SoCLEAN®
Level Plus®
Operation Manual
Magnetostrictive Liquid Level Transmitterswith Temposonics® Technology
2
Level Plus® SoClean®
Operation Manual
Table of contents
1. Contact information ....................................................................32. Terms and definitions .................................................................43. Introduction .................................................................................64. Safety instructions ......................................................................6
4.1 Intended use ......................................................................... 64.2 Foreseeable misuse ............................................................... 64.3 Installation, commissioning, and operation .......................... 6
5. Product overview ........................................................................65.1 Components .......................................................................... 75.2 Accuracy ............................................................................... 85.3 Warranty ............................................................................... 85.4 Storage ................................................................................. 85.5 Model number identification ................................................. 95.6 Specifications ...................................................................... 11
6. Installation and mounting ........................................................126.1 Training ............................................................................... 126.2 Tools ................................................................................... 126.3 Stilling wells and guide poles .............................................. 126.4 Installation steps ................................................................. 126.5 Mounting ............................................................................ 12
7. Electrical connections ..............................................................137.1 Basic information ................................................................ 137.2 Safety recommendations .................................................... 137.3 Industrial topologies ........................................................... 137.4 Cable recommendations ..................................................... 147.5 Electrical conduit ................................................................. 147.6 Grounding ........................................................................... 157.7 Safety barriers ..................................................................... 15
8. Commissioning .........................................................................158.1 Training ............................................................................... 158.2 Tools ................................................................................... 158.3 Setup software .................................................................... 158.4 Commissioning steps ......................................................... 15
9. Maintenance .............................................................................169.1 Training ............................................................................... 169.2 Tools ................................................................................... 169.3 Inspection ........................................................................... 169.4 Preventative maintenance ................................................... 16
Repair ........................................................................................ 1710.1 RMA policy ....................................................................... 1710.2 Training ............................................................................. 1710.3 Tools ................................................................................. 1710.4 Troubleshooting ................................................................ 1710.5 Setup software .................................................................. 18
Interface .................................................................................... 1811.1 Modbus ............................................................................. 1811.2 DDA .................................................................................. 18
12. Agency information ................................................................. 1812.1 Approvals overview ......................................................... 1812.2 Certificates ...................................................................... 1812.3 FM ................................................................................... 1812.3.1 Special conditions of safe use ...................................... 1812.3.2 Labels .......................................................................... 1812.3.3 Installation drawing ...................................................... 1912.4 FMC ................................................................................ 2112.4.1 Special conditions of safe use ...................................... 2112.4.2 Labels .......................................................................... 2112.4.3 Installation drawing ...................................................... 2212.5 ATEX and IECEx .............................................................. 2412.5.1 Special conditions of safe use ...................................... 2412.5.2 Labels .......................................................................... 2412.5.3 Installation drawing ...................................................... 2512.5.4 EC Declaration of Conformity ....................................... 27
10.
11.
3
Level Plus® SoClean®
Operation Manual
1. Contact information
United States
GeneralTel: +1-919-677-0100Fax: +1-919-677-2343E-mail: [email protected]://www.mtssensors.com
Mailing and shipping addressMTS Systems CorporationSensors Division3001 Sheldon DriveCary, North Carolina, 27513, USA
Customer serviceTel: +1-800-633-7609Fax: +1-800-498-4442E-mail: [email protected]
Technical support and applications24 Hour Emergency Technical SupportTel: +1-800-633-7609e-mail: [email protected]
Germany
GeneralTel.: +49-2351-9587-0Fax: +49-2351-56491e-mail: [email protected]://www.mtssensors.com
Mailing and shipping addressMTS Sensor Technologie, GmbH & Co. KGAuf dem Schüffel 9D - 58513 Lüdenscheid, Germany
Technical support and applicationsTel.: +49-2351-9587-0e-mail: [email protected]://www.mtssensors.com
Japan
GeneralTel.: +81-42-775-3838Fax: +81-42-775-5516 e-mail: [email protected]://www.mtssensors.com
Mailing and shipping addressMTS Sensors Technology Corporation737 Aihara-cho, Machida-shiTokyo 194-0211, Japan
Technical support and applicationsTel.: +81-42-775-3838Fax: +81-42-775-5512
4
Level Plus® SoClean®
Operation Manual
2. Terms and definitions
6A Heavy Oils‘Generalized Crude Oils’, Correction of Volume to 60 °F against API Gravity.
6B Light Oils‘Generalized Products’, Correction of Volume to 60 °F against API Gravity.
6C Chemical‘Volume Correction Factors (VCF)’ for individual and special applica-tions, volume correction to 60 °F against thermal expansion coeffi-cients.
6C ModAn adjustable temperature reference for defining VCF.
A
API Gravity The measure of how heavy or light a petroleum liquid is compared to
water. Allowable values are 0 to 100 degrees API for (6A) and 0 to 85 degrees API for (6B).
D
DDA ‘Direct Digital Access’ – The proprietary digital protocol developed by
MTS for use in intrinsically safe areas.
Density Mass divided by the volume of an object at a specific temperature. The
density value should be entered as lb / cu. ft..
E
Explosionproof Type of protection based on enclosure in which the parts which can
ignite an explosive gas atmosphere are placed within, and which can withstand the pressure developed during an internal explosion of an ex-plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.
F
Flameproof Type of protection based on enclosure in which the parts which can
ignite an explosive gas atmosphere are placed within and which can withstand the pressure developed during an internal explosion of an ex-plosive mixture, and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure.
FOUNDATION™ fieldbus An all digital, serial, two-way communications system that serves as
the base-level network in a plant or factory automation environment. Developed and administered by the fieldbus FOUNDATION™.
G
GOVI ‘Gross Observed Volume of the Interface’ – The total volume of the tank
occupied by the interface liquid. The GOVI is only given when mea-suring two liquids and is calculated by subtracting the volume of the product from the total volume of liquid in the tank (GOVT – GOVP).
GOVP ‘Gross Observed Volume of the Product’ – The total volume of the tank
occupied by the product liquid. When measuring only one liquid, it is also the total volume of liquid in the tank (GOVT). When measuring two liquids it is the total volume of liquid in the tank minus the volume of the interface liquid (GOVT – GOVI).
GOVT ‘Total Gross Observed Volume’ – The total volume of liquid in the tank.
When measuring only one liquid it is equal to the volume of the product (GOVP). When measuring two liquids it is equal to the volume of the product and interface liquids (GOVP + GOVI).
GOVU ‘Gross Observed Volume Ullage’ – the difference in volume between the
working capacity of a tank and the total volume in the tank (Working Capacity – GOVT).
H
HART® A Bidirectional communication protocol that provides data access
between intelligent field instruments and host systems.
I
Interface Noun; The measurement of the level of one liquid when that liquid is
below another liquid.
Interface Adj.; The Software Graphical User Interface (GUI) that allows the user
to access software protocols (HART, DDA, MODBUS).
Intrinsic safety ‘Intrinsically safe’ - Type of protection based on the restriction of
electrical energy within apparatus of interconnecting wiring exposed to potentially explosive atmosphere to a level below that which can cause ignition by either sparking or heating effects.
5
Level Plus® SoClean®
Operation Manual
M
Mass The property of a body that causes it to have weight in a gravitational
field, calculated by density at the reference temperature multiplied by the volume correction factor (Density * VCF).
MODBUS A serial communications protocol published by Modicon in 1979 for use
with its programmable logic controllers (PLCs). It has become a de fac-to standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices.
N
NEMA Type 4X A product Enclosure intended for indoor or outdoor use primarily to
provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water; and to be undamaged by the formation of ice on the enclosure. They are not intended to provide protection against conditions such as internal condensation or internal icing.
NPT U.S. standard defining tapered pipe threads used to join pipes and
fittings.
NSVP ‘Net Standard Volume of the Product’ – The temperature corrected
volume for the product liquid in the tank, requires the transmitter to be ordered with temperature measurement capabilities. The NSVP is calculated by multiplying the volume of the product liquid by a volume correction factor based on temperature (GOVP * VCF).
R
Reference Temperature The temperature at which the density measurement is given, the allow-
able values are 32 °F to 150 °F.
S
Specific Gravity The density ratio of a liquid to the density of water at the same condi-
tions.
Sphere Radius The internal radius of the sphere that contains the liquid, the value is
used to calculate the volume along with the Sphere Offset.
Sphere Offset An offset value that accounts for additional volume in a sphere from
non-uniform sphere geometry, the value is used to calculate the volume along with the Sphere Radius.
Strap TableA table of measurement correlating the height of a vessel to the volume that is contained at that height. The transmitter can contain up to 100 points.
T
TEC ‘Thermal Expansion Coefficient’ - a value correlating the change in tem-
perature for an object with the change in its volume. Allowable values are 270.0 to 930.0. TEC units are in 10 E-6/Deg F.
Temperature Correction Method One of five product correction methods used to correct the product
volume in the tank due to changes in temperature from 60 °F including (6A, 6B, 6C, 6C Mod, and Custom Table.
V
Volume Calculation Mode One of two methods use to calculate volume measurements from level
measurements, including Sphere and Strap Table.
VCF ‘Volume Correction Factor’ – A table of measurements correlating
temperature points with correction factors for the liquids expansion/contraction. The transmitter can contain up to 50 points.
W
Working Capacity The maximum volume of liquid that the user desires for their vessel to
hold, typically 80% of the vessels maximum volume before overfill.
6
Level Plus® SoClean®
Operation Manual
3. Introduction
3.1 Purpose and use of this manual
The content of this technical documentation and of its various annexes is intended to provide information on mounting, installation and commissioning by qualified service personnel according to IEC 60079-14 or MTS trained service technicians and local regulations.
3.2 Used symbols and warningsWarnings are intended for your personal safety and for avoidance of damage to the described product or connected devices. In this documentation, safety information and warnings to avoid dangers that might affect the life and health of personnel or cause material damage are highlighted by the preceding pictogram, which is defined below.
4. Safety instructions
4.1 Intended useThe liquid level transmitter is intended to be used to measure the level of liquid(s) contained by a structure as well as the temperature of the liquid. The product may only be used for the applications defined under item 1 to item 4 below and only in conjunction with third-party devices and components recommended or approved by MTS Sensors. As a prerequisite of proper and safe operation, the product requires correct transport, storage, mounting and commissioning and must be operated with utmost care.
1. Application does not exceed product’s performance specification in section 5.6.
2. Product may only be installed in hazardous areas as specified by approval certifications in section 12 following special conditions of safe use outlined in section 12 or in safe areas.
3. The liquid(s) being measured are compatible with the selected wetted parts of the product.
4. MTS floats should be used for proper functionality and safety approval.
4.2 Foreseeable misuse
Important:Before starting the operation of the equipment read this documentation thoroughly and follow the safety information.
Symbol Meaning
NOTICE This symbol is used to point to situationsthat may lead to material damage, and/or personal injury.
