SoCLEAN ® Level Plus ® Operation Manual Magnetostrictive Liquid Level Transmitters with Temposonics ® Technology

Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

SoCLEAN®

Level Plus®

Operation Manual

Magnetostrictive Liquid Level Transmitterswith Temposonics® Technology

Page 2: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

2

Level Plus® SoClean®

Operation Manual

Table of contents

1. Contact information ....................................................................32. Terms and definitions .................................................................43. Introduction .................................................................................64. Safety instructions ......................................................................6

4.1 Intended use ......................................................................... 64.2 Foreseeable misuse ............................................................... 64.3 Installation, commissioning, and operation .......................... 6

5. Product overview ........................................................................65.1 Components .......................................................................... 75.2 Accuracy ............................................................................... 85.3 Warranty ............................................................................... 85.4 Storage ................................................................................. 85.5 Model number identification ................................................. 95.6 Specifications ...................................................................... 11

6. Installation and mounting ........................................................126.1 Training ............................................................................... 126.2 Tools ................................................................................... 126.3 Stilling wells and guide poles .............................................. 126.4 Installation steps ................................................................. 126.5 Mounting ............................................................................ 12

7. Electrical connections ..............................................................137.1 Basic information ................................................................ 137.2 Safety recommendations .................................................... 137.3 Industrial topologies ........................................................... 137.4 Cable recommendations ..................................................... 147.5 Electrical conduit ................................................................. 147.6 Grounding ........................................................................... 157.7 Safety barriers ..................................................................... 15

8. Commissioning .........................................................................158.1 Training ............................................................................... 158.2 Tools ................................................................................... 158.3 Setup software .................................................................... 158.4 Commissioning steps ......................................................... 15

9. Maintenance .............................................................................169.1 Training ............................................................................... 169.2 Tools ................................................................................... 169.3 Inspection ........................................................................... 169.4 Preventative maintenance ................................................... 16

Repair ........................................................................................ 1710.1 RMA policy ....................................................................... 1710.2 Training ............................................................................. 1710.3 Tools ................................................................................. 1710.4 Troubleshooting ................................................................ 1710.5 Setup software .................................................................. 18

Interface .................................................................................... 1811.1 Modbus ............................................................................. 1811.2 DDA .................................................................................. 18

12. Agency information ................................................................. 1812.1 Approvals overview ......................................................... 1812.2 Certificates ...................................................................... 1812.3 FM ................................................................................... 1812.3.1 Special conditions of safe use ...................................... 1812.3.2 Labels .......................................................................... 1812.3.3 Installation drawing ...................................................... 1912.4 FMC ................................................................................ 2112.4.1 Special conditions of safe use ...................................... 2112.4.2 Labels .......................................................................... 2112.4.3 Installation drawing ...................................................... 2212.5 ATEX and IECEx .............................................................. 2412.5.1 Special conditions of safe use ...................................... 2412.5.2 Labels .......................................................................... 2412.5.3 Installation drawing ...................................................... 2512.5.4 EC Declaration of Conformity ....................................... 27

10.

11.

Page 3: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

3

Level Plus® SoClean®

Operation Manual

1. Contact information

United States

GeneralTel: +1-919-677-0100Fax: +1-919-677-2343E-mail: [email protected]://www.mtssensors.com

Mailing and shipping addressMTS Systems CorporationSensors Division3001 Sheldon DriveCary, North Carolina, 27513, USA

Customer serviceTel: +1-800-633-7609Fax: +1-800-498-4442E-mail: [email protected]

Technical support and applications24 Hour Emergency Technical SupportTel: +1-800-633-7609e-mail: [email protected]

Germany

GeneralTel.: +49-2351-9587-0Fax: +49-2351-56491e-mail: [email protected]://www.mtssensors.com

Mailing and shipping addressMTS Sensor Technologie, GmbH & Co. KGAuf dem Schüffel 9D - 58513 Lüdenscheid, Germany

Technical support and applicationsTel.: +49-2351-9587-0e-mail: [email protected]://www.mtssensors.com

Japan

GeneralTel.: +81-42-775-3838Fax: +81-42-775-5516 e-mail: [email protected]://www.mtssensors.com

Mailing and shipping addressMTS Sensors Technology Corporation737 Aihara-cho, Machida-shiTokyo 194-0211, Japan

Technical support and applicationsTel.: +81-42-775-3838Fax: +81-42-775-5512

Page 4: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

4

Level Plus® SoClean®

Operation Manual

2. Terms and definitions

6A Heavy Oils‘Generalized Crude Oils’, Correction of Volume to 60 °F against API Gravity.

6B Light Oils‘Generalized Products’, Correction of Volume to 60 °F against API Gravity.

6C Chemical‘Volume Correction Factors (VCF)’ for individual and special applica-tions, volume correction to 60 °F against thermal expansion coeffi-cients.

6C ModAn adjustable temperature reference for defining VCF.

A

API Gravity The measure of how heavy or light a petroleum liquid is compared to

water. Allowable values are 0 to 100 degrees API for (6A) and 0 to 85 degrees API for (6B).

D

DDA ‘Direct Digital Access’ – The proprietary digital protocol developed by

MTS for use in intrinsically safe areas.

Density Mass divided by the volume of an object at a specific temperature. The

density value should be entered as lb / cu. ft..

E

Explosionproof Type of protection based on enclosure in which the parts which can

ignite an explosive gas atmosphere are placed within, and which can withstand the pressure developed during an internal explosion of an ex-plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.

F

Flameproof Type of protection based on enclosure in which the parts which can

ignite an explosive gas atmosphere are placed within and which can withstand the pressure developed during an internal explosion of an ex-plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.

FOUNDATION™ fieldbus An all digital, serial, two-way communications system that serves as

the base-level network in a plant or factory automation environment. Developed and administered by the fieldbus FOUNDATION™.

G

GOVI ‘Gross Observed Volume of the Interface’ – The total volume of the tank

occupied by the interface liquid. The GOVI is only given when mea-suring two liquids and is calculated by subtracting the volume of the product from the total volume of liquid in the tank (GOVT – GOVP).

GOVP ‘Gross Observed Volume of the Product’ – The total volume of the tank

occupied by the product liquid. When measuring only one liquid, it is also the total volume of liquid in the tank (GOVT). When measuring two liquids it is the total volume of liquid in the tank minus the volume of the interface liquid (GOVT – GOVI).

GOVT ‘Total Gross Observed Volume’ – The total volume of liquid in the tank.

When measuring only one liquid it is equal to the volume of the product (GOVP). When measuring two liquids it is equal to the volume of the product and interface liquids (GOVP + GOVI).

GOVU ‘Gross Observed Volume Ullage’ – the difference in volume between the

working capacity of a tank and the total volume in the tank (Working Capacity – GOVT).

H

HART® A Bidirectional communication protocol that provides data access

between intelligent field instruments and host systems.

I

Interface Noun; The measurement of the level of one liquid when that liquid is

below another liquid.

Interface Adj.; The Software Graphical User Interface (GUI) that allows the user

to access software protocols (HART, DDA, MODBUS).

Intrinsic safety ‘Intrinsically safe’ - Type of protection based on the restriction of

electrical energy within apparatus of interconnecting wiring exposed to potentially explosive atmosphere to a level below that which can cause ignition by either sparking or heating effects.

Page 5: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

5

Level Plus® SoClean®

Operation Manual

M

Mass The property of a body that causes it to have weight in a gravitational

field, calculated by density at the reference temperature multiplied by the volume correction factor (Density * VCF).

MODBUS A serial communications protocol published by Modicon in 1979 for use

with its programmable logic controllers (PLCs). It has become a de fac-to standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices.

N

NEMA Type 4X A product Enclosure intended for indoor or outdoor use primarily to

provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water; and to be undamaged by the formation of ice on the enclosure. They are not intended to provide protection against conditions such as internal condensation or internal icing.

NPT U.S. standard defining tapered pipe threads used to join pipes and

fittings.

NSVP ‘Net Standard Volume of the Product’ – The temperature corrected

volume for the product liquid in the tank, requires the transmitter to be ordered with temperature measurement capabilities. The NSVP is calculated by multiplying the volume of the product liquid by a volume correction factor based on temperature (GOVP * VCF).

R

Reference Temperature The temperature at which the density measurement is given, the allow-

able values are 32 °F to 150 °F.

S

Specific Gravity The density ratio of a liquid to the density of water at the same condi-

tions.

Sphere Radius The internal radius of the sphere that contains the liquid, the value is

used to calculate the volume along with the Sphere Offset.

Sphere Offset An offset value that accounts for additional volume in a sphere from

non-uniform sphere geometry, the value is used to calculate the volume along with the Sphere Radius.

Strap TableA table of measurement correlating the height of a vessel to the volume that is contained at that height. The transmitter can contain up to 100 points.

T

TEC ‘Thermal Expansion Coefficient’ - a value correlating the change in tem-

perature for an object with the change in its volume. Allowable values are 270.0 to 930.0. TEC units are in 10 E-6/Deg F.

Temperature Correction Method One of five product correction methods used to correct the product

volume in the tank due to changes in temperature from 60 °F including (6A, 6B, 6C, 6C Mod, and Custom Table.

V

Volume Calculation Mode One of two methods use to calculate volume measurements from level

measurements, including Sphere and Strap Table.

VCF ‘Volume Correction Factor’ – A table of measurements correlating

temperature points with correction factors for the liquids expansion/contraction. The transmitter can contain up to 50 points.

W

Working Capacity The maximum volume of liquid that the user desires for their vessel to

hold, typically 80% of the vessels maximum volume before overfill.

Page 6: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

6

Level Plus® SoClean®

Operation Manual

3. Introduction

3.1 Purpose and use of this manual

The content of this technical documentation and of its various annexes is intended to provide information on mounting, installation and commissioning by qualified service personnel according to IEC 60079-14 or MTS trained service technicians and local regulations.

3.2 Used symbols and warningsWarnings are intended for your personal safety and for avoidance of damage to the described product or connected devices. In this documentation, safety information and warnings to avoid dangers that might affect the life and health of personnel or cause material damage are highlighted by the preceding pictogram, which is defined below.

4. Safety instructions

4.1 Intended useThe liquid level transmitter is intended to be used to measure the level of liquid(s) contained by a structure as well as the temperature of the liquid. The product may only be used for the applications defined under item 1 to item 4 below and only in conjunction with third-party devices and components recommended or approved by MTS Sensors. As a prerequisite of proper and safe operation, the product requires correct transport, storage, mounting and commissioning and must be operated with utmost care.

1. Application does not exceed product’s performance specification in section 5.6.

2. Product may only be installed in hazardous areas as specified by approval certifications in section 12 following special conditions of safe use outlined in section 12 or in safe areas.

