10

MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

MAGNETIC OIL LEVEL GAUGEDial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm)Contacts : Single or Multiple l Conservator Type : Conventional or Aircel

Float movement : Radial or Axial

AT01R1

India Relevant Models Only

l Available With 4-20mA Output

Page 2: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

SCHEMATIC (REPRESENTATIONAL ONLY)

Float

Gear & PinionPointer

Dial

Cam

Magnet MagnetMaterial Wall

In Air In Liquid

Micro Switch

CONSTRUCTION & WORKING MOUNTING SWITCH

The 'ATVUS' Magnetic Oil Level Gauge A suitable pad has to be provided to The indicator oil level gauge is factory consists of the main body with following mount the indicator. The mounting can calibrated to operate the switch at low / sub-assembly / parts : be done vertically or at an inclination to very low / high levels in any combination

facilitate easy viewing. as required by customer. 1. Gear assembly 2. Magnetic couple The indicators are normally mounted at The 'ATVUS' Indicator Oil level gauges 3. Float with arm the center of one end of the conservator can be used for varied purposes. In a 4. Cam assembly with micro switch or at the bottom. The different mounting transformer they are mounted on the 5. Dial with pointer positions are illustrated with individual conservator to read oil level in

models. hermetically sealed transformers. They The schematic diagram of the full are also mounted on side wall tank with assembly is shown below. radial float movement.

The float is hinged and swings up or down when oil level rises or falls. This rise or fall rotates the bevel gear and thus the pinion of the gear assembly. The pinion in turn rotates the driving magnet inside the conservator. The follower magnet positioned outside carries a pointer and a cam. The pointer reads oil level and the cam is set to operate the micro switch at a predetermined low level.

CALIBRATION

The dial is calibrated as per customers specification. Hence a drawing showing heights of oil levels inside the conservator at corresponding marking on dial should be made available.

We also provide a questionnaire for specifying your requirement.

Alternately calibration can be provided to ATVUS internal specification.

AT A GLANCE

Operating Liquids

Working PressureEnvironmentElectric SwitchContact RatingSwitch Operation

IP ProtectionDial SizeDial Marking

Transformer oil to IS 335. Other liquids on request.

As per drawing.

Std: Black on white marking. Customized options possible

Micro Switch SPST

0 to 4 Kg/Sq. Cm. Suitable for indoor & outdoor use.

Low Level (LOLA)/ Low and Very Low Level (LOLA & VLOLA) / Low and High Level (LOLA & HOLA) IP 67 / IPX7 100, 150, & 250 mm.

Page 3: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

CONVENTIONAL CONSERVATOR SO4 (100mm) AND SO6 (150mm)

FEATURESAll aluminium and brass body and components

Use of rare earth magnets for perfect coupling

Every unit tested for porosity test

Solid Nitrophyl float for lifetime trouble free performance.

Low level alarm contact standard.

Vertical or inclined mounting.

FRONT VIEW

SIDE VIEW

FLOAT MOMENT FORCONVENTIONAL MOLG

Dial:Switch :

Mounting :Switch Wiring :

4-20 mA output :

Standard or CustomisedLow Level Alarm (LOLA) Low & High Level Contacts (LOLA+HOLA) Low & Very Low Level Contacts (LOLA+VLOLA)Vertical, 15° or 30°Single Switch : 1 NO or 1 NC availableDouble Switch : Both switches NO, both switches NC or any combination thereofIntegrated type and separate CCU typeavailable

VARIETY AVAILABLE

Page 4: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

AIRCEL CONSERVATOR S04 (100mm) AND SO6 (150mm)

FEATURESInhouse facility of conservator with air cell to checkperformance with rising and falling oil levelInterchangeable with other makes.Individually calibrated and tested.Float arm length with solid float train assembly,in line with international specification.

FRONT VIEW

SIDE VIEW

Dial :Switch :

Mounting :Switch Wiring :

4-20 mA output :

Standard or CustomisedLow Level Alarm (LOLA) Low & High Level Contacts (LOLA+HOLA) Low & Very Low Level Contacts (LOLA+VLOLA)Vertical, 15° or 30°Single Switch : 1 NO or 1 NC availableDouble Switch : Both switches NO, bothswitches NC or any combination thereofIntegrated type and separate CCU type available

