iCOM Where to Save Manual Rev. 07-06
Disclaimer of Warranties and Limitations ofLiabilities
The authors and editors have taken every precaution to ensure accuracy andcompleteness in this manual. The authors and editors make no expressed or impliedwarranty of any kind with regard to the documentation in this manual. LiebertCorporation assumes no responsibility, and disclaims all liability for incidental orconsequential damages resulting from the use of this information or from errors oromissions. Liebert Corporation may make improvements and/or changes in theproduct(s) described in this manual at any time. Information in this manual is subjectto change at any time and does not represent a commitment on the part of LiebertCorporation.
Liebert® and the Liebert logo are registered trademarks of Liebert Corporation.Emerson® and the Emerson logo are registered trademarks of Emerson Electric Co.
Copyright © 2006 by Liebert Corporation
All rights reserved throughout the world.Specifications subject to change without notice.
Printed in the United States of America
2
8/20/2019 Manual 07-06 Networking-where to Save
3/47
iCOM Where to Save Manual Rev. 07-06
Table of Contents
Where and When to Save 3
Level 1 – User Menu Parameters 3
Level 2 – Service Menu Parameters 7
Level 3 – Advanced Menu Parameters 21
Networking 25
Basic (U2U) networking with Small Screens 28
Multi-Unit IP Address Setup Chart Sample 29
Use as your Guide 30
Teamwork Operation Guide 31
Basic Unit Cable Connections 33
Sample Configurations List 36
Preparing for Networking 36
Blank Multi-unit IP Address Setup Chart 37
Setpoints Blank Read and Record Forms 38
Standby Setting/Lead-Lag Blank Read and Record Form 39
System/Network Setup Blank Read and Record Forms 40
Unit Code Blank Read and Record Form 42
Site Survey for Networking Request Form 43
3
8/20/2019 Manual 07-06 Networking-where to Save
4/47
iCOM Where to Save Manual Rev. 07-06
Where and When to Save
This section of the manual provides a quick reference of when and where to savechanges to the various iCOM programming parameters:
Control BoardConfiguration Safe = CSFNetwork Safe = NSFUnit Code = UCO
Large DisplayConfiguration Safe = CSFNetwork Safe = NSF
The column indicated by TW1 is a list of parameters that may or may not be shared
when Teamwork Mode 1 is selected for control operation.
Level 1 - User Menus
MenuLine Setpoint Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
U102 Temperature Setpoint YES CSF -
U103 Humidity Setpoint YES CSF -
U104 Humidity Control Type YES CSF -
U105 Supply Limit YES CSF -
U106 Supply Limit Temp Value YES CSF -
MenuLine Graphics Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
- System Temperature Time Scale NO CSF -
- System Temperature Graph Height NO - CSF
- System Humidity Time Scale NO CSF -
- System Humidity Graph Height NO - CSF
- Unit Temperature Time Scale NO CSF -
- Unit Temperature Graph Height NO - CSF
- Unit Humidity Time Scale NO CSF -
- Unit Humidity Graph Height NO - CSF
4
8/20/2019 Manual 07-06 Networking-where to Save
5/47
iCOM Where to Save Manual Rev. 07-06
MenuLine Set Alarm Parameters
sharedin TW1
ControlBoard Safe
DisplaySafe
U202 Return Sensor Alarms YES CSF -
U203 High Return Temperature YES CSF -U204 Low Return Temperature YES CSF -
U205 High Return Humidity YES CSF -
U206 Low Return Humidity YES CSF -
U207 Sensor A Alarms YES CSF -
U208 High Temperature Sensor A YES CSF -
U209 Low Temperature Sensor A YES CSF -
U210 High Humidity Sensor A YES CSF -
U211 Low Humidity Sensor A YES CSF -
MenuLine
Various Sensors Parameters,page 1 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
U301 Actual Temperature Setpoint YES - -
U302 Actual Humidity Setpoint YES - -
U303 Optional Sensor A Temperature NO - -
U304 Optional Sensor A Humidity NO - -
U305 Optional Sensor B Temperature NO - -
U306 Optional Sensor B Humidity NO - -
U307 Optional Sensor C Temperature NO - -
U308 Optional Sensor C Humidity NO - -
U309 Freecooling Fluid Temperature NO - -
U310 DigiScroll 1 Temperature NO - -
U311 DigiScroll 2 Temperature NO - -
U312 Freecooling Status NO - -
5
8/20/2019 Manual 07-06 Networking-where to Save
6/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Various Sensors Parameters,page 2 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
U313 Daily High Temperature and Time NO - -
U314 Daily Low Temperature and Time NO - -
U315 Daily High Humidity and Time NO - -U316 Daily Low Humidity and Time NO - -
MenuLine Display Setup Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
U401 Language NO - CSF
U402 Date (Month/Day/Year) YES - -
U403 Time (Hours:Minutes:Seconds) YES - -
U404 Temperature Indication NO CSF CSFU405 Display Contrast NO - CSF
U406 Buzzer Frequency NO - CSF
U407 Backlite Off After x Hours NO - CSF
U408 Screen NO - CSF
U409 Display Shows NO - CSF
U410 Display Colors NO - CSF
U411 Display Date NO CSF
6
8/20/2019 Manual 07-06 Networking-where to Save
7/47
iCOM Where to Save Manual Rev. 07-06
MenuLine Total Run Hours Parameter
