Upload
malli55
View
226
Download
1
Embed Size (px)
DESCRIPTION
LV board
Citation preview
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.A
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 1250A VCB 1 VCB INCOMER-1
2 1250A VCB 1 VCB INCOMER-2
OUTGOINGS - FEEDER
3 630A VCB 1 VCB HEAD HOUSE -1
4 630A VCB 1 VCB HEAD HOUSE -2
5 630A VCB 1 VCB Future ( Spare)
6 1250A VCB 1 VCB BUS TIE
B
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 1250A VCB 1 VCB INCOMER-1
2 1250A VCB 1 VCB INCOMER-2
OUTGOINGS - FEEDER
3 630A VCB 1 VCB WARE HOUSE -1
4 630A VCB 1 VCB WARE HOUSE -2
33kV MV SWITCHBOARD- HEAD HOUSE AREA (Ref. Drawing No.20110824191132421, Page - 1)33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42, MV Switchboard.
33kV MV SWITCHBOARD- WARE HOUSE AREA (Ref. Drawing No.20110824191132421, Page - 1)33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42, MV Switchboard.
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
5 630A VCB 1 VCB SPARE-1
6 1250A VCB 1 VCB BUS TIE
C 33kV MV SWITCHBOARD- BERTH AREA (Ref. Drawing No.20110824191132421, Page - 1)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 1250A VCB 1 VCB INCOMER-1
2 1250A VCB 1 VCB INCOMER-2
OUTGOINGS - FEEDER
3 630A VCB 1 VCB BERTH AREA -1
4 630A VCB 1 VCB BERTH AREA -1
5 630A VCB 1 VCB BERTH AREA -1
6 630A VCB 1 VCB BERTH AREA -2
7 630A VCB 1 VCB SPARE-1
8 630A VCB 1 VCB SPARE-2
33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42, MV Switchboard.
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
9 1250A VCB 1 VCB BUS TIE
D POWER TRANSFORMER (Ref. Drawing No.20110824191132421, Page - 1)
Sl No Head House Area QTY. Type of Feeder TAG NO. Feeder Details
1 3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V, 1 ONAN Tx-1
2 3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V, 1 ONAN Tx-2
3 1 ONAN FUTURE
Ware House Area
4 3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V, 1 ONAN Tx-3
5 3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V, 1 ONAN Tx-4
Berth Area
6 1 ONAN Tx-5
7 1 ONAN Tx-6
8 1 ONAN Tx-7
9 3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V, 1 ONAN Tx-8
3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,
3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,
3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,
3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
E LV SWITCHBOARD- HEAD HOUSE AREA (Ref. Drawing No.20110824191132421, Page - 2)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER- (BUS-A)
1 5000A, 4P, ACB, INCOMER from Tx-1 1 ACB INCOMER-1
2 5000A, 4P, ACB, BUS COUPLER 1 ACB BUS COUPLER
OUTGOINGS - FEEDER- BUS SECTION :A
3 800A 3P ACB 1 ACB MCC-1
4 2500A 3P ACB 1 ACB MCC-2
5 2500A 3P ACB 1 ACB MCC-3
6 300A 3P MCCB for 200KVAR Capacitor Banks 1 MCCB PFC-1
INCOMER- (BUS-B)
7 5000A, 4P, ACB, INCOMER from Tx-2 1 ACB INCOMER-2
OUTGOINGS - FEEDER- BUS SECTION :B
8 300A 3P MCCB 1 MCCB OFFICE
9 300A 3P MCCB 1 MCCB AMEMNES
10 200A 3P MCCB 1 MCCB
11 300A 3P MCCB for 200KVAR Capacitor Banks 1 MCCB PFC-2
400V AC , 5000A, 3PH, 4W, 50Hz, 65KA, 1Sec, Form-4B, Drawout type, IP43, LV Switchboard.
