Upload
cynthia-shavonne-anderson
View
237
Download
2
Embed Size (px)
Citation preview
M7900 ALARM SERVER FOR MOBILITY3
SECURITY
GLOBAL COMMUNICATION
SECURED SOLUTIONS
FOR ENTREPRISES
M7900 ALARM SERVER FOR MOBILITY
HEALTH INDUSTRY
DECT
WEB ACCESS
EXPERTISE
M7900 ALARM SERVER FOR MOBILITY4
M7900 ALARM SERVER FOR MOBILITYOur Dect Market segments
17%
15% 3%
35%
30%
Industries
Office
Health
Small MediumEnterprise
Hotels
Health
First Market Target for the M7900 Alarm Server
Industries
Second Market Target
for the M7900 Alarm Server
M7900 ALARM SERVER FOR MOBILITY5
M7900 ALARM SERVER FOR MOBILITYCustomers Applications
• Hospitals / old people home
• Notifications of alarms on the Dect mobiles coming from patient call systems
• Industries
• technical alarms of the plants (access, detection of fire, out of working alarms for equipments )
• process alarms for production lines
• technical alarms for maintenance people
M7900 ALARM SERVER FOR MOBILITY6
M7900 ALARM SERVER FOR MOBILITY M7900 The customer interfaces
• French Hospitals
– 100 % patient call systems covered with:
• ACKERMANN 50% of th French market
• ASCOM NIRA 30%
• MATHER§PLATT 20%
• Industries
– to be developped on business basis with the common standard ESPA4.4
– Forecasts a financial cost per business case:
• 1man month devt/integration + 1man month validation/qualification
= 25 k€
• Export
– Indentical to industries model
M7900 ALARM SERVER FOR MOBILITY7
M7900 ALARM SERVER FOR MOBILITYEADS TELECOM products
Patient call station
Dect Mobile M 90X
Technical Station IP NETWORK
Succession M6500
Dect Base Station
RS232 link
IP NETWORK
M7900 MOBIXITY
M7900 ALARM SERVER FOR MOBILITY8
Technical Station
IP NETWORK
Succession M6500
Dect Base Station
RS232 link
Patient presses Urgent Button in
Chamber 101
Chamber 101 Priority 2 Melody 3
Destination N°10
N°2115
Chamber 101 URGENT Melody 3
Destination n°2115
Chamber 101
Urgent
ACK
IP NETWORK
M7900 ALARMS SERVERHealth Application
M7900 MOBIXITY
M7900 ALARM SERVER FOR MOBILITY9
M7900 ALARM SERVER FOR MOBILITY List of compatible Patient call stations
Patient call station
Dect Mobile M 90X
Technical Station
Succession M6500
Dect Base Station
RS232 link
ACKERMANN
MATHER§PLATT
ASCOM NIRA
ESPA 4.4
IP NETWORK
M7900 MOBIXITY
M7900 ALARM SERVER FOR MOBILITY10
CHAMBER 101
URGENT
ACK
Notification of an alarm
• when the mobile is free
• or in communication
• with ACK or not
Picto presence of alarms
MESS XX Alarms counter
Alarms Lighted key
• by pressing key: access to none reading alarms
Softkey ACK
•by pressing ACK key:alarm is tagged in the server alarms log
Navigation Key
by pressing key: access to alarms log depth 10 alarms
MOBILES FEATURESMain Features
M7900 ALARM SERVER FOR MOBILITY11
MOBILE FEATURES
The acknowledgement CHAMBER 101
URGENT
ACQ
By pressing the softkey ACQ
The Alarm log Book records the acknowledgement of the alarm
M7900 ALARM SERVER FOR MOBILITY12
The two users in a group can acknowledge an alarm simultaneously
The Alarm Log Book records the two acknowledgements
N°10
N°11
N°10
N°11
ACK at 10.45
ACK at 10.45
CHAMBER 101
URGENT
ACK
By pressing on the softkey ACK
CHAMBRE 101
URGENT
ACK
By pressing on the softkey ACK
Group ( broadcast )
N°10
N°11
MOBILE FEATURES
The acknowledgement in a group
M7900 ALARM SERVER FOR MOBILITY13
The alarm 1 has been delivered but not acknowledged
N°10
N°10
alarm 1
No acknowledgement by a user
CHAMBER 101
URGENT
ACK
The alarm 2 has been delivered and acknowledged
The alarm 1 can not be acknowledged now
N°10
N°10
alarm 2
CHAMBER 101
URGENT
ACK
alarm 1
alarm 2
Acknowledgement by the user
MOBILE FEATURESThe acknowledgement of the on going alarm
M7900 ALARM SERVER FOR MOBILITY22
M7900 SERVER FEATURES Web Access / the Users
• All the features are usable either localy or via the Web for telemanagement.
