LNG TERMINAL

COMPATABILITY

DOCUMENT

Page 2: LNG Compatibility Document - Full Doc

SHIP SHORE LINK SYSTEMS Seatechnik has compiled the following document and are manufactures of Ship-Shore Link Systems. These systems are fitted to certain LNG terminals and ships in order to enable Shore-ship, and in most cases, ship-shore emergency shutdown. They also enable telecommunication and in some cases analogue control signal and/or data transmission between ship and shore. The information contained within this document is compiled using the best available information from several sources and is made available in the interests of maintaining ship-shore compatibility amongst the many types of system, connector and configuration which are in use world-wide. It cannot be guaranteed as 100% correct and users must make their own enquiries before acting on the information contained herein. Any corrections or additional information will be welcomed and included in future updates. Contents • Index of LNG Terminals and Emergency Shutdown Systems and Ship-Shore

Link systems fitted • Fibre-optic connector SSL System • Pyle National SSL-ESD system - pin configuration for LNGC Terminals • Miyaki Connector SSL-ESD system - pin configuration for LNGC Terminals • ‘ITT Cannon’ Connector SSL System - Pin Configuration for LNGC Terminals

Email: [email protected] +44 1244 539635 Fax +44 1244 539880

Airfield View, Hawarden Industrial Estate,

Hawarden, Deeside, UK CH5 3QW

FO Connector (29-1-10).doc 29/01/2010

Page 3: LNG Compatibility Document - Full Doc

FIBREOPTIC CONNECTOR SSL SYSTEM

The communication signals are

Signal Direction Optical Fibre number

4 channel Telephone/Data Audio

Ship-shore 1

4 channel Telephone/Data Audio

Shore-ship 2

ESD volt free Circuit Ship-shore 3

ESD volt free Circuit Shore-ship 4

Spare Ship-shore 5

Spare Shore-ship 6

Telephone Channel allocation:

CH1 MLM Modem signal 1200 baud

CH2 Interphone audio signal (Hotline Telephone), Iwatsu TS3 format only supported

CH3 Terminal Public telephone audio signal,

CH4 Terminal PABX (Internal) telephone audio signal.

(last updated 11/10/07) The Ship Shore Link was developed for Japanese receiving terminals in 1989 by Sumitomo and later by Furukawa. Seatechnik developed a system in 1996 which was certified by Oman LNG as compatible. The system uses a 6-way fibre-optic connector to carry full duplex signals as: • 4 channels of Telephone/Data • Ship-shore and shore-ship emergency

shutdown ESD

The configuration of all plant and shore systems is the same although not all facilities, (such as MLM) are supported by all terminals

FO Connector (29-1-10).doc 29/01/2010

Page 4: LNG Compatibility Document - Full Doc

PYLE NATIONAL SSL-ESD SYSTEM - PIN CONFIGURATION FOR LNGC TERMINALS (Updated 20-06-06) Original System developed by El Paso corp in 1976 using Pyle National Connectors, type A, manufactured to National Electric Flameproof standards for Class 1 Divn 1 Group C & D hazardous areas carrying FM approval. Pyle National product was designated AF-B1716-621 SL-AG ( receptacle ) and AF-1016-621PL-37 ( Plug). Hazardous area approval certificate 23686 ( 3615 ) was withdrawn by FM in 1989. Manufacture of Pyle compatible Product continued in 1997 by Vantage Technology, Denver USA and EEC, Chicago USA. EEC product is designated HDE-B1716-621 SL-AG ( receptacle ) and HDE 1016-621PL-37 ( Plug) and up to July 2003 has hazardous area approvals CENELEC – KEMA Ex’d’ Zone 1 IIc T6 dated 03/2001. From August 2003 the EEC certification complies with ATEX and is issued by DEMKO 03ATEX135617. Vantage product has Canadian Standards (CSA ) listing 11/2002 reported. ATEX KEMA Certification reported in 11/ 2004. Seatechnik Issued with Manufacturers Certificate DEMKO 05ATEX139889 03/2005 View on receptacle Type Pyle National Compatible receptacle Contacts numbered in spiral arrangement.

(37) #16 AWG. FEMALE CONTACTS

II 2 G EEx d IIC T6

DO NOT OPEN WHILE ENERGIZED

0539DEMKO 05 ATEX 139889

VOLTS PART #

SEA SYSTEMS TECHNOLOGY LTD, UKSEATECHNIK

XXX-XXXX-XXXXX600 AMPS 10 YEAR OF CON.

SERIAL # XXX-XX-XX200X

Page 5: LNG Compatibility Document - Full Doc

Index of LNG Terminals and Emergency Shutdown Systems and Ship-Shore Link

systems fitted. (updated 19/05/11- NS)

Country Terminal

Name Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

Algeria

Arzew Export Pyle National

Fibre Optic

Algeria

Bethioua

Export Pyle National

Algeria Skikda Export Export Pyle National for ESD only

Earth Bonding

Angola Angola LNG

Export Pyle National (SeaTechnik-EEC)

Seatechnik

Argentina Bahia Blanca (Ship to Ship)

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Argentina

Escobar Import Pyle National (SeaTechnik-EEC)

Seatechnik

Australia Darwin Export Pyle National (SeaTechnik-EEC)

Pneumatic Umbilical

Australia Pluto

Pyle National (SeaTechnik-EEC)

Seatechnik Seatechnik Pneumatic umbilical

Australia Woodside Karratha Gas Plant 1

Export Seatechnik GMB Pneumatic Umbilical

Strainstall/ No data to ship

Australia Woodside Karratha Gas Plant 2

Export SeaTechnik GMB Pneumatic Umbilical

Belgium

Zeebrugge Import Pyle National Strainstall No data to ship

Brazil Pecem

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

Brazil

Guanabara Bay

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

Brunei Lumut

Export Furukawa

Strainstall/

YEWMAC Via Fibreoptic System

Canada Canaport

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Chile Mejillones

Import Pyle National Compatible (Seatechnik)

Seatechnik

Chile Quintero LNG

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Chile

Manzanilla Import Pyle National (Vantage)

Pneumatic Umbilical

Page 6: LNG Compatibility Document - Full Doc

Country Terminal Name

Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

China

Dalian

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic

China

Jiangsu Import Pyle National (SeaTechnik-EEC)

Seatechnik

China

Ningbo (Zhejiang)

Import Pyle National (SeaTechnik-EEC)

Seatechnik

China Da Peng (Guangdong)

Import Pyle National (Seatechnik-EEC)

Seatechnik Pneumatic Umbilical

China Fujian Import Pyle National SeaTechnik Pneumatic

Umbilical

China Shanghai Ditch (Wu Hao Gou)

Import Pyle National (SeaTechnik-EEC)

Seatechnik

China Shanghai Main

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Dominican Republic

AES Andres

Import Pyle National (Vantage)

