Cyclonic Area Design Manual 1
Using TOPSPAN profles
and LYSAGHT roofngand walling claddings
in cyclonic areasCyclc AaDesign Manual
This manual has bn prpard to assist
architcts, nginrs and buildrs in thcorrct spcication and installation of
LYSAGHT TOPSPAN prols and roong &
walling claddings in cyclonic aras.
It is a supplmnt to th LYSAGHT
Roong & Walling Manual and individual
product brochurs, and should b usd in
conjunction with thos publications.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
2/36
2 Cyclonic Area Design Manual
1. Us ths maualAll information in this manual should b rad in conjunction
with th rlvant Australian Standards and Amndmnts:
AS1170.2:2002 Wind Loads on Housing: Structural Dsign
Actions, Part 2: Wind Actions and AS4055:2006.
Th Wind Prssur Capacity tabls ar dtrmind by
full scal tsts conductd at BluScop Lysaghts NATA-
accrditd tsting laboratory, using th dirct prssur-
tsting rig. This offrs th full bnts of th latst mthods
for modlling wind prssurs. Tsting was conductd in
accordanc with th low-high-low rquirmnts of th
Building Cod of Australia. Appropriat rduction factors hav
bn applid to capacitis as tstd to gnrat th dsign
capacitis prsntd in this Manual.
Fastnrs, cyclonic washrs and fastning pattrn all form an
intgratd roong/walling systm prscribd in this manual.
This manual contains th following tchnical information:
Ultimat limit stat dsign capacity tabls ar providd to
allow nginrs dsigning largr non-rsidntial structurs
to prform th ncssary calculations basd on thir
spcic dsigns in accordanc with AS1170.2: 2002.
Rsidntial tabls ar supplid to provid quick and asy
look up of th suitability of products in rsidntial roong
and walling, according to AS4055:2006.
Data is supplid in Ultimat Limit Stat dsign capacity
tabls for a rang of LYSAGHT TOPSPAN stl sctions.
Spcic tchnical information such as Matrial
Spcications, Sction Proprtis and rcommndd
fastnrs and connction dtails ar providd.
Gnral tchnical information such as Wind Classications
and Topographic Classications ar providd in appndics..
Ctts1. Using this manual 2
2. L-H-L tsting procdurs usd for this dsign manual 3
3. Rsidntial & non rsidntial dsign capacity tabls 4-11
4. Rsidntial slction tabls - roong 12-14
5. Rsidntial slction tabls - walling 15
6. Cladding span slction tabls 16-18
7. TOPSPAN prols 19
8. TOPSPAN Capacity tabls 19-22
9. TOPSPAN sction proprtis 23
10. Matrial spcications 24
11. Rcommndd fastnr locations and lap dtails 25
12. Fastnr slction 26
13. Fastning to supports 27
14. Impact loading by wind-born dbris 29
Appendices
Appndix 1) Wind classication 30
Appndix 2) Topographic classication 31
Appndix 3) Tropical cyclons and wind forcson buildings 32
Appndix 4) Local prssur aras 33
BluScop Stl has bn a long tim supportr of th
Cyclon Tsting Station at Jams Cook Univrsity. Through
our involvmnt with this important rsarch facility, w hav
contributd to safr building practics in cyclon pron aras.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
3/36
Cyclonic Area Design Manual 3
Th information in this documnt includs cyclonic capacitis
for a rang of LYSAGHT claddings and TOPSPAN prols.
Ths capacitis ar drivd from xtnsiv full scalcyclonic tsts conductd at BluScop Lysaghts NATA-
accrditd matrials scinc tsting laboratory.
L-Hh-L Pssu Squc Cyclc Aas
Th Building Cod of Australia (BCA) currntly rquirs all
roof claddings, xing connctions and immdiat supporting
mmbrs to withstand a low-high-low (LHL) cyclonic tsting
rgim. TOPSPAN prols ar immdiat supporting mmbrs
according to th BCA dnition, and as such, must b tstd
using th LHL cyclonic tsting mthodology to dtrmin th
outward capacity.
BluScop Lysaght Rsarch & Tchnology has prformdcomprhnsiv full scal tsts of th ntir rang of claddings
and TOPSPAN prols. Ths tsts wr conductd on our
dirct air prssur rig in our tsting laboratory.
2.L-H-L tst pcdus usd thsds maual
4500 cycles - 0.45Pt
5000 cycles 10000 cycles
600 cycles - 0.6Pt
80 cycles - 0.8Pt
1 cycle - Pt
L-H-L Loading regime from BCA
Low Low
HighPt
Fu 2.2 Dct A Pssu tst shcladd alu
Typs alus
Our xtnsiv tsting has rvald that battns can b
subjct to fatigu failur. Whn dsign is basd on valus
within th publishd capacity tabls, failur du to fatigu will
not occur, as our tsts ar prformd according to th L-H-L
rgim.
Non-LYSAGHT products cannot b substitutd using ths
tst valus. Bcaus our products hav bn subjctd to
full scal L-H-L tsting, you can rly on th prformanc data
w supply for gnuin LYSAGHT products. Substituting non-
LYSAGHT products using ths tst valus could caus failur
du to fatigu.
Th squnc L-H-L loading rgim is shown in th graph
abov whr Pt is th ultimat limit stat wind prssur. Fu 2.3 ToPSPAn stl sct (batt) atucac
Fu 2.1Low-high-low tsting
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
4/36
4 Cyclonic Area Design Manual
kLiP-Lok 700 Hi-STrengTH
kLiP-Lok 700HS clp
Tabl 3.1:kLiP-Lok 700HS 0.42 BMT -Ultmat Lmt Stat d pssu (Pa)
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
700 mm cover
43 mm
UnderlapOverlap
3. rsdtal & -sdtalds capacty tabls
SpanRoofing or Walling
mmClip fastened
Single End Internal
600 8.10
900 6.40
1200 4.86
1500 3.95
1800 3.13
2100 2.75
2400 2.29
2700 2.20
8.55
6.31
4.50
3.13
2.85
2.56
2.28
2.00
11.25
11.25
8.46
6.14
4.30
2.93
2.04
1.62
SpanRoofing or Walling
mmClip fastened
Single End Internal
600 9.45
900 7.42
1200 5.58
1500 4.47
1800 3.46
2100 2.97
2400 2.37
2700 2.20
9.45
6.90
4.86
3.32
3.04
2.76
2.48
2.21
11.25
11.25
8.46
6.16
4.36
3.04
2.22
1.89
noTeS
i) Mor dtaild information is availabl in th individual product
brochurs, and/or th currnt LYSAGHT Roong & Walling Manual
which ar availabl at: www.lysaght.com. W also rfr you to th
rlvant Australian Standards.
ii) Th dsign tabls in th manual ar valid for KLIP-LOK 700HS
ovrhang lngths not xcding 100mm. Longr ovrhangs ar
possibl subjct to additional tsting.
iii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
iv) KLIP-LOK 700HS ovrhangs shall b xd as shown on Figur 6.1
(pag 14) whn prssur xcds 4.0kPa for 0.42 BMT and 6.6kPa
for 0.48 BMT
Tabl 3.2: kLiP-Lok 700HS 0.48 BMT -Ultmat Lmt Stat d pssu (Pa)
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
5/36
Cyclonic Area Design Manual 5
Tabl 3.3: CUSToM orB 0.42 BMT - Ultmat Lmt Stat d pssu (Pa)
Tabl 3.4: CUSToM orB 0.48 BMT - Ultmat Lmt Stat d pssu (Pa)
Span
Roofing or Walling Walling only
(mm)
Crest fastened without Crest fastened withValley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 8.64 6.47 8.09 8.64 8.10 10.13 10.80 8.10 8.09900 6.19 4.37 5.57 6.19 5.18 7.34 7.00 5.18 6.17
1200 4.05 2.74 3.71 4.05 3.01 5.05 4.05 3.01 4.521500 2.23 1.58 2.52 2.23 1.58 3.27 1.96 1.58 3.121800 0.72 0.90 1.99 0.72 0.90 1.99 0.72 0.90 1.99
Span
Roofing or Walling Walling only
(mm)
Crest fastened without Crest fastened withValley fastened
cyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 10.80 8.10 10.13 10.80 8.16 10.80 10.80 8.10 10.13900 6.98 5.56 7.14 6.98 6.54 8.65 6.98 5.56 7.38
1200 4.05 3.57 4.81 4.05 5.05 6.68 4.05 3.57 5.18
1500 2.02 2.12 3.15 2.02 3.69 4.88 2.02 2.12 3.511800 0.88 1.22 2.14 0.88 2.46 3.25 0.88 1.22 2.392100 0.86 1.80 0.00 1.36 1.80 0.00 0.86 1.80
CUSToM orB
762 mm cover
17 mm
UnderlapOverlap
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
noTeS
i) Mor dtaild information (including ovrhangs) is availabl in th
individual product brochurs, and/or th currnt LYSAGHT Roong
& Walling Manual which ar availabl at: www.lysaght.com. W
also rfr you to th rlvant Australian Standards.
ii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
6/36
6 Cyclonic Area Design Manual
Tabl 3.5: CUSToM BLUe orB 0.60 BMT - Ultmat Lmt Stat d pssu (Pa)
CUSToM BLUe orB
762 mm cover
17 mm
UnderlapOverlap
Span
Roofing or Walling Walling only
(mm)
Crest fastened without Crest fastened with Valley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 10.80 10.80 10.80 10.80 10.80 10.80 10.80 10.80 10.80900 6.30 8.04 8.62 7.45 8.52 9.82 6.30 8.04 8.62
1200 3.38 5.88 6.64 5.28 6.68 8.62 3.38 5.88 6.641500 2.81 4.32 4.86 4.88 5.27 7.20 2.81 4.32 4.861800 2.25 3.36 3.28 4.47 4.28 5.56 2.25 3.36 3.282100 3.00 1.90 3.73 3.70 3.00 1.90
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
noTeS
i) Mor dtaild information (including ovrhangs) is availabl in th
individual product brochurs, and/or th currnt LYSAGHT Roong
& Walling Manual which ar availabl at: www.lysaght.com. W
also rfr you to th rlvant Australian Standards.