HEAD HOUSE LIGHTS/POWER
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
F LV SWITCHBOARD- WARE HOUSE AREA (Ref. Drawing No. 20110824191132421, Page - 3)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER- (BUS-A)
1 1 ACB INCOMER-1
2 1 ACB BUS COUPLER
OUTGOINGS - FEEDER- BUS SECTION :A
3 1000A 3P ACB 1 ACB MCC-4
4 400A 3P MCCB 1 MCCB
5 100A 3P MCCB 1 MCCB GATE HOUSE
6 3P MCCB for Capacitor Banks 1 MCCB PFC-3
INCOMER- (BUS-B)
7 1 ACB INCOMER-2
OUTGOINGS - FEEDER- BUS SECTION :B
8 200A 3P MCCB 1 MCCB
400V AC , 2000A, 3PH, 4W, 50Hz, 65KA, 1Sec, Form-4B, Drawout type, IP43, LV Switchboard.
2000A, 4P, ACB, INCOMER from Tx-3
2000A, 4P, ACB, BUS COUPLER
WARE HOUSE LIGHTS/POWER
2000A, 4P, ACB, INCOMER from Tx-4
REGISTRATION BLDG
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
9 3P MCCB 1 MCCB SPARE
10 3P MCCB 1 MCCB SPACE
11 3P MCCB for Capacitor Banks 1 MCCB PFC - 4
G
Sl No QTY.of Panel Type of Feeder TAG NO. Feeder Details
1 1 VCB SHIP UNLOADER-1
2 1 VCB SHIP UNLOADER-2
3 1 VCB SHIP UNLOADER-3
H LV SWITCHBOARD- BERTH AREA- 2 (Ref. Drawing No. 20110824191132421, Page - 5)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
11 KV MV SWITCHBOARD- BERTH AREA-1 (Ref. Drawing No. 20110824191132421, Page-4)11kV AC , 630A, 3PH, 50Hz, 16KA, 1Sec, IP43, Standalone Cabinet. 11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from Tx- 5.
11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from Tx- 6.
11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from Tx- 7.
400V AC , 1000A, 3PH, 4W, 50Hz, 65KA, 1Sec, Form-4B, Drawout type, IP43, LV Switchboard.
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
1 1 ACB INCOMER
OUTGOINGS - FEEDER
2 Feeder-1 1
3 Feeder-2 1
4 Feeder-3 1
5 3P MCCB for Capacitor Banks 1 MCCB PFC - 5
I MCC - 1 (Ref. Drawing No. 20110823094801671)
1000A, 4P, ACB, INCOMER from Tx-8
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 800A, 3P, ACB, INCOMER 1 ACB INCOMER
OUTGOINGS- Intelligent Starter feeder
2 7.5 KW 1 DOL Starter 110-07MS
3 7.5 KW 1 DOL Starter 120-07MS
4 25.0 KW 1 DOL Starter 110-19C INTAKE CONVEYOR
5 25.0 KW 1 DOL Starter 120-19C INTAKE CONVEYOR
6 40.0 KW 1 Soft starter 140-03C
7 40.0 KW 1 Soft starter 210-01B
8 40.0 KW 1 Soft starter 220-01B
9 40.0 KW 1 Soft starter 230-01B
10 40.0 KW 1 Soft starter 240-01B
11 7.5 KW 6 DOL Starter 23A
12 2.0 KW 6 DOL Starter 23B
13 3.0 KW 1 DOL Starter DF36
14 25.0 KW 1 DOL Starter 25A AIR COMPRESSOR
400V AC , 800A, 3PH, 4W, 50Hz, 50KA, 1Sec, Form-4B, Drawout type, IP43, Intelligent MCC with modbus TCP protocol .
MAGNET SEPARATOR
MAGNET SEPARATOR
TRUCK INTAKE CONVEYOR
OUT TAKE BELT CONVEYOR
OUT TAKE BELT CONVEYOR
OUT TAKE BELT CONVEYOR
OUT TAKE BELT CONVEYOR
TRUCK/BAGGING DOZ CONVEYOR
TRUCK LOADING SPOUTS/BELLOW
LOADING DUST FILTER
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
15 15.0 KW 1 DOL Starter 25 AIR COMPRESSOR
J MCC - 2 (Ref. Drawing No. 20110823094801671)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 2500A, 3P, ACB, INCOMER 1 ACB INCOMER
OUTGOINGS- Intelligent Starter feeder
2 125 KW 1 Soft starter 210-05C
3 125 KW 1 Soft starter 220-05C
4 300 KW 1 Soft starter 110-05B LONG HAUL BELT
5 300 KW 1 Soft starter 120-05B LONG HAUL BELT
6 300 KW 1 Soft starter 110-17E
400V AC , 2500A, 3PH, 4W, 50Hz, 50KA, 1Sec, Form-4B, Drawout type, IP43, Intelligent MCC with modbus TCP protocol .