4.3 Installation, commissioning and operation
1. Wear proper personal protection equipment such as hard hat, safety shoes, flame resistant clothing, safety glasses, gloves, and hearing protection.
2. Follow the specifications given in the technical documentation.3. Two (2) individuals are recommended to conduct proper installati-
on, commissioning, and repair of the level transmitter.4. Ensure the equipment used in a hazardous environment is selected
and installed in compliance with regulations governing the geogra-phical installation and facility. Only install equipment that complies with the types of protection relevant to the applicable classes, division, zones, category, gas group, and temperature code.
5. Protect the sensor against mechanical damage during installation and operation.
6. Do not use damaged products and secure them against unintentio-nal use. Mark damaged products as being defective.
7. Connect the sensor very carefully and pay attention to the polarity of connections. MTS recommends to not make connections while power is live.
8. Before turning on power, ensure that nobody’s safety is jeopar-dized by starting level transmitter and/or process.
9. Regularly follow preventative maintenance to prevent safety risks.10. Make sure that no wire strands are loose or sticking out of the
terminal block connection which could short and cause a problem.11. Make sure that no wire strands, including shield, are in contact
with the electronic module enclosure.
5. Product overview
The Level Plus® SoClean® Liquid-Level transmitter is a continuous multi-functional magnetostrictive transmitter that provides product level, interface level, and temperature to the user via Modbus, or DDA. Magnetostrictive technology is one of the most accurate and
Forseeable misuse Consequence
Process Temperature out of rangeSignal Degradation, Possible Damage to SensorSee Section 5.6 for Specifications
Power Supply out of rangeNo Communication, Possible Dam-age to SensorSee Section 5.6 for Specifications
Process Pressure out of rangePossible Damage to Sensor,See Section 5.6 for Specifications
Improper Chemical Compatibility
Possible Damage to Sensor,Customer Must Select Wetted Mate-rial that is compatible with liquid(s) in tank
Modifying SensorWarranty Void, Hazardous Approval Void Customer should contact facto-ry for custom unit
Improper GroundingPossible Damage to Sensor, Full Protection Compromised,See Section 7.6 for Grounding
Forseeable misuse Consequence
Wrong sensor connectionPossible damage to electronicsSee Section 7 for Electrical Connections
Improper InstallationPhysical damage to packagingSee Section 6 for Installation
Installation in unapproved Hazardous Area
Potential SparkSee Section 12 for Agency Information
Table 1: Foreseeable misuse
7
Level Plus® SoClean®
Operation Manual
Industries » Pharmaceutical » Food & beverage » Cosmetics
Applications » Bioreactor » Day Tanks » Storage tanks
Features » 3-in-1 measurement
» Product level » Interface level » Temperature
» No scheduled maintenance or recalibration » Field repairable » Inherent Accuracy ±1mm » 200 Point Strap Table » API Temperature Corrected Volumes
5.1 ComponentsThe Level Plus® SoClean® liquid level transmitter consists of four main components; a housing, outer pipe, float, and electronics. Varying the components of the transmitter allows the transmitter to be customized to almost any application.
HousingsLevel Plus® SoClean® transmitters are available in three housing configu-rations; NEMA Type 4X 316L stainless steel, explosion-proof single and dual-cavity housings as shown:
Fig. 3: Dual cavity explosion-proof housing
Fig. 2: Single cavity explosion-proof housing
Fig. 1: NEMA Type 4X 316L stainless-steel housing
1
1
2
2
3
3
4
4
A A
B B
C C
D D
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES� � �� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE C LL drawing
1 1
DRAWN BY:
114 mm(4.5 in.)
152 mm(6 in.)
124 mm(4.9 in.)
132 mm(5.2 in.)
87 mm(3.4 in.)
109 mm(4.3 in.)
75 mm(3 in.)
206 mm(8.1 in.)
152 mm(6 in.)
117 mm(4.6 in.)
145 mm(5.7 in.)
1
1
2
2
3
3
4
4
A A
B B
C C
D D
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES� � �� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE C LL drawing
1 1
DRAWN BY:
114 mm(4.5 in.)
152 mm(6 in.)
124 mm(4.9 in.)
132 mm(5.2 in.)
87 mm(3.4 in.)
109 mm(4.3 in.)
75 mm(3 in.)
206 mm(8.1 in.)
152 mm(6 in.)
117 mm(4.6 in.)
145 mm(5.7 in.)
1
1
2
2
3
3
4
4
A A
B B
C C
D D
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES� � �� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE C LL drawing
1 1
DRAWN BY:
114 mm(4.5 in.)
152 mm(6 in.)
124 mm(4.9 in.)
132 mm(5.2 in.)
87 mm(3.4 in.)
109 mm(4.3 in.)
75 mm(3 in.)
206 mm(8.1 in.)
152 mm(6 in.)
117 mm(4.6 in.)
145 mm(5.7 in.)
repeatable level technologies available to date. MTS is the inventor and purveyor of magnetostrictive technology and has been serving the level industry for over 35 years.
8
Level Plus® SoClean®
Operation Manual
Internal electronicsAll transmitters come with two electronic components of a sensing element and a board set. Rigid sensing elements are standard on SoClean® . Flexible sensing elements are available upon request. The board set consists of up to three electronic boards and a display. The display is capable of displaying the product level, interface level, and temperature. Designed into the display are five buttons for local setup of level transmitter using the stylus.
A temperature sensing function is optional with the SoClean® transmitter. The temperature sensing device is a Digital Thermometer mounted inside the transmitter’s outer pipe assembly. The SoClean® can be ordered with 1, 5, 12, or 16 temperature points.
AccessoriesMTS also offers a series of displays, housings, converters, and other accessories, please refer to the ‘Accessories Catalog’, MTS part number 551103.
5.2 AccuracyFor magnetostrictive transmitters inherent accuracy is measured in terms of non-linearity. Non-linearity is a measurement of any imperfections in the waveguide that are reflected in the linearity of the transmitter’s output. MTS tolerances reflect a maximum non-linearity of ± 1mm. MTS is able to achieve such strict tolerances by manufacturing all of its own waveguide from a proprietary alloy and testing 100% of all transmitters before shipping.
5.3 Warranty
All Level Plus® transmitters come with a two year limited warranty from the factory shipment date. A Return Materials Authorization (RMA) number is required and must accompany any transmitter returns. Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory. A Material Safety Data Sheet (MSDS) must also accompany the transmitter that was used in any process.
5.4 StorageIf storage is required prior to installation, store indoors in a dry environ-ment at ambient temperature range not to exceed -40°C (-40°F) to 71°C (160°F).
Important:Contact Technical Support or Customer Service for assistance if you suspect that the transmitter is not working correctly. Technical support can assist you with troubleshooting, part replacement, and Returned Material Authorization (RMA) information if required.
FloatsSoClean® transmitters offer numerous floats for different applications such as stainless steel, 3-A sanitary, hastelloy, Teflon, and Nitrophyl for both product level and interface level. To be able to accurately detect the interface level there needs to be a difference of at least 0.05 in specific gravities between the product and interface liquids. For detailed information about floats, refer to the ‘Accessories Catalog’, MTS part number 551103.For assistance with selecting a specific float for your application, please contact Technical Support with the following information: » Specific gravity of liquid(s) being measured » Process temperature » Process opening size » Vessel pressure
For ATEX and IECEx approvals, SoClean® transmitters should be used with a float having an offset weight and made of stainless steel or Has-telloy C. This allows the float to stay in contact with the pipe to prevent the buildup of an electrostatic charge. For detailed information about floats, refer to the ‘Accessories Catalog’, MTS part number 551103.Non-metalic floats with a projected surface area of less than 5,000 mm² should only be used in Zone 0, Gas group IIA such as float part numbers 201643-2, 201649-2, 201650-2, 201109, 251115 and 251116. All other non-metallic floats offered by MTS such as, 251939, 251119, 251120 and 252999, should not be used in a hazardous area application.
Outer pipe configurationsThe outer pipe is constructed of a variety of configurations. The SoClean® is available in a sanitary pipe. For other pipe options please consult other MTS options such as RefineMe®, Tank Slayer®, and/or USTDII.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES� � �� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE C Marketing
1 1
DRAWN BY:
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***
Order length
Order Length
3/4 in NPTAdjustable fitting
Pipe diameter16mm (0.625 in)
74 mm (2.9 in) minInactive zone
Tip of transmitter
Tank Flange(Provided by customer)
127 [5] minimum
Tank Flange
1 in NPT or BSPP Adjustablecompression fitting, male
127mm [5 in ]
Order Length
Pipe diameter (0.625 in. dia)constructed of 316l stainless steel
Sanitary process connection (sanitary cap)
304.8 mm(12 in.)
Fig. 4: Outer pipe configuration (TB version shown)
9
Level Plus® SoClean®
Operation Manual
5.5 Model number identification (Order code)
b Output
M Modbus
D DDA
j DT Placement
F Evenly spaced per API
C Custom
X None
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
a Sensor model
L P S SoClean® Level Transmitter
L P S16 17 18 19 20 21 22
a b c d e k
d Electronics mounting
1 Standard
f Materials of construction (Wetted parts)
1 316L stainless steel
2 Electropolished 316L stainless steel
f g h i j l m n o p
c Housing type
A NEMA housing w/cable
B NEMA housing w/terminal
C NEMA housing w/connector
D Single cavity with display
E Dual cavity with display
L SS single cavity w/display
g Process connection type
1 NPT adjustable
2 BSPP adjustable
4 Sanitary Tri-Clamp, Welded
5 Sanitary Tri-Clamp, Adjustable
e Sensor pipe
C Sanitary T-bar, TB
D Sanitary drain-in-place DP
E Sanitary clean-in-place CP
F Sanitary drain-in-place no hole, DN
Note: Contact factory for other materials
h Process connection size
B 1 in. (DN25)
D 2 in. (DN50)
E 2 1/2 in. (DN65)
F 3 in. (DN80)
G 4 in. (DN100)
J 6 in. (DN150)
X None
i Number of DT‘s (Digital Thermometer)
0 None
1 One DT
5 5 DTs
K Twelve DTs
M Sixteen DTs
k Notified body
C CEC (FMC)
E ATEX
F NEC (FM)
I IEC
X None
l Protection method
I IS
X No approval
(Continued on next page)
10
Level Plus® SoClean®
Operation Manual
n Unit of measure
M Metric - Millimeters
U US customary - Inches
1 2 3 4 5 6 7 8 9 10 11
ORDERING NOTE
Accessories such as floats, cables, and displays have to be ordered separately. All accessories are shown in the Accessories Catalog (551103).
L P S
a b c d e f g h i
Gas group
A Group A
B Group B
C Group C
D Group D
1 IIA
2 IIB
3 IIC
X None
p Special
S Standard Product
m
o Length (no decimal spaces)
X X X X X Rigid Pipe: 12 to 300 in (code as 01200 to 30000)
X X X X X Rigid Pipe: 305 to 7620 mm (code as 00305 to 07620)
12 13 14 15 16 17 18 19 20 21 22
kj l m n o p
5.5 Model number identification (continued)
11
Level Plus® SoClean®
Operation Manual
Level Output
Measured variable Product level and interface level
Output signal /Protocol Modbus RTU, DDA
Order length Sanitary Pipe: 305 mm (12 in.) to 7620 mm (300 in.) Ƥ
Inherent Accuracy ±1 mm (0.039 in.)
Repeatability 0.001% F.S. or 0.381 mm (0.015 in.) *(any direction)
Temperature Output
Measured variable Average and multipoint temperatures
Temperature accuracy ±0.2 ºC (0.4 ºF) range -40 ºC (-40 ºF) to -20 ºC (-4 ºF)*,±0.1 ºC (0.2 ºF) range -20 ºC (-4 ºF) to 70 ºC (158 ºF)*,±0.15 ºC (0.3 ºF) range 70 ºC (158 ºF) to 100 ºC (212 ºF)*,±0.5 ºC (0.9 ºF) range 100 ºC (212 ºF) to 105 ºC (221 ºF)
Electronics
Input voltage 10.5 to 28 Vdc
Fail safe High, Full scale for digital
Reverse polarity protection Series diode
EMC Standards IEC 61326-3-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8
Environmental
Enclosure rating NEMA Type 4X, IP65
Humidity 0 to 100% relative humidity, non-condensing
Operating temperatures Electronics: -40 °C (-40 °F) to 71 °C (160 ºF)Sensing element: -40 °C (-40 °F) to 125 °C (257 °F) ◊Temperature element: -40 °C (-40 °F) to 105 °C (221 °F)
Vessel pressure Rigid pipe: 2000 psi (138 bar)
Materials Wetted parts: 316L stainless steel †Non-wetted parts: 316L stainless steel, Epoxy coated aluminum
Field Installation
Housing dimensions Single cavity:145 mm (5.7 in.) W x by 127 mm (5 in.) D x 109 mm (4.3 in.) H Dual cavity:117 mm (4.6 in.) W x by 127 mm (5 in.) D x 206 mm (8.1 in.) H Stainless steel single cavity:178 mm (7.1 in.) W x by 135 mm (5.3 in.) D x 153 mm (6 in.) H NEMA Type 4X:87 mm (3.4 in.) W x by 124 mm (4.9 in.) D x 132 mm (5.2 in.) H
Mounting
Rigid pipe Tri-Clamp, 3/4 in. Adjustable MNPT or BSPP fitting
Wiring
Connections 4-wire shielded cable or twisted pair, Daniel Woodhead 6-pin male connector,4570 mm (180 in.) integral cable with pigtail
Electrical Connections
Single and Dual Cavity 3/4 in. FNPT conduit opening, M20 for ATEX/IECEx version
NEMA Type 4X 1/2 in. FNPT conduit opening
Display
Measured variables Product level, interface level and temperature
* Whichever is greater ∆ Contact factory for longer lengths.◊ Contact factory for specific temperature ranges.† Contact factory for alternative materials.§ Order length equals the measurement range plus the inactive zone.
5.6 Specifications (Technical data)
12
Caution:It is recommended that assembly and mounting of this transmitter should not be done alone. To ensure proper and safe assembly of the SoClean® transmitter, a minimum of two (2) individuals are recommended. Gloves are also recommended. PPE is required for work areas such as safety shoes, safety glasses, hard hat, and fire resistant clothing.
Level Plus® SoClean®
Operation Manual
6. Installation and mounting
6.1 Training
Installation should only be conducted by qualified service personnel according to IEC 60079-14 or MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.
6.2 Stilling wells and guide polesLevel Plus® transmitters can be mounted in slotted or unslotted stilling wells but a slotted stilling well is always preferred. Using a unslotted stilling well will negatively affect performance of any level device as the level in the stilling well can differ from the level in the tank. The Level Plus® transmitter can also be installed to one side of the stilling well to also allow for sampling and manual gauging from the same opening as the automatic tank gauging. Contact Technical Support for details.
Level Plus® transmitters do not require a stilling well for installation. Our transmitters are installed in numerous tanks without stilling wells with no loss in performance. A stilling well is highly recommended for agitated, turbulent, and/or fast filling tanks.
6.3 Tools » Channel Lock pliers » Common head screwdriver
6.4 Installation steps
1. Consult Section 4.3 before starting.2. Perform Commissioning Steps 1-9 in Section 8.4.3. For CP end plug, remove hitch pin and install float. For DN end plug, install float but be careful as float is not retained and will fall off. For TB and DP end plugs, the float is already installed. 4. Secure the Tri-Clamp onto the mating connection on tank.5. Tighten the Tri-Clamp to hold the transmitter in place. 6. Terminate the field wire cables noting proper wire orientation.
6.5 MountingThe method of mounting the transmitter is dependent on the vessel or tank in which it is being used, and what type of transmitter is being mounted. There are two typical methods for mounting; threaded flange mounting and welded Tri-clamp mounting.
13
7. Electrical connections
7.1 Basic informationA typical intrinsically safe connection for the Level Plus® SoClean® trans-mitter includes protective safety barriers, a power supply and a reading or monitoring device. Refer to Agency information in Section 12.
7.2 Safety recommendationsBe sure to:1. Always follow applicable local and national electrical codes and observe polarity when making electrical connections. 2. Never make electrical connections to the SoClean® transmitter with power turned on. 3. Make sure that no wire strands are loose or sticking out of the terminal block connection which could short and cause a problem. 4. Make sure that no wire strands, including shield, are in contact with the electronic module enclosure. 5. The electronics module enclosure is grounded through internal circuitry and is electronically isolated from the explosion-proof housing.
7.3 Industrial topologiesThere are four topologies described and illustrated below. However, the daisy chain topology is not recommended by MTS.
Point-to-pointThe point-to-point topology consists of having only one device on the loop as shown in Figure 8. This topology is not usually used with a bus network since it does not take advantage of placing multiple devices on a loop.
PLC
Level Plus® SoClean®
Operation Manual
Riser
Tank flange(customer suppliedor ordered separately)
Float accessport
Fig. 6: Threaded flange mounting for flexible pipe
Fig. 7: Tri-Clamp mounting for pipe
Tri-Clamp mountingThe SoClean® transmitter can also be mounted to a Tri-Clamp as shown in Figure 7. First, install float(s) onto the transmitter. Second, install the float retaining hardware on the tip of the transmitter. To complete the installation, mount the transmitter, Tri-Clamp and float(s) as a unit in to the tank.
Fig. 8: Point-to-point topology
Threaded flange mountingIn some applications, the SoClean® transmitter can be mounted directly to the tank or flange via a NPT or BSPP threaded fitting, assuming there is a proper threaded connection available. If the float will not fit through the flange opening when the flange is removed, there must be some alternative means to mount the float on the transmitter from inside the vessel; this may require an access port nearby the entry point of the transmitter as shown in Figure 6.
Riser
NPT or BSPP fitting
Tank flange(customer suppliedor ordered separately)
Float accessport
Tip of transmitter
14
Notes:1. Tighten housing cover (both front and back covers if dual cavity) to full stop against the O-ring.2. Do not over-tighten compression fittings.3. Use side conduit entry only.4. In high humidity areas, use a breather drain type conduit sealing fitting to minimize moisture intrusion.
Conduit sealing fitting
NPT FittingDo not over-tightencompression fitting!
Interface float(ordered
separately)
Product float(ordered
separately)
View shown withcover removed
Plugged entryDo not use(see notes)
Do not remove cover with circuit livein hazardous locations!
Follow safe work procedures.
3/4 NPT conduit accessUse NPT conduit fitting only!
Conduit(flexible or rigid)
Conduit fromcontrol room
Level Plus®
Level Plus® SoClean®
Operation Manual
7.4 Cable recommendationsRefer to ‘Table 1’ below for general requirements of cable types for the Level Plus® SoClean® analog transmitter.
Cable specifications
7.5 Electrical conduit
Table 2: Cable specification and parameters
Fig. 12: Electrical conduit installation
Bus with spursThe bus with spurs topology has a main trunk cable that has each device connected via its own spur at a junction box as shown in Figure 9. The bus with spurs and tree topologies can also be used together to form a hybrid topology.
Tree alignmentThe tree topology is very similar to the bus with spurs topology with the main difference of having a common junction box for all of the transmit-ters as shown in Figure 10. Bus with spurs and tree topologies can also be used together to form a hybrid topology.
Daisy chainThe daisy-chain topology utilizes a single cable that is connected to all of the transmitters with the cable being interconnected at each field device. When using this topology make sure that the wiring practice allows for one transmitter to be disconnected without disconnecting the entire loop as shown in Figure 11. MTS does not suggest using the daisy-chain topology.
PLC
PLC
Fig. 9: Bus with spurs topology
Fig. 10: Tree topology
Fig. 11: Daisy-chain topology
PLC
Parameter Specification
Minimum cable size 24 AWG or heavier (0.51 mm diameter)
Cable type Single pair shielded or multiple pair with overall shield; minimum 0.010 in. (0.25 mm) insulation thickness
Capacitance Less than 30 pF/Ft
15
Level Plus® SoClean®
Operation Manual
Entity parameters
Digital supply Ui = 28 Vdc
Ii = 100 mA
Ci = 0.0 µF
Li = 0 mH
Pi = 700 mW
Digital communication
Ui = 8.6 Vdc
Ii = 10 mA
Ci = 0.0 µF
Li = 0.0 mH
Pi = 21.5 mW
Table 3: Safety barrier entity parameter references
Table 4: Safety barrier entity parameter references
7.6 Grounding
There are two methods to provide an earth ground to the earth ground of the electronics. Refer to’ Table 2’ for safety barrier references.
» Run an earth ground through the conduit and connect directly to the earth ground lug inside the housing. » Run an earth ground directly to the ground lug on the outside of the
housing.
7.7 Safety barriersRefer to Table 2 for entity parameters and Table 3 for example safety barriers
Note:Grounding the transmitter through a threaded conduit connection does not provide sufficient ground.
8. Commissioning
8.1 TrainingCommissioning should only be conducted by qualified service person-nel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.
8.2 Tools » Channel Lock pliers » RS485 to USB Converter (MTS Part # 380114) » PC » Linear Regulated Power Supply » MTS Setup Software
8.3 Setup softwareMTS offers Setup Software that is shipped with the level transmitter and is also available for download from www.mtssensors.com. The Setup Software is to be used for installation, commissioning, and troubleshoo-ting. For further details on how to use the setup software consult the Interface Manual Modbus (MTS Part# 551700) and the Interface Manual DDA (MTS Part# 551701).
