MECHANICAL GENERAL NOTES BE APPLICABLE TO THIS PROJECT. ALL SYMBOLS SHOWN ABOVE MAY NOT SECTION DESIGNATION EXISTING WORK TO BE WORK TO REMAIN AND POINT BETWEEN EXISTING EQUIPMENT DESIGNATION EQUIPMENT NUMBER EQUIPMENT DESIGNATION SECTION LETTER/NUMBER AND EXISTING WORK BETWEEN NEW WORK POINT OF CONNECTION DESIGNATIONS REMOVED DETAIL DESIGNATION CONTAINING DETAIL DRAWING NUMBER DETAIL LETTER/NUMBER DRAWING SECTION SHOWN NOTE: ABBREVIATIONS DESCRIPTION GLOBE VALVE DIRECTION OF PITCH GATE VALVE CHECK VALVE BUTTERFLY VALVE BALL VALVE PLUG VALVE CONCENTRIC REDUCER OR INCREASER ECCENTRIC REDUCER OR INCREASER CIRCUIT BALANCING VALVE DIRECTION OF FLOW SOLENOID VALVE AUTOMATIC CONTROL VALVE (3-WAY) AUTOMATIC CONTROL VALVE (2-WAY) PIPE RISING UP STRAINER PIPE DROPPING DOWN UNION - SCREWED OR FLANGED THERMOMETER WELL/PRESSURE GAGE (EXTEND DISCH. TO DRAIN) AUTOMATIC AIR VENT MANUAL AIR VENT DRAIN SYMBOL MAV AAV VALVES AND FITTINGS OUTSIDE STEM & YOKE VALVE STEAM TRAP PRESSURE REDUCING VALVE LOW PRESSURE STEAM LPS PIPING LEGEND PUMPED CONDENSATE CONDENSATE DRAIN REFRIGERANT HOT GAS REFRIGERANT SUCTION REFRIGERANT VENT (RELIEF) VENT REFRIGERANT LIQUID PC D V HG RV RS RL COLD WATER (DOMESTIC) CW SPRINKLER SP NATURAL GAS G CONDENSER WATER RETURN CDWR CONDENSER WATER SUPPLY CDWS HOT WATER RETURN (HEATING) HWR HOT WATER SUPPLY (HEATING) HWS CHILLED WATER RETURN CHWR CHILLED WATER SUPPLY CHWS HEAT PUMP WATER RETURN HPWR HEAT PUMP WATER SUPPLY HPWS DUCTWORK LEGEND H SIDEWALL/DUCT MOUNTED RETURN/EXHAUST REGISTER SIDEWALL/DUCT MOUNTED SUPPLY REGISTER H HYDROGEN SENSOR NO AIRFLOW) (SHADED AREA INDICATES T HUMIDITY SENSOR/HUMIDISTAT TEMPERATURE SENSOR/THERMOSTAT RETURN AIR GRILLE 3-WAY BLOW DIFFUSER NEW DUCTWORK D R D R EXISTING DUCTWORK TO REMAIN VOLUME DAMPER (VD) SUPPLY DIFFUSER DROP IN DUCT ELEVATION RISE IN DUCT ELEVATION AD AP AD AP DUCT UP DUCT DOWN VANED RECTANGULAR ELBOW RETURN REGISTER/GRILLE ACCESS DOOR (AD)/ACCESS PANEL (AP) 90 DEG. SPLIT (TEE) FLEXIBLE CONNECTION (FC) BRANCH DUCT TAKE-OFF (45 DEG.) TRANSITION M TRANSITION (RECTANG. TO ROUND) EXHAUST FAN (CLG. HUNG TYPE) EXHAUST FAN (ROOF TOP) ELECTRIC MOTOR-OPERATED DAMPER HEATING COIL (ELECTRIC) HEATING COIL (HOT WATER) W/ACCESS DOOR EXHAUST FAN (IN-LINE TYPE) (RECTANGULAR) FLEXIBLE DUCTWORK BDD BDD NON-POWERED BACKDRAFT DAMPER SMOKE DAMPER FIRE DAMPER COMBO FIRE/SMOKE DAMPER FSD FD SD M EXHAUST AIR GRILLE FSD FD SD ROUND RADIUS ELBOW SINGLE LINE DOUBLE LINE DESCRIPTION 1. THE WORK TO BE DONE UNDER THESE SPECIFICATIONS AND THE DRAWINGS CONSISTS OF FURNISHING ALL EQUIPMENT, MATERIALS, LABOR AND SERVICES, AND PERFORMING ALL OPERATIONS TO COMPLETE THE MECHANICAL CONSTRUCTION WORK FOR THIS PROJECT. 2. THE TERM "FURNISH" SHALL MEAN TO OBTAIN AND SUPPLY TO THE JOB SITE. THE TERM "INSTALL" SHALL MEAN TO FIX IN POSITION AND CONNECT FOR USE. THE TERM "PROVIDE" SHALL MEAN TO FURNISH AND INSTALL. THE TERM "MECHANICAL WORK" OR "WORK" SHALL MEAN ALL LABOR, MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, SUPERVISION, SERVICES AND OTHER INCIDENTALS NECESSARY FOR COMPLETE AND OPERABLE INSTALLATION. 3. ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND APPROVED BY THE ENGINEER OR OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION. 4. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT, GENERAL CHARACTER AND LOCATION OF THE WORK INCLUDED. OFFSETS OR CHANGES IN DUCT SHAPE TO AVOID STRUCTURAL OR OTHER INTERFERENCES, AND WORK INDICATED BUT HAVING MINOR DETAILS OBVIOUSLY OMITTED SHALL BE PROVIDED WITHOUT EXTRA COST. 5. ALL DEVICES SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION AND SHOWN FOR GENERAL WIRING PURPOSES ONLY. ALL DEVICES INDICATED TO BE INSTALLED IN THE SAME LOCATIONS WITH DIFFERENT ELEVATIONS SHALL BE ALIGNED VERTICALLY AND HORIZONTALLY FOR MOUNTING DETAILS OF SWITCHES, OUTLETS, FIRE ALARM STROBES, AUDIBLE & VISUAL DEVICES, FIRE ALARM PULL STATIONS, CLOCKS, SECURITY DEVICES, CARD READERS, THERMOSTATS, SENSORS, ETC.; REFER TO THE ARCHITECTURAL DRAWINGS AND COORDINATE ALL LOCATIONS BETWEEN TRADES. 6. ALL MATERIALS, EQUIPMENT, AND INSTALLATIONS SHALL BE IN STRICT ACCORDANCE WITH THE 2009 MECHANICAL CODE, 2009 ENERGY CONSERVATION CODE, SMACNA, UL, MANUFACTURER'S RECOMMENDATIONS, STATE CODES, LOCAL CODES AND ALL AUTHORITIES HAVING JURISDICTION. 7. ALL DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. 8. ALL NEW DUCTS SHALL HAVE FIRE RATED SLEEVES AND/OR FIRE RATED DAMPERS WHEN PASSING THROUGH FIRE RATED CONSTRUCTION. 9. WALL MOUNTED THERMOSTATS SHALL BE INSTALLED 48" ABOVE THE FLOOR AND HANDICAPPED ACCESSIBLE. 10. INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FEET FROM THE ROOF EDGE OR ANY CHANGE IN ROOF HEIGHT GREATER THAN 2 FEET. 11. PROVIDE 4" THICK CONCRETE PADS FOR EQUIPMENT INSTALLED ON FLOORS OR ON GRADE, 6" LARGER THAN THE EQUIPMENT ON ALL SIDES. 12. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT, MATERIALS, AND LABOR TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM AS INDICATED ON THE DESIGN DOCUMENTS. 13. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES IN FIELD PRIOR TO INSTALLATION OF ANY WORK. REPORT ALL CONFLICTS IMMEDIATELY TO ARCHITECT AND ENGINEER. 14. THE CONTRACTOR SHALL COORDINATE THE ACTUAL LOCATIONS OF ALL EQUIPMENT, CASEWORK, DEVICES, FIXTURES, SWITCHES, SENSORS, ETC., WITH THE ARCHITECTURAL DRAWINGS PRIOR TO PERFORMING ANY ROUGH-IN WORK FOR THE UTILITIES. 15. REMOVE ALL TRASH, DEBRIS, AND DEMOLITION MATERIAL FROM PREMISES AT THE END OF EACH WORK DAY. 16. THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS AT THE SITE AND NOTIFY THE OWNER/ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WITH WORK. 17. THE CONTRACTOR SHALL OBTAIN ALL PERMITS AND APPROVALS PRIOR TO STARTING CONSTRUCTION. EHT ELECTRIC HEAT TRACING ET EXPANSION TANK FD FIRE DAMPER FSD FIRE & SMOKE DAMPER FTR FINNED TUBE RADIATION HC HEATING COIL HTX HEAT EXCHANGER HWP HOT WATER PUMP RF RETURN AIR FAN RHP RADIANT HEATING PANEL SD SMOKE DAMPER SF SUPPLY AIR FAN SRV SAFETY RELIEF VALVE SSAC SPLIT SYSTEM AIR CONDITIONER UH UNIT HEATER UVE ULTRAVIOLET EMITTER VAV VARIABLE AIR VOLUME WMTR WATER METER AAV AUTOMATIC AIR VENT ADS AIR AND DIRT SEPARATOR AHU AIR HANDLING UNIT AS AIR SEPARATOR BDD BACK DRAFT DAMPER BFBP BOILER FEED BOOSTER PUMP BFP-RP BACK FLOW PREVENTER, OF THE REDUCED PRESSURE PRINCIPAL TYPE BLR BOILER CAV CONSTANT AIR VOLUME CC COOLING COIL CDP CONDENSATE DRAIN PUMP CH CHILLER CHWP CHILLED WATER PUMP CU CONDENSING UNIT CUH CABINET UNIT HEATER EF EXHAUST FAN EF-LF EXHAUST FAN - LABORATORY FUME RLF RELIEF AIR FAN GRV GRAVITY ROOF VENTILATOR SSAH SPLIT SYSTEM AIR HANDLER SSHP SPLIT SYSTEM HEAT PUMP HVAC DESIGN CRITERIA ROOM NAME/ NOTES: PROJECT LOCATION AUTHORITY JURISDICTION IMC 2009 MECHANICAL CODE 93°F db / 75°F wb BASED ON ASHRAE 0.4% & 99.6% 10°F WEATHER DATA WINTER DESIGN TEMP. SUMMER DESIGN TEMP. 73 66 75 80 OCC UNOCC OCC UNOCC 60 - SUM. WIN. CLASSIFICATION 1 & 2 1. 1 & 2 1 & 2 73 66 75 80 60 - 73 66 75 80 60 - MIDDLETOWN, PA LABS CLASSROOMS OPEN AREAS/CORRIDORS CFM/PERSON CFM/SQ.FT. 10 10 - 0.18 0.18 0.06 SENSIBLE LATENT 250 250 250 250 250 250 1.2 1.2 1.2 1.5 1.5 1.5 NO NO NO SUMMER 0.60 0.60 0.60 YES YES YES HEATING COOLING 0.8 1.0 0.8 1.0 0.8 1.0 SUPPLY AIR DIFFUSER THROWS SIZED FOR 50 FPM AIR VELOCITY. AVERAGE AIR SPEED VELOCITY IN OCCUPIED ZONE TO BE 20 FPM. 2. CLOTHING CLO VALUES DETERMINED FROM ASHRAE 55-2010. RELATIVE HUMIDITY (% RH) VENTILATION EFFECTIVENESS ACTIVE TEMPERATURE CONTROL CLOTHING INSULATION VALUES (CLO) ACTIVE HUMIDITY CONTROL MISC. W/SQ.FT. LIGHTING W/SQ.FT. PEOPLE HEAT GAIN VENTILATION COOLING SPACE TEMP. (°F) NOTES HEATING SPACE TEMP. (°F) 18. THE CONTRACTOR SHALL PROVIDE ALL FLUIDS SUCH AS GYLCOL AND REFRIGERANT AND FILL ALL REQUIRED SYSTEMS. EG ETHELYNE GLYCOL AUTOMATIC CONTROL VALVE (3-WAY) THERMOMETER PRESSURE GAGE - 70 70 70 70 100 100 CURING ROOM - - - - 1.2 - YES - YES - - PA LABOR & INDUSTRY (MAXIMUM ALLOWABLE) PROVIDE DUCT MATERIAL, GAUGES, REINFORCING AND SEALING FOR OPERATING PRESSURES INDICATED IN CLASSIFICATION SCHEDULE. DUCT SIZES: INSIDE CLEAR DIMENSIONS. FOR LINED DUCTS, MAINTAIN PRESSURE AND VELOCITIES GREATER THAN 2,000 FPM. LOW PRESSURE: THREE PRESSURE CLASSIFICATIONS: 1/2 INCH WG POSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 2,000 FPM, 1 INCH WG POSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 2,500 FPM AND 2 INCH WG POSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 2,500 FPM. MEDIUM PRESSURE: THREE PRESSURE CLASSIFICATION: 3 INCH WG POSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 4,000 FPM, 4 INCH WG POSITIVE STATIC PRESSURE AND VELOCITIES GREATER THAN 2,000 FPM, 6 INCH WG POSITIVE STATIC SIZES INSIDE LINING. 4. 2. 3. 1. CLASSIFICATION MEDIUM PRESSURE: 4 INCH, SEAL CLASS A (PER SMACNA HIGH PRESSURE DUCT CONSTRUCTION STANDARDS) LOW PRESSURE: 2 INCH LOW PRESSURE: 2 INCH LOW PRESSURE: 2 INCH LOW PRESSURE: 2 INCH LOW PRESSURE: 2 INCH DUCTWORK: TERMINAL UNIT TO DUCTWORK: EXHAUST DUCTWORK: RETURN AIR DUCTWORK: OUTSIDE AIR NOTES: AIR OUTLET SYSTEM DUCTWORK: AIR HANDLING UNIT TO VAV BOXES (VAV SYSTEMS) DUCTWORK: AIR HANDLING UNIT TO AIR OUTLET (CONSTANT VOLUME) DUCTWORK PRESSURE CLASSIFICATION AFF ABOVE FINISHED FLOOR WH WALL HEATER WINTER 0.90 0.90 0.90 - 307 Fourth Avenue Suite 1300 Pittsburgh, PA 15222 v: 412.765.3890 f: 412.765.2209 Scale Date BCJ Project Number Seal Revisions © 2012 Bohlin Cywinski Jackson Not For Construction Client Project Number General Notes Office for Planning and Architecture 234 Liberty Street Harrisburg, PA 17101 v: 717-230-9660 f: 717-230-9664 Consultant Office Name or Logo Address 1 Address 2 v: xxx-xxx-xxxx f: xxx-xxx-xxxx 1/8" = 1'-0" 11/19/2012 4:33:36 PM M0.01 Mechanical Legend Notes & Abbreviations NOVEMBER 21, 2012 11209 PENNSYLVANIA STATE UNIVERSITY PSU HARRISBURG - EDUCATIONAL ACTIVITIES BUILDING GMP / 90% CONSTRUCTION DOCUMENTS SET 01-03602.01 777 West Harrisburg Pike Middletown, PA 17057 No. Description Date

M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

MECHANICAL GENERAL NOTES

BE APPLICABLE TO THIS PROJECT.ALL SYMBOLS SHOWN ABOVE MAY NOT

SECTION DESIGNATION

EXISTING WORK TO BEWORK TO REMAIN ANDPOINT BETWEEN EXISTING

EQUIPMENT DESIGNATION

EQUIPMENT NUMBER

EQUIPMENT DESIGNATION

SECTION LETTER/NUMBER

AND EXISTING WORKBETWEEN NEW WORKPOINT OF CONNECTION

DESIGNATIONS

REMOVED

DETAIL DESIGNATION

CONTAINING DETAILDRAWING NUMBER

DETAIL LETTER/NUMBER

DRAWING SECTION SHOWN

NOTE:

ABBREVIATIONSDESCRIPTION

GLOBE VALVE

DIRECTION OF PITCH

GATE VALVE

CHECK VALVE

BUTTERFLY VALVE

BALL VALVE

PLUG VALVE

CONCENTRIC REDUCER OR INCREASER

ECCENTRIC REDUCER OR INCREASER

CIRCUIT BALANCING VALVE

DIRECTION OF FLOW

SOLENOID VALVE

AUTOMATIC CONTROL VALVE (3-WAY)

AUTOMATIC CONTROL VALVE (2-WAY)

PIPE RISING UP

STRAINER

PIPE DROPPING DOWN

UNION - SCREWED OR FLANGED

THERMOMETER WELL/PRESSURE GAGE

(EXTEND DISCH. TO DRAIN)AUTOMATIC AIR VENT

MANUAL AIR VENT

DRAIN

SYMBOL

MAV

AAV

VALVES AND FITTINGS

OUTSIDE STEM & YOKE VALVE

STEAM TRAP

PRESSURE REDUCING VALVE

LOW PRESSURE STEAMLPS

PIPING LEGEND

PUMPED CONDENSATECONDENSATE DRAIN

REFRIGERANT HOT GAS

REFRIGERANT SUCTION

REFRIGERANT VENT (RELIEF)

VENT

REFRIGERANT LIQUID

PCDV

HGRV

RSRL

COLD WATER (DOMESTIC)CWSPRINKLERSPNATURAL GASG

CONDENSER WATER RETURNCDWRCONDENSER WATER SUPPLYCDWSHOT WATER RETURN (HEATING)HWRHOT WATER SUPPLY (HEATING)HWSCHILLED WATER RETURNCHWRCHILLED WATER SUPPLYCHWS

HEAT PUMP WATER RETURNHPWRHEAT PUMP WATER SUPPLYHPWS

DUCTWORK LEGEND

H

SIDEWALL/DUCT MOUNTED RETURN/EXHAUST REGISTER

SIDEWALL/DUCT MOUNTED SUPPLY REGISTER

H HYDROGEN SENSOR

NO AIRFLOW)(SHADED AREA INDICATES

T

HUMIDITY SENSOR/HUMIDISTAT

TEMPERATURE SENSOR/THERMOSTAT

RETURN AIR GRILLE

3-WAY BLOW DIFFUSER

NEW DUCTWORK

D

R

D

R

EXISTING DUCTWORK TO REMAIN

VOLUME DAMPER (VD)

SUPPLY DIFFUSER

DROP IN DUCT ELEVATION

RISE IN DUCT ELEVATION

ADAPADAP

DUCT UP

DUCT DOWN

VANED RECTANGULAR ELBOW

RETURN REGISTER/GRILLE

ACCESS DOOR (AD)/ACCESS PANEL (AP)

90 DEG. SPLIT (TEE)

FLEXIBLE CONNECTION (FC)

BRANCH DUCT TAKE-OFF (45 DEG.)

TRANSITION

M

TRANSITION (RECTANG. TO ROUND)

EXHAUST FAN (CLG. HUNG TYPE)

EXHAUST FAN (ROOF TOP)

ELECTRIC MOTOR-OPERATED DAMPER

HEATING COIL (ELECTRIC)

HEATING COIL (HOT WATER) W/ACCESS DOOR

EXHAUST FAN (IN-LINE TYPE)

(RECTANGULAR)

FLEXIBLE DUCTWORK

BDDBDD

NON-POWERED BACKDRAFT DAMPER

SMOKE DAMPER

FIRE DAMPER

COMBO FIRE/SMOKE DAMPERFSD

FD

SD

M

EXHAUST AIR GRILLE

FSD

FD

SD

ROUND RADIUS ELBOW

SINGLE LINE DOUBLE LINE DESCRIPTION

1. THE WORK TO BE DONE UNDER THESE SPECIFICATIONS AND THE DRAWINGS CONSISTS OFFURNISHING ALL EQUIPMENT, MATERIALS, LABOR AND SERVICES, AND PERFORMING ALLOPERATIONS TO COMPLETE THE MECHANICAL CONSTRUCTION WORK FOR THIS PROJECT.

2. THE TERM "FURNISH" SHALL MEAN TO OBTAIN AND SUPPLY TO THE JOB SITE. THE TERM"INSTALL" SHALL MEAN TO FIX IN POSITION AND CONNECT FOR USE. THE TERM "PROVIDE"SHALL MEAN TO FURNISH AND INSTALL. THE TERM "MECHANICAL WORK" OR "WORK" SHALLMEAN ALL LABOR, MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, SUPERVISION,SERVICES AND OTHER INCIDENTALS NECESSARY FOR COMPLETE AND OPERABLEINSTALLATION.

3. ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND APPROVED BY THE ENGINEEROR OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION.

4. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT, GENERAL CHARACTER ANDLOCATION OF THE WORK INCLUDED. OFFSETS OR CHANGES IN DUCT SHAPE TO AVOIDSTRUCTURAL OR OTHER INTERFERENCES, AND WORK INDICATED BUT HAVING MINOR DETAILSOBVIOUSLY OMITTED SHALL BE PROVIDED WITHOUT EXTRA COST.

5. ALL DEVICES SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION AND SHOWN FORGENERAL WIRING PURPOSES ONLY. ALL DEVICES INDICATED TO BE INSTALLED IN THE SAMELOCATIONS WITH DIFFERENT ELEVATIONS SHALL BE ALIGNED VERTICALLY AND HORIZONTALLYFOR MOUNTING DETAILS OF SWITCHES, OUTLETS, FIRE ALARM STROBES, AUDIBLE & VISUALDEVICES, FIRE ALARM PULL STATIONS, CLOCKS, SECURITY DEVICES, CARD READERS,THERMOSTATS, SENSORS, ETC.; REFER TO THE ARCHITECTURAL DRAWINGS AND COORDINATEALL LOCATIONS BETWEEN TRADES.

6. ALL MATERIALS, EQUIPMENT, AND INSTALLATIONS SHALL BE IN STRICT ACCORDANCE WITH THE2009 MECHANICAL CODE, 2009 ENERGY CONSERVATION CODE, SMACNA, UL, MANUFACTURER'SRECOMMENDATIONS, STATE CODES, LOCAL CODES AND ALL AUTHORITIES HAVINGJURISDICTION.

7. ALL DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS.

8. ALL NEW DUCTS SHALL HAVE FIRE RATED SLEEVES AND/OR FIRE RATED DAMPERS WHENPASSING THROUGH FIRE RATED CONSTRUCTION.

9. WALL MOUNTED THERMOSTATS SHALL BE INSTALLED 48" ABOVE THE FLOOR AND HANDICAPPEDACCESSIBLE.

10. INSTALL ROOFTOP EQUIPMENT NOT LESS THAN 10 FEET FROM THE ROOF EDGE OR ANYCHANGE IN ROOF HEIGHT GREATER THAN 2 FEET.

11. PROVIDE 4" THICK CONCRETE PADS FOR EQUIPMENT INSTALLED ON FLOORS OR ON GRADE, 6"LARGER THAN THE EQUIPMENT ON ALL SIDES.

12. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT, MATERIALS, AND LABOR TOPROVIDE A COMPLETE AND OPERATIONAL SYSTEM AS INDICATED ON THE DESIGN DOCUMENTS.

13. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES IN FIELD PRIOR TOINSTALLATION OF ANY WORK. REPORT ALL CONFLICTS IMMEDIATELY TO ARCHITECT ANDENGINEER.

14. THE CONTRACTOR SHALL COORDINATE THE ACTUAL LOCATIONS OF ALL EQUIPMENT,CASEWORK, DEVICES, FIXTURES, SWITCHES, SENSORS, ETC., WITH THE ARCHITECTURALDRAWINGS PRIOR TO PERFORMING ANY ROUGH-IN WORK FOR THE UTILITIES.

15. REMOVE ALL TRASH, DEBRIS, AND DEMOLITION MATERIAL FROM PREMISES AT THE END OFEACH WORK DAY.

16. THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS AT THE SITE AND NOTIFY THEOWNER/ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WITH WORK.

17. THE CONTRACTOR SHALL OBTAIN ALL PERMITS AND APPROVALS PRIOR TO STARTINGCONSTRUCTION.

EHT ELECTRIC HEAT TRACINGET EXPANSION TANK

FD FIRE DAMPERFSD FIRE & SMOKE DAMPERFTR FINNED TUBE RADIATION

HC HEATING COILHTX HEAT EXCHANGERHWP HOT WATER PUMPRF RETURN AIR FAN

RHP RADIANT HEATING PANELSD SMOKE DAMPERSF SUPPLY AIR FANSRV SAFETY RELIEF VALVESSAC SPLIT SYSTEM AIR CONDITIONER

UH UNIT HEATERUVE ULTRAVIOLET EMITTERVAV VARIABLE AIR VOLUME

WMTR WATER METER

AAV AUTOMATIC AIR VENTADS AIR AND DIRT SEPARATOR

AHU AIR HANDLING UNITAS AIR SEPARATORBDD BACK DRAFT DAMPERBFBP BOILER FEED BOOSTER PUMPBFP-RP BACK FLOW PREVENTER, OF THE REDUCED PRESSURE PRINCIPAL TYPEBLR BOILERCAV CONSTANT AIR VOLUMECC COOLING COILCDP CONDENSATE DRAIN PUMPCH CHILLERCHWP CHILLED WATER PUMPCU CONDENSING UNITCUH CABINET UNIT HEATEREF EXHAUST FANEF-LF EXHAUST FAN - LABORATORY FUME

RLF RELIEF AIR FAN

GRV GRAVITY ROOF VENTILATOR

SSAH SPLIT SYSTEM AIR HANDLERSSHP SPLIT SYSTEM HEAT PUMP

HVAC DESIGN CRITERIA

ROOM NAME/

NOTES:

PROJECT LOCATION

AUTHORITY JURISDICTION

IMC 2009MECHANICAL CODE 93°F db / 75°F wb

BASED ON ASHRAE 0.4% & 99.6%

10°F

WEATHER DATA

WINTER DESIGN TEMP.