3. The liquid(s) being measured are compatible with the selected wetted parts of the product.

4. MTS floats should be used for proper functionality and safety approval.

4.2 Foreseeable misuse

Important:Before starting the operation of the equipment read this documentation thoroughly and follow the safety information.

Symbol Meaning

NOTICE This symbol is used to point to situationsthat may lead to material damage, and/or personal injury.

4.3 Installation, commissioning and operation

1. Wear proper personal protection equipment such as hard hat, safety shoes, flame resistant clothing, safety glasses, gloves, and hearing protection.

2. Follow the specifications given in the technical documentation.3. Two (2) individuals are recommended to conduct proper installati-

on, commissioning, and repair of the level transmitter.4. Ensure the equipment used in a hazardous environment is selected

and installed in compliance with regulations governing the geogra-phical installation and facility. Only install equipment that complies with the types of protection relevant to the applicable classes, division, zones, category, gas group, and temperature code.

5. Protect the sensor against mechanical damage during installation and operation.

6. Do not use damaged products and secure them against unintentio-nal use. Mark damaged products as being defective.

7. Connect the sensor very carefully and pay attention to the polarity of connections. MTS recommends to not make connections while power is live.

8. Before turning on power, ensure that nobody’s safety is jeopar-dized by starting level transmitter and/or process.

9. Regularly follow preventative maintenance to prevent safety risks.10. Make sure that no wire strands are loose or sticking out of the

terminal block connection which could short and cause a problem.11. Make sure that no wire strands, including shield, are in contact

with the electronic module enclosure.

5. Product overview

The Level Plus® SoClean® Liquid-Level transmitter is a continuous multi-functional magnetostrictive transmitter that provides product level, interface level, and temperature to the user via Modbus, or DDA. Magnetostrictive technology is one of the most accurate and

Forseeable misuse Consequence

Process Temperature out of rangeSignal Degradation, Possible Damage to SensorSee Section 5.6 for Specifications

Power Supply out of rangeNo Communication, Possible Dam-age to SensorSee Section 5.6 for Specifications

Process Pressure out of rangePossible Damage to Sensor,See Section 5.6 for Specifications

Improper Chemical Compatibility

Possible Damage to Sensor,Customer Must Select Wetted Mate-rial that is compatible with liquid(s) in tank

Modifying SensorWarranty Void, Hazardous Approval Void Customer should contact facto-ry for custom unit

Improper GroundingPossible Damage to Sensor, Full Protection Compromised,See Section 7.6 for Grounding

Forseeable misuse Consequence

Wrong sensor connectionPossible damage to electronicsSee Section 7 for Electrical Connections

Improper InstallationPhysical damage to packagingSee Section 6 for Installation

Installation in unapproved Hazardous Area

Potential SparkSee Section 12 for Agency Information

Table 1: Foreseeable misuse

Page 7: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

7

Level Plus® SoClean®

Operation Manual

Industries » Pharmaceutical » Food & beverage » Cosmetics

Applications » Bioreactor » Day Tanks » Storage tanks

Features » 3-in-1 measurement

» Product level » Interface level » Temperature

» No scheduled maintenance or recalibration » Field repairable » Inherent Accuracy ±1mm » 200 Point Strap Table » API Temperature Corrected Volumes

5.1 ComponentsThe Level Plus® SoClean® liquid level transmitter consists of four main components; a housing, outer pipe, float, and electronics. Varying the components of the transmitter allows the transmitter to be customized to almost any application.

HousingsLevel Plus® SoClean® transmitters are available in three housing configu-rations; NEMA Type 4X 316L stainless steel, explosion-proof single and dual-cavity housings as shown:

Fig. 3: Dual cavity explosion-proof housing

Fig. 2: Single cavity explosion-proof housing

Fig. 1: NEMA Type 4X 316L stainless-steel housing

1

1

2

2

3

3

4

4

A A

B B

C C

D D

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES� � �� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE C LL drawing

1 1

DRAWN BY:

114 mm(4.5 in.)

152 mm(6 in.)

124 mm(4.9 in.)

132 mm(5.2 in.)

87 mm(3.4 in.)

109 mm(4.3 in.)

75 mm(3 in.)

206 mm(8.1 in.)

152 mm(6 in.)

117 mm(4.6 in.)

145 mm(5.7 in.)

1

1

2

2

3

3

4

4

A A

B B

C C

D D

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES� � �� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE C LL drawing

1 1

DRAWN BY:

114 mm(4.5 in.)

152 mm(6 in.)

124 mm(4.9 in.)

132 mm(5.2 in.)

87 mm(3.4 in.)

109 mm(4.3 in.)

75 mm(3 in.)

206 mm(8.1 in.)

152 mm(6 in.)

117 mm(4.6 in.)

145 mm(5.7 in.)

1

1

2

2

3

3

4

4

A A

B B

C C

D D

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES� � �� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE C LL drawing

1 1

DRAWN BY:

114 mm(4.5 in.)

152 mm(6 in.)

124 mm(4.9 in.)

132 mm(5.2 in.)

87 mm(3.4 in.)

109 mm(4.3 in.)

75 mm(3 in.)

206 mm(8.1 in.)

152 mm(6 in.)

117 mm(4.6 in.)

145 mm(5.7 in.)

repeatable level technologies available to date. MTS is the inventor and purveyor of magnetostrictive technology and has been serving the level industry for over 35 years.

Page 8: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

8

Level Plus® SoClean®

Operation Manual

Internal electronicsAll transmitters come with two electronic components of a sensing element and a board set. Rigid sensing elements are standard on SoClean® . Flexible sensing elements are available upon request. The board set consists of up to three electronic boards and a display. The display is capable of displaying the product level, interface level, and temperature. Designed into the display are five buttons for local setup of level transmitter using the stylus.

A temperature sensing function is optional with the SoClean® transmitter. The temperature sensing device is a Digital Thermometer mounted inside the transmitter’s outer pipe assembly. The SoClean® can be ordered with 1, 5, 12, or 16 temperature points.

AccessoriesMTS also offers a series of displays, housings, converters, and other accessories, please refer to the ‘Accessories Catalog’, MTS part number 551103.

5.2 AccuracyFor magnetostrictive transmitters inherent accuracy is measured in terms of non-linearity. Non-linearity is a measurement of any imperfections in the waveguide that are reflected in the linearity of the transmitter’s output. MTS tolerances reflect a maximum non-linearity of ± 1mm. MTS is able to achieve such strict tolerances by manufacturing all of its own waveguide from a proprietary alloy and testing 100% of all transmitters before shipping.

5.3 Warranty

All Level Plus® transmitters come with a two year limited warranty from the factory shipment date. A Return Materials Authorization (RMA) number is required and must accompany any transmitter returns. Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory. A Material Safety Data Sheet (MSDS) must also accompany the transmitter that was used in any process.

5.4 StorageIf storage is required prior to installation, store indoors in a dry environ-ment at ambient temperature range not to exceed -40°C (-40°F) to 71°C (160°F).

Important:Contact Technical Support or Customer Service for assistance if you suspect that the transmitter is not working correctly. Technical support can assist you with troubleshooting, part replacement, and Returned Material Authorization (RMA) information if required.

FloatsSoClean® transmitters offer numerous floats for different applications such as stainless steel, 3-A sanitary, hastelloy, Teflon, and Nitrophyl for both product level and interface level. To be able to accurately detect the interface level there needs to be a difference of at least 0.05 in specific gravities between the product and interface liquids. For detailed information about floats, refer to the ‘Accessories Catalog’, MTS part number 551103.For assistance with selecting a specific float for your application, please contact Technical Support with the following information: » Specific gravity of liquid(s) being measured » Process temperature » Process opening size » Vessel pressure

For ATEX and IECEx approvals, SoClean® transmitters should be used with a float having an offset weight and made of stainless steel or Has-telloy C. This allows the float to stay in contact with the pipe to prevent the buildup of an electrostatic charge. For detailed information about floats, refer to the ‘Accessories Catalog’, MTS part number 551103.Non-metalic floats with a projected surface area of less than 5,000 mm² should only be used in Zone 0, Gas group IIA such as float part numbers 201643-2, 201649-2, 201650-2, 201109, 251115 and 251116. All other non-metallic floats offered by MTS such as, 251939, 251119, 251120 and 252999, should not be used in a hazardous area application.

Outer pipe configurationsThe outer pipe is constructed of a variety of configurations. The SoClean® is available in a sanitary pipe. For other pipe options please consult other MTS options such as RefineMe®, Tank Slayer®, and/or USTDII.

1

1

2

2

3

3

4

4

A A

B B

C C

D D

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES� � �� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE C Marketing

1 1

DRAWN BY:

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***

Order length

Order Length

3/4 in NPTAdjustable fitting

Pipe diameter16mm (0.625 in)

74 mm (2.9 in) minInactive zone

Tip of transmitter

Tank Flange(Provided by customer)

127 [5] minimum

Tank Flange

1 in NPT or BSPP Adjustablecompression fitting, male

127mm [5 in ]

Order Length

Pipe diameter (0.625 in. dia)constructed of 316l stainless steel

Sanitary process connection (sanitary cap)

304.8 mm(12 in.)

Fig. 4: Outer pipe configuration (TB version shown)

Page 9: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

9

Level Plus® SoClean®

Operation Manual

5.5 Model number identification (Order code)

b Output

M Modbus

D DDA

j DT Placement

F Evenly spaced per API

C Custom

X None

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

a Sensor model

L P S SoClean® Level Transmitter

L P S16 17 18 19 20 21 22

a b c d e k

d Electronics mounting

1 Standard

f Materials of construction (Wetted parts)

1 316L stainless steel

2 Electropolished 316L stainless steel

f g h i j l m n o p

c Housing type

A NEMA housing w/cable

B NEMA housing w/terminal

C NEMA housing w/connector

D Single cavity with display

E Dual cavity with display

L SS single cavity w/display

g Process connection type

1 NPT adjustable

2 BSPP adjustable

4 Sanitary Tri-Clamp, Welded

5 Sanitary Tri-Clamp, Adjustable

e Sensor pipe

C Sanitary T-bar, TB

D Sanitary drain-in-place DP

E Sanitary clean-in-place CP

F Sanitary drain-in-place no hole, DN

Note: Contact factory for other materials

h Process connection size

B 1 in. (DN25)

D 2 in. (DN50)

E 2 1/2 in. (DN65)

F 3 in. (DN80)

G 4 in. (DN100)

J 6 in. (DN150)

X None

i Number of DT‘s (Digital Thermometer)

0 None

1 One DT

5 5 DTs

K Twelve DTs

M Sixteen DTs

k Notified body

C CEC (FMC)

E ATEX

F NEC (FM)

I IEC

X None

l Protection method

I IS

X No approval

(Continued on next page)

Page 10: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

10

Level Plus® SoClean®

Operation Manual

n Unit of measure

M Metric - Millimeters

U US customary - Inches

1 2 3 4 5 6 7 8 9 10 11

ORDERING NOTE

Accessories such as floats, cables, and displays have to be ordered separately. All accessories are shown in the Accessories Catalog (551103).