Supplier STAHL STAHL
Type 9001/01-280-100-101
9001/01-086-010-101
Maximum voltage 28 Vdc 8.6 Vdc
Maximum current(each channel)
100 mA 10 mA
Maximum power(each channel)
700 mW 21.5 mW
Number of channels 1 1
Interface Modbus/DDA Modbus/DDA
8.4 Commissioning steps
1. Consult Section 4.3 before starting2. Remove level transmitter from shipping container.3. Insert pipe into float(s) making sure float(s) are in the active range.4. Connect power, RS485 to USB converter, and PC.5. Open MTS Setup Software.6. Establish Communication.7. For DDA Interface – Set Address. 8. For Modbus Interface – Set Address, Enter Strap Table, Setup Volume Correction Method. 9. Disconnect Power and Communication. Remove floats. Prepare level transmitter for transport to the top of the tank.10. Complete Installation in Section 6.4.11. Have qualified technician perform hand measurement. Enter hand measurement into MTS Setup Software and calibrate.12. Store all settings as backup file according to site name and tank number.
Note:For Additional details consult the protocol specific Interface Manual Modbus (MTS Part #551700) and Interface Manual DDA (MTS Part #551701).
16
Level Plus® SoClean®
Operation Manual
9.3 InspectionBelow are some standard items that should be inspected on a regular basis to make sure that the level transmitter and surrounding environ-ment are in operating condition.
» Hazardous Area Label is present and legible » Hazardous Area approval is correct for installation » There are no visible unauthorized modifications » Electrical connections are tight » Condition of enclosure gasket is satisfactory » No water ingress (white powder) » No obvious damage to cable » Sealing of conduit or cable gland is satisfactory » Earth ground is satisfactory » Single or Dual Cavity Enclosure threads are not damaged » Housing and sensing element piston o-ring is not damaged or
cracked » No corrosion on visible parts » Printed circuit boards are clean and undamaged
9.4 Preventative maintenanceLevel Plus® level transmitters do not typically require preventative maintenance but may require preventative maintenance dependent on the application. For general purpose applications where there is no potential for buildup on the pipe and/or float there is no need for preventative maintenance but routine inspection is still suggested. For severe service applications where there is potential for buildup on the pipe and/or float then preventative maintenance is required.
9.4.1 General purpose applications
9.4.1.1 Perform Inspection suggested in section 9.3
9.4.2 Severe Service Applications
9.4.2.1 Perform Inspection suggested in section 9.3
9.4.2.2 Disconnect Power.
9.4.2.3 Disconnect process connection from tank. Remove pipe from tank.
9.4.2.4 When the bottom of the pipe is reached inspect the floats.
9.4.2.4.1 If the floats are highly contaminated then remove the assembly from the tank and remove the floats from the pipe. This is not possible with TB and DP end plugs.
9.4.2.4.2 If the floats are slightly contaminated then clean the floats without remo-ving the floats from the pipe.
9.4.2.5 Replace pipe and floats in tank.
9.4.2.6 Connect process connection to tank.
9.4.2.7 Connect Power.
9.4.2.8 The process should be carried out regularly until a consistent pattern has been established as to how long the intervals between cleanings should be.
Note:It is best to clean the pipe as it is removed from the tank to minimize the amount of product that is removed from the tank. The user should take caution and abide by all regulations so that product is not spilled and the environment is not contaminated.
9. Maintenance
9.1 TrainingMaintenance should only be conducted by qualified service personnel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.
9.2 Tools » Channel Lock pliers » RS485 to USB Converter (MTS Part # 380114) » PC » Linear Regulated Power Supply » MTS Setup Software
9.4.1.2 No additional preventative maintenance is necessary. Preventative maintenance suggested for Severe Service Applications may be performed.
17
Level Plus® SoClean®
Operation Manual
10. Repair
10.1 RMA policy
All Level Plus® transmitters come with a two year limited warranty from the factory shipment date. A Return Materials Authorization (RMA) num-ber is required and must accompany any transmitter returns. Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory. A Material Safety Data Sheet (MSDS) must also accompany the transmitter that was used in any process.
10.2 TrainingRepair should only be conducted by qualified service personnel according to IEC 60079-14 and MTS trained service technicians and local regulations. MTS offers web based and in person training for installation, commissioning, maintenance, and repair. MTS also offers factory direct services for these same functions. Contact MTS to discuss training or factory direct services before starting.
10.3 Tools » Channel Lock pliers » Phillips head screwdriver » Common head screwdriver » RS485 to USB Conververter (MTS Part # 380114) » PC » Linear Regulated Power Supply
Important:Contact Technical Support or Customer Service for assistance if you suspect that the transmitter is not working correctly. Technical support can assist you with troubleshooting, part replacement, and Returned Material Authorization (RMA) information if required.
10.4 TroubleshootingSymptom Possible cause Action
No communication with tramitter
No power Check voltage at transmitter
Wiring incorrect Reference installation drawing section 12
Wrong address DDA factory default is ‘192 ’Modbus factory default is ‘247 ’
Wrong software Confirm correct software
Wrong protocol Confirm software and transmitter are same protocol
Missing magnet error
Float not recognized Confirm that the float is attached
Float is in the dead zone
Raise float to see if the error stops
Wrong number of floats selected
Confirm that the number of floats on the transmitter and the number of floats the transmitter is attempting to verify are the same.
Trigger level error
Gain needs to be adjusted
Consult Factory
SE is damaged Consult Factory
Min. trigger level too high
Consult Factory
Volume calculation error
No strap table entered
Enter strap table
Level outside range of strap table
Enter additional points in strap table
Strap table incorrect
Check value entries
VCF error No VCF table entered
Enter VCF table
VCF table incorrect
Check VCF value entries
Table 5: Troubleshooting reference
10.4 Troubleshooting
18
Level Plus® SoClean®
Operation Manual
12.2 CertificatesDownloadable copies of all certificates are located at www.mtssensors.com and can be downloaded on the product specific landing page. If there is any difficulty in obtaining the certificates from the web contact MTS Technical Support and they will be sent electronically.
12.3 FM
12.3.1 Special Conditions of Safe Use 1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.
Fig. 13: FM label
Fig. 14: FM label
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES
0.5 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE 551629-1 B
1 2
DRAWN BY: NJ
A NJ
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***
INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDCL. I, Zone 0/1, AEx ia IIC T4Ta = -50°C to +71°C ; IP65when connected in accordance with FM approved installa on drawing # 651543-1
WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS
Model No: Serial No: Date :
MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513
Level Plus Transmitter
USE MTS LOGO ARTWORK
10 POINT SIZE
8 POINT TEXT SIZE
4.5 POINT TEXT SIZE
MTS TO PRINTMODEL NO.SERIAL NO.
DATE CODE.
ENTITY PARAMETERS:SEE PRINT REFERENCE CHART
4.5 POINT TEXT SIZE
FM APPROVED
USE FM LOGO ARTWORK
US
LEVEL
1:1
7570 RELEASE TO PRODUCTION
(ACP) LABEL, LP, IS US - DIGITAL
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.
P/N 551629-1 Rev B
10/24/14
86.30 [3.40]
1.78 [.07]
34.69 [1.37]
1.78 [.07]
69.85 [2.75]
R3.30 [.13]
28.70 [1.13]
15.80 [.62]
12/02/14NJB 7847 IP RATING WAS 66
®
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES���� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE A 551634- B
1 1
DRAWN BY: NJ
A NJIP RATING WAS 66.7847B 12/2/14
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***NJ
MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513
INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDCL. I, Zone 0/1, AEx ia IIC T4Ta = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS
INSTALL PER DRAWING # 651543-1SUPPLY VOLTAGE: 28 VDC
Level Plus Transmitter
35.05 [1.38]
"L1"∆ "L2"
17.53 [.69]
7.5 POINT SIZEMTS TO PRINTMODEL NO.
SERIAL NO./DATE CODE
� 3.05 [.12] X2
4.0 POINT TEXT SIZE(TYP.)
8.97 [.35] 3.47 [.14]
7570 RELEASE FOR PRODUCTION
(ACP) LABEL, LP, IS US - DIGITAL
FM LOGO ARTWORK4.5 POINT TEXT SIZE
FM US
USE MTS LOGO ARTWORK14.0 POINT SIZE
LEVEL
1:1
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS.4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.5. MATERIAL: .8 [0.03] THICK ALUMINUM6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.
APPROVED
P/N 551634-X Rev B
10/24/14
TABLE 1DASH # HSG "L1" "L2"
-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]
SEE TABLE 1 FOR DASH #.
®
12.3.2 Labels
11.1 ModbusMTS offers Modbus RTU over a RS485 half-duplex network. For additional information consult Interface Manual Modbus, MTS Part# 551700.
11.2 DDAMTS offers DDA (Direct Digital Access) over a RS485 half-duplex network. For additional information consult Interface Manual DDA, MTS Part# 551701.
12. Agency information
12.1 Approvals overviewThe Notified Body is designated in the 13th digit of the model number and the Protection Method is designated in the 14th digit of the model number. These two digits of the model number specify the hazardous area approval that provided with the selected level transmitter.
Table 6: Agency approvals
10.5 Setup softwareMTS offers Setup Software that is shipped with the level transmitter and is also available for download from www.mtssensors.com. The Setup Software is to be used for installation, commissioning, and troubleshoo-ting. For further details on how to use the setup software consult the Interface Manual Modbus (MTS Part# 551700) and the Interface Manual DDA (MTS Part# 551701).
11. Interface
SoClean® is available with multiple outputs including Modbus and DDA. This Operation and Installation Manual includes all of these outputs. Each output has its own specialized Interface Manual that should be consulted for additional information on the specific output.
Notified body
Protection method
Classifications Standard
C = CEC I = Instrinsic Safety
Clss I, Division 1, Groups A, B, C, DEx ia IIC T4 Ga/GbTa = -50 °C to 71 °C
CSA C22.2 No. 1010.1 2004,CSA C22.2 No. 157-92 (2012),CSA C22.2 No. 60079-0:2011,CSA C22.2 No. 60079-11:2014CSA C22.2 No. 60529
E = ATEX
I = Instrinsic Safety
Ex II 1/2 G Ex ia IIC T4 Ga/GbTa = -50 °C to 71 °C
EN 60079-0:2012EN 60079-11:2012
F = NEC I = Instrinsic Safety
Class I, Division 1, Groups A, B, C, DClass I, Zone 0/1, AEx ia IIC T4Ta = -50 °C to 71 °C
FM 3600:2011FM 3610:2010FM 3810: 2005ANSI/ISA 60079-0:2013, ANSI/ISA 60079-11:2014, ANSI/ISA 60529-:2004
I = IEC I = Instrinsic Safety
Ex ia IIC T4 Ga/GbTa = -50 °C to 71 °C
IEC 60079-0:2011IEC 60079-11:2011
19
Level Plus® SoClean®
Operation Manual
12.3.3 Installation drawing
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-1
1 2
DR
AWN
BY: M
S
***NO
REV
ISION
S SH
ALL BE M
ADE W
ITHO
UT TH
E NO
TIFICATIO
N TO
APPR
OV
AL AG
ENC
Y(S
).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 12/2/14C
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
24 VDC
COM
MO
N- >
Rx /Tx+
Rx /Tx-
GRO
UN
D
EARTH G
ROU
ND
(SEE NO
TE 4)
EARTH G
ROU
ND
(SEE NO
TE 4)
Rx/Tx-
Rx/Tx+
GND
+24V
SAFETY BARRIER
SAFETY BARRIER
SAFETY BARRIER
NO
TES
:1.A
LL NA
TION
AL A
ND
LOC
AL C
OD
ES
AN
D R
EGU
LATIO
NS
MU
ST BE
AD
HE
RE
D TO
WH
EN IN
STALLIN
G TH
E LE
VEL SE
NSO
R IN
HA
ZAR
DO
US
EN
VIRO
NM
EN
TS.
SE
AL A
LL CO
ND
UITS W
ITHIN
457 MM
(18"). 2.LO
OP
CAB
LE M
US
T BE 24 AW
G TO
14 AW
G (.511M
M² to 1.6M
M²)
SH
IELDE
D TW
ISTE
D P
AIR
CA
BLE
WITH
SH
IELD. C
ABLE C
AP
ACITA
NC
E M
US
T B
E LE
SS TH
AN
30 pF PER
FOO
T (98 pF PE
R M
). CA
BLE SH
IELD
IS CO
NN
EC
TED
TO SY
STE
M G
RO
UN
D IN
NO
N-H
AZAR
DO
US
AR
EA
. SE
E INS
TALLA
TION
MA
NU
AL FO
R
AD
DITIO
NA
L CAB
LE IN
FOR
MA
TION
. 3.TH
E R
ES
ISTAN
CE
BE
TWEE
N E
ARTH
GR
OU
ND
AND
THE
INTR
INSIC
ALLY
SA
FE GR
OU
ND
MU
ST B
E LESS
THA
N 1 O
HM
. 4.TH
E TR
AN
SD
UC
ER
FRA
ME
SHA
LL BE
GR
OU
ND
ED
TO EA
RTH
GR
OU
ND
DIR
ECTLY
OR
THR
OU
GH
THE
EQU
IPM
EN
T ON
WH
ICH
IT IS M
OU
NTE
D.
5. CO
NTR
OL E
QU
IPM
ENT C
ON
NE
CTE
D TO
AS
SO
CIATE
D A
PPA
RA
TUS
MU
ST
NO
T US
E OR
GE
NE
RATE
MO
RE
THAN
250 VR
MS
OR
VD
C 6.A
SS
OC
IATED
APP
AR
ATUS
MA
NU
FACTU
RE
R'S
INS
TALLA
TION
DR
AW
ING
MU
ST B
E FO
LLOW
ED W
HE
N IN
STA
LLING
THIS
EQU
IPM
EN
T. 7.O
NLY
US
E NE
C (e.g FM
) APP
RO
VE
D B
AR
RIE
RS
. 8.E
NTITY P
AR
AME
TER
S: S
UPP
LY: R
x/Tx-: Rx/Tx+:
Ui = 28V
DC
Ui= 8.6V
Ui= 8.6V
Ii = 100mA
Ii = 10mA
Ii = 10mA
C
i = 0 µF Ci = 0 µF C
i = 0 µF Li = 0 µH
Li = 0 µH Li = 0 µH
Pi = 0.7 W
Pi= 0.0215 W
P i= 0.0215 W
9.THE
ENTITY
CO
NC
EPT A
LLOW
S INTE
RC
ON
NE
CTIO
N O
F INTR
INS
ICA
LLY S
AFE
APP
AR
ATU
S W
ITH AS
SO
CIA
TED A
PPA
RA
TUS
WH
EN
THE
FOLLO
WIN
G IS
TRU
E:
V
max or U
i ≥ Voc, V
t or Uo;
Imax or Ii ≥ Isc, It or Io;
Pm
ax or Pi ≥ Po;
Ca ≥ C
i + Ccable;
La ≥ Li + Lcable. 10.D
UAL-C
AVITY
EN
CLO
SU
RE
S: C
US
TOM
ER
CO
NN
EC
TION
S WILL BE
MA
DE AT TE
RM
INA
L BLO
CK
ON
PO
WE
R SID
E O
F HO
US
ING
(NO
T TO TE
RM
INA
L BLO
CK
ON
INTER
CO
NN
EC
T BO
ARD
). 11.IN
STA
LLATIO
N SH
OU
LD B
E IN A
CC
OR
DAN
CE
WITH
ANS
I/ISA
RP
12.06.01 "INS
TALLA
TION
OF
INTR
INS
ICA
LLY SA
FE S
YSTE
MS
FOR
HA
ZAR
DO
US
(CLA
SS
IFIED
) LOC
ATIO
NS
" A
ND
THE
NA
TION
AL E
LEC
TRIC
AL C
OD
E (AN
SI/N
FPA
70). 12.TH
E M
AX
IMU
M PE
RM
ITTED
AM
BIE
NT TE
MP
ER
ATU
RE
OF TH
E LE
VEL P
LUS
DIG
ITAL/A
NA
LOG
LE
VE
L TRAN
SM
ITTER
IS 71 °C
. TO A
VO
ID TH
E E
FFEC
TS O
F PR
OC
ESS
TEM
PE
RA
TUR
E A
ND
O
THE
R TH
ER
MAL EFFE
CTS C
AR
E S
HALL B
E TAK
EN
TO EN
SU
RE
THE
SU
RR
OU
ND
ING
AM
BIEN
T A
ND
THE
AMBIE
NT IN
SID
E TH
E TR
ANS
MITTE
R H
OU
SING
DO
ES
NO
T EX
CE
ED
71°C 13.C
AU
TION
: FLEX
IBLE
GA
UG
ES
HA
VE
A MIN
IMU
M B
EN
D D
IAM
ETER
OF 406M
M(16")
14.WA
RN
ING
: THE
APP
AR
ATU
S EN
CLO
SU
RE
CO
NTA
INS A
LUM
INU
M A
ND
IS CO
NS
IDE
RED
TO C
ON
STITU
TE A
PO
TEN
TIAL R
ISK O
F IGN
ITION
BY IM
PAC
T OR
FRIC
TION
. CAR
E M
UST B
E TA
KEN
IN
TO A
CC
OU
NT D
UR
ING
INS
TALLA
TION
AN
D U
SE
TO P
REV
EN
T IMP
ACT O
R FR
ICTIO
N 15.W
AR
NIN
G: S
UBS
TITUTIO
N O
F CO
MP
ON
EN
TS M
AY
IMP
AIR
INTR
INS
IC S
AFE
TY.
16.WA
RN
ING
: TO PR
EV
ENT IG
NITIO
N O
F FLAM
MA
BLE
OR
CO
MB
USTIB
LE A
TMO
SP
HER
ES
, D
ISC
ON
NE
CT P
OW
ER BE
FOR
E S
ERV
ICIN
G
17.WA
RN
ING
: THE
EQU
IPM
EN
T CO
NTA
INS N
ON
-ME
TALLIC E
NC
LOS
UR
E PA
RTS, TO
PR
EV
EN
T TH
E R
ISK
OF E
LEC
TRO
STA
TIC SP
AR
KING
. THE
NO
N-M
ETA
LLIC S
UR
FACE
SH
OU
LD O
NLY
B
E C
LEAN
ED
WITH
A DA
MP
CLO
TH.
NO
N H
AZARDO
US LO
CATION
HAZARD
OU
S LOCATIO
N
AGEN
CY C
ON
TRO
LLED D
RAW
ING
(US). N
O C
HAN
GES W
ITHO
UT PR
IOR
AGEN
CY APPR
OVAL
EARTH TERM
INAL
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTR
INSICALLY SAFE FO
R U
S
7570
LEVEL
FM
APPROVED US
N/A
INTRIN
SICALLY SAFECL. I, D
IV. 1, GR. ABCD
Ex ia IIC T4 Ga/G
bTa =
-50 to 71°C ; IP65
Fig. 15: FM installation drawing
20
Level Plus® SoClean®
Operation Manual
12.3.3 Installation drawing (cont.)
DETAIL A
SCALE 1.60 : 1
DETAIL C
SCALE 3 : 1
DETAIL D
SCALE 1.2
DETAIL E
SCALE 1 : 1
A
C
D
E
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-1
2 2
DR
AWN
BY: M
S
***NO
REV
ISION
S SH
ALL BE M
ADE W
ITHO
UT TH
E NO
TIFICATIO
N TO
APPR
OV
AL AG
ENC
Y(S
).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 12/2/14C
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
+24V GNDEARTHTX/RX+TX/RX-
GND+24V
TX/RX-TX/RX+EARTH
GND
+24V
TX/RX-
TX/RX+
EARTH
FIGU
RE 1
SING
LE CAVITY & N
EMA H
OU
SING
FIGU
RE 2
DU
AL CAVITY H
OU
SING
NO
TES: 1. TH
E CU
STOM
ER SH
OU
LD C
ON
NEC
T THE O
UTSID
E GR
OU
ND
LUG
TO TH
E SAFETY EARTH
ING
GR
OU
ND
SYSTEM W
ARN
ING
: C
ON
DU
IT SEALS REQ
UIR
ED W
ITHIN
457 MM
(18") OF H
OU
SING
.
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTRIN
SICALLY SAFE FOR U
S
+24V GND EARTH Tx/Rx+ Tx/Rx-
7570
Fig. 16: FM installation drawing
21
Level Plus® SoClean®
Operation Manual
12.4 FMC
12.4.1 Special conditions of safe use
1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus® Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.
12.4.2 Labels
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES
0.5 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE 551629-2 B
1 2
DRAWN BY:
A
NJ
NJ
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***
WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS
INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDEx ia IIC T4 Ga/GbTa = -50°C to +71°C ; IP65when connected in accordancewith FM approved installation drawing # 651543-2
MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513
Model No: Serial No: Date :
USE MTS LOGO ARTWORK
10 POINT SIZE
8 POINT TEXT SIZE
4.5 POINT TEXT SIZE
MTS TO PRINTMODEL NO.SERIAL NO.
DATE CODE.
ENTITY PARAMETERS:SEE PRINT REFERENCE CHART
4.5 POINT TEXT SIZE
FM APPROVED
USE FM LOGO ARTWORK
C
LEVEL
1:1
7570 RELEASE TO PRODUCTION
(ACP) LABEL, LP, IS CANADA - DIGITAL
Transmitter
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.
P/N: 551629-2 Rev B
10/24/14
69.85 [2.75]
R3.30 [.13]
28.70 [1.13]1.78 [.07]
15.80 [.62]
34.69 [1.37]
1.78 [.07]
86.30 [3.40]
IP RATING WAS 66 12/02/14NJ7847B
Level Plus ®
Fig. 17: FMC label
Fig. 18: FMC label
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES���� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE A 551702- B
1 1
DRAWN BY: NJ
NJNJ 12/2/14B 7847 IP RATING WAS 66.