SILO OUT TAKE CONVEYOR
SILO OUT TAKE CONVEYOR
RECEIVE BUCKET ELEVATOR
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
7 300 KW 1 Soft starter 120-17E
8 125 KW 1 Soft starter 110-21C
9 125 KW 1 Soft starter 120-21C
K MCC - 3 (Ref. Drawing No. 20110823094801671)
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 2500A, 3P, ACB, INCOMER 1 ACB INCOMER
OUTGOINGS- Intelligent Starter feeder
2 100 KW 1 Soft starter 110-23C
3 100 KW 1 Soft starter 120-23C
4 100 KW 1 Soft starter 130-23C
RECEIVE BUCKET ELEVATOR
DISTRIBUTION CHAIN CONVEYOR
DISTRIBUTION CHAIN CONVEYOR
400V AC , 2500A, 3PH, 4W, 50Hz, 50KA, 1Sec, Form-4B, Drawout type, IP43, Intelligent MCC with modbus TCP protocol .
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
5 100 KW 1 Soft starter 140-23C
6 100 KW 1 Soft starter 110-25C
7 100 KW 1 Soft starter 120-25C
8 100 KW 1 Soft starter 130-25C
9 100 KW 1 Soft starter 140-25C
10 200 KW 1 Soft starter 210-17E
11 200 KW 1 Soft starter 220-07E
12 125 KW 1 Soft starter 210-09C
13 125 KW 1 Soft starter 220-09C
L MCC - 4 (Ref. Drawing No. 20110823094801671)
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
SILO INTAKE CONVEYOR
OUT TAKE BUCKET ELEVATOR
OUT TAKE BUCKET ELEVATOR
OUT TAKE CHAIN CONVEYOR
OUT TAKE CHAIN CONVEYOR
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
Sl No QTY.of Feeder Type of Feeder TAG NO. Feeder Details
INCOMER
1 1000A, 3P, ACB, INCOMER 1 ACB INCOMER
OUTGOINGS- Intelligent Starter feeder
2 0.5 KW 4 DOL Starter 11 PELLET DISPENSER
3 3.0 KW 1 DOL Starter DF1
4 3.0 KW 1 DOL Starter DF2
5 3.0 KW 1 DOL Starter DF3
6 3.0 KW 4 DOL Starter DF4--DF7
7 3.0 KW 7 DOL Starter DF8--DF14
8 3.0 KW 7 DOL Starter DF15--DF21
9 3.0 KW 7 DOL Starter DF22--DF28
10 3.0 KW 7 DOL Starter DF29--DF35
11 30.0 KW 1 Soft starter 15E FAN
12 3.0 KW 1 DOL Starter 15D AIRLOCK
13 20.0 KW 1 DOL Starter 15N FAN
14 3.0 KW 1 DOL Starter 15E AIRLOCK
15 3.0 KW 4 DOL Starter DF4B, DF5B, DF6B, DF7B.
16 1.0 KW 2 DOL Starter 24A
400V AC , 1000A, 3PH, 4W, 50Hz, 50KA, 1Sec, Form-4B, Drawout type, IP43, Intelligent MCC with modbus TCP protocol .
DUST FILTER LONG CONVEYOR
DUST FILTER LONG CONVEYOR
DUST FILTER RECEIVE B.E
DUST FILTER INTAKE CONVEYOR
DUST FILTER CONVEYOR 210-01B
DUST FILTER CONVEYOR 220-01B
DUST FILTER CONVEYOR 230-01B
DUST FILTER CONVEYOR 240-01B
BAG CLOSE CONVEYOR
Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
17 1.0 KW 2 DOL Starter 24B SEWINE HEAD
M 110VDC SYSTEM/MOTORS & DRIVES
1
2 Motors & drives
Control voltage shall be 110 V DC;During a power failure, the 110V DC power supply of the MDS shall be operational for at least six hours
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
We have considered the Bus tie as mentioned in the attached specifications, however same is not shown in drawing (Ref. Drawing No.20110824191132421, Page - 1). Please confirm whether the same is correct.
please to follow the rating indicated on the dwg. No.2011082419113242
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
same as above
same as above
We have considered the Bus tie & spare feeder as mentioned in the above attached specifications, however same is not shown in drawing(Ref. Drawing No.20110824191132421, Page - 1). Please confirm whether the same is correct.