ii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
7/36
Cyclonic Area Design Manual 7
TriMDekOverlap Underlap
762 mm cover
29 mm
Tabl 3.6: TriMDek0.42 BMT - Ultmat Lmt Stat d pssu (Pa)
Tabl 3.7: TriMDek0.48 BMT - Ultmat Lmt Stat d pssu (Pa)
SpanRoofing or Walling Walling only
(mm)Crest fastened without Crest fastened with
Valley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 5.94 5.94 5.04 10.80 10.80 10.80 10.80 5.94 7.43900 4.30 4.31 3.59 7.03 7.23 8.02 6.25 4.31 5.49
1200 2.97 2.96 2.51 4.15 4.43 5.70 2.97 2.96 3.931500 1.94 1.91 1.80 2.14 2.40 3.83 0.96 1.91 2.751800 1.20 1.15 1.64 1.02 1.15 2.43 0.87 1.15 1.932100 0.77 0.68 1.49 0.77 0.68 1.49 0.77 0.68 1.49
SpanRoofing or Walling Walling
(mm)Crest fastened without Crest fastened with
Valley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 6.91 6.21 6.48 10.80 10.80 10.80 10.80 6.21 10.80900 5.22 4.74 5.28 7.88 7.65 8.61 6.84 4.74 7.68
1200 3.80 3.50 4.25 5.47 5.15 6.69 3.80 3.50 5.211500 2.65 2.48 3.38 3.56 3.29 5.05 3.06 2.48 4.341800 1.78 1.70 2.67 2.16 2.09 3.68 2.33 1.70 3.482100 1.18 1.14 2.13 1.25 1.85 2.58 1.59 1.14 2.622400 0.86 0.81 1.76 0.86 1.62 1.76 0.86 0.81 1.76
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
noTeS
i) Mor dtaild information (including ovrhangs) is availabl in th
individual product brochurs, and/or th currnt LYSAGHT Roong
& Walling Manual which ar availabl at: www.lysaght.com. Walso rfr you to th rlvant Australian Standards.
ii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
8/36
8 Cyclonic Area Design Manual
Tabl 3.8: SPAnDek0.42 BMT - Ultmat Lmt Stat d pssu (Pa)
SpanRoofing or Walling Walling only
(mm)Crest fastened without Crest fastened with
Valley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 6.56 4.05 5.07 10.80 10.80 10.80 8.10 4.05 5.07900 3.89 3.01 3.95 7.48 7.52 8.14 4.51 3.01 3.95
1200 2.03 2.20 3.03 4.86 4.97 5.98 2.03 2.20 3.031500 1.76 1.62 2.30 2.95 3.13 4.30 1.76 1.62 2.301800 1.50 1.26 1.78 1.74 2.02 3.12 1.50 1.26 1.782100 1.24 1.13 1.45 1.24 1.62 2.43 1.24 1.13 1.45
Tabl 3.9: SPAnDek0.48 BMT - Ultmat Lmt Stat d pssu (Pa)
SpanRoofing or Walling Walling only
(mm) Crest fastened without Crest fastened with Valley fastenedcyclonic washers cyclonic washers
Single End Internal Single End Internal Single End Internal
600 8.64 6.21 6.98 10.80 10.80 10.80 10.80 6.21 7.76900 5.47 4.74 5.38 8.04 7.56 8.74 6.37 4.74 5.81
1200 3.11 3.49 4.08 5.77 5.00 6.92 3.11 3.49 4.261500 2.73 2.48 3.11 3.99 3.13 5.34 2.73 2.48 3.111800 2.36 1.71 2.44 2.71 2.63 4.00 2.36 1.71 2.752100 1.99 1.16 2.09 1.92 2.12 2.91 1.99 1.16 2.402400 1.62 0.86 2.05 1.62 1.62 2.05 1.62 0.86 2.05
SPAnDek
700 mm cover
24 mm
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
noTeS
i) Mor dtaild information (including ovrhangs) is availabl in th
individual product brochurs, and/or th currnt LYSAGHT Roong
& Walling Manual which ar availabl at: www.lysaght.com. W
also rfr you to th rlvant Australian Standards.
ii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
9/36
Cyclonic Area Design Manual 9
kLiP-Lok 406
HigH winD(nth Tty ad w.A. ly)
406 mm cover
41 mm
KLIP-LOK 406 High Wind
Span
600
900
1200
1500
1800
Crest fastened withcyclonic washers
End Internal
Roofing or Walling Roofing or Walling
1900
Span
600
900
1200
1500
1800
Crest fastened withcyclonic washers
End Internal
1900
2100
12.00
9.27
6.98
4.93
3.88
12.00
10.60
7.91
6.27
5.07
3.58 4.78
2400
12.00
9.70
7.31
5.37
4.18
12.00
11.94
8.96
7.31
5.52
3.88 5.07
3.43 4.48
2.99 3.73
mmmm
Tabl 3.10: kLiP-Lok 406 Hh wd0.55 BMT - Ultmat Lmt Statd pssu (Pa)
Tabl 3.11: kLiP-Lok 406 Hh wd0.70 BMT - Ultmat Lmt Statd pssu (Pa)
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
noTeS
i) Rfr to th currnt LYSAGHT Roong & Walling Manual which is
availabl on our wbsit: www.lysaght.com. W also rfr you to
th rlvant Australian Standards.
ii) Th dsign tabls in th manual ar valid for KLIP-LOK 406 High
Wind ovrhang lngths not xcding 100mm. Longr ovrhangs
ar possibl subjct to additional tsting.
iii) For KLIP-LOK 406 High Wind dtaild information, rfr to
Northrn Trritory Dmd to comply documntation. This data
is also availabl on our wbsit: www.lysaght.com
iv) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
10/36
10 Cyclonic Area Design Manual
In cyclonic applications, KLIP-LOK CLASSIC 700 is
pirc xd through th ribs using fastnrs with
cyclonic washrs.
kLiP-Lok CLASSiC 700
Tabl 3.11:kLiP-Lok CLASSiC 700 0.42 BMT- Ultmat Lmt Stat d pssu (Pa)
ES
IS
ES Single span
Spacing definitionsES = End spanIS = Internal spanO = Overhang
IS
O
O
Walling profiles only
Roofing & Walling profiles
Step
Cover width 700mm
Overlap Underlap
40mm
Span
Roofing or Walling
(mm) Crest fastened with cyclonic washers Single End Internal
600 8.26 7.85 7.85
900 6.61 5.79 6.20
1200 4.55 3.72 4.96
1500 2.89 2.89 3.72
1800 2.07 2.07 2.48
2100 1.65 1.65 1.65
Span
Roofing or Walling
(mm) Crest fastened with cyclonic washers
Single End Internal
600 9.09 8.26 8.26
900 7.44 6.61 7.02
1200 5.37 4.55 5.79
1500 4.55 3.72 4.55
1800 3.31 2.89 3.31
2100 2.07 2.48 2.89
noTeS
i) Mor dtaild information is availabl in th individual product
brochurs, and/or th currnt LYSAGHT Roong & Walling Manual
which ar availabl at: www.lysaght.com. W also rfr you to th
rlvant Australian Standards.
ii) Th dsign tabls in th manual ar valid for KLIP-LOK CLASSIC
700 ovrhang lngths not xcding 100mm. Longr ovrhangs
ar possibl subjct to additional tsting.
iii) Th prssurs supplid ar applicabl whn th cladding is xd
to a minimum of 1.5mm G450 stl.
Tabl 3.12: kLiP-Lok CLASSiC 700 0.48 BMT -Ultmat Lmt Stat d pssu (Pa)
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
11/36
Cyclonic Area Design Manual 11
FLATDeKdiffrs from othr roong products bcaus it isxd to supports through th pans. It is colourd both sids
and is rcommndd for applications such as carports and
patios and is not rcommndd for rsidntial roofs.
FLATDek ii(Hm impvmts pfl)
Span (mm) Single Span Double Span
1500
1800
2100
2400
2700
3000
33003600
4000
5.26 4.64
4.76 4.21
4.32 3.82
3.84 3.68
3.38 3.44
3.08 3.14
2.80 2.802.51 2.46
2.25 2.04
Spa dfts
OverlapUnderlap
mm
(nominal)
Single span
OverhangDouble
span
Overhang
Tabl 3.13: FLATDek ii0.42 BMTUltmat Lmt Stat d pssu (Pa)
noTeS
i) Mor dtaild information (including ovrhangs) is availabl in
th individual product brochurs, and/or th currnt LYSAGHT
Roong & Walling Manual which ar availabl at: www.lysaght.
com. W also rfr you to th rlvant Australian Standards.
ii) Th prssurs supplid ar applicabl whn th cladding is
xd to a minimum of two thicknsss of 0.55mm (total 1.10mm)
G450 stl or a singl thicknss of 1.50mm G450.
iii) Th dsign tabls in th manual ar valid for FLATDeK II
ovrhang lngths not xcding 100mm.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
12/36
12 Cyclonic Area Design Manual
4. rsdtal slct tabls - rooFing
Table 4.1 CUSTOM ORB 0.42mm BMTRoofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK X X
600 OK OK X X
750 OK OK X X
900 OK X X X
1200 X X X X
Table 4.2 CUSTOM ORB 0.42mm BMT
Roofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK X
600 OK OK X
750 OK OK
OK
OK
OK X
900 OK OK
OK
X X
1200 X X X
Table 4.3 CUSTOM ORB 0.48mm BMTRoofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK X
600 OK OK X
750 OK OK
OK
OK
OK X
900 OK OK
OK
X X
1200 X X X
Table 4.4 CUSTOM ORB 0.48mm BMTRoofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK
600 OK OK
750 OK OK X
900 OK OK
OK
OK
OK
OK
OK
OK
OK X
1200 OK X X
Table 4.5 CUSTOM BLUE ORB 0.60mm BMT
Roofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK OK
600 OK OK OK OK
750 OK OK OK
OK
X
900 OK OK X
1200 OK OK X X
Table 4.6 CUSTOM BLUE ORB 0.60mm BMTRoofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK OK
600 OK OK OK OK
750 OK OK OK X900 OK OK
OK
OK X
1200 OK OK X
762 mm cover
UnderlapOverlap
16 mm CO
17 mm CBO
customorb
customblueorb
Not:
1. Maximum prssur of 10.8 kPa for C4 catgory
is limitd by tsting quipmnt. It is ncssaryto us AS 1170.2 for houss to chck ifmaximum wind prssur dos not xcd 10.8kPa.