Sharedin TW1
ControlBoard Safe
DisplaySafe
U502 Fan Motor(s) Limit NO CSF -
U503 Compressor 1 Limit NO CSF -
U504 Compressor 2 Limit NO CSF -U505 Chilled Water/Free Cool Limit NO CSF -
U506 HotGas / HotWater Limit NO CSF -
U507 Electrical Heater 1 Limit NO CSF -
U508 Electrical Heater 2 Limit NO CSF -
U509 Electrical Heater 3 Limit NO CSF -
U510 Humidifier Limit NO CSF -
U511 Dehumidification Limit NO CSF -
MenuLine Sleep Mode Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
U602 Sleep On - - -
U603 Mon, Tue, Wed, Thu, Fri, Sat, Sun YES CSF -
U604 Sleep Every Day (1) YES CSF -
U605 From / To YES CSF -
U606 Sleep Every Day (2) YES CSF -U607 From / To YES CSF -
U609 Timer mode YES CSF -
U610 Timer Mode Type YES CSF -
U611 Deadband YES CSF -
MenuLine Service contacts
Sharedin TW1
ControlBoard Safe
DisplaySafe
U703 Address Line 1 N/A CSF -U704 Address Line 2 N/A CSF -
U705 Address Line 3 N/A CSF -
U706 Address Line 4 N/A CSF -
7
8/20/2019 Manual 07-06 Networking-where to Save
8/47
iCOM Where to Save Manual Rev. 07-06
Level 2 – Service Menus
MenuLine Setpoint Parameters, page 1 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S102 Temperature Setpoint YES CSF -
S103 Humidity Setpoint YES CSF -
S104 Humidity Control Type YES CSF -
S105 Supply Limit YES CSF -
S106 Supply Limit Temp Value YES - -
S107 AutoSet Enable YES CSF -
S108 Temperature Proportional Band YES CSF -
S109 Temperature Integration Time YES CSF -
S110 Temperature DeadBand YES CSF -
S111 Short Cycle Control YES CSF
MenuLine Setpoint Parameters, page 2 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S113 Humidity Proportional Band YES CSF -
S114 Humidity Integration Time YES CSF -
S115 Humidity Deadband YES CSF -
S116 ∆ T Between Room / FC Type NO CSF -S117 ∆ T Between Room Air / FC Fluid NO CSF -
S118 Minimum CW Temp NO CSF -
S119 Minimum CW Temp Value NO CSF -
8
8/20/2019 Manual 07-06 Networking-where to Save
9/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Standby Setting / Lead-lagParameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
S502 Number of Standby Units YES CSF -
S503 Rotation Frequency YES CSF -
S504 Rotate at (hour) YES CSF -S505 Rotate at (minute) YES CSF -
S506 Rotate by YES CSF -
S507 Perform one Rotation YES - -
S508 Cascade Units YES CSF -
S509 Start all Standby Units by HT YES CSF
MenuLine
Maintenance / WellnessParameters, page 1 0f 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S002 Maintenance Frequency Per Year YES CSF -
S003 Max Bonus YES CSF -
S004 Max Penalty YES CSF -
S005 Last Maintenance YES CSF -
S006 Service Engineer YES CSF -
S007 Confirm PM YES - -
S008 Calculated Next Maintenance YES - -
MenuLine
Motor Settings Parameters, page 2of 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S013 Number of Starts NO - -
S014 Run Hours NO - -
S015 Average Run Time NO - -
S016 Starts per Day Best NO CSF -
S017 Starts per Day Worst NO CSF -S018 Number of Alarms NO - -
S019 Actual Bonus NO - -
9
8/20/2019 Manual 07-06 Networking-where to Save
10/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Compressor 1 SettingsParameters, page 3 of 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S024 Number of Starts NO - -
S025 Run Hours NO - -
S026 Average Run Time NO - -S027 Starts per Day Best NO CSF -
S028 Starts per Day Worst NO CSF -
S029 Number of HP Alarms NO - -
S030 Number of LP Alarms NO - -
S031 Number of OL Alarms NO - -
S032 Number of DS HT Alarms NO - -
S033 Actual Bonus NO - -
MenuLine
Compressor 2 SettingsParameters, page 4 of 8
sharedin TW1
ControlBoard Safe
DisplaySafe
S035 Number of Starts NO - -
S036 Run Hours NO - -
S037 Average Run Time NO - -
S038 Starts per Day Best NO CSF -
S039 Starts per Day Worst NO CSF -
S040 Number of HP Alarms NO - -
S041 Number of LP Alarms NO - -
S042 Number of OL Alarms NO - -
S043 Number of DS HT Alarms NO - -
S044 Actual Bonus NO - -
10
8/20/2019 Manual 07-06 Networking-where to Save
11/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
EL Heater 1 Settings Parameters,page 5 of 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S046 Number of Starts NO - -
S047 Run Hours NO - -
S048 Average Run Time NO - -S049 Starts per Day Best NO CSF -
S050 Starts per Day Worst NO CSF -
S051 Number of Alarms NO - -
S052 Actual Bonus NO - -
MenuLine
EL Heater 2 Settings Parameters,page 6 of 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S057 Number of Starts NO - -S058 Run Hours NO - -
S059 Average Run Time NO - -
S060 Starts per Day Best NO CSF -
S061 Starts per Day Worst NO CSF -
S062 Number of Alarms NO - -
S063 Actual Bonus NO - -
MenuLine EL Heater 3 Settings Parameters,page 7 of 8 Sharedin TW1 ControlBoard Safe DisplaySafeS068 Number of Starts NO - -
S069 Run Hours NO - -
S070 Average Run Time NO - -
S071 Starts per Day Best NO CSF -
S072 Starts per Day Worst NO CSF -
S073 Number of Alarms NO - -
S074 Actual Bonus NO - -
11
8/20/2019 Manual 07-06 Networking-where to Save
12/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Humidifier Settings Parameters,page 8 of 8