We have considered the Bus tie & spare feeder as mentioned in the above attached specifications, however same is not shown in drawing(Ref. Drawing No.20110824191132421, Page - 1). Please confirm whether the same is correct.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
confirmed
We have considered the Bus tie & spare feeder as mentioned in the above attached specifications, however same is not shown in drawing(Ref. Drawing No.20110824191132421, Page - 1). Please confirm whether the same is correct.
Rating of future Transformer is not shown in drawing, we have considered the rating as 3200kVA . Please confirm whether the same is correct.
We have considered the ratng of Transformers for Ware house & Berth area as 3200kVA as shown in the attached drawing(Ref. Drawing no.20110824191132421, Page - 1). Please confirm whether the same is correct.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
PFC-2 is required
PFC-1(200kvar) has been indicated in drawing for the Bus-A(Ref. Drawing No.20110824191132421, Page - 2), but for the Bus B capacitor bank is not shown in the drawing. Please confirm whether PFC-2 is required or not for Bus B.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
confirmed
The rating of incomer feeder is 2000A as shown in drawing where as the rating of incoming Transformer is 3200kVA. Please confirm whether the same is correct.
Please confirm rating of Capacitor bank/feeder.
The rating of incomer feeder is 2000A as shown in drawing where as the rating of incoming Transformer is 3200kVA. Please confirm whether the same is correct.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
200A
200A
Please confirm rating of spare feeder.Please confirm rating of spare space of future feeder.
Capacitor Bank(PFC-3) has been indicated in drawing for the Bus-A(Ref. Drawing No.20110824191132421, Page - 3), but for the Bus B capacitor bank is not shown in the drawing. Please confirm with rating whether PFC-4 is required or not for Bus B.
consider cap. Bank for each bus(headhouse , ware house, berth area )
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
CONFIRMED , VALUE IS CORRECT
100A for each feeder
The rating of incomer feeder is 1000A as shown in drawing where as the rating of incoming Transformer is 3200kVA. Please confirm whether the same is correct.
The rating of the outgoing feeder are not shown in the drawing, Please provide the same
Please confirm rating of Capacitor bank/feeder if required..
We have considered the rating( in KW )and quantity of feeder as per the attached drawing(Ref. Drawing No. 20110823094801671), however starter type has not been indicated in the drawing. Please confirm/approve the Rating, Starter type & no. of feeder indicated in this BOQ to enable us prepare the offer.
DOL type and the rating not confirmed from client yet ,
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
same as above
We have considered the rating( in KW )and quantity of feeder as per the attached drawing(Ref. Drawing No. 20110823094801671), however starter type has not been indicated in the drawing. Please confirm/approve the Rating, Starter type & no. of feeder indicated in this BOQ to enable us prepare the offer.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
same as above
We have considered the rating( in KW )and quantity of feeder as per the attached drawing(Ref. Drawing No. 20110823094801671), however starter type has not been indicated in the drawing. Please confirm/approve the Rating, Starter type & no. of feeder indicated in this BOQ to enable us prepare the offer.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
same as abopv
We have considered the rating( in KW )and quantity of feeder as per the attached drawing(Ref. Drawing No. 20110823094801671), however starter type has not been indicated in the drawing. Please confirm/approve the Rating, Starter type & no. of feeder indicated in this BOQ to enable us prepare the offer.