SUMMER DESIGN TEMP.

73 66 75 80

OCC UNOCC OCC UNOCC60 -

SUM. WIN.CLASSIFICATION

1 & 2

1.

1 & 2

1 & 2

73 66 75 80 60 -

73 66 75 80 60 -

MIDDLETOWN, PA

LABS

CLASSROOMS

OPEN AREAS/CORRIDORS

CFM/PERSON CFM/SQ.FT.10

10

-

0.18

0.18

0.06

SENSIBLE LATENT250

250

250

250

250

250

1.2

1.2

1.2

1.5

1.5

1.5

NO

NO

NO

SUMMER0.60

0.60

0.60

YES

YES

YES

HEATING COOLING0.8 1.0

0.8 1.00.8 1.0

SUPPLY AIR DIFFUSER THROWS SIZED FOR 50 FPM AIR VELOCITY. AVERAGE AIR SPEED VELOCITY IN OCCUPIED ZONE TO BE 20 FPM.2. CLOTHING CLO VALUES DETERMINED FROM ASHRAE 55-2010.

RELATIVEHUMIDITY

(% RH)

VENTILATIONEFFECTIVENESS

ACTIVETEMPERATURE

CONTROL

CLOTHING INSULATIONVALUES (CLO)

ACTIVEHUMIDITYCONTROL

MISC.W/SQ.FT.

LIGHTINGW/SQ.FT.

PEOPLE HEATGAIN

VENTILATIONCOOLINGSPACE TEMP.

(°F) NOTES

HEATINGSPACE TEMP.

(°F)

EHTELECTRI C HEAT TRACING WM TRWATER M ETER

18. THE CONTRACTOR SHALL PROVIDE ALL FLUIDS SUCH AS GYLCOL AND REFRIGERANTAND FILL ALL REQUIRED SYSTEMS.

EG ETHELYNE GLYCOL

AUTOMATIC CONTROL VALVE (3-WAY)

THERMOMETER

PRESSURE GAGE

-70 70 70 70 100 100CURING ROOM - - - - 1.2 - YES -YES- -

PA LABOR & INDUSTRY

(MAXIMUMALLOWABLE)

PROVIDE DUCT MATERIAL, GAUGES, REINFORCING AND SEALING FOROPERATING PRESSURES INDICATED IN CLASSIFICATION SCHEDULE.

DUCT SIZES: INSIDE CLEAR DIMENSIONS. FOR LINED DUCTS, MAINTAIN

PRESSURE AND VELOCITIES GREATER THAN 2,000 FPM.

LOW PRESSURE: THREE PRESSURE CLASSIFICATIONS: 1/2 INCH WGPOSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESSTHAN 2,000 FPM, 1 INCH WG POSITIVE OR NEGATIVE STATIC PRESSUREAND VELOCITIES LESS THAN 2,500 FPM AND 2 INCH WG POSITIVE ORNEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 2,500 FPM.

MEDIUM PRESSURE: THREE PRESSURE CLASSIFICATION: 3 INCH WGPOSITIVE OR NEGATIVE STATIC PRESSURE AND VELOCITIES LESSTHAN 4,000 FPM, 4 INCH WG POSITIVE STATIC PRESSURE ANDVELOCITIES GREATER THAN 2,000 FPM, 6 INCH WG POSITIVE STATIC

SIZES INSIDE LINING.

4.

2.

3.

1.

CLASSIFICATION

MEDIUM PRESSURE: 4 INCH,SEAL CLASS A (PER SMACNAHIGH PRESSURE DUCTCONSTRUCTION STANDARDS)

LOW PRESSURE: 2 INCH

LOW PRESSURE: 2 INCH

LOW PRESSURE: 2 INCH

LOW PRESSURE: 2 INCH

LOW PRESSURE: 2 INCH

DUCTWORK: TERMINAL UNIT TO

DUCTWORK: EXHAUST

DUCTWORK: RETURN AIR

DUCTWORK: OUTSIDE AIR

NOTES:

AIR OUTLET

SYSTEM

DUCTWORK: AIR HANDLING UNIT TOVAV BOXES (VAV SYSTEMS)

DUCTWORK: AIR HANDLING UNIT TOAIR OUTLET (CONSTANT VOLUME)

DUCTWORK PRESSURE CLASSIFICATION

AFF ABOVE FINISHED FLOOR

WH WALL HEATER

WINTER0.90

0.90

0.90

-

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:33

:36 P

M M0.01

Mechanical Legend Notes &Abbreviations

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 2: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

DN

DN

DN

DN

DN

DN

74

321

E

F

G

H

J

5 6 8

9

3.40 0.2

10

E.3

3.3

5.2

K

1.6

??

??

BUILDINGMECHANICAL

ROOMM108

MEN'S ROOMR106

WOMEN'S ROOMR105

JANITORJ107

TELE/DATAT106

ELEVATORV101

BUILDINGELECTRICAL

ROOMP108

NORTHVESTIBULE

F101

MAIN JANITOR/STORAGE

J115

??

MACHINE ROOMM106

20"x

14"

4"ø

18"x

8"

12"x12"

24"x

20"

18"x

14"

18"x

14"

18"x

14"

34"x

24"

14"ø

34"x

20"

26"x

20"

20"x

20"

14"ø

14"ø

14"ø

18"x16"

18"x16"

18"x16"

18"x16"

18"x16"

18"x16"

18"x16"

18"x16"

18"x16"

14"ø

60"x

22"

44"x

24"

42"x

20"

20"x

14"

30"x

18"

30"x

18"

24"x20"

8"x8"

60"x22"

60"x

22"

44"x

24"

10"ø

48"x

22"

34"x

30"

14"ø

34"x

28"

48"x22"

48"x

22"

48"x

22"

12"x12"

8"x4

"

8"x8

"

10"x10"

8"x4

"

8"x8"

6"x4

"

48"x22"

20"x7"

18"x

14"

12"ø

24"x

20"

(TYP. 4)

SD-A150 CFM(TYP. 4)

14"ø18"x16"

(TYP. 11)

SD-D70 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM

SD-A150 CFM(TYP. 11)

(TYP. 11)

(TYP. 11)

(TYP. 11)

(TYP. 11)

(TYP. 11)

(TYP. 11)

(TYP. 11)

FDFD

VAV3-1-1

VAV3-1-2

VAV3-1-3

VAV4-1-1

VAV4-1-2

VAV4-1-3

VAV3-2-1

VAV3-2-2

VAV3-2-3

VAV3-3-1

VAV3-3-2

VAV3-3-3

VAV4-1-4

VAV2-3-1

(TYP. 3) (TYP. 3) (TYP. 3)

EF7

EF5

EF6

5 5

FCU1

3 3

RG-I

RG-I

3 3

33

RG-I

RG-I

RG-KSD-H

250 CFM

DAH1

SD-B350 CFM

SD-B350 CFM

2

FD3

(TYP. 6)

ER-M115 CFM

UH2

UH3

SD-A200 CFM

SD-A200 CFM

SD-A200 CFM

SD-A200 CFM

(TYP. 8)

(TYP. 8)

(TYP. 8)

(TYP. 8)

8"x8

" 8"x4

"

SD-J70 CFM

SD-Q70 CFM

6

6

6

6

6

7

8

8

9

9

6

10

11

4

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:38

:45 P

M M2.01

Mechanical Ductwork PlanLevel 1 North

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Ductwork Plan Level 1 North

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE DUCTED HEATING ONLY FAN COIL UNIT ABOVE GALLERY CEILING

2 PROVIDE DUCTLESS SPLIT SYSTEM AIR HANDLER

1

2

2

3 PROVIDE DUCT SLEEVE FOR DUCT PENETRATING WALL

4 PROVIDE PIPE SLEEVE FOR PIPES PENETRATING WALL

4 33

3

4 3

5 PROVIDE FIRE DAMPER IN DUCTWORK PENETRATING FIRE RATED ASSEMBLIES

No. Description Date

6 20x14 DUCT OPENING WITH WIRE MESHED SCREEN & VOLUME DAMPER

7 6x6 DUCT OPENING WITH WIRE MESHED SCREEN & VOLUME DAMPER

8 8x8 DUCT OPENING WITH WIRE MESHED SCREEN & VOLUME DAMPER

9 10x10 DUCT OPENING WITH WIRE MESHED SCREEN & VOLUME DAMPER

10 PROVIDE INACTIVE LINEAR SUPPLY DIFFUSERWITH BLANK OUT PLATES

11 PROVIDE WIRE MESH SCREEN

Page 3: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

321

A

C

D

E

5 6 8 93.4

B

0 0.2 103.3

5.2

0.5A

0.7A

AA

BB

B.5

8.8 9.18.2

1.6

SMALLCLASSROOM

110

ELECT: POWERLAB114

CIVIL: SURVEY111

CIVIL: GEO(SOILS) TEACHING

LAB112CIVIL: STUDENT

PROJECT LAB113

??

CIVIL: CONCRETEPREP116

CIVIL: CONC/ASPHALT LAB

117

CIVIL:STRUCTURES LAB

118

STRENGTH OFMATERIALS LAB

119

CONNECTORQ104

LOBBYF102

MAIN JANITOR/STORAGE

J115

LOADING BAY115

STAIR 3Z103

CORRIDORQ103

??

SOUTHVESTIBULE

F10316"x12"

16"x12"10"ø

16"x12"

16"x

14"

16"x14" 26"x14"50"x20"

44"x20" 36"x18" 34"x14" 16"x14"

14"x

12"

16"x

14"

14"x

10"

16"x

14"

16"x

12"

20"x16"10"ø 14"ø 10"ø

10"ø

20"x20"

16"x

12"

16"x

12"

18"x

12"

18"x

16"

16"x

12"

8"ø

34"x12"

16"x

12"

24"x8"

18"x

8"

14"ø

14"ø

12"ø

10"ø

10"ø

14"ø

10"ø

20"x20" 18"x18" 18"x14"

30"x

20"

12"x10"

12"x

12"

24"x20"

18"x8"

10"ø

10"ø

16"x

14"

64"x

18"

64"x

18"

24"x20"

60"x22"

64"x18"

60"x22"

16"x

12"

16"x

12"

48"x

22"

20"x7"

6"ø

SD-C255 CFM(TYP. 4)

(TYP. 4)

(TYP. 4)

SD-C255 CFM

SD-C250 CFM

SD-C210 CFM(TYP. 6)

SD-C250 CFM(TYP. 4)

SD-C255 CFM(TYP. 4)

SD-C255 CFM(TYP. 4)

SD-C365 CFM

SD-C365 CFM

(TYP. 3)

(TYP. 3)

SD-C310 CFM(TYP. 3)

SD-C310 CFM(TYP. 3)

SD-A160 CFM(TYP. 2)

VAV4-3-1

VAV4-4-1

VAV2-8-1

VAV2-9-1

VAV2-9-2

VAV2-10-1 VAV

2-10-2

VAV2-1-2

VAV2-1-1

VAV2-7-2

VAV2-7-1

VAV2-6-1

VAV2-5-1

VAV2-2-1

VAV2-4-2VAV

2-4-1

RG-J RG-J

(TYP. 3) (TYP. 3)

RG-J

(TYP. 3)

RG-J

(TYP. 3) RG-J

(TYP. 3)

RG-J

(TYP. 3)

RG-J

(TYP. 3)

SD-C340 CFM(TYP. 3)

RG-J

(TYP. 3)

RG-L

(TYP. 10)

SD-F410 CFM(TYP. 4)

FCU2

2

4

T

5

T

SD-H250 CFM

RG-K

8"ø

8"ø

10"ø

14"ø

10"ø

10"ø10"ø

FD3

FD3 FD3

16"x12"

16"x12"

16"x12"

16"x

14"

FD3

FD3

RG-Q

FCU3

555

11

5

H1

SD-P450 CFM(TYP 2)

5

5SD-A

200 CFM(TYP. 3)

24"x

20"

5

55

4

66"x6"

24x4 PLENUM

14x8 PLENUM

6"ø

SD-H75 CFM

EF10

10"ø7

8

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:56

:20 P

M M2.02

Mechanical Ductwork PlanLevel 1 South

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Ductwork Plan Level 1 South

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE DUCTED HEATING ONLY FAN COIL UNIT ABOVE GALLERY CEILING.

2 MOUNT EF-8 ABOVE BATTERY RACK- COORDINATE WITH OWNER. FAN TO RUN CONTINUOUSLY.

3 PROVIDE FIRE DAMPER IN HORIZONTAL DUCTWORK PENETRATING FIRE RATED SHAFTS.

1

2

No. Description Date

4 PROVIDE AND MOUNT BRICK VENT FOR EF-8 ABOVE DOOR

5 PROVIDE WIRE MESH SCREEN OVER RETURN DUCT OPENING

6 PROVIDE TRANSFER AIR DUCT

7 10x10 PENETRATION THRU WALL WIRE MESH SCREEN OVER OPENING

8 8" EXTRACTION ARMS

Page 4: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

74

321

A

C

D

E

F

5 6 8

9

3.4

B

0 0.2

10

E.3

3.3

5.2

B.5

8.8 9.18.2

1.6

??

UPPER CORRIDORQ201

WOOD/METALSHOP207BELECT: LARGE

EQUIP STORAGE207

??

GATHERINGQ201A

ELECT: RL 3205

GATHERING217

STAIR 3Z203 ELECT: SIGNAL

INTEGRITYCENTER

216

??

MULTI-PURPOSEROOM

204

MEN'S RMR203

WOMEN'S RMR201

JANITORJ204

CORRIDORQ202

STUDENTLOUNGE

201

ELECT: MICRO/COMM LAB

209ELECT:

COMPUTER LAB210

??

ELECT: RL 5208

ELECT: RL 4206

ELECT: RL 1216A

ELECT: RLPHYSICS

214A

CORRIDORQ203

ELECT: AUTO/ROBOTICS LAB

211 ELECT: SENIORPROJECT LAB

212

ELECT: GEN. EELAB213

ELECT: PHYSICSLAB214

??

18"x

16"

18"x

14"

18"x

14"

18"x

14"

18"x

14"

12"ø

26"x18"

6"ø

18"x

14"

20"x18"

8"x6"18"x14"

20"x

12"

16"x10"

12"ø

8"ø18"x14"

10"x10"

6"ø

10"x

10"

10"x12"8"ø 16"x18"

24"x20"

18"x

16"

14"ø

14"x

12"

18"x16"

14"x

12"

20"x

18"

16"ø

16"ø

10"x10"

10"x6"

22"x

14"

20"x14"

8"x6

"

12"x

10"

44"x20"

10"x

6"

18"x

12"

26"x14"

18"x

12"

6"ø

24"x16"40"x16"

8"x6"

6"x4

"6"

x4"10"x6"

8"x4

"

16"x16"

48"x

16"

66"x

30"

48"x16" 32"x18"

84"x

24"

54"x20"

48"x16"

50"x

28"

54"x

24"

48"x

16"

14"ø

14"ø

14"ø

12"ø

12"ø

12"ø

14"ø16"ø

10"x10"

22"x

14"

8"x6

"

24"x

14"

20"x

18"

10"ø

20"x10"

----

SD-C240 CFM(TYP 8)

SD-C250 CFM(TYP 6)

SD-C230 CFM(TYP 6)

L-359245 CFM(TYP 6)

SD-C255 CFM(TYP 6)

SD-A250 CFM

SD-A250 CFM

SD-A250 CFM

(TYP 8)

(TYP 8)

(TYP 8)

RG-J

(TYP 3)RG-J

RG-J

RG-JRG-JRG-JRD-J(TYP 3)(TYP 3)(TYP 3)(TYP 3)

RG-JRG-J

RG-J

RG-J

RG-J RG-J(TYP 3) (TYP 3)

RG-J

(TYP 2)

SD-A155 CFM(TYP 2)

SD-B280 CFM

SD-B280 CFM

RG-L

VAV1-1-2

VAV1-1-1

VAV1-2-1

VAV4-5-1

VAV4-6-1

VAV1-8-1

VAV4-5-2

VAV1-10-1

VAV1-9-1

VAV1-7-1

VAV1-5-1

VAV1-6-1

VAV1-4-1

VAV1-3-1

VAV1-11-1

VAV1-12-1

VAV1-13-1

VAV1-14-1

VAV1-16-1

VAV1-15-1

VAV1-17-1

VAV4-7-1

VAV4-5-3

SD-G505 CFM(TYP 4)

SD-C285 CFM(TYP 6)

SD-C265 CFM(TYP 6) SD-C

295 CFM(TYP 6)

SD-C260 CFM(TYP 3)

SD-C240 CFM(TYP 2)

SD-C255 CFM SD-C

255 CFM(TYP 2)(TYP 2)

10"x12"

10"x12"

SD-C260 CFM(TYP 2)

SD-C230 CFM(TYP 2)

SD-C245 CFM(TYP 2)

SD-A200 CFM(TYP 3)

FD

FD

FDFD

2

2

222

(TYP 10)

RHZP2

----

----

18"x

14"

10"ø

10"ø

ER-M105 CFM(TYP. 4)

ER-M70 CFM

ER-M70 CFM

----

----

33

3333

16"x

10"

16"x

10"

16"x

10"

32"x24"

16"x

10"3

3 3

18"x10"

10"ø

3 3 3

3

4

3

12"ø

14"ø

16"x

12"

3

12"ø

14"ø

16"x

12"

3

14"x

12"

12"x

12"

----

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:39

:56 P

M M2.03

Mechanical Ductwork PlanLevel 2

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Ductwork Plan Level 2

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE MULTI-CIRCUIT RADIANT HEAT ZONE PANEL- RECESSED INTO WALL.

PROVIDE FIRE DAMPER IN DUCTWORK PENETRATING FIRE RATED ASSEMBLIES.

PROVIDE WIRE MESH SCREEN OVER OPENING WITH VOLUME DAMPER.

PROVIDE INACTIVE LENGTH LINEAR SUPPLY DIFFUSER WITH BLANK OFF PLATES.

1

RADIANT HEAT ZONE '3'

2

No. Description Date

3

4

Page 5: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

DN

DN

DN

DN

DN

DN

74

321

E

F

G

H

J

5 6 8

9

3.40 0.2

10

E.3

3.3

5.2

K

1.6

STAIR 2Z102

BUILDINGMECHANICAL

ROOMM108

MEN'S ROOMR106

WOMEN'S ROOMR105

JANITORJ107

TELE/DATAT106ELEVATOR

V101

BUILDINGELECTRICAL

ROOMP108

CORRIDORQ102

NORTHVESTIBULE

F101

MAIN JANITOR/STORAGE

J115

MACHINE ROOMM106

3/4"ø

3/4"ø

1 1/4"ø

1 1/4"ø

1"ø1"

ø

2"ø

2"ø

2"ø

2"ø

1 1/

2"ø

1 1/

4"ø

1 1/

4"ø

1 1/

4"ø

1 1/

4"ø

1"ø

1"ø

1"ø

1"ø

1"ø

1"ø

1"ø

1"ø

1 1/4"ø

VAV3-1-1

VAV3-1-2

VAV3-1-3

VAV4-1-1

VAV4-1-2

VAV4-1-3

VAV3-2-1

VAV3-2-2

VAV3-2-3

VAV3-3-1

VAV3-3-2

VAV3-3-3

VAV4-1-4

VAV2-3-1

VAV4-2-1

5T

FCU1

T5

T 5

T5

T5

T5

6

T

T 5

UH2

UH3

3/4"ø

3/4"

ø3/

4"ø

3/4"ø

1/2"ø 1/2"øWH1

1/2"ø 1/2"ø

4

1"ø 1"ø

3/4"

ø

2

HW

SH

WR

HWSHWR

RHZP-1

1

4

4

4

4

4

4

4

4

4

4

4

4

4

1 1/

4"ø

HW

SH

WR

3

RADIANT HEAT ZONE 1

WH1

120 SEATCLASSROOM

102

120 SEATCLASSROOM

103

120 SEATCLASSROOM

104

CORRIDORQ101

MEN'S ROOMR106

CORRIDORQ101T5

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

5:20

:04 P

M M2.04

Mechanical Piping PlanLevel 1 North

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Piping Plan Level 1 North

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE MULTI-CIRCUIT RADIANT HEAT ZONE PANEL - RECESSED INTO WALL.

2 EXTEND 4" HTHW SUPPLY & RETURN PIPING TO STUB OUTS AT MANHOLE -SEE SITE PLAN FOR EXACT LOCATION

3 PROVIDE CONTROL POWER TRANSFORMER MOUNTED ABOVE CEILING.

4 SEE VAV SCHEDULE FOR PIPE RUN OUT SIZE.

5 PROVIDE THERMOSTAT FOR VAV

6 PROVIDE THERMOSTAT FOR FCU-1

MECHANICAL GENERAL WORK NOTES:

1. PROVIDE BALL VALVE TYPE SHUT OFF VALVES ON SUPPLY AND RETURN LINES ON ALL BRANCH LINES FROM MAINS SERVING MULTIPLE VAV BOXES.

2. ADD GATE VALVE SHUT OFFS ON ALL MAINS SERVING EACH FLOOR FROM RISERS.

No. Description Date

Page 6: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

321

A

C

D

E

5 6 8 93.4

B

0 0.2 103.3

5.2

0.5A

0.7A

AA

BB

B.5

8.8 9.18.2

1.6

STAIR 2Z102

SMALLCLASSROOM

110

ELECT: POWERLAB114

CIVIL: SURVEY111

CIVIL: GEO(SOILS) TEACHING

LAB112CIVIL: STUDENT

PROJECT LAB113

CIVIL: CONCRETEPREP116

CIVIL: CONC/ASPHALT LAB

117

CIVIL:STRUCTURES LAB

118

STRENGTH OFMATERIALS LAB

119

CONNECTORQ104

LOBBYF102

CORRIDORQ102

MAIN JANITOR/STORAGE

J115

LOADING BAY115

STAIR 3Z103

CORRIDORQ103

SOUTHVESTIBULE

F103

1 1/4"ø1 1/4"ø

1"ø1"ø

3/4"ø3/4"ø

3/4"

ø3/

4"ø

2"ø2"ø

1 1/2"ø1 1/2"ø

1 1/4"ø1 1/4"ø

1 1/2"ø1 1/2"ø

1"ø1"ø 1"ø

1"ø

VAV4-3-1

VAV4-4-1

VAV2-9-1

VAV2-9-2

VAV2-10-1

VAV2-10-2

VAV2-1-2

VAV2-1-1

VAV2-7-2

VAV2-7-1

VAV2-6-1

VAV2-5-1

VAV2-2-1

VAV2-4-2VAV

2-4-1

VAV4-2-1

FCU2

T

7

VAV2-8-1

6

T

T

6

T6

T6

T6

T6

T

6

6

T

6

T

6

T 6

T

WH1

4

1 1/2"ø1 1/2"ø

4

WH1

HWSHWR

WH1

3/4"

ø3/

4"ø HWS

HWR

H1

25

RADIANT HEAT ZONE 1

UH4

UH5

T

8UH-4

3/4"ø3/4"ø

3/4"ø3/4"ø

11

FCU3

T

13

11 9

10

3/4"

ø3/

4"ø

3/4"

ø3/

4"ø

CHWSCHWR

T UH-5

8

1"ø 1"ø1"

ø1"

ø3/

4"ø

3/4"

øH

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

5:20

:29 P

M M2.05

Mechanical Piping PlanLevel 1 South

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Piping Plan Level 1 South

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE MULTI-CIRCUIT RADIANT HEAT ZONE PANEL.

2 PROVIDE AIR AUTOMIZING HUMIDIFIER (H-1). RUN COMPRESSED AIR ANDDOMESTIC COLD WATER LINE (BY P.C.) TO HUMIDIFIER.

3

4

5

6

PROVIDE FOGGING MANIFOLD FOR HUMIDIFIER. RUN INSULATED WATER ANDCOMPRESSED AIR LINES FROM HUMIDIFIER (H-1) TO FOGGING MANIFOLD.

MOUNT CONTROL POWER TRANSFORMER ABOVE CEILING.

PROVIDE HUMIDIFIER CONTROL PANEL.

PROVIDE THERMOSTAT FOR VAV

7 PROVIDE THERMOSTAT FOR FCU-2

MECHANICAL GENERAL WORK NOTES:

1. PROVIDE BALL VALVE TYPE SHUT OFF VALVES ON SUPPLY AND RETURN LINES ON ALL BRANCH LINES FROM MAINS SERVING MULTIPLE VAV BOXES.

2. ADD GATE VALVE SHUT OFFS ON ALL MAINS SERVING EACH FLOOR FROM RISERS.

No. Description Date

8 PROVIDE THERMOSTAT FOR UNIT HEATER.

9 PROVIDE DIGITAL REMOTE HUMIDITY SENSOR FOR H-1 CONTROL.

10 PROVIDE THERMOSTAT FOR FCU-3.

11 2 1/2" HWS AND HWR PIPING UP TO SECOND FLOOR.

12 1" CHWS AND CHWR PIPING UP TO SECOND FLOOR.