L P S

a b c d e f g h i

Gas group

A Group A

B Group B

C Group C

D Group D

1 IIA

2 IIB

3 IIC

X None

p Special

S Standard Product

m

o Length (no decimal spaces)

X X X X X Rigid Pipe: 12 to 300 in (code as 01200 to 30000)

X X X X X Rigid Pipe: 305 to 7620 mm (code as 00305 to 07620)

12 13 14 15 16 17 18 19 20 21 22

kj l m n o p

5.5 Model number identification (continued)

Page 11: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

11

Level Plus® SoClean®

Operation Manual

Level Output

Measured variable Product level and interface level

Output signal /Protocol Modbus RTU, DDA

Order length Sanitary Pipe: 305 mm (12 in.) to 7620 mm (300 in.) Ƥ

Inherent Accuracy ±1 mm (0.039 in.)

Repeatability 0.001% F.S. or 0.381 mm (0.015 in.) *(any direction)

Temperature Output

Measured variable Average and multipoint temperatures

Temperature accuracy ±0.2 ºC (0.4 ºF) range -40 ºC (-40 ºF) to -20 ºC (-4 ºF)*,±0.1 ºC (0.2 ºF) range -20 ºC (-4 ºF) to 70 ºC (158 ºF)*,±0.15 ºC (0.3 ºF) range 70 ºC (158 ºF) to 100 ºC (212 ºF)*,±0.5 ºC (0.9 ºF) range 100 ºC (212 ºF) to 105 ºC (221 ºF)

Electronics

Input voltage 10.5 to 28 Vdc

Fail safe High, Full scale for digital

Reverse polarity protection Series diode

EMC Standards IEC 61326-3-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8

Environmental

Enclosure rating NEMA Type 4X, IP65

Humidity 0 to 100% relative humidity, non-condensing

Operating temperatures Electronics: -40 °C (-40 °F) to 71 °C (160 ºF)Sensing element: -40 °C (-40 °F) to 125 °C (257 °F) ◊Temperature element: -40 °C (-40 °F) to 105 °C (221 °F)

Vessel pressure Rigid pipe: 2000 psi (138 bar)

Materials Wetted parts: 316L stainless steel †Non-wetted parts: 316L stainless steel, Epoxy coated aluminum

Field Installation

Housing dimensions Single cavity:145 mm (5.7 in.) W x by 127 mm (5 in.) D x 109 mm (4.3 in.) H Dual cavity:117 mm (4.6 in.) W x by 127 mm (5 in.) D x 206 mm (8.1 in.) H Stainless steel single cavity:178 mm (7.1 in.) W x by 135 mm (5.3 in.) D x 153 mm (6 in.) H NEMA Type 4X:87 mm (3.4 in.) W x by 124 mm (4.9 in.) D x 132 mm (5.2 in.) H

Mounting

Rigid pipe Tri-Clamp, 3/4 in. Adjustable MNPT or BSPP fitting

Wiring

Connections 4-wire shielded cable or twisted pair, Daniel Woodhead 6-pin male connector,4570 mm (180 in.) integral cable with pigtail

Electrical Connections

Single and Dual Cavity 3/4 in. FNPT conduit opening, M20 for ATEX/IECEx version

NEMA Type 4X 1/2 in. FNPT conduit opening

Display

Measured variables Product level, interface level and temperature

* Whichever is greater ∆ Contact factory for longer lengths.◊ Contact factory for specific temperature ranges.† Contact factory for alternative materials.§ Order length equals the measurement range plus the inactive zone.

5.6 Specifications (Technical data)

Page 12: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

12

Caution:It is recommended that assembly and mounting of this transmitter should not be done alone. To ensure proper and safe assembly of the SoClean® transmitter, a minimum of two (2) individuals are recommended. Gloves are also recommended. PPE is required for work areas such as safety shoes, safety glasses, hard hat, and fire resistant clothing.

Level Plus® SoClean®

Operation Manual

6. Installation and mounting

6.1 Training

Installation should only be conducted by qualified service personnel according to IEC 60079-14 or MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.

6.2 Stilling wells and guide polesLevel Plus® transmitters can be mounted in slotted or unslotted stilling wells but a slotted stilling well is always preferred. Using a unslotted stilling well will negatively affect performance of any level device as the level in the stilling well can differ from the level in the tank. The Level Plus® transmitter can also be installed to one side of the stilling well to also allow for sampling and manual gauging from the same opening as the automatic tank gauging. Contact Technical Support for details.

Level Plus® transmitters do not require a stilling well for installation. Our transmitters are installed in numerous tanks without stilling wells with no loss in performance. A stilling well is highly recommended for agitated, turbulent, and/or fast filling tanks.

6.3 Tools » Channel Lock pliers » Common head screwdriver

6.4 Installation steps

1. Consult Section 4.3 before starting.2. Perform Commissioning Steps 1-9 in Section 8.4.3. For CP end plug, remove hitch pin and install float. For DN end plug, install float but be careful as float is not retained and will fall off. For TB and DP end plugs, the float is already installed. 4. Secure the Tri-Clamp onto the mating connection on tank.5. Tighten the Tri-Clamp to hold the transmitter in place. 6. Terminate the field wire cables noting proper wire orientation.

6.5 MountingThe method of mounting the transmitter is dependent on the vessel or tank in which it is being used, and what type of transmitter is being mounted. There are two typical methods for mounting; threaded flange mounting and welded Tri-clamp mounting.

Page 13: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

13

7. Electrical connections

7.1 Basic informationA typical intrinsically safe connection for the Level Plus® SoClean® trans-mitter includes protective safety barriers, a power supply and a reading or monitoring device. Refer to Agency information in Section 12.

7.2 Safety recommendationsBe sure to:1. Always follow applicable local and national electrical codes and observe polarity when making electrical connections. 2. Never make electrical connections to the SoClean® transmitter with power turned on. 3. Make sure that no wire strands are loose or sticking out of the terminal block connection which could short and cause a problem. 4. Make sure that no wire strands, including shield, are in contact with the electronic module enclosure. 5. The electronics module enclosure is grounded through internal circuitry and is electronically isolated from the explosion-proof housing.

7.3 Industrial topologiesThere are four topologies described and illustrated below. However, the daisy chain topology is not recommended by MTS.

Point-to-pointThe point-to-point topology consists of having only one device on the loop as shown in Figure 8. This topology is not usually used with a bus network since it does not take advantage of placing multiple devices on a loop.

PLC

Level Plus® SoClean®

Operation Manual

Riser

Tank flange(customer suppliedor ordered separately)

Float accessport

Fig. 6: Threaded flange mounting for flexible pipe

Fig. 7: Tri-Clamp mounting for pipe

Tri-Clamp mountingThe SoClean® transmitter can also be mounted to a Tri-Clamp as shown in Figure 7. First, install float(s) onto the transmitter. Second, install the float retaining hardware on the tip of the transmitter. To complete the installation, mount the transmitter, Tri-Clamp and float(s) as a unit in to the tank.

Fig. 8: Point-to-point topology

Threaded flange mountingIn some applications, the SoClean® transmitter can be mounted directly to the tank or flange via a NPT or BSPP threaded fitting, assuming there is a proper threaded connection available. If the float will not fit through the flange opening when the flange is removed, there must be some alternative means to mount the float on the transmitter from inside the vessel; this may require an access port nearby the entry point of the transmitter as shown in Figure 6.

Riser

NPT or BSPP fitting

Tank flange(customer suppliedor ordered separately)

Float accessport

Tip of transmitter

Page 14: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

14

Notes:1. Tighten housing cover (both front and back covers if dual cavity) to full stop against the O-ring.2. Do not over-tighten compression fittings.3. Use side conduit entry only.4. In high humidity areas, use a breather drain type conduit sealing fitting to minimize moisture intrusion.

Conduit sealing fitting

NPT FittingDo not over-tightencompression fitting!

Interface float(ordered

separately)

Product float(ordered

separately)

View shown withcover removed

Plugged entryDo not use(see notes)

Do not remove cover with circuit livein hazardous locations!

Follow safe work procedures.

3/4 NPT conduit accessUse NPT conduit fitting only!

Conduit(flexible or rigid)

Conduit fromcontrol room

Level Plus®

Level Plus® SoClean®

Operation Manual

7.4 Cable recommendationsRefer to ‘Table 1’ below for general requirements of cable types for the Level Plus® SoClean® analog transmitter.

Cable specifications

7.5 Electrical conduit

Table 2: Cable specification and parameters

Fig. 12: Electrical conduit installation

Bus with spursThe bus with spurs topology has a main trunk cable that has each device connected via its own spur at a junction box as shown in Figure 9. The bus with spurs and tree topologies can also be used together to form a hybrid topology.

Tree alignmentThe tree topology is very similar to the bus with spurs topology with the main difference of having a common junction box for all of the transmit-ters as shown in Figure 10. Bus with spurs and tree topologies can also be used together to form a hybrid topology.

Daisy chainThe daisy-chain topology utilizes a single cable that is connected to all of the transmitters with the cable being interconnected at each field device. When using this topology make sure that the wiring practice allows for one transmitter to be disconnected without disconnecting the entire loop as shown in Figure 11. MTS does not suggest using the daisy-chain topology.

PLC

PLC

Fig. 9: Bus with spurs topology

Fig. 10: Tree topology

Fig. 11: Daisy-chain topology

PLC

Parameter Specification

Minimum cable size 24 AWG or heavier (0.51 mm diameter)

Cable type Single pair shielded or multiple pair with overall shield; minimum 0.010 in. (0.25 mm) insulation thickness

Capacitance Less than 30 pF/Ft

Page 15: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

15

Level Plus® SoClean®

Operation Manual

Entity parameters

Digital supply Ui = 28 Vdc

Ii = 100 mA

Ci = 0.0 µF

Li = 0 mH

Pi = 700 mW

Digital communication

Ui = 8.6 Vdc

Ii = 10 mA

Ci = 0.0 µF

Li = 0.0 mH

Pi = 21.5 mW

Table 3: Safety barrier entity parameter references

Table 4: Safety barrier entity parameter references

7.6 Grounding

There are two methods to provide an earth ground to the earth ground of the electronics. Refer to’ Table 2’ for safety barrier references.