2. Wind prssurs corrsponding to C windcatgoris ar takn for aras within 1200mmof roof dgs with load prssur cofcintK
l=2.0. Othr aras with lowr prssurs can
b consrvativly dsignd using ths tabls.Us tabls in Sctions 3 and 6 of this manual formor conomical dsigns.
3. end span lngth should b 0.8 tims th valusgivn in ths continuous span tabls, in th
cas whr a maximum possibl roof span ischosn.
4) Th prssurs supplid ar applicabl whn
th cladding is xd to a minimum of 1.5mm
BMT G450 stl.
Rsidntial tabls ar supplid to provid quick
and asy look up of th suitability of products
in rsidntial roong and walling, according
to AS4055:2006. To us ths tabls, turn toth product you ar thinking of using, look up
th span width you want to us and th Wind
Classication according to AS4055:2006. An OK
mans this product can b usd, a cross (7)
mans it is not suitabl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
13/36
Cyclonic Area Design Manual 13
Table 4.7 TRIMDEK 0.42 BMTRoofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
450 OK X X
600 OK
OK
OK X X
750 OK X X X900 OK X X X
1200 X X X X
Table 4.8 TRIMDEK 0.42 BMTRoofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
450 OK OK OK OK
600 OK OK OK OK
750 OK OK OK X
900 OK OK
OK
X X
1200OK X X
Table 4.9 TRIMDEK 0.48 BMT
Roofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK X X
600 OK OK
OK
X X
750 OK X X
900 OK
OK
X X X
1200 X X X
Table 4.10 TRIMDEK 0.48 BMT
Roofs Crest fixed With cyclonic washersSpan C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK OK
600 OK OK OK OK
750 OK OK OK X
900 OK OK OK
OK
X
1200 OK X X
TriMDek
Not:
1. Maximum prssur of 10.8 kPa for C4 catgory
is limitd by tsting quipmnt. It is ncssaryto us AS 1170.2 for houss to chck if maximumwind prssur dos not xcd 10.8 kPa.
2. Wind prssurs corrsponding to C windcatgoris ar takn for aras within 1200mmof roof dgs with load prssur cofcintK
l=2.0. Othr aras with lowr prssurs can b
consrvativly dsignd using ths tabls. Ustabls in Sctions 3 and 6 of this manual for morconomical dsigns.
3. end span lngth should b 0.8 tims th valusgivn in ths continuous span tabls, in thcas whr a maximum possibl roof span is
chosn.4) Th prssurs supplid ar applicabl whn th
cladding is xd to a minimum of 1.5mm BMT
G450 stl.
rsdtal slct tabls - rooFing
762 mm cover
29 mm
Rsidntial tabls ar supplid to provid quick
and asy look up of th suitability of products
in rsidntial roong and walling, according
to AS4055:2006. To us ths tabls, turn to
th product you ar thinking of using, look up
th span width you want to us and th Wind
Classication according to AS4055:2006. An OKmans this product can b usd, a cross (7)
mans it is not suitabl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
14/36
14 Cyclonic Area Design Manual
Table 4.11 SPANDEK 0.42 BMTRoofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK X X X600 OK
OK
OK
X X X
750 X X X900 X X X
1200 X X X X
Table 4.12 SPANDEK 0.42 BMTRoofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK OK600 OK OK OK OK750 OK OK OK X900 OK OK
OK
X X
1200 OK X X
Table 4.13 SPANDEK 0.48 BMTRoofs Crest fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK X X600 OK OK X X750 OK X X900 OK
OK
OK
X X X
1200 X X X
Table 4.14 SPANDEK 0.48 BMTRoofs Crest fixed With cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK OK600 OK OK OK OK750 OK OK OK X900 OK OK OK
OK
X
1200 OK X X
700 mm cover
24 mm
SPAnDek
rsdtal slct tabls - rooFing
Not:
1. Maximum prssur of 10.8 kPa for C4 catgory is limitdby tsting quipmnt. It is ncssary to us AS 1170.2for houss to chck if maximum wind prssur dos notxcd 10.8 kPa.
2. Wind prssurs corrsponding to C wind catgorisar takn for aras within 1200mm of roof dgs withload prssur cofcint K
l=2.0. Othr aras with lowr
prssurs can b consrvativly dsignd using thstabls. Us tabls in Sctions 3 and 6 of this manual formor conomical dsigns.
3. end span lngth should b 0.8 tims th valus givnin ths continuous span tabls, in th cas whr amaximum possibl roof span is chosn.
4) Th prssurs supplid ar applicabl whn th cladding
is xd to a minimum of 1.5mm BMT G450 stl.
Rsidntial tabls ar supplid to provid quick
and asy look up of th suitability of products
in rsidntial roong and walling, according
to AS4055:2006. To us ths tabls, turn to
th product you ar thinking of using, look up
th span width you want to us and th Wind
Classication according to AS4055:2006. An OKmans this product can b usd, a cross (7)
mans it is not suitabl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
15/36
Cyclonic Area Design Manual 15
5. rsdtal slct tabls - wALLing
762 mm cover
UnderlapOverlap
16 mm CO
17 mm CBO
Table 5.1 CUSTOM ORB 0.42 BMT
Walls Valley fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK OK X
600 OK OK OK X
750 OK OK OK X900 OK OK
OK
X X
1200 OK X X
Table 5.2 CUSTOM ORB 0.48 BMT
Walls Valley fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
450 OK OK OK
600 OK OK OK
OK
OK
750 OK OK OK X
900 OK OK OK
OK
X
1200 OK X X
customorb
customblueorb
Overlap Underlap
762 mm cover
29 mm
trimdek
Table 5.3 TRIMDEK 0.42 BMT
Walls Valley fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
450 OK OK X
600 OK OK
OK
OK X
750OK OK X X
900 OK OK
OK
X X
1200 X X X
Table 5.4 TRIMDEK 0.48 BMT
Walls Valley fixed No cyclonic washers
Span C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)450 OK OK
600 OK OK
750 OK OK
900 OK OK
OK
OK
OK
OK
OK
OK
OK
OK
X
1200 OK X X
Not:
1. Maximum prssur of 10.8 kPa for C4 catgory is limitdby tsting quipmnt. It is ncssary to us AS 1170.2for houss to chck if maximum wind prssur dos notxcd 10.8 kPa.
2. Wind prssurs corrsponding to C wind catgorisar takn for aras within 1200mm of roof dgs withload prssur cofcint K
l=2.0. Othr aras with lowr
prssurs can b consrvativly dsignd using thstabls. Us tabls in Sctions 3 and 6 of this manual formor conomical dsigns.
3. end span lngth should b 0.8 tims th valus givnin ths continuous span tabls, in th cas whr amaximum possibl roof span is chosn.
4) Th prssurs supplid ar applicabl whn th cladding
is xd to a minimum of 1.5mm BMT G450 stl.
Rsidntial tabls ar supplid to provid quick
and asy look up of th suitability of products
in rsidntial roong and walling, according
to AS4055:2006. To us ths tabls, turn toth product you ar thinking of using, look up
th span width you want to us and th Wind
Classication according to AS4055:2006. An OK
mans this product can b usd, a cross (7)
mans it is not suitabl.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
16/36
16 Cyclonic Area Design Manual
nts:
1. Fastning shall comply with Sctions 12 & 13 of this Manual.
2. Fixing to stl supports with thicknss btwn 0.75 and 1.5mm may also rsult in rducd maximum spans du to rducd scrw pull-out
capacity.
3. Ultimat Limit Stat Wind prssur corrsponding to AS 4055:2006 wind classication in this tabl rfrs to roof aras within 1200mm.
(Kl= 2.0) according to AS 4055:2006 Tabl 3.3. excpt for C4 wind catgory whr prssurs ar givn for aras away from dgs and within
1200mm of dgs. Diffrnt prssurs will apply on othr roof and wall aras.
4. Whn prssur is calculatd in accordanc to AS/NZS 1170.2:2002 following paramtrs shall b usd:
Cpi
= +0.7 and -0.65
Kc
= 1.0
Kl= 1.5 and 2.0. K
l= 3.0 may b ncssary for walls of tall (>25m) buildings.
5. Outdatd W classication is givn as approximat rfrnc only.
6. Maximum prssur of 10.8 kPa for C4 catgory is limitd by tsting quipmnt. It is ncssary to us AS/NZS1170.2 for houss to chck if
maximum wind prssur dos not xcd 10.8 kPa.
7. No washrs ar rquird for KLIP-LOK-700 Hi-Strngth sinc it is usd as a concald xd cladding.
8. Th spans supplid ar applicabl whn th cladding is xd to a minimum of 1.5mm G450 stl.
6. Cladd spa slct tabls
kLiP-Lok 700HS qus std vhas
Whn xing KLIP-LOK 700 Hi-Strngth in cyclonic conditionsfor wind prssurs xcding 4.0kPa for 0.42BMT and 6.6kPa
for 0.48BMT, it is ssntial to x th shts at th nds, as
shown in th altrnativs illustratd in th gur at right.
Guttr can b xd through th rturn lip to th undrsid of
th roof shting at mid-span btwn th ribs, and this will
provid th rquird stiffning.
Altrnativly, x a 50 x 50 x 1.2mm stl angl approximatly
50mm from th nd of th KLIP-LOK sht and at mid-span
btwn ribs. Th guttr may thn b xd to th angl, if
rquird.
If an ovrhang stiffning is not an option, maximum prssursshall not xcd 4.0kPa for 0.42 BMT and 6.6kPa for 0.48 BMT. Steel angle 50 x 50 x 1.2 mm
fixed to underside of roofing(200 mm centres).Gutter may be fixed to angle.