Sharedin TW1
ControlBoard Safe
DisplaySafe
S079 Number of Starts NO - -
S080 Run Hours NO - -
S081 Average Run Time NO - -S082 Starts per Day Best NO CSF -
S083 Starts per Day Worst NO CSF -
S084 Number of Alarms NO - -
S085 Actual Bonus NO - -
MenuLine
Diagnosti cs / Service ModeParameters, page 1 of 5
Sharedin TW1
ControlBoard Safe
DisplaySafe
S302 Manual Mode NO - -S303 Motor(s) NO - -
S304 Compressor 1 NO - -
S305 Compressor 1 Capacity NO - -
S306 Compressor 1 Cycle Ramp NO - -
S307 Compressor 1 LLSV NO - -
S308 Compressor 2 NO - -
S309 Compressor 2 Capacity NO - -S310 Compressor 2 Cycle Ramp NO - -
S307 Compressor 2 LLSV NO - -
MenuLine
Diagnosti cs / Service ModeParameters, page 2 of 5
Sharedin TW1
ControlBoard Safe
DisplaySafe
S313 HP 1 Alarm Counter NO - -
S314 HP 2 Alarm Counter NO - -
S315 HT 1 Alarm Counter NO - -
S316 HT 2 Alarm Counter NO
S320 Electric Heat 1 (or HG/HW) - - -
S321 Electric Heat 2 (or E.Heat 1) - - -
S322 Electric Heat 3 (or E.Heat 2) - - -
12
8/20/2019 Manual 07-06 Networking-where to Save
13/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Diagnosti cs / Service ModeParameters, page 3 of 5
Sharedin TW1
ControlBoard Safe
DisplaySafe
S324 Humidifier Fill NO - -
S325 Humidifier NO - -
S326 Alarm Relay NO - -S327 FC Relay NO - -
S328 3P Actuator open NO - -
S329 3P Actuator close NO - -
S330 Analog Out 1 NO - -
S331 Analog Out 2 NO - -
S332 Analog Out 3 NO - -
S333 Analog Out 4 NO - -
MenuLine
Diagnosti cs / Service ModeParameters, page 4 of 5
Sharedin TW1
ControlBoard Safe
DisplaySafe
S335 Status Remote Shutdown NO - -
S336 Status Airflow Loss NO - -
S337 Status Motor Overload NO - -
S338 Status Filter NO - -
S339 Status Customer Input 1 NO - -
S340 Status Customer Input 2 NO - -
S341 Status Customer Input 3 NO - -
S342 Status Customer Input 4 NO - -
13
8/20/2019 Manual 07-06 Networking-where to Save
14/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Diagnosti cs / Service ModeParameters, page 5 of 5
Sharedin TW1
ControlBoard Safe
DisplaySafe
S346 Status HP1 NO - -
S347 Status LP1 NO - -
S348 Status C1 OL NO - -S349 Status HP2 NO - -
S350 Status LP2 NO - -
S351 Status C2 OL NO - -
S352 Status Humidifier Problem NO - -
S353 Status DT2 NO - -
S354 Status Min CW NO - -
MenuLine Set Alarm Parameters, page 1 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S202 Return Sensor Alarms YES CSF -
S203 High Return Temperature YES CSF -
S204 Low Return Temperature YES CSF -
S205 High Return Humidity YES CSF -
S206 Low Return Humidity YES CSF -
S207 Sensor A Alarms YES CSF -S208 High Temperature Sensor A YES CSF -
S209 Low Temperature Sensor A YES CSF -
S210 High Humidity Sensor A YES CSF -
S211 Low Humidity Sensor A YES CSF -
14
8/20/2019 Manual 07-06 Networking-where to Save
15/47
iCOM Where to Save Manual Rev. 07-06
MenuLine Set Alarm Parameters, page 2 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S213 Customer Input 1 NO CSF -
S214 Customer Input 1 active when NO CSF -
S215 Customer Input 2 NO CSF -S216 Customer Input 2 active when NO CSF -
S217 Customer Input 3 NO CSF -
S218 Customer Input 3 active when NO CSF -
S219 Customer Input 4 NO CSF -
S220 Customer Input 4 active when NO CSF -
S221 Warning Activates Alarm Relay NO CSF -
S222 Reset Disabled Alarms - - -
MenuLine Set Alarm Parameters, page 3 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S225 Main Fan Overload: Any Change NO CSF -
S226 Loss Of Airflow: Any Change NO CSF -
S227 Clogged Filters: Any Change NO CSF -
S228 High Room Temp: Any Change NO CSF -
S229 Low Room Temp: Any Change NO CSF -
S230 High Room Humid: Any Change NO CSF -
S231 Low Room Humid: Any Change NO CSF -
S232 High Temp Sensor A: Any Change NO CSF -
S233 Low Temp Sensor A: Any Change NO CSF -
S234 High Humid Sensor A: Any Change NO CSF -
S235 Low Humid Sensor A: Any Change NO CSF -
15
8/20/2019 Manual 07-06 Networking-where to Save
16/47
iCOM Where to Save Manual Rev. 07-06
MenuLine Set Alarm Parameters, page 4 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S238 Comp 1 Overload: Any Change NO CSF -
S239 Comp 2 Overload: Any Change NO CSF -S240 Comp 1 High Press: Any Change NO - -
S241 Comp 2 High Press: Any Change NO - -
S242 Comp 1 Low Press: Any Change NO - -
S243 Comp 2 Low Press: Any Change NO - -
S244 Comp 1 Pumpdown Fail: AnyChange NO - -
S245 Comp 2 Pumpdown Fail: AnyChange NO - -
S246 Did Scroll 1 High Temp: Any Change NO - -
S247 Did Scroll 2 High Temp: Any Change NO - -
MenuLine Set Alarm Parameters, page 5 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S251 Working Hours Exceeded: AnyChange NO CSF -
S252 Smoke Detected: Any Change NO CSF -
S253 Water Under Floor: Any Change NO CSF -
S254 Cond Pump High Water: AnyChange NO CSF -
S255 Loss Of Flow: Any Change NO CSF -
S256 Stby Glycol Pump On: Any Change NO CSF -
S257 Standby Unit On: Any Change NO CSF -
S258 Humidifier Problem: Any Change NO CSF -
S259 No Connection w/ Unit: Any Change NO - -
S260 Unit X Disconnected: Any Change NO - -
16