» Run an earth ground through the conduit and connect directly to the earth ground lug inside the housing. » Run an earth ground directly to the ground lug on the outside of the

housing.

7.7 Safety barriersRefer to Table 2 for entity parameters and Table 3 for example safety barriers

Note:Grounding the transmitter through a threaded conduit connection does not provide sufficient ground.

8. Commissioning

8.1 TrainingCommissioning should only be conducted by qualified service person-nel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.

8.2 Tools » Channel Lock pliers » RS485 to USB Converter (MTS Part # 380114) » PC » Linear Regulated Power Supply » MTS Setup Software

8.3 Setup softwareMTS offers Setup Software that is shipped with the level transmitter and is also available for download from www.mtssensors.com. The Setup Software is to be used for installation, commissioning, and troubleshoo-ting. For further details on how to use the setup software consult the Interface Manual Modbus (MTS Part# 551700) and the Interface Manual DDA (MTS Part# 551701).

Supplier STAHL STAHL

Type 9001/01-280-100-101

9001/01-086-010-101

Maximum voltage 28 Vdc 8.6 Vdc

Maximum current(each channel)

100 mA 10 mA

Maximum power(each channel)

700 mW 21.5 mW

Number of channels 1 1

Interface Modbus/DDA Modbus/DDA

8.4 Commissioning steps

1. Consult Section 4.3 before starting2. Remove level transmitter from shipping container.3. Insert pipe into float(s) making sure float(s) are in the active range.4. Connect power, RS485 to USB converter, and PC.5. Open MTS Setup Software.6. Establish Communication.7. For DDA Interface – Set Address. 8. For Modbus Interface – Set Address, Enter Strap Table, Setup Volume Correction Method. 9. Disconnect Power and Communication. Remove floats. Prepare level transmitter for transport to the top of the tank.10. Complete Installation in Section 6.4.11. Have qualified technician perform hand measurement. Enter hand measurement into MTS Setup Software and calibrate.12. Store all settings as backup file according to site name and tank number.

Note:For Additional details consult the protocol specific Interface Manual Modbus (MTS Part #551700) and Interface Manual DDA (MTS Part #551701).

Page 16: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

16

Level Plus® SoClean®

Operation Manual

9.3 InspectionBelow are some standard items that should be inspected on a regular basis to make sure that the level transmitter and surrounding environ-ment are in operating condition.

» Hazardous Area Label is present and legible » Hazardous Area approval is correct for installation » There are no visible unauthorized modifications » Electrical connections are tight » Condition of enclosure gasket is satisfactory » No water ingress (white powder) » No obvious damage to cable » Sealing of conduit or cable gland is satisfactory » Earth ground is satisfactory » Single or Dual Cavity Enclosure threads are not damaged » Housing and sensing element piston o-ring is not damaged or

cracked » No corrosion on visible parts » Printed circuit boards are clean and undamaged

9.4 Preventative maintenanceLevel Plus® level transmitters do not typically require preventative maintenance but may require preventative maintenance dependent on the application. For general purpose applications where there is no potential for buildup on the pipe and/or float there is no need for preventative maintenance but routine inspection is still suggested. For severe service applications where there is potential for buildup on the pipe and/or float then preventative maintenance is required.

9.4.1 General purpose applications

9.4.1.1 Perform Inspection suggested in section 9.3

9.4.2 Severe Service Applications

9.4.2.1 Perform Inspection suggested in section 9.3

9.4.2.2 Disconnect Power.

9.4.2.3 Disconnect process connection from tank. Remove pipe from tank.

9.4.2.4 When the bottom of the pipe is reached inspect the floats.

9.4.2.4.1 If the floats are highly contaminated then remove the assembly from the tank and remove the floats from the pipe. This is not possible with TB and DP end plugs.

9.4.2.4.2 If the floats are slightly contaminated then clean the floats without remo-ving the floats from the pipe.

9.4.2.5 Replace pipe and floats in tank.

9.4.2.6 Connect process connection to tank.

9.4.2.7 Connect Power.

9.4.2.8 The process should be carried out regularly until a consistent pattern has been established as to how long the intervals between cleanings should be.

Note:It is best to clean the pipe as it is removed from the tank to minimize the amount of product that is removed from the tank. The user should take caution and abide by all regulations so that product is not spilled and the environment is not contaminated.

9. Maintenance

9.1 TrainingMaintenance should only be conducted by qualified service personnel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.

9.2 Tools » Channel Lock pliers » RS485 to USB Converter (MTS Part # 380114) » PC » Linear Regulated Power Supply » MTS Setup Software

9.4.1.2 No additional preventative maintenance is necessary. Preventative maintenance suggested for Severe Service Applications may be performed.

Page 17: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

17

Level Plus® SoClean®

Operation Manual

10. Repair

10.1 RMA policy

All Level Plus® transmitters come with a two year limited warranty from the factory shipment date. A Return Materials Authorization (RMA) num-ber is required and must accompany any transmitter returns. Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory. A Material Safety Data Sheet (MSDS) must also accompany the transmitter that was used in any process.

10.2 TrainingRepair should only be conducted by qualified service personnel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.

10.3 Tools » Channel Lock pliers » Phillips head screwdriver » Common head screwdriver » RS485 to USB Conververter (MTS Part # 380114) » PC » Linear Regulated Power Supply

Important:Contact Technical Support or Customer Service for assistance if you suspect that the transmitter is not working correctly. Technical support can assist you with troubleshooting, part replacement, and Returned Material Authorization (RMA) information if required.

10.4 TroubleshootingSymptom Possible cause Action

No communication with tramitter

No power Check voltage at transmitter

Wiring incorrect Reference installation drawing section 12

Wrong address DDA factory default is ‘192 ’Modbus factory default is ‘247 ’

Wrong software Confirm correct software

Wrong protocol Confirm software and transmitter are same protocol

Missing magnet error

Float not recognized Confirm that the float is attached

Float is in the dead zone

Raise float to see if the error stops

Wrong number of floats selected

Confirm that the number of floats on the transmitter and the number of floats the transmitter is attempting to verify are the same.

Trigger level error

Gain needs to be adjusted

Consult Factory

SE is damaged Consult Factory

Min. trigger level too high

Consult Factory

Volume calculation error

No strap table entered

Enter strap table

Level outside range of strap table

Enter additional points in strap table

Strap table incorrect

Check value entries

VCF error No VCF table entered

Enter VCF table

VCF table incorrect

Check VCF value entries

Table 5: Troubleshooting reference

10.4 Troubleshooting

Page 18: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

18

Level Plus® SoClean®

Operation Manual

12.2 CertificatesDownloadable copies of all certificates are located at www.mtssensors.com and can be downloaded on the product specific landing page. If there is any difficulty in obtaining the certificates from the web contact MTS Technical Support and they will be sent electronically.

12.3 FM

12.3.1 Special Conditions of Safe Use 1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.

Fig. 13: FM label

Fig. 14: FM label

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES

0.5 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE 551629-1 B

1 2

DRAWN BY: NJ

A NJ

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***

INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDCL. I, Zone 0/1, AEx ia IIC T4Ta = -50°C to +71°C ; IP65when connected in accordance with FM approved installa on drawing # 651543-1

WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS

Model No: Serial No: Date :

MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513

Level Plus Transmitter

USE MTS LOGO ARTWORK

10 POINT SIZE

8 POINT TEXT SIZE

4.5 POINT TEXT SIZE

MTS TO PRINTMODEL NO.SERIAL NO.

DATE CODE.

ENTITY PARAMETERS:SEE PRINT REFERENCE CHART

4.5 POINT TEXT SIZE

FM APPROVED

USE FM LOGO ARTWORK

US

LEVEL

1:1

7570 RELEASE TO PRODUCTION

(ACP) LABEL, LP, IS US - DIGITAL

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.

P/N 551629-1 Rev B

10/24/14

86.30 [3.40]

1.78 [.07]

34.69 [1.37]

1.78 [.07]

69.85 [2.75]

R3.30 [.13]

28.70 [1.13]

15.80 [.62]

12/02/14NJB 7847 IP RATING WAS 66

®

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES���� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE A 551634- B

1 1

DRAWN BY: NJ

A NJIP RATING WAS 66.7847B 12/2/14

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***NJ

MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513

INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDCL. I, Zone 0/1, AEx ia IIC T4Ta = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS

INSTALL PER DRAWING # 651543-1SUPPLY VOLTAGE: 28 VDC

Level Plus Transmitter

35.05 [1.38]

"L1"∆ "L2"

17.53 [.69]

7.5 POINT SIZEMTS TO PRINTMODEL NO.

SERIAL NO./DATE CODE

� 3.05 [.12] X2

4.0 POINT TEXT SIZE(TYP.)

8.97 [.35] 3.47 [.14]

7570 RELEASE FOR PRODUCTION

(ACP) LABEL, LP, IS US - DIGITAL

FM LOGO ARTWORK4.5 POINT TEXT SIZE

FM US

USE MTS LOGO ARTWORK14.0 POINT SIZE

LEVEL

1:1

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS.4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.5. MATERIAL: .8 [0.03] THICK ALUMINUM6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.

APPROVED

P/N 551634-X Rev B

10/24/14

TABLE 1DASH # HSG "L1" "L2"

-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]

SEE TABLE 1 FOR DASH #.

®

12.3.2 Labels

11.1 ModbusMTS offers Modbus RTU over a RS485 half-duplex network. For additional information consult Interface Manual Modbus, MTS Part# 551700.

11.2 DDAMTS offers DDA (Direct Digital Access) over a RS485 half-duplex network. For additional information consult Interface Manual DDA, MTS Part# 551701.

12. Agency information

12.1 Approvals overviewThe Notified Body is designated in the 13th digit of the model number and the Protection Method is designated in the 14th digit of the model number. These two digits of the model number specify the hazardous area approval that provided with the selected level transmitter.

Table 6: Agency approvals

10.5 Setup softwareMTS offers Setup Software that is shipped with the level transmitter and is also available for download from www.mtssensors.com. The Setup Software is to be used for installation, commissioning, and troubleshoo-ting. For further details on how to use the setup software consult the Interface Manual Modbus (MTS Part# 551700) and the Interface Manual DDA (MTS Part# 551701).

11. Interface

SoClean® is available with multiple outputs including Modbus and DDA. This Operation and Installation Manual includes all of these outputs. Each output has its own specialized Interface Manual that should be consulted for additional information on the specific output.