VARIETY AVAILABLE

FLOAT MOMENT FORATMS MOLG

Page 5: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

FEATURES

S 4 WITHOUT SWITCH, 100mm DIALo

VARIETY AVAILABLE

Radial type available in switched models alsoCustomized dials available

L = ADJUSTABLE OR FIXED FLOAT ARM LENGTH.PROVIDED TO CUSTOMER SPECIFICATION

X

MOLG

FULL

EMPTY

L

20

12

40

30

165 PCD

6

EMPTY

3/41/4

1/2

MADE IN INDIA

R

FULL

Radial or axial dial movementGenuine 100 mm dial with economical designMagnetic coupling allows no possibility ofoil leakage

Page 6: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

CONVENTIONAL CONSERVATOR S010 (250mm)

FEATURES

Switch Wiring : Single Switch : 1NO or 1NC available

VARIETY AVAILABLE

Low & High Level Contacts (LOLA+HOLA) Low & Very Low Level Contacts (LOLA+VLOLA)

Dial : Standard or CustomisedSwitch : Low Level Alarm (LOLA)

Mounting : Vertical, 15° or 30°

Double Switch : Both switches NO, both switches NC or any combination thereof

FRONT VIEW SIDE VIEW

Single piece aluminium housing.Front view toughened glass replaceable.Use of rare earth magnets for perfect coupling.Solid Nirtophyl float assemblyVery simple and robust internal design

MADE IN INDIA

TERMINAL BOX

V 4 0 1 6 H

OPTION - BPLUG & SOCKET

OIL LEVEL INDICATORMODEL:SIZE:

SR. NO:

R

VIAT INSTRUMENTS PVT. LTD.

INDIA

VERTICAL AND INCLINEDMOUNTED POSSIBLE

FULL

EMPTY CO

NS

ER

VA

TO

R D

IA

.MOLG

8 Studs M10 at PCD 225 6 Studs M10 at PCD 127

43

13

231

3/4"BSC THD.

5

FLOAT ARM LENGTH PROVIDED

TO CUSTOMER SPECIFICATION

OPTION - ATERMINAL BOX

MOUNTING DETAILV - VERTICAL

SWITCH CONNECTIONL - (LOLA :- LOW OIL LEVEL ALARM)LL - (LOLA VLOLA :- LOW OIL LEVEL ALARM & VERY LOW OIL LEVEL ALARM)LH - (LOLA HOLA :- LOW OIL LEVEL ALARM & HIGH OIL LEVEL ALARM)

MOUNTING PCD225 :- 8Nos HOLE 225 PCD127 :- 6Nos HOLE 127 PCD

CONNECTION TYPEST-TERMINAL BOX2C - ALARM SWT ONLY PLUG AND SOCKET CONNECTOR5C - ALARM AND TRIP SWT ONLY PLUG AND SOCKET CONNECTOR

SO10 NORMAL X X 225 X

FLOAT MOVEMENT CROSS SECTION

DETAIL OF MOUNTING

Page 7: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

AIRCEL TYPE CONSERVATOR S010 (250mm)

FEATURESSingle piece aluminium housing.

Front view toughened glass replaceable.

Use of rare earth magnets for perfect coupling.

Solid float train assembly.

Very simple and robust internal design.

In house facility of conservator with air cell to checkcalibration.

Switch : Low Level Alarm (LOLA)Dial : Standard or Customised

Double Switch : Both switches NO, both switches NC or any combination thereof

Low & Very Low Level Contacts (LOLA+VLOLA)Mounting : Vertical, 15° or 30°Switch Wiring : Single Switch : 1NO or 1NC available

VARIETY AVAILABLE

Low & High Level Contacts (LOLA+HOLA)

50.8

98.0

230

VARIETY AND CODING

MOUNTING DETAILV - VERTICAL

SWITCH CONNECTIONL - (LOLA :- LOW OIL LEVEL ALARM)LL - (LOLA VLOLA :- LOW OIL LEVEL ALARM & VERY LOW OIL LEVEL ALARM)LH - (LOLA HOLA :- LOW OIL LEVEL ALARM & HIGH OIL LEVEL ALARM)

CONNECTION TYPEST-TERMINAL BOX2C - ALARM SWT ONLY PLUG AND SOCKET CONNECTOR5C - ALARM AND TRIP SWT ONLY PLUG AND SOCKET CONNECTOR

SO10 ATMS X X 225 X

MOUNTING PCD225 :- 8Nos HOLE 225 PCD127:- 6Nos HOLE 127 PCD

3/4

Fu

ll

1/4

OIL LEVEL INDICATOR VERTICAL &

13

6

15

0

10

0

Em

pty

AIR CELL

.