• Four types of Logins are available, localy or via the Web
– The Super Administrator manages the full set of stations applications running on the server
– The Administrator manages the event log, the users login, the station management and the list of set Numbers
– The Installator configures the server
– The User consults the log
M7900 ALARM SERVER FOR MOBILITY23
M7900 SERVER FEATURES Web Acces
communication server
SuccessionMedia Gateway
administration Server
Common network (VLAN)
Core ToIP network
Internet
téléphone IPPC
Re
mo
te s
ite
s
Remote Sites
Remote WorkerSOHO
distant manager
DMZ
M7900 MOBIXITY
M7900 USERS
M7900 SUPER ADMINISTRATOR
M7900 ADMINISTRATOR
M7900 SUPPORT
M7900 SURVEYOR
M7900 ALARM SERVER FOR MOBILITY24
M7900 SERVER FEATURES multi sites installation
• The M7900 alarm servers are usable in a multi site situation
• You can install a server closed to your customer station ( patient call or technical ).
• One M7900 server supports 2 external stations.
Patient call station
Technical Station
Succession M6500
RS232 link
Succession M6500
M7900 MOBIXITY
IP NETWORK
M7900 MOBIXITY
M7900 ALARM SERVER FOR MOBILITY25
M7900 ALARM SERVER FOR MOBILITY System requirements
R2.1.03 release for system and base stations Supported by M6501/M6540/M6550 IP card 5 virtual set accesses Dect mobile with new 0.60 software release
M7900 ALARM SERVER FOR MOBILITY26
M7900 ALARM SERVER FOR MOBILITY PC server requirements
Windows NT, 2000, XP Penthium III 500 Mhz minimum or equivalent 1 Go available hard disk space minimum RAM : 128 Mo CD Rom drive 10 Base T Ethernet card Monitor CRT 17, resolution : 1024x768, 65 536 colours 2 ports COM
M7900 ALARM SERVER FOR MOBILITY27
M7900 ALARM SERVER FOR MOBILITY
Main Specifications ( 1 )• ALARMS :
– Reception on the M90X mobile of a VSMS ( Very Short Message of 29 Characters ) – A specific melody is played on the mobile ( 9 melodies : very urgent, urgent, normal, then a number of bips from 4 to 9)– Fast Flashing of the message key to advise of the reception of an alarm– Possible Reception on a fixed digital set with display ( advise feature )
• ACKNOWLEDGMENT :– Possibility to acknowledge an alarm on the mobile when in communication ( during 10 seconds ) or out of communication – Only the last alarm received can be acknowledged.– Choice of an acknowledged alarm or not ( used in diffusion mode )
• ALARM LOG BOOK IN THE MOBILE– The ten last alarms are recorded in the mobile– The alarms are time horodated– ACK state or Read state recorded in the alarm log book– Direct Acces by pressing message key to the unread alarms log book– Direct Acces by pressing the navigation key <> to the no ack or no read alarm log book – Possible Erase of the total alarm logbook by menu– Automatic erase of the oldest alarm when the alarm logbook is full– Display of the total number of received alarms: MESS nn– Picto to alert for the reception af an alarm
M7900 ALARM SERVER FOR MOBILITY28
M7900 ALARM SERVER FOR MOBILITY
Main Specifications ( 2 )
• SERVER – Management of two external alarm equipments simultaneously with complete User Datas separation– Multi site PABX configuration ( two servers linked to only one PABX is supported )– Multi servers with PABX multi sites Configurations– WEB based