Notified body

Protection method

Classifications Standard

C = CEC I = Instrinsic Safety

Clss I, Division 1, Groups A, B, C, DEx ia IIC T4 Ga/GbTa = -50 °C to 71 °C

CSA C22.2 No. 1010.1 2004,CSA C22.2 No. 157-92 (2012),CSA C22.2 No. 60079-0:2011,CSA C22.2 No. 60079-11:2014CSA C22.2 No. 60529

E = ATEX

I = Instrinsic Safety

Ex II 1/2 G Ex ia IIC T4 Ga/GbTa = -50 °C to 71 °C

EN 60079-0:2012EN 60079-11:2012

F = NEC I = Instrinsic Safety

Class I, Division 1, Groups A, B, C, DClass I, Zone 0/1, AEx ia IIC T4Ta = -50 °C to 71 °C

FM 3600:2011FM 3610:2010FM 3810: 2005ANSI/ISA 60079-0:2013, ANSI/ISA 60079-11:2014, ANSI/ISA 60529-:2004

I = IEC I = Instrinsic Safety

Ex ia IIC T4 Ga/GbTa = -50 °C to 71 °C

IEC 60079-0:2011IEC 60079-11:2011

Page 19: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

19

Level Plus® SoClean®

Operation Manual

12.3.3 Installation drawing

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-1

1 2

DR

AWN

BY: M

S

***NO

REV

ISION

S SH

ALL BE M

ADE W

ITHO

UT TH

E NO

TIFICATIO

N TO

APPR

OV

AL AG

ENC

Y(S

).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 12/2/14C

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

24 VDC

COM

MO

N- >

Rx /Tx+

Rx /Tx-

GRO

UN

D

EARTH G

ROU

ND

(SEE NO

TE 4)

EARTH G

ROU

ND

(SEE NO

TE 4)

Rx/Tx-

Rx/Tx+

GND

+24V

SAFETY BARRIER

SAFETY BARRIER

SAFETY BARRIER

NO

TES

:1.A

LL NA

TION

AL A

ND

LOC

AL C

OD

ES

AN

D R

EGU

LATIO

NS

MU

ST BE

AD

HE

RE

D TO

WH

EN IN

STALLIN

G TH

E LE

VEL SE

NSO

R IN

HA

ZAR

DO

US

EN

VIRO

NM

EN

TS.

SE

AL A

LL CO

ND

UITS W

ITHIN

457 MM

(18"). 2.LO

OP

CAB

LE M

US

T BE 24 AW

G TO

14 AW

G (.511M

M² to 1.6M

M²)

SH

IELDE

D TW

ISTE

D P

AIR

CA

BLE

WITH

SH

IELD. C

ABLE C

AP

ACITA

NC

E M

US

T B

E LE

SS TH

AN

30 pF PER

FOO

T (98 pF PE

R M

). CA

BLE SH

IELD

IS CO

NN

EC

TED

TO SY

STE

M G

RO

UN

D IN

NO

N-H

AZAR

DO

US

AR

EA

. SE

E INS

TALLA

TION

MA

NU

AL FO

R

AD

DITIO

NA

L CAB

LE IN

FOR

MA

TION

. 3.TH

E R

ES

ISTAN

CE

BE

TWEE

N E

ARTH

GR

OU

ND

AND

THE

INTR

INSIC

ALLY

SA

FE GR

OU

ND

MU

ST B

E LESS

THA

N 1 O

HM

. 4.TH

E TR

AN

SD

UC

ER

FRA

ME

SHA

LL BE

GR

OU

ND

ED

TO EA

RTH

GR

OU

ND

DIR

ECTLY

OR

THR

OU

GH

THE

EQU

IPM

EN

T ON

WH

ICH

IT IS M

OU

NTE

D.

5. CO

NTR

OL E

QU

IPM

ENT C

ON

NE

CTE

D TO

AS

SO

CIATE

D A

PPA

RA

TUS

MU

ST

NO

T US

E OR

GE

NE

RATE

MO

RE

THAN

250 VR

MS

OR

VD

C 6.A

SS

OC

IATED

APP

AR

ATUS

MA

NU

FACTU

RE

R'S

INS

TALLA

TION

DR

AW

ING

MU

ST B

E FO

LLOW

ED W

HE

N IN

STA

LLING

THIS

EQU

IPM

EN

T. 7.O

NLY

US

E NE

C (e.g FM

) APP

RO

VE

D B

AR

RIE

RS

. 8.E

NTITY P

AR

AME

TER

S: S

UPP

LY: R

x/Tx-: Rx/Tx+:

Ui = 28V

DC

Ui= 8.6V

Ui= 8.6V

Ii = 100mA

Ii = 10mA

Ii = 10mA

C

i = 0 µF Ci = 0 µF C

i = 0 µF Li = 0 µH

Li = 0 µH Li = 0 µH

Pi = 0.7 W

Pi= 0.0215 W

P i= 0.0215 W

9.THE

ENTITY

CO

NC

EPT A

LLOW

S INTE

RC

ON

NE

CTIO

N O

F INTR

INS

ICA

LLY S

AFE

APP

AR

ATU

S W

ITH AS

SO

CIA

TED A

PPA

RA

TUS

WH

EN

THE

FOLLO

WIN

G IS

TRU

E:

V

max or U

i ≥ Voc, V

t or Uo;

Imax or Ii ≥ Isc, It or Io;

Pm

ax or Pi ≥ Po;

Ca ≥ C

i + Ccable;

La ≥ Li + Lcable. 10.D

UAL-C

AVITY

EN

CLO

SU

RE

S: C

US

TOM

ER

CO

NN

EC

TION

S WILL BE

MA

DE AT TE

RM

INA

L BLO

CK

ON

PO

WE

R SID

E O

F HO

US

ING

(NO

T TO TE

RM

INA

L BLO

CK

ON

INTER

CO

NN

EC

T BO

ARD

). 11.IN

STA

LLATIO

N SH

OU

LD B

E IN A

CC

OR

DAN

CE

WITH

ANS

I/ISA

RP

12.06.01 "INS

TALLA

TION

OF

INTR

INS

ICA

LLY SA

FE S

YSTE

MS

FOR

HA

ZAR

DO

US

(CLA

SS

IFIED

) LOC

ATIO

NS

" A

ND

THE

NA

TION

AL E

LEC

TRIC

AL C

OD

E (AN

SI/N

FPA

70). 12.TH

E M

AX

IMU

M PE

RM

ITTED

AM

BIE

NT TE

MP

ER

ATU

RE

OF TH

E LE

VEL P

LUS

DIG

ITAL/A

NA

LOG

LE

VE

L TRAN

SM

ITTER

IS 71 °C

. TO A

VO

ID TH

E E

FFEC

TS O

F PR

OC

ESS

TEM

PE

RA

TUR

E A

ND

O

THE

R TH

ER

MAL EFFE

CTS C

AR

E S

HALL B

E TAK

EN

TO EN

SU

RE

THE

SU

RR

OU

ND

ING

AM

BIEN

T A

ND

THE

AMBIE

NT IN

SID

E TH

E TR

ANS

MITTE

R H

OU

SING

DO

ES

NO

T EX

CE

ED

71°C 13.C

AU

TION

: FLEX

IBLE

GA

UG

ES

HA

VE

A MIN

IMU

M B

EN

D D

IAM

ETER

OF 406M

M(16")

14.WA

RN

ING

: THE

APP

AR

ATU

S EN

CLO

SU

RE

CO

NTA

INS A

LUM

INU

M A

ND

IS CO

NS

IDE

RED

TO C

ON

STITU

TE A

PO

TEN

TIAL R

ISK O

F IGN

ITION

BY IM

PAC

T OR

FRIC

TION

. CAR

E M

UST B

E TA

KEN

IN

TO A

CC

OU

NT D

UR

ING

INS

TALLA

TION

AN

D U

SE

TO P

REV

EN

T IMP

ACT O

R FR

ICTIO

N 15.W

AR

NIN

G: S

UBS

TITUTIO

N O

F CO

MP

ON

EN

TS M

AY

IMP

AIR

INTR

INS

IC S

AFE

TY.

16.WA

RN

ING

: TO PR

EV

ENT IG

NITIO

N O

F FLAM

MA

BLE

OR

CO

MB

USTIB

LE A

TMO

SP

HER

ES

, D

ISC

ON

NE

CT P

OW

ER BE

FOR

E S

ERV

ICIN

G

17.WA

RN

ING

: THE

EQU

IPM

EN

T CO

NTA

INS N

ON

-ME

TALLIC E

NC

LOS

UR

E PA

RTS, TO

PR

EV

EN

T TH

E R

ISK

OF E

LEC

TRO

STA

TIC SP

AR

KING

. THE

NO

N-M

ETA

LLIC S

UR

FACE

SH

OU

LD O

NLY

B

E C

LEAN

ED

WITH

A DA

MP

CLO

TH.

NO

N H

AZARDO

US LO

CATION

HAZARD

OU

S LOCATIO

N

AGEN

CY C

ON

TRO

LLED D

RAW

ING

(US). N

O C

HAN

GES W

ITHO

UT PR

IOR

AGEN

CY APPR

OVAL

EARTH TERM

INAL

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTR

INSICALLY SAFE FO

R U

S

7570

LEVEL

FM

APPROVED US

N/A

INTRIN

SICALLY SAFECL. I, D

IV. 1, GR. ABCD

Ex ia IIC T4 Ga/G

bTa =

-50 to 71°C ; IP65

Fig. 15: FM installation drawing

Page 20: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

20

Level Plus® SoClean®

Operation Manual

12.3.3 Installation drawing (cont.)

DETAIL A

SCALE 1.60 : 1

DETAIL C

SCALE 3 : 1

DETAIL D

SCALE 1.2

DETAIL E

SCALE 1 : 1

A

C

D

E

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-1

2 2

DR

AWN

BY: M

S

***NO

REV

ISION

S SH

ALL BE M

ADE W

ITHO

UT TH

E NO

TIFICATIO

N TO

APPR

OV

AL AG

ENC

Y(S

).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 12/2/14C

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

+24V GNDEARTHTX/RX+TX/RX-

GND+24V

TX/RX-TX/RX+EARTH

GND

+24V

TX/RX-

TX/RX+

EARTH

FIGU

RE 1

SING

LE CAVITY & N

EMA H

OU

SING

FIGU

RE 2

DU

AL CAVITY H

OU

SING

NO

TES: 1. TH

E CU

STOM

ER SH

OU

LD C

ON

NEC

T THE O

UTSID

E GR

OU

ND

LUG

TO TH

E SAFETY EARTH

ING

GR

OU

ND

SYSTEM W

ARN

ING

: C

ON

DU

IT SEALS REQ

UIR

ED W

ITHIN

457 MM

(18") OF H

OU

SING

.