ABB reply/queries dtd 22-Sep-2011 Astraco Reply
We have considered the CDP as part of MCC-4 in this BOQ. Please confirm whether the same is correct
ABB reply/queries dtd 22-Sep-2011 Astraco ReplyWe have considered the CDP as part of MCC-4 in this BOQ. Please confirm whether the same is correct
DC UPS: Please confirm whether the supply of DC UPS is in the scope of this package. If required, please provide us the rating & other details of the DC UPS & Batteries
DC UPS is required with 110V DC , 6 hr , 750A
Motors & Drive: Please confirm whether the supply of Motors & Drive are in the scope of this package. If required, please provide us the rating, Qty & other details of the same.
included in the scope , but no data from client
S.NO. RATING QTY1. Switchgear Tag No: A1-SP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 1 Rev H )
SIEMENS MAKE 380V SWITCHGEAR 1250A, ACB 1 3380V,50HZ,50KA
1 01A1 01B
01C100A 1 1A
1 1B1 1C1 1D
100A 1 2A100A 1 2B6.4KW,100A 1 2C125A 1 2D100A 1 2E
1 3A3B4A
1 4B1 4C
20KW,100A 1 4D1 4E
2. Switchgear Tag No: A1-SSP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 2 Rev H )SIEMENS MAKE 380V SWITCHGEAR
404KW,1250A 1 61
1250A, ACB 1 3380V,50HZ,50KA100A 1A
1 1B1 1C
10KW,100A 1 2A100A 1 2B10KW,100A 1 2C100A 1 2D100A 1 2E
1 3A50A 1 4A
1 4B1 4C
NUMBERING AS PER CUBICLES
125A 1 4D125A 1 4E
1 5A1 5B
5C1 5D1 5E
3. Switchgear Tag No: A1-SG-D3( Ref Drg No: 6400-A1-400-70-37 Rev K )SIEMENS MAKE 380V SWITCHGEAR
3150A, ACB 2380V,50HZ,50KA3150A, ACB 1100A 115KW,75A 215KW,75A 2110A 1229A 1100A 315KW,75A 22KW,75A 10.25KW,75A 23KW,75A 1110A 1250A 3100A 232KW,100A 1400A 1400A 14KW,75A 12000A,ACB 2
4. Switchgear Tag No: A1-SP-SSP-D3( Ref Drg No: 6400-A1-400-70-44-001 )SIEMENS MAKE 380V SWITCHGEAR
2000A, ACB 1 72000A, ACB 1 82000A, ACB 1 9380V,50HZ,50KA40A 1 1A
1 1B100A 1 1C
1 1D1 1E
5KW 5 2A-2E8KW 1 3A
50A 1 3B40A 1 3C60KW 1 3D100KW 1 3E6KW 1 4A
1 4B25KW 1 4C175A 1 4D175A 1 4E
1 5A11KW,<75A 2 5B &14D80-125A 1 5C
1 5D1250A,ACB 2 6 & 10
3 11A-11C110A-170A 1 11D6KW 1 12A5KW 1 12B175A 1 12C175A 2 12D-12E8KW 1 13A
1 13B1 13C
81-125A 1 13D1 13E
10KW 1 14A1 14B1 14C
40-53A 1 14E
7. Switchgear Tag No: C5-SG-D1( Ref Drg No: 6400-A1-SS11-70-4 Rev H )SIEMENS MAKE 380V SWITCHGEAR
1250A, ACB 1380V,50HZ,50KA4KW,100A 24KW,100A 220KW,100A 1
110KW,100A 2
2225A 3400A 1400A,5KVA 1400A 175A 2
33KW,100A
2KW,100A
8. Switchgear Tag No: AP-LC-D ( Ref Drg No: 406-4001. )SIEMENS MAKE 380V SWITCHGEAR
800A, ACB 2800A, ACB 1800A,380V,50HZ,50KA,3-PH,4N,50A,3P, 130A,3P 180A,3P 1100A,3P 140A,SP 1
9. Switchgear Tag No: AP-LCE-D ( Ref Drg No: 406-4001. )SIEMENS MAKE 380V SWITCHGEAR
800A, ACB 1800A,380V,50HZ,50KA,3-PH,4N,160A,3P 1630A,3P 160A,3P 140A,SP 180A,3P 230A,3P 150A,3P, 150A,SP 130A,SP 1
10. Switchgear Tag No: A1-SG-D1( Ref Drg No: 6400-A1-400-70-42 Rev J )SIEMENS MAKE 380V SWITCHGEAR
2000A, ACB 22000A, ACB 1380V,3-ph,50HZ,50KA for 1sec225A,40KW 1100A 350KW,100A 275A 10110A 6100A 6100KW,225A 215KW,100A 20.5KW,100A 21250A,ACB 234KW,225A 1
11. Switchgear Tag No: A1-SP-SSP-D1( Ref Drg No: 6400-A1-400-70-48 )SIEMENS MAKE 380V SWITCHGEAR
