing

University of Zagreb, Croatia

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas 1

Page 2: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

2

Presentation outline

Introduction

Model of distribution network in EMTP-ATP

Simulation of lightning overvoltages including direct lightningstroke to tower and phase conductor

Simulation results

Analysis of data from lightning location system

Conclusions

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 3: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

3

Introduction (1)

The increasing demand of utility customers for stability of thepower supply has stressed the importance of improving thereliability and power quality in the distribution network.

Lightning is a major cause of faults on overhead lines, so it isessential to evaluate the lightning electromagnetic environmentin order to mitigate its effects and improve the power systemreliability.

Transient faults are usually acceptable by the consumers, exceptin cases where the loads are very sensitive to short timeinterruptions or voltage dips.

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 4: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

4

Introduction (2)

Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software.

Mixed overhead line and underground cable distribution network supplying an industrial consumer.

An open end of a cable was considered in the simulations as the most unfavorable switching configuration.

An optimal overvoltage protection was selected which significantly improves the overvoltage protection of the cable.

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 5: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

5

Combined overhead line and underground cable distribution network

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

110 kV 35 kV A B

AlFe 3x120/20 mm2 XHE-49 A

3x(1x240) mm2

Substation

Overhead line Cable

35 kV overhead line with steel lattice towers and a single shield wire

35 kV cable with cross-linked polyethylene (XLPE) insulation

9.63 km 9.2 km

Page 6: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

6

Model of distribution network in EMTP-ATP

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Uzemljivac

LCC LCC

Polim H

MO

VP

E

LCCLCCLCCV VLCC

+

V

VN-M

U

SN-M

U

NN-M U

RayUr=36 kV

MO

VP

E

Uzemljivac

CCI

Udar munje

35 kV DV Ivanic Grad - Zutica

TR2 110/35 kV

35 kV KB Zutica-OkoliTS Ivanic Grad

35 kV transmission line

Lightning current

35 kV

underground

cable

Substation 110/35 kV

The overhead line and cable were represented by thefrequency-dependent model in EMTP-ATP.

The equipment in high voltage substation were represented bysurge capacitances obtained from manufacturer’s data.

Page 7: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

The lightning stroke (hitting a tower or a phase conductor) wasrepresented by a CIGRE concave shape.

The peak current magnitude and the tail time are important whenobserving the arrester energy. Front time is an important parameterwith regard to the insulator flashover.

The CIGRE shape represents more accurately the concave front of alightning stroke and usually gives more realistic results.

7

Lightning current

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 8: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

8

Transmission line tower model

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

The tower surge impedance depends onthe direction of wave propagation and theshape of a lightning current.

An approximation of surge impedanceequation is determined by equivalentlyreplacing the tower with a cylinder:

where H represents the tower height and Rthe equivalent radius of a tower base.

Uzemljivac

LCC LCC

Polim H

MO

VP

E

LCCLCCLCCV VLCC

+

V

VN-M

U

SN-M

U

NN-M URayUr=36 kV

MO

VP

E

Uzemljivac

CCI

Udar munje

35 kV DV Ivanic Grad - Zutica

TR2 110/35 kV

35 kV KB Zutica-OkoliTS Ivanic Grad

35 kV transmission line

Lightning current

35 kV

underground

cable

Substation 110/35 kV

= 1ln60

R

HZ

Page 9: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

9

Insulator flashover - Leader Propagation Model

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

lg U(t)

Leader

−== 10

)()( E

lg

tUtUk

dt

dlv l

The flashover mechanism of the overhead line insulators wasrepresented with differential equation of the leader propagationmodel recommended by the CIGRE WG 33-01:

v – leader velocity (m/s);U(t) - voltage across the gap (kV);g - gap length (m);l - leader length (m);E10 - critical leader inception gradient (kV/m);kl - leader coefficient (m2V-2s-1).

Page 10: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

The ionization model takes into account the soil ionization causedby the lightning currents.

Tower grounding non-linear resistor should be represented as:

10

Tower footing resistance model – soil ionization

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

+

=

g

i

I

I

RR

1

0

Arc StreamerElectrolytic

conductivity

Constant

conductivityEarth surface

R0 - footing resistance at low current and lowfrequency, i.e. 50 or 60 Hz;I - stroke current through the resistance;Ig - limiting current to initiate sufficient soilionization.