13 PROVIDE FAN COIL UNIT FOR CONCRETE CURING ROOM.

Page 7: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

74

321

A

C

D

E

F

5 6 8

9

3.4

B

0 0.2

10

E.3

3.3

5.2

B.5

8.8 9.18.2

1.6

0 0.2 1 2 3 3.4 4 5 5.2 6 7 7.5

7.8

8 8.8 9.19 10

A

B

B.5

C

D

D.8

E

E.3

E.5

F

0.7A

AA

1.6

Z.11 Z.12

7.7

3.3

0.5A

3.5

E.1

8.2

UPPER CORRIDORQ201

WOOD/METALSHOP207B

ELECT: LARGEEQUIP STORAGE

207GATHERING

Q201A

ELECT: RL 3205

GATHERING217

STAIR 3Z203 ELECT: SIGNAL

INTEGRITYCENTER

216

MULTI-PURPOSEROOM

204

MEN'S RMR203

WOMEN'S RMR201

JANITORJ204

CORRIDORQ202

STUDENTLOUNGE

201

ELECT: MICRO/COMM LAB

209

ELECT:COMPUTER LAB

210

ELECT: RL 5208

ELECT: RL 4206

ELECT: RL 1216A

ELECT: RLPHYSICS

214A

CORRIDORQ203

ELECT: AUTO/ROBOTICS LAB

211

ELECT: SENIORPROJECT LAB

212

ELECT: GEN. EELAB213

ELECT: PHYSICSLAB214

2 1/2"ø2 1/2"ø

1"ø1"ø 3/4"ø

3/4"ø2 1/2"ø

2 1/2"ø2"ø

2"ø

2 1/

2"ø

2 1/

2"ø

2"ø2"ø

1 1/4"ø1 1/4"ø

1"ø1"ø

3/4"ø3/4"ø

2"ø

T 6

6

T

T 6

6

T

6 T6 T

6 T

6

T

T6

T

6T 6T

6

T

6

T 6

T6

T

6

T6

T 6

T

6

T6T 6

T 6

VAV1-1-2

VAV1-1-1

VAV1-2-1

VAV4-5-1

VAV4-6-1

VAV1-8-1

VAV4-5-2

VAV1-10-1

VAV1-9-1

VAV1-7-1

VAV1-5-1

VAV1-6-1

VAV1-4-1

VAV1-3-1

VAV1-11-1

VAV1-12-1

VAV1-13-1

VAV1-14-1

VAV1-16-1

VAV1-15-1

VAV1-17-1

VAV4-7-1

VAV4-5-3

RHZP2

RADIANT ZONE 2

2"ø

1"ø1"ø

2 1/

2"ø

2 1/

2"ø

HWRHWS

2

3" PIPE UP TO PENTHOUSE

HWRHWS

HW

RH

WS

1

HW

SH

WR

2"ø

4"ø

1 1/

4"ø

1 1/

4"ø MECHANICAL SPECIFIC WORK NOTES:

PROVIDE MULTI-CIRCUIT RADIANT HEAT ZONE PANELRECESSED INTO WALL.

PROVIDE CONTROL POWER TRANSFORMER ABOVE CEILING.

1

2

MECHANICAL GENERAL WORK NOTES:

1. PROVIDE BALL VALVE TYPE SHUT OFF VALVES ON SUPPLY AND RETURN LINES ON ALL BRANCH LINES FROM MAINS SERVING MULTIPLE VAV BOXES.

2. ADD GATE VALVE SHUT OFFS ON ALL MAINS SERVING EACH FLOOR FROM RISERS.

4 3

2"ø

2"ø

1"ø1"ø

5

2 1

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

5:21

:07 P

M M2.06

Mechanical Piping PlanLevel 2

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Piping Plan Level 2

1

MECHANICAL SPECIFIC WORK NOTES:

2

3

4

5

6 PROVIDE THERMOSTAT FOR VAV

1 1/4" LTHWS AND LTHWR AND 4" HTHWS AND HTHWR.

1 1/4" LTHWS AND LTHWR PIPING DOWN IN SHAFT TO FIRST FLOOR.

4" HTHWS AND HTHWR PIPING DOWN TO FIRST FLOOR.

1" CHWS AND CHWR PIPING UP TO PENTHOUSE.

3" HWS AND HWR UP TO PENTHOUSE.

No. Description Date

Page 8: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

7432

C

D

E

F

5 6 83.4

E.3

3.53.3

5.2

1.6

D.8

E.9

44"x26"

50"x30"

AHU1

AHU2

HX3

HX1

HX2

BLR1

AS1

EF4

AS2

HWP2

HWP1

CHWP2

AHU3

AHU4

ET1

ET2

CHWR5"ø

5"ø

4"ø

4"ø

2 1/

2"ø

2 1/

2"ø

2"ø

2"ø

3"ø

3"ø

2 1/

2"ø

2 1/

2"ø

2"ø

2"ø

3"ø

3"ø

3"ø

3"ø

3"ø

3"ø

6"ø

6"ø

ACC1

CHWP1

HWS

4"ø

4"ø

4"ø

44"x32"66"x30"

CHWS

HWR

EF1

1 2 3 3.4 4 5 5.2 6 7

D

D.8

E

E.3

E.5

F

1.6

Z.9

Z.8

Z.11 Z.12

3.3 3.5

E.1

78"x

26"

34"x46"

32"x

32"

82"x

26"

30"x3

4"

50"x

30"

44"x

26"

44"x

32"

32"x

32"

82"x

26"

96"x

26"

EF2

7

14 14 14 14 14

13131313

7

11

2

7

7

8 10

11

2 2

2

11 1

1

15

1919

1

18

18

17

18

1

17

1717

16

11

12

20 21

HWP3

HWP4

22

34"x

46"

7

7

7

7

23

23

23

23

8

VD

VD

VD

VD

6

6

3

5

DCU1 4

VFD4

VFD3

VFD2

VFD1

ATC PANEL

ATC PANEL

ATC PANEL

ATC PANELATC PANEL

ATC PANEL

ATC PANEL

54"x

30"

14 14

----

----

----

2725

26

28

24 24

96"x

86"

80"x

80"

30

24 24

1 1/4"ø1 1/4"ø

4"ø4"ø

28

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/4" = 1'-0"

11/19

/2012

4:42

:06 P

M M2.07

Mechanical EnlargedPenthouse Plans

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/4" = 1'-0"1 Mechanical Plan Penthouse

66" x 30" RETURN DUCT RUNNINGTO SECOND FLOOR CEILING

30" x 46" SUPPLY DUCTRUNNING TOSECOND FLOOR CEILING

44" x 32" SUPPLY DUCT RUNNINGTO SECOND FLOOR CEILING

44" x 32" RETURN DUCT RUNNINGTO SECOND FLOOR CEILING

44" x 26" SUPPLY DUCTRUNNING TOFIRST AND SECOND FLOORCEILING

50" x 30" RETURN DUCTRUNNING TOFIRST AND SECOND FLOORCEILING

34" x 30" SUPPLY DUCTRUNNINGTO FIRST FLOOR CEILING

46" x 34" RETURN DUCTRUNNINGTO FIRST FLOOR CEILING

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE 4" HOUSEKEEPING PADS.

PROVIDE NEW CONTROL STATION AIR HANDLER (AHU -1 THRU AHU - 4).

PROVIDE NEW AIR COOLED CHILLER (ACC-1). MOUNT ON STEEL FRAME. INSULATE AND HEATTRACE EXTERIOR CHILLED WATER.

PROVIDE NEW DUCTLESS SPLIT SYSTEM, CONDENSING UNIT (DCU-1). MOUNT ON BASE RAILS.

PROVIDE PIPE PORTAL REFRIGERANT PIPING, CONTROL WIRE, AND POWER WIRING.

PROVIDE WALL AND FLOOR PIPE SLEEVES. CAULK AROUND OPENING.

PROVIDE WALL, FLOOR, AND ROOF DUCT SLEEVES. CAULK AROUND OPENING.

EXHAUST UP TO EXHAUST FAN (EF) ON ROOF. PROVIDE DUCT SLEEVES AND CAULK AROUNDOPENING.

EXHAUST DUCT UP THRU ROOF TO EXHAUST STACK. PROVIDE DUCT SLEEVES AND CAULKAROUND OPENING.

EXHAUST DUCT UP FROM FLOOR BELOW. PROVIDE DUCT SLEEVES AND CAULK AROUND OPENING.

PROVIDE RELIEF DUCT UP THRU ROOF TO RELIEF HOOD (RH) LOCATED ON ROOF. PROVIDE DUCTSLEEVES AND CAULK AROUND OPENING.

PROVIDE OUTSIDE AIR DUCT THRU ROOF FROM INTAKE HOOD (IH) LOCATED ON ROOF. PROVIDEDUCT SLEEVES AND CAULK AROUND OPENING.

ATTACH INTAKE DUCTWORK TO WALL LOUVER. INSULATE OUTSIDE AIR DUCT FROM WALLLOUVER TO AHU.

PROVIDE 4" RIGID INSULATED PANEL WITH SHEETMETAL COVER OVER ENTIRE UNUSED WALLLOUVER AREA.

2

3

4

5

6

7

8

9

10

11

12

15 PROVIDE EXHAUST STACK UP THRU ROOF. PROVIDE DUCT SLEEVES AND CAULK AROUND OPENING. SEE DETAIL.

PROVIDE NEW GAS FIRED CONDENSING BOILER. MOUNT ON 4" CONCRETE HOUSEKEEPING PAD.

PROVIDE BASE MOUNTED CHILLED WATER (CHWP) AND BASE MOUNTED HEATING WATER (HWP) PUMPS. MOUNTON VIBRATION INERTIA BASE.

PROVIDE PLATE AND FRAME HEAT EXCHANGER (HX). MOUNT ON 4" CONCRETE HOUSEKEEPING PAD.

PROVIDE HYDRONIC EXPANSION TANKS. MOUNT ON 4" CONCRETE HOUSEKEEPING PAD.

PROVIDE WATER TREATMENT CONTROL PANEL.

PROVIDE WATER TREATMENT TANK.

PROVIDE WATER TREATMENT INJECTION PUMPS.

PROVIDE FIRE DAMPER IN VERTICAL DUCTWORK PENETRATING FLOOR OF MECHANICAL ROOM INTO SHAFTBELOW.

WALL LOUVER PROVIDED AND INSTALLED BY G.C.

PROVIDE 7" ROUND STAINLESS STELL COMBUSTION AIR DUCT.

PROVIDE 7" ROUND STAINLESS STEEL VENTING.

PROVIDE DOWN-TURNED ELBOW INSECT SCREEN.

PROVIDE 24"x24" OUTSIDE AIR DUCT TAPPED INTO BLANK-OFF PANEL. PROVIDE MOTORIZED DAMPER.

PROVIDE THERMOSTAT FOR PENTHOUSE HEATING AND VENTILATION CONTROL.

PROVIDE HYDRONIC UNIT HEATER. MOUNT 10'-0" AFF.

16

17

18

19

20

21

22

23

24

25

No. Description Date

13

14

26

27

28

29

30

Page 9: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

74

321

A

C

D

E

F

5 6 8

9

3.4

B

0 0.2

10

E.3

3.53.3

5.2

B.5

8.8 9.18.2

1.6

D.8

E.9

EF3

RH1

RH2

RH3

IH7

0 0.2 1 2 3 3.4 4 5 5.2 6 7 7.5

7.8

8

8.8 9.1

9 10

A

B

B.5

C

D

D.8

E

E.3

E.5

F

0.7A

AA

BB

1.6

Z.9

Z.8

Z.11 Z.12

7.7

3.3

0.5A

3.5

E.1

8.2

RH9

ACC1

DCU3

DCU1

EF4

2111

4

3

3

5 67

8

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:42

:21 P

M M2.08

Mechanical Plan Roof

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

1/8" = 1'-0"1 Mechanical Plan Roof

1

MECHANICAL SPECIFIC WORK NOTES:PROVIDE NEW ROOF MOUNTED RELIEF HOOD. MOUNT ON ROOF CURB.

2

No. Description Date

PROVIDE NEW ROOF MOUNTED INTAKE HOOD. MOUNT ON ROOF CURB.

3 PROVIDE NEW ROOF MOUNTED EXHAUST FAN. MOUNT ON ROOF CURB.

4 PROVIDE 10" FUME HOOD EXHAUST STACK. EXTEND 10'-0" ABOVE ROOF. SEE DETAIL.

5 HEAT TRACE ALL EXTERIOR CHILLED WATER SUPPLY AND RETURN PIPING.

6 PROVIDE AIR COOLED CHILLER.

7 PROVIDE DUCTLESS SPLIT SYSTEM CONDENSING UNIT - MOUNT ON CURB RAILS.

8 PROVIDE PIPING PORTAL. SEE DETAIL.

Page 10: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

DNDN

ROOF BELOW

X

X

XX

X

UPUP

DN DN

DN

M

M

M

T

T

T

SCALE: NONE

EXISTING BUILDING MECHANICAL PLAN - SECOND FLOOR1M-2.09

SCALE: NONE

EXISTING BUILDING MECHANICAL PLAN - FIRST FLOOR2M-2.09

203CLASSROOM

WOMENMEN

101NEW

MECHANICALCONTROL /

VIBRATION LAB

104NEW

MECHANICALTHERMAL / FLUIDS

LAB

Q101CORRIDOR

106OFFICE ADMIN

107OPEN OFFICE

AREA108

STORAGE

F102LOBBY

V101

F101VESTIBULE

STAIRZ101

113OFFICE / ADMIN

114AOFFICE

114OFFICE

115STORAGE

STAIRZ102

J112JANITOR

Q102CORRIDOR

F103VESTIBULE

Q103CORRIDOR

120NEW ENTRY /

LOUNGE

121CLASSROOM

117CLASSROOM

116CLASSROOM

Q201CORRIDOR

J214JANITOR

J211JANITOR

202BNEW

MECHANICALRESEARCH

202ANEW CIVILRESEARCH

202NEW CIVILRESEARCH

MEN WOMEN 209NEW CIVILRESEARCH

209ANEW

MECHANICALRESEARCH

208OBSERVATION

208ATESTING

V201

Z201STAIR

Z202STAIR

217NEW COMPUTER

LAB204

VENDING

207CLASSROOM

206CLASSROOM

M201ELEV. MACH.

216APARTMENT

1SSAH

1L

2SSAH

2L

3

L

3SSAH

3

SSHP

2

SSHP

1

SSHP

1ECH

1EDH

9EF

1SF

16x6

24x624x6

12x10 8x814x12

24x6

2

2

2

3

3

3

5

5

5

4

4

4

18x624x6

12x6

24x8

14"∅

12"∅

10"∅

12"∅

20x10

24x6

6

9

12X12

10x8

10x8

8

7

14x4

14x4

1 10

1 10

1 10

11

11

11

10"C 200

TYP 6

C 375

TYP 2

E 200

TYP 6

H

TYP 2

H

TYP 2

H

TYP 2 C 200 CFM

TYP 6

10"

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:42

:31 P

M M2.09

Mechanical ExistingBuilding Plan

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

KEYED NOTES:

MOUNT SPLIT SYSTEM HEAT PUMP (SSHP-X) ON 4" HOUSEKEEPING PAD ON GRADE BELOW. ROUTE REFRIGERANTPIPING UP EXTERIOR WALL AND INTO FIRST FLOOR CEILING SPACE. TYPICAL FOR ALL (SSHP-X).

MOUNT SPLIT SYSTEM AIR HANDLER IN CEILING SPACE

PROVIDE FULL SIZE RETURN DUCT PLENUM WITH 30% FILTERS

PROVIDE 24V MOTORIZED DAMPER ON OUTSIDE AIR DUCT

PROVIDE FULL SIZE PLENUM ON OUTSIDE AIR LOUVER. PROVIDE WALL LOUVER. INSULATE PLENUM.

PROVIDE 3'x5' GALVANIZED SHEET METAL EXHAUST HOOD - SEE DETAIL

PROVIDE SUPPLY FAN - MOUNT ON SLOPED ROOF CURB - SEE DETAIL

PROVIDE UPBLAST EXHAUST FAN - MOUNT ON SLOPED ROOF CURB- SEE DETAIL

PROVIDE ELECTRIC DUCT HEATER - SEE DETAIL

PROVIDE REFRIGERANT PIPING BETWEEN INDOOR AND OUTDOOR UNIT- SIZE PER MANUFACTURER'S RECOMMENDATIONS.FILL SYSTEM WITH REFRIGERANT.

PROVIDE WALL MOUNTED THERMOSTAT. (LOW VOLTAGE)

1

2

3

4

5

6

7

8

9

10

11

No. Description Date

Page 11: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

-FCU

SCALE: NONE

DUCTWORK THRU ROOF CURB DETAIL4M-3.01

SCALE: NONE

DUCTWORK CONNECTION DETAILS1M-3.01 SCALE: NONE

DUCT HANGER DETAILSSCALE: NONE

ELBOW TURNING VANE DETAILS

SCALE: NONE

SCALE: NONE

GRILLE DUCT DETAILRETURN/EXHAUST AIR

SCALE: NONE

DETAIL - HARD CEILINGDIFFUSER DUCTWORK CONNECTION

DETAIL - EXPOSED CEILINGDIFFUSER DUCTWORK CONNECTION

SCALE: NONE

ROOF CURB DETAIL DETAIL

2M-3.01

3M-3.01

12M-3.01

7M-3.01

5M-3.01

9M-3.01SCALE: NONE

FIRE DAMPER DETAIL8M-3.01

SCALE: NONE

INTAKE/RELIEF HOOD DETAIL (RH 1 THRU 3 AND IH-1)6M-3.01

SCALE: NONE

ADJUSTABLE LINEAR DIFFUSER DETAIL (SD)10M-3.01 SCALE: NONE

EXTERIOR WALL LOUVER DETAIL13M-3.01SCALE: NONE

FAN COIL UNIT DUCTWORK DETAIL11M-3.01

INSTALL PER MFR RECOMMENDATIONSWEATHERTIGHT EQUIPMENT ROOT CURB.

LEVEL.

NOTES:

MINIMUM 3'-0" ABOVE ROOF. OUTDOOR AIR INTAKE AT A2.) CURB HEIGHT SHALL PROVIDE

1.) ALL EQUIPMENT SHALL BE SET

FLASHING OF ROOF BY G.C.

ROOF CONSTRUCTION

HVAC UNIT

SHEET METAL FLASHINGWOOD NAILER

COUNTERFLASHING BY G.C.

EQUIPMENT BASE FOR ALL ROOFTOPINSTALL PER MFR INSTRUCTIONS

NEOPRENE GASKET

AIR CONDITIONING UNITS.

RETURN/EXHAUST DUCT

SHEET METALPLENUM BOX

NOTE:SEE FLOOR PLANS FOR LOCATIONS OF RETURN/EXHAUSTAIR REGISTERS & GRILLES.

CEILING

OPPOSED BLADEDAMPER

RETURN/EXHAUST DUCT

MAX. SIDE

(8 FT. MAX. HANGER SPACING)

NOTE:

TYPE "B", "C", & "D"

FOR SEVERAL DUCTS ON ONE HANGER, TYPE "B", "C",OR "D" MAY BE USED. SIZE OF HANGER WILL BESELECTED ON SUM OF DUCT WIDTHS EQUAL TO MAX.WIDTH OF DUCT SCHEDULE.

OR BRANCH.)

1" STRAP

DOVER 96"

UP TO 18"

19" TO 60"

61" TO 96"

DIMENSIONDUCT HANGER

A

B

C

TYPE

1-1/2" x 1-1/2" x 1/8"

1-1/2" x 1-1/2" x 3/16"

1/2" 2" x 2" x 1/4"

ROD

5/16"

3/8"

DIA.ANGLE

SIZE

4'-0"

MAX

8'-0"

8'-0"

8'-0"

SPACING

MAX. SIDE

(8 FT. MAX. HANGER SPACING. ALSOPROVIDE 3 HANGERS AT EACH TAKE-OFF

TYPE "A"

1" x 16 GA.GALV. IRONSTRAP ORALUMINUM

SHEET METAL SCREW,RIVET OR BOLT TOBOTH SIDES OF DUCT.

SECURE TO STRUCTUREABOVE AS RECOMMENDEDBY SMACNA

FOR BRACING ANGLES

NUT & WASHER AT

SEE NOTES

END OF ROD.

HANGER ROD (TYP)

SECURE TO STRUCTUREABOVE AS RECOMMENDEDBY SMACNA

ROUND NECKON DIFFUSER

VOLUME DAMPER

MAIN SUPPLY DUCTBUTTERFLY

CEILING DIFFUSER

OR SQUARE-TO-ROUNDADAPTER

AIR FLOW

DOUBLE SIDE

TRANSITIONS

SINGLE SIDE

W2xD2

& BRANCH MAINS

MAINS

BxD1

MAINS, SUBMAINS

AxD1

W1xD1

W2xD2W2xD2+W3xD3

W3xD3W2xD2+W3xD3

TURNING VANESDOUBLE-THICKNESS

VANED ELBOWS

B=

A=

RADIUS

NOTE

W

R

R=W

BOOT TAP

AIR FLOW

W3xD3

L=W/4, MIN 4"NOTE:

W

VOLUME DAMPER

15°

30°

45°

6" MIN.

TYPICAL ELBOW

IN WIDTH AND/OR DEPTHUSE FOR ELBOWS UP TO 36"SMALL DOUBLE VANE ELBOW

LARGE DOUBLE VANE ELBOW USE

ANY DEPTHFOR ELBOWS 36" OR WIDER AND

4 1/2" RADIUS

45° (TYP.)

2 1/4" 2 1/4"

DEPTH (D)

2 1/4" RADIUS

WIDTH (W)

2" RADIUS

3 1/

4"

1" RADIUS

1 1/8"

45°

2 1/

8"

SUPPLY DUCT AIR FLOW

RETURN OR EXHAUST DUCT AIR FLOWSUPPLY DUCT AIR FLOW

RETURN OR EXHAUST DUCT AIR FLOW

DUCT MAX. 5'-0"INSULATEDFLEXIBLE

ROUND NECKON DIFFUSER

HARD CEILING

VOLUME DAMPER

(INSULATED)BUTTERFLY

CEILING DIFFUSER

OR SQUARE-TO-ROUNDADAPTER

AIRFLOW

INSECT SCREEN (INTAKE HOODS ONLY)

DUCT THRU ROOF, SIZEAT THROAT CONNECTION

ULTRA-LOW LEAKAGE DAMPERON RELIEF HOODS ONLY

INTAKE OR RELIEF AIR HOOD

SECURE HOOD TO CURBWITH SCREWS OR LAGBOLTS

WOOD BLOCKING (BY G.C.)

SIZE VARIES SEE PLANSROOF OPENING BY G.C.

AND SCHEDULES

CONTRACTOR TO FURNISH. GENERALCURB BY HOOD MANUFACTURER.12" HIGH PREFABRICATED INSULATED

CONTRACTOR TO INSTALL AND FLASHAS PER ROOFING MANUFACTURER.CONSULT ROOFING MFGR FOR TYPE.

ROOF MEMBRANE

DECK

HOODS ONLY, SEE PLANS FOR SIZEDUCTED CONNECTION ON INTAKE

12" M

IN.

WOOD BLOCKING (BY G.C.)

ROOF MEMBRANE

ROOF INSULATION

DECK

18" M

IN.

ADJUSTABLE PATTERNLINEAR SUPPLY

12" HIGH LINED PLENUMBY DIFFUSER MFG.

KINK-FREE ANDBRANCH DUCT INSTALLINSULATED FLEXIBLE

INSTALL DAMPER

SUPPLY DUCT,

OPERATOR OUTSIDE

NYLON TIES

WITH NO SAGS

SEE PLANS

INSULATION

CONTROLLERSAIR DIFFUSER

FLASHING BY ROOFINGCONTRACTOR

WOOD NAILER BYCURB MFGR.

COUNTERFLASHING BY M.C.WELD & SEAL TO DUCT

REFER TO ARCHITECTURAL ANDSTRUCTURAL DWGS. FOR ROOFOPENINGS, COORDINATE WITHGENERAL CONTRACTORS

18" HIGH PREFABRICATED INSULATED CURB.MECHANICAL CONTRACTOR TO FURNISH.ROOFING CONTRACTOR TO INSTALL

18 GUAGE WEATHERPROOFDUCTWORK AND JOINTS

EXTERIOR RIGID INSULATION COVERED WITH EDPMROOFING (WHITE). ON ALL EXTERIOR DUCTWORK FORSUPPLY AND RETURN AIR. PROVIDE UV COATING

TURNING VANES

NOTE:

USE HARD DUCT FOR ALL ELBOWSDOWN TO GRD'S FOR EXPOSED CEILNGS.

ACCESS DOOR

PROVIDE METAL NOSING ONLEADING EDGES OF LINER

DUCT LINER, WHEREAPPLICABLE

UL 555 LISTED APPROVEDFIRE DAMPER

1 1/2"x1 1/2"x1/8" ANGLE IRONALL AROUND DUCT WELD TOSLEEVE AND INSTALL TIGHTTO WALL CONSTRUCTION

FIRE RATED WALL OR FLOOR

BREAKWAY TYPESLIP JOINT DUCTCONNECTION

WELD FIRE DAMPERFRAME TO LEEVE

165°F FUSIBLE LINK

16 GAUGE BLACK IRONSLEEVE ALL AROUND

PACK VOID WITH 1/4" MIN. TO 1/2"MAX. FIRE-RATED CAULKING

NOTES:1. HORIZONTAL MONTED DAMPERS SHALL

HAVE STAINLESS STEEL NEGATOR SPRING

WALL LOUVERW/ BIRD SCREEN

REFER TO ARCH DWGS FOR

SEALANT ALL AROUNDSHIM AND CONTINUOUS

-L

24 V MOTORIZEDDAMPER

DETAILED CONSTRUCTION

NOTE: FLEX DUCT IS ONLY USEDFOR GRD'S ABOVE HARD CEILING.