8/20/2019 Manual 07-06 Networking-where to Save
17/47
iCOM Where to Save Manual Rev. 07-06
MenuLine Set Alarm Parameters, page 6 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
S264 CUSTOMER INPUT 1 NO CSF -
S265 CUSTOMER INPUT 2 NO CSF -
S266 CUSTOMER INPUT 3 NO CSF -S267 CUSTOMER INPUT 4 NO CSF -
S268 CALL SERVICE NO CSF -
S269 HIGH TEMPERATURE NO CSF -
S270 LOSS OF AIR BLOWER 1 NO CSF -
S271 REHEAT LOCKOUT NO CSF -[
S272 HUMIDIFIER LOCKOUT NO CSF -
S273 HUM+REHEAT LOCKOUT NO CSF -S274 COMPRESSOR(S) LOCKOUT NO CSF -
MenuLine
Sensor Calibration/ SetupParameters, page 1 of 3
Sharedin TW1
ControlBoard Safe
DisplaySafe
S602 Return Temperature NO CSF -
S603 Calibrated Return Temperature NO - -
S604 Return Humidity NO CSF -
S605 Calibrated Return Humidity NO - -S606 Digiscroll 1 NTC NO CSF -
S607 Calibrated Digiscroll 1 NTC NO - -
S608 Digiscroll 2 NTC NO CSF -
S609 Calibrated Digiscroll 2 NTC NO - -
17
8/20/2019 Manual 07-06 Networking-where to Save
18/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Sensor Calibration/ SetupParameters, page 2 of 3
Sharedin TW1
ControlBoard Safe
DisplaySafe
S613 Temperature Sensor A NO CSF -
S614 Calibrated Temp. Sensor A NO - -
S615 Humidity Sensor A NO CSF -S616 Calibrated Humidity Sensor A NO - -
S617 Temperature Sensor B NO CSF l -
S618 Calibrated Temp. Sensor B NO - -
S619 Humidity Sensor B NO CSF -
S620 Calibrated Humidity Sensor B NO - -
Menu
Line
Sensor Calibration/ Setup
Parameters, page 3 of 3
Shared
in TW1
Control
Board Safe
Display
SafeS624 Freecool Sensor PTC or NTC NO CSF -
S625 Freecool Sensor NO CSF -
S626 Calibrated Freecool Sensor NO - -
S627 Supply Sensor PTC or NTC NO CSF -
S628 Supply Sensor NO CSF -
S629 Calibrated Supply Sensor NO - -
S630 Temperature Sensor C NO CSF -
S631 Calibrated Temp. Sensor C NO - -
S632 Humidity Sensor C NO CSF -
S633 Calibrated Humidity Sensor C NO - -
18
8/20/2019 Manual 07-06 Networking-where to Save
19/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
System Network Setup (Display)Parameters, page 1 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S802 Number of Connected Units NO CSF -
S803 Teamwork Mode NO CSF -
S805 U2U Group NO - NSFS809 Configuration Safe Status NO - -
S809 Configuration Safe Control NO
S810 Network Safe Status NO - -
S810 Network Safe Control NO
S811 SW Version - -
Menu
Line
System Network Setup (Display)
Parameters, page 2 of 2
Shared
in TW1
Control
Board Safe
Display
SafeS813 IP Address NO - NSF
S814 Netmask NO - NSF
S815 Gateway NO - NSF
S816 MAC NO - NSF
S817 U2U Protocol NO - NSF
S818 U2U Adress NO - NSF
S821 Bootloader Variables Status NO - -
S821 Bootloader Variables Control NO - -
MenuLine
System Network Setup (Contro lBoard) Parameters, page 1 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S824 Monitoring Address NO NSF -
S826 U2U Group NO NSF
S827 Unit Name NO NSF
S831 Configuration Safe Status NO - -
S831 Configuration Safe Control NO
S832 Network Safe Status NO - -
S832 Network Safe Control NO
S833 SW Version - -
19
8/20/2019 Manual 07-06 Networking-where to Save
20/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
System Network Setup (Contro lBoard) Parameters, page 2 of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S835 Monitoring Protocol NSF -
S836 IP Address NO NSF -
S837 Netmask NO NSF -S838 Gateway NO NSF -
S839 MAC NO NSF -
S840 U2U Protocol NO NSF -
S841 U2U Adress NO NSF -
S843 Bootloader Variables Status NO - -
S843 Bootloader Variables Control NO - -
S844 Static RAM Status NOS844 Static RAM Control NO
MenuLine
Options Setup Parameters, page 1of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S402 Compressor Sequence NO CSF -
S403 Low Pressure Alarm Delay NO CSF -
S404 Actual LP1 Pressure NO - -
S405 Actual LP2 Pressure NO - -S406 Electric Stages NO CSF -
S407 Hot Water Heat On/Off NO CSF -
S408 Hot Gas Heat NO CSF -
S409 Total Heat Stages NO - -
S410 3P Actuator Runtime NO CSF -
S411 3P Actuator Direction NO CSF -
20
8/20/2019 Manual 07-06 Networking-where to Save
21/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Options Setup Parameters, page 2of 2
Sharedin TW1
ControlBoard Safe
DisplaySafe
S412 Password - - -
S413 Humidification enabled NO CSF -
S414 Infrared Flush Rate NO CSF -S415 Dehum enabled NO CSF -
S416 Electric reheat operation NO CSF -
S417 Single unit auto restart NO CSF -
S418 On-Off enabled NO - CSF
S419
S420 CW Flush NO CSF -
S421 Freecooling Flush NO CSF -S422 Hot Water Flush NO CSF -
MenuLine Service Contact Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
S702 Country - CSF -
S703 Address line 1 - CSF -
S704 Address line 2 - CSF -
S705 Address line 3 - CSF -S706 Address line 4 - CSF -
21
8/20/2019 Manual 07-06 Networking-where to Save
22/47
iCOM Where to Save Manual Rev. 07-06
Level 3 - Advanced Menus
MenuLine
Factory Settings Parameters, page1 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A002 Unit Code Field: (1-6) - -
A003 Set Code: - UCO -
A004 Unit Code Field: (7-12) - -
A005 Set Code: - UCO -
A006 Unit Code Field: (13-18) - -
A007 Set Code: UCO -
A008 Unit Code Control - - -
A009 Unit Code Status - - -
A010 Exception List Control - - -
A011 Exception List Status - - -
MenuLine
Factory Settings Parameters, page2 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A102 Refrigerant Type NO CSF -
A103 Main Fan Overload NO CSF -
A104 Loss Of Airflow NO CSF -
A105 Number of Compressors NO CSF - A106 Compressor Delay Time NO CSF -
A107 Compressor Min ON Time NO CSF -
A108 Compressor Min OFF Time NO CSF -
A109 Pump Down NO CSF -
A110 Capacity Control Type NO CSF -
22
8/20/2019 Manual 07-06 Networking-where to Save
23/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Factory Settings Parameters, page3 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A113 Digital Scroll Cycle NO CSF -
A114 High Temp Digital Scroll NO CSF - A115 Digital Scroll Switchback NO CSF -
A116 Low Pressure Device Type NO CSF -
A117 Low Pressure Threshold Phase 1 NO CSF -
A118 Low Pressure Threshold Phase 2 NO CSF -
MenuLine
Factory Settings Parameters, page4 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A13 LP1 Sensor 0% = NO CSF -
A13 LP1 Sensor 0% = NO CSF -
A125 LP1 Sensor 100% = NO CSF -
A125 LP1 Sensor 100% = NO CSF -
A126 Actual LP1 Signal NO CSF -
A127 LP2 Sensor 0% = NO CSF -
A127 LP2 Sensor 0% = NO CSF -
A128 LP2 Sensor 100% = NO CSF -
A128 LP2 Sensor 100% = NO CSF -
A129 Actual LP2 Signal NO CSF -
A130 Pumpdown Cutout NO CSF -
A131 Pumpdown Recycle NO CSF -
A132 Heat Rejection Control Type NO CSF -
23
8/20/2019 Manual 07-06 Networking-where to Save
24/47
iCOM Where to Save Manual Rev. 07-06
MenuLine
Factory Settings Parameters, page5 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A136 CW Flush Duration NO CSF -
A137 Freecooling NO CSF -
A139 Freecooling Flush Duration NO CSF - A140 Freecooling Flush Starts R5 NO CSF -
A141 Comp + FC Simultaneously NO CSF -
A143 Hot Water Flush Duration NO CSF -
MenuLine
Factory Settings Parameters, page6 of 6
Sharedin TW1
ControlBoard Safe
DisplaySafe
A146 Humidifier Model NO CSF -
A147 Humidity in Last xxx Hours NO CSF - A148 Prefill Time NO CSF -
A149 Fill Time NO CSF -
A150 Humidifier On Time NO CSF -
A151 Dehumidification with Comp NO CSF -
A152 Analog Output 1 NO CSF -
A153 Analog Output 2 NO CSF -
A154 Analog Output 3 NO CSF -
A155 Analog Output 4 NO CSF -
MenuLine Access Parameters
Sharedin TW1
ControlBoard Safe
DisplaySafe
A201 Password Level 1 (User) 4 digits CSF CSF
A202 Password Level 2 (Service) 4 digits CSF CSF
A203 Password Level 3 (Advanced) 4 digits CSF CSF
24
8/20/2019 Manual 07-06 Networking-where to Save
25/47
iCOM Where to Save Manual Rev. 07-06
Notes:
A008 and A009 for Unit Code; when the status indicates “Not Available”; you wouldneed to enter the correct code for the system by the decal on the unit into A003,
A005 and A007.
Next you would select the “Unit Code Control” Parameter and use the“Save+Execute” command and then select the “Load+Execute” command. Unit CodeStatus will show “OK”
A010 and A011 for Exception List; when status indicates “Not Available”; you wouldneed to save the variables selecting “Exception List Control” and select “Load”
S821 and S843 should always be checked and Rebooted as need in a changedstatus.
A201 through A203 can not be accessed to change passwords.
25
8/20/2019 Manual 07-06 Networking-where to Save
26/47
iCOM Where to Save Manual Rev. 07-06
Networking
This section of the manual provides a quick reference to information for setting upand networking the Liebert Systems supplied with the iCOM control. Systems
supplied with the iCOM control can be interconnected to create a private network forcommunications and control operations. There are several key factors that must beknown and considered to first setup a network and then to use the networkingprograms.
The following describes the Liebert control default settings, terminology, anddescriptions of functions and features.
Things you should know:
iCOM Control Default Settings and Ranges:
Large Display Default Settings: – IP: 192.168.254.003 – Netmask: 255.255.255.000 – Gateway: 000.000.000.000
Control Board Default Settings: – IP: 192.168.254.001 – Netmask: 255.255.255.000 – Gateway: 000.000.000.000
The U2U Address Default Setting and Range: – Large Display: 33 (range: 33 - 64) – Control Boards: 1 (range: 1 - 32)
Number of Units Connected Default Setting and Range: – 1 (range: 1 – 32)
Teamwork Default Setting and Choices: – No (choices: 1 or 2)
iCOM Terminology
PAB: Designation for the Large Display Board (Firmware)(earlier versions were designated LBB)
cdl: Designation for the Large Display Board (Hardware)
PAL: Designation for the Large Control Board (Firmware)(earlier versions were designated LBL)
gcl: Designation for the Large Control Board (Hardware)
26
8/20/2019 Manual 07-06 Networking-where to Save
27/47
iCOM Where to Save Manual Rev. 07-06
Network Basics
The Liebert iCOM Control Network is a Class C Private Network and will usethe 192.168.254.000 to 192.168.254.255 series of static IP addresses.