Page 11: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

Limiting current to initiate sufficient soil ionization:

119th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

ρ- soil resistivity (Ωm);E0 - is the soil ionization gradient, recommended value: 400 (kV/m).

2

0

0

2 R

EI g

=

Tower grounding was represented as a non-linear resistor usingMODELS language and TACS-controlled time-dependent resistorin EMTP-ATP.

Tower footing resistance model – soil ionization

Page 12: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

SAs with continuous operating voltage Uc=30 kV, rated voltageUr=37.5 kV and energy class 4 (13.3 kJ/kV(Uc)) were considered insimulations.

U-I characteristic of SA for impulse current waveform 8/20 µs:

The SA leads were represented by the inductance of 1 μH/mtaking into account the effects of additional voltage rise acrossthe lead inductance.

129th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Gapless type surge arresters (SA)

Current [kA] 2 5 10 20 40Voltage [kV 79.5 83.4 87.0 94.9 106.2

Page 13: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

13

Simulation of different overvoltage protection scenarios

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Lightning strikes the upper phase conductor and a shield wire atthe first tower close to the beginning of the cable section.

Three different overvoltage protection scenarios were analyzed:

1) no SAs installed;2) SAs installed at the beginning of a cable;3) SAs installed at the beginning and at the end of a cable.

The most severe switching condition was considered: openedcircuit breaker at the end of cable.

Page 14: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

14

Simulation resultsLightning stroke to tower

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 15: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

15

Scenario 1): no SAs installed

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 6 Lightning current

150 kA, 9.8/77.5 μs

Fig. 7 Overvoltages on the insulator strings of

the struck tower (flashover in all phases)

Fig. 8 Overvoltages at the beginning of the

cable (Umax=272.8 kV)

Fig. 9 Overvoltages at the end of the cable

(Umax=456.0 kV)

(f ile Iv anicGrad35.pl4; x-v ar t) c:XX0043-XX0007

0,00 0,04 0,08 0,12 0,16 0,20[ms]

0

30

60

90

120

150

[kA]

(f ile Iv anicGrad35.pl4; x-v ar t) v :XX0047-X0004A v :XX0045-X0004B v :XX0055-X0004C

0 4 8 12 16 20[us]

-50

0

50

100

150

200

250

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0022A v :X0022B v :X0022C

0,00 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40[ms]

-200

-100

0

100

200

300

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0023A v :X0023B v :X0023C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-300

-200

-100

0

100

200

300

400

500

[kV]

Lightning current 150 kA, 9.8/77.5 µs

Overvoltages on the insulator strings of the struck tower (flashover in all phases)

Page 16: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

16

Scenario 1): no SAs installed

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 6 Lightning current

150 kA, 9.8/77.5 μs

Fig. 7 Overvoltages on the insulator strings of

the struck tower (flashover in all phases)

Fig. 8 Overvoltages at the beginning of the

cable (Umax=272.8 kV)

Fig. 9 Overvoltages at the end of the cable

(Umax=456.0 kV)

(f ile Iv anicGrad35.pl4; x-v ar t) c:XX0043-XX0007

0,00 0,04 0,08 0,12 0,16 0,20[ms]

0

30

60

90

120

150

[kA]

(f ile Iv anicGrad35.pl4; x-v ar t) v :XX0047-X0004A v :XX0045-X0004B v :XX0055-X0004C

0 4 8 12 16 20[us]

-50

0

50

100

150

200

250

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0022A v :X0022B v :X0022C

0,00 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40[ms]

-200

-100

0

100

200

300

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0023A v :X0023B v :X0023C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-300

-200

-100

0

100

200

300

400

500

[kV]

Overvoltages at the beginning of the cable (Umax=272.8 kV)

Overvoltages at the end of the cable (Umax=456.0 kV)

Lightning-impulse withstand voltage of the cable: 142 kV.

Page 17: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

17

Scenario 2): SAs installed at the beginning of a cable

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 10 Overvoltages at the beginning of the

cable (Umax=98.3 kV)

Fig. 11 Overvoltages at the end of the cable

(Umax=192.7 kV)

Fig. 12 SA energy (Emax=85.9 kJ)

Fig. 13 Currents through SAs (Imax=10.6 kA)

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0013A v :X0013B v :X0013C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-70

-36

-2

32

66

100

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-150

-100

-50

0

50

100

150

200

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0013A-X0005A e:X0013B-X0005B e:X0013C-X0005C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

15

30

45

60

75

90

[kJ]

(f ile Iv anicGrad35.pl4; x-v ar t) c:X0013A-X0005A c:X0013B-X0005B c:X0013C-X0005C

0,00 0,05 0,10 0,15 0,20 0,25[ms]

-2

0

2

4

6

8

10

12

[kA]

Overvoltages at the beginning of the cable (Umax=98.3 kV)

Overvoltages at the end of the cable (Umax=192.7 kV)

Lightning-impulse withstand voltage of the cable: 142 kV.