1250A, ACB 2
1250A, ACB 1380V,3-ph,50HZ,50KA for 1sec75A 330KW,110A 2150W,100A 310KW,100A 215KW,100A 4225A 36KW,100A 24KW,100A 230KW,100A 15KW,100A 1400A 1100A 1100A 1
14. Switchgear Tag No: A4-SG-D1 ( Ref Drg No: 6400-A1-444-70-6 Rev F )SIEMENS MAKE 380V SWITCHGEAR
1250A, ACB 21250A, ACB 1380V,3-ph,50HZ,50KA for 1sec75A 7100A 3100A 37.5KW,75A 1
15. Switchgear Tag No: A1-SG-D4 ( Ref Drg No: 6400-A1-400-70-38 Rev J )SIEMENS MAKE 380V SWITCHGEAR
REFER DRAWING FOR OPTION -1
FOR OPTION -22000A, ACB 22000A, ACB 1380V,3-ph,50HZ,50KA for 1sec225A,40KW 1100A 350KW,100A 275A 10110A 6
TYPE OF FEEDER TYPE FEEDER DETAILS1. Switchgear Tag No: A1-SP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 1 Rev H )
SIEMENS MAKE 380V SWITCHGEAR LOCATION : CONTROL ROOMINCOMER TYPE-3 DRAWOUT TYPE ACB BUSBARMETERINGSTANDBY SUPPLY FOR HVAC TYPE-3 DRAWOUT TYPE MCCB BLANK
TYPE-3 DRAWOUT TYPE MCCB SAFENIFE UPS2 INPUT TYPE-3 DRAWOUT TYPE MCCB SPARE EMPTYGUTOR UPS-1 TYPE-3 DRAWOUT TYPE MCCB REHEATING INVERTER TYPE-3 DRAWOUT TYPE MCCB WELDING RECEPTABLE TYPE-3 DRAWOUT TYPE MCCB CHARGER NO.-1 TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB METERINGBLANKBLANK48V DC BATTERY CHARGER-1SPARENORMAL LIGHTINGSPARE
2. Switchgear Tag No: A1-SSP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 2 Rev H )SIEMENS MAKE 380V SWITCHGEAR LOCATION : CONTROL ROOM
AIR CONDITIONING CONTROL ROOM TYPE-3 DRAWOUT TYPE MCCB METERING & PROTECTIONINCOMER TYPE-3 DRAWOUT TYPE ACB BUSBARSPARE EMPTYSAFENIFE UPS INPUT TYPE-3 DRAWOUT TYPE MCCB SAFENIFE UPS1 INPUT TYPE-3 DRAWOUT TYPE MCCB EMERGENCY LIGHTING TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB METERING TYPE-3SPARE TYPE-3 DRAWOUT TYPE MCCB 48V DC BATTERY CHARGER-2 TYPE-3 DRAWOUT TYPE MCCB TRANSFORMER TYPE-3 DRAWOUT TYPE MCCB
SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB REHEATING STATIC CHARGER OVER TYPE-3 DRAWOUT TYPE MCCB REHEATING INVERTER NO.-2 TYPE-3 DRAWOUT TYPE MCCB SPARE EMPTYGUTOR BYPASS TYPE-3 DRAWOUT TYPE MCCB GUTOR UPS-2 TYPE-3 DRAWOUT TYPE MCCB
3. Switchgear Tag No: A1-SG-D3( Ref Drg No: 6400-A1-400-70-37 Rev K )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 02
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSBARBUSCOUPLER TYPE-3 DRAWOUT TYPE ACB SPARE TYPE-3 DRAWOUT TYPE MCCB CRUDE OIL PUMP TYPE-3 DRAWOUT TYPE MCCB AIR COOLED HEAT EXCHANGER TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB RESIDUAL PUMP TYPE-3 DRAWOUT TYPE MCCB OIL RECIRCULATING PUMP TYPE-3 DRAWOUT TYPE MCCB INJECTION PUMP TYPE-3 DRAWOUT TYPE MCCB DIESEL FEED PUMP TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB WELDING RECEPTABLE TYPE-3 DRAWOUT TYPE MCCB NORMAL LIGHTING TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB AIR CONDITIONING TYPE-3 DRAWOUT TYPE MCCB CRUDE HEATER FAN TYPE-3 DRAWOUT TYPE MCCB
TYPE-4 DRAWOUT TYPE ACB
4. Switchgear Tag No: A1-SP-SSP-D3( Ref Drg No: 6400-A1-400-70-44-001 )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 02