Pneumatic Umbilical

None

Dubai Golar Freeze (DUSUP)

Pyle National (SeaTechnik-EEC)

SeaTechnik

Egypt Damietta Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Marimatech a/s via 2.4 GHz Radio link

Egypt Idku Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

None

Equatorial Guinea

Punta Europa

Export

Pyle National (SeaTechnik-EEC)

Seatechnik

France Fos sur Mer (Tonkin)

Import Pyle National Earth Bonding Via Pyle 4-way

Ship is required to supply both umbilicals

France Fos-sur-Mer (Cavaou)

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

France Montoir (Upstream & DownStream)

Import Pyle National

Earth Bonding required Clamp connection or Pyle 4-way 60A

Ship is required to supply both umbilicals

Greece Revithoussa

Import Import Pyle National (SeaTechnik-EEC) Non-standard 20mA loop signalling

Earth Bonding Pyle National 100A

Holland Gate LNG 1

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

Holland Gate LNG 2

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

India Dabhol (Ratnagiri)

Import Pyle National (SeaTechnik-EEC) For ESD only

Seatechnik Marimatech a/s by 2.4 GHz link

Page 7: LNG Compatibility Document - Full Doc

Country Terminal Name

Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

India Dahej

Import Pyle National (SeaTechnik-EEC)

Marimatech via Electric System

India Hazira

Import Pyle National (SeaTechnik-EEC)

Seatechnik Marimatech via FO system and Electric

India Kochi

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Indonesia Arun

Export ITT Cannon ( telephone Only)

Furukawa Pneumatic Umbilical Earth Bonding

Strainstall/ YEWMAC Transmission by dedicated Ex’ia’ connector

Indonesia Badak

Export ITT Cannon Furukawa Pneumatic Umbilical Earth Bonding

Strainstall/ YEWMAC Transmission by dedicated Ex’ia’ connector

Indonesia Bontang

Export ITT Cannon Furukawa Harbour & Marine YEWMAC Compatible via FO Channel 1

Indonesia

Tangguh

LNG

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Indonesia

West Java FRSU

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Italy Adriatic

Import Pyle National (Seatechnik)

Seatechnik Pneumatic Umbilical

Italy Golar Frost Liverno

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

Italy Panigaglia

Import Pyle National

(SeaTechnik-EEC)

Pneumatic Umbilical

None

Japan

Chita Import Miyaki system Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Chita Joint (II)

Import Miyaki system Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan Futtsu

Import Miyaki system Furukawa Pneumatic Umbilical

Strainstall/ YEWMAC Via Fibreoptic System

Japan Hatsukaichi Import Miyaki system Furukawa Pneumatic Umbilical

Strainstall/ YEWMAC Via Fibreoptic System

Japan Higashi-Ohgishima

Import Miyaki system (3 receptacles)

Furukawa Pneumatic Umbilical

Strainstall/ YEWMAC Via Fibreoptic System

Japan Himeji Import ITT Cannon Furukawa Pneumatic Umbilical Earth Bonding

Strainstall/ YEWMAC Via Fibreoptic System

Japan Kagoshima Import Furukawa Pneumatic Umbilical Earth Bonding

Strainstall/ YEWMAC

Japan Kawagoe Import Miyaki system Furukawa Pneumatic Umbilical

Strainstall/ YEWMAC Via Fibreoptic System

Japan

Mizushima

Import Furukawa Pneumatic Umbilical

YEWMAC

Page 8: LNG Compatibility Document - Full Doc

Country Terminal Name

Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

Japan

Negishi Import Miyaki Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Niigata Import Miyaki Furukawa Pneumatic Umbilical

ASTMAC Via Fibreoptic System

Japan Ohgishima Import Miyaki Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Oita Import Furukawa Pneumatic Umbilcal

YEWMAC Via Fibreoptic System

Japan

Sakia Import ITT Cannon Furukawa Pneumatic Umbilical

YEWMACVia Fibreoptic System

Japan Senboku I

Import ITT Cannon Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Senboku II –1 (Berth 1)

Import ITT Cannon Furukawa

Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan Senboku II –2 (Berth 2)

Import ITT Cannon Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Sendai

Import Miyaki Furukawa Pneumatic

Umbilical YEWMAC Via Fibreoptic System

Japan

Shimizu Import Miyaki Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan Sodegaura 1, 2 and 3

Import Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Tobata Import Miyaki Furukawa Pneumatic Umbilical

YEWMAC Via Fibreoptic System

Japan

Yanai Import Furukawa Pneumatic Umbilical

YEWMAC

Japan Yokkaichi Import Miyaki Furukawa Pneumatic Umbilical

YEWMAC

Korea Incheon 1 Import Miyaki system Furukawa1 Strainstall on Inchon 1

by direct dedicated Plug

Korea Incheon 2 Import Miyaki system TBA Marimatech a/s via 2.4 GHz Radio link on Inchon 2

Korea Kwang Yang

Import Miyaki system (SeaTechnik) 2 receptacles

Seatechnik Pneumatic Umbilical

Marimatech via UHF

Korea

P’yeong Taek 1

Import Miyaki Furukawa Pneumatic Umbilical

Strainstall Via dedicated plug

Korea

P’yeong Taek 2

Import Miyaki Furukawa Pneumatic Umbilical

Strainstall Via dedicated plug

Korea Tong Yeong Import Miyaki Furukawa Pneumatic Umbilical

Marimatech a/s Data via 2.4 GHz radio / Tablet provided by terminal

Page 9: LNG Compatibility Document - Full Doc

Country Terminal

Name Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

Kuwait

Mina Al Ahmadi Gas Port 10

Import

Pyle National (SeaTechnik-EEC)

Seatechnik

Libya

Marsa el Brega

Export Special switch

Malaysia Bintulu 1 Export Miyaki system 3-receptacles

Furukawa Strainstall/ YEWMAC Via Fibreoptic System

Mexico

Altamira Import

Pyle National (SeaTechnik-EEC)

Pneumatic Umbilical

Mexico

Costa Azul (Ensenada)

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Nigeria

Bonny 1 Export Pyle National (SeaTechnik-EEC)

Seatechnik Marimatech a/s via FO Channel 1

Nigeria Bonny 2 (Expansion Plus)

Export ( dual LPG /LNG)

Pyle National (SeaTechnik-EEC)

Seatechnik Marimatech via UHF

Norway Snohvit Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Oman

Qalhat Export Pyle National (SeaTechnik-EEC)

Seatechnik

Peru Peru LNG

Import Pyle National (SeaTechnik-EEC)

Seatechnik

Portugal Sinnes

Import Pyle National

(SeaTechnik-EEC)

Pneumatic Umbilical

None

Puerto Rico

Penuelas Import Pyle National (Vantage

2)