(5) FEET OF DUCTWORKINSULATE FIRST FIVE

ON DUCTEDSYSTEM

NOTES:

ACTUAL DUCT & PIPE CONNECTIONS MAY VARY FROM THIS TYPICALDETAIL. SEE MANUFACTURERS IOM FOR SPECIFIC CONFIGURATIONS.

1.

(TYPICAL)TO 5'-0" FROM UNIT1" ACOUSTICAL LINING

FLEXIBLE CONNECTOR

S/A

STEEL BY MCMISC. SUPPORT

W/ VIB. ISOLATORSSUPPORT RODS

R/A

MANUAL VOLUMEDAMPER

RETURN AIR DUCT

ON BOTTOM OF UNIT PER FCU SCHEDULEREMOVABLE ACCESS PANEL

(FROM SIDES)PROVIDE REMOVABLE RACK

M

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

M

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:33

:44 P

M M3.01

Mechanical Details

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 12: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

P

-

SSHP

-

SSAH

DAH

DCU

-UH

13M-3.02

2M-3.02

6M-3.02

3M-3.02

1M-3.02

5M-3.02

14M-3.02

9M-3.02

7M-3.02

SCALE: NONE

DUCTLESS SPLIT SYSTEM DETAIL (DAH-1/DCU-1)10M-3.02

4M-3.02

12M-3.02

8M-3.02

11M-3.02

CHEMICAL FEEDER DETAILSCALE: N.T.S.

ELECTRIC CEILING HEATER DETAIL (ECH-1)SCALE: N.T.S.

AIR HANDLING UNIT CONDENSATE DRAIN TRAP DETAILSCALE: N.T.S.

HVAC PIPING SUPPORT DETAILSSCALE: N.T.S.

PIPING ARRANGEMENT FOR MAIN HEATING/COOLING COILSSCALE: N.T.S.

PIPE SLEEVE THRU FLOOR DETAILSCALE: N.T.S.

PIPE PENETRATION THRU WALL DETAILSCALE: N.T.S.

MAKE-UP WATER & EXPANSION TANK DETAIL (ET - 1, 2 & 3)SCALE: N.T.S.

HYDRONIC IN-FLOOR RADIANT DETAILSCALE: N.T.S.

SPLIT SYSTEM UNIT DETAIL (SSAH/SSHP)SCALE: N.T.S.

HYDRONIC UNIT HEATER DETAIL (UH-1, 2 & 3)SCALE: N.T.S.

PIPING PORTAL DETAILSCALE: N.T.S.

SIDE STREAM FILTER DETAILSCALE: N.T.S.

3/4" EXPANSION LINE

DIAPHRAGM EXPANSIONTANK MOUNTED ON6" EQUIPMENT PAD

PREVENTER AND REDUCINGCOMBINATION BACKFLOW

VALVE. SET TO 35 PSIG

3/4" BYPASS PIPING

1" DOMESTIC WATER

GATE VALVE W/

AIR SEPERATOR

HOSE FITTING

AUTOMATIC AIR VENT

METAL JACKET

FIRE-RATED SEALANT

PIPE WITHOUT INSULATION

BACK-UP MATERIAL18 GA. PIPE SLEEVE

PIPE WITH INSULATION

PIPE INSULATION

BACK-UP MATERIAL

FIRE-RATED SEALANT

16 GAUGE SHEETMETALSLEEVE OF SIZE TOPASS PIPE & INSULATION

INTERIOR WALL

NON COMBUSTIBLE

INSULATED PIPE

CAULKING COMPOUND

FILLER

FIRE RATED IFRATED WALL

PIPE

PROVIDE FEEDER FOR BOTH

TO FLOOR DRAIN1/2" DRAIN VALVE

NOTE:

HOT AND CHILLED WATER SYSTEMS.

ASME RATED POT FEEDER5 GALLON CAPACITY

LINES TO BE SIZE OFFEEDER CONNECTIONS (TYP)

MAX 4'-0" AFF

FUNNEL

1"

THERMOMETER (TYP.)

CONNECTION (TYP.)CAPPED HOSE

HOSE BIBB DRAIN CONNECTION

AS SHOWN ON PLANS (TYP.)HEADER SIZE TO BE FULL SIZE

PRESSURE GAUGE (TYP.)

SHUT-OFF VALVE (TYP.)

AIR COIL

AIR FLOW

M

AIR FLOW

M

3/4"

WITH CAP

3/4"

STRAINER

MANUAL AIR VENT

FOR COIL PULL EASE (TYP)SPOOL PIECE OR UNION, LOCATE

REDUCER OR INCREASER (TYP)

M

SUPPLY

M

FLOW

BALANCING SHUT-OFFVALVE (TYP.)

FLOW MEASURING DEVICE (TYPICAL)

2-WAY CONTROL VALVE (TYPICAL)

RETURN

UNION (TYPICAL)

FLOW

UP TO AND

INSULATION(AS REQUIRED)

INCLUDING 5"

AROUND PIPINGPROVIDE CLEARANCE

FOR PIPING TO BE USED

GANG HANGER

AND COLD PIPINGSHIELD FOR HOT360° PROTECTION

CLEVIS HANGER

HANGER ROD

SEE PIPINGPROTECTIONDETAIL

NOTE:

COLD PIPING HOT PIPING

(AS REQUIRED)INSULATION

(AS REQUIRED)

FOR PIPING TO BE USED

INSULATION

85% MAGNESIAOR KAYLO PIPE SHIELD

PROTECTION

INSULATION

ROD ROLLER HANGER

HANGER ROD

SEE PIPINGPROTECTIONDETAIL

OVER 5"

NOTE:

INSULATION FILLSADDLE WITH

ACCESS PANEL

CEILINGECH

BALL VALVE

GLOBE VALVE

X = SUCTION PRESSURE IN SECTION

X + 1 = MIN DROP

X/2 + 1 = MIN LEG

LEVEL OF DRAIN PANDISCHARGE BELOW

PITCH

DRAIN PANPLUG

DRAIN CONNECTIONCLEAN-OUT

VENT

DRAIN PAN2" ABOVE TOP OF

NOTE: IF MORE THAN 2COILS ARE STACKED,PIPE EACH COIL ASSHOWN.

LOCATE PIPE DROPS OUT OF THEWAY OF THE COIL PULL AREA

RETURNFLOW

FLOWSUPPLY

SHUT OFF VALVE

Y-STRAINER

UNION TYPICAL

CONCENTRIC REDUCER2-WAY CONTROL VALVE

BALANCING & SHUT-OFF VALVE

M

HOSE BIB DRAINCONNECTION W/ CAP

MANUAL AIR VENT

(TYPICAL)

APPLICATIONS:1.) AHU-1 TO 42.) VAV REHEAT COIL

(TYPICAL)

3.) FCU'S

ELECTRIC CEILING HEATERMOUNTED ABOVE CEILING

TLOW VOLTAGE WALLMOUNTED THERMOSTAT

RA

SA

PIPE

C

TUBING

FINISHED FLOOR

CONCRETE SLAB

GRADE

T

4" CONCRETE

WEATHERPROOF FUSEDDISCONNECT PER NEC

OUTDOOR CONDENSING UNIT

LIQUID & SUCTION LINES(RUN IN FURRED OUT WALLS)

ELECTRICAL WIRING (LINE VOLATGE)BY E.C.

SPACE THERMOSTATAND FIELD LOW

VOLTAGE WIRING.

FUSED DISCONNECT BY E.C.

SPLIT SYSTEM AIR HANDLER(VERTICAL OR HORIZONTAL)SEE FLOOR PLANS FOR CONFIGURATION

RUN 1" MIN. COND. DRAIN TO FLOOR DRAIN ORJANITORS SLOP SINKPUMP CONDENSATE IF UNIT IS BELOW (BY P.C.)

INDOOR UNIT

RL RS

OUTDOOR UNIT

POWER LEAD ANDDISCONNECT BY E.C.(TYP)

CONDENSATE DRAIN(SEE PLUMBING PLANS)

CONTROL WIRING BY M.C.

NOTE :OUTDOOR UNIT DCU-2 SERVES BOTHINDOOR UNITS DAH-2 & DAH-3.

M.C. TO VERIFY REFRIGERENTLINE SIZES WITH UNITMANUFACTURER

PROVIDE TRAP

LINES TO BE LEVEL ORPITCHED APPROXIMATELY1/4" PER LINEAR FOOTTOWARD COMPRESSOR.

POWER LEAD ANDDISCONNECT BY E.C.(TYP)

LINES TO BE LEVEL ORPITCHED APPROXIMATELY 1/4"PER LINEAR FOOT AWAY FROMEVAPORATOR.

SERVICEVALVES

REMOTE THERMOSTAT

FLOOR

THREADED RODS3/8"-16

STEEL FROM TOP OF JOIST.PROVIDE MISC. SUPPORT

8'-0" MIN

UNIT HEATER

10'-0" MAX

SUCTIONORLIQUID

CURB MFGR.PROVIDED BYFLEXIBLE BOOTS

NOTES:1.) ROOF OPENING & FLASHING BY G.C.

CONDUITELECTRICAL

CONDUITCONTROL

8" ROOF CURB

HOUSEKEEPING PAD

MOUNT UNIT ONBASE RAILS.

LOW VOLTAGE INTERLOCK

MANUFACTURER PORTALPLUS MODEL ER-2A.

2.) MANUFACTURER: PORTAL PLUS

FLOOR

5'-6"

(MAX

.)

MAV

SIGHT FLOWINDICATORP/T PORT (PETE'S PLUG)

1" MINIMUM

1" MINIMUM

BALL VALVE

COMBINATION BALL VALVE ANDAUTO FLOW REGULATOR

UNION

PRESSUREGAUGE

DRAIN VALVE W/ CAP

SIDESTREAMFILTER

SYSTEM PUMPS

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:34

:16 P

M M3.02

Mechanical Details

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 13: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

-EF

-L

EF

M

FS

AIR-COOLED CHILLER PIPING CONNECTION DETAIL (ACC-1)SCALE: N.T.S.

END-SUCTION PUMP DETAIL (CHWP-1,2/HWP-1,2)SCALE: N.T.S.

PUMP INERTIA BASE DETAILSCALE: N.T.S.

FLEXIBLE CONNECTION CONTROL PANEL

LEFT SIDE

HEAT TRACEEXPOSED PIPING(TYP)

MANUAL VENT

STRAINER

GATE VALVE (TYP)

THERMOMETER

FLOWSWITCH

PRESSURE GAUGE (TYP)

BALANCINGVALVE

PIPESUPPORT

UNION ORFLANGE (TYP)

FLEXIBLECONNECTION(TYP)

CHILLED WATERSUPPLY AND RETURN

ISOLATION VALVE

UNION OR FLANGE

REDUCER

SCREWED ENDY-STRAINER W/

(IF REQ'D)

W/GAUGECOCK

CHECK VALVE

PRESSURE GAUGE

CLOSE-COUPLEDHORIZONTALIN-LINE PUMP

GATE VALVE

VALVEBALANCING

ROOF

DUNNAGE STEEL

VALVE & HOSE COUPLINGY-STRAINER W/BLOW-OFF

FLEXIBLE CONNECTION

1" DRAIN LINE TO NEAREST FL. DR. (BY P.C.)

SUCTION DIFFUSER

SHAFT COUPLING GUARD

4" CONCRETE PAD

W/GATE VALVEPRESSURE GAUGE

END SUCTION BASEMOUNTED PUMP

DRIP PAN

WATER SUPPLY

BUTTERFLY VALVE

CHECK VALVE

VENTURI FLOW METER

BALANCING COCK

WATER RETURN

INERTIA BASESEE DETAIL

VIBRATION ISOLATORS

SCALE: 1/4" = 1'-0"

AIR HANDLING UNIT DETAIL (AHU 1 THRU 3)1M-3.03

4M-3.02

SCALE: NONE

ROOF EXHAUST FAN DETAIL (EF-1, 3 & 4)10M-3.01

SCALE: NONEVAV BOX DETAIL (VAV)5

M-3.01

SCALE: NONE

UTILITY SET EXHAUST FAN DETAIL (EF-2)8M-3.01 SCALE: NONE

INLINE EXHAUST FAN DETAIL (EF-5, 6, 7 & 10)9M-3.01

SCALE: 1/4" = 1'-0"

AIR HANDLING UNIT DETAIL (AHU 4)2M-3.03

3M-3.03

SCALE: NONE

IN-LINE PUMP DETAIL (HWP-3, 4)7M-3.01

CLOSE-COUPLED HORIZONTAL

6M-3.04

M

DIV 16CONDUIT BY & ROOF OPENING

OF OTHER DETAILNOTE FOR ANGLES

CURB TO NAILER STRIP.

ROOF

CURB BY UNIT MFG..12" HIGH PREFAB. INSULATED

ROOFING, RUN UP AND OVER

FAN FLASH CAP

(SEE PLANS FOR SIZE)EXHAUST DUCT

BACKDRAFT DAMPERLOW LEAKAGE

DISCONNECT BY UNIT MFG..INTEGRAL FAN ELECTRICAL

CURB NAILER STRIP.

TAKE OFF (TYPICAL)

CEILING DIFFUSERS

SUPPLY DUCTLOW PRESSURE AIR

VOLUME DAMPER. INSTALL BACK AT

(SEE PLANS FOR SIZE)

PRESSURE DUCT DROP TODIFFUSER MAXIMUM 5'

LOW PRESSURE BRANCH DUCTS (INTERNALLYINSULATED WITH 1" ACOUSTICAL LINER FOR FIRST

HOT WATER REHEAT COIL FACTORY MOUNTED

INSULATED FLEXIBLE LOW

(SEE PLANS AND SCHEDULESFOR TYPE) (TYPICAL)

SUSPEND UNIT FROM STRUCTURE ABOVE

MAXIMUM LENGTH = 3 DUCT DIA.

AIR SUPPLY DUCT, FOR SIZESEE DRAWINGS. NO FLEXIBLE

WITH HANGER RODS.

DUCTWORK ALLOWED.

(SEE PLANS AND SCHEDULES)VARIABLE AIR VOLUME BOX

MEDIUM PRESSURESUPPLY DUCT

BOOT TYPE FITTING

(SEE FLOOR PLAN

INSULATION(TYPICAL)

RUNOUT MEDIUM PRESSURE

FOR SIZE).SCHEDULEFOR SIZE

VAV

BOX. SEEINLET TO

DISCHARGE VIEW

F.C.

EXHAUST DUCT, SEE PLANS

PLAN VIEWTIER 1

SAOA

EA

PLAN VIEWTIER 2 - INLET END

RA

EXHAUST FAN

FILTER/MIXINGBOX

EXHAUST FAN

FILTER BOX

ANGLEFILTER

HEATWHEEL

HEATWHEEL

INLET/

VARIABLELENGTHACCESS

SUPPLYFAN

COOLINGCOIL

SUPPLYFAN

VFD

VFD

BDW

- C

OO

LIN

G

BDW

- H

EATI

NG

VFD

HEATINGCOIL OUTLET

VARIABLELENGTHACCESS

PLAN VIEWTIER 1

SUPPLYFAN

BDW

- H

EATI

NG

BDW

- C

OO

LIN

G

SUPPLYFAN

SAVFD

COOLINGCOIL

VARIABLELENGTHACCESS

HEATINGCOIL

FILTER/ECONOMIZER

OA

OA VFD

EA

RA

RETURNFAN

ALL EXTERIOR CHWS&R PIPING AND EVAPORATORBARREL ARE TO BE HEAT TRACED AND INSULATED.

ROOF JOIST

3/4" HANGER ROD

EXHAUST DUCT

TRANSITION

FLEXIBLECONNECTION (TYP)

ANGLE SUPPORTFASTENED TO FANCASING (TYP)

AIRFLOW

SPRINGISOLATOR(TYP)

ROOF

EXTERIORWALL

CEILING

SEE LOUVER SCHEDULEFOR SIZES

(INTAKE)

NOTES:1.)

SEE MANUFACTURER'S INSTALLATION DRAWINGSFOR EXACT LOCATION OF PIPE CONNECTIONS.

2.) (SEE HEATING COIL DETAIL ON DRAWING M-3.02)

MERV 13 CARTRIDGE FILTER

MERV 13 CARTRIDGE FILTER

FLOOR

4" HOUSEKEEPING PADVIBRATION ISOLATORS

EXTEND THROUGH PENTHOUSEROOF. SEE STACK DETAIL.

10"� DISCHARGESTACK

5' IN ALL DIRECTIONS.

WITH MERV 8 PREFILTER

INTERIM LIGHT (TYPICAL)WIRE TO SWITCH

UV LIGHT

WITH MERV 8 PREFILTER

INTERIM LIGHT (TYPICAL)WIRE TO SWITCH

UV LIGHTMERV 13 CARTRIDGE FILTERWITH MERV 8 PREFILTER

GROUT

FOUNDATIONABOVE SURFACE OFBOLT DO NOT EXTENDTIMES DIAMETER OFPIPE OR CONDUIT 3

FOR GROUTAFFORD GOOD HOLDFOUNDATION ROUGH TOLEAVE SURFACE OF

GROUTBOLT WHILE POURINGSTUFF WASTE AROUND

TO RECIEVE SPRINGS WHERE REQUIRED.2. CONCRETE GASE SHALL BE RECESSED

FOR TYPE REQUIRED.1. SEE VIBRATION ISOLATION SPECIFICATION

FLOORFINISHED

FOR HEIGHTSPECIFICATIONSCHECK

2"4"

SEE SPEC.VIBRATION ISOLATION 6"6"

PADCONCRETEREINFORCEDB.I. PAN10 GAUGE

ELBOW BASE SUPPORT

2" GROUT

<BOLTANGLE ANCHOR

IN PANREINFORCED CONCRETE

(ALL SIDES AND BOTTOM)10 GAUGE BLACK IRON PAN

NOTES:

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:34

:22 P

M M3.03

Mechanical Details

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 14: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

R

-

FCU

-

FCU

OTHER CONNECTIONS & CONTROLS.2.

RELIEF VALVEASME RATED PRESSURE

BOILER MANUFACTURER.1.

NOTES:

TO FLOOR DRAIN1" BOILER DRAIN, PIPE

1/2" MANUAL VENT

AQUASTAT

4" HOUSEKEEPING

LOW-WATER CUTOFF

FLOOR DRAINPIPE DISCHARGE TO

M

FLANGE OR UNION

PAD

SHUT-OFF VALVE(TYP.)

-

BLR

THERMOMETER

VENT PIPING

COMBUSTION AIR PIPING

SEE SPECIFICATIONS FOR

COORDINATE CONNECTIONS WITHWHERE ACCEPTABLE BY MANUFACTURER.

3. USE CONCENTRIC VENT TERMINATION KIT

HWR HWS

ISOLATION VALVEMOTORIZED CONTROL

DETAIL.4. SEE PLUMBING DRAWINGS FOR GAS CONNECTION

2M-3.04

1M-3.04

3M-3.04

4M-3.04

6M-3.04

5M-3.04

7M-3.04 8

M-3.049

M-3.04

10M-3.04

11M-3.04

12M-3.04

14M-3.04

15M-3.04

SCALE: NONE

CONDENSING HOT WATER GAS BOILER DETAIL (BLR-1)13M-3.01

RANKINE CYCLER CANOPY HOOD DETAILSCALE: N.T.S.

PLATE & FRAME HEAT EXCHANGER DETAIL (HX-1, 2 & 3)SCALE: N.T.S.

CEILING EXHAUST FAN DETAIL (EF-8)SCALE: N.T.S.

FAN COIL UNIT INSTALLATION DETAIL (FCU-1,2)SCALE: N.T.S.

DUST EXTRACTION ARM DETAILSCALE: N.T.S.

RADIANT HEAT ZONE PANEL DETAILSCALE: N.T.S.

ROUND SPIRAL DUCTWORK DIFFUSER DETAILSCALE: N.T.S. FUME HOOD EXHAUST FAN STACK DETAIL

SCALE: N.T.S.CONCENTRIC VENT (THRU WALL) DETAILSCALE: N.T.S.

EXTERIOR WALL LOUVER BLANK OFF DETAILSCALE: N.T.S.

ATOMIZING HUMIDIFIER DETAIL (H-1)SCALE: N.T.S.

SUPPLY FAN DETAIL (SF-1)SCALE: N.T.S.

FAN COIL UNIT INSTALLATION DETAIL (FCU-3)SCALE: N.T.S.

CLOSED LOOP CHEMICAL WATER TREATMENT SYSTEMSCALE: N.T.S.

45° MIN.

#36 GALVANIZED STEELSASH CHAIN

STEEL DECKING

1/8" DIAMETER"S" HOOK

36" X 60"

4"

ROOF

10"x10"

20 GAGE GALVANIZEDSHEET METAL

4" HOUSEKEEPING PAD

PRESSURE/TEMPERATUREPLUG (TYP.)

THERMOMETER (TYP.)

HWR

P/T

HWSLTHWR

P/T P/T

P/T

LTHWS

(TYPICAL)NEOPRENE PADS

SEE CONTROL DRAWINGS FOR ADDITIONAL PIPETAPS REQUIRED FOR ATC DEVICES.

BUTTERFLY VALVE (TYP.)

3/4" DRAIN3/4" DRAIN

RADIANT FLOOR HEATING LOOPHOT WATER LOOP

INOUT

IN

OUT

COMBINATION BALANCINGAND SHUT OFF VALVE

MODULATING CONTROLVALVE

FLOOR6" HIGH STAND

FLOOR

5' BOOM

10"� EXHAUST TRUNK

8"� STRUCTURAL ROOF STEEL

ROOF

6"� STEEL POLEATTACHED TO ROOFSTRUCTURE

MINIMUM TWO FEET FROMFLOOR TO MANIFOLD

CONDUIT ELBOWS

3/4" UV PROTECTED PEX

CONCRETE SLAB

STYROFOAM

STAINLESS STEEL MANIFOLD(SEE SCHEDULE FOR CIRCUIT QUANTITY)

OR SUB-FLOOR

LTHW

R

LTHW

S

RECESSED MANIFOLDENCLOSURE

INSULATED OUTSIDE AIROR EXHAUST AIR DUCTWORK

MOUNT DUCTWORK TOEXTERIOR LOUVER. FOLLOWSMACNA DUCT STANDARDS

BLANK OFF ANY UNUSED AREA OF THELOUVER NOT BEING UTILIZED. BLANK OFFWITH 4" RIGID INSULATION LINED ON BOTHSIDES WITH 22 GAGE SHEET METAL.

EXTERIOR WALL LOUVER IN PENTHOUSE.WALL LOUVER IS SUPPLIED AND INSTALLEDBY THE G.C.

DUCT INSULATION

INSULATED BLANK OFFPANEL WITH SHEETMETAL LINER.

SHEET METAL DUCT

CURING ROOM

ATOMIZING NOZZLE

REMOTE HUMIDITYSENSOR

CIVIL CONCRETE PREP

CONTROLLER

BALL VALVETYPICAL

COLD WATERSUPPLY

COMPRESSEDAIR

120V POWERSUPPLY

REGULATOR

SEE FLOOR PLAN FORLOCATION. COORDINATEHEIGHT A.F.F IN FIELD.

10' - 0"

14' ARM

EXHAUST GRILLE (SUPPLIED

CAULK BRICKVENT

6"�

WITH EXHAUST FAN)

6"�

FLEXIBLE CONNECTION

EF

-STRUCTURE ABOVE

(BY M.C.)

VIBRATION ISOLATOR

SUPPLY

MOUNT UP ABOVE CEILING.FAN COIL UNIT

FLEXIBLE CONNECTION

DUCT

E

WIRINGLOW VOLTAGE CONTROLELECTRICAL POWER &

VIBRATION ISOLATORSHANGING RODS WITH SPRINGACCESS PANEL

CONTROL BOX

HWSHWR

AUXILIARY DRAIN PAN UNDERPIPE CONNECTIONS TO UNIT

RETURN AIR DUCT

ROUND SPIRAL DUCT

AIRFLOW

AIRFLOW

INSTALL IN SPIRAL AT 90°VOLUME EXTRACTORANEMOSTAT ECO REGISTER WITH

ROOF DECK

(3 REQUIRED)GUY WIRE SUPPORTS

10'-0"

DISCHARGE

3/4" PRESSURE

TREATED PLYWOOD

ROOF CURB

14" HIGH

SHEET METAL COVER

1 1/2" DRAIN HOLE

10"∅ EXHAUST DUCT

APPLICATIONS

1. USED FOR COMBUSTION AIR AND VENTINGOF GAS BOILER (BLR-1)

BUILDING OVERHANG

BUILDING PROJECTION

AD

JOIN

ING

BU

ILD

ING

3 ' -0" MIN.

3 ' -0" MIN.

6 ' -0" MIN.

SINGLE LENGTH OFTYPE B VENTING

SCREENED EXHAUST CAP

AIR INLET GAURD

1 6 " M IN. 2 4" MAX.

2 "

2 " IF W AL L IS COM BUSTABL E

BRACKETCONCENTRICADAPTER BOX

THIMBLE

WALL 1" MIN. - 48" MAX.