INCOMER TYPE-3 DRAWOUT TYPE ACB BUS TIE TYPE-3 DRAWOUT TYPE ACB INCOMER TYPE-3 DRAWOUT TYPE ACB BUSBARSPARE TYPE-3 DRAWOUT TYPE MCCB FIRE STATION BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB CRUDE TRANSFER PUMP DRAWOUT TYPE CONTACTORSPARE EMPTYREHEAT MOTORS & CELLS TYPE-3 DRAWOUT TYPE MCCB BATTERY CHARGER 48VDC TYPE-3 DRAWOUT TYPE MCCB
SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB FIRE STATION TYPE-3 DRAWOUT TYPE MCCB LABORATORY TYPE-3 DRAWOUT TYPE MCCB 125V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB SPARE EMPTYGATE HOUSE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE EMPTYSTRIPPER REBOILING PUMP TYPE-3 DRAWOUT TYPE CONTACTORSPARE TYPE-3 DRAWOUT TYPE CONTACTORSPARE EMPTYCONTROL ROOM TYPE-3 DRAWOUT TYPE ACB SPARE EMPTYSPARE TYPE-3 DRAWOUT TYPE CONTACTOR125V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB SUBSTN. AUXILLARIES TYPE-3 DRAWOUT TYPE MCCB MOV PANEL TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB BATTERY CHARGER 48VDC TYPE-3 DRAWOUT TYPE MCCB FIRE STATION BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB FIRE STATION TRANSFORMER TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE CONTACTORSPARE EMPTYEMERGENCY LIGHTING TYPE-3 DRAWOUT TYPE MCCB LAB. TRAFO TYPE-3 DRAWOUT TYPE MCCB OIL DEHYDRATION PROJECT TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE CONTACTOR
7. Switchgear Tag No: C5-SG-D1( Ref Drg No: 6400-A1-SS11-70-4 Rev H )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 11
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSBAR125V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB 48V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB SUBSTATION AUXILLARIES TYPE-3 DRAWOUT TYPE MCCB AIR CONDITIONING SUBSTATION TYPE-3 DRAWOUT TYPE MCCB REHEATING SWITCHGEAR TYPE-3 DRAWOUT TYPE MCCB ONLOAD TAP CHANGER OUTGOING TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB
TYPE-3 DRAWOUT TYPE MCCB FIRE ALARM PANEL TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB
8. Switchgear Tag No: AP-LC-D ( Ref Drg No: 406-4001. )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 14
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSCOUPLER TYPE-3 DRAWOUT TYPE ACB BUSBAR
TYPE-3 DRAWOUT TYPE MCCB TYPE-3 DRAWOUT TYPE MCCB TYPE-3 DRAWOUT TYPE MCCB TYPE-3 DRAWOUT TYPE MCCB TYPE-3 DRAWOUT TYPE MCCB
9. Switchgear Tag No: AP-LCE-D ( Ref Drg No: 406-4001. )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 14
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSBAR
10. Switchgear Tag No: A1-SG-D1( Ref Drg No: 6400-A1-400-70-42 Rev J )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 15
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSCOUPLER TYPE-3 DRAWOUT TYPE ACB BUSBARNORMAL LIGHTING TYPE-3 DRAWOUT TYPE MCCB WELDING RECEPTABLE TYPE-3 DRAWOUT TYPE MCCB PUMPING STN. EQPT. TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB DESALINATION PLANT TYPE-3 DRAWOUT TYPE MCCB SEA WATER CHLORINATION UNIT TYPE-3 DRAWOUT TYPE MCCB REHEATING RIGHT ANGLE FAN TYPE-3 DRAWOUT TYPE MCCB
TYPE-3 DRAWOUT TYPE ACB AIR CONDITIONING SUBSTATION TYPE-3 DRAWOUT TYPE MCCB