8 STUD M10AT PCD 225

6 STUD M10AT PCD 127

7

OPTION - BPLUG & SOCKET

OIL LEVEL INDICATORMODEL:SIZE:

SR. NO:VIAT INSTRUMENTS PVT. LTD.

INDIA

V 4 0 1 5

FULL

3/4

1/4EMPTY

FRONT VIEW

FLOAT ARMGEAR

13

23

1

3/4"BSC THD.

FLOAT

OPTION - ATERMINAL BOX

FLOAT ARM LENGTH PROVIDED

TO CUSTOMER SPECIFICATION

SIDE VIEW

FLOAT MOVEMENT CROSS SECTION DETAIL OF MOUNTING

SOLID FLOAT TRAIN ASSEMBLY

Page 8: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

MOLG WITH 4-20mA OUTPUT : SEPARATE CCU TYPE

1 2

4 5 6 7 E 8 9

MIN W

SPAN ZERO

RESISTANCEARRAY OPENINDICATION

SUPPLY INPUT90-260V AC/DC

N L

+-EARTH

OUTPUT-1 OUTPUT-2

+-+-

VIAT INSTRUMENTS PVT LTDINDIA

OUTPUT-14-20mA

INPUT FROMMOLG(POT)

OUTPUT-24-20mA

SUPPLY INPUT90-260V AC/DC

11

FLOAT ARM LENGTH PROVIDED TO CUSTOMER SPECIFICATION

GEAR

FLOAT ARM FLOAT

POTENTIOMETER

3/4" BSC THD.

C

TERMINAL BOX

B

A

MOLG

MODEL

SIZE

SL NO.

MOUNTING

VIAT INSTRUMENTS PVT. LTD.

MADE IN INDIA

FULL3/4

1/2

1/4EMPTY

TERMINAL BOXMOLG

MODEL

SIZE

SL NO.

MOUNTING

VIAT INSTRUMENTS PVT. LTD.

FRONT VIEWCONVENTIONAL

FRONT VIEWATMS

SIDE VIEW

FEATURESMOLG with 100/150mm dial 4-20mA output(s)Physical pointer and dial and regular electrical contacts are presenton MOLG, besides addition of 4-20mA output. Separate CCU type: Electronic circuit is in separate CCU that isconnected to MOLG and to be placed in the marshalling box.Power input and 4-20mA output from CCU.Each piece calibrated individuallyRemote display available

VARIETY AVAILABLEDial :Conservator: Switch :

Mounting :Switch Wiring :

Standard or CustomisedConventional or AircelLow Level Alarm (LOLA) Low & Very Low Level Contacts(LOLA+VLOLA)Vertical, 15°Single Switch : 1 NO or 1 NC availableDouble Switch : Both switches NO, bothswitches NC or any combination thereof

CURRENT CONVERTER MARKING

118

100

86

60

10

2Nos HOLE

70

35

10

CCU MOUNTING DETAIL

1 2 3 4MIN W

POT

LOLA:- LOW OIL LEVEL ALARM_(1-SWITCH)

VLOLA:- VERY LOW OIL LEVEL ALARM_(2-SWITCHS)

1 2 3 4 5 6MIN W

POT

WIRING DIAGRAM FOR MOLG

Page 9: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

MOLG WITH 4-20mA OUTPUT : INTEGRATED TYPE

FLOAT ARM LENGTH PROVIDED TO CUSTOMER SPECIFICATION

GEAR

FLOAT ARM

FLOAT

POTENTIOMETER

3/4" BSC THD.

L = ADJUSTABLE OR FIXED FLOAT ARM LENGTH.PROVIDED TO CUSTOMER SPECIFICATION

DIN RAIL MOUNTING

INPUT (3-4)85 - 264 VAC

120 - 370 VDC

OUTPUT (1-2) 24 VDC

EMPTY FULL

1/4

1/2

3/4

MADE IN INDIA

C

TERMINAL BOX

B

FILLING LEVEL

DO NOT OPEN

MOLG

MODEL

SIZE

SL NO.

MOUNTING

VIAT INSTRUMENTS PVT. LTD.

TERMINAL BOXMOLG

MODELSIZE

SL NO.

MOUNTING

VIAT INSTRUMENTS PVT. LTD.