SINGLE WALL VENTING &COMBUSTION AIR PIPE

M

MFGR. CONTRACTOR TO

(SIZE VARIES SEE PLANSROOF OPENING BY G.C.

WOOD BLOCKING (BY G.C.)

DECK

AND FLASH AS PER ROOFINGFURNISH. G.C. TO INSTALL

INSULATED CURB BY HOOD14" HIGH PREFABRICATED

ROOF INSULATION

ROOF MEMBRANEMIN

.14

"

DUCT THRU ROOF

SECURE FAN TOCURB WITH SCREWS

ROOFING MFGR FOR TYPE.

OR LAG BOLTS

MOTORIZED DAMPER BY UNIT MFGR.

AND SCHEDULES)ACTUATOR BY CONTROL VENDOR.

IH

MOTOR ENCLOSURE

2" WASHABLEALUMINUM FILTERS

APPLICATIONS:1.) HEATING ONLY

SUPPLY

MOUNT UP ABOVE CEILING.FAN COIL UNIT

FLEXIBLE CONNECTION

DUCT

E

WIRINGLOW VOLTAGE CONTROLELECTRICAL POWER &

VIBRATION ISOLATORSHANGING RODS WITH SPRINGACCESS PANEL

CONTROL BOX

HWSHWR

AUXILIARY DRAIN PAN UNDERPIPE CONNECTIONS TO UNIT

RETURN AIR DUCT

APPLICATIONS:1.) HEATING AND COOLING

CHWRCHWS

CORROSIONINHIBITOR

55 GALLON CHEMICALDRUMS4" CONCRETE PAD BY G.C.

BY DIV. 15

FLEXIBLE SUCTION HOSE

CONTROL PANEL(WALL MOUNTED)

ROUND ALL SHARP EDGES

1/16" PLATE WITH WALLBRACKETS FOR SUPPORT

CHEMICAL FEEDPUMP REFER TOSPECS FOR DETAILS

STOP AND INJECTIONASSEMBLY

120V-1PH, 60 HZ POWERLEAD BY DIV. 16

CONDUCTIVITY PROBE

STEEL CHEMICAL FEED PIPING

3/4"

LOCATE VALVES 5'-0"AFF. DISCHARGE PIPESTO FLOOR DRAIN

INOUT

120-1-60 POWERSUPPLY TO BLEEDVALVE BY DIV. 15

FLOW

CHWS/HWS/LTHWS

3-WAY DIVERTING VALE(BY ATC CONTRACTOR)

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:34

:28 P

M M3.04

Mechanical Details

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 15: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

PUMP SCHEDULE

TAGSERVICED

NOTESEQUIPMENT

HWP-1

TYPEHP RPM

VOLTS/PHASE

CONNECTIONS

SUCT. DISCH.MFR / MODEL

ELECTRICAL

HWP

CHWP-1 480

(GPM)FLOW

(FT.)HEAD

1,750 6" 5"

WEIGHT

565 B&G / 1510 5BC

FLUID

480/3225 75 7.50BASE MOUNTED 1,750 3" 2.5" 350 B&G / 1510 2-1/2BBWATER

HWP-2

67.46

75.58

%EFF.

1 & 2

EXPANSION TANK SCHEDULE

BLADDER

TAG

ET-1

TYPEHEIGHT

DIMENSIONS

DIAM.MFR / MODEL NOTESSYSTEM

TANK VOLUME(GAL)

ACCEPTANCE(GAL)

SYS.CONN.

21.3 11.3 29"16-1/4" 1/2" B&G / D-401/2" 1, 2 & 3CHILLED WATER

AIR SEPARATOR

AS-1

TAG MFR / MODEL

PENTHOUSE

LOCATION SIZE

5" 480

NOTESSYSTEM

CHILLED WATER LOOP

FLOWGPM

B&G / R-5F 1, 2, & 3

1 & 2

WEIGHT(LB)

263

DRAINCONN.

FACTORFOULING

AIR-COOLED WATER CHILLER SCHEDULE

TAG

(°F)(°F) (FT.)

CHILLED WATER

EWT WPDLWTREFRIG.

OPERATINGWEIGHT (LB)

EERTONS

CAPACITYELECTRICAL

MCA MOCPQTY.NOTES

PHASEVOLT /

ACC-1 YORK / YVAA0248CEV46BA200 2 54.0 44.0 11.7 0.00010 460/3 347 450 19.7R-134A 17,398.0 1 THRU 4

TYPE

COMPRESSORIPLV

11.3

TEMP (°F)AMBIENT

95.0

FLUID

30% EG

MFGR / MODELTOTALKW

212.8

LOCATION

ROOF - ON DUNNAGE STEEL

14,720

NOTES

AHU-1

TYPE

AIR FOILSECOND FLOOR

TAG

AHU- AIR HANDLING UNIT SCHEDULE

WEIGHT

UNIT CHILLED WATER COOLING COIL

MBHMBH

918.9 654.5

TOTAL SENSIBLE WBLAT

54.455.1

(FT)

17.2 198.1 45.0

GPMW.P.D.MAX

EWT WB

79.9 66.7 55.4

EATDB

EATDBLAT

LWT(FT/MIN)

499

F.V.MAX

(IN/w.g.)

0.50

A.P.D.MAX

(^F)(^F)(^F)(^F)

UNIT HEATING COIL

MBH

554.3

TOTAL

55.4

GPM

52.2 73.3

EATDB DB

LAT

(IN/w.g.)

0.06

A.P.D.MAX

(°F)(°F)2

ESPIN. H 0 HPS.P.

SUPPLY FAN

BHPTOTAL MTR. V/PH/HZ

2.50 7.88 40.39 50 1,42225,000

2

ESPIN. H 0 HPS.P.

EXHAUST/RETURN FAN

BHPTOTAL MTR. V/PH/HZ

1.00 460/3/603.84 20.27 25 1099

0.36

(INITIAL)

A.P.D.IN W.G. D.F.A.

(IN. W.G.)(SQ. FT)F.A.

(FT/MIN)

MAXF.V. DEPTH

PLEATED 0.2546.7 3.11 2"

1.

460/3/60

PROVIDE FACTORY MOUNTED & WIRED VARIABLE FREQUENCY DRIVES ON ALL SUPPLY & EXHAUST FANS WITH FUSED DISCONNECT.

LOCATIONUNIT

PENTHOUSE

HEAT RECOVERY WHEEL

S/A(db/wb)

WINTERO/A

(db/wb)(db/wb)O/A

SUMMER

(db/wb)S/A

AIRFLOWS (CFM)

O/AE/A EFFICIENT%

EFFICIENT%

23,750 25,000 92.0 / 74.0 79.9 / 66.7 69.51 9.0 / 8.0 52.2 /42.4 70.14

REQ'DCFMMIN.

JCI/ SOLUTION XTI-75x123

MFGR / MODEL

(LBS.)

UNIT

AHU-2

AHU-3

AHU-4

-

MOCP

100

MCA

90.0

MFS

150

MCA

47.5 4.6

LWT

160.0

EWT

180.0

V/PH/HZ

460/3/60

MOCP

15

MCA

2.13

IN.xIN. (# OF FILTERS)SIZE (QTY) / SIZE (QTY)

TYPE

PRE-FILTER

0.60

(INITIAL)

A.P.D.IN W.G. D.F.A.

(IN. W.G.) DEPTH

MERV-13 0.50 12"

EFF.

HIGH EFFICIENCY FILTER

MERV-8

EFF.

RIGID

TYPESERVEDUNIT

AHU-1

OUTSIDE AIR FILTER SCHEDULE

NOTES:1.2.3.

REFER TO AIR HANLING UNIT SCHEDULE FOR CORRESPONDING UNIT.PROVIDE 1 SET OF SPARE FILTERS FOR BOTH MERV-8 & MERV-13 FILTERS.CHANGE OUT CONSTRUCTION FILTERS PRIOR TO FINAL AIR BALANCING.

0.25PLEATED 0.2537.3 2.46 2" 0.38MERV-13 0.50 12"MERV-8 RIGIDAHU-2

PLEATED 2" MERV-13MERV-8 RIGIDAHU-3

NOTES

1 THRU 3

1 THRU 10

NOTES

2. EXTENDED LUBE LINES.3. PROVIDE LOW LEAKAGE SUPPLY & EXHAUST DAMPERS.4. PROVIDE 1 SPARE SET OF BELTS.

3"

5. PROVIDE CONDENSATE DRAIN TRAP FOR EACH COOLING COIL SECTION.

7. PROVIDE TIMED EXHAUST FROST CONTROL.8. REFER TO FILTER SCHEDULE FOR CORRESPONDING FILTER PERFORMANCE CHARACTERISTICS.9. PROVIDE LIGHTS IN SUPPLY FAN, EXHAUST FAN, ENERGY WHEEL AND COIL ACCESS SECTIONS. WIRE TO EXTERIOR SWITCH MOUNTED ON UNIT CASING.10. COOLING COILS ARE SELECTED FOR USE WITH 30% E.G.

6.

CONN.RTRN.SUPP./

10,826AIR FOILFIRST FLOOR CLASSROOMS 350.72.50 5.92 18.45 25 1,58815,0006,900 1.00 460/3/603.39 11.05 15 1,310460/3/60 14,250 15,000 92.0 / 74.0 79.5 / 66.4 71.86 9.0 / 8.0 54.0 / 43.5 72.71 JCI / SOLUTION-XTI-66x1085047.5 8028.8 460/3/60152.13

6,457AIR FOIL 504.8 357.2 54.555.09.4 109.2 45.0 80.0 67.0 55.2 487 0.54306.4 30.6 63.9 85.7 0.142.00 4.51 13.39 20 1,70313,5001,350 1.25 460/3/601.67 7.50 10 1,393460/3/60 - - - - - - - - JCI/ SOLUTION-XTI-57x9613,5004038.8 6019.3 6.8160.0180.0 ---3"

RPMFAN

RPMFAN

20x20(6)/24x20(9)

24x12(12)/24x20(4)

AIR-COOLEDSCREW

FIRST FLOOR LABS

CORRIDORS

25,000 7,500

15,000

13,500

RELIEF/INTAKE HOOD SCHEDULE

NOTES:

SERVICEDAREA

TAGROOF OPENING

CFM(FT/MIN)

VELOCITY MFGR / MODEL NOTES

1. FIELD PAINT- COLOR BY ARCHITECT.2. PROVIDE ALUMINUMIN BIRD SCEEN.

THROAT

(FT )AREA

THROAT

2

S.P.

(in wg)

3. ROOF OPENING AND INSTALLATION OF CURB BY G.C.4. PROVIDE ROOF CURB

RH-1 44 x 88 GREENHECK / FGR 1 THRU 626.899370.14925,200

RH

(W x H)

RH-2 48 x 60 GREENHECK / FGR 1 THRU 6207600.09815,200AHU-2

LOUVER SCHEDULE (INTAKE & EXHAUST)

TAG

L

SIZE (in) CFMFT/MIN

VELOCITYMFGR / MODEL NOTES

FTAREAFREE

2

S.P.(IN. W.G.)

0.25 0.2537.3 2.46 0.38 0.50 12"24x12(12)/24x20(4)

MFR / MODEL NOTES

VARIABLE FREQUENCY DRIVE SCHEDULE

TAG HPSYSTEMSERVED

VFD-1

VFD-2

VFD-3

460/3

VOLTS/PHASE

NOTES:1.2.

3.PROVIDE FUSED DISCONNECT SWITCHMANUAL TRANSFER BYPASS

AUXILIARY CONTROL TRANSFORMER

1, 2 & 3

EQUIPMENTSERVEDLOCATION

PENTHOUSE CHILLED WATER LOOP CHWP-1

1, 2 & 3CHWP-2

1, 2 & 3HEATING WATER LOOP HWP-1

ABB/ACH 550

ABB/ACH 550

460/3

460/3

CHILLED WATER LOOP

VFD-4 1, 2 & 3HEATING WATER LOOP HWP-2 460/3

SERVEDAREA

OUTSIDEAIRMIN.

OUTSIDEAIR

MAX.CFM

EXHUSTAIRMIN.

EXHUSTAIR

MAX.

EQUIPMENT SERVED

NOTES:1. PROVIDE PERIMETER FLANGE.2. PROVIDE BIRD SCREEN.

CHWP-2

WATER

30% E.G.

30% E.G.

50 15

PENTHOUSE

PENTHOUSE

PENTHOUSE

HEATING HOT WATER

CHILLED WATER LOOP

CHILLED WATER LOOP

HEATING HOT WATER

BASE MOUNTED

BASE MOUNTED

BASE MOUNTED

480/3225 75 7.50 1,750 3" 2.5" 350 B&G / 1510 2-1/2BB75.58 1, 2 & 3

480/3

480 1,750 6" 5" 565 B&G / 1510 5BC67.4650 15 480/3

RH-3 1 THRU 6AHU-3

IH-1 44 x 56 GREENHECK / FGR 1 THRU 617.117890.10613,500AHU-4

AHU-1

48 x 60 GREENHECK / FGR207600.09815,200

5. PROVIDE GALVANIZED STEEL HOUSING.6. PROVIDE ALUMINUM MESH INSECT SCREEN OVER THROAT.

NOTES:1. PROVIDE FACTORY MOUNTED AND WIRED FUSED DISCONNECT, STARTERS AND VFD'S.2. FILL SYSTEM WITH 30% E.G.3. INTERFACE PANEL (BACNET)

NOTES:1. INSULATE EXPANSION TANK.2. TANKS NOT SUBJECT TO L&I CLEARANCE REQUIREMENTS

(LESS THAN 100 GAL.)3. TANKS TO BE ASME RATED.

NOTES:1. ASME CONSTRUCTED.2. PROVIDE WITH STRAINER.3. FLANGED CONNECTIONS.

NOTES:1. FURNISH WITH PREMIUM HIGH EFFICIENCY DRIP PROOF MOTORS, COMPATIBLE FOR VFD'S.2. PUMPS TO BE BRONZE FITTED.

DESIGNGPM

528.5

MIN.GPM

300.0

SYSTEMVOLUME(GAL.)

73.0

CHWP

(FT)W.P.DMAX

(°F) (°F)

PENTHOUSE

PENTHOUSE

PENTHOUSE

10,826AIR FOIL 566.9 405.4 54.055.010.3 123.7 45.0 79.9 66.7 54.6 409 0.39350.7 35.1 54.0 76.2 0.042.50 5.92 18.45 25 1,58815,0002,500 1.00 460/3/603.39 11.05 15 1,310460/3/60 14,250 15,000 92.0 / 74.0 79.5 / 66.4 71.86 9.0 / 8.0 54.0 / 43.5 72.71 JCI / SOLUTION-XTI-66x10815,0005047.5 8028.8 15.0159.9180.0 460/3/60152.133"15,000

6,900

-

7,500

2,500

23,750

14,250

12,825

14,250

HWP-4

HWP-3 WATER

WATER

HOT WATER RADIANT INFLOOR HEATING INLINE

INLINE

277/114 35 3/4 1,750 1" 1" 55 B&G / 60 1x5-1/437.79 2

HOT WATER RADIANT INFLOOR HEATING 14 2 & 3

L-1 1 THRU 4GREENHECK/ESD-403AH-1 (EXISTING BUILDING)

L-2 1 THRU 4GREENHECK/ESD-4030.664860.04132016 x 16AH-2 (EXISTING BUILDING)

0.835740.05747518 x18

L-3 1 THRU 4GREENHECK/ESD-4030.535380.0528515 x 15AH-3 (EXISTING BUILDING)

73.0

WATERVOLUME(GAL.)

4. PROVIDE ELECTRICAL HEAT TRACING ON EVAPORATOR BARREL AND EXPOSEDPIPING. TIE INTO EMERGENCY GENERATOR.

AS-2 PENTHOUSE 4" 180HOT WATER LOOP B&G / R-4F 1, 2, & 3

BLADDERET-2 44.4 22.6 56-7/8"16-1/4" 1/2" B&G / D-401/2" 1, 2 & 3HEATING HOT WATER 516

3. PROVIDE 120V CONTROL DAMPER W/ END SWITCH4. PROVIDE INSECT SCREEN

L-4 1, 2 & 4GREENHECK/ESD-4030.665690.05637516 x 16EF-5,6,7

L-5 1 THRU 4GREENHECK/ESD-4031.155300.04961020 x 20EF-6,7

WEIGHT

(LBS.)

296

216

205

216

15

15

7.5

7.5

TAG TYPE AREA SERVED MANUFACTURER MODEL # VOLTS/PHASE

AMPS KW NOTES

EDH-1 SLIP-IN RANKINE CYCLER BERKO OT018031034YNY 12"X12" 208/1 1886.5

NOTES:1.2.

PROVIDE AIRFLOW SWITCHPROVIDE MAGNETIC SAFETY CONTACTORS

ELECTRIC DUCT HEATER SCHEDULE

1 THRU 6

SIZE

3.4.

PROVIDE FUSING PER NECPROVIDE 24V CONTROL TRANSFORMER

5. PROVIDE FUSED INTERLOCKING DISCONNECTPROVIDE SCR CONTROLLER6.

IH

AS-3 PENTHOUSE 2" 14LOW TEMPERATURE HOT WATER LOOP B&G / R-2N 1, 2, & 4

4. NPT CONNECTIONS

566.9 405.4 54.055.010.3 123.7 45.0 79.9 66.7 54.6 409 0.3935.1 54.0 76.2 0.04 15,000 15.0159.9180.0 3"

RADIANT HEAT SCHEDULEZONE

NOTE:

AREA (FT2)

RHZP-1 LEVEL 1 GALLERIES

RHZP-2 LEVEL 2 GALLERY LOUNGE

3,900

1,900

BTUH

87,781

42,765

GPM

9.4

4.6

AVERAGE

493'

481'

AREA SERVED

1.) PROVIDE RECESSED ENCLOSURE.2.) PROVIDE STAINLESS STEEL MANIFOLD.

HD (FT)

6.1

5.7

# CIRCUITS

8

4

CIRCUIT LENGTHCIRCUIT

12"

12"

SPACINGCIRCUIT

3/4"

3/4"

SIZE

1 & 2

1 &2

NOTES

TYPE

INTAKE

INTAKE

INTAKE

EXHAUST

INTAKE

BLADDERET-3 8.0 2.4 19-1/4"12" 1/2" B&G / D-151/2" 1, 2 & 3RADINAT INFLOOR 102

MECHANICAL EQUIPMENT SOUND POWER LEVELS

LOCATIONTAG

AHU-2

63HzSOURCE 1000Hz500Hz250Hz 2000Hz

RADIATED

125Hz 4000Hz 8000Hz

CLASS

II

S

S

S

AHU MANUFACTURER TO PROVIDE MOTOR HORSEPOWER AS SHOWN. REDUCTION IN MOTOR HORSEPOWER WILL NOT BE ACCEPTABLE.

0.36

(INITIAL)

A.P.D.IN W.G. D.F.A.

(IN. W.G.)(SQ. FT)F.A.

(FT/MIN)

MAXF.V. DEPTH

PLEATED 0.2546.7 3.11 2"

IN.xIN. (# OF FILTERS)SIZE (QTY) / SIZE (QTY)

TYPE

PRE-FILTER

0.60

(INITIAL)

A.P.D.IN W.G. D.F.A.

(IN. W.G.) DEPTH

MERV-13 0.50 12"

EFF.

HIGH EFFICIENCY FILTER

MERV-8

EFF.

RIGID

TYPESERVEDUNIT

AHU-1

RETURN AIR FILTER SCHEDULE

NOTES:1.2.3.

REFER TO AIR HANLING UNIT SCHEDULE FOR CORRESPONDING UNIT.PROVIDE 1 SET OF SPARE FILTERS FOR BOTH MERV-8 & MERV-13 FILTERS.CHANGE OUT CONSTRUCTION FILTERS PRIOR TO FINAL AIR BALANCING.

0.25PLEATED 0.2537.3 2.46 2" 0.38MERV-13 0.50 12"MERV-8 RIGIDAHU-2

PLEATED 2" MERV-13MERV-8 RIGIDAHU-3

PLEATED 2" MERV-13MERV-8 RIGIDAHU-4

NOTES

1 THRU 320x20(6)/24x20(9)

24x12(12)/24x20(4)

0.25 0.2537.3 2.46 0.38 0.50 12"24x12(12)/24x20(4)

0.31 0.2528.0 2.47 0.50 0.50 12"12x24(2)/24x24(6)

AHU-1

AHU-3

AHU-4

ACC-1

RADIATED

RADIATED

RADIATED

RADIATED

PENTHOUSE

PENTHOUSE

PENTHOUSE

PENTHOUSE

ROOF

NOTES: 1.) SOUND DATA TESTED IN ACCORDANCE WITH AHRI-260 (2001).2.) THE OVERALL A-WEIGHTED SOUND POWER LEVEL SHOWN IS FOR CASING RADIATED SOUND.

UVC EMMITER SCHEDULE

AHU-1

TAG

UV-1

EQUIPMENT SERVED# ROWSQUANTITY

3 3

MFGR / MODEL

277/1

NOTES

1

PER ROW ELECTRICALFROM COIL

12"(2) 42", (1) 36"9 STERIL-AIRE / DE361 VO DE421 VO25,000

CFM TOTAL FIXTURES

3.4

AMPSSIZE

NOTES:1. FILED INSTALLED BY UVC EMITTER SUPPLIER.

DISTANCE

OF ROWS

24"

CENTERLINE

AHU-2UV-2 2 2 115"(1) 62", (1) 36"4 STERIL-AIRE / DE361 VO DE621 VO15,000 1.830"

UV-3 115,000

UV-4 2 3 110"(1) 62", (1) 24"6 STERIL-AIRE / DE241 VO DE621 VO13,500 2.421"

AHU-3

AHU-4

277/1

277/1

2 2 15"(1) 62", (1) 36"4 1.830" 277/1

96.0 96.0 96.0 96.0 92.0 87.0 83.0 79.0

LWA

97.0

3. PUMPS HWP-2, HWP-4, CHWP-2 ARE STAND BY PUMPS.

1, 2 & 3

ABB/ACH 550

ABB/ACH 550

277/135 3/4 1,750 1" 1" 55 B&G / 60 1x5-1/437.79

1 THRU 10

1 THRU 10

1 THRU 10

1 THRU 3

1 THRU 3

1 THRU 3

1 THRU 3

1 THRU 3

STERIL-AIRE / DE361 VO DE621 VO

TAG TYPE AREA SERVED MANUFACTURER MODEL # NOMINALCFM

VOLTS/PHASE

MCA AUX. HEATKW

NOTES

SSAH-1

SSAH-2

SSAH-3

VARIABLE SPEED LAB 101

LAB 104

LAB 217

JOHNSON CONTROLS AVG36C

AVG24B

AVG24B

1200

800

800

208/1 18

13

13

85.32

62.6

62.6

208/1

208/1

NOTES:PROVIDE TWO (2) SETS OF FILTERS1.

2. PROVIDE 208/24 VOLT CONTROL XFMRPROVIDE CONDENSATE TRAP3.

4. PROVIDE HORIZONTAL GASKET KIT

SPLIT SYSTEM AIR HANDLER SCHEDULE (INDOOR UNIT)

1 THRU 4

TAG EQUIPMENT SERVED MANUFACTURER MODEL # HEATING CAP.@ 17°F DB (BTUH)

VOLTS/PHASE

MOCP NOTES

SSHP-1

SSHP-2

SSHP-3

SSAH-1

SSAH-2

SSAH-3

JOHNSON CONTROLS YZH03611(C) 18

18

18

4.2

4.0

4.0

36,000

24,000

24,000

208/1 25

20

20

NOTES:PROVIDE LIQUID LINE FILTER DRYER1.

2. PROVIDE HOUSEKEEPING PAD (4' CONCRETE)

SPLIT SYSTEM HEAT PUMP UNIT SCHEDULE (OUTDOOR UNIT)

1 THRU 5

YZH02411(C)

SEER COP

26,600

16,900

16,900

REFRIG.

R410A

R410A

R410A

1 THRU 4

1 THRU 4

1 THRU 5

1 THRU 5

JOHNSON CONTROLS

JOHNSON CONTROLS YZH02411(C)

HEATING CAP.@ 47°F DB (BTUH)

JOHNSON CONTROLS

JOHNSON CONTROLS

VARIABLE SPEED

VARIABLE SPEED

HEATING CAP.@ 17°F DB (BTUH)

36,000

24,000

24,000

26,600

16,900

16,900

HEATING CAP.@ 47°F DB (BTUH)

36,000

24,000

24,000

COOLING CAP.@ 47°F DB (BTUH)

WEIGHTLBS.

164

134

134

WEIGHTLBS.

275

275

275

MOCP

90

70

70

208/1

208/1

AMPS

16.6

12.3

12.3

PROVIDE AND FILL SYSTEM WITH R-410A REFRIGERANT.3.PROVIDE AND WIRE LOW VOLTAGE SPACE THERMOSTAT (24V).4.

PROVIDE 24V CONTROL POWER TRANSFORMER.5.

VFD-5 1, 2 & 3FUME HOOD EXHAUST EF-2 460/3PENTHOUSE 1/2 ABB/ACH 550

ET

AS

ACC

VFD

EDH

RHZP

UV

NOTES:1. FOR ALL EQUIPMENT SCHEDULED ON THIS DRAWING ; THE MANUFACTURER

AND MODEL NUMBER SHOWN ARE THE BASIS OF DESIGN.2. A FORMAL SUBMITTAL MUST BE SUPPLIED WITH ALTERNATE MANUFACTURER

PROPOSALS. SEE SPECIFICATIONS FOR ACCEPTABLE MANUFACTURERS.

SSAH

SSHP

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:59

:41 P

M M4.01

Mechanical Schedules

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 16: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

EXHAUST FAN SCHEDULE

SONES

PROVIDE GRAVITY OPERATED BACKDRAFT DAMPERS.NOTES:

EF

CFM

EF-2

EF-1

TAG TYPE SP(IN. H 0)2

HP VOLTAGE/PHASE

GREENHECK / GB-141-5

MFGR / MODELROOF/WALLOPENING

DRIVE REMARKS

PROVIDE 12" HIGH ROOF CURB.

830

1425 0.5 1/2

1/2

115/1 8.2

19.2

1,052 18.5"x18.5" BELT

BELTGREENHECK / 10-BISW-21-10-I-5460/31.33

TAG MAX. N.C.MAX. S.P. NOTES

GRILLE, REGISTER & DIFFUSER SCHEDULEMFG. MODEL

B

C

D

SERVICE CFM THROW COLOR

150-250A 15'-17'ANEMOSTAT BY ARCHITECTSUPPLY 0.06 1 & 2SLAD-T9-75

12"x12"

1.2.3.4.5.

PROVIDE BIRD SCREEN.PROVIDE NEOPRENE VIBRATION ISOLATORS.

1, 2 & 3

1, 4 & 6-

FANRPM

2,152

G

I

J

F

M

250-350 16'-20'SUPPLY 0.03 1, 2 & 4DP

SUPPLYDP

SUPPLYECO20

200-375 10'-13' 0.09 1, 2, & 4

300-420 8'-15' 0.11 1 & 5

SUPPLYCM-1P

RETURNS3VD

490-550 5'-13' 0.07

1, 2, & 3

12"� 24"�

1500-2050 - 0.02

S3VOD

300-700 - 0.02

EXHAUST

S3VOD

100-200 - 0.05

-

HYDRONIC UNIT HEATER SCHEDULE

DESCRIPTIONTAG

NOTES

UH-1

UH

MFG / MODELBTU/HRCFM NOTESLWTEWTGPMPHASEVOLTS/

UH-2

HORIZONTAL

HORIZONTAL

1400 61,000 6.1 180 160 115/1 VULCAN / HV-84 1 THRU 3

°F °F

450 17,400 1.8 180 160 115/1 VULCAN / HV-24 1 THRU 3

PROVIDE DISCHARGE AIR LOUVERS.1. NEMA TYPE-1 MANUAL STARTER2.

BOILER SCHEDULE

CONNECTIONS

RETURN

MBH RATING

OUTPUTEFF.TAG

INPUTFUELHP SUPPLY

ELECTRICAL

VOLT / PHCOMB. RLAMFG / MODEL NOTES

BLR-1

NOTES:

VENT

WATERCONTENT WEIGHT

(GAL)GPM EWT

(°F)LWT(°F) MOCPLOCATION

MECHANICAL ROOM

TYPE

CONDENSING

(LB)GAS

PROVIDE SIDEWALL CONCENTRIC VENT TERMINATION KIT.1.

2,500 2,300 92% - NAT. GAS 225 160 180 3" 3" 8" 9" 2" 480/3/60 10.2 15 161 2,560 LOCHINVAR / FBN2500 1 & 2

WALL HEATER SCHEDULE

1. FLUID - WATERNOTES:

BTU/HR

WH-1

TAG GPMVOLT/PHASE

MFG / MODEL NOTESLOCATION MOUNTINGCFM

BATTERY STORAGE 1.64 16,400 120/1 230/185 WALL RECESSED VULCAN / RW-1120-02 1 & 2

EWT

180

2. 2-SPEED FAN SWITCH

LWT

160

PROVIDE WITH BMS GATEWAY, CONDENSATE NEUTRALIZATION KIT AND STAINLESS STEEL VENT KITS.2.

MFGR / MODEL

VAV BOX SCHEDULE

TAG

VAV 1-1-1

VAV

SIZEMAX

REHEATRUNOUT NOTES

CFM CFMMIN

CFMSPDTOTAL

EWT

1,010 335 0.25 55 97.4 JCI / TSL-SINGLE DUCT 1 & 2

LAT°F

EAT°F

REHEARSAL STUDIO

UNITSIZE

10

AREASERVED

2.71803/4"

SYSTEM

AHU-1

GPM LWT

160

VAV 1-1-2 1,010 335 0.25 55 97.410 2.7180 160

VAV 1-2-1 860 290 0.19 55 100WOMEN'S ROOM & MEN'S ROOM 10 2.3180 160

VAV 1-3-1 1,700 570 0.2 55 100.3ELECTRICAL COMPUTER LAB 14 2.1180 160

VAV 1-4-1 1,575 525 0.17 55 100.3ELECTRICAL MICRO/COMM LAB 14 2.1180 160

VAV 1-5-1 1,180 395 0.19 55 101RL5 12 5180 160

VAV 1-6-1 780 260 0.16 55 101.9ELECT. LARGE EQUIPMENT STORAGE 10 2.1180 160

VAV 1-7-1 525 175 0.14 55 94STUDENT SELF SERVICE 8 1.2180 160

VAV 1-8-1 475 160 0.27 55 98.4WOOD/METAL SHOP 6 0.6180 160

VAV 1-9-1 475 160 0.27 55 98.46 0.6180 160

VAV 1-10-1 475 160 0.27 55 98.46 0.6180 160

VAV 1-11-1 1,525 510 0.3 55 96.4ELECT. AUTO/ROBOTICS LAB 12 6.6180 160

VAV 1-12-1 1,460 490 0.28 55 97.1ELECT. SENIOR PROJECT LAB 12 6.3180 160

VAV 1-13-1 1,375 460 0.25 55 98.2ELECT. GEN EE LAB 12 5.9180 160

VAV 1-14-1 1,490 500 0.29 55 96.712 6.5180 160

VAV 1-15-1 460 155 0.26 55 98.96 0.6180 160

VAV 1-16-1 485 165 0.28 55 97.86 0.6180 160

VAV 1-17-1 1,900 635 0.24 55 98.414 2.3180 160

VAV 2-1-1

VAV 2-2-1 990 330 0.24 55 97.6CIVIL STUDENT PROJECT LAB 10 2.7180 160

VAV 2-3-1 800 270 0.16 55 101.3WOMEN'S ROOM & MEN'S ROOM 10 2.2180 160

VAV 2-4-1 1,025 345 0.26 55 96.9ELECTRICAL POWER LAB 10 2.8180 160

VAV 2-4-2 1,025 345 0.26 55 96.910 2.8180 160

VAV 2-5-1 1,250 420 0.21 55 99.8CIVIL SOILS TEACHING LAB 12 5.4180 160

VAV 2-6-1 1,800 600 0.22 55 99.4CIVIL SURVEY 14 2.2180 160

VAV 2-7-1 1,025 345 0.26 55 96.950 SEAT CLASSROOM 10 2.8180 160

VAV 2-8-1 1,650 1,650 0.25 55 95.0CIVIL CONCRETE PREP 14 5.8180 160

VAV 2-9-1 1,025 345 0.26 55 96.9CIVIL CONCRETE ASPHALT LAB 10 2.8180 160

VAV 2-9-2 1,025 345 0.26 55 96.910 2.8180 160

VAV 2-10-1 925 310 0.22 55 98.8CIVIL STRUCTURES LAB 10 2.5180 160

VAV 2-10-2 925 310 0.22 55 98.810 2.5180 160

1,100 370 0.29 55 95.7STRENGTH OF MATERIALS LAB 10 3180 160

VAV 2-1-2 1,100 370 0.29 55 95.710 3180 160

VAV 4-1-1 1,525 510 0.3 55 96.4GALLERY & NORTH VESTIBULE 12 6.6180 160

VAV 4-1-2 510 0.3 55 96.412 6.6180 160

VAV 4-1-3 510 0.3 55 96.412 6.6180 160

VAV 4-1-4 510 0.3 55 96.412 6.6180 160

VAV 4-2-1 250 85 0.06 55 110.1CORRIDOR 4 0.3180 160

VAV 4-3-1 960 320 0.23 55 98.2GALLERY 10 2.6180 160

VAV 4-4-1 580 195 0.18 55 98.9CORRIDOR 8 0.9180 160

VAV 4-5-1 1,980 660 0.26 55 97.7UPPER GALLERY & STUDENT LOUNGE 14 2.4180 160

VAV 4-5-2 1,980 660 0.26 55 97.714 2.4180 160

VAV 4-6-1 310 105 0.09 55 106.1CORRIDOR 5 0.4180 160

VAV 4-7-1 625 210 0.21 55 97.6CORRIDOR 8 1180 160

NOTES:1. COLOR TO BE BAKED ENAMEL AS SELECTED BY ARCHITECT.2. COORDINATE LOCATION AND FRAME STYLES WITH ARCHITECTURAL REFLECTED CEILING PLANS.3. PAINT INSIDE OF DUCTS AT RETURN, EXHAUST, AND RELIEF GRILLES FLAT BLACK.4. PROVIDE SQUARE TO ROUND ADAPTERS FOR CEILING DIFFUSERS AS REQUIRED.

ASPHALT LAB

RESTROOM/JANITOR ROOF MOUNTED

UTILITY

NECKSIZE

PANELSIZE

TYPE/PATTERN

LAY-IN / 2-SLOT 20

AREASERVED

<20

23

27DUCT MOUNT

25

24SURFACE

21LAY-IN

<20SURFACE

<20

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-1

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-2

AHU-4

MAXWPD

EF-3 1350 1/2 9.1 BELTGREENHECK / GB-131-5115/10.35PENTHOUSE EXHAUST ROOF MOUNTED 14.5"x14.5"1,134 1, 2 & 3

RL4

RL3

ELECT. RL 1

ELECT. RL 2

ELECT. PHYSICS LAB

ELECT. SIGNAL INTEGRITY CENTER

EF-4 1350 0.35PENTHOUSE EXHAUST ROOF MOUNTED

VAV 4-5-3 1,980 660 0.26 55 97.714 2.4180 160

VAV 2-7-2 1,025 345 0.26 55 96.910 2.8180 160AHU-2

1,525

1,525

1,525

335

335

290

570

525

395

260

175

160

160

160

510

490

460

500

155

165

635

330

270

345

345

420

600

345

1,650

345

345

310

310

370

370

510

510

510

510

85

320

195

660

660

105

210

660

345

1.6

1.4

2.9

2.9

2

1.4

1.1

0.8

0.8

0.8

2.3

2.3

2.2

2.3

0.8

0.8

3.1

1.6

1.4

1.6

1.6

2.1

3

1.6

6.2

1.6

1.6

1.5

1.5

1.7

1.7

2.3

2.3

2.3

2.3

0.5

1.5

1

3.1

3.1

0.6

1

3.1

1.6

1.6

REHEARSAL STUDIO

STRENGTH OF MATERIALS LAB

ELECTRICAL POWER LAB

50 SEAT CLASSROOM

CIVIL CONCRETE ASPHALT LAB

CIVIL STRUCTURES LAB

GALLERY & NORTH VESTIBULE

GALLERY & NORTH VESTIBULE

GALLERY & NORTH VESTIBULE

UPPER GALLERY & STUDENT LOUNGE

UPPER GALLERY & STUDENT LOUNGE

UNIT MAXSPD

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

ROWS CIRCUITSWCOIL

CAPMBH

15.4

14.1

28

28

19.7

13.2

11

7.5

7.5

7.5

22.9

22.3

21.5

22.6

7.4

7.7

29.8

15.2

13.5

15.6

15.6

20.4

28.8

15.6

62.9

15.6

15.6

14.7

14.7

16.3

16.3

22.9

22.9

22.9

22.9

5.1

15

9.3

30.5

30.5

5.8

9.7

30.5

15.6

15.4

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

1

1

1

2

1

2

1

1

1

1

1

1

1

1

1

1

1

1

1

2

2

1

1

2

1

1

WH-2 STAIRS 2 1.64 16,400 120/1 230/185 1 & 2180 160

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

AHU-4

VAV 3-1-1 1,685 565 0.19 55 100.5120 SEAT CLASSROOM 14 2.1180 160

VAV 3-1-2 1,685 565 0.19 55 100.514 2.1180 160

VAV 3-1-3 1,685 565 0.19 55 100.514 2.1180 160

VAV 3-2-1 565 0.19 55 100.5120 SEAT CLASSROOM 14 2.1180 160

VAV 3-2-2 0.19 55 100.514 2.1180 160

VAV 3-2-3 0.19 55 100.514 2.1180 160

VAV 3-3-1 0.19 55 100.5120 SEAT CLASSROOM 14 2.1180 160

VAV 3-3-2 0.19 55 100.514 2.1180 160

VAV 3-3-3 0.19 55 100.514 2.1180 160

565

565

565

565

565

1,685

1,685

1,685

1,685

1,685

1,685

565

565

565

565

565

565

565

565

565

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

120 SEAT CLASSROOM

120 SEAT CLASSROOM

120 SEAT CLASSROOM

120 SEAT CLASSROOM

120 SEAT CLASSROOM

120 SEAT CLASSROOM

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

27.8

27.8

27.8

27.8

27.8

27.8

27.8

27.8

27.8

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

AHU-3

AHU-3

AHU-3

AHU-3

AHU-3

AHU-3

AHU-3

AHU-3

AHU-3

1/2"

EF-5 75 1/2 8.0 BELTGREENHECK / BSQ-70-5115/10.5 1 & 4ELEVATOR MACHINE ROOM INLINE -1,216

EF-6 375 1/2 8.2 BELTGREENHECK / BSQ-90-5115/10.5BUILDING MECHANICAL ROOM INLINE -1,239

EF-7 610 1/2 10.5 BELTGREENHECK / BSQ-90-5115/10.5BUILDING ELECTRICAL ROOM INLINE -1,465

1 & 4

1 & 4

FLA

9.8

-

9.8

9.8

9.8

9.8

ATOMIZING HUMIDIFIER SCHEDULE

1. PROVIDE WALL MOUNT CONTROLLERNOTES:H-1

TAGCAPACITY VOLT/

PHASEMFG / MODEL NOTES

2. PROVIDE DIGITAL WALL MOUNT HUMIDISTAT

LOCATION

CONCRETE CURING 30.0 120/1/60 NORTEC / MINI 1 1, 2 & 3

3. PROVIDE WATER FILTER CARTRIDGE AND FILTER.

LBS/HR. KW

0.02

WEIGHT(LBS.)

94

179

85

92

94

94

ELECTRIC CEILING HEATERS

1. PROVIDE T-BAR FRAME KIT.NOTES:

ECH-1

TAGVOLT/PHASE

MFG / MODEL NOTES

2. PROVIDE WALL MOUNTED LOW VOLTAGE THERMOSTAT.

LOCATION AMPS

NEW ENTRY 102 208/1 17.3 BERKO / QFF4804 1, 2 & 3

KW

4.8

BTU/HR

16,382

WEIGHT

23

LBS.

EF-8 94 80W 2.0 DIRECTGREENHECK / SP-B110115/10.5BATTERY STORAGE ROOM CEILING 8.125"x7.75"950 1, 4 & 51.1 15

PROVIDE BRICK VENT

EF-9 750 1/2 7.0 BELTGREENHECK / CUBE-101-5115/10.5RANKINE CYCLER ROOF MOUNTED 14.5"x14.5"1,338 1, 2 & 35.4 94

PLATE & FRAME HEAT EXCHANGER SCHEDULE

NOTES:

TAG MFR / MODEL

1. PROVIDE FLOOR STAND

NOTES

B&G/P22BY5434 1 & 2

LOCATION

PENTHOUSEHTX-1

HOT SIDE

278.6 190200

SURFACE# PLATES

34 89.6

AREA(SQ. FT.)

0.9 1,042

HOLD-UPVOLUME

(FT )3WEIGHT

(LBS) GPM EWT LWT

WATER

FLUID

COLD SIDE

138.2 180160

GPM EWT LWT

WATER

FLUID

23.62 20.5

WIDTH(IN)

LENGTH(IN)

51

HEIGHT(IN)

DIMENSIONS

HTX-2

B&G/P4BY5448 1HTX-3 14.3 16018013 4.7 0.0 86 WATER 14.1 125105 WATER9.84 8.5 19

PENTHOUSE

PENTHOUSE

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

RETURN

EXHAUST

S3VD

18"x18"

12"x10"

24"x48"

22"x22"

6"x6"

8"x8"

24"x24"

24"x24"

13-9/16"x11-3/4"

25-13/16"x29-13/16"

24"x24"

7-13/16"x7-13/16"

9-13/16"x9-13/16"

LAY-IN / 2S

LAY-IN / 4S

DUCT MOUNT

SURFACE 490-550 0.05

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

5. PROVIDE DIVERTING DAMPER.

1, 2, & 3

1, 2, & 3

1, 2, & 3

3-5/16"x48" 4-3/4"x48"

TAG

NOTES:

SEERCOOLING

MBHCAPACITY

INDOOR UNIT

V/PH/HZ

DAH-1

WEIGHT

DUCTLESS SPLIT SYSTEM AIR CONDITIONING SYSTEM SCHEDULE

1.

3.4.

5.SYSTEM COOLING CAPACITY BASED ON 80/67°F EAT ON EVAPORATOR AND 95°F AMBIENT AIR ON OUTDOOR UNIT.PROVIDE LOW AMBIENT WIND BAFFLE AND FAN CYCLE SWITCH FOR FAN CONTROL DOWN TO 0°F AMBIENT AIR TEMPERATURE.PROVIDE INVERTOR DUTY COMPREESSORPROVIDE AND WIRE REMOTE WIRED THERMOSTAT.

HEATING

MBHCAPACITY

MCA TAG V/PH/HZ MCAMFG. / MODEL MFG. / MODELCOMP. REFRIG.SERVICETYPE CFM

PROVIDE WALL MOUNTING BRACKET.2.

NOTESOUTDOOR UNIT

BREAKER

COOLING ONLY T106 328 115/1/60 1.2 MITSUBISHI/MS-A09WA 9.5 - 13.0 DCU-1 115/1/60 1 R410A 14.0 20 78LBS. MITSUBISHI/MU-A09WA 1 THRU 9

6. PROVIDE FIELD INSTALLED CONDENSATE PUMP KIT. FIELD INSTALLED.7. MOUNT CONDENSING UNIT A MINIMUM OF 14" ABOVE ROOF SURFACE.8. MECHANICAL CONTRACTOR TO VERIFY REFRIGERANT PIPE SIZES WITH UNIT MANUFACTURER.

EF-10 1,650 1 17.6 BELTGREENHECK / QEI-12-I-10460/31.8CIVIL CONCRETE PREP DUST EXTRACTION INLINE -2,098 1 & 41.7 219

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSL-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

JCI / TSS-SINGLE DUCT

RUN-OUTSIZE

8"�

10"�

10"�

-

12"�

-

-

-

-

1/2 115/1 9.8 9.1 BELTGREENHECK / GB-131-514.5"x14.5"1,134 1, 2 & 385

SUPPLYDP 50 - 70 5'-6' 0.02 1, 2, & 4<20ANEMOSTAT 6"x6" 24"x24" LAY-IN / 4S BY ARCHITECT6"�

6.7

PRESSURE

2.9

DROP(PSI)

1.8

PRESSURE

3.2

DROP(PSI)

N

FLUID - WATER3.

9. FURNISH AND INSTALL R-410A REFRIGERANT. FILL SYSTEM.

FAN COIL UNIT SCHEDULESUPPLY FAN

TAG

HEATING PERFORMANCE

HEATINGMBH

EATDB°F

LATDB°F

EWT°F GPM WPD

FT

COOLING PERFORMANCE 30% ETHYLENE GLYCOL

SMBHEATDB°F

EATWB°F

LATDB°F

LATWB°F

EWT°F

LWT°F GPM WPD

FT

ELECTRICAL DATA

MCAMAX

FILTER%

MFR / MODEL

TMBH EFFICIENCYESPIN. WG FUSE

HIGH

LWT°F

NOTES

FCU-1 15.7 126 180 160 - - - - - - - - - 115/1 0.8 JCI/FHP20

FCU-2

FCU-3

WIDTHLENGTH

29 30 66

PHYSICAL DATA

HEIGHT

10

WEIGHT(IN.) (IN.) (IN.) (LBS)

0.8 0.9

FANSPEED

1/30

HP

250

180 45 55

AREA SERVED

SOUTH VESTIBULE

NORTH VESTIBULE

CONCRETE CURING ROOM

0.3

CFM

1

-

120/1

VOLTS/ PHASE

HIGH

15

NOTES:1. PROVIDE SECONDARY DRAIN PAN WITH CONDENSATE OVERFLOW

SWITCH FOR FIELD INSTALLATION.2. CONNECTION SIZES TO BE VERIFIED WITH MANUFACTURER.3. CONTROLS PROVIDED, MOUNTED, AND WIRED BY ATC VENDOR.4. PROVIDE CONTROLS ENCLOSURE.

1/3 IEC/HBD127.2 15900 37.5 37 29621.560

69

69.970150 36.6 12.3 57.5 57.5 62.4 7.336.1 96.7 8

1 THRU 5

CONFIGURATION

CONCEALED

CONCEALED

HIGH 15.7 126 180 160 - - - - - - - - - 115/1 0.8 JCI/FHP2029 30 66100.8 0.91/30250 0.3 - 1569CONCEALED

E

H

K

L

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ANEMOSTAT

ECO20

S20H

S30H

SLAR-FS-100

SUPPLY

SUPPLY

RETURN

RETURN

14"x6"

14"x8"

14"x8"

6.5"x48"

15-9/16"x7-3/4"

15-13/16"x9-13/16"

15-13/16"x9-13/16"

7-1/2"x48"

DUCT MOUNT

SURFACE

SURFACE

LAY-IN/THREE SLOT

150-200

200-270

200-270

640-720

-

-

-

-

9'-11'

14'-16'

0.05

0.02

0.06

0.06

<20

<20

25

23

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

BY ARCHITECT

1 & 5

1

1 & 3

1 & 2

°F °F

B&G/P22BY5434 1 & 2278.6 19020034 89.6 0.9 1,042 WATER 138.2 180160 WATER23.62 20.5 51 6.7 1.8

S20H 22'-25' <20ANEMOSTAT SUPPLY 16"x10" 17-13/16"x11-13/16" SURFACE 400-450 0.04 BY ARCHITECT 1-P

S30H - 37ANEMOSTAT RETURN 24"x12" 25-13/16"x13-13/16" SURFACE 800-900 0.10 BY ARCHITECT 1 & 3-Q

STANDARDTHROWAWAY

STANDARDTHROWAWAY

STANDARDTHROWAWAY

NOZZLESQTY. CAPACITY AIR FLOW WATER FLOW

2 15LBS/HR 1.8 SCFM 2 G/HR

UH-3 HORIZONTAL 450 17,400 1.8 180 160 115/1 VULCAN / HV-24 1 THRU 3

LOCATIONS

PENTHOUSE 300

MECH ROOM M108

ELEC ROOM P108

WH-3 STAIRS 3 1.64 16,400 120/1 230/185 1 & 2180 160

SERVICE

BUILDING HEAT

BUILDING HEAT

LOW TEMPERATURE HEAT

2. HTX - 1 & 2 (SIZED TO 60% OF LOAD)

3. PROVIDE CONTROL POWER TRANSFORMER (208V/24)

PIPE

(ID)

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1 & 2

1. PROVIDE HOT WATER COIL ACCESS PANELNOTES:

2. PROVIDE CONTROLS ENCLOSURE

WALL RECESSED

WALL RECESSED

VULCAN / RW-1120-02

VULCAN / RW-1120-02

UH-4 HORIZONTAL 450 17,400 1.8 180 160 115/1 VULCAN / HV-24 1 THRU 3JAN'S STOR. J115

UH-5 HORIZONTAL 450 17,400 1.8 180 160 115/1 VULCAN / HV-24 1 THRU 3LOAD. DOCK 115

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

5. PROVIDE 115V/24V CONTROL POWER TRANSFORMER.

1 THRU 5

1 THRU 5

1

1/2"

1/2"

1/2"

1/2"

1/2"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

SUPPLY FAN SCHEDULE

SONES

PROVIDE STANDARD - 1 IN WASHABLE ALUMINUM FILTERS.

NOTES:

SF

CFM

SF-1

TAG TYPE SP(IN. H 0)2

HP VOLTAGE/PHASE

GREENHECK / TCBRS-1-09-4

MFGR / MODELROOF/WALLOPENING

DRIVE REMARKS

PROVIDE 12" HIGH ROOF CURB.

750 0.5 1/4 208/3 10.5 1,743 16"x16" BELT

1.2.

3.4.PROVIDE WITH SPARE BELTS. STEEL CONSTRUCTION.

1 THRU 4

AREASERVED

ROOF MOUNTED

FANRPM

FLA

-

WEIGHT(LBS.)

197RANKINE CYCLER

PROVIDE INVERTER DUTY MOTOR6.

NOTES:1. FOR ALL EQUIPMENT SCHEDULED ON THIS DRAWING ; THE MANUFACTURER

AND MODEL NUMBER SHOWN ARE THE BASIS OF DESIGN.2. A FORMAL SUBMITTAL MUST BE SUPPLIED WITH ALTERNATE MANUFACTURER

PROPOSALS. SEE SPECIFICATIONS FOR ACCEPTABLE MANUFACTURERS.