A
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***
MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513
INTRINSICALLY SAFECL. I, Div. 1, GR. ABCDEx ia IIC T4 Ga/GbTa = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNING
INSTALL PER DRAWING # 651543-2SUPPLY VOLTAGE: 28 VDC
35.05 [1.38]
"L1"∆ "L2"
17.53 [.69]
7.5 POINT SIZEMTS TO PRINTMODEL NO.
SERIAL NO./DATE CODE
� 3.05 [.12] X2
4.0 POINT TEXT SIZE(TYP.)
8.97 [.35] 3.47 [.14]
7570 RELEASE FOR PRODUCTION
(ACP) LABEL, LP, IS CANADA - DIGITAL
FM LOGO ARTWORK4.5 POINT TEXT SIZE
FM C
USE MTS LOGO ARTWORK14.0 POINT SIZE
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS..4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.5. MATERIAL: .8 [.03] THICK ALUMINUM.6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.
APPROVED
P/N 551702-X Rev B
LEVEL
1:1
10/24/14
SEE TABLE 1 FOR DASH #.
TABLE 1DASH # HOUSING "L1" "L2"
-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]
Level Plus Transmitter®
22
Level Plus® SoClean®
Operation Manual
12.4.3 Installation drawing
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-2
1 2
DR
AWN
BY: M
S
***NO
REVISIO
NS
SHALL B
E MAD
E WITH
OU
T THE N
OTIFIC
ATIO
N TO
APPR
OV
AL AG
EN
CY(S).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 12/2/14
B
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
24 VDC
COM
MO
N- >
Rx/Tx+
Rx /Tx-
GRO
UN
D
EARTH G
ROU
ND
(SEE NO
TE 4)
EARTH G
ROU
ND
(SEE NO
TE 4)
Rx/Tx-
Rx/Tx+
GND
+24V
SAFETY BARRIER
SAFETY BARRIER
SAFETY BARRIER
NO
TES
:1.A
LL NA
TION
AL A
ND
LOC
AL C
OD
ES
AN
D R
EGU
LATIO
NS
MU
ST BE
AD
HE
RE
D TO
WH
EN IN
STALLIN
G TH
E LE
VEL SE
NSO
R IN
HA
ZAR
DO
US
EN
VIRO
NM
EN
TS.
SE
AL A
LL CO
ND
UITS W
ITHIN
457 MM
(18"). 2.LO
OP
CAB
LE M
US
T BE 24 AW
G TO
14 AW
G (.511M
M² to 1.6M
M²)
SH
IELDE
D TW
ISTED
PA
IR C
AB
LE W
ITH S
HIELD
. CA
BLE CA
PAC
ITAN
CE
MU
ST
BE
LES
S THA
N 30 pF P
ER FO
OT (98 pF P
ER
M). C
AB
LE SHIE
LD IS C
ON
NE
CTE
D TO
SYS
TEM
GR
OU
ND
IN N
ON
-HAZA
RD
OU
S A
RE
A. S
EE IN
STA
LLATIO
N M
AN
UA
L FOR
A
DD
ITION
AL C
ABLE
INFO
RM
ATIO
N.
3.THE
RE
SIS
TANC
E B
ETW
EEN
EAR
TH G
RO
UN
D AN
D TH
E IN
TRIN
SICA
LLY S
AFE G
RO
UN
D M
US
T BE LES
S TH
AN
1 OH
M.
4.THE
TRA
NS
DU
CE
R FR
AM
E SH
ALL B
E G
RO
UN
DE
D TO
EAR
TH G
RO
UN
D D
IREC
TLY O
R TH
RO
UG
H TH
E EQ
UIP
ME
NT O
N W
HIC
H IT IS
MO
UN
TED
. 5. C
ON
TRO
L EQ
UIP
MEN
T CO
NN
EC
TED
TO A
SS
OC
IATED
APP
AR
ATU
S M
US
T N
OT U
SE O
R G
EN
ER
ATE M
OR
E TH
AN 250 V
RM
S O
R V
DC
6.AS
SO
CIATE
D A
PPA
RATU
S M
AN
UFAC
TUR
ER
'S IN
STA
LLATIO
N D
RA
WIN
G M
UST
BE
FOLLO
WED
WH
EN
INS
TALLIN
G TH
IS EQ
UIP
ME
NT.
7.ON
LY U
SE C
EC
AP
PR
OV
ED B
AR
RIE
RS
. 8.E
NTITY P
AR
AME
TER
S: S
UPP
LY: R
x/Tx- : Rx/Tx+ :
Ui = 28V
DC
Ui= 8.6V
Ui= 8.6V
Ii = 100mA
Ii = 10mA
Ii = 10mA
C
i = 0 µF Ci = 0 µF C
i = 0 µF Li = 0 µH
Li = 0 µH Li = 0 µH
Pi = 0.7 W
Pi= 0.0215 W
P i= 0.0215 W
9.THE
ENTITY
CO
NC
EPT A
LLOW
S INTE
RC
ON
NE
CTIO
N O
F INTR
INS
ICA
LLY S
AFE
APP
AR
ATU
S W
ITH AS
SO
CIA
TED A
PPA
RA
TUS
WH
EN
THE
FOLLO
WIN
G IS
TRU
E:
V
max or U
i ≥ Voc, V
t or Uo;
Imax or Ii ≥ Isc, It or Io;
Pm
ax or Pi ≥ Po;
Ca ≥ C
i + Ccable;
La ≥ Li + Lcable. 10.D
UAL-C
AVITY
EN
CLO
SU
RE
S: C
US
TOM
ER
CO
NN
EC
TION
S WILL BE
MA
DE AT TE
RM
INA
L BLO
CK
ON
PO
WE
R SID
E O
F HO
US
ING
(NO
T TO TE
RM
INA
L BLO
CK
ON
INTER
CO
NN
EC
T BO
ARD
). 11.FO
R IN
STALLA
TION
WITH
IN C
AN
AD
A SE
E, C
AN
AD
IAN E
LEC
TRIC
AL C
OD
E,
CS
A No. C
22.1. 12.TH
E M
AX
IMU
M PE
RM
ITTED
AM
BIE
NT TE
MP
ER
ATU
RE
OF TH
E LE
VEL P
LUS
DIG
ITAL/A
NA
LOG
LE
VE
L TRAN
SM
ITTER
IS 71 °C
. TO A
VO
ID TH
E E
FFEC
TS O
F PR
OC
ESS
TEM
PE
RA
TUR
E A
ND
O
THE
R TH
ER
MAL EFFE
CTS C
AR
E S
HALL B
E TAK
EN
TO EN
SU
RE
THE
SU
RR
OU
ND
ING
AM
BIEN
T A
ND
THE
AMBIE
NT IN
SID
E TH
E TR
ANS
MITTE
R H
OU
SING
DO
ES
NO
T EX
CE
ED
71°C 13.C
AU
TION
: FLEX
IBLE
GA
UG
ES
HA
VE
A MIN
IMU
M B
EN
D D
IAM
ETER
OF 406M
M(16")
14.WA
RN
ING
: THE
APP
AR
ATU
S EN
CLO
SU
RE
CO
NTA
INS A
LUM
INU
M A
ND
IS CO
NS
IDE
RED
TO C
ON
STITU
TE A
PO
TEN
TIAL R
ISK O
F IGN
ITION
BY IM
PACT O
R FR
ICTIO
N. C
ARE
MU
ST BE
TAKE
N
INTO
AC
CO
UN
T DU
RIN
G IN
STA
LLATIO
N A
ND
US
E TO
PR
EVE
NT IM
PAC
T OR
FRIC
TION
15.WA
RN
ING
: SU
BSTITU
TION
OF C
OM
PO
NE
NTS
MA
Y IM
PA
IR IN
TRIN
SIC
SA
FETY
. 16.W
AR
NIN
G: TO
PRE
VEN
T IGN
ITION
OF FLA
MM
AB
LE O
R C
OM
BU
STIBLE
ATM
OS
PH
ERE
S,
DIS
CO
NN
EC
T PO
WE
R BE
FOR
E S
ERV
ICIN
G
17.WA
RN
ING
: THE
EQU
IPM
EN
T CO
NTA
INS N
ON
-ME
TALLIC E
NC
LOS
UR
E PA
RTS, TO
PR
EV
EN
T TH
E R
ISK
OF E
LEC
TRO
STA
TIC SP
AR
KING
. THE
NO
N-M
ETA
LLIC S
UR
FACE
SH
OU
LD O
NLY
B
E C
LEAN
ED
WITH
A DA
MP
CLO
TH.
NO
N H
AZARDO
US LO
CATION
HAZARD
OU
S LOCATIO
N
AGEN
CY C
ON
TRO
LLED D
RAW
ING
(CAN
ADA). N
O C
HAN
GES W
ITHO
UT PR
IOR
AGEN
CY APPR
OVAL
EARTH TERM
INAL
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTR
INSICALLY SAFE FO
R CAN
ADA
7570
LEVEL
FM
APPROVED
C
N/A
INTRIN
SICALLY SAFECL. I, D
IV. 1, GR. ABCD
Ex ia IIC T4 Ga/G
bTa =
-50 to 71°C ; IP65
Fig. 19: FMC installation drawing
23
Level Plus® SoClean®
Operation Manual
12.4.3 Installation drawing (cont.)
DETAIL A
SCALE 1.60 : 1
DETAIL C
SCALE 3 : 1
DETAIL D
SCALE 1.2
DETAIL E
SCALE 1 : 1
A
C
D
E
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-2
2 2
DR
AWN
BY: M
S
***NO
REVISIO
NS
SHALL B
E MAD
E WITH
OU
T THE N
OTIFIC
ATIO
N TO
APPR
OV
AL AG
EN
CY(S).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 12/2/14
B
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
+24V GNDEARTHTX/RX+TX/RX-
GND+24V
TX/RX-TX/RX+EARTH
GND
+24V
TX/RX-
TX/RX+
EARTH
FIGU
RE 1
SING
LE CAVITY & N
EMA H
OU
SING
FIGU
RE 2
DU
AL CAVITY H
OU
SING
NO
TES: 1. TH
E CU
STOM
ER SH
OU
LD C
ON
NEC
T THE O
UTSID
E GR
OU
ND
LUG
TO TH
E SAFETY EARTH
ING
GR
OU
ND
SYSTEM W
ARN
ING
: C
ON
DU
IT SEALS REQ
UIR
ED W
ITHIN
457 MM
(18") OF H
OU
SING
.
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTRIN
SICALLY SAFE FOR CAN
ADA
+24V GND EARTH Tx/Rx+ Tx/Rx-
7570
Fig. 20: FMC installation drawing
24
Level Plus® SoClean®
Operation Manual
12.5 ATEX and IECEx
12.5.1 Special conditions of safe use
1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. ( When installed in a Ga Approval)2. The maximum permitted ambient temperature of the Level Plus® Digital/Analog Level Transmitter is 71 °C. To avoid the effects of process temperature and other thermal effects care shall be taken to ensure the surrounding ambient and the ambient inside the transmitter housing does not exceed 71°C3. Some models contain non-metallic enclosure parts, to prevent the risk of electrostatic sparking the nonmetallic surface should only be cleaned with a damp cloth.
12.5.2 Labels
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINESCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIEDTOLERANCES
0 PLACESMM
1 PLACEMM
ANGLES
0.5 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FINISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISCLOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE 551629-3 B
1 2
DRAWN BY: NJ
A NJ
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***
WARNING: REFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS
FM14ATEX0068XIECEx FMG 14.0032X II 1/2 G Ex ia IIC T4 Ga/Gb Ta = -50°C to +71°C ; IP65when connected in accordancewith FM approved installation drawing # 651543-3
MTS Systems CorporationSensors Division3001 Sheldon Dr.Cary, NC 27513
Model No: Serial No: Date :
USE MTS LOGO ARTWORK
10 POINT SIZE
8 POINT TEXT SIZE
4.5 POINT TEXT SIZE
MTS TO PRINTMODEL NO.SERIAL NO.
DATE CODE.
ENTITY PARAMETERS:SEE PRINT REFERENCE CHART
LEVEL
1:1
7570 RELEASE TO PRODUCTION
(ACP) LABEL, LP, IS ATEX/IECEx - DIGITAL
10/24/14
1725
Level Plus Transmitter
P/N 551629-3 Rev B
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES.3. MATERIAL: 3M 7883 METALLIZED POLYESTER FOIL W/GAS RESISTANT INK.
R3.30 [.13]
1.78 [.07]
1.78 [.07]
28.70 [1.13]
15.80 [.62]
34.69 [1.37]
86.30 [3.40]
69.85 [2.75]
IP RATING WAS 66 1/19/15NJ7847B
®
Fig. 21: ATEX label
Fig. 22: IECEx label
1
1
2
2
A A
B B
REV ECO # DESCRIPTION
TITLE
SIZE DWG NO. REV
PRODUCT LINE
SCALE:
BY DATE
SHEET OF
UNLESS OTHERWISE SPECIFIED
TOLERANCES0 PLACES
MM1 PLACE
MMANGLES
���� 0.5 � 0.1
- THREAD DEPTHS ARE TO MIN. FULL THDS- DRILL DEPTHS ARE TO FULL DIA.- REMOVE BURRS AND SHARP EDGES- DO NOT SCALE PRINT- MACHINED SURFACE FI NISH 3.2uM [125 uIn]
PROPRIETARY DATATHE INFORMATION AND DESIGN(S) DISCLOSEDHEREIN ARE THE PROPERTY OF MTS SYSTEMSCORPORATION AND MAY NOT BE USED,REPRODUCED OR DISC LOSED IN ANY FORMEXCEPT AS GRANTED IN WRITING BY MTSSYSTEMS CORPORATION. THIS RESTRICTIONEXCLUDES INFORMATION THAT IS IN THE PUBLIC DOMAIN OR WAS LEGITIMATELY IN THEPRIOR POSSESSION OF THE RECIPIENT.
mMTS SYSTEMS CORPORATIONSENSORS DIVISION3001 SHELDON DRIVE, CARY, NC 27513
METRIC
FIRST ANGLE A 551703- B
1 1
DRAWN BY: NJ
A NJ
***NO REVISIONS SHALL BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY(S).***IP RATING WAS 66.7847B NJ 1/19/15
MTS Systems CorporationSensors Division3001 Sheldon Drive, Cary, N.C. 27513
II 1/2 G Ex ia IIC T4 Ga/GbTa = -50°C TO +71°C ; IP65WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETYREFER TO INSTALLATION DRAWING FOR CAUTION/WARNINGS
INSTALL PER DRAWING # 651543-3SUPPLY VOLTAGE: 28 VDC
FM14ATEX0068XIECEx FMG 14.0032X
35.05 [1.38]
"L1"∆ "L2"
17.53 [.69]
7.5 POINT SIZE
USE MTS LOGO ARTWORK14.0 POINT SIZE
MTS TO PRINTMODEL NO.
SERIAL NO./DATE CODE
� 3.05 [.12] X2
4.0 POINT TEXT SIZE(TYP.)
12.70 [.50] 3.70 [.15]
7570 RELEASE FOR PRODUCTION
(ACP) LABEL, LP, IS ATEX/IECEX - DIGITAL
NOTES:1. STANDARD LETTERING UNIVERS 55 OR ITC GARAMOND BOOK.2. MATERIAL TO BE SCREEN PRINTED ALUMINUM WITH SATIN BACKGROUND AND BLACK TEXT OR LASER ETCHED ALUMINUM.3. ∆ INDICATES CRITICAL DIMENSIONS.4. DIMENSIONS IN BRACKETS [ ] ARE IN INCHES5. MATERIAL: .8 [.03] THICK ALUMINUM6. REFER TO TABLE 1 FOR "L1" & "L2" DIMENSIONS.
1725
Level Plus Transmitter
P/N 551703-X Rev B
1:1LEVEL
10/24/14
TABLE 1DASH # HOUSING "L1" "L2"
-1 ADALET 85.85 [3.38] 79.76 [3.14]-2 LIMATHERM 65 [2.56] 58 [2.28]
SEE TABLE 1 FOR DASH #.
®
25
Level Plus® SoClean®
Operation Manual
12.5.3 Installation drawing
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-3
1 2
DR
AWN
BY: M
S
***NO
RE
VISION
S SHALL BE
MA
DE
WITH
OU
T THE
NO
TIFICA
TION
TO A
PPRO
VAL AG
EN
CY(S).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 1/19/15
C
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
24 VDC
COM
MO
N- >
Rx/Tx+
Rx/Tx -
GRO
UN
D
EARTH G
ROU
ND
(SEE NO
TE 4)
EARTH G
ROU
ND
(SEE NO
TE 4)
Rx/Tx-
Rx/Tx+
GND
+24V
SAFETY BARRIER
SAFETY BARRIER
SAFETY BARRIER
NO
TES
:1.A
LL NA
TION
AL A
ND
LOC
AL C
OD
ES
AN
D R
EGU
LATIO
NS
MU
ST BE
AD
HE
RE
D TO
WH
EN IN
STALLIN
G TH
E LE
VEL SE
NSO
R IN
HA
ZAR
DO
US
EN
VIRO
NM
EN
TS.
SE
AL A
LL CO
ND
UITS W
ITHIN
457 MM
(18"). 2.LO
OP
CAB
LE M
US
T BE 24 AW
G TO
14 AW
G (.511M
M² to 1.6M
M²)
SH
IELDE
D TW
ISTED
PA
IR C
AB
LE W
ITH S
HIELD
. CA
BLE CA
PAC
ITAN
CE
MU
ST
BE
LES
S THA
N 30 pF P
ER FO
OT (98 pF P
ER
M). C
AB
LE SHIE
LD IS C
ON
NE
CTE
D TO
SYS
TEM
GR
OU
ND
IN N
ON
-HAZA
RD
OU
S A
RE
A. S
EE IN
STA
LLATIO
N M
AN
UA
L FOR
A
DD
ITION
AL C
ABLE
INFO
RM
ATIO
N.
3.THE
RE
SIS
TANC
E B
ETW
EEN
EAR
TH G
RO
UN
D AN
D TH
E IN
TRIN
SICA
LLY S
AFE G
RO
UN
D M
US
T BE LES
S TH
AN
1 OH
M.
4.THE
TRA
NS
DU
CE
R FR
AM
E SH
ALL B
E G
RO
UN
DE
D TO
EAR
TH G
RO
UN
D D
IREC
TLY O
R TH
RO
UG
H TH
E EQ
UIP
ME
NT O
N W
HIC
H IT IS
MO
UN
TED
. 5. C
ON
TRO
L EQ
UIP
MEN
T CO
NN
EC
TED
TO A
SS
OC
IATED
APP
AR
ATU
S M
US
T N
OT U
SE O
R G
EN
ER
ATE M
OR
E TH
AN 250 V
RM
S O
R V
DC
6.AS
SO
CIATE
D A
PPA
RATU
S M
AN
UFAC
TUR
ER
'S IN
STA
LLATIO
N D
RA
WIN
G M
UST
BE
FOLLO
WED
WH
EN
INS
TALLIN
G TH
IS EQ
UIP
ME
NT.
7.ON
LY U
SE A
TEX
/IEC
AP
PR
OVE
D B
ARR
IERS
. 8.E
NTITY P
AR
AME
TER
S: S
UPP
LY: R
x/Tx-: Rx/Tx+:
Ui = 28V
DC
Ui= 8.6V
Ui= 8.6V
Ii = 100mA
Ii = 10mA
Ii = 10mA
C
i = 0 µF Ci = 0 µF C
i = 0 µF Li = 0 µH
Li = 0 µH Li = 0 µH
Pi = 0.7 W
Pi= 0.0215 W
P i= 0.0215 W
9.THE
ENTITY
CO
NC
EPT A
LLOW
S INTE
RC
ON
NE
CTIO
N O
F INTR
INS
ICA
LLY S
AFE
APP
AR
ATU
S W
ITH AS
SO
CIA
TED A
PPA
RA
TUS
WH
EN
THE
FOLLO
WIN
G IS
TRU
E:
V
max or U
i ≥ Voc, V
t or Uo;
Imax or Ii ≥ Isc, It or Io;
Pm
ax or Pi ≥ Po;
Ca ≥ C
i + Ccable;
La ≥ Li + Lcable. 10.D
UAL-C
AVITY
EN
CLO
SU
RE
S: C
US
TOM
ER
CO
NN
EC
TION
S WILL BE
MA
DE AT TE
RM
INA
L BLO
CK
ON
PO
WE
R SID
E O
F HO
US
ING
(NO
T TO TE
RM
INA
L BLO
CK
ON
INTER
CO
NN
EC
T BO
ARD
). 11.FO
R INSTALLATIO
N W
ITHIN
THE EU
ROPEAN
UN
ION
, SEE EN 60079-14.