MADE IN INDIA

FULL3/4

1/2

1/4EMPTY

DO NOT OPEN

FRONT VIEWCONVENTIONAL

FRONT VIEWATMS

Integrated type: Electronic circuit is integrated inside MOLG and 4-20mA output is available directly from MOLG terminal box. 24 VDC power needs to be supplied to the MOG from a separate (included) power supplyRemote display available

Physical pointer and dial and regular electrical contacts are present on MOLG, besides addition of 4-20mA output.

MOLG with 100/150mm dial 4-20mA output(s)Direct 4-20mA output from MOG itself

Models for Aircel and conventional conservators available

SIDE VIEW

+ - ]]

OUTPUT

POWERINPUT24 VDC

COM NO]

SWITCH-1LOW

ALARM

]

SWITCH-2V.LOWALARM

COM NOOU

TE

RW

IRIN

G 1 2 3 4 5 6 7 8

FROM INCLUDED POWER SUPPLYPLACED IN MARSHALING BOX

MOLG TERMINAL BOXCONNECTION

POWER SUPPLY FOR MOLG(PLACED IN MARSHALING BOX)

VARIETY AVAILABLEDial :Conservator: Switch :

Mounting :Switch Wiring :

Standard or CustomisedConventional or AircelLow Level Alarm (LOLA) Low & Very Low Level Contacts(LOLA+VLOLA)Vertical, 15°Single Switch : 1 NO or 1 NC availableDouble Switch : Both switches NO, bothswitches NC or any combination thereof

Page 10: MAGNETIC OIL LEVEL GAUGE · MAGNETIC OIL LEVEL GAUGE Dial Size : 4” (100 mm), 6” (150 mm) and 10” (250 mm) Contacts : Single or Multiple l Conservator Type : Conventional or

VARIETY AND CODING FOR S04 AND S06

GENERAL NOTES

The calibration and switch setting is factory adjusted and should not be tampered.

We continuously review specifications and where appropriate, introduce modifications.

Indicators with different specifications are not interchangeable.

We therefore, reserve the right to change specifications in this catalogue without prior notice.

Calibration for dial in other units is possible.

HOW TO ORDER

3. Conservator diameter.

4. Oil level inside conservator, corresponding to dial marking.

2. Dial marking.

5. A separate Questionnaire is made available in which details of technical

specifications required by us are given. Please ask for the same.

1. Mounting position of indicator.

S04 | S06 WITHOUT 4-20 MA OUTPOUT

S04 | S06 WITHOUT 4-20 MA OUTPOUT

MOUNTING DETAILV - VERTICAL

SWITCH CONNECTIONL - (LOLA :- LOW OIL LEVEL ALARM)LL - (LOLA VLOLA :- LOW OIL LEVEL ALARM & VERY LOW OIL LEVEL ALARM)LH - (LOLA HOLA :- LOW OIL LEVEL ALARM & HIGH OIL LEVEL ALARM)

SO4 ATMS L X X

DIAL SIZESO4:-100mmSO6:-150mm

CONSERVATOR TYPEBLANK :- CONVENTIONAL TYPEATMS :- AIRCEL TYPE

CONNECTION TYPESBLANK -TERMINAL BOX2C - 1 SWITCH PS CONNECTION5C - 2 SWITCH PS CONNECTION

MOUNTING DETAILV - VERTICAL

SWITCH CONNECTIONL - (LOLA :- LOW OIL LEVEL ALARM)LL - (LOLA VLOLA :- LOW OIL LEVEL ALARM & VERY LOW OIL LEVEL ALARM)LH - (LOLA HOLA :- LOW OIL LEVEL ALARM & HIGH OIL LEVEL ALARM)

SO4 NORMAL X X CCU

CONSERVATOR TYPENORMALATMS

CONNECTIONBLANK:- NO 4-20mA OUTPUT PROVIDEDCCU:- SEPARATE CCU 4-20mA OUTPUT4-20mA:- INTEGRATED TYPE WITH 4-20mA OUTPUT

DIAL SIZESO4 :- 100mmSO6 :- 150mm

Due to our policy of continuous product improvement, dimensions and designs are subject to change.

VIAT INSTRUMENTS PVT. LTD. (UNIT-I)2701-2704, Shilpangan Phase-II, Block LB-1, Sector-III, Salt Lake, Kolkata 700 098, INDIA

Phones : +91 33 23352925, +91 9903805104

VIAT INSTRUMENTS PVT. LTD. (UNIT-II)6, Neelkanth Estate, Iyava, Sanand, Ahmedabad 382 170, INDIA

Phones : +91 0 7575 804128 / 804174

E-mail : [email protected] l Website : www.viatin.com