Page 18: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

18

Scenario 2): SAs installed at the beginning of a cable

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 10 Overvoltages at the beginning of the

cable (Umax=98.3 kV)

Fig. 11 Overvoltages at the end of the cable

(Umax=192.7 kV)

Fig. 12 SA energy (Emax=85.9 kJ)

Fig. 13 Currents through SAs (Imax=10.6 kA)

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0013A v :X0013B v :X0013C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-70

-36

-2

32

66

100

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-150

-100

-50

0

50

100

150

200

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0013A-X0005A e:X0013B-X0005B e:X0013C-X0005C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

15

30

45

60

75

90

[kJ]

(f ile Iv anicGrad35.pl4; x-v ar t) c:X0013A-X0005A c:X0013B-X0005B c:X0013C-X0005C

0,00 0,05 0,10 0,15 0,20 0,25[ms]

-2

0

2

4

6

8

10

12

[kA]

SA energy(Emax=85.9 kJ)

SA currents (Imax=10.6 kA)

Surge arrester energy capability: 13.3 kJ/kV(Uc) = 399 kJ

Page 19: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

19

Scenario 3): SAs installed at both cable ends

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 14 Overvoltages at the beginning of the

cable (Umax=98.3 kV)

Fig. 15 Overvoltages at the end of the cable

(Umax=86.3 kV)

Fig. 16 SA energy at the beginning of the cable

(Emax=32.9 kJ)

Fig. 17 SA energy at the end of the cable

(Emax=61.9 kJ)

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0013A v :X0013B v :X0013C

0,00 0,05 0,10 0,15 0,20 0,25 0,30[ms]

-20

0

20

40

60

80

100

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-30

-15

0

15

30

45

60

75

90

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0024A-X0045A e:X0024B-X0045B e:X0024C-X0045C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

5

10

15

20

25

30

35

[kJ]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0013A-X0005A e:X0013B-X0005B e:X0013C-X0005C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

10

20

30

40

50

60

70

[kJ]

Overvoltages at the beginning of the cable (Umax=98.3 kV)

Overvoltages at the end of the cable (Umax=86.3 kV)

Lightning-impulse withstand voltage of the cable: 142 kV.

Page 20: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

20

Scenario 3): SAs installed at both cable ends

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 14 Overvoltages at the beginning of the

cable (Umax=98.3 kV)

Fig. 15 Overvoltages at the end of the cable

(Umax=86.3 kV)

Fig. 16 SA energy at the beginning of the cable

(Emax=32.9 kJ)

Fig. 17 SA energy at the end of the cable

(Emax=61.9 kJ)

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0013A v :X0013B v :X0013C

0,00 0,05 0,10 0,15 0,20 0,25 0,30[ms]

-20

0

20

40

60

80

100

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-30

-15

0

15

30

45

60

75

90

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0024A-X0045A e:X0024B-X0045B e:X0024C-X0045C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

5

10

15

20

25

30

35

[kJ]

(f ile Iv anicGrad35.pl4; x-v ar t) e:X0013A-X0005A e:X0013B-X0005B e:X0013C-X0005C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

0

10

20

30

40

50

60

70

[kJ]

SA energy at the beginning of the cable (Emax=32.9 kJ)

SA energy at the end of the cable (Emax=61.9 kJ)

Surge arrester energy capability: 13.3 kJ/kV(Uc) = 399 kJ

Page 21: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

21

Simulation results – lightning stroke to tower

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Scenario

Insulator flashover at the struck

tower

Overvoltages at the

beginning of the cable

Overvoltages at the end of

the cable

SA energy at the

beginning of the cable

SA energy at the end of the cable

1) No SAs installedYes, phases

A, B, C272.8 kV 456.0 kV - -

2) SAs at the beginning of a

cable

Yes, phases A, B, C

98.3 kV 192.7 kV 85.9 kJ -

3) SAs at the beginning and at

the end of a cable

Yes, phases A, B, C

98.3 kV 86.3 kV 61.9 kJ 32.9 kJ

Lightning-impulse withstand voltage of the cable: 142 kV.

Page 22: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

22

Simulation resultsLightning stroke to upper phase conductor

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Page 23: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

23

Lightning stroke to upper phase conductor

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 18 Lightning current 17.8 kA, 3/77.5 μs

Fig. 19 Overvoltages on the insulator strings of

the struck tower (flashover in upper phase A)

Fig. 20 Overvoltages at the beginning of the

cable (Umax=70.8 kV)

Fig. 21 Overvoltages at the end of the cable

(Umax=95.04 kV)

(f ile Iv anicGrad35.pl4; x-v ar t) c:XX0045-X0004A

0,00 0,02 0,04 0,06 0,08 0,10 0,12 0,14 0,16[ms]

-2

2

6

10

14

18

[kA]

(f ile Iv anicGrad35.pl4; x-v ar t) v :XX0049-X0004A v :XX0047-X0004B v :XX0057-X0004C

0 1 2 3 4 5[us]

-500

-400

-300

-200

-100

0

100

200

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0023A v :X0023B v :X0023C

0,00 0,05 0,10 0,15 0,20 0,25 0,30[ms]

-30

-8

14

36

58

80

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-60

-40

-20

0

20

40

60

80

100

[kV]

Lightning current 17.8 kA, 3/77.5 µs

Overvoltages on the insulator strings of the struck tower (flashover in upper phase A)

According to the electro-geometric model of the overhead linethe highest (critical) lightning current that can hit the upperphase conductor is 17.8 kA.

Page 24: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

24

Lightning stroke to upper phase conductor

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Fig. 18 Lightning current 17.8 kA, 3/77.5 μs

Fig. 19 Overvoltages on the insulator strings of

the struck tower (flashover in upper phase A)

Fig. 20 Overvoltages at the beginning of the

cable (Umax=70.8 kV)

Fig. 21 Overvoltages at the end of the cable

(Umax=95.04 kV)

(f ile Iv anicGrad35.pl4; x-v ar t) c:XX0045-X0004A

0,00 0,02 0,04 0,06 0,08 0,10 0,12 0,14 0,16[ms]

-2

2

6

10

14

18

[kA]

(f ile Iv anicGrad35.pl4; x-v ar t) v :XX0049-X0004A v :XX0047-X0004B v :XX0057-X0004C

0 1 2 3 4 5[us]

-500

-400

-300

-200

-100

0

100

200

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0023A v :X0023B v :X0023C

0,00 0,05 0,10 0,15 0,20 0,25 0,30[ms]

-30

-8

14

36

58

80

[kV]

(f ile Iv anicGrad35.pl4; x-v ar t) v :X0024A v :X0024B v :X0024C

0,0 0,1 0,2 0,3 0,4 0,5[ms]

-60

-40

-20

0

20

40

60

80

100

[kV]

Overvoltages at the beginning of the cable (Umax=70.8 kV)

Overvoltages at the end of the cable (Umax=95.04 kV)

No SAs installed.

Lightning-impulse withstand voltage of the cable: 142 kV.

Page 25: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

25

Simulation results – lightning stroke to upper phase conductor

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Scenario

Insulator flashover at the struck

tower

Overvoltages at the

beginning of the cable

Overvoltages at the end of

the cable

SA energy at the beginning of the cable

SA energy at the end of the cable

1) No SAs installed

Yes, phasesA, B, C

70.8 kV 95.0 kV - -

2) SAs at the beginning of a

cable

Yes, phases A, B, C

64.4 kV 85.5 kV 1.9 kJ -

3) SAs at the beginning and at

the end of a cable

Yes, phases A, B, C

64.4 kV 73.5 kV 1.4 kJ 1.9 kJ

Page 26: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

26

Data from lightning location system (1)

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

The lightning activity around 35 kV overhead line (9.63 km long)was observed for a 7 year period within an alarm zone radius of2 km (surface of 50.71 km2).

The data were obtained from the LINET lightning location system(LLS).

An algorithm was developed to group lightning strokes into flashes(lightning stroke multiplicity) in order to determine the currentprobability distribution of the first and subsequent CG strokes.

The multiplicity was calculated for a maximum temporal separationof 200 ms and a maximum lateral distance of 2 km betweensuccessive strokes.

Page 27: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

279th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

FMF - Flash Multiplicity Factor;Ngf - the lightning flash density;Ngs - the lightning stroke density.

Data from lightning location system (2)

Page 28: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

289th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

Number of CG and IC lightning strokes detected by LLS around 35 kV overhead line

Data from lightning location system (3)

Page 29: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

299th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

CG negative lightning strokes CG positive lightning strokes

Data from lightning location system (4)

Page 30: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

309th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

There is a significantly higher probability of lightning strokesoccurrence with lower current amplitudes, compared to CIGREdata.

This difference is caused by the sensitivity of LLS which iscapable of detecting multiple CG strokes with low currentamplitudes.

LLS gives lower median values of current amplitudes both forfirst and subsequent strokes.

Data from lightning location system (5)

Page 31: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

31

Conclusions (1)

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

An optimal overvoltage protection was selected including theinstallation of surge arresters at both cable ends whichsignificantly improves the overvoltage protection of the cable.

Lightning parameters derived from the LINET lightning locationsystem were analyzed and compared to the ones used inliterature.

The analysis of the LLS data showed that the lightning currentparameters used in the simulations were conservative and onthe “safe side”.

Page 32: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

32

Conclusions (2)

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

The selected surge arrester with Uc=30 kV, Ur=37.5 kV andenergy class 4 can withstand energy stress caused by multiplelightning strokes with relatively high amplitudes and long tailtimes.

Induced overvoltages were not analyzed but in some cases theymay also cause an insulator flashover.

This can be prevented by installing line surge arresters (LSAs) inorder to reduce the number of overhead line outages.

Page 33: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

33

References

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas

CIGRE Working Group 01 (Lightning) of Study Committee 33 (Overvoltages and InsulationCoordination), “Guide to Procedures for Estimating the Lightning Performance of Transmission Lines”,brochure 63, October 1991.

IEC 60071-2: “Insulation co-ordination - Part 2: Application guide”, 1996. IEC/TR 60071-4, “Insulation co-ordination - Part 4: Computational guide to insulation co-ordination and

modelling of electrical networks”, 1st edition, 2004. A. Piantini, “Lightning protection of overhead power distribution lines”, 29th International Conference

on Lightning Protection Uppsala, Sweden, June 2008. M. Paolone, C. A. Nucci, E. Petrache, F. Rachidi, “Mitigation of Lightning-Induced Overvoltages in

Medium Voltage Distribution Lines by Means of Periodical Grounding of Shielding Wires and of SurgeArresters: Modeling and Experimental Validation”, IEEE Transactions on Power Delivery, Vol. 19, No. 1,pp. 423-431, January 2004.

D. Filipović-Grčić, B. Filipović-Grčić, I. Uglešić, “Lightning Critical Flashover Voltage of High VoltageInsulators: Laboratory Measurements and Calculations”, International Review of Electrical Engineering,vol. 7, no. 2 - part B, pp. 4321-4328, 2012.

I. Uglešić, V. Milardić, B. Franc, B. Filipović-Grčić, J. Horvat, “Establishment of a new lightning locationsystem in Croatia”, CIGRE C4 International Colloquium on Lightning and Power Systems, Kuala Lumpur,Malaysia, 2010.

B. Franc, I. Uglešić, B. Filipović-Grčić, “Application of Lightning Location System Data for Designing theExternal Lightning Protection System”, CIGRE International Colloquium on Lightning and Power Systems,Lyon, France, 2014.

H.-D. Betz, K. Schmidt, B. Fuchs, W. P. Oettinger, H. Höller, “Cloud Lightning: Detection and Utilizationfor Total Lightning measured in the VLF/LF Regime”, Journal of Lightning Research, Vol. 2, pp. 1-17,2007.

Page 34: Lightning overvoltage protection of combined overhead line ...4 Introduction (2) Lightning overvoltages in a 35 kV distribution network were calculated by using the EMTP-ATP software

This work has been supported in part by the Croatian Science Foundation under the project “Development of advanced high

voltage systems by application of new information andcommunication technologies” (DAHVAT).

Božidar Filipović-Grčić, PhD

Prof. Ivo Uglešić

Faculty of Electrical Engineering and Computing

University of Zagreb, Croatia

9th Annual Grounding & Lightning Conference, October 3 - 4, 2017 • San Antonio,Texas 34

THANK YOU FOR YOUR ATTENTION