The Liebert iCOM Control Network has nothing to do with the local building orowner network.
The Liebert iCOM Control Network can only be attached to the local buildingor owner network by using a Liebert WEB Card or Liebert 485 Card installedthe Liebert Intellislot.
To be able to configure a host for communicating on an IP network, at least 3pieces of information are absolutely mandatory:
• The IP addresses are to uniquely identify the host (at least within thescope of the LAN).
• The Netmask addresses are to allow for the host to identify which otherhosts are connected directly to its IP subnet.
• The Default Gateway addresses are to allow for the host to directmessages to a router that are not intended for the local IP subnet.
A series of basic rules must be followed to connect and program the units forthis private iCOM Network. Here are some of the rules to be followed.
iCOM Basic Programming for a Network….
By default, each iCOM unit will try to establish a connection with other iCOM units in the same IP address subnet in order to create a group.
Whether or not this group of units will then act as a system depends oncertain iCOM application parameters, the group of iCOM units needs to beprogrammed in a specific “order”.
Small Displays use CAN connections only. Small Displays do not have aNetwork View or an IP Address.
Small Displays are networked with a CAT 5 crossover cable directly connectedbetween large control board of each unit. Only two (2) units can be networkedusing this arrangement.
27
8/20/2019 Manual 07-06 Networking-where to Save
28/47
iCOM Where to Save Manual Rev. 07-06
All Large Displays and Control Boards will use a CAT 5 or greater straightthrough (patch) cable to connect to the switch when networked.
An IP address number will be used to identify each receiver / sender ofinformation. Each large control board and each large display must have their
own individual IP Address. Each set of boards must be set up individually, then connected to the network
switch and checked before the next set of boards are connected to the switch.Connect the next set of boards to the switch one at a time and verifycommunications through the switch. Start with the last unit in group.
To locate the Network menu program selection in the cont rol:
Simply navigate the display by pressing▼
Down to move from System screen to Unit screen then,▼ Down to move from the Unit screen to the User Menu screen then,► Right to move from User Menu screen to the Service Menu screen.
Now press the Enter Key to highlight the Setpoints icon. Using the right► and down ▼ arrow keys navigate to Network icon and press the Enter key to select.
These parameters will be designated as the S800 series of parameters.
In the network parameters view there are two screens in each set of pages.The first set of pages are for the Large Display (called System Views with thefirmware designation PAB). The second set of pages are for the unit ControlBoard (called Unit Views with the firmware designation PAL). The user selectsthe ▼ or ▲ arrow keys for page 1 or 2 of the Large Display (PAB) and ► right arrow key to get to the Large Control Board (PAL) then the ▼ or ▲ arrowkeys to access page 1 or 2. Pressing the left ◄ arrow key will return thescreens to return to the Display.
28
8/20/2019 Manual 07-06 Networking-where to Save
29/47
iCOM Where to Save Manual Rev. 07-06
Example - Basic (U2U) with Small Displays
CAT5 (Crossover - cable)
Unit No. 1 Unit No. 2
Unit No. 1 Unit No. 2Program Unit #1 to the following Program Unit #2 to the following
IP: 192.168.254.001 IP: 192.168.254.002
Netmask: 255.255.255.000 Netmask: 255.255.255.000
Gateway: Leave Blank Gateway: Leave Blank
U2U Address: 1 U2U Address: 2
Number units connected: 2 Number units connected: 2
Teamwork: No Teamwork: No
Note: Remember, Small Displays use CAN connections only between the displayand control board. Small Displays do not have a Network View. Small Displays arenetworked with a CAT 5 crossover cable between the control boards. Only 2 unitswith small display can be networked together.
29
8/20/2019 Manual 07-06 Networking-where to Save
30/47
iCOM Where to Save Manual Rev. 07-06
000.000.000.000000.000.000.000255.255.255.0255.255.255.0
192.168.254.3 192.168.254.1
Default Settings
192.168.254.0192.168.254.0 255.255.255.0255.255.255.0192.168.254.7192.168.254. 6
192.168.254.0192.168.254.0
255.255.255.0255.255.255.0192.168.254.4192.168.254.3
192.168.254.0 192.168.254.0 255.255.255.0255.255.255.0192.168.254.2 192.168.254.1
192.168.254.0192.168.254.0 255.255.255.0255.255.255.0
192.168.254.13192.168.254.12
192.168.254.0192.168.254.0
255.255.255.0255.255.255.0
192.168.254.11192.168.254.10
192.168.254.0 192.168.254.0 255.255.255.0255.255.255.0
192.168.254.9 192.168.254.8
U2U = 3 U2U = 35U2U = 2 U2U = 34
U2U = 6 U2U = 38U2U = 5 U2U = 37U2U = 4 U2U = 36
Number Units Connected
654
321
Control Display
Multi-Unit IP Address Setup Chart Sample
The Plan for Networking
For “ iCOM System Networks” the room and equipment lay out is critical for thetype of program selected for functionally and…...
– Unit locations (loads, air flow, etc) – Unit name and number designations (identity) – Unit configurations (which type of programs)
Basic Rules to Apply
Multi-zones – No Teamwork
Balanced Loads – Small room – Teamwork 1
Unbalanced Loads – Large room – Teamwork 2
30
8/20/2019 Manual 07-06 Networking-where to Save
31/47
iCOM Where to Save Manual Rev. 07-06
Use as your GuideThe Plan
Each unit that is to be connected into the network requires a Read andRecord Form be completed prior to making any program changes in thecontrols. All programmed parameters located in the User, Service and
Advanced Menus must be recorded.
A blank Multi-Unit Setup Chart must be completed for the planned number ofunits to be connected into the network. This plan will be used to identify thenumerically identify the units, list each new IP Address , and Unit-2-Unit (U2U)
Address.
Remember the floor plan is the key. All units must be named for correctoperation when selecting the programs for networking.
31
8/20/2019 Manual 07-06 Networking-where to Save
32/47
iCOM Where to Save Manual Rev. 07-06
Teamwork Operation Guide All Networked units will run in the same Teamwork Mode (No Teamwork,
Mode 1 or Mode 2).
No auto changeover from TW mode to mode
Cascade brings the units on/off as the Temperature or Humidity goes up/down
Teamwork 1 only cascades standby units
Teamwork 1 – Alarms in operational units can activate the standby units
Teamwork 1 – Autoset controls the settings – More than two units must use integration
Teamwork: No or TW 1 or TW2 – Uses standard settings for Temperature/Humidity
• Autoset adjusts the proportional band (TW 1)• Autoset will not adjust the proportional band (No TW or TW 2)
– No Teamwork (no shared values)• Standby – Rotation allowed (no Cascading)
– Teamwork 1 (shared values)• Unit #1 determines the operational requirements (unit numbering
key)• Standby - Rotation• Cascade
– Teamwork 2 (shared values)• Most demanding operational request determines the operational
requirements (unit numbering key)• Opposite operational functions prevented (stops Fighting)• Standby – Rotation allowed (no Cascading)
– System Deviation• System T/H values compared to system setpoint and
proportional band (all values found in system screen)• Unit #1 calculates deviation. (0 - 100%)
– Proportional Band (relative part distribution)• Full band divided by number of available units.• 2 units: Unit #1 operates in 1-50% (first half) of the proportional
band, Unit #2 operates in 51 – 100% (second half) of theproportional band
• Applies to all functions – Cooling, Heating, Humidification andDehumidification.
– Changing Setpoints, Proportional Band or Dead Band will reset theshared parameters.
32
8/20/2019 Manual 07-06 Networking-where to Save
33/47
iCOM Where to Save Manual Rev. 07-06
– Autoset will control the proportional band if enabled in Teamwork 1. – Cascading
• 2 units standby + cascade• First unit is 1 - 50% and second unit is 51 - 100%• Standby unit waiting for an alarm or additional requirement•
As the need for an additional function is required the standby willcome on and start fan with load. (Minimum run time is 4 hours fora cascade unit)
• T/H of cascade unit not shared for system average
– Network units have same set points but not P-Band or D-band – Networked units have no magic override if a unit is locked out – If the switch used in the network fails all units will run in normal single
unit mode – Diagnostics of networking hardware and system require special tools.
Networking and troubleshooting requires a good understanding of manydetails and requires practice to get it right the first time.
33
8/20/2019 Manual 07-06 Networking-where to Save
34/47
iCOM Where to Save Manual Rev. 07-06
Basic Unit Cable Connections1. Review network wiring connections to unit I/O boards and large displays2. Review unit control board connections3. Become familiar with various U2U configurations4. Review examples of actual room layouts and unit placement.5. Discuss preparing for networking
Unit Connections (left) Small Screen Stand alone (right)
34
8/20/2019 Manual 07-06 Networking-where to Save
35/47
iCOM Where to Save Manual Rev. 07-06
Unit Connections
Stand-alone: Small Screen to Control Board
Networked using Switch: Small Screen to Control Board
35
8/20/2019 Manual 07-06 Networking-where to Save
36/47
iCOM Where to Save Manual Rev. 07-06
Unit Connections
Stand-alone: Large Screen to Control Board
Networked using Switch: Large Screen to Control Board
36
8/20/2019 Manual 07-06 Networking-where to Save
37/47
iCOM Where to Save Manual Rev. 07-06
Sample Configurations List
ConfigurationNumber
LargeDisplays
SmallDisplays
PrivateSwitch
RemoteLarge
DisplayFunction LiebertProducts Comments
1 No 2 No No Lead-Lag/ Rotation DSU2U with
cross-over
2 No 2 Yes 1 Lead-Lag/ Rotation DS
3 No 5 Yes 1 Lead-Lag/ Rotation DS
4 1 1 Yes No Lead-Lag/ Rotation DS
5 1 4 Yes No Lead-Lag
/ RotationDS
2 groups: 2units and 3
units
6 2 No Yes No Lead-Lag/ Rotation DS
7 3 no Yes 1 Lead-Lag/ Rotation DS
8 1 7 Yes no Lead-Lag/ Rotation DS2 groups of
4 units
Preparing for NetworkingSteps:
1. Become familiar with the room layout and unit placement.2. Determine total number of units to be networked.3. Define control programs and method(s) to be used – lead./.lag, rotation,
groups, teamwork mode, cascade.4. Determine U2U configurations to be used.5. Determine number and location of network switches and power requirements.6. Determine number of patch cables to be used and lengths.7. Make network wiring connections to unit control boards and large displays.8. Review unit Control Board and Large Display Setup parameters:
• Define IP Address• Define Netmask Number• Define Gateway Number• Define U2U Address• More
9. Create a network setup sheet (map) to document how each unit isprogrammed and connected (use labels).
37
8/20/2019 Manual 07-06 Networking-where to Save
38/47
iCOM Where to Save Manual Rev. 07-06
Warning: All parameters and variables changed must be saved inthe “ Network” screen – System View and Unit Views or informationwill be lost. The unit must be turned off the main power and back onwith the main power and then the start switch to reboot thecomputers (Display and Control Board) in the uni ts. See attachedsheets fo r additional information.
Blank Form
Multi-Unit IP Address Setup Chart
Number Units Connected
38
8/20/2019 Manual 07-06 Networking-where to Save
39/47
iCOM Where to Save Manual Rev. 07-06
Setpoints Blank Read and Record FormsThis information to be recorded is found in the Service Menu section, consists of2 pages and are coded S100.
Code Parameters , page 1 of 2 Value
S101 Password
S102 Temp Setpoint
S103 Humidity Setpoint
S104 Humid Control Type
S105 Supply Limit
S106 Supply Limit Temp Value
S107 Autoset Enabled
S108 Temperature Proportional Band
S109 Temperature Integration Time
S110 Temperature Deadband
S111 Short Cycle Control
S112 Password
Code Parameters, page 2 of 2 Value
S113 Humidity Proportional Band
S114 Humidity Integration Time
S115 Humidity Deadband
S116 DT between Room / FC Type
S117 DT between Room Air/ FC Fluid
S118 Minimum CW Temp
S119 Minimum CW Temp Value
39
8/20/2019 Manual 07-06 Networking-where to Save
40/47
iCOM Where to Save Manual Rev. 07-06
Standby Setting/Lead-Lag Blank Read andRecord Form
This information to be recorded is found in the Service Menu section, consists of
1 page and is coded S500.
Code Parameter Value
S501 Password
S502 Number Standby Units
S503 Rotation Freq.
S504 Rotation at Hour
S505 Rotation at Minutes
S506 Rotate by
S507 Perform one rotation
S508 Cascade units
S509 Start all Standby Units on HT
40
8/20/2019 Manual 07-06 Networking-where to Save
41/47
iCOM Where to Save Manual Rev. 07-06
System/Network Setup Blank Read and RecordForms
This information to be recorded is found in the Service Menu section, consists of
4 pages and are coded S800.
System View Code Parameters, page 1 of 2 Value
S801 Password
S802 Number of Connected Units
S803 Teamwork Mode
S804
S805 U2U GroupS806
S807
S808
S809 Configuration Safe
S810 Network Safe
S811 SW Version PAB1__________________________
Code Parameters, page 2 of 2
S812 Password
S813 IP Address 192.168.254.____________________
S814 Netmask 255.255.255.000
S815 Gateway 000.000.000.000
S816 MAC Factory Set – Do Not Change
S817 U2U Protocol
S818 U2U Address
S819
S820
S821 Boot Loader Variables
41
8/20/2019 Manual 07-06 Networking-where to Save
42/47
iCOM Where to Save Manual Rev. 07-06
Unit View
Code Parameters, page 1 of 2 Value
S823 Password
S824 Monitoring Address
S825
S826 U2U Group
S827 Unit Name
S828
S829
S830
S831 Configuration Safe
S832 Network Safe
S833 SW Version PAL1________________________
Code Parameters, page 2 of 2
S834 Password
S835 Monitoring Protocol
S836 IP Address 192.168.254.__________________
S837 Netmask 255.255.255.255
S838 Gateway 000.000.000.000.
S839 MAC Factory Set – Do Not Change
S840 U2U Protocol
S841 U2U Address
S842
S843 Boot Loader Variables
S844 Static RAM
42
8/20/2019 Manual 07-06 Networking-where to Save
43/47
iCOM Where to Save Manual Rev. 07-06
Unit Code Blank Read and Record Form This information to be recorded is found in the Advanced Menu section, consists of1 page and is coded A000.
Code Parameters
A001 Password
A002 Unit Field Code (1-6) 001 002 003 004 005 006
A003 Set Code
A004 Unit Field Code (7-12) 007 008 009 010 011 012
A005 Set Code
A006 Unit Field Code (13-18) 013 014 015 016 017 018 A007 Set Code
A008 Unit Code Control
A009 Unit Code Status
A010 Exception List Control
A011 Exception List Status
43
8/20/2019 Manual 07-06 Networking-where to Save
44/47
iCOM Where to Save Manual Rev. 07-06
Site Survey for Networking Request Form
(For factory assistance complete the following pages and return toES&S Service. Attn: Henry Fudge - fax 614-841- 6781 or e-mail
[email protected]) A copy of the room floor plan with equipment layout must accompany this request:
YES ________ No ______
Number of unit’s: _______________
A copy of the cable layout diagram must accompany this request:
YES ________ No ______
Who is providing the networking cables? _________________________________
Who will run the cables? _____________________________________________
(Liebert does not provide this service)
If used, who is providing the network switches? ____________________________
If used, who will provide the 120vac outlet for the switch(s)? ___________________(Liebert does not provide this service)
Equipment Information:Unit Model Numbers Unit Serial Numbers Unit Name/ ID Number
44
8/20/2019 Manual 07-06 Networking-where to Save
45/47
iCOM Where to Save Manual Rev. 07-06
Display Information:Number of Large
DisplaysNumber of Small
DisplaysNumber of Wall
Mounted Displays
Distance from Unit to Unit:Unit ID Number Distance Between Unit ID Number
Distance from Each Unit to Switch:Unit ID Number Distance to Switch
List date when site will be ready for networking : ___________________________
45
8/20/2019 Manual 07-06 Networking-where to Save
46/47
iCOM Where to Save Manual Rev. 07-06
Identify which of the following programs will be used for operation andnetworking (review the previous pages for information on programs).
Control Operation Yes No
Lead-Lag OperationNo Teamwork
Teamwork #1
Teamwork $2
Rotation
Cascade
Addi tional Services:
Is remote monitoring required? ____________
If yes, what type? IGM _______ OCWEB __________ OC485 __________
If not provided already we can offer remote monitor ing capability. Select fromthe choices li sted below to determine your site needs.
Monitoring options:
1. Liebert IGMnet for SiteScan __________2. Liebert OC Web: SNMP __________
Liebert OC485 __________
Nform __________
3. MODbus __________
4. SiteScan __________
5. 3 rd. Party __________
46
8/20/2019 Manual 07-06 Networking-where to Save
47/47
iCOM Where to Save Manual Rev. 07-06
Notes