11. Switchgear Tag No: A1-SP-SSP-D1( Ref Drg No: 6400-A1-400-70-48 )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 15
INCOMER TYPE-3 DRAWOUT TYPE ACB
BUSCOUPLER TYPE-3 DRAWOUT TYPE ACB BUSBARSPARE TYPE-3 DRAWOUT TYPE MCCB FIRE WATER JOKEY PUMP TYPE-3 DRAWOUT TYPE MCCB REHEATING CELLS TYPE-3 DRAWOUT TYPE MCCB SEA WATER PREFILTERATION TYPE-3 DRAWOUT TYPE MCCB SUBSTATION AUXILLARIES TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB 48V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB 125V DC BATTERY CHARGER TYPE-3 DRAWOUT TYPE MCCB EMERGENCY LIGHTING TYPE-3 DRAWOUT TYPE MCCB SUBSTATION AUXILLARIES TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB MOV PANEL TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB
14. Switchgear Tag No: A4-SG-D1 ( Ref Drg No: 6400-A1-444-70-6 Rev F )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 111
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSCOUPLER TYPE-3 DRAWOUT TYPE ACB BUSBARSPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB WELDING RECEPTABLE TYPE-3 DRAWOUT TYPE MCCB LUBE OIL PUMP TYPE-3 DRAWOUT TYPE MCCB
15. Switchgear Tag No: A1-SG-D4 ( Ref Drg No: 6400-A1-400-70-38 Rev J )SIEMENS MAKE 380V SWITCHGEAR LOCATION : SUBSTATION 111
INCOMER TYPE-3 DRAWOUT TYPE ACB BUSCOUPLER TYPE-3 DRAWOUT TYPE ACB BUSBARNORMAL LIGHTING TYPE-3 DRAWOUT TYPE MCCB WELDING RECEPTABLE TYPE-3 DRAWOUT TYPE MCCB PUMPING STN. EQPT. TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB SPARE TYPE-3 DRAWOUT TYPE MCCB
ADDITIONAL INFO.1. Switchgear Tag No: A1-SP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 1 Rev H )
LOCATION : CONTROL ROOM
2. Switchgear Tag No: A1-SSP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 2 Rev H )LOCATION : CONTROL ROOM
3. Switchgear Tag No: A1-SG-D3( Ref Drg No: 6400-A1-400-70-37 Rev K )LOCATION : SUBSTATION 02AUTOMATIC TRANSFER SCHEME WITH BUS COUPLER
INCOMERS FOR NEXT LV BOARD
4. Switchgear Tag No: A1-SP-SSP-D3( Ref Drg No: 6400-A1-400-70-44-001 )LOCATION : SUBSTATION 02TWO FEEDERS MERGED AUTOMATIC TRANSFER WITH INCOMER -9 & ANOTHER FEEDER
7. Switchgear Tag No: C5-SG-D1( Ref Drg No: 6400-A1-SS11-70-4 Rev H )LOCATION : SUBSTATION 11
8. Switchgear Tag No: AP-LC-D ( Ref Drg No: 406-4001. )LOCATION : SUBSTATION 14
INTERLOCKED WITH INCOMERS FROM TRAFO's
9. Switchgear Tag No: AP-LCE-D ( Ref Drg No: 406-4001. )LOCATION : SUBSTATION 14INCOMING FROM GENERATOR VIA AUTO TRANSFER SWITCH
10. Switchgear Tag No: A1-SG-D1( Ref Drg No: 6400-A1-400-70-42 Rev J )LOCATION : SUBSTATION 15AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER
11. Switchgear Tag No: A1-SP-SSP-D1( Ref Drg No: 6400-A1-400-70-48 )LOCATION : SUBSTATION 15AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER
INCOMERS FROM 630KVA, 22KV/380V
14. Switchgear Tag No: A4-SG-D1 ( Ref Drg No: 6400-A1-444-70-6 Rev F )LOCATION : SUBSTATION 111
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER
15. Switchgear Tag No: A1-SG-D4 ( Ref Drg No: 6400-A1-400-70-38 Rev J )LOCATION : SUBSTATION 111
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER