Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 1 All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com RISK Assessment® Report March 12, 2020 Macauley Ekpenisi Van Nuys, CA 91401 Inspector - Charles Simington Confidential and Proprietary 2550 Honolulu Ave. #101, Montrose, CA 91020 818.957.4654 www.creillc.com

Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 1All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

RISK Assessment® ReportMarch 12, 2020

Macauley Ekpenisi14401 Gilmore St

Van Nuys, CA 91401Inspector - Charles Simington

Confidential and Proprietary

2550 Honolulu Ave. #101, Montrose, CA 91020818.957.4654 www.creillc.com

Page 2: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 2All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

Macauley Ekpenisi14401 Gilmore St

Van Nuys, CA 91401

Page 3: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 1All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

This is an assessment of the five major systems - Plumbing, Electrical, Heating and AirConditioning, Structure and Roofing along with an assessment of any other current deferred maintenanceissues for the site.

This assessment will cover three aspects of these systems per industry standards, namely:

1. Expected useful life left in each system.2. Maintenance/Repairs that are needed immediately for each system.3. Total costs that are expected over the next five years for each system.

Note: The cost estimates are industry standards per the R.S. Means - 2007 Building Construction CostData 20th Annual Western Edition along with review and consultation with local contractors.

Although care and thought have gone into this assessment there are many variables that can cause the actualprices to differ greatly, such as: local building ordinances, requirements, specifications and details, localdemand for labor, materials, etc.

No implied warrantee is given.

No cosmetic concerns have been addressed in these estimates.

No Routine Maintenance concerns have been addressed in these estimates below $1000.

ADDRESS: 14401 Gilmore St, Van Nuys, CA 91401

CLIENT: Macauley Ekpenisi March 12, 2020

Page 4: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 2All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

PLUMBING:

1. The expected useful life left in the Plumbing System:

The expected useful life left appears to be approx. 30 - 50+ years - If properlymaintained.

2. What Maintenance/Repairs are needed immediately for the Plumbing System:

A. The system appeared to be in serviceable condition at the time of theinspection and other than routine maintenance no immediate significantdeficiencies or repairs were observed to be needed.B. Installing or locating an approved easily accessible emergency shut off valvefor the main water supply line is advised for health and safety.C. It is noted that a sewer line camera inspection was performed. Please fullyreview the report before the contingency period is over.D. Hot water is a typical requirement for all restroom sinks for hygienic reasons. It is advised to provide hot water to all required locations such as the restrooms.E. It is advised to have an approved Earth Quake Shut off valve installed on thegas system for safety.F. The main water supply lines appear to have been upgraded from the originalpiping. Full disclosure of work performed, permits and warranties from currentowner is advised.

3. What costs are expected over the next five years for the Plumbing System:

The cost for the above listed repairs/upgrades is approx. $2,000 - $3,000.

TOTAL:

$2,000 - $3,000

ELECTRICAL:

1. What is the expected useful life left in the Electrical System:

The system has had alterations throughout the years and the life expectancy variesdepending on the age. Typical systems have a 50 - 70 year life expectancydepending on the materials used and the quality of maintenance.

2. What Maintenance/Repairs are needed immediately for the Electrical System:

A. Improper or non-standard improvements to the electrical system have beenmade to the site. A detailed evaluation is advised at this time by a qualified

Page 5: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 3All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

electrical specialist to determine what repairs/replacements are needed to helpensure health and safety for this location and the conditions present.B. Complete and detailed labeling of all electrical panels and circuit breakers isrecommended for convenience and safety in the event of emergency and asrequired by code.C. It is advised to have GFCI outlets installed in all recommended locations.

3. What costs are expected over the next five years for the Electrical System:

Beyond routine maintenance no significant costs are anticipated for the ElectricalSystem over the next five years.

TOTAL:

Specialty Evaluation isneeded to determine

costs

HEATING AND COOLING:

1. What is the expected useful life left in the Heating and Air ConditioningSystem:

There are 7 systems for this site - 6 on the roof and 1 interior system. Theexpected useful life left for four of the systems is 10+ years. Three systems are ator near the end of their expected useful service life.

2. What Maintenance/Repairs are needed immediately for the Heating and AirConditioning system:

It is advised to have each unit fully cleaned and serviced at this time. Typical costis approx. $100 - $150 per individual unit.Due to the age of the units, approximately 10 years or more since the date ofmanufacture, the presence of the coolant known as R22 is typical. This coolant isno longer allowed to be used and if repairs are needed that involve installing morecoolant for any reason, replacement of the unit is usually warranted.

3. What costs are expected over the next five years for the Heating and AirConditioning System:

Anticipated replacement cost in the next five years for the units on this site isapprox. $22,000 - $30,000+ at current costs.

TOTAL:

$22,000 - $30,000+

Page 6: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 4All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

ROOF:

1. What is the expected useful life left in the Roofing System:

It appears that this roofing system has approx. 5 - 7 years of expected useful lifeleft in it if diligently and properly maintained.

2. What Maintenance/Repairs are needed immediately for the Roofing System:

The roof is in need of maintenance or repairs to the existing roof system at thistime to help ensure a leak free condition at this time.It is strongly advised to remove all areas where the water does not flow off theroof easily. Ponding will accelerate the deterioration of the roof materials greatlyand should be removed. Review by a qualified roofing specialist is advised.

3. What costs are expected over the next five years for the Roofing System:

It appears that Routine Maintenance is all that will be needed for the next 5 years.

TOTAL:

Routine Maintenance -Specialty ReviewRecommended

STRUCTURE:

1. What is the expected useful life left in the Structural System:

It appears that the expected useful life is from roughly 30 - 50+ years if properlymaintained.

2. What Maintenance/Repairs are needed immediately for the Structural System:

Due to age a seismic review of the building's structure is recommended todetermine feasible, cost-effective upgrades to improve the building's resistance toearthquake movement according to improvements and upgrades to earthquakesafety standards since the building's construction. This is advised as aprecautionary measure and not due to any significant deficiencies observed.

Structural components of the building have had additions or alterations made to itin the past. Such additions/alterations would typically be carried out pursuant toapproved engineering, work permits, progress and final inspections of all workperformed. The full extent of the work that was carried out is not known. It isadvised to obtain any plans or permits relating to this or other work on thestructure and property.

Page 7: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 5All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

3. What costs are expected over the next five years for the Structural System:

No significant costs are anticipated for repairs in the next five years to theStructure

TOTAL:

Routine Maintenance.Specialty Evaluation

recommended

GENERAL MAINTENANCE & REPAIRS:

1. What is the expected useful life left in the Site:

The expected useful life left in the site is approx. 30 - 40 years with routinemaintenance.

2. What Maintenance/Repairs are needed immediately currently for the Site:

A. It is advised to have all openable windows examined and any maintenance orrepairs done at this time for ease of use and proper function.B. It is advised to repair or replace deteriorated areas of the exterior windowwood trim and then have them repainted to help ensure a longer lasting condition.C. Testing of the spray texture ceilings is advised to determine if any asbestostype materials are present. This is advised for health and safety.D. A structural pest control inspection, typically referred to as a termiteinspection, is recommended at this time. E. It is advised to have a Phase 1 Environmental inspection done on the site. Thisis to help ensure health and safety. This inspection is typically between $1,500 -$2,000.F. Due to modifications to the site since the original construction that wouldtypically require Building Department permits it is advised to have all paperworkreviewed by a qualified general contractor with the local Department of Buildingand Safety to ensure all proper procedures were taken and approved.

3. What costs are expected over the next five years for the Site:

No significant costs are anticipated for the next five years for the site and groundsother than routine maintenance.

TOTAL:

Routine Maintenance -Specialty Evaluation

Recommended

Page 8: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave., Montrose, CA 91020 Page 6All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

TOTAL COMBINED ESTIMATED EXPENSES:

It is noted that in this Report a number of Specialty Inspections have been deemednecessary and are recommended.

Costs associated with the findings of Specialist Inspections can add significantly tothese Total Combined Estimated Expenses.

Upgrades and renovations to interiors are not included in these costings.

Further review by qualified specialists is advised at this time to determine the fullscope of work.

These estimates should be used as guidelines only.

TOTAL:

$24,000 - $33,000+

Page 9: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 3All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

INSPECTION CONDITIONS

CLIENT & SITE INFORMATION:DATE OF INSPECTION:

March 12, 2020 TIME OF INSPECTION:

1:00 PMCLIENT NAME:

Macauley EkpenisiADDRESS:

14401 Gilmore StVan Nuys, CA 91401

INSPECTOR:Charles Simington

CLIMATIC CONDITIONS:WEATHER:

RainTEMPERATURE:

50's

BUILDING CHARACTERISTICS:BUILDING TYPE:

Office BuildingSTORIES:

Two

UTILITY SERVICES:UTILITIES STATUS:

The utilities were on

OTHER INFORMATION:OCCUPIED:

The building was partially occupiedAPPROX. DATE OFCONSTRUCTION

1960's Per Disclosure at the time of the inspection.

Page 10: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 4All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

CLIENT PRESENT:No

GENERAL OVERVIEW:Overall the building and its systems are Serviceable with typical wear.Further review and repairs of the Electrical system is advised at this time. Some repairs and maintenance are needed to the Roofing system.

The property appears to have been through some renovations andmodifications. Due to alterations and modifications observed to thebuilding a full review at the local department of Building and Safety isstrongly advised to determine if all proper procedures have beenaddressed. This is advised by a qualified general contractor at this time.

NOTE - The original date of construction is before 1978. Due to this thereare two aspects that should be taken into consideration during futureupgrades or renovations: 1. The use of lead based paint was common andtypical. 2. The use of asbestos materials in items such as insulation andflooring materials was common. Both items are considered hazardousmaterials and require specialty methods and personnel for mitigation. Theability to determine if these are present require detailed reviews by qualifiedprofessionals which is beyond the scope of a general visual inspection such asthis.

Equipment, furniture and personal items are not moved during theinspection. Due to the amount of items in portions of the building theviews are limited. Limited views can obscure deficiencies.

NOTE: In the Report, building orientation is established by "front, back, leftand right" indications, with "Front" of the building determined by the wallcontaining the building's main entry door.

Page 11: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 5All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

DEFINITIONS AND STANDARDS

TERMS OF THE INSPECTION:SERVICEABLE:

It is the inspectors opinion that this item is doing the job for which it wasintended and exhibits normal wear and tear for it's age.

NEEDS ATTENTION:It is the inspectors opinion that this item is in need of further investigationand/or repairs or appears to be at the end of its expected useful life. Theinspector has made the client aware of this situation by calling it "needsattention" in the report. It is then the clients responsibility to takeappropriate action concerning the situation with the appropriate professionalin a timely manner.

NOT ACCEPTABLE:It is the inspectors opinion that this item is either in need of immediate repairsor is a safety hazard due to adverse conditions. Also the item may be in sucha state of disrepair that significant repairs or replacement is strongly advised.

The inspector has made the client aware of this situation by calling it "notacceptable" and it is then the clients responsibility to take appropriate actionconcerning the situation with the appropriate professional in a timely manner.

STANDARDS:A. The report conforms to the Commercial Standards of Practice of theCalifornia Real Estate Inspection Association and the Business andProfessions Code which defines a commercial real estate inspection as: Theinspection to be performed consists of non-intrusive visual observations tosurvey the readily accessible, easily visible material components, systems andequipment of the building. The inspection is designed to identify materialphysical deficiencies in the buildings components, systems and equipment, asthey exist at the time of the inspection. Unless otherwise agreed between theinspector and client, the specific systems, structures and components of abuilding to be examined are listed in these Commercial Standards of Practice.B. A commercial real estate inspection report provides writtendocumentation of material physical deficiencies discovered in the inspectedbuilding's systems and components which, in the opinion of the Inspector, aresafety hazards, are not functioning properly or appear to be at the end of theirexpected useful life. The report may include the Inspector'srecommendations for correction or further evaluation.

The term material physical deficiencies means the presence of conspicuouspatent defects or material deferred maintenance of the buildings materialsystems, components or building equipment as observed during theinspection. This definition specifically excludes deficiencies that may beremedied by routine maintenance.

Page 12: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 6All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

C. Inspections performed in accordance with these Standards of Practice arenot technically exhaustive and shall apply to the primary building and itsassociated primary parking structure.

Page 13: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 7All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

PLUMBING SYSTEM

While some plumbing observation may be code related, this inspection does not determine if the system complies with code. Supply and waste lines are inspected only where they are accessible and while operating accessible fixtures and drains. Performance of the water flow can vary during different times of the day and performance of the drain during actual usage isundetermined. Drain blockage is common in vacant property. It is advised to have any underground drain lines examined by aspecialist with a camera to determine their actual condition. The following are not included: inaccessible supply or waste lines;leaks in inaccessible areas such as walls, underground or the crawl space; the interior of pipes for mineral or corrosiveclogging, water hammering, solar equipment or water temperature, and the condition of shower pans or if a shower will leakwhen used. No water testing of any type is performed. The type of copper is not part of this inspection and will not bedetermined. The gas system is not tested for leaks and any underground or hidden gas lines are specifically excluded from thisreport. Determining the operation of sewer ejection systems is excluded from this inspection and it should be examined by aspecialist. The shutoff valves under sinks and other plumbing valves, such as the main shut off valve, are not turned or tested.

PLUMBING OVERVIEWOverall the plumbing system, both supply lines and the waste lines, appear tobe serviceable. No significant defects were observed and it appears thattypical and routine maintenance is all that will be needed for the near future.

MAIN WATER SUPPLY LINE:MAIN WATER SHUT OFFLOCATION:

The shut off appears tobe at the street meter inthe vault in thesidewalk. No othermain shut off valve waslocated.

MAIN WATER LINEMATERIAL:

The visible portion of the water main is composed of copper. This is thewater supply piping that runs between the city water meter and the building.

Page 14: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 8All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

CONDITION:Needs Attention:

No shut off handle for the main shut off valve was observed in an easilyaccessible location. A handle/lever is necessary for use in the event of anemergency.

PRESSURE REGULATORCONDITION:

There was a pressureregulator observed onthe water supplysystem. It is not knownhow well or if it isfunctioning, as this isbeyond the scope of ageneral visualinspection.

INTERIOR WATER SUPPLY LINES:WATER SUPPLY PIPINGMATERIAL:

The interior piping that supplies the water throughout the building is made ofcopper where viewed.

CONDITION:Serviceable where viewed.

Page 15: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 9All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

WATER VOLUME ATFIXTURES:

Serviceable

WASTE LINES:WASTE LINE MATERIAL:

The piping that takes the waste water to the sewer system is a combination ofdifferent materials where viewed.

CONDITION:The visible waste lines appear to be serviceable, however the view is verylimited due to the majority of the piping being either in the wall or under thebuilding.

MAIN SEWER CLEANOUT:A main waste linecleanout was located inthe Restroom.

WASTE LINE COMMENTS:The interior of the waste lines are not visible. A detailed investigationcan only be performed by the use of an internal camera by a specialtycontractor. Such an inspection is recommended at this time as only bythis kind of inspection can the actual condition of the waste lines bedetermined.

It is noted that this camera inspection was being done at the time of thegeneral visual inspection. See this detailed report for the overallcondition of the underground sewer lines.

Page 16: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 10All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

GAS SYSTEM:GAS METER LOCATION:

The meter is located inan underground vault.

GAS SYSTEM CONDITION:Serviceable.

SEISMIC GAS SHUT OFFVALVE:

Needs Attention:

There is no automatic seismic gas shut-off valve on the main gas line. Itis advised to have this installed for health and safety purposes.

WATER HEATER OVERVIEW:OVERALL:

There are multiple water heaters on the site. Some plumbing fixtures do nothave hot water. Hot water for sink fixtures is a minimum requirementfor health and safety.

WATER HEATER:

Page 17: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 11All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

LOCATION:Rear restroom

FUEL:This is an Electric water heater.

CONDITION:Serviceable.

WATER HEATER:LOCATION:

In a water heater closetin the rear office.

FUEL:This is an Electric water heater.

SIZE:10 gallons.

Page 18: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 12All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

CONDITION:Serviceable.

STRAPPING AND SUPPORT:Needs Attention:

The water heater bracing is not installed properly which allows for theunit to be easily shaken. This is not per state requirements. Properbracing is mandatory for earthquake safety.

TEMPERATURE/PRESSURERELIEF VALVE:

Serviceable.

EXTERIOR PLUMBING:SPRINKLER SYSTEM:

Exterior sprinklers and plumbing lines are beyond the scope of a generalvisual inspection.

PLUMBING COMMENTS AND RECOMMENDATIONS:WASTE LINERECOMMENDATIONS:

The interior of the waste lines are not visible. A detailed investigationcan only be performed by the use of an internal camera by a specialtycontractor. Such an inspection is recommended at this time.

WATER SUPPLY LINESRECOMMENDATIONS:

No repairs are recommended other than regular routine maintenance of thesystem as needed.

GENERAL COMMENTS:The majority of the water supply pipes, waste lines and gas lines areunderground, in walls or installed in concealed parts of the structure and thusare not visible. Their condition cannot be determined and no representationis made as to their status. During the inspection a Representative Sampling ofthe plumbing is viewed. This is to include any limited view areas such as in acrawl space, attic, etc. This is not a detailed specialty inspection.

The adequacy or efficiency of any hot water heater cannot be determined in alimited time visual inspection. It is not known how hot water will get or howlong it will last and this is many times a matter of personal preference.

Page 19: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 13All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

ELECTRICAL SYSTEM

Electrical features are operated with normal controls. The general wiring, switches, outlets and fixtures are randomly checkedin accessible areas. While some observations may be code related, this inspection does not determine if the system complieswith code. The inspection does not determine electrical capacity, determining over current capacity for any item includingappliances, comparing circuit breaker capacity to installed appliance listings; interior or exterior low voltage wiring or fixtures;telephone, security, intercom, stereo, cable or satellite TV, remote controls or timers. The exterior lighting, landscape lightingor any lighting outside the footprint of the building is not inspected. Light bulbs are not removed or changed during aninspection. This inspection does not certify or warrant the system to be free of risk of fire, electrocution or personal injury ordeath.

ELECTRICAL OVERVIEWThe electrical system appears to have been through a number ofalterations, modifications or renovations. However the quality of therenovations, or some of them, is not up to professional standards. Thiscondition often conceals defects that are not easily observed during ageneral visual inspection such as this.

MAIN ELECTRICAL SUPPLY:PATH OF ELECTRICALSUPPLY:

The electricity is supplied by an underground line to the building.

ELECTRICAL SUPPLYCONDITION:

Serviceable.

MAIN SUPPLY PANEL :

Page 20: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 14All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

PANEL LOCATION:Inside the building atthe rear storage room.

MAIN PANEL SPEC'S:Single Phase 120/240 volts.

Service Amperage rating - 400.

MAIN PANEL PROTECTIONDEVICE:

The main panel disconnect is a lever.

BREAKER SYSTEM:Needs Attention:

The panel is missing some required labels. This is a safety issue. Eachpanel and breaker is required clearly visible label as to its size and whatarea it serves.

GROUNDING SYSTEM:The connection of the grounding wires to the grounding system was notviewed. It should be connected to a grounding rod and/or the cold waterpiping system but in many cases these connections are not observable and arecovered over within the building.

MAIN PANEL CONDITION:Needs Attention:

The main service to the site is aged and may be nearing the end of itsexpected useful life. This appears to be the original main service to thebuilding. While the system is generally working, review is advised by aqualified electrical contractor for safety and to determine whetherrepairs/improvements are necessary for the purpose of prolonging thesystem's useful life.

Page 21: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 15All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

The main electrical panel does not have three feet of clearance in frontof it as is required for safe access.

MAIN SUPPLY PANEL 2:PANEL LOCATION:

Inside the building atthe rear storage room.

MAIN PANEL SPEC'S:This is a single phase, 3 wire system.

120/240 volts.

Service Amperage rating - 200.

MAIN PANEL PROTECTIONDEVICE:

The main panel disconnect is a circuit breaker.

BREAKER SYSTEM:Serviceable.

GROUNDING SYSTEM:The visible portion of the grounding system, where the main panel connectsto what appears to be a cold water pipe of the plumbing system andgrounding rod, appears serviceable. Much of the grounding system wiring isnot fully visible.

It is noted that the outlets tested in the interiors of the building did prove tohave proper grounding overall.

Page 22: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 16All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

MAIN PANEL CONDITION:Needs Attention:

There is more thanone wire connected toa single circuitbreaker, where onlyone wire should beconnected to eachbreaker. This cansometimes causeoverloading of thewires or breakers. Italso can cause thewires to haveimproper contact withthe breaker and arcbetween the wire andbreaker connection.Needs Attention:

The main electrical panel does not have three feet of clearance in frontof it as is required for safe access.

Installation of the panel is improper and non-standard. The electricalpanel has been installed upside down. Further review is advised by aqualified electrical specialist to ensure that the panel has been properlyinstalled and that all required procedures have been followed such aspermitting and inspections with the local building authority.

INTERIOR ELECTRICAL WIRING:TYPE OF WIRING:

The wiring in the unit consists of plastic coated wires.

TYPE OF WIRING CONDUIT:The conduit that carries the wiring is a combination of different types whereobserved.

Page 23: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 17All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

WIRING CONDITION:Needs Attention:

There are areas ofexposed and/ordangling wiring thatare not properlysecured.

OUTLETS:CONDITION:

A representative sampling of outlets were tested and those that were checkedwere found to be in working order.

OUTLET COMMENTS:It is recommended that Ground Fault Circuit Interrupter (GFCI) safetyoutlets be installed at the exterior, restrooms, & any kitchen outlets. Not all the outlets may have these at the proper locations. This isadvised for health and safety.

SWITCHES:CONDITION:

Needs Attention:

There are switchesfound and it is notknown what exactlythey operate. Thesemay be for burned outbulbs, or these mayoperate switchedoutlets or other items,but were not traced,located or tested. It isadvised to check withthe owner regardingthese, such as in theupstairs office.

Page 24: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 18All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

FIXTURES:CONDITION:

The fixtures observed of the property appeared to be serviceable overall.

FIRE SUPPRESSION & SAFETY SYSTEMS:FIRE SAFETY SYSTEMS:

This type of building site is required to have certain fire safety items,such as exit signs and/or fire extinguishers. It is advised to check withthe local Fire Marshal to determine if this building meets current firesafety regulations.

EXTERIOR ELECTRICAL:CONDITION:

Inspection of the exterior lighting outside the building and on the grounds istypically not part of the inspection.

ELECTRICAL COMMENTS AND RECOMMENDATIONS:ELECTRICAL SYSTEMRECOMMENDATION:

It is advisable to have an electrician examine the system and make allneeded repairs to ensure a properly installed and correctly operatingelectrical system. It is expected that when the electrical specialist checksout the system they will find more problems as this is a generalinspection and not designed to list every fault but to isolate areas inneed of further detailed inspections.

Low voltage lighting and wiring is excluded from a standard propertyinspection including outdoor lights, phone lines, security systems and speakersystems. Regular voltage exterior lighting is also excluded.

The wiring is enclosed within the walls and ceilings and other parts of thestructure. It is not visible and its condition cannot be fully determined. Norepresentation is made as to its status.

Page 25: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 19All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

HEATING AND COOLING SYSTEM

While some observations may be code related, this inspection does not determine if the system complies with building codes. Weather permitting a representative sampling of the systems are operated with normal controls. In order not to damage thesystem, the air conditioners are not activated if the outdoor temperature is below 65 degrees. Gas furnaces are not checked forcarbon monoxide leakage or fire risks. There are carbon monoxide and fire detection devices which can be purchased andinstalled, which we recommend. Air ducts and registers are randomly checked for air flow. Heat exchangers are specificallyexcluded from the inspection, due to being visually obstructed by the design of the system and a complete inspection requiresspecial tools and disassembly, which is beyond the scope of the inspection. The following are additional items that are beyondthe scope of the inspection: balance of the air flow, capacity or velocity of the air flow, humidifiers, air duct cleanliness, theability of the system to heat or cool evenly, the presence of toxic or hazardous material or asbestos, system refrigerant levels,cooling or heating capacity to determine if its sufficient for the building, electronic air filters, solar equipment andprogrammable thermostats. Units that are shut down with not be tested or operated. Determining the remaining life of thesystem is based on industry standards. Window A/C's are not built in units and therefore not usually inspected.

HVAC OVERVIEW:The HVAC systems for this property are in varying conditions. Someare in overall serviceable condition and some are in need of maintenanceand/or repairs.

Due to the age of the units, approximately 10 years or more since thedate of manufacture, the presence of the coolant known as R22 istypical. This coolant is no longer allowed to be used and if repairs areneeded that involve installing more coolant for any reason, replacementof the unit is usually warranted.

SYSTEMLOCATION:

There are 6 heating and cooling units located on the roof.

Page 26: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 20All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

LOCATION CONDITION:

Needs Attention:

The units are sitting on wooden blocks. This is not a reliable methodregarding moisture intrusion. It is advised to have platforms with metalcaps installed to help ensure a leak free condition.

SYSTEM TYPE:The heating and cooling systems for the building are known as "RoofPackages". This is the type of system where the gas heating furnace and theelectric air conditioning (cooling) components are packaged inside onecontainer and perform both functions from this common location on the roof.

SYSTEM AGE:The units are various ages and conditions.

One unit is approx. 22 years old.

One unit is approx. 13 years o.d

The remaining 4 units appear to be between 3 to 7 years old.

CONDENSATE LINE:Serviceable. The condensate line appears properly drained to an authorizedlocation for the removal of condensate liquid.

THERMOSTAT:Serviceable.

VENTING:Serviceable.

Page 27: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 21All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

RETURN AIR AND FILTERS:Needs Attention:

Some of the air filtersare dirty and need tobe replaced.

DUCTING:

Needs Attention:

The seals on the ducting do not appear to be water tight. Maintenanceis needed at this time to ensure a leak free condition.

Page 28: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 22All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

Needs Attention:

There is ducting on the roof that are rusted.

Most of the ducts are in the ceiling and not accessible or fully visible.

Needs Attention:

There is ducting on the roof that has improper sealing material appliedto them. This type of sealer is not designed for exposed roofing ducts.

ELECTRICAL DISCONNECT:Serviceable.

The units do have an electrical disconnect within line of sight of a servicingtechnician.

Page 29: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 23All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

HVAC SYSTEM CONDITION:Needs Attention:

One of the heatingand cooling systems(23 years old) is agedand worn and past itsexpected useful life. Asecond unit, (13 yearsold) is nearing the endof its expected useful.While these systemmay still be functionaland working, it isnoted that this type ofsystem has a lifeexpectancy of approx.15 - 20 years. Depending on thequality ofmaintenance, thesystems are at or nearthis age.

SYSTEMLOCATION:

The condenser for theair conditioning islocated in the rear yard.

Page 30: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 24All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

The heating unit islocated inside thebuilding

SYSTEM TYPE:The heating and cooling system is known as a "split system" heat pump. Thisis an HVAC system with an electric forced air heater that is usually enclosedwithin the building and a separate but connected AC condenser at theexterior.

SYSTEM AGE:The system is approx. 23 years old.

Per industry standards the expected useful life of a condenser unit such as thisis approx. 15 - 20 years depending on the frequency and quality ofmaintenance. The expected useful life of the interior furnace unit such as thisis approx. 20 - 30 years depending on the frequency and quality ofmaintenance.

CONDENSATE LINE:Needs Attention:

There is no secondarycondensate lineinstalled (the primaryand secondary line areconnected). All airconditioning pullsmoisture from the airand this moisture hasto be takensomewhere. There issupposed to be a maincondensate line to dothis and a back up incase the primary linefails. The secondary

Page 31: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 25All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

backup line is missing.

THERMOSTAT:Serviceable.

RETURN AIR AND FILTERS:The air filters were not observed.

DUCTING:Most of the ducts are in the ceiling and not accessible or fully visible.

ELECTRICAL DISCONNECT:Serviceable.

HVAC SYSTEM CONDITION:Needs Attention:

The heating and cooling system is aged and worn. While the systemmay still be functional and working, it is noted that this type of systemhas a life expectancy of approx. 15 - 20 years. Depending on the qualityof maintenance, the system is at or near this age.

HEATING AND COOLING COMMENTS:RECOMMENDATIONS:

Due to the overall condition, replacement of 1 to 2 systems should beanticipated at this time or in the near future.

As units get older more maintenance and repairs should be expected andreplacement should be factored in. Note: the quality of the maintenance canprolong the life of HVAC equipment significantly.

GENERAL COMMENTS:It is advised to keep all units properly serviced and maintained. Properservice and timely repairs can significantly increase the normal expected,industry standard service life.

Per the California Energy Commission, "Beginning October 1, 2005, Title 24of the Building Energy Efficiency Standards requires that ducts be tested forleaks when a central air conditioner or furnace is installed or replaced. Ductsthat leak 15% or more must be repaired"

A property inspection will not be able to determine if this air loss exceeds themaximum allowed of 15%. This test can only be done by a qualifiedtechnician and is beyond he scope of this inspection. It is advised to consultwith a qualified specialist on this matter as the examination may determine

Page 32: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 26All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

that repairs or replacement of the ducting system is required.

Page 33: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 27All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

ROOF SYSTEM

The report is not intended to be conclusive regarding the life span of the roofing system, if it is leak free or how long it willremain leak free in the future. The inspection and report are based on visible and apparent condition at the time of theinspection. The inspection does not address manufacturing defects, fastener appropriateness, if the roof was installed per code,if flashing is present in all locations or the numbers of layers present. Unless a rain has fallen just prior to the inspection, it isnot possible to determine if active leakage is occurring. Not all attic areas are readily accessible for inspection. Tile roofs andsteeply pitched roofs are not safe to walk on and access is limited on them. Conclusions made by the inspector do not constitutea warranty, guaranty, or policy of insurance. All roofs require periodic maintenance to achieve typical life spans and should beinspected annually. Expect to make minor repairs to any roof.

While it is possible some prior repairs and leaks may be reported, it is not the intention of the inspection to identify and reportall prior repairs and conditions. It is recommended to refer to the seller and sellers disclosure about the presence of any roofleaks or prior repairs. Also it should be noted that all gutters have rust and have a limited life span before they need to bereplaced.

ROOF OVERVIEW:Overall the roof is generally serviceable, however there are some areas inneed of repairs or maintenance at this time.

ACCESS TO ROOF:ACCESS TO ROOF:

Access to the roof is viaa ladder that is accessedinside the building.

ACCESS CONDITION:Needs Attention:

The roof access is not up to current OSHA standards and is difficult toclimb over the hatch with the currently installed ladder.

Page 34: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 28All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

HOW ROOF ACCESSED:The roofing was walked on to inspect it.

ROOF:ROOF STYLE:

The roofing system hasa Low Slope to it. Thismeans that the slope ofthe roof appears to beno more than 2" of risefor every 12" ofhorizontalmeasurement.

TYPE OF ROOFINGMATERIAL:

The roofing material on the low sloped roof is multi-layered roofingmaterials.

Page 35: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 29All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

ROOF COVERING STATUS:

Needs Attention:

It is noted that it was raining heavily at the time of the inspection,however there are areas of the roof where water appears to pond andinstead of flowing toward the drains.

Standing water will accelerate the deterioration of roofing materialsaffected. It is advised to eliminate these areas of ponding by improvingthe slope of the roof wherever needed, or to reinforce affected areaswhere slope improvement is impractical.

Page 36: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 30All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

Needs Attention:

There is debris on the roof. It is advised to have this removed.

EXPOSED FLASHINGS:CONDITION:

Needs Attention:

The mastic is cracked in areas and is not reliable to ensure a watertightseal.

ROOF DRAINAGE:

Page 37: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 31All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

ROOF DRAINS:

Needs Attention:

The drains appear to be higher than the immediate surrounding areawhich promotes standing water from rains. It is advised to have thedrains lower than the surrounding areas so that water does not standduring and after rains.

ROOF DRAINAGECOMMENTS:

There are portions of the building that have no guttering system to take theroof water properly off the structure.

This drainage system has the drains in the roof surface and the drain piping isinternal and not visible for the most part. The inspection of this type ofsystem is very limited. It is advised to obtain the history of the performanceof this system from the current tenant. Repairs for this type of system requireinternal wall damage. Yearly maintenance is strongly advised.

ROOF COMMENTS AND RECOMMENDATIONS:RECOMMENDATIONS:

The roofing is in need of maintenance/repairs at this time. It is advisedto have a roofer examine the entire roofing and drainage system andmake any needed repairs or do any maintenance functions needed tohelp ensure a leak free condition at this time.

COMMENTS:It is advised to obtain the roofing Maintenance History for the site. This is tohelp determine the quality of maintenance along with this can be a very strongindicator as to how well the site performs during rains. The quality ofmaintenance can allow a roofing system to perform well past industrystandards regarding typical useful life. Industry wisdom is to have all roofingsystems inspected every year and for any maintenance or repairs to be doneby a qualified professional to help maintain a leak free condition.

California usually has seasonal rains which typically occur near the end

Page 38: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 32All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

and the beginning of each calendar year. Occasionally, the rainfall isexceptionally high. In recent years Southern California has been goingthrough a drought. During drought periods many conditions visiblefollowing rains do not appear. The duty of a building inspector is todisclose visible conditions present at the time of the inspection. If acondition is not visible, it cannot be reported. All roofing systemsrequire regular routine maintenance. It is advised to ensure that theroofing system receives regular routine maintenance.

Page 39: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 33All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

STRUCTURAL SUPPORT SYSTEM

Structural comments are of the conditions observed at the time of the inspection and are the opinion of the inspector and notfact. If further information or facts are needed, they can be obtained through a structural engineer or foundation expert. Theinspection does not determine the potential of the structure to experience future problems, geological conditions or the potentialof the underlying soils to experience movement or water flow or whether the soil is stable. If any form of prior structuralmovement is reported you should expect future movements and possible repairs.

The inspection does not calculate crawl space ventilation capacities, deck and balcony capacity, retaining wall conditions,construction material type, quality or capacity. It does not address the existence of prior repairs, the potential of future repairs,failure analysis, documentation of all possible movement or cracks in floor slabs covered by floor furnishings. It is typical forconcrete floor slabs to have some hairline cracks as a result of the normal drying process of the concrete plus the stressoccurring by settlement and seismic activity. Crawl spaces are observed in a cursory fashion and wood probing is not done andwood damage, dryrot and termites are not part of this inspection but part of the structural pest control operators report.

STRUCTURAL OVERVIEW:Overall the structure appears generally serviceable, however there are someareas in need of further review at this time for health and safety by a qualifiedstructural specialist.

STRUCTURAL FOUNDATION SYSTEM:DESCRIPTION:

The building is supported by a slab foundation system.

SLAB FOUNDATION:SLAB ON GRADE:

This building is on a monolithic slab of concrete.

There were no observable signs of significant settlement or deflection in theslab from observing the finish flooring. It appears to be performing itsfunction of supporting the structure; however, the actual slab itself was notseen and it may appear different once the finish flooring is removed.

By the nature of slab construction the structure would typically be anchored

Page 40: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 34All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

to this concrete slab.

SLAB ON GRADECOMMENTS:

The concrete slab is not visible due to floor coverings, thus any cracks cannotbe seen; however, all concrete has some typical cracking and it is expectedthat this would have such typical cracking if it were fully exposed to view.

STRUCTURAL WALL SYSTEM:This appears to be aWood Frame buildingwith Stucco covering.

EXTERIOR WALLSCONDITION:

Needs Attention:

There appear to have been alterations to the building such as the rear ofthe building where it appears that a carport has been enclosed andconverted to office space. Full disclosure is advised as well as furtherreview of the building history by a qualified general contractor to ensureproper procedures have been followed such as permitting, inspections,etc. by the local building authority.

Page 41: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 35All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

STRUCTURAL COMMENTS AND RECOMMENDATIONS:RECOMMENDATIONS:

Structural components of the building have had additions or alterationsmade to it in the past. Such additions/alterations would typically becarried out pursuant to approved engineering, work permits, progressand final inspections of all work performed. The full extent of the workthat was carried out is not known. It is advised to obtain any plans orpermits relating to this or other work on the structure and property.

Page 42: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 36All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

EXTERIOR

The exterior is viewed in a cursory fashion. Areas of the exterior that are hidden from view by vegetation or stored itemscannot be judged and are not a part of this inspection. Minor cracks are typical in many exterior wall coverings and most donot represent a structural problem. Peeling and cracking exterior paint on windows, doors and trim allow water to enter andcause damage and deterioration. It is important to keep these exterior surfaces properly painted and/or sealed. Many timeschimneys have hidden undisclosed cracks that cannot be seen. A chimney specialist inspector should be employed to determinethe true condition of the structure of any chimney as it is beyond the scope of this inspection to determine damage to chimneys.All exterior grades should allow for surface and roof water to flow away from the foundation and exterior walls.

EXTERIOR OVERVIEW:Overall the exteriors are generally serviceable, however there are some areasin need of repairs or maintenance at this time.

EXTERIOR COVERING OF THE BUILDING:MATERIAL:

The exterior building covering is stucco.

CONDITION:Serviceable.

Some areas of typical wear were noted.

EXTERIOR WINDOW SURFACES:

Page 43: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 37All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

MATERIAL:

The exterior window surfaces are various types of materials.

CONDITION:Needs Attention:

There are areas ofdeterioration to someof the wood windowsills.

EXTERIOR DOOR SURFACES:MATERIAL:

The exterior door surfaces are vinyl.

Page 44: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 38All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

CONDITION:Serviceable overall.

EXTERIOR STAIRS:CONDITION:

Serviceable.

RAILINGS:CONDITION:

Serviceable.

DECKS AND BALCONIES:TYPE:

Page 45: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 39All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

EXTERIOR COMMENTS AND RECOMMENDATIONS:EXTERIORRECOMMENDATIONS:

It appears only typical and routine maintenance will be needed.

COMMENTS:This inspection is not a structural pest control inspection, otherwise known asa termite inspection. The "termite" inspection also covers such things as dryrot and wood damage and deterioration as well as wood destroyingorganisms. Any and all of these items need to be examined and any repairscompleted by the "termite" company in a timely manner and they usually havea guarantee on their work. Please refer to the structural pest control reportfor any information concerning them

This is not a mold or fungus inspection, it is therefore advised to have a moldspecialist examine the property and structure and do a complete inspection todetermine the presence or not of any mold that may affect the health or safetyof the occupants.

Page 46: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 40All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

GROUNDS

This inspection is not intended to address or include any geological conditions or site stability information. For informationconcerning these conditions, a geo-technical engineer should be consulted. Proper grading is important to keep water awayfrom the foundation. If it is not raining during the inspection the course of water flowing toward the structure or off the sitecannot be observed. The soil should slope away from the structure to prevent problems caused by excess water not flowingaway properly. Gutter discharge should be directed away from the foundation for the same reason. Out buildings, such asstorage sheds, on the property are excluded from the inspection. Fire pits, a B.B.Q. and other similar items are not inspectednor is the gas to them tested or lit.

This inspection is visual in nature and does not attempt to determine drainage performance of the site or the condition of anyunderground piping, including municipal water and sewer service piping or septic systems. Landscape lighting, sprinklers andtheir timers are not part of a general property inspection. The inspection report does not include the identification of theproperty boundaries.

MAIN ENTRY:CONDITION:

Serviceable.

WALKWAYS:CONDITION:

Serviceable.

PARKING AREA:

Page 47: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 41All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

PARKING LOT:

Needs Attention:

The parking area asphalt has areas of wear, weathering anddeterioration to the point that resurfacing should be stronglyconsidered.

PROPERTY WALLS, FENCES & GATES:CONDITION:

Serviceable.

LANDSCAPING:CONDITION:

This grounds of this property have no landscaping at this time.

DRAINAGE:SITE:

Relatively flat site.

Page 48: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 42All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

DRAINAGE CONDITION:There were no significant observable defects in the grading and drainagewithin six feet of the building.

The site is a relatively flat site, it is expected that there will be some areaswhere water will pool during rainy periods.

COMMENTS:Determining the adequacy of the grounds to shed water and prevent moistureintrusion into the structure is beyond the scope of the inspection. It isadvised to obtain the history of any drainage problems and monitor the siteregarding water run-off and drainage in general.

This inspection does not address drainage issues further than 6 feet from thebuilding. Additionally drainage systems that are not visible such asunderground systems are not evaluated or inspected. If more information isrequired it is advised to consult with a qualified general contractor whospecializes in drainage systems.

GROUNDS COMMENTS:GROUNDSRECOMMENDATIONS:

The site is in need of maintenance and repairs at this time.

GENERAL COMMENTS:Low-voltage systems such as phone, cable, internet or grounds lightingon the site are not part of the real estate inspection.

This report does not include identification of property boundaries. Ifthis information is desired, it is advised to consult with a qualifiedprofessional.

California usually has seasonal rains which typically occur near the endand the beginning of each calendar year. Occasionally, the rainfall isexceptionally high. In recent years Southern California has been goingthrough a drought. During drought periods many conditions visiblefollowing rains do not appear. The duty of a building inspector is todisclose visible conditions present at the time of the inspection. If acondition is not visible, it cannot be reported.

Page 49: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 43All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

INTERIORS

As a general rule, cosmetic deficiencies are considered normal wear and tear and are not reported. The condition of wallsbehind wall coverings, paneling and furnishings cannot be judged. Minor cracks are found on interior surfaces in all buildingsand are typically cosmetic in nature. The condition of floors underneath carpet, furniture and other coverings cannot bedetermined and is specifically excluded from the inspection and report. Only the general condition of visible portions of floorsis included in this inspection.

INTERIOR AREAS:OVERALL:

Finishes, surfaces and fixtures of the interiors were found to be generallyserviceable.

The property appears to be the product of past modifications and alterations.The properness of all such construction and renovation is beyond the scopeof a limited time, general building inspection. It is recommended to obtain allrecords of plans, permits, progress and final inspections for such work,usually available through contact with the municipal Department of Buildingand Safety.

ENTRY:Serviceable.

MAIN ENTRY DOOR:Serviceable.

STAIRWELLS:Serviceable.

Page 50: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 44All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

STAIR CONDITION:Serviceable.

RAILING CONDITION:Needs Attention:

The railing does notreturn to the wall butstops with the end ofit exposed. This isconsidered a safetyhazard as the end of itcould catch a garmentor handbag and causesomeone to trip or fall.

EXIT SIGNS:

Needs Attention:

Location and quantity of exit signs for a commercial property arebeyond the scope of this inspection and require a specialty inspection todetermine if all requirements are being met. However, from anexamination of the property, there are inadequate numbers and type ofrequired exit signs present.

It is recommended to consult with the Fire Marshal's office to determinecurrent standards.

Page 51: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 45All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

OFFICE AREAS:OFFICE AREAS:

Serviceable overall with typical wear.

Needs Attention:

It is noted that the rear offices on the first floor appear to have beenaltered from the original construction design. Full disclosure is advisedas well as further review of the building history by a qualified generalcontractor to ensure proper procedures have been followed such aspermitting, inspections, etc. by the local building authority.

Page 52: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 46All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

2ND FLOOR OFFICE AREAS:

Serviceable overall with typical wear. These areas are currently vacant.

KITCHENS:KITCHEN FACILITIES:

The kitchenette / breakroom was found to bein generally serviceablecondition regardingsurfaces, finishes andfixtures.

Page 53: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 47All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

RESTROOMS:INTERIORS:

Ground floor - The interior surfaces, such as the walls, ceiling and such werefound to be serviceable.

RESTROOM FIXTURES:Needs Attention:

There is no hot water provided to the sink, which is required forsanitary purposes.

RESTROOMS:INTERIORS:

Upstairs - The interior surfaces, such as the walls, ceilings and such aregenerally aged and worn, but remain serviceable.

RESTROOM FIXTURES:Women's Restroom

Needs Attention:

The sink drains slowly.

Page 54: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 48All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

Needs Attention:

There is no or insufficient hot water to the sinks. This is required forhygienic reasons.