BLR

WH

-H

-ECH

HTX

DAH DCU

FCU

Page 17: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

P

P

P

4" HIGH TEMPERATURE HOT WATER (200°F)FROM CAMPUS BOILER PLANT

CONDENSING GASBOILER

4" HIGH TEMPERATURE HOT WATER (200°F)FROM CAMPUS BOILER PLANT

SCALE: N.T.S.

HEATING HOT WATER PIPING SYSTEM SCHEMATIC (PLANT LEVEL)1M-5.01

SCALE: N.T.S.

CHILLED WATER PIPING SYSTEM SCHEMATIC (PLANT LEVEL)2M-5.01

CHECK VALVE

5'-6"

(MAX

.)

MAV

3/4" MINIMUM

3/4"

(N.O.) (N.O.)

(N.C.)

(N.C.)

(N.C.) (N.C.)

(N.O.)

(N.O.)

1

2

4

5

(N.O.)

7

8

9

PENTHOUSE WALL

10

11

TO DRAIN

FILL LINE12 13

14

1415

M

16

17

181"

1"

1"

1"1"

3

3

3

6

(N.O.)

19

20

21

22

23

(N.O.) (N.O.)

1"1"

24

24 24

25

444 4

21

26

(N.C.)

1"

3 1/2" FILLCAPOPENING(N.C.)

1" MINIMUM

VALVE WITHMEMORY STOPS

SIGHT FLOWINDICATOR

V-1A V-3A

V-4A

V-6A V-7A

V-8A

V-9A

V-5A

V-2A

PRESSURE GAUGEW/ NEEDLE VALVE

P/T PORT (PETE'S PLUG)

1" MINIMUM

1" MINIMUM

V-10A V-11A V-12A

V-13A

CHECK VALVE

3 1/2" FILLCAPOPENING(N.C.)

FLOOR

5'-6"

(MAX

.)

MAV

1" MINIMUM

VALVE WITHMEMORY STOPS

3/4" MINIMUM

3/4"

SIGHT FLOWINDICATOR

V-1A V-3A

V-4A

V-6A V-7A

V-8A

V-9A

V-5A

V-2A

(N.O.) (N.O.)

(N.C.)

(N.C.)

(N.C.) (N.C.)

(N.O.)

(N.O.)

1

1

2

2

3

4

4

5

5

6

(N.O.)

AIR COOLEDCHILLER

7

7

8

8

9

9

MECHANICAL ROOM WALL

10

11

12

13

14

10

11

TO DRAIN

FILL LINE12PRESSURE GAUGE

W/ NEEDLE VALVE13

14

WHERE PSU VALVE SPECIFICATION DICTATES THAT BUTTERFLY VALVES MUST BE USED BASEDUPON PIPE SIZE, PROVIDE HIGH PERFORMANCE BUTTERFLY VALVES ONLY WHERE PIPING EXITSMECHANICAL ROOM. ALL OTHERS IN HOT WATER SYSTEM SHOULD BE STANDARD BUTTERFLYVALVES.

AIR CHARGING VALVE. DRY TANK FILL VALVE PRESSURE (PSIG) IS DETERMINED BY THEFOLLOWING EQUATION:P=[(0.433 X VERTICAL DISTANCE IN FEET FROM SYSTEM HIGHPOINT DOWN TO TANK CENTERLINE) +4]

SAFETY PRESSURE RELIEF VALVE - PIPED TO FLOOR DRAIN. SELECT RELIEF VALVE TO PREVENTSYSTEM PRESSURE FROM RISING MORE THAN 10% ABOVE THE MAXIMUM ALLOWABLE WORKINGPRESSURE OF THE SYSTEM COMPONENTS, TAKING INTO ACCOUNT THE EFFECT OF STATIC HEAD.NOT REQUIRED AT THIS LOCATION IF SAFETY PRESSURE RELIEF VALVE IS BEING PROVIDEDELSEWHERE IN THE SYSTEM TO MEET PA L&I REQUIREMENTS.

15

15

M

16

16

SIDE STREAM BAG FILTER W/ BOLT-ON TOP. FILTER FLOW RATE FOR A GIVEN SYSTEM SHALL BETHAT REQUIRED TO PROVIDE EIGHT (8) TOTAL WATER SYSTEM VOLUME CHANGES PER DAY.DESIGNER SHALL UTILIZE THE FOLLOWING EQUATION:

BAG FILTER FLOW (GPM) = [(TOTAL SYSTEM VOLUME X 8) / 1440]

FOR SIDESTREAM FLOWS UP TO 25GPM, USE #BFN11 BY FILTER SPECIALIST INC. GASKETS RATEDFOR 230°F MINIMUM. CARBON STEEL VESSEL. 30 MICRON BAG FILTER. 1-1/2" FLANGED SIDE INLETAND BOTTOM OUTLET. FOR HIGHER SIDESTREAM FLOW APPLICATIONS, SPECIFY A LARGER BFNSERIES VESSEL. FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.

17

17

PRESSURE GAUGE W/ ISOLATION COCKS

SIZE FOR 4 FOOT PER SECOND MAXIMUM VELOCITY AT DESIGN FLOW.

DRAIN VALVE (N.C.) WITH MALE HOSE THREAD END.

FLOW DESIGN MODEL AC COMBINATION BALL VALVE, AUTOFLOW REGULATOR, AND UNION. SIZEFOR REQUIRED SIDESTREAM BAG FILTER FLOW.

FOR SYSTEMS HAVING A TOTAL VOLUME GREATER THAN 500 GALLONS, INCREASE SIZE OFMAKE-UP SYSTEM COMPONENTS AS NEEDED TO ALLOW FOR A TOTAL SYSTEM FILL TIME OFUNDER 2 HOURS.

SPIROVENT AIR/DIRT SEPARATOR. AUTOMATIC AIR VENT INCLUDED WITH UNIT. SELECT BASEDUPON MANUFACTURER'S FLOW VELOCITY GUIDELINES.

SEE TYPICAL AIR COOLED CHILLER PIPING DETAIL

PRESSURE REDUCING VALVE. PRV SETTING (PSIG) IS DETERMINED BY THE FOLLOWING EQUATION:P=[(0.433 X VERTICAL DISTANCE IN FEET FROM PRV TO SYSTEM HIGHPOINT) + 4]

REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER WITH OPEN AIR GAP

PROVIDE SAFETY PRESSURE RELIEF VALVE AT THIS LOCATION BETWEEN PRESSURE VESSEL AND FIRST ISOLATION VALVE IFPRESSURE VESSEL CAPACITY IS GREATER THAN OR EQUAL TO 120 GALLONS (PA L&I REQUIREMENT). PRESSURE VESSEL MUSTBE ASME CERTIFIED IF GREATER THAN OR EQUAL TO 120 GALLON CAPACITY. SELECT RELIEF VALVE TO PREVENT SYSTEMPRESSURE FROM RISING MORE THAN 10% ABOVE THE MAXIMUM ALLOWABLE WORKING PRESSURE OF THE SYSTEMCOMPONENTS, TAKING INTO ACCOUNT THE EFFECT OF STATIC HEAD, PIPE TO FLOOR DRAIN.

SEE TYPICAL PUMP PIPING DETAIL

5/8" NEPTUNE T-10 DIRECT READ WATER METER

CHEMICAL POT FEEDER. NEPTUNE MODEL #DBF-2HP. FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.

SPIROVENT AIR/DIRT SEPARATOR SHOULD BE PERIODICALLY BLOWN DOWN THROUGH THE BAG FILTER FOR ABOUT 10 SECONDSONCE EVERY 4 WEEKS. THIS SHALL BE ACCOMPLISHED BY FULLY CLOSING V-5A, FULLY OPENING V-4A, AND PARTIALLY CLOSINGV-3A UNTIL FLOW IS DETECTED THROUGH THE BAG FILTER SIGHT FLOW INDICATOR. THIS IS THE POINT WHERE THE MEMORYSTOPS ON V-3A SHOULD BE TIGHTENED TO PREVENT THE VALVE FROM BEING CLOSED ANY FURTHER IN THE FUTURE. ONCEBLOWN DOWN, THE VALVE POSITIONING DESCRIBED ABOVE SHOULD BE REVERSED.

PRESSURE GAUGE WITH NEEDLE VALVE

EXPANSION TANK (FIXED OR REPLACEABLE BLADDER TYPE)

B&G #87 AUTOMATIC AIR VENT

FLOW DESIGN MODEL AC COMBINATION BALL VALVE, AUTOFLOW REGULATOR, AND UNION. SIZE FOR 2GPM.

COUPON RACK. GE PART #2032806. 304SS, 1"NPT, WITH 4 COUPON HOLDERS.

JOHN C. ERNST CO. LOW PRESSURE, DOUBLE WINDOW, THREADED, BRONZE WITH PADDLE WHEEL INDICATOR.MODEL #138P. MATCH PIPE SIZE.

UNDERSLUNG CONNECTION TO CREATE THERMAL TRAP (12" MIN. DROP)

TAP FOR FUTURE AUTOMATED CHEMICAL INJECTOR

18

18

P/T PORT (PETE'S PLUG)

1"

1"

1" MINIMUM

1" 1" MINIMUM

1"1"

3

3

3

6

V-10A(N.O.)

19

19

20

20

2121

22

23

22

23V-11A(N.O.)

V-12A(N.O.)

1"1"

2424

24 24

2525

444 4

21

26

V-13A(N.C.)

1"

26

ACC-1

28HWP-1

HWS

HWR

HTHWR

BLR-1

28

HWS

HWR

27

HWP-2

6"

6"

CHWP-1

CHWP-2

1

2

3

4

5

6

7

8

9

10

11

12

13

14WHERE PSU VALVE SPECIFICATION DICTATES THAT BUTTERFLY VALVES MUST BE USED BASEDUPON PIPE SIZE, PROVIDE HIGH PERFORMANCE BUTTERFLY VALVES ONLY WHERE PIPING EXITSMECHANICAL ROOM. ALL OTHERS IN HOT WATER SYSTEM SHOULD BE STANDARD BUTTERFLYVALVES.

AIR CHARGING VALVE. DRY TANK FILL VALVE PRESSURE (PSIG) IS DETERMINED BY THEFOLLOWING EQUATION:P=[(0.433 X VERTICAL DISTANCE IN FEET FROM SYSTEM HIGHPOINT DOWN TO TANK CENTERLINE) +4]

SAFETY PRESSURE RELIEF VALVE - PIPED TO FLOOR DRAIN. SELECT RELIEF VALVE TO PREVENTSYSTEM PRESSURE FROM RISING MORE THAN 10% ABOVE THE MAXIMUM ALLOWABLE WORKINGPRESSURE OF THE SYSTEM COMPONENTS, TAKING INTO ACCOUNT THE EFFECT OF STATIC HEAD.NOT REQUIRED AT THIS LOCATION IF SAFETY PRESSURE RELIEF VALVE IS BEING PROVIDEDELSEWHERE IN THE SYSTEM TO MEET PA L&I REQUIREMENTS.

15

16

SIDE STREAM BAG FILTER W/ BOLT-ON TOP. FILTER FLOW RATE FOR A GIVEN SYSTEM SHALL BETHAT REQUIRED TO PROVIDE EIGHT (8) TOTAL WATER SYSTEM VOLUME CHANGES PER DAY.DESIGNER SHALL UTILIZE THE FOLLOWING EQUATION:

BAG FILTER FLOW (GPM) = [(TOTAL SYSTEM VOLUME X 8) / 1440]

FOR SIDESTREAM FLOWS UP TO 25GPM, USE #BFN11 BY FILTER SPECIALIST INC. GASKETS RATEDFOR 230°F MINIMUM. CARBON STEEL VESSEL. 30 MICRON BAG FILTER. 1-1/2" FLANGED SIDE INLETAND BOTTOM OUTLET. FOR HIGHER SIDESTREAM FLOW APPLICATIONS, SPECIFY A LARGER BFNSERIES VESSEL. FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.

17

PRESSURE GAUGE W/ ISOLATION COCKS

SIZE FOR 4 FOOT PER SECOND MAXIMUM VELOCITY AT DESIGN FLOW.

DRAIN VALVE (N.C.) WITH MALE HOSE THREAD END.

FLOW DESIGN MODEL AC COMBINATION BALL VALVE, AUTOFLOW REGULATOR, AND UNION. SIZEFOR REQUIRED SIDESTREAM BAG FILTER FLOW.

FOR SYSTEMS HAVING A TOTAL VOLUME GREATER THAN 500 GALLONS, INCREASE SIZE OFMAKE-UP SYSTEM COMPONENTS AS NEEDED TO ALLOW FOR A TOTAL SYSTEM FILL TIME OFUNDER 2 HOURS.

SPIROVENT AIR/DIRT SEPARATOR. AUTOMATIC AIR VENT INCLUDED WITH UNIT. SELECT BASEDUPON MANUFACTURER'S FLOW VELOCITY GUIDELINES.

SEE TYPICAL HEAT EXCHANGER PIPING DETAIL

PRESSURE REDUCING VALVE. PRV SETTING (PSIG) IS DETERMINED BY THE FOLLOWING EQUATION:P=[(0.433 X VERTICAL DISTANCE IN FEET FROM PRV TO SYSTEM HIGHPOINT) + 4]

REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER WITH OPEN AIR GAP

PROVIDE SAFETY PRESSURE RELIEF VALVE AT THIS LOCATION BETWEEN PRESSURE VESSEL AND FIRST ISOLATION VALVE IFPRESSURE VESSEL CAPACITY IS GREATER THAN OR EQUAL TO 120 GALLONS (PA L&I REQUIREMENT). PRESSURE VESSEL MUSTBE ASME CERTIFIED IF GREATER THAN OR EQUAL TO 120 GALLON CAPACITY. SELECT RELIEF VALVE TO PREVENT SYSTEMPRESSURE FROM RISING MORE THAN 10% ABOVE THE MAXIMUM ALLOWABLE WORKING PRESSURE OF THE SYSTEMCOMPONENTS, TAKING INTO ACCOUNT THE EFFECT OF STATIC HEAD, PIPE TO FLOOR DRAIN.

SEE TYPICAL PUMP PIPING DETAIL

5/8" NEPTUNE T-10 DIRECT READ WATER METER

CHEMICAL POT FEEDER. NEPTUNE MODEL #DBF-2HP. FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.

SPIROVENT AIR/DIRT SEPARATOR SHOULD BE PERIODICALLY BLOWN DOWN THROUGH THE BAG FILTER FOR ABOUT 10 SECONDSONCE EVERY 4 WEEKS. THIS SHALL BE ACCOMPLISHED BY FULLY CLOSING V-5A, FULLY OPENING V-4A, AND PARTIALLY CLOSINGV-3A UNTIL FLOW IS DETECTED THROUGH THE BAG FILTER SIGHT FLOW INDICATOR. THIS IS THE POINT WHERE THE MEMORYSTOPS ON V-3A SHOULD BE TIGHTENED TO PREVENT THE VALVE FROM BEING CLOSED ANY FURTHER IN THE FUTURE. ONCEBLOWN DOWN, THE VALVE POSITIONING DESCRIBED ABOVE SHOULD BE REVERSED.

PRESSURE GAUGE WITH NEEDLE VALVE

EXPANSION TANK (FIXED OR REPLACEABLE BLADDER TYPE)

B&G #87 AUTOMATIC AIR VENT

FLOW DESIGN MODEL AC COMBINATION BALL VALVE, AUTOFLOW REGULATOR, AND UNION. SIZE FOR 2GPM.

COUPON RACK. GE PART #2032806. 304SS, 1"NPT, WITH 4 COUPON HOLDERS.

JOHN C. ERNST CO. LOW PRESSURE, DOUBLE WINDOW, THREADED, BRONZE WITH PADDLE WHEEL INDICATOR.MODEL #138P. MATCH PIPE SIZE.

UNDERSLUNG CONNECTION TO CREATE THERMAL TRAP (12" MIN. DROP)

TAP FOR FUTURE AUTOMATED CHEMICAL INJECTOR

18

19

20

21

22

23

24

25

26

SEE TYPICAL BOILER PIPING DETAIL.27

ISOLATION CONTROL VALVES28

CHECK VALVE

3 1/2" FILLCAPOPENING(N.C.)

FLOOR

5'-6"

(MAX

.)

MAV

1" MINIMUM

VALVE WITHMEMORY STOPS

3/4" MINIMUM

3/4"

SIGHT FLOWINDICATOR

V-1B V-3B

V-4A

V-6B V-7B

V-8B

V-9B

V-5B

V-2B

(N.O.) (N.O.)

(N.C.)

(N.C.)

(N.C.) (N.C.)

(N.O.)

(N.O.)

1

2

4

5

(N.O.)

7

10

11

TO DRAIN

FILL LINE12PRESSURE GAUGE

W/ NEEDLE VALVE13

14

15

M

16

17

18

P/T PORT (PETE'S PLUG)

1"

1"

1" MINIMUM

1" 1" MINIMUM

1"1"

3

3

3

6

B-10B(N.O.)

19

20

21

22

23

V-11B(N.O.)

V-12B(N.O.)

1"1"

24

24 24

25

444 4

21

HWP-3

LTHWS

LTHWR

HWP-4

HTHWS

HEAT EXCHANGER

8

14

28

HTHWRHTHWS

HTX-3

9

9

9

8

HTX-2

HTX-1

HEATEXCHANGER

26

V-13B(N.C.)

1"

4"

4"

HEAT EXCHANGER

1-1/2"

4"

HWS

HWR

CHWS

CHWR

9

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:34

:47 P

M M5.01

Mechanical PipingSchematics

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 18: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

AHU4

AHU3

AHU2

AHU1

JANITOR CLOSET103

MEN &WOMEN

RESTROOMS106 & 105

CIVIL STUDENTPROJECT LAB

110

CIVIL STRENGTHOF MATERIALS

LAB 109

CIVIL GEOTEACHING LAB

112

CIVILSTRUCTURES

LAB 111CIVIL SURVEY

114

CIVIL CONCRETE& ASPHAULT LAB

113ELECTRICAL

ROOM 116

CIVIL PREP &CURING

115 & 115AELECTRICAL POWER LAB 118 MECHANICAL

ROOMSTAIRS

2-1

STAIRS2-2

STAIRS2-3

PENTHOUSEMECHANICAL ROOM

300

JANITOR CLOSET203

MEN & WOMENRESTROOMS

206 & 205CORRIDOR 262

WOOD/MACHNIESHOP212C

MISC. ELECTRICALRESEARCH LABS

208, 209A, 210, 211, 214

MISC. ELECTRICAL WORK LABS(ELECT. LAB, PHYSICS LAB, SIGNAL LAB)

217, 215, 209REHEARSAL STUDIO 207 CORR.

260

CORR.161

CORR.162

CORR.165

50 SEAT & 100 SEATCLASSROOMS

100, 101, 102, 107

STUDENTGATHERING

222

ELECTRICALCOMPUTER LAB

220

ELECTRICALAUTO/ROBOTICS

LAB 221

ELECTRICALMICRO/COMM.

LAB 218

ELECTRICALSENIOR PROJECTS

LAB 219CORRIDOR 261

ELECTRICAL EQUIPSTORAGE

212

STUDENTSELF

SERVICE 212A

BATTERYSTORAGE

ELEV MACHINEROOM1ST FLOOR

2ND FLOOR

PENTHOUSE

AHU4

AHU3

AHU2

AHU1

JANITOR CLOSET103

MEN &WOMEN

RESTROOMS106 & 105

CIVIL STUDENTPROJECT LAB

110

CIVIL STRENGTHOF MATERIALS

LAB 109

CIVIL GEOTEACHING LAB

112

CIVILSTRUCTURES

LAB 111CIVIL SURVEY

114

CIVIL CONCRETE& ASPHAULT LAB

113ELECTRICAL

ROOM 116

CIVIL PREP &CURING

115 & 115AELECTRICAL POWER LAB 118 MECHANICAL

ROOMSTAIRS

2-1

STAIRS2-2

STAIRS2-3

PENTHOUSEMECHANICAL ROOM

300

JANITOR CLOSET203

MEN & WOMENRESTROOMS

206 & 205CORRIDOR 262

WOOD/MACHNIESHOP212C

MISC. ELECTRICALRESEARCH LABS

208, 209A, 210, 211, 214

MISC. ELECTRICAL WORK LABS(ELECT. LAB, PHYSICS LAB, SIGNAL LAB)

217, 215, 209REHEARSAL STUDIO 207 CORR.

260

CORR.161

CORR.162

CORR.165

50 SEAT & 100 SEATCLASSROOMS

100, 101, 102, 107

STUDENTGATHERING

222

ELECTRICALCOMPUTER LAB

220

ELECTRICALAUTO/ROBOTICS

LAB 221

ELECTRICALMICRO/COMM.

LAB 218

ELECTRICALSENIOR PROJECTS

LAB 219CORRIDOR 261

ELECTRICAL EQUIPSTORAGE

212

STUDENTSELF

SERVICE 212A

BATTERYSTORAGE

ELEV MACHINEROOM1ST FLOOR

2ND FLOOR

PENTHOUSE

AHU4

AHU3

AHU2

AHU1

JANITOR CLOSET103

MEN &WOMEN

RESTROOMS106 & 105

CIVIL STUDENTPROJECT LAB

110

CIVIL STRENGTHOF MATERIALS

LAB 109

CIVIL GEOTEACHING LAB

112

CIVILSTRUCTURES

LAB 111CIVIL SURVEY

114

CIVIL CONCRETE& ASPHAULT LAB

113ELECTRICAL

ROOM 116

CIVIL PREP &CURING

115 & 115AELECTRICAL POWER LAB 118 MECHANICAL

ROOMSTAIRS

2-1

STAIRS2-2

STAIRS2-3

PENTHOUSEMECHANICAL ROOM

300

JANITOR CLOSET203

MEN & WOMENRESTROOMS

206 & 205CORRIDOR 262

WOOD/MACHNIESHOP212C

MISC. ELECTRICALRESEARCH LABS

208, 209A, 210, 211, 214

MISC. ELECTRICAL WORK LABS(ELECT. LAB, PHYSICS LAB, SIGNAL LAB)

217, 215, 209REHEARSAL STUDIO 207 CORR.

260

CORR.161

CORR.162

CORR.165

50 SEAT & 100 SEATCLASSROOMS

100, 101, 102, 107

STUDENTGATHERING

222

ELECTRICALCOMPUTER LAB

220

ELECTRICALAUTO/ROBOTICS

LAB 221

ELECTRICALMICRO/COMM.

LAB 218

ELECTRICALSENIOR PROJECTS

LAB 219CORRIDOR 261

ELECTRICAL EQUIPSTORAGE

212

STUDENTSELF

SERVICE 212A

BATTERYSTORAGE

ELEV MACHINEROOM1ST FLOOR

2ND FLOOR

PENTHOUSE

AHU4

AHU3

AHU2

AHU1

JANITOR CLOSET103

MEN &WOMEN

RESTROOMS106 & 105

CIVIL STUDENTPROJECT LAB

110

CIVIL STRENGTHOF MATERIALS

LAB 109

CIVIL GEOTEACHING LAB

112

CIVILSTRUCTURES

LAB 111CIVIL SURVEY

114

CIVIL CONCRETE& ASPHAULT LAB

113ELECTRICAL

ROOM 116

CIVIL PREP &CURING

115 & 115AELECTRICAL POWER LAB 118 MECHANICAL

ROOMSTAIRS

2-1

STAIRS2-2

STAIRS2-3

PENTHOUSEMECHANICAL ROOM

300

JANITOR CLOSET203

MEN & WOMENRESTROOMS

206 & 205CORRIDOR 262

WOOD/MACHNIESHOP212C

MISC. ELECTRICALRESEARCH LABS

208, 209A, 210, 211, 214

MISC. ELECTRICAL WORK LABS(ELECT. LAB, PHYSICS LAB, SIGNAL LAB)

217, 215, 209REHEARSAL STUDIO 207 CORR.

260

CORR.161

CORR.162

CORR.165

50 SEAT & 100 SEATCLASSROOMS

100, 101, 102, 107

STUDENTGATHERING

222

ELECTRICALCOMPUTER LAB

220

ELECTRICALAUTO/ROBOTICS

LAB 221

ELECTRICALMICRO/COMM.

LAB 218

ELECTRICALSENIOR PROJECTS

LAB 219CORRIDOR 261

ELECTRICAL EQUIPSTORAGE

212

STUDENTSELF

SERVICE 212A

BATTERYSTORAGE

ELEV MACHINEROOM1ST FLOOR

2ND FLOOR

PENTHOUSE

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

4-7 4-64-5

4-4 4-2 4-1

4-3

HVAC SUPPLY AIR RISER DIAGRAM HVAC RETURN AIR RISER DIAGRAM

HVAC EXHAUST RISER DIAGRAMS HVAC HYDRONIC RISER DIAGRAMS

1

M-5.02 NOT TO SCALE

2

M-5.02 NOT TO SCALE

3

M-5.02 NOT TO SCALE

4

M-5.02 NOT TO SCALE

EF-3

X X X XXX

EF-4

EF-2 EF-1

EF-6EF-7EF-5EF-10

EF-8

X X X

X X X

2-4 2-8 2-9 2-5 2-10 2-2 2-6 2-1 2-7 2-3

X X X

X X X

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

1-3 1-11 1-4 1-12 4-7 4-6 1-1 1-6 1-7 1-171-14 1-5 1-9 1-10

1-15 1-16

1-8 1-24-5

2-4 2-8 2-9 2-6 2-10 2-7 2-5 2-1 2-2 2-34-4 4-24-1

4-3

1-13

1-3 1-11 1-4 1-12 4-7 4-6 1-1 1-6 1-7 1-171-14 1-5 1-9 1-10

1-15 1-16

1-8 1-24-5

2-4 2-8 2-9 2-5 2-10 2-2 2-6 2-7 2-34-4 4-24-1

4-3

1-13

2-1

1-3 1-11 1-4 1-12 1-1 1-6 1-7 1-171-14 1-5 1-9 1-10

1-15 1-16

1-8 1-21-13

SUPPLY DUCT TO (3) 100 SEAT CLASSROOMS, ZONES 3-1, 3-2, AND 3-3. OPEN ENDED RETURN DUCT FROM (3) 100 SEATCLASSROOMS - ZONES 3-1, 3-2, AND 3-3.