Gutter fixed to underside of roofing(at mid-span between ribs)
Overhang
Overhan
g
Figure 6.1
Table 6.1Maximum cladding span tables (mm) for various LYSAGHT claddings and cyclonic winds WITHOUT cyclonic washers
BMT SpanC1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
Cladding(mm) Type
Away from edges Within 1200 mm of edges
2.40 kPa 3.75 kPa 5.58 kPa 8.21 kPa 10.8 kPa
CUSTOMBLUE ORB
CUSTOM ORB
CUSTOM ORB
0.42 End 1280 1010 720Internal 1560 1190 890
0.48End 1440 1170 890
Internal 1720 1390 1100 790
0.60End 2100 1670 1250 880 600
Internal 1990 1710 1370 960 600
TRIMDEK 0.42End 1350 1020 660
660Internal 1350 1020
TRIMDEK 0.48End 1530 1130 720
Internal 1950 1370 820
SPANDEK
SPANDEK
0.42End 1120 680
Internal 1460 960
0.48End 1530 1130 720
1830 1300 860Internal
2380 1710 1200 780
2320 1570 1050
2490 1410 1090 740
2270 1360 1020 640KLIP-LOK 700HS
KLIP-LOK 700HS
0.42End
Internal
0.48End
Internal
--
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
--
-
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
17/36
Cyclonic Area Design Manual 17
nts:
1. Fastning shall comply with Sctions 12 & 13 of this Manual.
2. Fixing to stl supports with thicknss btwn 0.75 and 1.5mm may also rsult in rducd maximum spans du to rducd scrw pull-out
capacity.
3. Ultimat Limit Stat Wind prssur corrsponding to AS 4055:2006 wind classication in this tabl rfrs to roof aras within 1200mm.
(Kl= 2.0) according to AS 4055:2006 Tabl 3.3. excpt for C4 wind catgory whr prssurs ar givn for aras away from dgs and within
1200mm of dgs. Diffrnt prssurs will apply on othr roof and wall aras.
4. Whn prssur is calculatd in accordanc to AS/NZS 1170.2:2002 following paramtrs shall b usd:
Cpi
= +0.7 and -0.65
Kc
= 1.0
Kl= 1.5 and 2.0. K
l= 3.0 may b ncssary for walls of tall (>25m) buildings.
5. Outdatd W classication is givn as approximat rfrnc only.
6. Maximum prssur of 10.8 kPa for C4 catgory is limitd by tsting quipmnt. It is ncssary to us AS/NZS 1170.2 for houss to chck if
maximum wind prssur dos not xcd 10.8 kPa.
7. No washrs ar rquird for KLIP-LOK-700 High Strngth sinc it is usd as a concald xd cladding.
8. Th spans supplid ar applicabl whn th cladding is xd to a minimum of 1.5mm G450 stl.
Table 6.2: Maximum purlins /girts spacing (mm) for various LYSAGHT Claddings and cyclonic w inds WITH cyclonic washers
RoofBMT Span
C1 (W41C) C2 (W50C) C3 (W60C) C4 (W70C)
Cladding(mm) Type
Away from edges Within 1200 mm from edges
2.40 3.75 5.58 8.21 10.8
CUSTOM ORB 0.42End 1320 1090 850
Internal 1700 1410 1130 800
CUSTOM ORB 0.48End 1810 1480 1090
Internal 1970 1700 1380 960 600
CUSTOM BLUE ORB 0.60End 2100 2080 1430 950 600
Internal 2100 2090 1790 1280 600
TRIMDEK 0.42End 1500 1300 1070 810 600
Internal 1800 1510 1210 870 600
TRIMDEK 0.48End 1720 1420 1140 840 600
Internal 2160 1780 1400 960 600
SPANDEK 0.42End 1690 1390 1120 830 600
Internal 2100 1640 1270 890 600
SPANDEK 0.48End 1930 1400 1130 830 600
Internal 2270 1860 1450 980 600
KLIP-LOK 700HS 0.42End 2270 1360 1020 640
Internal 2320 1570 1050
KLIP-LOK 700HS 0.48 End 2490 1410 1090 740Internal 2380 1710 1200 780
KLIP-LOK CLASSIC 700 0.42End 1670 1190 920
Internal 1820 1490 1040
KLIP-LOK CLASSIC 700 0.48End 2030 1480 1040 600
Internal 1740 1690 1240 610
-
-
--
-
-
-
-
-
-
--
-
-
-
-
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
18/36
18 Cyclonic Area Design Manual
Table 6.3 KLIP-LOK 406 HIGH WIND Maximum Span Tables WITH cyclonic washers
ULTIMATELIMIT
BUILDINGHEIGHT
TERRAINCATEGORY
Kl
pz
(kPa)
END END INTERNAL
UP TO5M
UP TO10M
1 & 2
1
1.5
2
1
1.5
4.16
5.33
6.50
3.53
4.52
2 5.52
1 2.95
3.78
4.61
2.5
3 & 4 1.5
2
1 & 2
1
1.5
2
1
1.5
2
1
2.5
3 & 4 1.5
2
4.61
5.91
7.20
4.12
5.28
3.65
4.68
5.71
6.43
INTERNAL
CREST FASTENED WITH CYCLONIC WASHERS
END END INTERNALINTERNAL
Mt
= 1.0 Mt
= 1.3
0.70 BMT0.55 BMT 0.70 BMT0.55 BMT
1710
1440
1260
1900
1610
1410
1900
1830
1590
1590
1350
1170
1730
1440
1870
1570
1380
1270
1900
1730
1450
1900
1900
1680
1900
1900
1900
1900
1590
1320
1900
1740
1900
1900
1640
1470
1800
1510
1320
2050
1710
1470
2400
1940
1690
1690
1410
1210
1810
1520
2000
1670
1440
1330
2220
1840
1630
2400
2080
1800
2400
2380
2050
2050
1730
1510
2240
1850
2400
2030
1760
1640
1190
710
1340
1110
890
1490
1280
1090
1090
820
N/A
1200
940
1310
1070
850
720
1360
1070
810
1570
1240
1040
1820
1470
1220
1220
960
N/A
1370
1080
1520
1200
1000
840
1240
980
730
1400
1150
940
1590
1340
1140
1140
860
N/A
1250
990
1370
1120
900
740
1540
1190
1720
1440
1160
1920
1650
1410
1410
1090
N/A
1550
1200
1690
1390
1130
1000
930
990
pz
(kPa)
7.03
9.01
10.99
5.97
7.64
9.33
4.99
6.39
7.79
7.79
9.99
12.17
6.96
8.92
6.17
7.91
9.65
10.87
1. Fastening shall comply with Sections 12 & 13 of this Manual.2. Fixing to steel supports with thickness between 0.75 and 1.5mm may also result in reduced maximum spans due to reduced screw pull-out capacity.
3. The spans supplied are applicable when the cladding is fixed to a minimum of 1.5mm G450 steel.4. Design Criteria :The following criteria from AS/NZS 1170.2:2002 have been used to generate
the tables:
a) Importance Level 2 with return period of 500 yearsb) VR = 66 m/sec., Fc = 1.05
c) Ms = Md = 1.0d) Mt = 1.0 & 1.3 5.e) Cpe = -0.9; Cpi = +0.7
f) Height multipliers from table 6.4
HEIGHT(m)
TERRAIN / HEIGHT MULTIPLIER (Mz,cat)1 & 2
5
2.5 3 & 4
0.95 0.88 0.80 10 1.00 0.95 0.89
NOTES:
Table 6.4
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
19/36
Cyclonic Area Design Manual 19
8. ToPSPAn Capacty tablsToPSPAn 40 Capacty tabl
Capacities for softwood Capacities for hardwood Capacities for softwood and hardwood
Table 8.1 TOPSPAN 40 - Continuous Span - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS4075 1.0mm 1.2mm 1.5mm 1.9 mm 1.0mm 1.2mm 1.5mm 1.9 mm600 7.98 5.51 7.19 8.99 11.93 7.75 10.41 13.09 15.69900 4.72 3.68 4.79 5.99 7.95 5.16 6.94 8.73 10.461200 2.41 2.76 3.59 4.49 5.96 3.87 5.21 6.54 7.84
1500 1.83 2.21 2.88 3.60 4.77 3.10 4.16 5.24 6.271800 1.25 1.84 2.40 3.00 3.98 2.58 3.47 4.36 5.23
2000 0.87 1.65 2.16 2.70 3.58 2.32 3.12 3.93 4.71
Notes: 1) Support members: 1.0mm BMT: G550; 1.2mm BMT: G500; 1.5 & 1.9mm BMT: G450
2) Outward capacity is limited by the minimum value between member strength and screw capacity.
3) Interpolation of capacity values in the table is permitted.
4) Laps are 40mm long. Refer Figure 11.5 and 11.6 in this manual.5) Design capacity tables can be used to design TOPSPAN with timber supports:
2 fastener connections with M5.5-11x40 BattenZips - 1.5mm BMT steel support is equivalent to softwood timber,1.9mm BMT steel support is equivalent to hardwood timber.4 fastener connections with M5.5-11x40 BattenZips - 1.9mm BMT steel support is equivalent to both hardwood and
softwood timber supports.