12.THE
MA
XIM
UM
PER
MITTE
D A
MB
IEN
T TEM
PE
RA
TUR
E O
F THE
LEVE
L PLU
S D
IGITA
L/AN
ALO
G
LEV
EL TR
ANS
MITTE
R IS
71 °C. TO
AV
OID
THE
EFFE
CTS
OF P
RO
CES
S TE
MP
ER
ATU
RE
AN
D
OTH
ER
THE
RM
AL EFFEC
TS CA
RE
SH
ALL BE TA
KE
N TO
ENS
UR
E TH
E S
UR
RO
UN
DIN
G A
MB
IENT
AN
D TH
E AM
BIEN
T INS
IDE
THE
TRAN
SM
ITTER
HO
USIN
G D
OE
S N
OT E
XC
EE
D 71°C
13.CA
UTIO
N: FLE
XIB
LE G
AU
GE
S H
AV
E A M
INIM
UM
BE
ND
DIA
METE
R O
F 406MM
(16") 14.W
AR
NIN
G: TH
E AP
PA
RA
TUS E
NC
LOS
UR
E C
ON
TAIN
S ALU
MIN
UM
AN
D IS C
ON
SID
ER
ED TO
CO
NS
TITUTE
A P
OTE
NTIA
L RIS
K OF IG
NITIO
N B
Y IMP
ACT O
R FR
ICTIO
N. C
ARE
MU
ST BE
TAKE
N
INTO
AC
CO
UN
T DU
RIN
G IN
STA
LLATIO
N A
ND
US
E TO
PR
EVE
NT IM
PAC
T OR
FRIC
TION
15.WA
RN
ING
: SU
BSTITU
TION
OF C
OM
PO
NE
NTS
MA
Y IM
PA
IR IN
TRIN
SIC
SA
FETY
. 16.W
AR
NIN
G: TO
PRE
VEN
T IGN
ITION
OF FLA
MM
AB
LE O
R C
OM
BU
STIBLE
ATM
OS
PH
ERE
S,
DIS
CO
NN
EC
T PO
WE
R BE
FOR
E S
ERV
ICIN
G
17.WA
RN
ING
: THE
EQU
IPM
EN
T CO
NTA
INS N
ON
-ME
TALLIC E
NC
LOS
UR
E PA
RTS, TO
PR
EV
EN
T TH
E R
ISK
OF E
LEC
TRO
STA
TIC SP
AR
KING
. THE
NO
N-M
ETALLIC
SU
RFAC
E S
HO
ULD
ON
LY
BE
CLEA
NE
D W
ITH A D
AM
P C
LOTH
.
NO
N H
AZARDO
US LO
CATION
HAZARD
OU
S LOCATIO
N
INTR
INS
ICA
LLY S
AFEFM
14ATE
X0068XIE
CE
x FMG
14.0032X
AGEN
CY C
ON
TRO
LLED D
RAW
ING
(ATEX/IEC). N
O C
HAN
GES W
ITHO
UT PR
IOR
AGEN
CY APPR
OVAL
EARTH TERM
INAL
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTR
INSICALLY SAFE FO
R ATEX/IEC
7570
LEVEL
N/A
1725
II 1/2 G Ex ia T4 G
a/Gb
Ta = -50 TO
71°C; IP65
Fig. 23: ATEX / IECEx installation drawing
26
Level Plus® SoClean®
Operation Manual
12.5.3 Installation drawing (cont.)
DETAIL A
SCALE 1.60 : 1
DETAIL C
SCALE 3 : 1
DETAIL D
SCALE 1.2
DETAIL E
SCALE 1 : 1
A
C
D
E
11
22
33
44
55
66
77
88
AA
BB
CC
DD
REV
EC
O #
DESC
RIP
TION
TITLE
SIZED
WG
NO
.R
EV
PRO
DU
CT LIN
ESC
ALE:
BYD
ATE
SHEET
OF
UN
LES
S OTH
ER
WISE
SPEC
IFIED
TOLER
ANC
ES0 P
LACE
SM
M1 PLA
CE
MM
AN
GLE
S
0.5
0.1
- THR
EA
D D
EP
THS
AR
E TO
MIN
. FULL TH
DS
- DR
ILL DE
PTH
S A
RE
TO FU
LL DIA
.- R
EM
OV
E B
UR
RS
AN
D S
HA
RP
ED
GE
S- D
O N
OT S
CA
LE P
RIN
T- M
AC
HIN
ED
SU
RFA
CE
FINIS
H 3.2uM
[125 uIn]
PRO
PRIETA
RY D
ATA
THE
INFO
RM
ATIO
N A
ND
DE
SIG
N(S
) DIS
CLO
SE
DH
ER
EIN
AR
E TH
E P
RO
PE
RTY
OF M
TS S
YS
TEM
SC
OR
PO
RA
TION
AN
D M
AY
NO
T BE
US
ED
,R
EP
RO
DU
CE
D O
R D
ISC
LOS
ED
IN A
NY
FOR
ME
XC
EP
T AS
GR
AN
TED
IN W
RITIN
G B
Y M
TSS
YS
TEM
S C
OR
PO
RA
TION
. THIS
RE
STR
ICTIO
NE
XC
LUD
ES
INFO
RM
ATIO
N TH
AT IS
IN TH
E
PU
BLIC
DO
MA
IN O
R W
AS
LEG
ITIMA
TELY
IN TH
EP
RIO
R P
OS
SE
SS
ION
OF TH
E R
EC
IPIE
NT.
mM
TS SYS
TEMS
CO
RP
OR
ATIO
NS
ENSO
RS D
IVISIO
N3001 SH
ELDO
N D
RIVE
, CA
RY, N
C 27513
METRIC
FIRST
ANG
LED
651543-3
2 2
DR
AWN
BY: M
S
***NO
RE
VISION
S SHALL BE
MA
DE
WITH
OU
T THE
NO
TIFICA
TION
TO A
PPRO
VAL AG
EN
CY(S).***
AM
S10/24/14
RELEASE TO PRO
DU
CTION
B 7847 UPD
ATED IP RATIN
G FO
R HO
USIN
G TYPES M
S 1/19/15
C
C 7898 UPD
ATED TEM
PERATURE O
N N
OTE 12 TO
71C MS 2/23/15
+24V GNDEARTHTX/RX+TX/RX-
GND+24V
TX/RX-TX/RX+EARTH
GND
+24V
TX/RX-
TX/RX+
EARTH
FIGU
RE 1
SING
LE CAVITY & N
EMA H
OU
SING
FIGU
RE 2
DU
AL CAVITY H
OU
SING
NO
TES: 1. TH
E CU
STOM
ER SH
OU
LD C
ON
NEC
T THE O
UTSID
E GR
OU
ND
LUG
TO TH
E SAFETY EARTH
ING
GR
OU
ND
SYSTEM W
ARN
ING
: C
ON
DU
IT SEALS REQ
UIR
ED W
ITHIN
457 MM
(18") OF H
OU
SING
.
(ACP) INSTALLATIN
DW
G LP D
IGITAL
INTRIN
SICALLY SAFE FOR ATEX/IEC
+24V GND EARTH Tx/Rx+ Tx/Rx-
7570
Fig. 24: ATEX / IECEx installation drawing
27
Level Plus® SoClean®
Operation Manual
12.5.3 EC Declaration of Conformity
EC Declaration of Conformity
EG-Konformitätserklärung
Déclaration CE de Conformité
MTS Systems Corporation, Sensors Division, 3001 Sheldon Drive, Cary NC 27513, USA declares as manufacturer in sole responsibility that the products erklärt als Hersteller in alleiniger Verantwortung, dass die Produkte déclare en qualité de fabricant sous sa seule responsabilité que les produits
Level Plus LPT x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (Tank Slayer)
Level Plus LPR x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (RefineME)
Level Plus LPS x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (SoClean)
Level Plus LPC x_x_x_x_x_x_x_x_x_E_x_x_x_x_x_x_x_x_x (Chambered)
comply with the regulations of the following European Directives: den Vorschriften folgender europäischer Richtlinien entsprechen: sont conformes aux prescriptions des directives européennes suivantes :
94/9/EC Equipment and protective systems for use in potentially explosive atmospheres
Geräte und Schutzsysteme zur Verwendung in explosionsgefährdeten Bereichen Appareils et systèmes de protection à être utilisés en atmosphères explosibles
2004/108/EC Electromagnetic Compatibility
Elektromagnetische Verträglichkeit Compatibilité électromagnétique
Applied harmonized standards: Angewandte harmonisierte Normen: Normes harmonisées appliquées :
EN 60079-0:2012, EN 60079-11:2012, EN 60529:1991+A1:2000, EN 61326-1:2013, EN 61326-2-3:2013
EC type examination certificate: EG-Baumusterprüfbescheinigung: FM 14 ATEX 0068 X, 1st Supplement Certificat de l’examen CE de type : issued by / ausgestellt durch / exposé par: FM Approvals Ltd. Windsor, Berkshire, United Kingdom
Notified body for quality assurance control: FM Approvals Ltd. Benannte Stelle für Qualitätsüberwachung: Windsor, Berkshire, United Kingdom Organisme notifié pour l’assurance qualité : Ident number / Kennnummer / Numéro d’identification : 1725
Marking / Kennzeichnung / Marquage : II 1/2 G Ex ia IIC/ T4
Ta = -50°C to +71°C
Lüdenscheid, 2015-07-07
MTS Sensor Technologie GmbH & Co. KG, Auf dem Schüffel 9, 58513 Lüdenscheid, Germany
__________________________________
Thomas Muckenhaupt Quality Management ATEX Representative
EC14.012B
28
Document Part Number: 551693 Revision A (EN) 09/2015
Reg.-No. 003095-QN
MTS, Temposonics and Level Plus are registered trademarks of MTS Systems Corporation in the United States; MTS SENSORS and the MTS SENSORS logo are trademarks of MTS Systems Corporation within the United States. These trademarks may be protected in other countries. All other trademarks are the property of their respective owners. Copyright © 2015 MTS Systems Corporation. No license of any intellectual property rights is granted. MTS reserves the right to change the information within this document, change product designs, or withdraw products from availability for purchase without notice. Typographic and graphics errors or omissions are unintentional and subject to correction. Visit www.mtssensors.com for the latest product information. Product change notification alerts are available through the MTS Product Change Management System; register at www.mtssensors.com/PCMS.
LOCA
TION
S
LEGA
L NO
TICE
SUSA MTS Systems CorporationSensors Division3001 Sheldon DriveCary, N.C. 27513, USATel. +1 919 677-0100Fax +1 919 [email protected]
JAPANMTS Sensors Technology Corp.737 Aihara-machi, Machida-shi, Tokyo 194-0211, JapanTel. + 81 42 775-3838Fax + 81 42 775- [email protected]
FRANCEMTS Systems SASZone EUROPARC Bâtiment EXA 1616/18, rue Eugène Dupuis94046 Creteil, FranceTel. + 33 1 58 4390-28Fax + 33 1 58 [email protected]
GERMANYMTS Sensor TechnologieGmbH & Co. KGAuf dem Schüffel 958513 Lüdenscheid, GermanyTel. + 49 2351 9587-0Fax + 49 2351 [email protected]
CHINAMTS Sensors Room 504, Huajing Commercial Center, No. 188, North Qinzhou Road200233 Shanghai, ChinaTel. +86 21 6485 5800 Fax +86 21 6495 [email protected]
ITALYMTS Systems Srl.Sensor DivisionVia Diaz,425050 Provaglio d‘Iseo (BS), ItalyTel. + 39 030 988 3819Fax + 39 030 982 [email protected]