ZONE 1-2

ZONE 2-3ZONE 2-8 ZONE 2-9

HWS & HWRTO HYDRONICRADIANTHEATERS

HOT WATERMANIFOLD

HWS & HWRTO HYDRONICRADIANTHEATERS

HOT WATERMANIFOLD

SEE SCHEMATIC DETAILSON DRAWING M-5.01 FORCONTINUATION OF HWS &HWR PIPING & EQUIPMENT.

NOTE:SEE MECHANICAL PENTHOUSE FLOOR PLANS ON SHEET M-2.06 FORACTUAL LOCATIONS AND ORIENTATIONS OF AIR HANDLING UNITS.

NOTE:SEE MECHANICAL PENTHOUSE FLOOR PLANS ON SHEET M-2.06 FORACTUAL LOCATIONS AND ORIENTATIONS OF AIR HANDLING UNITS.

NOTE:SEE MECHANICAL PENTHOUSE FLOOR PLANS ON SHEET M-2.06 FORACTUAL LOCATIONS AND ORIENTATIONS OF AIR HANDLING UNITS.

NOTE:SEE MECHANICAL PENTHOUSE FLOOR PLANS ON SHEET M-2.06 FORACTUAL LOCATIONS AND ORIENTATIONS OF AIR HANDLING UNITS.

HOT WATER SUPPLY & RETURN TO (3) 100 SEATCLASSROOMS - ZONES 3-1, 3-2, AND 3-3.INLINE/CEILING FANS WITH EXTERIOR SIDEWALL

TERMINATIONS (TYP. FOR EF-5, 6, 7, 8 & 10)

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:34

:55 P

M M5.02

Mechanical Riser Diagrams

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 19: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

CONTROL SYMBOLS CONTROL ABBREVIATIONS

NO

NO

NC

H L

EC

DXC

COMPEVAP

COND

COMP EVAP

HC

CC

SC

NC

M

M

M

AFS

TS

AQS

OAH

HTS

HS

CS

PS

SD

PS

PS

SPS

TS

OA

TS

TLS

TS

TS

CT

VFD

HOA

M

FS

DPS

SPT

PT SL AFS

SCALE: NONE

AHU CONTROL SCHEMATIC (AHU-1 TO 3)3M-6.01

SCALE: NONE

SPACE TEMPERATURE SENSORS5M-6.01

SCALE: NONE

ATC SYSTEM ARCHITECTURE2M-6.01

SCALE: NONE

VAV BOX CONTROL SCHEMATIC (VAV)6M-6.01SCALE: NONE

AHU CONTROL SCHEMATIC (AHU-4)4M-6.01

SCALE: NONE

FAN COIL UNIT CONTROL SCHEMATIC (FCU-1,2,3)1M-6.01

BACNET

VAV BOX CONTROLLERS

ETHERNET LAN

WORKSTATION

ENTERPRISESERVER

HEATING PLANTCONTROLLERS

NIC CARDWITH BUILT IN

WIRELESSLOCATED INSERVER ROOM

RS 485

MISCELLANEOUSCONTROLLERS

BACNET

RS 485

MISCELLANEOUSCONTROLLERS

REMOTEWORKSTATION

BACNET

FIELD MOUNTED & WIRED APPLICATION

MAIN PANEL LOCATED IN SECOND FLOORELECTRICAL ROOM

MAIN PANEL LOCATED IN FIRSTFLOOR ELECTRICAL ROOM

MAIN PANEL LOCATEDIN PENTHOUSE

NOTES:

1. ATC/BMS VENDER TO PROVIDE ETHERNET LOCAL AREA NETWORK WIRING AND INSTALLATION. THISWILL BE A DEDICATED LAN FOR BUILDING MANAGEMENT SYSTEM.

2. ATC CONTROL VENDOR SHALL PROVIDE THE COST IN THIS BID TO COVER THE COSTS ASSOCIATEDWITH (120 VOLT) POWER TO CONTROL PANELS AND CONTROL TRANSFORMERS AS REQUIRED.

3. ALL CONTROL TRANSFORMERS, CONTROLLERS, RELAYS, I/O BOARDS, ETC. ARE TO BE HOUSED IN ANEMA (LOCABLE) ELECTRICAL PANEL, SUITABLE FOR ITS LOCATION.

4. ALL CONTROL WIRING OR COMMUNICATION CABLE LOCATED IN EQUIPMENT ROOMS OR EXPOSEDAREAS SHALL BE RUN IN CONDUIT TO 12'-0" A.F.F.

5. ALL DEVICES SHOWN ON ALL OTHER CONTROL SCHEMATICS ON THE CONTROL SCHEMATIC DRAWINGSARE THE RESPONSIBILITY OF THE ATC CONTROL VENDOR UNLESS OTHERWISE NOTED.

VAV BOXCONTROLLERS

BY PENN STATE UNIVERSITY (TECHNOLOGY CONTRACTOR)

AHU-1

AHU-2

AHU-3

AHU-4

LABTOP

ETHERNETCONNECTION

RADIANT LOOP RADIANT LOOP

PUMPSCONTROLLER

COOLING PLANTCONTROLLERS

MISCELLANEOUSCONTROLLERS

LIGHTING CONTROLPANEL INTERFACE

LIGHTING CONTROL PANEL INTERFACEINTERFACE WITH UP TO 15

INTERFACE WITH UP TO 15 LIGHTINGMODULES CONTROL PANELS

LIGHTING MODULE CONTROL PANELS

WEB

AO

AI

DO

DI

AO

TT

AI

TT

AI

M

AO

AI

AI

AFS

AI

TS

OA

HDI

HC

CT

M

DOAO

SPEED ALARMDI

VFD

OA

H

DI

HC

CT

M

DOAO

SPEED ALARMDI

VFD

HT

AI AI

TS

OA

H

DI

HC

CT

M

AO DO

AO

SPEED ALARMDI

VFD

C

C

AODI

SD HL

DIHIGH LIMIT DUCT STATIC PRESSURE(2"W.C.)

FURNISHED BY DIV 16INSTALLED BY M.C.WIRED TO SUPPLY FAN STARTER BY E.C.STATUS TO DDC BY ATC

AI

CO2

AI

AI

AFS

H

C

DP

DI

SPECIFIC CONTROLLER (TYP)

AFS

AI

H

C

AO M

AI

AFS

AI

TS

OA

HDI

HC

CT

M

DOAO

SPEED ALARMDI

VFD

OA

HDI

HC

CT

M

DOAO

SPEED ALARMDI

VFD

HT

AI AI

TS

OA

H

DI

HC

CT

M

AO DO

AO

SPEED ALARMDI

VFD

C

C

AODI

SD HL

DIHIGH LIMIT DUCT STATIC PRESSURE(2"W.C.)

FURNISHED BY DIV 16INSTALLED BY M.C.WIRED TO SUPPLY FAN STARTER BY E.C.STATUS TO DDC BY ATC

AI

CO2

AI

AI

AFS

H

C

DP

DI

AO M

AI

DUCT PRESSURE SENSORLOCATED 2/3 DOWN DUCTSYSTEM

AO

M

AIDUCT PRESSURE SENSORLOCATED 2/3 DOWN DUCTSYSTEM

AO

AO

AFS

AO

AFS

AO

AI

TS

DD

DI

DP

DI

AI

TS

AI

TS

AI

TSAO

M

AI

TS

AI

TS

IF

LTER

HW H

W

C

AO

AO

HWS

CHWS

RA

DP

DI

T

AI

SA

DI

CT

M

OA

H

DO

ENERGY RECOVERY WHEEL

RETURN AIR

RELIEF AIR

OUTSIDE AIR

HYDRONICCOOLING COIL

(FROM CHILLER PLANT)

SPACE CARBONDIOXIDE SENSOR(SET AT 800 PPM)

SENSORS LOCATED IN RETURNDUCTWORK WITHIN THE BUILDING.

SPT

2-WAYMODULATING

FILTERS HYDRONIC HEATING COIL

HWS

ON SYSTEMS 1, 2, 3.

RETURN AIR

SUPPLY AIR

RELIEF AIR

OUTSIDE AIR

HYDRONICCOOLING COIL

(FROM CHILLER PLANT)

SPACE CARBONDIOXIDE SENSOR(SET AT 800 PPM)

SENSORS LOCATED IN RETURNDUCTWORK WITHIN THE BUILDING.

SPT

2-WAYMODULATING

FILTERS

HYDRONIC HEATING COIL

SPT

SUPPLY AIR

SPT

(FROM HOT WATER PLANT)

(FROM HOT WATER PLANT)

CURRENTSENSOR

RELAY

FILTERS

BE APPLICABLE TO THIS PROJECT.ALL SYMBOLS SHOWN ABOVE MAY NOT

NOTE:

DAMPER WITHACTUATOR(NORMALLY OPEN)

DAMPER WITHACTUATOR(NORMALLY CLOSED)

FILTER

DAMPER ONLY(NORMALLY OPEN)

DAMPER ONLY(NORMALLY CLOSED)

DUCT MOUNTED, BULBTEMPERATURE SENSOR

DUCT MOUNTED, AVERAGINGTEMPERATURE SENSOR

TEMPERATURE LIMITSWITCH, AVERAGING

WALL MOUNTEDTEMPERATURE SENSOR

WELL MOUNTEDTEMPERATURE SENSOR

OUTSIDE AIRTEMPERATURE SENSOR

STRAP-ONTEMPERATURE SENSOR

DUCT MOUNTEDPRESSURE SENSOR

HOT/ CHILLED WATERDIFFERENTIAL WATERPRESSURE SENSOR

STEAM PRESSURE SENSOR

DUCT MOUNTEDSMOKE DETECTOR

DUCT MOUNTEDPRESSURE SENSOR

CURRENT SENSOR,CURRENT SWITCH,CURRENT SWITCHWITH RELAY

DUCT MOUNTEDHUMIDITY SENSOR

DUCT MOUNTEDHUMIDITY ANDTEMPERATURE SENSOR

OUTSIDE AIRHUMIDITY SENSOR

DUCT MOUNTEDAIR QUALITY SENSOR

AIR FLOW MEASURINGSTATION WITHDIFFERENTIALPRESSURESENSOR

HUMIDIFIER

ELECTRIC HEATING COIL

DIRECT EXPANSION COIL

3-WAY CONTROL VALVE - MODULATING

FAN

PUMP

CHECK VALVE

FLOW DIRECTIONARROW

PIPE/ DUCT BREAK

CONTROL PANEL

BOILER

HEAT EXCHANGER

AIR COOLEDCHILLER

WATER COOLEDCHILLER

COOLING TOWER

HOT WATER HEATING COIL

CHILLED WATER COIL

STEAM HEATING COIL

CURRENT TRANSMITTER

ANALOG OUTPUT

ANALOG INPUT

DIGITAL OUTPUT

DIGITAL INPUT

VARIABLE FREQUENCY DRIVE

HAND-OFF-AUTO SWITCH2-WAY CONTROL VALVE - MODULATING

3-WAY CONTROL VALVE - 2-POSITION

2-WAY CONTROL VALVE - 2-POSITION

HUMIDIFIER INLET VANESPNEUMATICALLY CONTROLLED

ADC ANALOG TO DIGITAL CONVERTER

AI ANALOG INPUT

AN APPLICATION NODE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AO ANALOG OUTPUT

ASCII AMERICAN STANDARD CODE FOR INFORMATION INTERCHANGE

AWG AMERICAN WIRE GAUGE

BMS BUILDING MANAGEMENT SYSTEM

CFM CUBIC FEET PER MINUTE

CPU CENTRAL PROCESSING UNIT

CRT CATHODE RAY TUBE

DAC DIGITAL TO ANALOG CONVERTER

DDC

DI

DO

EEPROM

EMI

ENCL

FAS

HOA

IEEE

I/O

LAN

LCD

LED

MCC

NC

NIC

NO

OWS

OAH

OAT

PC

RAM

RF

RFI

RH

ROM

RTD

SPDT

SPST

XVGA

TBA

ENCLOSURE

DIRECT DIGITAL CONTROL

(BINARY) DIGITAL INPUT

(BINARY) DIGITAL OUTPUT

ELECTRONICALLY ERASABLE PROGRAMMABLE READ ONLY MEMORY

ELECTROMAGNETIC INTERFERENCE

FIRE ALARM DETECTION AND ANNUNCIATION SYSTEM

HAND-OFF-AUTO

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

INPUT/OUTPUT

LOCAL AREA NETWORK

LIQUID CRYSTAL DISPLAY

LIGHT EMITTING DIODE

MOTOR CONTROL CENTER

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

OPERATOR WORKSTATION

OUTDOOR AIR HUMIDITY

OUTDOOR AIR TEMPERATURE

PERSONAL COMPUTER

RANDOM ACCESS MEMORY

RADIO FREQUENCY

RADIO FREQUENCY INTERFERENCE

RELATIVE HUMIDITY

READ ONLY MEMORY

RESISTANCE TEMPERATURE DETECTOR

SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROW

EXTENDED VIDEO GRAPHICS ADAPTER

TO BE ADVISEDFS FREEZE STAT

BDD BACKDRAFT DAMPER

DPS DIFFERENTIAL PRESSURE SWITCH

PT PRESSURE TRANSMITTER

SPT STATIC PRESSURE TRANSMITTER

FREEZE STAT

DIFFERENTIAL PRESSURE SENSOR

STATIC PRESSURE SENSOR

PRESSURE TRANSMITTER

SL SUMP LEVEL

SUMP LEVEL SENSOR

CT COOLING TOWER

CV CONTROL VALVE

PROVIDE (1) IN MAIN MECHANICAL ROOM

PROVIDE (2) IN I.T. CLOSETS

PROVIDE (1) IN PENTHOUSE ROOM

PROVIDE (1) IN TRUCK DOCK

AFS AIR FLOW SENSOR

AIR FLOW SENSOR(EBTRON - GOLD SERIES)

HOT WATER HEATING COIL

SPACE TEMPERATURESENSOR W/ TOC

T

STATUS/FAILUREALARM

START/STOP

STATUS/FAILUREALARM

START/STOP

STATUS/FAILUREALARM

SPEED START/STOP

EXHAUSTFAN

SUPPLYFAN

SPACE

OUTDOOR

BUILDINGTRANSMITTER

FROM AHUPRIMARY AIR

STATUS/FAILUREALARM

START/STOP

STATUS/FAILUREALARM

START/STOP

STATUS/FAILUREALARM

SPEED START/STOP

RETURNFAN

SUPPLYFAN

SPACE

OUTDOOR

BUILDINGTRANSMITTER

SUPPLYFAN

STATUS/FAILUREALARM

START/STOP

NOTE: FCU-1 & 2 HEATING ONLY

SPACE TEMPERATURE

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:35

:02 P

M M6.01

Mechanical ControlSchematics

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date

Page 20: M0erieconstructioncouncil.com/plan_room_documents/Mechanical Bid Set (20).pdfmechanical general notes be applicable to this project. all symbols shown above may not ... bfp-rp back

G

CW

E

SL

SL

SCALE: NONE

EF-2 CONTROL SCHEMATIC (LAB CONTROL)5M-6.02

SCALE: NONE

UNIT HEATER CONTROL SCHEMATIC (UH-1,2,3,4&5)15M-6.02SCALE: NONE

FIRE/SMOKE DAMPER CONTROL SCHEMATIC14M-6.02

SCALE: NONE

WALL UNIT HEATER CONTROL SCHEMATIC (WH-1,2&3)9M-6.02

SCALE: NONE

CHILLED WATER SYSTEM CONTROL SCHEMATIC1M-6.02

SCALE: NONE

EXHAUST FAN OCCUPIED/UNOCCUPIED CONTROL (EF-1,10)7M-6.02SCALE: NONE

EXHAUST FAN CONTROL VIA THERMOSTAT (EF-3,4,5,6,7,8)6M-6.02SCALE: NONE

UTILITY METERS4M-6.02

SCALE: NONE

DUCTLESS SPLIT SYSTEMS (DAH-1/DCU-1)10M-6.02

SCALE: NONE

HOT WATER HEATING SYSTEM CONTROL SCHEMATIC2M-6.02

SCALE: NONE

RADIANT HEAT ZONE CONTROL SCHEMATIC (RHZP-1,2)8M-6.02

SCALE: NONE

LOW TEMPERATURE HOT WATER HEATING SYSTEM CONTROL SCHEMATIC3M-6.02

SCALE: NONE

SPLIT SYSTEMS HEAT PUMP (SSAH/SSHP-1,2,3)13M-6.02

SCALE: NONE

RANKINE CYCLER EXHAUST/SUPPLY AIR CONTROL (EF-9/SF-1)11M-6.02

SCALE: NONE

ELECTRIC DUCT HEATER CONTROL SCHEMATIC (EDH-1)12M-6.02

SCALE: NONE

ELECTRIC CEILING HEATER CONTROL SCHEMATIC (ECH-1)16M-6.02

ALARMFAILURE

DI

STOPSTART/

DI

A0

CT

M

H

EXHA

UST

AIR

A0

M

H

EXHA

UST

AIR

TS

AI

SPT

AI

AOSPEED

ALARMSTATUS/FAILURE

DI

STOPALARM

DI

VFD

START/DO

A0

CT

MHC

H

DODI

FS

TS

AI

TS

AI

AOAO

SPEED

DI

STOPALARM

DI

VFD

START/

A0

CT

MHC

H

STOPSTART/

DO

TS

AI

DO

DO

ROOMAIR

DPT

AI

AOSPEED

ALARMFAILURE

DI

STOPALARM

DI

VFD

START/DO

A0

CT

MHC

H

EXHA

UST

AIR

SDSD

M

AO

SPT

AI

AI

AI

AI

DO

DI

A1

DO

A1TS

AI

TS

AI

TS

AI

TS

AI

TS

AI

DO

T

AI

M AO

DISTOPSTART/

M AO

DO

M DOOPEN/CLOSE(WITH END SWITCH)

DO STOP/START

DI STATUS

ON ROOFMDO

OPEN/CLOSE(WITH END SWITCH)

STOP/START

ON ROOFDI

DO

STATUS

ROOF

EA SA

T

AI

E

AFS

DI

AIRFLOW SWITCHHARD WIRE TO CONTACTOR INSERIES. PROOF OF FLOW BEFOREENERGIZING COIL.

CONTACTORS AO SCR HEAT CONTROL

SUPPLY DUCTT

AI

SPACE THERMOSTAT

ELECTRIC COIL

M

DO ON/OFF

E

POWER WIRECONTACTORS

DO ON/OFF PER STAGE OF HEAT

T

AI

SPACE THERMOSTAT

SPACE TEMPERATURE

SPACE TEMPERATURE

POWER WIRING SCR CONTROLLER

ACC1

P2

UH

VFD

WH

P1

WHP3

WHP4

SFEF

ECH

QTY. 2

DOMESTIC SUB WATER METER TO HVAC MAKEUP

GAS SUB METER TO BOILERS & TO

ELECTRIC SUB METER TO CHILLER

NOTES1. GRAPHICS FOR SUBMETERED UTILITIES SHALL BE SHOWN

2. UTILITY VALUES SHALL BE TREND LOGGED AND STORED FORA THREE (3) MONTH PERIOD.

3. VALUES SHALL BE TOTALED EVERY MONTH AND SAVED INTHE HEAD END PANEL.

(REAL TIME VALUES).

4. UTILITY SUB METERS ARE TO BE SUPPLIED BY THE ATCVENDOR & WIRED BY THE ATC VENDOR.

LOW VOLTAGE COMMUNICATIONWIRING FIELD INSTALLED BYATC VENDOR

EVAPORATORINDOOR

CONDENSEROUTDOOR

T LOW VOLTAGE SPACETHERMOSTAT FIELD INSTALLEDBY ATC VENDOR

DOMESTIC HOT WATER HEATER

TS

AI

SPT

AI

TS

AI

OUTDOOR AIRSENSOR

LOCATED INMECH ROOM

AOSPEED

ALARMSTATUS/FAILURE

DI

STOPALARM

DI

VFD

START/DO

A0

CT

MHC

H

BLR1

HTX1

DODI

ENABLESTATUS

FS

HARD WIRE FLOWSWITCH TO BOILERPANEL. TYPICALFOR BOTH.

TS

AI

TS

AI

TS

AI

HWP

HWP

HWR

VAV'S

HWS

VAV'S

AO

HWS

HWR

DIFFERENTIAL PRESSUREBYPASS CONTROL VALVELOCATED AT END OFLOOP ON 3RD FLOOR

2

1

AOSPEED

ALARMSTATUS/FAILURE

DI

STOPALARM

DI

VFD

START/DO

A0

CT

MHC

H

(MODULATING BURNER)

DECOUPLERPIPE

AO

AO

2-WAYCONTROLVALVE

2-WAY

CONTROLVALVE

HTHWS

HTHWR

ISOLATION

HWR

HWS

-

-

HWR

HWS

HWR

HTX2

DIAO

RESETALARM

TS

AI

TS

AI

TS

AI

TS

AI

TS

AI

OUTDOORRH

(TYP 2)

ALSO (1) IN MECH ROOMFOR LOCAL PANEL CONNECTION

AO

ZONE LOOP SUPPLY

AO

ZONE LOOP RETURN

LTHWR LTHWS

SUPPLY MANIFOLD

DIVERTING VALVE BY ATC VENDOR

RECESSED ZONE PANEL

RETURN MANIFOLD

SPACE TEMPERATURESENSOR

SLAB TEMPERATURESENSOR

HTX3

TS

AI

AO

HWS

HWR

LTHWR

ALARMSTATUS/FAILURE

DI

CT

MHC

A0H

DO

STOP/START

LTHWS

ALARMSTATUS/FAILURE

DI

CT

MHC

A0H

DO

STOP/START

LOW VOLTAGE COMMUNICATIONWIRING FIELD INSTALLED BYATC VENDOR

EVAPORATORINDOOR

CONDENSEROUTDOOR

T LOW VOLTAGE SPACETHERMOSTAT FIELD INSTALLEDBY ATC VENDOR

(SUPPLIED BY RADIANT LOOP MANUFACTURER)

SA

HARD WIRE FLOWSWITCH TO BOILERPANEL. TYPICALFOR BOTH.

19

1

CONTROLDAMPER

ALARMFAILURE

DI

CT

LOCATED INPENTEHOUSEENABLESTATUS

CHWR

FROM AHU'S

CHWS

TO AHU'S

DIFFERENTIAL PRESSUREBYPASS CONTROL VALVELOCATED AT END OFLOOP IN PENTHOUSE #1

CHWR

CHWS

ALARMSTATUS/FAILURE

(VFD CHILLER)

ISOLATION VAVE

M

M

COMBINATION FIRESMOKE DAMPER

INTERLOCK WITH SPACESMOKE DETECTOR

SMOKE BARRIERABOVE CEILING

CEILING

SMOKE DETECTOR FURNISHED BYDIV 16 WIRED TO FIRE/SMOKE DAMPERBY ATC CONTRACTOR. WIRING TO FIREALARM SYSTEM BY E.C.

ISOLATIONDAMPER

SPACE STATIC

SA

RA

TSPACE THERMOSTAT

WAL

L

M

HEATING COIL

ALARM

ON/OFF

T

SPARE TEMPERATURE SENSOR

ON/OFF

SPACE THERMOSTAT

MAY BE LOCATEDIN DISCHARGE OF FAN

LOCAL WALL SWITCHFOR STARTING OF EF-10SERVING CIVIL CONCRETEPREP EXTRACTION

CONTROLDAMPERMAY BE LOCATEDIN DISCHARGE OF FAN

ON/OFF

SA RA

CEILING

307 Fourth AvenueSuite 1300Pittsburgh, PA 15222v: 412.765.3890 f: 412.765.2209

Scale

Date

BCJ Project Number

Seal

Revisions

© 2012 Bohlin Cywinski Jackson

Not For Construction

Client Project Number

General Notes

Office for Planning and Architecture234 Liberty StreetHarrisburg, PA 17101v: 717-230-9660f: 717-230-9664

Consultant Office Name or LogoAddress 1Address 2v: xxx-xxx-xxxxf: xxx-xxx-xxxx

1/8" = 1'-0"

11/19

/2012

4:35

:11 P

M M6.02

Mechanical ControlSchematics

NOVEMBER 21, 2012

11209

PENNSYLVANIA STATEUNIVERSITYPSU HARRISBURG - EDUCATIONALACTIVITIES BUILDING

GMP / 90% CONSTRUCTIONDOCUMENTS SET

01-03602.01

777 West Harrisburg PikeMiddletown, PA 17057

No. Description Date