117
32
96
102.5
36.5
61
169
40
120
75
32
40
Top
flange
Bottomflange
ToPSPAn 40 ToPSPAn 61 ToPSPAn 96 ToPSPAn 120
0.55mm BMT 0.75mm BMT 0.75mm BMT 0.90mm BMT
0.75mm BMT 1.00mm BMT 1.00mm BMT 1.00mm BMT
1.20mm BMT 1.20mm BMT
7. ToPSPAn pfls
Fu 7.1TOPSPAN sctions
Table 2.1: Key to product codesTS4055 = TOPSPAN 40, 0.55mm BMTTS4075 = TOPSPAN 40, 0.75mm BMT
TS6175 = TOPSPAN 61, 0.75mm BMT
TS6110 = TOPSPAN 61, 1.0mm BMTTS6112 = TOPSPAN 61, 1.2mm BMT
TS9675 = TOPSPAN 96, 0.75mm BMTTS9610 = TOPSPAN 96, 1.0mm BMT
TS9612 = TOPSPAN 96, 1.2mm BMT
TS12090 = TOPSPAN 120, 0.90mm BMTTS12010 = TOPSPAN 120, 1.0mm BMT#
Consult your local LYSAGHT price list for productavailability. # Availability is subject to enquiry.For TS4055, contact your local technical salesrepresentative for cyclonic data.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
20/36
20 Cyclonic Area Design Manual
ToPSPAn 61 Capacty tabls
Capacities for softwood Capacities for hardwood Capacities for softwood and hardwood
Table 8.2 TOPSPAN 61 - 2 Span Lapped - Outward Ultimate Limit State Connection Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS6175 TS6110 TS6112 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm1500 4.45 6.48 1.90 2.48 3.1 4.12 2.67 3.59 4.52 5.41
2000 2.98 3.79 3.85 1.43 1.86 2.33 3.09 2.01 2.69 3.39 4.06
2500 1.87 2.52 2.97 1.14 1.49 1.86 2.47 1.6 2.16 2.71 3.25
3000 1.45 1.95 2.22 0.95 1.24 1.55 2.06 1.34 1.80 2.26 2.71
3500 1.17 1.57 1.62 0.82 1.06 1.33 1.76 1.15 1.54 1.94 2.32
4000 0.88 1.10 1.16 0.71 0.93 1.16 1.54 1.00 1.35 1.69 2.03
4500 1.05 0.63 0.83 1.03 1.37 0.89 1.20 1.51 1.80
5000 0.94 0.57 0.74 0.93 1.23 0.80 1.08 1.36 1.62
5500 0.83 0.52 0.68 0.85 1.12 0.73 0.98 1.23 1.48
6000 0.72 0.48 0.62 0.78 1.03 0.67 0.90 1.13 1.35
Table 8.3 TOPSPAN 61 - 3 Span Lapped - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS6175 TS6110 TS6112 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm1500 4.31 5.88 2.19 2.86 3.57 4.74 3.08 4.14 5.20 6.24
2000 2.68 2.91 3.05 1.64 2.14 2.68 3.56 2.31 3.10 3.90 4.68
2500 1.48 2.17 2.37 1.31 1.71 2.14 2.84 1.85 2.48 3.12 3.74
3000 1.13 1.66 1.79 1.1 1.43 1.79 2.37 1.54 2.07 2.60 3.12
3500 0.94 1.20 1.32 0.94 1.22 1.53 2.03 1.32 1.77 2.23 2.67
4000 0.74 0.94 0.96 0.82 1.07 1.34 1.78 1.15 1.55 1.95 2.34
4500 0.87 0.73 0.95 1.19 1.58 1.03 1.38 1.73 2.08
5000 0.77 0.66 0.86 1.07 1.42 0.92 1.24 1.56 1.87
5500 0.68 0.6 0.78 0.97 1.29 0.84 1.13 1.42 1.70
6000 0.58 0.55 0.71 0.89 1.19 0.77 1.03 1.30 1.56
Table 8.4 TOPSPAN 61 - 2 Span Continuous - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS6175 TS6110 TS6112 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm1500 3.84 5.33 1.94 2.53 3.16 4.20 2.73 3.67 4.61 5.52
2000 2.51 3.37 3.48 1.46 1.90 2.37 3.15 2.05 2.75 3.46 4.14
2500 1.51 1.91 2.41 1.16 1.52 1.90 2.52 1.64 2.20 2.76 3.31
3000 1.17 1.44 1.78 0.97 1.27 1.58 2.10 1.36 1.83 2.30 2.76
3500 0.94 1.14 1.38 0.83 1.08 1.36 1.80 1.17 1.57 1.97 2.37
4000 0.72 0.84 1.11 0.73 0.95 1.19 1.57 1.02 1.37 1.73 2.07
Table 8.5 TOPSPAN 61 - Single Span - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness
2, #15 -15 2, #14-10 4, #15-15 4, #14-10Span (mm) TS6175 TS6110 TS6112 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm1500 2.32 3.26 4.85 6.33 7.91 10.50 6.82 9.16 11.52 13.80
2000 1.73 1.99 2.03 3.64 4.74 5.93 7.87 5.11 6.87 8.64 10.35
2500 1.24 1.38 1.65 2.91 3.80 4.75 6.30 4.09 5.50 6.91 8.28
3000 0.87 1.11 1.31 2.43 3.16 3.95 5.25 3.41 4.58 5.76 6.90
3500 0.60 0.95 1.03 2.08 2.71 3.39 4.50 2.92 3.93 4.94 5.92
4000 0.44 0.78 0.80 1.82 2.37 2.97 3.94 2.56 3.44 4.32 5.18
4500 0.62 1.62 2.11 2.64 3.50 2.27 3.05 3.84 4.60
5000 0.49 1.46 1.90 2.37 3.15 2.05 2.75 3.46 4.14
Notes: 1) Support members: 1.0mm BMT: G550; 1.2mm BMT: G500; 1.5 & 1.9mm BMT: G4502) Outward capacity is limited by the minimum value between member strength and screw capacity.
3) Interpolation of capacity values in the table is permitted.4) Laps 15% of the span. (Refer to Figure 11.6)5) Design capacity tables can be used to design TOPSPAN with timber supports:
2 fastener connections with M5.5-11x40 BattenZips - 1.5mm BMT steel support is equivalent to softwood timber, 1.9mm BMT steel supportis equivalent to hardwood timber.
4 fastener connections with M5.5-11x40 BattenZips - 1.9mm BMT steel support is equivalent to both hardwood and softwood timber supports.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
21/36
Cyclonic Area Design Manual 21
Table 8.5 TOPSPAN 96 - 2 Span Lapped - Outward Ultimate Limit State Connection Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS9675 TS9610 TS9612 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 1.78 3.13 3.77 0.95 1.24 1.55 2.06 1.34 1.80 2.26 2.71
3500 1.47 2.51 3.06 0.82 1.06 1.33 1.76 1.15 1.54 1.94 2.324000 1.19 1.98 2.45 0.71 0.93 1.16 1.54 1.00 1.35 1.69 2.03
4500 0.96 1.53 1.92 0.63 0.83 1.03 1.37 0.89 1.20 1.51 1.80
5000 0.78 1.16 1.49 0.57 0.74 0.93 1.23 0.80 1.08 1.36 1.62
5500 0.68 0.98 1.25 0.52 0.68 0.85 1.12 0.73 0.98 1.23 1.48
6000 0.62 0.88 1.11 0.48 0.62 0.78 1.03 0.67 0.90 1.13 1.35
6500 0.57 0.78 0.97 0.44 0.57 0.72 0.95 0.62 0.83 1.04 1.25
7000 0.51 0.68 0.82 0.41 0.53 0.66 0.88 0.57 0.77 0.97 1.16
7500 0.45 0.58 0.68 0.38 0.50 0.62 0.82 0.53 0.72 0.90 1.08
Table 8.6 TOPSPAN 96 - 3 Span Lapped - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS9675 TS9610 TS9612 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 1.60 2.62 3.22 1.10 1.43 1.79 2.37 1.54 2.07 2.60 3.12
3500 1.32 2.16 2.61 0.94 1.22 1.53 2.03 1.32 1.77 2.23 2.67
4000 1.08 1.75 2.08 0.82 1.07 1.34 1.78 1.15 1.55 1.95 2.34
4500 0.87 1.40 1.63 0.73 0.95 1.19 1.58 1.03 1.38 1.73 2.08
5000 0.70 1.11 1.26 0.66 0.86 1.07 1.42 0.92 1.24 1.56 1.87
5500 0.61 0.88 1.06 0.60 0.78 0.97 1.29 0.84 1.13 1.42 1.70
6000 0.56 0.70 0.95 0.55 0.71 0.89 1.19 0.77 1.03 1.30 1.56
6500 0.50 0.58 0.83 0.51 0.66 0.82 1.09 0.71 0.96 1.20 1.44
7000 0.45 0.52 0.72 0.47 0.61 0.77 1.02 0.66 0.89 1.11 1.34
7500 0.40 0.51 0.60 0.44 0.57 0.71 0.95 0.62 0.83 1.04 1.25
Table 8.7 TOPSPAN 96 - 2 Span Continuous - Outward Ultimate Limit State Capacity (kN/m)
Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS9675 TS9610 TS9612 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 1.62 2.8 3.15 0.97 1.27 1.58 2.1 1.36 1.83 2.3 2.76
3500 1.21 1.98 2.31 0.83 1.08 1.36 1.88 1.17 1.57 1.97 2.37
4000 0.95 1.46 1.77 0.73 0.95 1.19 1.57 1.02 1.37 1.73 2.07
4500 0.76 1.12 1.40 0.65 0.84 1.05 1.40 0.91 1.22 1.54 1.84
Table 8.8 TOPSPAN 96 - Single Span - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS9675 TS9610 TS9612 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 0.96 1.76 1.89 2.43 3.16 3.95 5.25 3.41 4.58 5.76 6.90
3500 0.82 1.40 1.54 2.08 2.71 3.39 4.50 2.92 3.93 4.94 5.92
4000 0.69 1.09 1.23 1.82 2.37 2.97 3.94 2.56 3.44 4.32 5.18
4500 0.58 0.82 0.97 1.62 2.11 2.64 3.50 2.27 3.05 3.84 4.60
5000 0.48 0.61 0.76 1.46 1.90 2.37 3.15 2.05 2.75 3.46 4.14
5500 0.40 0.50 0.65 1.32 1.73 2.16 2.86 1.86 2.50 3.14 3.76
6000 0.34 0.45 0.58 1.21 1.58 1.98 2.62 1.70 2.29 2.88 3.45
6500 0.28 0.39 0.52 1.12 1.46 1.83 2.42 1.57 2.11 2.66 3.19
Notes: 1) Support members: 1.0mm BMT: G550; 1.2mm BMT: G500; 1.5 & 1.9mm BMT: G4502) Outward capacity is limited by the minimum value between member strength and screw capacity.
3) Interpolation of capacity values in the table is permitted.