Pneumatic Umbilical

None

Qatar Ras Laffan Berth 1 Qatar Gas

Export Miyaki Furukawa

Qatar Ras Laffan 2 (Ras Gas)

Export Pyle National (SeaTechnik-EEC)

Furukawa Pneumatic Umbilcal

Yamatake –YEWMAC format Via Fibreoptic System Rasgas can employ own repeater via Channel 3 FO system

Qatar Ras Laffan 3 (Ras Gas)

Export Pyle National (SeaTechnik-EEC) Miyaki

Seatechnik

Qatar Ras Laffan 4 (Qatargas)

Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Qatar Ras Laffan 5 (Qatargas)

Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Qatar Ras Laffan 6 (Qatargas)

Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Page 10: LNG Compatibility Document - Full Doc

Country Terminal

Name Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

Russia

Sakhalin

Export Pyle National Seatechnik Marimatech a/s

Singapore

Singapore Import Pyle National Seatechnik

Spain

Barcelona Import Pyle National

Spain

Bilbao

Import Pyle National

(Vantage) Pneumatic

Umbilical None

Spain

Cartagena

Import Pyle National Strainstall/ NO data to ship

Spain

Huelva Pyle National

Earth Bonding

Spain

Huelva 2

Import Pyle National

(Vantage) Pneumatic

Umbilical None

Spain Mugardos Reganosa

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Spain Sagunto

Import Pyle National (SeaTechnik-EEC)

Seatechnik None

Sultanate of Oman

Qalhat

Export Pyle National (SeaTechnik-EEC)

Seatechnik Marimatech a/s Data via 2.4 GHz radio / Tablet provided by terminal Shore recommends that ships are fitted with Marimatech LAN

Taiwan

Yung An 1 Import ITT Cannon Pneumatic Umbilical

Strainstall No conn to ship

Taiwan

Yung An 2 Import ITT Cannon Pneumatic Umbilical

Strainstall No conn to ship

Thailand Map Ta Phut

Import Pyle National Compatible (Seatechnik)

Seatechnik

Trinidad & Tobago

Point Fortin Export Pyle National (Vantage)

Harbour & Marine VHF repeater MLM by shore side

Turkey Izmir Import Pyle National Compatible (Vantage)

Pneumatic Umbilical

Turkey

Marmara Ereglisi

Import Pyle National

UAE Das Island Export Seatechnik Pneumatic Umbilical Miyaki system for telephone only

Marimatech a/s via FO Channel 1

UK Dragon LNG Import Pyle National (SeaTechnik-EEC)

SeaTechnik

UK Isle of Grain 1

Import Pyle National (SeaTechnik-EEC)

Seatechnik Harbour & Marine VHF repeater MLM by shore side

Page 11: LNG Compatibility Document - Full Doc

Country Terminal

Name Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

UK Isle of Grain 3

Import Pyle National (SeaTechnik-EEC)

Seatechnik Harbour & Marine VHF repeater MLM by shore side

UK South Hook Berth 1 West

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

UK South Hook Berth 2 East

Import Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

UK Teeside Gasport

Import Pyle National (SeaTechnik-EEC)

Seatechnik

USA Cameron North Jetty

Import Pyle National (SeaTechnik-EEC)

Seatechnik

USA Cameron South Jetty

Import Pyle National (SeaTechnik-EEC)

Seatechnik

USA

Cove Point North

Import Pyle National (SeaTechnik-EEC)

Seatechnik Harbour & Marine via VHF Link

USA Cove Point South

Import Pyle National (SeaTechnik-EEC)

Seatechnik Harbour & Marine via VHF Link

USA Elba Island Import Pyle National With Miyaki Adapter

USA Freeport

Import Pyle National (SeaTechnik-EEC)

SeaTechnik

USA Golden Pass Berth 1

Import Pyle National (SeaTechnik-EEC)

SeaTechnik Pneumatic Umbilical

USA Golden Pass Berth 2

Import Pyle National (SeaTechnik-EEC)

SeaTechnik Pneumatic Umbilical

USA Lake Charles

Import Pyle National Earth Bonding to Plate

USA Pascagoula

Import Pyle National (SeaTechnik-EEC)

Seatechnik

USA Sabine Pass

Import Pyle National (Vantage)

Page 12: LNG Compatibility Document - Full Doc

Country Terminal

Name Import/Export

ESD-SSL Electric

ESD-SSL Fibre optic

Other Mooring Load Monitor (MLM) with transmission to Ship

Yemen Bal Haf

Export Pyle National (SeaTechnik-EEC)

Seatechnik Pneumatic Umbilical

Terminals for which no systems are fitted or no information is available

Terminal Name

Country Import/Export

ESD-SSL Electric

ESD-SSL Fibreoptic

Other MLM Other

Everett USA Import No system

currently Installed

Kenai USA Export Pneumatic Umbilical

3

Pneumatic Conn only – telephone provided by shore

1 Strainstall MLM is connected via a dedicated plug not via the Fibre optic System.

2 Has non standard receptacles with pins in place of sockets

3 Kenai has dedicated plug-socket for intrinsically safe telephone only

** Specified

Page 13: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

Adriatic AES Altamira Angola A

LNG

Angola B LPG Angola C

Butane

Arzew

1, 2 ,3 4,

Bahia Blanca

(Ship to Ship)

Bal Haf

Italy Dominican Rep. Mexico Angola Angola Angola Algeria Argentina Yemen

Exxon-Mobil TLA Pending Pending Pending Yemgas

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

Spare Hotline Lift to Ring Spare Unused Unused Unused Sound Powered Telephone Electric Telecoms

(Network Data)

Spare

3 & 4 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

Continuity Check

Cct (Link on Ship)

Plant Telephone Lift to Ring

Telephone

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone also Lift

to Ring

InterPhone Seatechnik Hotphone also Lift to

Ring

3 Seatechnik Hotphone also

Lift to Ring

CCR, JCR and Marine Ops

Rm.

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

Public Telephone

456 (No Outside

Line)

Spare Spare Public Telephone Public Telephone Public Telephone Public Telephone #1 Public Telephone Public Telephone 6227

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

Plant Telephone

466

CCR 201

Spare Plant Telephone

X3784

CCR 3766 or 3768

Private Telephone Private Telephone Private Telephone Public Telephone #2 Public Telephone Plant Telephone 6228

CCR 201

11 & 12 Unused Spare Spare Spare Unused Unused Unused 4-20mA Vapour Press. signal for

vapour press control Ship transmits

4..20mA for 0..100%

Spare Spare

13 &14 ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

15 & 16 ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

Continuity Check

Cct (Link on Ship)

Spare Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare Continuity Check Cct (Link on Ship) Continuity Check Cct (Link on

Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

Continuity Check

Cct (Link on Ship)

Spare Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link on Ship) Continuity Check Cct (Link on Ship) Continuity Check Cct (Link on

Ship)

21 & 22 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

23 & 24 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

25 & 26 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

27 & 28 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

+24V 35mA max

for test circuit

Spare +24V 35mA max

for test circuit

Spare Spare Spare Power for Shore ETU +24V 35mA max for test circuit +24V 35mA max for test circuit

31 Spare Spare Spare MLM (Com) Sigtto Power cct Sigtto Power cct MLM or Sigtto ESD out RS232 - Common Spare

32 Spare Spare Spare MLM (Tx) Sigtto Power cct Sigtto Power cct MLM or Sigtto ESD in RS232 - Tx Spare

33 Spare Spare Spare MLM (Rx) Sigtto ESD loop Sigtto ESD loop MLM or Sigtto Healthy out RS232 - RX Spare

34 Spare Spare Spare Spare Sigtto ESD loop Sigtto ESD loop MLM or Sigtto Healthy in Spare Spare

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

Spare Spare Spare 24V ETU Supply IS 24V Supply

(ETU)

IS 24V Supply

(ETU)

Spare Spare Spare

37 Unused Spare Spare Spare Spare Spare Spare Spare Spare Spare

Earth Bond Not recommended by OCIMF

Regulations

Unused Unused Unused Unused Unused Unused Unused Unused

Umbilical

Cables

Ship or shore supply 50m supplied by

shore

35m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

35m supplied by shore 50m supplied by shore

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Modified by NS 1of 12

Page 14: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Barcelona 1 Bethouia

M2 and M3

Bilbao, Bonny

LNG 1

(North)

Bonny

LNG 2 & (LPG)

(South)

Cameron

North Jetty

Cameron

South Jetty

Canaport Cartagena

Spain Algeria Spain Nigeria Nigeria USA USA Canada Spain

ENERGAS BBG ENERGASHotline Lift to Ring Spare Hotline Lift to Ring Seatechnik Hotphone Seatechnik Hotphone Spare Spare Spare Plant Telephone

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Plant Telephone Spare Spare Plant Telephone Extn.

3757 - CCR

Plant Telephone Extn.

3772 - CCR

2 Seatechnik

Hotphones also Lift

to Ring. CCR &

JCR

2 Seatechnik

Hotphones also Lift

to Ring. JCR &

CCR

2 Seatechnik

Hotphones also Lift

to Ring

CCR & JCR

Spare

Spare Spare Public Telephone Public Telephone Extn.

3525

Public Telephone Extn.

3771

Public Telephone

6010

Spare

Spare Spare Spare Spare Spare CCR 762 3414

North JCR 762

3425

South JCR 762

3426

CCR 762 3414

North JCR 762

3425

South JCR 762

3426

Plant Telephone

6011

Spare

Spare Spare Spare Spare Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

(Dual input as 23-24)

ESD Shore-Ship

(Dual input as 23-24)

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Spare Spare Spare Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Spare Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare ESD Shore-Ship (Dual i/p

as 13-14)

ESD Shore-Ship (Dual i/p

as 13-14)

Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare +24V 35mA max for test

circuit

+24V 35mA max for test

circuit

+24V 35mA max for

test circuit

+24V 35mA max for

test circuit

+24V 35mA max for

test circuit

Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Unused Unused Unused Unused Unused Unused Unused

50m supplied by shore 50m supplied by shore 50m supplied by

shore

50m supplied by shore 50m supplied by shore 75m supplied by

shore

75m supplied by

shore

50m supplied by

shore

50m supplied by

shore

Modified by NS 2of 12

Page 15: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Costa Azul

Ensanada

Cove Point

North

Cove Point

South

Dabhol

(Ratnagiri)

Dahej Dalian Damietta Dapeng

Mexico USA USA India India China Egypt China

RGPPL Pending

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Seatechnik Hotphone

also Lift to Ring

Seatechnik Hotphone

also Lift to Ring

Seatechnik

Hotphone also Lift to

Ring

Seatechnik Hotphone also

Lift to Ring

Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone Tel: Not Completed

Spare Public Telephone

(410) -286-5168

Public Telephone

(410) -286-5703

Public Tel

830

Spare Public Telephone Telephone

74367

Telephone

3059

Plant Telephone 222-

2132

Control Room 222-

2900

Plant Telephone (410)

-286-5169

JCR 5150

Plant Telephone

(410) -286-5704

JCR 5150

Plant Tel 832

JCR 835

JCR Outside Tel 833

(Near Reels)

Telephone Private Telephone Telephone

74368

Telephone

3058

Spare Spare Spare Spare Spare Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check

Circuit

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check

Circuit

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

+24V 35mA max for

test circuit

+24V 35mA max for

test circuit

+24V 35mA max for

test circuit

+24V 35mA max for test

circuit

+24V 35mA max for test

circuit

Spare +24V 35mA max for test

circuit

Spare

Strainstall MLM (Com) Spare Spare MLM (Com) MLM (Com) MLM (Com) Spare MLM (Com)

MLM (Tx) Spare Spare MLM (Tx) MLM (Tx) MLM (Tx) Spare MLM (Tx)

Spare Spare Spare MLM (Rx) MLM (Rx) MLM (Rx) Spare MLM (Rx)

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare 24V Supply (ETU) Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Unused Unused Unused Welding clamp on ship’s

side

Unused Unused

50m supplied by

shore

35m supplied by

shore

35m supplied by

shore

50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore

Modified by NS 3of 12

Page 16: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Darwin Dragon LNG Elba Island, Escobar Fos-sur-Mer

Cavaou

Fos-sur-Mer

Tonkin

Freeport

Australia UK. USA Argentina France France USA

Gaz de France Gaz de France

Spare Spare Hotline Lift to Ring Electric LAN Hotline Iwatsu TS3

compatable

Hotline Iwatsu TS3

compatable

Spare

Spare Spare Spare Spare Spare Spare Spare

Spare 3 Seatechnik Hotphones also

Lift to Ring

CCR, JCR & Incident Rm.

Plant Telehone x3857 Seatechnik Hotphone Seatechnik Hotphone Shore Telephone line

Inside Use only - 7759

Seatechnik Hotphone

also Lift to Ring

Tel: Not Completed Public Telephone

5009

Spare Public Telephone Public Telephone Public Telephone

0442050430

Spare

Tel: Not Completed Plant Telephone

5008

CCR 2007/8 (+441646694017)

JCR 5006 (+441646699345)

Public Telephone+1 (912) 231 9117 Public Telephone Public Telephone Public Telephone

442055535

Plant Telephone

(979)-415-8739

Dock Control Rm (979)-

415-8760

Spare Spare 4-20mA Vapour Press. signal for

vapour press control Ship transmits

4..20mA for 0..100%

Spare-Spare Spare-Spare Spare-Spare Spare

ESD Shore-Ship ESD Shore - Ship ESD Shore-Ship Spare-Spare Spare-Spare Spare-Spare ESD Shore-Ship

ESD Ship-Shore ESD Ship - Shore ESD Ship-Shore Spare-Spare ESD Ship to Shore ESD Ship to Shore ESD Ship-Shore

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on

Ship)

Spare Continuity Check Cct (Link on Ship) Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Circuit

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct (Link on Ship) Continuity Check Cct (Link on Ship) Continuity Check Cct

(Link on Ship)

Spare Continuity Check Circuit

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare ESD Shore-Ship ESD Shore-Ship Spare

Spare Spare Spare ESD Shore-Ship Spare Spare Spare

Spare Spare Spare ESD Ship-Shore Spare Spare Spare

Spare +24V 35mA max for test circuit +24V 35mA max for test circuit Power for Shore ETU Spare Spare +24V 35mA max for test

circuit

Spare Strainstall MLM (Com) Spare MLM (Com) Spare Spare

Spare MLM (Tx) Spare MLM (Tx) Spare Spare

Spare Spare Spare MLM (Rx) Spare Spare

Spare Spare Spare Spare Spare Spare

Spare Spare Spare Reserved Spare Spare

Spare Spare Spare Spare Spare Spare

Unused Spare Unused Unused Via GD-4 pin 60A Pyle

Connector

100m supplied by shore 50m supplied by shore 35m supplied by shore 50m supplied by shore 50m supplied by

shore

Supplied by Ship 50m supplied by shore

Modified by NS 4of 12

Page 17: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Fujian Gate

LNG1

Gate

LNG2

Golar Freeze Golar Frost

Liverono

Golden Pass

Berth 1

Golden Pass

Berth2

Guanabara

Carrier Berth

Hazira

China Netherlands Netherlands Dubai Italy USA USA Brazil India

Pending Petrobras

Spare Unused Unused Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Seatechnik Hotphone

also Lift to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone

Seatechnik

Hotphone

Seatechnik

Hotphone

Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone

also Lift to Ring

Telephone 7832 Public Telephone Public Telephone Public Telephone Public Telephone Public Telephone Public Telephone Public Telephone Telephone 261 305

1252

Telephone 7833 Plant Telephone Plant Telephone Plant Telephone Plant Telephone Plant Telephone Plant Telephone Plant Telephone Telephone 261 305

1253

Spare Spare Spare Spare Spare Spare Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship to Shore

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct

(Link on Ship)

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

+24V 35mA max for

test circuit

24V Supply

(Shore ETU)

24V Supply

(Shore ETU)

24V Supply

(Shore ETU)

Spare +24V 35mA max

for test circuit

+24V 35mA max for test

circuit

+24V 35mA max for test

circuit

+24V 35mA max for

test circuit

MLM (Com) MLM (Com) MLM (Com) MLM (Com) MLM (Com) MLM (Com) MLM (Com) Spare MLM (Com)

MLM (Tx) MLM (Tx) MLM (Tx) MLM (Tx) MLM (Tx) MLM (Tx) MLM (Tx) Spare MLM (Tx)

MLM (Rx) MLM (Rx) MLM (Rx) MLM (Rx) MLM (Rx) MLM (Rx) MLM (Rx) Spare MLM (Rx)

Spare Spare Spare Spare Spare Spare Spare Spare Spare

24V Supply (Ship

ETU)

24V Supply (Ship

ETU)

24V Supply (ETU) 24V Supply (ETU) Spare Spare Spare

Unused Unused Spare Spare Spare Spare Spare

Unused Unused Unused Unused Spare Unused Unused Unused Unused

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by shore 50m supplied by shore 50m supplied by

shore

All REGAS vessels

contact

SeaTechnik UK

for Info

Modified by NS 5of 12

Page 18: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Huelva, 1 & 2 Idku Idku

Upgrade

Isle of Grain 1 Isle of Grain 3 Izmir Jiangsu Kochi

Spain Egypt Egypt UK. UK Turkey China India

Pending SKANSKA Pending

Plant Telephone

Extension 4986

Spare Not Used Spare Spare Config Unknown Sound Powered

Phone

Not Used

Spare Spare Spare Spare Spare Spare Spare

Spare Seatechnik Hotphone also

Lift to Ring

Seatechnik Hotphone also

Lift to Ring

Seatechnik Hotphone also

Lift to Ring

Seatechnik Hotphone also Lift

to Ring

Seatechnik

Hotphone

Seatechnik

Hotphone

Spare Public Telephone Public Telephone Public Telephone Public Telephone Plant Telephone Plant Telephone

Spare Plant Telephone Plant Telephone Plant Telephone Plant Telephone Public Telephone Public Telephone

Spare Spare Spare Spare Spare 4-20mA Vapour

Pressure

Unused

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship to Shore ESD Ship to Shore ESD Ship to Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare ESD Shore - Ship Load

Arm

Spare Spare Spare Spare Spare

Spare +24V 35mA max for test

circuit

Spare +24V 35mA max for test

circuit

+24V 35mA max for test

circuit

Spare Spare

Spare Spare MLM (Com) Spare Spare MLM (Com) MLM (Com)

Spare Spare MLM (Tx) Spare Spare MLM (Tx) MLM (Tx)

Spare Spare MLM (Rx) Spare Spare MLM (Rx) MLM (Rx)

Spare Spatre Spare Spare Spare Spare Spare

Spare Spare 24V Supply (ETU) Spare Spare 24V Supply ETU 24V Supply ETU

Spare Spare Spare Spare Spare Spare Spare

Welding clamp on ship’s

side

Unused Unused Unused Unused Unused Unused

35m supplied by shore 30m supplied by shore 37m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by

shore

50m supplied by

shore

Modified by NS 6of 12

Page 19: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

La Spezia

(Panigaglia)

Lake

Charles

(Trunkline)

Map Ta Phut Marmara

Ereglisi

Marsa

el Brega

Mejillones

Carrier Berth

Mina Al-Ahmadi

Gas Port 10

(North)

Montoir-de

Bretagne

(East)

Montoir-de

Bretagne

(West)

Italy USA Thailand Turkey Libya Chile Kuwait France France

GNL

Config Unknown Hotline Lift to

Ring

Spare Public line for Fax Config Unknown Spare Spare Hotline Lift to Ring Hotline Lift to Ring

Credit Card

Payment

Spare Spare Spare Spare Spare Spare

Plant

Telephone

Seatechnik Hotphone Hotline Iwatsu TS3

compatable

Seatechnik Hotphone Seatechnik

Hotphone

linked to GP9 &

MCR

Plant Telephone

5505

Plant Telephone

5506

Public

Telephone

Public Telephone Spare Public Telephone Not Completed Public Tel

+33 240 900 765

(FO Channel 3)

Public Tel

409 02844

(FO Channel 3)

Spare Plant Telephone Spare Plant Telephone Not Completed Public Tel

+33 240 902 844

Public Tel

409 02843

4-20mA

Vapour Press.

signal for

vapour press

Spare Spare Spare Spare Spare Spare

ESD Shore-

Ship

ESD Shore-Ship ESD Shore-Ship ESD Shore - Ship ESD Shore-Ship Spare Spare

ESD Ship-

Shore

ESD Ship-Shore ESD Ship-Shore ESD Ship - Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Spare Continuity Check Cct (Link

on Ship)

Spare Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity

Check Cct

(Link on Ship)

Continuity Check Cct (Link

on Ship)

Spare Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare Spare

Spare Spare Spare Spare Spare Shore-Ship Shore

Tank HL ESD trip

Shore-Ship Shore

Tank HL ESD trip

Spare Spare Spare Spare Spare ESD Shore-Ship ESD Shore-Ship

Spare Spare Spare Spare CNG ESD Shore

to Ship

ESD Shore-Ship,

Load arm 1st Stage

ESD Shore-Ship,

Load arm 1st Stage

Spare Spare Spare Spare CNG ESD Ship to

Shore

ESD Shore-Ship,

Load arm 2nd

Stage

ESD Shore-Ship,

Load arm 2nd

Stage

Spare Spare Spare +24V 35mA max for

test circuit

+24V 35mA max

for test circuit

Spare Spare

Spare MLM (Com) Spare MLM (Com) Strainstall MLM

(Com)

Spare Spare

Spare MLM (Tx) Spare MLM (Tx) MLM (Tx)

Spare MLM (Rx) Spare MLM (Rx) Spare Spare Spare

Spare Spare Spare

Spare 24V Supply (ETU) Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Welding clamp

on ship’s side

Unused Unused Spare Unused Via GD-4 pin 60A

Pyle Connector

Via GD-4 pin 60A

Pyle Connector

35m supplied by

shore

35m supplied

by shore

50m supplied by shore 50m supplied by shore 50m supplied by

shore

Supplied by Ship Supplied by Ship

All REGAS vessels

contact

SeaTechnik UK

for Info

Modified by NS 7of 12

Page 20: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Murgados

(Reganosa)

(El Ferrol)

Ningbo

( Zhejiang)

Pascagoula Pecem

Carrier Berth

Penuelas Peru LNG Pluto Point Fortin

Spain China USA Brazil Puerto Rico Peru Australia Trinidad

Pending Petrobras

Spare Spare Unused Spare Hotline Lift to Ring Spare Spare Hotline Lift to Ring

Spare Spare Spare Spare Spare Unused Spare Spare

Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone Unused Seatechnik Hotphone Seatechnik Hotphone

also Lift to Ring

Hotline Iwatsu TS3

compatable

Public Telephone

+34 981 930 290

Public Telephone

+34 981 930 290

Public Telephone Public Telephone Unused Public Telephone Public Telephone Public Telephone 1

Plant Telephone

181

Plant Telephone

181

Plant Telephone Plant Telephone Unused Plant Telephone Plant Telephone Public Telephone 2

Vapour Pressure. Ship

transmits 'Active' 4 to

20mA. Scaling unknown

Vapour Pressure. Ship

transmits 'Active' 4 to

20mA. Scaling unknown

Vapour Pressure Signal

4-20 Ma

Spare Spare Spare Spare

ESD Shore - Ship ESD Shore - Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship - Shore ESD Ship - Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Spare

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Continuity Check Cct (Link

on Ship)

Spare Continuity Check Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Was PERC release

now Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

+24V 35mA max for test

circuit

+24V 35mA max for test

circuit

24V Supply for Shore ETU +24V 35mA max for test

circuit

Spare 24V Supply for ETU 24V Supply for ETU Spare

MLM (Com) MLM (Com) MLM (Com) Spare Spare MLM (Com) MLM (Com) Spare

MLM (Tx) MLM (Tx) MLM (Tx) Spare MLM (Tx) MLM (Tx)

MLM (Rx) MLM (Rx) MLM (Rx) Spare Spare MLM (Rx) MLM (Rx) Spare

Spare Spare Spare Spare Spare Spare

Spare 24V Supply (ETU) Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Unused Unused Spare Unused Unused Spare

50m supplied by shore 50m supplied by shore 76m supplied by shore 50m supplied by shore 35m supplied by

shore

50m supplied by shore 50m supplied by

shore

35m from shore to

socket, shore supply

adapter for most shipsAll REGAS vessels

contact

SeaTechnik UK

for Info

Modified by NS 8of 12

Page 21: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Punta Europa

Malabu

(Alba)

Qalhat Quintero LNG Ras Laffan LNG2

(Rasgas2)

Ras Laffan LNG3

(Rasgas3)

Ras Laffan LNG4

(QG4)

Ras Laffan LNG5

(QG5)

Ras Laffan LNG6

(QG6)

Equatorial

Guniea

Oman Chile Qatar Qatar Qatar Qatar Qatar

ENAP RASGAS RASGAS QATARGAS QATARGAS QATARGAS

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Hotline Iwatsu TS3

compatable

Hotline Iwatsu TS3

compatable

Seatechnik Hotphones

also Lift to Ring.

Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone also Lift to

Ring

Seatechnik Hotphone also Lift

to Ring

Seatechnik Hotphone

also Lift to Ring

Public Telephone

2498

JCR 2500

PublicTelephone 1 Public Telephone Phone Phone Phone/MLM Phone Phone

Spare Public Telephone 2 Plant Telephone Phone Phone Phone Phone Phone

Spare Spare Spare Spare Spare Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check

Cct (Link on Ship)

Spare Spare Continuity Check Cct

(Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Spare Spare Continuity Check Cct

(Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

+24V 35mA max

for test circuit

Spare Spare +24V 35mA max for test

circuit

+24V 35mA max for test

circuit

+24V 35mA max for test circuit +24V 35mA max for test

circuit

+24V 35mA max for test

circuit

Spare Spare Spare MLM (Com) MLM (Com) Spare Spare Spare

Spare Spare MLM (Tx) MLM (Tx) Spare Spare Spare

Spare Spare Spare MLM (Rx) MLM (Rx) Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Unused Unused Spare Spare Spare Spare Spare

50m supplied by

shore

50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore 50m supplied by shore

Modified by NS 9of 12

Page 22: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Ras Laffan LPG

1A

Ras Laffan LPG

1B

Ras Laffan LPG

3A

Ras Laffan LPG

3B

(Pearl GTL) LPG

Revithoussa Sabine Pass Sagunto Sakhalin

Qatar Qatar Qatar Qatar Greece USA Spain Russia

DEPASpare Spare Spare Spare ESD Ship-Shore

Side A (Both 1 & 2, 3 & 4 O/C for

ESD)

Spare Spare Marimatech

MLM System

Spare Spare Spare Spare ESD Ship-Shore

Side B (Both 1 & 2, 3 & 4 O/C for

Spare Spare Spare

Seatechnik Hotphone Seatechnik Hotphone Seatechnik Hotphone Seatechnik

Hotphone

ESD Shore-Ship Hotline Iwatsu TS3

compatable

Seatechnik Hotphone

also Lift to Ring

Lift to Ring

5712

Phone Phone Phone Phone High level Tank A

LAHH-32010

(Optional or for Indication)

Phone Public Telephone

8504

Public

Telephone

5713

Phone Phone Phone Phone High level Tank B

LAHH-32110

(Optional or for Indication)

Phone Plant Telephone

8805

Plant Telephone

5714

Spare Spare Spare Spare High pressure

Tank A or B

PAHH-32036

(Optional or for Indication)

Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship DEPA Hotline

(IS Protected)

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore Telephone

(IS Protected)

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check Cct (Link on Ship) Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on Ship) Continuity Check

Cct (Link on Ship)

Continuity Link for Telephone Line

on pins 25 & 26

Continuity Check Cct

(Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on

Ship)Continuity Check Cct (Link on Ship) Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on Ship) Continuity Check

Cct (Link on Ship)

Spare Continuity Check Cct

(Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on

Ship)Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Normal Telephone

Tel No 6134

Terminal Control Room 6142

Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

+24V 35mA max for test circuit +24V 35mA max for

test circuit

+24V 35mA max for test circuit +24V 35mA max for

test circuit

Spare +24V 35mA max for

test circuit

+24V 35mA max for

test circuit

+24V 35mA max

for test circuit

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare Spare Via GD-4 pin 60A Pyle Connector Spare Unused Unused

100m supplied by shore 100m supplied by

shore

100m supplied by shore 100m supplied by

shore

50m supplied by shore 60m supplied by

shore

50m supplied by

shore

Supplied by

Shore

Modified by NS 10of 12

Page 23: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Shanghai

Ditch

Shanghai

Main

Sines, Singapore Skikda Snohvit South Hook

Berth 1 (West)

South Hook

Berth 2 (East)

Tangguh A

(Condensate)

(West)

Tangguh B

(East)

China China Portugal Singapore Algeria Norway UK UK Indonesia Indonesia

Pending

Spare Spare Spare Spare Config Unknown Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Seatechnik

Hotphone also

Lift to Ring

Seatechnik Hotphone

also Lift to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik

Hotphone also Lift

to Ring

Seatechnik Hotphone

also Lift to Ring

Seatechnik Hotphone also Lift to

Ring

Public

Telephone

Public Telephone Public Telephone Public Telephone

+34 981 930 290

Public Telephone

7840 4943

Public Telephone

2622

Public Telephone

2623

Public Telephone Public Telephone

Plant Telephone Plant Telephone Plant Telephone Plant Telephone

181

Plant Telephone

7840 4944

Plant Telephone

2029

CCR 2122/2133

(+441437 782122)

JCR 2161/2162

Plant Telephone

2029

CCR 2122/2133

(+441437 782122)

JCR 2161/2162

Plant Telephone Plant Telephone

Spare Spare Spare Vapour Pressure.

Ship transmits

'Active' 4 to 20mA.

Scaling unknown

Spare Spare Spare Spare Spare

ESD Shore-Ship ESD Shore-Ship ESD Shore-Ship ESD Shore - Ship ESD Shore-Ship ESD Shore - Ship ESD Shore - Ship ESD Shore-Ship ESD Shore-Ship

ESD Ship-Shore ESD Ship-Shore ESD Ship-Shore ESD Ship - Shore ESD Ship-Shore ESD Ship - Shore ESD Ship - Shore ESD Ship-Shore ESD Ship-Shore

Continuity Check

Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on Ship)

Continuity Check

Cct (Link on

Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check

Cct (Link on Ship)

Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on Ship)

Spare Spare Shore-Ship Shore

Tank HL ESD trip

(Unused)

Spare Spare Spare Spare Spare Spare

Spare Spare ESD Shore-Ship

(Dual i/p as 13-14)

Spare Spare Spare Spare Spare Spare

Spare Spare ESD Shore-Ship,

Load arm 1st

Stage

Spare Spare Spare Spare Spare Spare

Spare Spare ESD Shore-Ship,

Load arm 2nd

Stage

Spare Spare Spare Spare Spare Spare

+24V 35mA max

for test circuit

+24V 35mA max for

test circuit

Spare +24V 35mA max

for test circuit

+24V 35mA max

for test circuit

+24V 35mA max

for test circuit

+24V 35mA max

for test circuit

+24V 35mA max for

test circuit

+24V 35mA max for test circuit

Spare Spare Spare MLM (Com) Spare MLM (Com) MLM (Com) Spare Spare

Spare Spare MLM (Tx) Spare MLM (Tx) MLM (Tx) Spare Spare

Spare Spare Spare MLM (Rx) Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare

Spare Spare Spare 24V Supply (ETU) Spare Spare Spare Spare Spare

Spare Spare Spare Spare Spare Spare Spare Spare Spare

Unused Unused Spare Spare Unused Spare Spare Unused Unused

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by

shore

50m supplied by shore 50m supplied by shore

Modified by NS 11of 12

Page 24: LNG Compatibility Document - Full Doc

Version 41 Date 20th May 2011

1 & 2 Sound Powered Telephone

(Cabinet Terminals T1,T2)

3 & 4 Unused

5 & 6 Seatechnik Hotphone Telephone

With Private line mode also called Lift to

Ring, Auto dial or Hotdial.

(Iwatsu TS3 compatable). (Cab T3,T4)

7 & 8 Public Telephone

(Connected to Fibre Optic Ch3 if fitted)

(Cabinet Terminals T5,T6)

9 & 10 Plant Telephone

(Connected to Fibre Optic Ch4 if fitted)

(Cabinet TerminalsT7,T8)

11 & 12 Unused

13 &14 ESD Shore-Ship

15 & 16 ESD Ship-Shore

17 & 18 Continuity Check Circuit

(Link these on Ship)

19 & 20 Continuity Check Circuit

(Link these on Ship)

21 & 22 Unused

23 & 24 Unused

25 & 26 Unused

27 & 28 Unused

29 & 30 24DCV 35mA max Shore systems test

circuit (29 is Positive)

31

32

33

34

35 & 36 24DCV 35mA max Ship System test

circuit (36 is Positive)

37 Unused

Earth Bond Not recommended by OCIMF

Regulations

Umbilical

Cables

Ship or shore supply

‘Standard’Pins

Reserved for MLM Connection.

May be switched to - Sigtto link pendant

power on Sigtto enabled systems

Reserved for MLM Connection.

May be switched to - Sigtto link ESD on

Sigtto enabled systems

Teesport Zeebrugge

UK Belgium

DATA Sound Powered

telephone

Spare Plant Telephone

6525

Seatechnik Hotphone also Lift to

Ring

Plant Telephone

6526

Control Room 6500 or

6600

Public Telephone Public Telephone 1

050/54 78 32

050/54 77 78

Plant Telephone Public Telephone 2

050/54 74 38

050/54 77 53

Spare Vapour Pressure. Ship

transmits 'Active' 4 to

20mA for -20 to

300mbarg. 15PT05ESD Shore - Ship Spare

ESD Ship-Shore

ESD Ship - Shore ESD Ship-Shore

Continuity Check Cct (Link on Ship) Continuity Check Cct

(Link on Ship)

Continuity Check Cct (Link on Ship) Spare

Spare Shore-Ship Shore

Tank HL ESD trip

Spare ESD Shore-Ship

Spare ESD Shore-Ship,

Load arm 1st Stage

Spare ESD Shore-Ship,

Load arm 2nd

Stage

+24V 35mA max for Test Circuit Vapour Pressure. Ship

transmits 'Active' 4 to

20mA for -20 to MLM (Com) MLM (Com)

MLM (Tx) MLM (Tx)

MLM (Rx) MLM (Rx)

Spare Spare

Spare Spare

Spare Spare

Spare Spare

50m Supplied by Shore 35m supplied by

shore

Modified by NS 12of 12

Page 25: LNG Compatibility Document - Full Doc

MIYAKI CONNECTOR-27Jul06 SSL.doc 27/07/2006

MIYAKI CONNECTOR SSL-ESD SYSTEM - PIN CONFIGURATION FOR LNGC TERMINALS Updated 27/07/05 Manufactured by Miyaki Denki, Kyoto, Japan Connector carries KEMA certification to CENELEC Ex’d’ standards. Prior to August 2003 Miyaki provided a 21E-P-T connector to TTIS standards and is compatible mechanically with the new units, which are designated 21CE-P-T.

‘Standard Connection’ is proposed as the most logical and/or numerous arrangement 2 or 3 21-E-P-T Receptacles are used , 1 dedicated to ESD and 1 or 2 to telephone connection. Pin 6 is grounded on Miyaki 21-E-P-T connectors Some terminals do not provide a ship-shore ESD facility, contrary to SIGTTO guidelines Almost all terminals employing this systems use 2 connectors ( 1 ESD, I Tel ) A small number use 3 connectors ( 1 ESD, 2 Tel ) Some Connectors use two pins linked (shown)

3

2

1

6

5

4

Page 26: LNG Compatibility Document - Full Doc

MIYAKI CONNECTOR-27Jul06 SSL.doc 27/07/2006

ESD CONNECTOR PIN ‘Standard’

Connection Ras Laffan 1 (Qatargas) Ras Laffan 1 (Rasgas)

Higashi –Ohgishima Futtsu 1 Futtsu 2

Bintulu P’yeong Taek 1 + 2 Incheon 1

Kawagoe, Yokkaichi

1 2

ESD Ship-Shore

No ESD fitted ESD Shore-Ship ONLY Pin 1+ Pin 2 Linked

ESD Ship-Shore Pins 2-5

ESD Shore-Ship ONLY Pin 1 - Pin 2

ESD Shore-Ship ONLY Pin 1 + Pin 2

3

4

ESD Shore-Ship

ESD Shore-Ship

5 ESD Shore-Ship ONLY Pin 4+Pin 5 Linked

ESD Ship-Shore Pins 2-5

ESD Shore-Ship ONLY Pin 4 + Pin 5

6

Spare

Spare

TELEPHONE CONNECTOR #1 PIN ‘Standard’

Connection Ras Laffan 1 (Qatargas) Ras Laffan 1 (Rasgas)

Higashi -Ohgishima

Bintulu P’yeong Taek 1 + 2 Incheon 1

Kawagoe, Yokkaichi Futtsu 1 Futtsu 2

1 2

Hotline Telephone

Iwatsu (QG) Seatechnik(RG) hotline telephone

PABX Telephone Pin 1 + Pin 2

PABX Telephone

Hotline Telephone

Not Used

3 4

PABX Telephone

PABX Phone 1 PABX Telephone Pin 3 + Pin 4

Spare PABX Telephone

Not Used

5 Spare 6

Public Telephone

PABX Phone 2 Spare

Spare Public Telephone

Not Used

TELEPHONE CONNECTOR #2 PIN ‘Standard’

Connection Bintulu Higashi -

Ohgishima

1 2

No connection - connector not used

Hotline Telephone

Iwatsu Hotline Telephone Pin 1 L1 Pin 2 L2

3 4

No connection - connector not used

Spare Iwatsu Hotline Telephone Pin 3 -12V Pin 4 +12V

5 6

No connection - connector not used

Spare Spare

Page 27: LNG Compatibility Document - Full Doc

MIYAKI CONNECTOR-27Jul06 SSL.doc 27/07/2006

ESD CONNECTOR PIN ‘Standard’

Connection Incheon 2 Tong Yeong

Kwang Yang

1 2

ESD Ship-Shore

ESD Shore-Ship Pin 1 + Pin 2

ESD Shore-Ship Pin 1 + Pin 2

3 4

ESD Shore-Ship

ESD Ship-Shore Pin 3 + Pin 4

5 +24V MIYAKI ETU

6

Spare

0V MIYAKI ETU

TELEPHONE CONNECTOR #1 PIN ‘Standard’

Connection Incheon 2 Tong Yeong

Kwang Yang

1 2

Sound Powered telephone

Hotline Telephone

Hotline Telephone

3 4

Spare PABX Telephone

PSTN Telephone

5 6

InterPhone or Hotline Telephone

Public Telephone

PABX Telephone

Page 28: LNG Compatibility Document - Full Doc

ITT CANNON CONNECTOR SS1 16-11-04.doc 27/07/2006 1

‘ITT CANNON’ CONNECTOR SSL SYSTEM - PIN CONFIGURATION FOR LNGC TERMINALS (last updated 10/05/04) Uses a MIL-STD 13 pin connector installed in safe area aft of accommodation front on ship. Carries only telephone functions with ESD at these terminals normally utilising pneumatic umbilical

CONNECTOR Pins ‘Standard’

Connection Kawagoe, Yokkaichi Chita

Arun Bontang

Yung An Himeji

A B

Public Telephone

Public Telephone

Public Telephone

Public Telephone

C D E

Hotline Telephone

Iwatsu Hotline Telephone

Iwatsu Hotline Telephone

Iwatsu Hotline Telephone

Iwatsu Hotline Telephone

F G H J

Plant (PABX) Telephone

Plant (PABX) Telephone

Plant (PABX) Telephone

Plant (PABX) Telephone

Plant (PABX) Telephone

K L