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTRIN

SICALLY SAFE FOR U

S

+24V GND EARTH Tx/Rx+ Tx/Rx-

7570

Fig. 16: FM installation drawing

Page 21: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

21

Level Plus® SoClean®

Operation Manual

12.4 FMC

12.4.1 Special conditions of safe use

1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus® Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.

12.4.2 Labels

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES

0.5 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE 551629-2 B

1 2

DRAWN BY:

A

NJ

NJ

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***

WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS

INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDEx ia IIC T4 Ga/GbTa = -50°C to +71°C ; IP65when connected in accordancewith FM approved installation drawing # 651543-2

MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513

Model No: Serial No: Date :

USE MTS LOGO ARTWORK

10 POINT SIZE

8 POINT TEXT SIZE

4.5 POINT TEXT SIZE

MTS TO PRINTMODEL NO.SERIAL NO.

DATE CODE.

ENTITY PARAMETERS:SEE PRINT REFERENCE CHART

4.5 POINT TEXT SIZE

FM APPROVED

USE FM LOGO ARTWORK

C

LEVEL

1:1

7570 RELEASE TO PRODUCTION

(ACP) LABEL, LP, IS CANADA - DIGITAL

Transmitter

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.

P/N: 551629-2 Rev B

10/24/14

69.85 [2.75]

R3.30 [.13]

28.70 [1.13]1.78 [.07]

15.80 [.62]

34.69 [1.37]

1.78 [.07]

86.30 [3.40]

IP RATING WAS 66 12/02/14NJ7847B

Level Plus ®

Fig. 17: FMC label

Fig. 18: FMC label

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES���� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE A 551702- B

1 1

DRAWN BY: NJ

NJNJ 12/2/14B 7847 IP RATING WAS 66.

A

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***

MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513

INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDEx ia IIC T4 Ga/GbTa = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNING

INSTALL PER DRAWING # 651543-2SUPPLY VOLTAGE: 28 VDC

35.05 [1.38]

"L1"∆ "L2"

17.53 [.69]

7.5 POINT SIZEMTS TO PRINTMODEL NO.

SERIAL NO./DATE CODE

� 3.05 [.12] X2

4.0 POINT TEXT SIZE(TYP.)

8.97 [.35] 3.47 [.14]

7570 RELEASE FOR PRODUCTION

(ACP) LABEL, LP, IS CANADA - DIGITAL

FM LOGO ARTWORK4.5 POINT TEXT SIZE

FM C

USE MTS LOGO ARTWORK14.0 POINT SIZE

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS..4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.5. MATERIAL: .8 [.03] THICK ALUMINUM.6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.

APPROVED

P/N 551702-X Rev B

LEVEL

1:1

10/24/14

SEE TABLE 1 FOR DASH #.

TABLE 1DASH # HOUSING "L1" "L2"

-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]

Level Plus Transmitter®

Page 22: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

22

Level Plus® SoClean®

Operation Manual

12.4.3 Installation drawing

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-2

1 2

DR

AWN

BY: M

S

***NO

REVISIO

NS

SHALL B

E MAD

E WITH

OU

T THE N

OTIFIC

ATIO

N TO

APPR

OV

AL AG

EN

CY(S).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 12/2/14

B

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

24 VDC

COM

MO

N- >

Rx/Tx+

Rx /Tx-

GRO

UN

D

EARTH G

ROU

ND

(SEE NO

TE 4)

EARTH G

ROU

ND

(SEE NO

TE 4)

Rx/Tx-

Rx/Tx+

GND

+24V

SAFETY BARRIER

SAFETY BARRIER

SAFETY BARRIER

NO

TES

:1.A

LL NA

TION

AL A

ND

LOC

AL C

OD

ES

AN

D R

EGU

LATIO

NS

MU

ST BE

AD

HE

RE

D TO

WH

EN IN

STALLIN

G TH

E LE

VEL SE

NSO

R IN

HA

ZAR

DO

US

EN

VIRO

NM

EN

TS.

SE

AL A

LL CO

ND

UITS W

ITHIN

457 MM

(18"). 2.LO

OP

CAB

LE M

US

T BE 24 AW

G TO

14 AW

G (.511M

M² to 1.6M

M²)

SH

IELDE

D TW

ISTED

PA

IR C

AB

LE W

ITH S

HIELD

. CA

BLE CA

PAC

ITAN

CE

MU

ST

BE

LES

S THA

N 30 pF P

ER FO

OT (98 pF P

ER

M). C

AB

LE SHIE

LD IS C

ON

NE

CTE

D TO

SYS

TEM

GR

OU

ND

IN N

ON

-HAZA

RD

OU

S A

RE

A. S

EE IN

STA

LLATIO

N M

AN

UA

L FOR

A

DD

ITION

AL C

ABLE

INFO

RM

ATIO

N.

3.THE

RE

SIS

TANC

E B

ETW

EEN

EAR

TH G

RO

UN

D AN

D TH

E IN

TRIN

SICA

LLY S

AFE G

RO

UN

D M

US

T BE LES

S TH

AN

1 OH

M.

4.THE

TRA

NS

DU

CE

R FR

AM

E SH

ALL B

E G

RO

UN

DE

D TO

EAR

TH G

RO

UN

D D

IREC

TLY O

R TH

RO

UG

H TH

E EQ

UIP

ME

NT O

N W

HIC

H IT IS

MO

UN

TED

. 5. C

ON

TRO

L EQ

UIP

MEN

T CO

NN

EC

TED

TO A

SS

OC

IATED

APP

AR

ATU

S M

US

T N

OT U

SE O

R G

EN

ER

ATE M

OR

E TH

AN 250 V

RM

S O

R V

DC

6.AS

SO

CIATE

D A

PPA

RATU

S M

AN

UFAC

TUR

ER

'S IN

STA

LLATIO

N D

RA

WIN

G M

UST

BE

FOLLO

WED

WH

EN

INS

TALLIN

G TH

IS EQ

UIP

ME

NT.

7.ON

LY U

SE C

EC

AP

PR

OV

ED B

AR

RIE

RS

. 8.E

NTITY P

AR

AME

TER

S: S

UPP

LY: R

x/Tx- : Rx/Tx+ :

Ui = 28V

DC

Ui= 8.6V

Ui= 8.6V

Ii = 100mA

Ii = 10mA

Ii = 10mA

C

i = 0 µF Ci = 0 µF C

i = 0 µF Li = 0 µH

Li = 0 µH Li = 0 µH

Pi = 0.7 W

Pi= 0.0215 W

P i= 0.0215 W

9.THE

ENTITY

CO

NC

EPT A

LLOW

S INTE

RC

ON

NE

CTIO

N O

F INTR

INS

ICA

LLY S

AFE

APP

AR

ATU

S W

ITH AS

SO

CIA

TED A

PPA

RA

TUS

WH

EN

THE

FOLLO

WIN

G IS

TRU

E:

V

max or U

i ≥ Voc, V

t or Uo;

Imax or Ii ≥ Isc, It or Io;

Pm

ax or Pi ≥ Po;

Ca ≥ C

i + Ccable;

La ≥ Li + Lcable. 10.D

UAL-C

AVITY

EN

CLO

SU

RE

S: C

US

TOM

ER

CO

NN

EC

TION

S WILL BE

MA

DE AT TE

RM

INA

L BLO

CK

ON

PO

WE

R SID

E O

F HO

US

ING

(NO

T TO TE

RM

INA

L BLO

CK

ON

INTER

CO

NN

EC

T BO

ARD

). 11.FO

R IN

STALLA

TION

WITH

IN C

AN

AD

A SE

E, C

AN

AD

IAN E

LEC

TRIC

AL C

OD

E,

CS

A No. C

22.1. 12.TH

E M

AX

IMU

M PE

RM

ITTED

AM

BIE

NT TE

MP

ER

ATU

RE

OF TH

E LE

VEL P

LUS

DIG

ITAL/A

NA

LOG

LE

VE

L TRAN

SM

ITTER

IS 71 °C

. TO A

VO

ID TH

E E

FFEC

TS O

F PR

OC

ESS

TEM

PE

RA

TUR

E A

ND

O

THE

R TH

ER

MAL EFFE

CTS C

AR

E S

HALL B

E TAK

EN

TO EN

SU

RE

THE

SU

RR

OU

ND

ING

AM

BIEN

T A

ND

THE

AMBIE

NT IN

SID

E TH

E TR

ANS

MITTE

R H

OU

SING

DO

ES

NO

T EX

CE

ED

71°C 13.C

AU

TION

: FLEX

IBLE

GA

UG

ES

HA

VE

A MIN

IMU

M B

EN

D D

IAM

ETER

OF 406M

M(16")

14.WA

RN

ING

: THE

APP

AR

ATU

S EN

CLO

SU

RE

CO

NTA

INS A

LUM

INU

M A

ND

IS CO

NS

IDE

RED

TO C

ON

STITU

TE A

PO

TEN

TIAL R

ISK O

F IGN

ITION

BY IM

PACT O

R FR

ICTIO

N. C

ARE

MU

ST BE

TAKE

N

INTO

AC

CO

UN

T DU

RIN

G IN

STA

LLATIO

N A

ND

US

E TO

PR

EVE

NT IM

PAC

T OR

FRIC

TION

15.WA

RN

ING

: SU

BSTITU

TION

OF C

OM

PO

NE

NTS

MA

Y IM

PA

IR IN

TRIN

SIC

SA

FETY

. 16.W

AR

NIN

G: TO

PRE

VEN

T IGN

ITION

OF FLA

MM

AB

LE O

R C

OM

BU

STIBLE

ATM

OS

PH

ERE

S,

DIS

CO

NN

EC

T PO

WE

R BE

FOR

E S

ERV

ICIN

G

17.WA

RN

ING

: THE

EQU

IPM

EN

T CO

NTA

INS N

ON

-ME

TALLIC E

NC

LOS

UR

E PA

RTS, TO

PR

EV

EN

T TH

E R

ISK

OF E

LEC

TRO

STA

TIC SP

AR

KING

. THE

NO

N-M

ETA

LLIC S

UR

FACE

SH

OU

LD O

NLY

B

E C

LEAN

ED

WITH

A DA

MP

CLO

TH.

NO

N H

AZARDO

US LO

CATION

HAZARD

OU

S LOCATIO

N

AGEN

CY C

ON

TRO

LLED D

RAW

ING

(CAN

ADA). N

O C

HAN

GES W

ITHO

UT PR

IOR

AGEN

CY APPR

OVAL

EARTH TERM

INAL

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTR

INSICALLY SAFE FO

R CAN

ADA

7570

LEVEL

FM

APPROVED

C

N/A

INTRIN

SICALLY SAFECL. I, D

IV. 1, GR. ABCD

Ex ia IIC T4 Ga/G

bTa =

-50 to 71°C ; IP65

Fig. 19: FMC installation drawing

Page 23: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

23

Level Plus® SoClean®

Operation Manual

12.4.3 Installation drawing (cont.)

DETAIL A

SCALE 1.60 : 1

DETAIL C

SCALE 3 : 1

DETAIL D

SCALE 1.2

DETAIL E

SCALE 1 : 1

A

C

D

E

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-2

2 2

DR

AWN

BY: M

S

***NO

REVISIO

NS

SHALL B

E MAD

E WITH

OU

T THE N

OTIFIC

ATIO

N TO

APPR

OV

AL AG

EN

CY(S).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 12/2/14

B

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

+24V GNDEARTHTX/RX+TX/RX-

GND+24V

TX/RX-TX/RX+EARTH

GND

+24V

TX/RX-

TX/RX+

EARTH

FIGU

RE 1

SING

LE CAVITY & N

EMA H

OU

SING

FIGU

RE 2

DU

AL CAVITY H

OU

SING

NO

TES: 1. TH

E CU

STOM

ER SH

OU

LD C

ON

NEC

T THE O

UTSID

E GR

OU

ND

LUG

TO TH

E SAFETY EARTH

ING

GR

OU

ND

SYSTEM W

ARN

ING

: C

ON

DU

IT SEALS REQ

UIR

ED W

ITHIN

457 MM

(18") OF H

OU

SING

.

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTRIN

SICALLY SAFE FOR CAN

ADA

+24V GND EARTH Tx/Rx+ Tx/Rx-

7570

Fig. 20: FMC installation drawing

Page 24: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

24

Level Plus® SoClean®

Operation Manual

12.5 ATEX and IECEx

12.5.1 Special conditions of safe use

1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus® Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.

12.5.2 Labels

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINESCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIEDTOLERANCES

0 PLACESMM

1 PLACEMM

ANGLES

0.5 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE 551629-3 B

1 2

DRAWN BY: NJ

A NJ

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***

WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS

FM14ATEX0068XIECEx FMG 14.0032X II 1/2 G Ex ia IIC T4 Ga/Gb Ta = -50°C to +71°C ; IP65when connected in accordancewith FM approved installation drawing # 651543-3

MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513

Model No: Serial No: Date :

USE MTS LOGO ARTWORK

10 POINT SIZE

8 POINT TEXT SIZE

4.5 POINT TEXT SIZE

MTS TO PRINTMODEL NO.SERIAL NO.

DATE CODE.

ENTITY PARAMETERS:SEE PRINT REFERENCE CHART

LEVEL

1:1

7570 RELEASE TO PRODUCTION

(ACP) LABEL, LP, IS ATEX/IECEx - DIGITAL

10/24/14

1725

Level Plus Transmitter

P/N 551629-3 Rev B

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.

R3.30 [.13]

1.78 [.07]

1.78 [.07]

28.70 [1.13]

15.80 [.62]

34.69 [1.37]

86.30 [3.40]

69.85 [2.75]

IP RATING WAS 66 1/19/15NJ7847B

®

Fig. 21: ATEX label

Fig. 22: IECEx label

1

1

2

2

A A

B B

REV ECO # DESCRIPTION

TITLE

SIZE DWG NO. REV

PRODUCT LINE

SCALE:

BY DATE

SHEET OF

UNLESS OTHERWISE SPECIFIED

TOLERANCES0 PLACES

MM1 PLACE

MMANGLES

���� 0.5 � 0.1

- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FI NISH 3.2uM [125 uIn]

PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISC LOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.

mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513

METRIC

FIRST ANGLE A 551703- B

1 1

DRAWN BY: NJ

A NJ

***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***IP RATING WAS 66.7847B NJ 1/19/15

MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513

II 1/2 G Ex ia IIC T4 Ga/GbTa = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS

INSTALL PER DRAWING # 651543-3SUPPLY VOLTAGE: 28 VDC

FM14ATEX0068XIECEx FMG 14.0032X

35.05 [1.38]

"L1"∆ "L2"

17.53 [.69]

7.5 POINT SIZE

USE MTS LOGO ARTWORK14.0 POINT SIZE

MTS TO PRINTMODEL NO.

SERIAL NO./DATE CODE

� 3.05 [.12] X2

4.0 POINT TEXT SIZE(TYP.)

12.70 [.50] 3.70 [.15]

7570 RELEASE FOR PRODUCTION

(ACP) LABEL, LP, IS ATEX/IECEX - DIGITAL

NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS.4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES5. MATERIAL: .8 [.03] THICK ALUMINUM6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.

1725

Level Plus Transmitter

P/N 551703-X Rev B

1:1LEVEL

10/24/14

TABLE 1DASH # HOUSING "L1" "L2"

-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]

SEE TABLE 1 FOR DASH #.

®

Page 25: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

25

Level Plus® SoClean®

Operation Manual

12.5.3 Installation drawing

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-3

1 2

DR

AWN

BY: M

S

***NO

RE

VISION

S SHALL BE

MA

DE

WITH

OU

T THE

NO

TIFICA

TION

TO A

PPRO

VAL AG

EN

CY(S).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 1/19/15

C

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

24 VDC

COM

MO

N- >

Rx/Tx+

Rx/Tx -

GRO

UN

D

EARTH G

ROU

ND

(SEE NO

TE 4)

EARTH G

ROU

ND

(SEE NO

TE 4)

Rx/Tx-

Rx/Tx+

GND

+24V

SAFETY BARRIER

SAFETY BARRIER

SAFETY BARRIER

NO

TES

:1.A

LL NA

TION

AL A

ND

LOC

AL C

OD

ES

AN

D R

EGU

LATIO

NS

MU

ST BE

AD

HE

RE

D TO

WH

EN IN

STALLIN

G TH

E LE

VEL SE

NSO

R IN

HA

ZAR

DO

US

EN

VIRO

NM

EN

TS.

SE

AL A

LL CO

ND

UITS W

ITHIN

457 MM

(18"). 2.LO

OP

CAB

LE M

US

T BE 24 AW

G TO

14 AW

G (.511M

M² to 1.6M

M²)

SH

IELDE

D TW

ISTED

PA

IR C

AB

LE W

ITH S

HIELD

. CA

BLE CA

PAC

ITAN

CE

MU

ST

BE

LES

S THA

N 30 pF P

ER FO

OT (98 pF P

ER

M). C

AB

LE SHIE

LD IS C

ON

NE

CTE

D TO

SYS

TEM

GR

OU

ND

IN N

ON

-HAZA

RD

OU

S A

RE

A. S

EE IN

STA

LLATIO

N M

AN

UA

L FOR

A

DD

ITION

AL C

ABLE

INFO

RM

ATIO

N.

3.THE

RE

SIS

TANC

E B

ETW

EEN

EAR

TH G

RO

UN

D AN

D TH

E IN

TRIN

SICA

LLY S

AFE G

RO

UN

D M

US

T BE LES

S TH

AN

1 OH

M.

4.THE

TRA

NS

DU

CE

R FR

AM

E SH

ALL B

E G

RO

UN

DE

D TO

EAR

TH G

RO

UN

D D

IREC

TLY O

R TH

RO

UG

H TH

E EQ

UIP

ME

NT O

N W

HIC

H IT IS

MO

UN

TED

. 5. C

ON

TRO

L EQ

UIP

MEN

T CO

NN

EC

TED

TO A

SS

OC

IATED

APP

AR

ATU

S M

US

T N

OT U

SE O

R G

EN

ER

ATE M

OR

E TH

AN 250 V

RM

S O

R V

DC

6.AS

SO

CIATE

D A

PPA

RATU

S M

AN

UFAC

TUR

ER

'S IN

STA

LLATIO

N D

RA

WIN

G M

UST

BE

FOLLO

WED

WH

EN

INS

TALLIN

G TH

IS EQ

UIP

ME

NT.

7.ON

LY U

SE A

TEX

/IEC

AP

PR

OVE

D B

ARR

IERS

. 8.E

NTITY P

AR

AME

TER

S: S

UPP

LY: R

x/Tx-: Rx/Tx+:

Ui = 28V

DC

Ui= 8.6V

Ui= 8.6V

Ii = 100mA

Ii = 10mA

Ii = 10mA

C

i = 0 µF Ci = 0 µF C

i = 0 µF Li = 0 µH

Li = 0 µH Li = 0 µH

Pi = 0.7 W

Pi= 0.0215 W

P i= 0.0215 W

9.THE

ENTITY

CO

NC

EPT A

LLOW

S INTE

RC

ON

NE

CTIO

N O

F INTR

INS

ICA

LLY S

AFE

APP

AR

ATU

S W

ITH AS

SO

CIA

TED A

PPA

RA

TUS

WH

EN

THE

FOLLO

WIN

G IS

TRU

E:

V

max or U

i ≥ Voc, V

t or Uo;

Imax or Ii ≥ Isc, It or Io;

Pm

ax or Pi ≥ Po;

Ca ≥ C

i + Ccable;

La ≥ Li + Lcable. 10.D

UAL-C

AVITY

EN

CLO

SU

RE

S: C

US

TOM

ER

CO

NN

EC

TION

S WILL BE

MA

DE AT TE

RM

INA

L BLO

CK

ON

PO

WE

R SID

E O

F HO

US

ING

(NO

T TO TE

RM

INA

L BLO

CK

ON

INTER

CO

NN

EC

T BO

ARD

). 11.FO

R INSTALLATIO

N W

ITHIN

THE EU

ROPEAN

UN

ION

, SEE EN 60079-14.

12.THE

MA

XIM

UM

PER

MITTE

D A

MB

IEN

T TEM

PE

RA

TUR

E O

F THE

LEVE

L PLU

S D

IGITA

L/AN

ALO

G

LEV

EL TR

ANS

MITTE

R IS

71 °C. TO

AV

OID

THE

EFFE

CTS

OF P

RO

CES

S TE

MP

ER

ATU

RE

AN

D

OTH

ER

THE

RM

AL EFFEC

TS CA

RE

SH

ALL BE TA

KE

N TO

ENS

UR

E TH

E S

UR

RO

UN

DIN

G A

MB

IENT

AN

D TH

E AM

BIEN

T INS

IDE

THE

TRAN

SM

ITTER

HO

USIN

G D

OE

S N

OT E

XC

EE

D 71°C

13.CA

UTIO

N: FLE

XIB

LE G

AU

GE

S H

AV

E A M

INIM

UM

BE

ND

DIA

METE

R O

F 406MM

(16") 14.W

AR

NIN

G: TH

E AP

PA

RA

TUS E

NC

LOS

UR

E C

ON

TAIN

S ALU

MIN

UM

AN

D IS C

ON

SID

ER

ED TO

CO

NS

TITUTE

A P

OTE

NTIA

L RIS

K OF IG

NITIO

N B

Y IMP

ACT O

R FR

ICTIO

N. C

ARE

MU

ST BE

TAKE

N

INTO

AC

CO

UN

T DU

RIN

G IN

STA

LLATIO

N A

ND

US

E TO

PR

EVE

NT IM

PAC

T OR

FRIC

TION

15.WA

RN

ING

: SU

BSTITU

TION

OF C

OM

PO

NE

NTS

MA

Y IM

PA

IR IN

TRIN

SIC

SA

FETY

. 16.W

AR

NIN

G: TO

PRE

VEN

T IGN

ITION

OF FLA

MM

AB

LE O

R C

OM

BU

STIBLE

ATM

OS

PH

ERE

S,

DIS

CO

NN

EC

T PO

WE

R BE

FOR

E S

ERV

ICIN

G

17.WA

RN

ING

: THE

EQU

IPM

EN

T CO

NTA

INS N

ON

-ME

TALLIC E

NC

LOS

UR

E PA

RTS, TO

PR

EV

EN

T TH

E R

ISK

OF E

LEC

TRO

STA

TIC SP

AR

KING

. THE

NO

N-M

ETALLIC

SU

RFAC

E S

HO

ULD

ON

LY

BE

CLEA

NE

D W

ITH A D

AM

P C

LOTH

.

NO

N H

AZARDO

US LO

CATION

HAZARD

OU

S LOCATIO

N

INTR

INS

ICA

LLY S

AFEFM

14ATE

X0068XIE

CE

x FMG

14.0032X

AGEN

CY C

ON

TRO

LLED D

RAW

ING

(ATEX/IEC). N

O C

HAN

GES W

ITHO

UT PR

IOR

AGEN

CY APPR

OVAL

EARTH TERM

INAL

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTR

INSICALLY SAFE FO

R ATEX/IEC

7570

LEVEL

N/A

1725

II 1/2 G Ex ia T4 G

a/Gb

Ta = -50 TO

71°C; IP65

Fig. 23: ATEX / IECEx installation drawing

Page 26: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

26

Level Plus® SoClean®

Operation Manual

12.5.3 Installation drawing (cont.)

DETAIL A

SCALE 1.60 : 1

DETAIL C

SCALE 3 : 1

DETAIL D

SCALE 1.2

DETAIL E

SCALE 1 : 1

A

C

D

E

11

22

33

44

55

66

77

88

AA

BB

CC

DD

REV

EC

O #

DESC

RIP

TION

TITLE

SIZED

WG

NO

.R

EV

PRO

DU

CT LIN

ESC

ALE:

BYD

ATE

SHEET

OF

UN

LES

S OTH

ER

WISE

SPEC

IFIED

TOLER

ANC

ES0 P

LACE

SM

M1 PLA

CE

MM

AN

GLE

S

0.5

0.1

- THR

EA

D D

EP

THS

AR

E TO

MIN

. FULL TH

DS

- DR

ILL DE

PTH

S A

RE

TO FU

LL DIA

.- R

EM

OV

E B

UR

RS

AN

D S

HA

RP

ED

GE

S- D

O N

OT S

CA

LE P

RIN

T- M

AC

HIN

ED

SU

RFA

CE

FINIS

H 3.2uM

[125 uIn]

PRO

PRIETA

RY D

ATA

THE

INFO

RM

ATIO

N A

ND

DE

SIG

N(S

) DIS

CLO

SE

DH

ER

EIN

AR

E TH

E P

RO

PE

RTY

OF M

TS S

YS

TEM

SC

OR

PO

RA

TION

AN

D M

AY

NO

T BE

US

ED

,R

EP

RO

DU

CE

D O

R D

ISC

LOS

ED

IN A

NY

FOR

ME

XC

EP

T AS

GR

AN

TED

IN W

RITIN

G B

Y M

TSS

YS

TEM

S C

OR

PO

RA

TION

. THIS

RE

STR

ICTIO

NE

XC

LUD

ES

INFO

RM

ATIO

N TH

AT IS

IN TH

E

PU

BLIC

DO

MA

IN O

R W

AS

LEG

ITIMA

TELY

IN TH

EP

RIO

R P

OS

SE

SS

ION

OF TH

E R

EC

IPIE

NT.

mM

TS SYS

TEMS

CO

RP

OR

ATIO

NS

ENSO

RS D

IVISIO

N3001 SH

ELDO

N D

RIVE

, CA

RY, N

C 27513

METRIC

FIRST

ANG

LED

651543-3

2 2

DR

AWN

BY: M

S

***NO

RE

VISION

S SHALL BE

MA

DE

WITH

OU

T THE

NO

TIFICA

TION

TO A

PPRO

VAL AG

EN

CY(S).***

AM

S10/24/14

RELEASE TO PRO

DU

CTION

B 7847 UPD

ATED IP RATIN

G FO

R HO

USIN

G TYPES M

S 1/19/15

C

C 7898 UPD

ATED TEM

PERATURE O

N N

OTE 12 TO

71C MS 2/23/15

+24V GNDEARTHTX/RX+TX/RX-

GND+24V

TX/RX-TX/RX+EARTH

GND

+24V

TX/RX-

TX/RX+

EARTH

FIGU

RE 1

SING

LE CAVITY & N

EMA H

OU

SING

FIGU

RE 2

DU

AL CAVITY H

OU

SING

NO

TES: 1. TH

E CU

STOM

ER SH

OU

LD C

ON

NEC

T THE O

UTSID

E GR

OU

ND

LUG

TO TH

E SAFETY EARTH

ING

GR

OU

ND

SYSTEM W

ARN

ING

: C

ON

DU

IT SEALS REQ

UIR

ED W

ITHIN

457 MM

(18") OF H

OU

SING

.

(ACP) INSTALLATIN

DW

G LP D

IGITAL

INTRIN

SICALLY SAFE FOR ATEX/IEC

+24V GND EARTH Tx/Rx+ Tx/Rx-

7570

Fig. 24: ATEX / IECEx installation drawing

Page 27: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

27

Level Plus® SoClean®

Operation Manual

12.5.3 EC Declaration of Conformity

EC Declaration of Conformity

EG-Konformitätserklärung

Déclaration CE de Conformité

MTS Systems Corporation, Sensors Division, 3001 Sheldon Drive, Cary NC 27513, USA declares as manufacturer in sole responsibility that the products erklärt als Hersteller in alleiniger Verantwortung, dass die Produkte déclare en qualité de fabricant sous sa seule responsabilité que les produits

Level Plus LPT x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (Tank Slayer)

Level Plus LPR x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (RefineME)

Level Plus LPS x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (SoClean)

Level Plus LPC x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (Chambered)

comply with the regulations of the following European Directives: den Vorschriften folgender europäischer Richtlinien entsprechen: sont conformes aux prescriptions des directives européennes suivantes :

94/9/EC Equipment and protective systems for use in potentially explosive atmospheres

Geräte und Schutzsysteme zur Verwendung in explosionsgefährdeten Bereichen Appareils et systèmes de protection à être utilisés en atmosphères explosibles

2004/108/EC Electromagnetic Compatibility

Elektromagnetische Verträglichkeit Compatibilité électromagnétique

Applied harmonized standards: Angewandte harmonisierte Normen: Normes harmonisées appliquées :

EN 60079-0:2012, EN 60079-11:2012, EN 60529:1991+A1:2000, EN 61326-1:2013, EN 61326-2-3:2013

EC type examination certificate: EG-Baumusterprüfbescheinigung: FM 14 ATEX 0068 X, 1st Supplement Certificat de l’examen CE de type : issued by / ausgestellt durch / exposé par: FM Approvals Ltd. Windsor, Berkshire, United Kingdom

Notified body for quality assurance control: FM Approvals Ltd. Benannte Stelle für Qualitätsüberwachung: Windsor, Berkshire, United Kingdom Organisme notifié pour l’assurance qualité : Ident number / Kennnummer / Numéro d’identification : 1725

Marking / Kennzeichnung / Marquage : II 1/2 G Ex ia IIC/ T4

Ta = -50°C to +71°C

Lüdenscheid, 2015-07-07

MTS Sensor Technologie GmbH & Co. KG, Auf dem Schüffel 9, 58513 Lüdenscheid, Germany

__________________________________

Thomas Muckenhaupt Quality Management ATEX Representative

EC14.012B

Page 28: Magnetostrictive Liquid Level Transmitters with …...4 Level Plus ® ®SoClean Operation Manual 2. Terms and definitions 6A Heavy Oils ‘Generalized Crude Oils’, Correction of

28

Document Part Number: 551693 Revision A (EN) 09/2015

Reg.-No. 003095-QN

MTS, Temposonics and Level Plus are registered trademarks of MTS Systems Corporation in the United States; MTS SENSORS and the MTS SENSORS logo are trademarks of MTS Systems Corporation within the United States. These trademarks may be protected in other countries. All other trademarks are the property of their respective owners. Copyright © 2015 MTS Systems Corporation. No license of any intellectual property rights is granted. MTS reserves the right to change the information within this document, change product designs, or withdraw products from availability for purchase without notice. Typographic and graphics errors or omissions are unintentional and subject to correction. Visit www.mtssensors.com for the latest product information. Product change notification alerts are available through the MTS Product Change Management System; register at www.mtssensors.com/PCMS.

LOCA

TION

S

LEGA

L NO

TICE

SUSA MTS Systems CorporationSensors Division3001 Sheldon DriveCary, N.C. 27513, USATel. +1 919 677-0100Fax +1 919 [email protected]

JAPANMTS Sensors Technology Corp.737 Aihara-machi, Machida-shi, Tokyo 194-0211, JapanTel. + 81 42 775-3838Fax + 81 42 775- [email protected]

FRANCEMTS Systems SASZone EUROPARC Bâtiment EXA 1616/18, rue Eugène Dupuis94046 Creteil, FranceTel. + 33 1 58 4390-28Fax + 33 1 58 [email protected]

GERMANYMTS Sensor TechnologieGmbH & Co. KGAuf dem Schüffel 958513 Lüdenscheid, GermanyTel. + 49 2351 9587-0Fax + 49 2351 [email protected]

CHINAMTS Sensors Room 504, Huajing Commercial Center, No. 188, North Qinzhou Road200233 Shanghai, ChinaTel. +86 21 6485 5800 Fax +86 21 6495 [email protected]

ITALYMTS Systems Srl.Sensor DivisionVia Diaz,425050 Provaglio d‘Iseo (BS), ItalyTel. + 39 030 988 3819Fax + 39 030 982 [email protected]