4) Laps 15% of the span. (Refer to Figures 11.6 & 11.7)5) Design capacity tables can be used to design TOPSPAN with timber supports:
2 fastener connections with M5.5-11x40 BattenZips - 1.5mm BMT steel support is equivalent to softwood timber,
1.9mm BMT steel support is equivalent to hardwood timber.4 fastener connections with M5.5-11x40 BattenZips - 1.9mm BMT steel support is equivalent to both hardwood and
softwood timber supports
Capacities for softwood Capacities for hardwood Capacities for softwood and hardwood
ToPSPAn 96 Capacty tabls
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
22/36
22 Cyclonic Area Design Manual
Capacities for softwood Capacities for hardwood Capacities for softwood and hardwood
Table 8.9 TOPSPAN 120 - 2 Span Lapped - Outward Ultimate Limit State Connection Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS12090 TS12010 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 4.24 5.03 0.95 1.24 1.55 2.06 1.34 1.80 2.26 2.71
3500 3.38 3.97 0.82 1.06 1.33 1.76 1.15 1.54 1.94 2.324000 2.64 3.07 0.71 0.93 1.16 1.54 1.00 1.35 1.69 2.03
4500 2.02 2.31 0.63 0.83 1.03 1.37 0.89 1.20 1.51 1.80
5000 1.52 1.71 0.57 0.74 0.93 1.23 0.80 1.08 1.36 1.62
5500 1.28 1.44 0.52 0.68 0.85 1.12 0.73 0.98 1.23 1.48
6000 1.17 1.31 0.48 0.62 0.78 1.03 0.67 0.90 1.13 1.35
6500 1.05 1.19 0.44 0.57 0.72 0.95 0.62 0.83 1.04 1.25
7000 0.93 1.07 0.41 0.53 0.66 0.88 0.57 0.77 0.97 1.16
7500 0.82 0.95 0.38 0.50 0.62 0.82 0.53 0.72 0.90 1.08
Table 8.10 TOPSPAN 120 - 3 Span Lapped - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS12090 TS12010 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 4.09 4.32 1.10 1.43 1.79 2.37 1.54 2.07 2.60 3.12
3500 3.27 3.47 0.94 1.22 1.53 2.03 1.32 1.77 2.23 2.67
4000 2.57 2.73 0.82 1.07 1.34 1.78 1.15 1.55 1.95 2.34
4500 1.97 2.11 0.73 0.95 1.19 1.58 1.03 1.38 1.73 2.08
5000 1.49 1.61 0.66 0.86 1.07 1.42 0.92 1.24 1.56 1.87
5500 1.24 1.36 0.60 0.78 0.97 1.29 0.84 1.13 1.42 1.70
6000 1.11 1.23 0.55 0.71 0.89 1.19 0.77 1.03 1.30 1.56
6500 0.98 1.09 0.51 0.66 0.82 1.09 0.71 0.96 1.20 1.44
7000 0.85 0.96 0.47 0.61 0.77 1.02 0.66 0.89 1.11 1.34
7500 0.71 0.83 0.44 0.57 0.71 0.95 0.62 0.83 1.04 1.25
Table 8.11 TOPSPAN 120 - 2 Span Continuous - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS12090 TS12010 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 3.91 4.75 0.97 1.27 1.58 2.10 1.36 1.83 2.30 2.76
3500 2.73 3.37 0.83 1.08 1.36 1.80 1.17 1.57 1.97 2.37
4000 2.00 2.51 0.73 0.95 1.19 1.57 1.02 1.37 1.73 2.07
4500 1.52 1.93 0.65 0.84 1.05 1.40 0.91 1.22 1.54 1.84
5000 1.19 1.53 0.58 0.76 0.95 1.26 0.82 1.10 1.38 1.66
Table 8.12 TOPSPAN 120 - Single Span - Outward Ultimate Limit State Capacity (kN/m)Member Strength 2 Screw Connection Capacity (kN/m) 4 Screw Connection Capacity (kN/m)
(kN/m) Support Thickness Support Thickness2, #15 -15 2, #14-10 4, #15-15 4, #14-10
Span (mm) TS12090 TS12010 1.0mm 1.2mm 1.5mm 1.9mm 1.0mm 1.2mm 1.5mm 1.9 mm3000 2.44 2.91 2.43 3.16 3.95 5.25 3.41 4.58 5.76 6.903500 1.93 2.30 2.08 2.71 3.39 4.50 2.92 3.93 4.94 5.92
4000 1.50 1.78 1.82 2.37 2.97 3.94 2.56 3.44 4.32 5.18
4500 1.14 1.35 1.62 2.11 2.64 3.50 2.27 3.05 3.84 4.60
5000 0.85 1.00 1.46 1.90 2.37 3.15 2.05 2.75 3.46 4.14
5500 0.72 0.85 1.32 1.73 2.16 2.86 1.86 2.50 3.14 3.76
6000 0.66 0.78 1.21 1.58 1.98 2.62 1.70 2.29 2.88 3.45
6500 0.60 0.71 1.12 1.46 1.83 2.42 1.57 2.11 2.66 3.19
7000 0.55 0.64 1.04 1.36 1.69 2.25 1.46 1.96 2.47 2.96
7500 0.49 0.57 0.97 1.27 1.58 2.10 1.36 1.83 2.30 2.76
Notes: 1) Support members: 1.0mm BMT: G550; 1.2mm BMT: G500; 1.5 & 1.9mm BMT: G4502) Outward capacity is limited by the minimum value between member strength and screw capacity.3) Interpolation of capacity values in the table is permitted.4) Laps 15% of the span. (Refer to Figures 11.6 & 11.7)
5) Design capacity tables can be used to design TOPSPAN with timber supports:2 fastener connections with M5.5-11x40 BattenZips - 1.5mm BMT steel support is equivalent to softwood timber, 1.9mm BMT steel supportis equivalent to hardwood timber.
4 fastener connections with M5.5-11x40 BattenZips - 1.9mm BMT steel support is equivalent to both hardwood and softwood timber supports.
ToPSPAn 120 Capacty tabls
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
23/36
Cyclonic Area Design Manual 23
0.55 83 0.66 0.039 0.020 31.84 0.969 15.7521.87 8.37 3.418 80.43
X0
TS4055
0.75 113 0.91 0.054 0.028 1.475
1.082
31.84 1.322 15.7221.84 21.23 4.661 80.43TS4075
Radius of
Gyration
Shear
centre
to centroid
distance
10
3
10
3
rx
ry
Product
9. ToPSPAn sct ppts
Tabl 9.1 ToPSPAn 40 Sct Ppts
Centroid
Shear centre
40
120
26
169
X
X
X
X X
YYY Y
11714
32
Xo
Shear centre
Centroid
96
36.5
YY
X
X
X
Centroid
102.5
61
14
Shear centre
32
YY
X
X
X
Centroid
75
40
12
Shear centre
All dimnsions
ar in mm.
Fu 9.3 ToPSPAn 96
Fu 9.1 ToPSPAn 40 Fu 9.2 ToPSPAn 61
Fu 9.4 ToPSPAn 120
Shear centre
to centroid
distance
X
9
9
9TS6112 1.20 234 0.1881.87 0.119 46.49
46.49
46.49
3.698 3.951 28.32 22.58 112.70 21.500
Product
Tabl 9.2 ToPSPAn 61 Sct Ppts
0.75 207 1.68 0.205 0.242 3.53371.76 4.922 38.91 55.08 160.6
1.00 277 2.22 0.273 0.323 4.71171.76 6.563 92.22 73.44 160.6
1.20 322 2.65 0.328 0.388 5.65371.76 7.875
31.43 34.19
34.19
34.73
31.43
31.93 159.4 88.12 160.6
X0
TS9610
TS9612
Radius of
Gyration
Shear
centre
to centroid
distance
103103r
xr
y
Product
Tabl 9.3 ToPSPAn 96 Sct Ppts
X
Shear
centre
to centroiddistance
80.87
80.871.00 369 2.93 0.694 0.701 8.25 10.92 43.6 43.3 123.2 457.0 187.2
Product
Tabl 9.4 ToPSPAn 120 Sct Ppts
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
24/36
24 Cyclonic Area Design Manual
Matal spccats - Cladd (xcpt kL-406Hw adCustm Blu ob)
ZINCALUMealuminium/zinc alloy-coatd stlcomplying with AS 1397:2011 G550, AZ150 (550MPaminimum yild strss,150g/m2 minimum coating mass);
or Stainlss stl standard grad dsignation is
AISI/ASTM Typ 430; UNS No. S43000
Stainlss stl is availabl in a limitd rang of colours,and is availabl subjct to nquiry. Dsign data on stainlssstl matrial is availabl subjct to additional tsting.
Matal spccats - kLiP-Lok 406 HigH winD adCUSToM BLUe orB
ZINCALUMealuminium/zinc alloy-coatd stl complyingwith AS-1397:2011 G300, AZ150 (300MPa minimum yild strss,
150g/m
2
minimum coating mass)
Matal spcfcats - ToPSPAn
TOPSPAN prols ar mad from high tnsil ZINCALUMe stl
(aluminium/zinc alloy coatd) complying with AS1397:2011 with
AZ150 (150 g/m2 minimum coating mass).
ToPSPAn 40
0.55mm BMT Yild Strngth (MPa) 550
0.75mm BMT Yild Strngth (MPa) 550
ToPSPAn 61
0.75mm BMT Yild Strngth (MPa) 550
1.00mm BMT Yild Strngth (MPa) 550
1.20mm BMT Yild Strngth (MPa) 500
ToPSPAn 96
0.75mm BMT Yild Strngth (MPa) 550
1.00mm BMT Yild Strngth (MPa) 550
1.20mm BMT Yild Strngth (MPa) 500
ToPSPAn 120
0.90mm BMT Yild Strngth (MPa) 550
1.00mm BMT Yild Strngth (MPa) 550
10. Matal spcfcatsCUSToM orB
0.42mm BMT Yild Strngth (MPa) 550
0.48mm BMT Yild Strngth (MPa) 550
CUSToM BLUe orB
0.60mm BMT Yild Strngth (MPa) 300
FLATDek ii
0.42mm BMT Yild Strngth (MPa) 550
kLiP-Lok 406 HigH winD
0.55mm BMT Yild Strngth (MPa) 300
0.70mm BMT Yild Strngth (MPa) 300
kLiP-Lok 700 Hi STrengTH
0.42mm BMT Yild Strngth (MPa) 550
0.48mm BMT Yild Strngth (MPa) 550
kLiP-Lok CLASSiC 700
0.42mm BMT Yild Strngth (MPa) 550
0.48mm BMT Yild Strngth (MPa) 550
SPAnDek
0.42mm BMT Yild Strngth (MPa) 550
0.48mm BMT Yild Strngth (MPa) 550
TriMDek
0.42mm BMT Yild Strngth (MPa) 550
0.48mm BMT Yild Strngth (MPa) 550
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
25/36
Cyclonic Area Design Manual 25
Fu 11.3Fastnr location
Fu 11.1Two scrw connction
25
25
MINDIS
T.FROM
EACHE
DGE-2
SCREW
S
EACH
SIDEO
FTOPSP
AN
LAP=1
5%OF
SPAN
10
10
MINDIS
T.FROM
EDGE
-1SCR
EW
EACHS
IDEOF
TOPSP
AN
10
=
=
=
=
=
=
For connectionto supports, see
Figures 11.1 and 11.2.