• CUSTOMERS EXTERNAL CENTRALS– link via the serial port com of PC ( configurable )– ESPA 4.4 compatible– Patient calls equipment ACKERMANN ; MATHER§PLATT ; ACSOM – Alarms Status sent by the server to the external equipment ( ASCOM )– Industrial Centrals : Please contact us and give us the reference of the equipment , the supplier
contact and the description of the protocole utilisé.• Forecast an amount of 25 k€ on each business case for the adaptation of a basic equipment
( serial link port com not far from ESPA 4.4 )
M7900 ALARM SERVER FOR MOBILITY29
M7900 ALARM SERVER FOR MOBILITY
Server specifications ( 1 )
• FOUR LEVELS OF ACCESS : Super administrator ; administrator ; installator ; user
• ALARMS LOG BOOK– Display of the ACK Alarms with 3 states ACK, delivered or not delivered– possibility of alarms log records saving – Search on date time , message , numbers of origin and numbers of set to reach
• TECHNICAL LOG BOOK – Display all the events of thr running application
• CENTRAL LISTS– Two applications manage two external equipments simultaneously– The customers datas are separated exeption for the super administrator access level
FEATURES Super admin Admin Installator Userlog book yes yes yestechnical log book yes yes yesusers list yes yespassword yes yes yes yescentrals list yesserver configuration yes yescentral management yes yesSets and Groups yes yesDictionnary yes yes1818 call yes yes
M7900 ALARM SERVER FOR MOBILITY30
M7900 ALARM SERVER FOR MOBILITY
Server specifications ( 2 )
• PABX CONFIGURATION– Programmation of the IP adress ; override feature; affectation of the virtual sets ( min 2to t 5 max). The digital
links of the virtual digital sets must be available in the PABX rack• CENTRAL MANAGEMENT
– via configurable port com ( parity ; 19200 bauds ; port com choice )– protocole ESPA 4.4 / LINE
• SETS AND GROUPS– Call lists constitution to a single set ( dect mobile or fixed set ) or to a group – The groups could be fixed , cyclic or diffused
• fixed : the alarm is sent to the head of the group . If the alarm is ACK the sending is stopped, otherwise the sending continue until to find a user to ack . Ath the end of the group the sending is stopped
• cyclic : the alarm is sent to the set which follows the last set which ACK. - if the alarm is aACK the sending is stopped otherwise the sending continue until to find a user to ACK. When a complete turn around has been done the sending is stopped.
• diffused : the alarm is sent to all the sets ; If the PABX has five virtual sets the sending is done on 5 sets simultaneously then after some seconds the alarm will be send to an other five number of sets and so until to reach the number of sets contained in the group..
– The set can be a fixed set with display . The consulting is the same than for consulting advise messages on fixed sets.
M7900 ALARM SERVER FOR MOBILITY31
M7900 ALARM SERVER FOR MOBILITY
Server specifications ( 3 )
• DICTIONARY– Possibility to translate the message coming from the central in the VSMS ( Very Short Message ) displayed
on the mobile so that to be more efficient.– On the mobile display the alarm is showed on two lines of 12 caracters and one loe third line of 5 caracters.– The time stamp is visible in the alarm log book and is not part of the usable 29 characters
• LOCAL ACCESS– The server can work in standalone mode
• WEB ACCESS– The complete set of features can be Web managed and Web used.
CHAMBER 1011
VERY URGENT
WINDO
CHAMBER 1011 BATIMENT C URG 3 WINDOW
MESS 05
Alarm of :
27/03 18H45
read ack
<>