DOORS:EXTERIOR DOORS

Serviceable.

Some wear was noted.

INTERIOR DOORS:Needs Attention:

Some of the doors aresealed shut such as onthe second floor.

WINDOWS:WINDOW CONDITION:

Needs Attention:

Some windows do notwork well and aregenerally difficult tooperate. They willneed adjustments orrepairs to operateproperly.

Page 55: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 49All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

FLOORS:FLOORING CONDITION:

Needs Attention:

The carpeting is generally worn.

WALLS AND CEILINGS:CEILINGS:

Needs Attention:

The ceilings are spraytexture material. Ifthe originalconstruction is before1978 it is possible thatthis spray containsasbestos materials. The only way todetermine if this is thecase is to have asample taken andexamined by aqualified professionallab.

Page 56: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 50All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

Needs Attention:

There are repairs andrough patching on theceiling.

WALLS:Needs Attention:

There are areas ofdamage to the walls. Itappears to be smokeor fire damage.

MISCELLANEOUS PLUMBING:SINK:

Page 57: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 51All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

FIRE SAFETY SYSTEMS:FIRE SAFETY COMMENTS:

This type of building site is required to have certain fire safety items. These are items such as exit signs and fire extinguishers. It is advised tocheck with the local Fire Marshal to determine if this building meetscurrent fire safety regulations.

INTERIOR COMMENTS AND RECOMMENDATIONS:RECOMMENDATIONS:

Due to observed alterations of the interior that do not appear to beoriginal or what appear to be obviously done after the originalconstruction it is advised to have a qualified general contractor reviewall building permits with the local department of building and safety toensure all proper procedures have been observed.

This inspection is not a structural pest control inspection, otherwiseknown as a termite inspection. The "termite" inspection also coverssuch things as dryrot and wood damage and deterioration as well aswood destroying organisms. Any and all of these items need to beexamined and any repairs completed before the close of escrow by the"termite" company and they usually have a guarantee on their work. Please refer to the structural pest control report for any informationconcerning them.

GENERAL COMMENTS:This is a general visual inspection, there was no destructive or intrusiontesting performed. The intention of this report is to inform the client of theoverall condition of the property.

It is typical when a building is remodeled or repairs are undertaken thatadditional problems surface that were not noted on the inspection report.This is to be expected as walls, floors and ceilings are opened up during thework to reveal areas that were not accessible during the inspection. Anyremodeling work undertaken on a property should be expected to revealsome of these problems and it is recommended that additional sums be setaside for this purpose.

Page 58: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 52All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

INSPECTION LIMITATIONS

SPECIFIC EXCLUSIONS AND LIMITATIONS:OUR GOAL:

Our Goal is to enlighten you as to the condition of the property by identifyingmaterial defects that would significantly affect the property and thereforeyour decisions concerning it. We strive to add significantly to yourknowledge of the building. Thus the goal is not to identify every defectconcerning the property but focus upon the material defects andthereby put you in a much better position to make an informed decision.

GENERALIST VS.SPECIALIST

A property inspector is a generalist and the inspection is conducted alonggeneralist guidelines as listed above. The generalist job is to note materialdefects in the property he is inspecting. When he observes and finds one ormore problems in a system of the property that affects its performance hemay then refer the entire system over to a specialist in that field for a furtherdetailed investigation. The specialist is expected to conduct a more detailedexamination on that system from his specialist sphere of knowledge andtraining to determine all the problems with the system and the related costs ofrepairs. The specialist is inspecting from a depth of knowledge andexperience that the generalist does not have.

REPRESENTATIVESAMPLING:

The building has many identical components such as windows, electricaloutlets, etc. We inspect a representative sampling of these only. We do notmove any furniture or personal belongings. This means that some deficiencieswhich were there may go unnoted or there may be items which are impossibleto anticipate. We suggest that you plan for unforeseen repairs. This is partof property ownership as all buildings will have some of these repairs as wellas normally occurring maintenance.

USE OF THE REPORT:The inspection report does not constitute a warranty, insurance policy orguarantee of any kind. It is confidential and is given solely for the use andbenefit of the client and is not intended to be used for the benefit of or berelied upon by any other buyer or other third party.

PRE-INSPECTIONAGREEMENT:

Terms and conditions crucial to interpretation of the report are contained in aseparate pre-inspection agreement. Do not use this report without consultingthe pre-inspection agreement as use of this report constitutes the acceptanceof all the terms, conditions and limitations in that agreement.

Page 59: Macauley Ekpenisi - Commercial Real Estate …...Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Ekpenisi - 14401 Gilmore St, Van Nuys CA 91401

Commercial Real Estate Inspections, LLC. 2550 Honolulu Ave.#101, Montrose, CA, 91020 Page 53All Rights Reserved Copyright 2007 Phone 818.957.4654 Fax 818.949.4435 www.creillc.com

MOLD, MILDEW ANDFUNGI:

Mold, mildew and fungus are specifically excluded from the inspection andthe report. The inspector is not qualified to note the presence or absence ofmold. Mold can be a serious problem and should not be overlooked. Thestructure should be inspected for mold during the inspection contingencyperiod by a specialist in this field to ensure that this hazard does not exist.

WOOD DESTROYINGORGANISMS:

Termites, dry rot, wood rot and wood destroying organisms are covered by astructural pest control operator's report. These are not part of the inspectionand the inspector will not be inspecting for them. The Business andProfessions Code prohibits anyone but licensed structural pest controloperators from commenting on this subject.

BUILDING CODES:This is not a building code or code compliance inspection. That is a differenttype of inspection performed by the local municipality, usually duringconstruction. It is advised to obtain all available documentation such asbuilding permits and certificates of occupancy during the inspectioncontingency period.

HAZARDOUS SUBSTANCES:Identifying hazardous substances is not part of this inspection. Items such asformaldehyde, lead based paint, asbestos, toxic or flammable chemicals andenvironmental hazards are not tested for and are not within the scope of theinspection.

INSPECTION LIMITATIONS:This is a limited time visual inspection. It excludes any items we cannotdirectly observe such as chimney interiors, furnace heat exchangers,underground piping, etc. These are specialty inspections and thoseinspections can be arranged using specialized equipment.

Additionally we do not inspect to see if components are installed properly. We do not have the specialized training, instruction sheets or manuals todetermine if they meet manufacturer's or building code requirements forinstallation, which can be quite varied. This is part of the specialist'sinspection and any questions concerning installation would best be answeredby the specialist