11. rcmmdd ast lcats ad lap dtals
Fu 11.4end support
Fu 11.9Typical structural lap TOPSPAN 96/120
Fu 11.5Typical non-structural lap for TOPSPAN 40
Fu 11.2Four scrw connction
25mm
4 fastenersat lap eachside
15mm TOPSPAN 120
25mm TOPSPAN 96
For connection to supports,see Figure 11.1, 11.2, 11.6 & 11.7
Lapis15%ofs
pan
Fu11.6Two scrw connction (timbr)
Fu11.7Four scrw connction
(timbr)
Fu11.8Typical structural lap for TOPSPAN 61
Support
Fastnr location-scrws must b locatd in th
mid-rgion of th at portion of both angs
40mmminimum lap
Lap must be
supported onrafter or truss
==
20mm
max.
TOPSPAN
(side view)
TOPSPAN
(side view)
Typical steel support
1.0mm BMT minimumOne screw each
bottom flange
Two screws each
bottom flange
Typical steel support1.0mm BMT minimum
20mmmax.
15mmmax.
50mm min.
End fastener
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
26/36
26 Cyclonic Area Design Manual
12. Fast slct
Tabl 12.1: Fast Slct - Cladd t suppts
ProfileFIXING TO STEEL FIXING TO STEEL FIXING TO STEEL
FIXING TO TIMBER FIXING TO TIMBERSingle & Lapped (Total 2.0mm) Single Lapped (Total 3.8mm)
Hardwood J1-J3 Softwood J40.75 up to 1.0mm BMT 1.0mm up to 3.0mm BMT 1.0mm up to 1.9mm BMT
CUSTOM ORB #15-15x47 HH, #14-10x42 HH #14-10x42 HH #12-11x50 T17 HG/TG HH M6-11x50 ROOFZIPS
CUSTOM BLUE ORB
M6.5-12x55 CyclonicZIPS #14-10x50 T17 HH
#15-15x47 HH,#14-10x42 HH #14-10x42 HH #12-11x50 T17 HG/TG HH
M6-11x50 ROOFZIPSM6.5-12x55 CyclonicZIPS #14-10x50 T17 HH
TRIMDEK
#15-15x55 HH,#14-10x50 HH #14-10x50 HH #12-11x65 T17 HG/TG HH
M6-11x65 ROOFZIPSSPANDEK
FLATDEK II
M6.5-12x55 CyclonicZIPS #14-10x65 T17 HH
#15-15x55 HH,#14-10x50 HH #14-10x50 HH #12-11x65 T17 HG/TG HH
M6-11x65 ROOFZIPS
M6.5-12x55 CyclonicZIPS #14-10x65 T17 HH
KLIP-LOK 700HS
KLIP-LOK 406HW
#12-14x20 HH #12-14x20 HH #12-14x20 HH#12-11x45 T17 HH #12-11x45 T17 HH
M5.5-11x40 BATTENZIPS M5.5-11x40 BATTENZIPS
CUSTOM ORB
#15-15x25 HH #14-10x25 HH #14-10x25 HH #12-11x25 T17 HH #14-10x39 T17 HH
#15-15x25 HH #14-10x25 HH #14-10x25 HH #12-11x25 T17 HH #14-10x39 T17 HH
#12-11x45 T17 HH orM5.5-11x40 BATTENZIPS
with 14g 25mm x 1.2mm
EPDM Seal bondedaluminium washer
#12-11x45 T17 HH orM5.5-11x40 BATTENZIPS
with 14g 25mm x 1.2mm
EPDM Seal bondedaluminium washer
#15-15x25 HH #14-10x25 HH #14-10x25 HH #12-11x25 T17 HH #14-10x39 T17 HH
#15-15x25 HH #14-10x25 HH #14-10x25 HH #12-11x25 T17 HH #14-10x39 T17 HH
CUSTOM BLUE ORB
TRIMDEK
SPANDEK
Valleyfixed
onwall
Clipfixed
onroof
Panfixed
onroof
Crestfixed
onroof
#14-10x65 HH #14-10x65 HH #12-11x75 T17 HH #14-10x75 T17 HH
KLIP-LOK CLASSIC700
#14-10x65 HH #14-10x65 HH #12-11x75 T17 HH #14-10x75 T17 HH
M5.5-14x25 AutoTek or
M5.5-14x35 AutoTek
with 14g 25mm x 1.2mm
EPDM Seal bondedaluminium washer
M5.5-14x25 AutoTek or
M5.5-14x35 AutoTek
with 14g 25mm x 1.2mm
EPDM Seal bondedaluminium washer
M5.5-14x25 AutoTek or
M5.5-14x35 AutoTek
with 14g 25mm x 1.2mm
EPDM Seal bondedaluminium washer
nts:1) HH = Hx Had, HG = HIGH GRIP, TG = TOP GRIP, T17 = TYPe 17 TIMBeR SCReW2) All fastnrs to stl supports ar to b slf drilling slf tapping scrws.
3) All fastnrs to timbr supports ar to b slf drilling scrws.
4) All fastnrs xposd dirctly to th wathr should b ttd with saling washrs.
5) For cyclonic washr rquirmnts, s Slction Tabls and Cladding Capacity Tabls.
6) Sid lap scrws (as spcid in th product brochurs) should always b locatd ovr supports as a minimum, with additional sid lap
scrws positiond as spcid in Sction 14 of this manual.7) No pr-bord hols prmittd.
8) For strngth groups of timbr, rfr to AS1720.2.9) Incras scrw lngth if xing ovr insulation to maintain minimum 3 scrw thrats protruding
far sid of support.
10) For FLATDeK 2, th 25mm Tk is usd to x to stl bams whr th shting is at against th bam g a purlin. Th 35mm Tk is usd
to x to stl whr th shting is at a slop against th bam, usually a rail in a pitchd structur. This lngth is satisfactory for pitchdroof with a slop up to 23 (dgrs). Th Tk lngth should b chckd whr th roof slop is highr than 23 (dgrs).
ToPSPAn ast slct
Cladd ast slct
Stl suppts:
1.0mm thick No.15-15 x 25mm hx.had slf-drilling scrws
1.0mm-1.9mm No.14-10 x 25mm hx.had slf-drilling scrws
Tmb Suppts:M5.5-11x40mm BattnZips
Stuctual laps:
No.14-10 x 25mm hx.had slf-drilling scrws
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
27/36
Cyclonic Area Design Manual 27
13. Fast t suppts
spandek
trimdek
customorb & customblueorb
Valley: 5 fasteners per sheet
Crest: 5 fasteners per sheet
l
S
Crest fixing for roof or walls
Valley fixing for walls only
S = Sid lap
S
Crest: 4 fasteners per sheet
Valley: 4 fasteners per sheet
Crest fixing for roof or walls
Valley fixing for walls only
SValley: 4 fasteners per sheet
S = Sid lap
S = Sid lap
Crest fixing for roofs or walls
Valley fixing for walls only
Cyclonic washer Class 4 G30038 x 35 x 1.0mm Buildex or equiv.
Crest fixing with
cyclonic washerat lap
Crest fixing with
cyclonic washer
Cyclonic washer Class 4 G300
38 x 34.5 x 1.0mm Buildex or equiv.
Crest fixing with
cyclonic washer
at lap
Crest fixing with
cyclonic washer
Crest fixing with
cyclonic washerat lap
Crest fixing with
cyclonic washer
Cyclonic washer Class 4 G300
38 x 35 x 1.0mm Buildex or equiv.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
28/36
28 Cyclonic Area Design Manual
Fu 13.1 Fast t Suppts: Cyclc Aas
UNDERLAP END OVERLAP END
CREST FIXING WITHCYCLONIC WASHER AT LAP
CREST FIXING CREST FIXING WITHCYCLONIC WASHER
CYCLONIC WASHERCLASS-4 G300
25 X 33 X 1.0mm'BUILDEX'.
(FINAL POSITION)
UNDERLAP ENDOVERLAP END
CREST FIXING WITHCYCLONIC WASHER AT LAP
CREST FIXING CREST FIXING WITHCYCLONIC WASHER
CYCLONIC WASHERCLASS-4 G300
25 X 33 X 1.0mm'BUILDEX'.
(FINAL POSITION)
klip-lok 406 HiGH Wind
klip-lok classic 700
FLATDek ii
Supports: 6 fasteners per sheet
25mm max.25mm max.
Centre of pan
Typcal FLATDek ll cct: A longr Tk would busd on th rail of a pitchd structur.
FIRMLOK beam
RAFTER
13. Fast t suppts (ct.)
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
29/36
Cyclonic Area Design Manual 29
14. impact lad by d-b dbs
Th abov photographs ar copyright Jams Cook Univrsity - Cyclon Tsting Station.
All rights rsrvd. Rprintd by prmission.
Parts of a building nvlop (cladding, doors, windows) may
b rquird to rsist windborn dbris according to AS/NZS
1170.2:2011 and Dsign Guidlins for Qunsland Public
Cyclon Shltrs: Impact tst rgims for vrtical trajctoris
(2006).
Tsting has shown th following roof shting matrials arcapabl of rsisting th Qunsland Public Cyclon Shltr
vrtical trajctory dbris load and ar dmd-to-comply
for roofs slops of 15 dgrs or attr, which ar subjct to
ngativ wind prssurs (suction).
Ths Standards spcify dbris impact loading by timbr
mmbr of 4kg mass with nominal cross-sction of 100 mm x
50 mm and sphrical stl balls 8 mm diamtr (approximatly
3 grams mass).
Spandk has bn tstd for maximum spds:
- Timbr mmbrs = 8.5 m/sc
- Sphrical balls = 25.5 m/scCorrugatd prol:
- Timbr mmbrs = 25.5 m/sc
- Sphrical balls = 34.0 m/sc
CUSTOM ORB complis with rquirmnts for corrugatd
prols according to AS 1445:1986.
Rfr furthr to Qunsland Govrnmnt wbsit
http://www.works.qld.gov.au/tdd/saf_build/cyclon-
matrials.asp#roof
CUSTOM ORB and SPANDeK 0.48BMT ar dmd to satisfy
th vrtical trajctory impact load prformanc rquirmnts
dtaild in th Dsign Guidlins for Qunsland Public
Cyclon Shltrs, Spt. 2006.
Although not spcically tstd, BluScop Lysaght
nginrs bliv LYSAGHT TRIMDeK and som othr prols
will prform in a similar way. For mor information, contact
Stl Dirct.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
30/36
30 Cyclonic Area Design Manual
Ld:FS = Full Shld
PS = Patal Shld
nS = n Shld
n/A = nt applcabl, s t 2.
nts:
1. Abov tabl is an xcrpt from Tabl 2.2 of AS 4055: 2006. C1, C2, C3 and C4 ar th dsign wind spd classications. WhrN/A appars, conditions ar byond th scop of AS 4055: 2006.
2. For topographic classication s Appndix 2, also xcrptd from AS 4055: 2006.
Appdx 1: wd classfcat
noigeRniarreT
yrogetaC
noitacifissalCcihpargopoT
1T 2T 3T 4T 5T
C
3CT
5.2CT
2CT,1CT
D
3CT
5.2CT
2CT,1CT
C1 C1 C2 C2 C2 C3 C2 C3 C3 C3 C3 C3 C3 C4 C4
C1 C2 C2 C2 C3 C3 C3 C3 C3 C3 C4 C4 C4 C4 NA
C2 C2 C2 C2 C3 C3 C3 C4 C4 C3 C4 C4 C4 NA NA
C2 C3 C3 C3 C4 C4 C3 C4 C4 C4 NA NA NA NA NA
C2 C3 C3 C3 C4 C4 C4 C4 NA NA C4 NA NA NA NA
C3 C3 C4 C4 NA NA C4 NA NA NA NA NA NA NA NA
FS PS NS FS PS NS FS PS NS FS PS NS FS PS NS
wd Classfcat Systm Cyclc Cdts
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
31/36
Cyclonic Area Design Manual 31
Appdx 2: Tpaphc classfcat
nts:
1. An scarpmnt has on avrag slop lss than 1 in 20 and anothr avrag slop gratr than 1 in 10.
2. Th location of a sit on a hill, ridg or scarpmnt is shown in th illustration abov.
3. Th avrag slop (a) is th slop masurd by avraging th stpst slop and th last slop through th top half of th
hill, ridg or scarpmnt.
Th avrag slop will not oftn occur at th actual proposd building sit and should b appraisd by considring th adjacnt
topography (s appndix D for th calculation of topography - Rfr to AS 4055).4. Th top-third zon xtnds for an qual distanc, d, ithr sid of th crst of an scarpmnt as shown abov.
Th distanc d is th avrag horizontal distanc masurd from th crst of th scarpmnt to th nar top-third zon.
5. Th ovr-top zon of an scarpmnt is considrd to xtnd to a distanc of 5H past th crst of an scarpmnt.
6. Th bottom of a hill, ridg or scarpmnt is that ara at th bas of a hill, ridg or scarpmnt whr th avrag slop is lss
than 1 in 20, .g. crk, rivr vally or at ara.
7. Abov data is an xcrpt from AS 4055: 2006.
d dd d
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
32/36
32 Cyclonic Area Design Manual
Appdx 3:Tpcal cycls ad d cs bulds
Tpcal cycls
Tropical cyclons ar warm cord wind systms whichaffct th coastal rgions of Northrn Australia. Thy ar
formd ovr warm tropical watrs, whr th tmpratur
must b >27C whn svr baromtric dprssions occur.
High spd winds blow spirally inward from all sids to form
a roughly circular cor or y which can rang in siz up to
about 50km in diamtr. Ovrall, a cyclonic wind systm can
hav a diamtr as larg as 650km.
Th spiralling action is causd by th arths rotation and is
clockwis in th southrn hmisphr, anti-clockwis in th
northrn hmishpr.
Air drawn into th y of a cyclon is carrid vrtically by
convction and a pumping action gnratd by high altitudwinds. This cor activity xtnds up to 12km abov th
sa. Th air rising in th cor of th cyclon carris with
it substantial amounts of watr vapour which condnss
to form havy cloud and rain in th ara of maximum wind
forc around th cor.
Th condnsing watr vapour rlass vast amounts of
hat nrgy which is xpndd nlarging th systm. As
cyclons xtract thir nrgy from th warm watr, thy
dissipat fairly quickly on raching land, but oftn not
bfor doing trmndous damag.
Cyclons usually mov at spds of btwn 2 and 15
m/sc and bcaus of thir siz, high wind spds can lastfor many hours. Ths winds ar of a cyclic natur, causing
signicant dynamic forcs on building componnts.
Ths cyclic forcs can induc fatigu in roong matrials,
thir supports and xings; fatigu which oftn limits th
prformanc of a componnt or systm. In addition,
bcaus of th rotation of th wind systm, th wind
dirction at a particular point can chang 180 as th
cyclon passs. Ths qus that buld dss shuldt ta shld t accut ulss t s uhly qual all sds.
wd Fcs Bulds
Wind crats a numbr of forcs on both intrnal andxtrnal surfacs of a building; forcs which must b
considrd whn dsigning or slcting cladding matrials,
thir fastnrs and supports. Ths forcs produc both
positiv prssur and ngativ prssur (suction) and
thir magnitud is affctd by th vlocity of th wind and
th buildings dgr of xposur and conguration. Th
rsultant prssurs ar calculatd using AS/NZS 1170.2:
2002 Structural Dsign Actions Part 2: Wind Actions.
In cyclonic aras, particular not should b takn of th
ffcts of intrnal prssurs on roof and wall cladding and
th importanc of local prssur aras.
Flying dbris is a signicant problm in tropical cyclonsand thr ar numrous instancs of buildings apparing to
stand up to th wind forcs until dbris brok windows or
pntratd wall cladding, thus allowing prssur from th
wind to build up insid. Th intrnal prssur, acting with
suction on th outsid of th roof, was thn sufcint to
caus failur of th roof systm - a sort of xplosion.
Failur of th roong can b du to inadquat fastning
of roof shting, in which cas th xings pull out or th
shting cracks around th fastnrs. It can b qually
du to inadquat xing of th roof framing, ithr th
connction btwn th battns and raftrs or th
connction of th raftrs to th building fram.Irrspctiv of th rason for th loss of roof, th rsult
is usually catastrophic. Watr damag commonly rsults
in th dstruction of furnitur and furnishings. In addition,
framd buildings los th bracing ffct caus by th roof
mmbran, rsulting in th collaps of som xtrnal walls.
wd Fcs As
Th Wind Classication for awnings and carports can b
takn from AS4055 Wind Loads on housing.
Th wind prssur multiplirs to apply to th basic wind
prssur should com from th cofcints in ASNZS
1170:2002 for frstanding and attachd awnings.
Ds wd Spds
Th various conditions which affct th dsign wind
spds, such as gographic location, trrain catgory, tc.,
ar to b takn from th ASNZS 1170.2:2002.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
33/36
Cyclonic Area Design Manual 33
Appdx 4: Lcal pssu aas
Lcal pssu aasWhr xtrnal prssurs ar ngativ, buildings ar
subjct to localisd aras of incrasd prssur at all
signicant xtrnal discontinuitis such as roof or wall
dgs including roof ridgs whr th roof pitch xcds
10. Consquntly, all roof and wall claddings, thir supports
and xings, must b dsignd to tak into account ths
incrasd xtrnal prssurs. Th aras affctd by ths
factors ar shown in th illustration abov (takn from th
AS/NZS 1170.2: 2002). Th xtnt of th local prssur aras
is givn by th dimnsion a, which should b dtrmind
as indicatd in th illustrations abov (also takn from
AS/NZS 1170.2: 2002).
Du car must b takn by th nginr whn dsigning
claddings and thir supports. Th ffct on both aras of
incrasd prssur must b considrd.
nts:
1. Abov illustration is takn from AS/NZS 1170.2:2002.
a x a subjct to local prssur factor of 1.5.
Such aras li within a zon of width a from dgs.
2. Ara 0.5 a x 0.5 a subjct to a local prssur factor of 2.0.
Such aras li within a zon of width 0.5 a from dgs.
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
34/36
34 Cyclonic Area Design Manual
notes:
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
35/36
Cyclonic Area Design Manual 35
7/27/2019 LysaghtCyclonicAreaDesignManualWA3September2012 (1).pdf
36/36
Dsclam, aats ad lmtat labltyThis publication is intndd to b an aid for all trads and profssionals involvdwith spcifying and installing LYSAGHT products and not to b a substitut forprofssional judgmnt.
Trms and conditions of sal availabl at local BluScop Lysaght sals offics.
excpt to th xtnt to which liability may not lawfully b xcludd or limitd,BluScop Stl Limitd will not b undr or incur any liability to you for anydirct or indirct loss or damag (including, without limitation, consquntialloss or damag such as loss of profit or anticipatd profit, loss of us, damag
to goodwill and loss du to dlay) howvr causd (including, without limitation,brach of contract, nglignc and/or brach of statut), which you may suffr
or incur in connction with this publication.
Copyright BluScop Stl Limitd Sptmbr 3, 2012
Tchcal qus: [email protected] call 1800 641 417