Manual Automatic Control SI

Embed Size (px)

Citation preview

  • AUTOMATICCONTROL forENGINEERING MANUAL of

    COMMERCIAL BUILDINGSSI Edition

  • ENGINEERING MANUAL OF AUTOMATIC CONTROLii

    Copyright 1989, 1995, and 1997 by Honeywell Inc.

    All rights reserved. This manual or portions thereof may not be reporducedin any form without permission of Honeywell Inc.

    Library of Congress Catalog Card Number: 97-77856

    Honeywell Europe S.A.3 Avenue du Bourget1140 BrusselsBelgium

    Honeywell Asia Pacific Inc.Room 3213-3225Sun Hung Kai CentreNo. 30 Harbour RoadWanchaiHong Kong

    Home and Building ControlHoneywell Limited-Honeywell Limite155 Gordon Baker RoadNorth York, OntarioM2H 3N7

    Honeywell Latin American Region480 Sawgrass Corporate ParkwaySuite 200Sunrise FL 33325

    Home and Building ControlHoneywell Inc.Honeywell PlazaP.O. Box 524Minneapolis MN 55408-0524

    Printed in USA

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL iii

    FOREWORD

    The Minneapolis Honeywell Regulator Company published the first edition of the Engineering Manual ofAutomatic Control in l934. The manual quickly became the standard textbook for the commercial buildingcontrols industry. Subsequent editions have enjoyed even greater success in colleges, universities, and contractorand consulting engineering offices throughout the world.

    Since the original 1934 edition, the building control industry has experienced dramatic change and madetremendous advances in equipment, system design, and application. In this edition, microprocessor controls areshown in most of the control applications rather than pneumatic, electric, or electronic to reflect the trends inindustry today. Consideration of configuration, functionality, and integration plays a significant role in thedesign of building control systems.

    Through the years Honeywell has been dedicated to assisting consulting engineers and architects in theapplication of automatic controls to heating, ventilating, and air conditioning systems. This manual is an outgrowthof that dedication. Our end user customers, the building owners and operators, will ultimately benefit from theefficiently designed systems resulting from the contents of this manual.

    All of this manuals original sections have been updated and enhanced to include the latest developments incontrol technology and use the International System of Units (SI). A new section has been added on indoor airquality and information on district heating has been added to the Chiller, Boiler, and Distribution SystemControl Applications Section.

    This third SI edition of the Engineering Manual of Automatic Control is our contribution to ensure that wecontinue to satisfy our customers requirements. The contributions and encouragement received from previoususers are gratefully acknowledged. Further suggestions will be most welcome.

    Minneapolis, MinnesotaDecember, 1997

    KEVIN GILLIGANPresident, H&BC Solutions and Services

  • ENGINEERING MANUAL OF AUTOMATIC CONTROLiv

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL v

    PREFACE

    The purpose of this manual is to provide the reader with a fundamental understanding of controls and howthey are applied to the many parts of heating, ventilating, and air conditioning systems in commercial buildings.

    Many aspects of control are presented including air handling units, terminal units, chillers, boilers, buildingairflow, water and steam distribution systems, smoke management, and indoor air quality. Control fundamentals,theory, and types of controls provide background for application of controls to heating, ventilating, and airconditioning systems. Discussions of pneumatic, electric, electronic, and digital controls illustrate that applicationsmay use one or more of several different control methods. Engineering data such as equipment sizing, use ofpsychrometric charts, and conversion formulas supplement and support the control information. To enhanceunderstanding, definitions of terms are provided within individual sections.

    Building management systems have evolved into a major consideration for the control engineer when evaluatinga total heating, ventilating, and air conditioning system design. In response to this consideration, the basics ofbuilding management systems configuration are presented.

    The control recommendations in this manual are general in nature and are not the basis for any specific job orinstallation. Control systems are furnished according to the plans and specifications prepared by the controlengineer. In many instances there is more than one control solution. Professional expertise and judgment arerequired for the design of a control system. This manual is not a substitute for such expertise and judgment.Always consult a licensed engineer for advice on designing control systems.

    It is hoped that the scope of information in this manual will provide the readers with the tools to expand theirknowledge base and help develop sound approaches to automatic control.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROLvi

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL vii

    CONTENTSForeward ............................................................................................................ iii

    Preface ............................................................................................................ v

    Control System Fundamentals .......................................................................................... 1Control Fundamentals ............................................................................................................ 3

    Introduction.......................................................................................... 5Definitions ............................................................................................ 5HVAC System Characteristics ............................................................. 8Control System Characteristics ........................................................... 15Control System Components .............................................................. 30Characteristics and Attributes of Control Methods .............................. 35

    Psychrometric Chart Fundamentals ............................................................................................................ 37Introduction.......................................................................................... 38Definitions ............................................................................................ 38Description of the Psychrometric Chart ............................................... 39The Abridged Psychrometric Chart ..................................................... 40Examples of Air Mixing Process .......................................................... 42Air Conditioning Processes ................................................................. 43Humidifying Process ............................................................................ 44Process Summary ............................................................................... 53ASHRAE Psychrometric Charts .......................................................... 53

    Pneumatic Control Fundamentals ............................................................................................................ 57Introduction.......................................................................................... 59Definitions ............................................................................................ 59Abbreviations ....................................................................................... 60Symbols ............................................................................................... 61Basic Pneumatic Control System ........................................................ 61Air Supply Equipment .......................................................................... 65Thermostats ........................................................................................ 69Controllers ........................................................................................... 70Sensor-Controller Systems ................................................................. 72Actuators and Final Control Elements ................................................. 74Relays and Switches ........................................................................... 77Pneumatic Control Combinations ........................................................ 84Pneumatic Centralization .................................................................... 89Pneumatic Control System Example ................................................... 90

    Electric Control Fundamentals ............................................................................................................ 95Introduction.......................................................................................... 97Definitions ............................................................................................ 97How Electric Control Circuits are Classified ........................................ 99Series 40 Control Circuits .................................................................... 100Series 80 Control Circuits .................................................................... 102Series 60 Two-Position Control Circuits ............................................... 103Series 60 Floating Control Circuits ...................................................... 106Series 90 Control Circuits .................................................................... 107Motor Control Circuits .......................................................................... 114

    ENGINEERING MANUAL ofAUTOMATICCONTROL

  • ENGINEERING MANUAL OF AUTOMATIC CONTROLviii

    Electronic Control Fundamentals ............................................................................................................ 119Introduction.......................................................................................... 120Definitions ............................................................................................ 120Typical System .................................................................................... 122Components ........................................................................................ 122Electronic Controller Fundamentals .................................................... 129Typical System Application .................................................................. 130

    Microprocessor-Based/DDC Fundamentals .................................................................................................... 131Introduction.......................................................................................... 133Definitions ............................................................................................ 133Background ......................................................................................... 134Advantages ......................................................................................... 134Controller Configuration ...................................................................... 135Types of Controllers ............................................................................. 136Controller Software .............................................................................. 137Controller Programming ...................................................................... 142Typical Applications ............................................................................. 145

    Indoor Air Quality Fundamentals ............................................................................................................ 149Introduction.......................................................................................... 151Definitions ............................................................................................ 151Abbreviations ....................................................................................... 153Indoor Air Quality Concerns ................................................................ 154Indoor Air Quality Control Applications................................................ 164Bibliography ......................................................................................... 170

    Smoke Management Fundamentals ............................................................................................................ 171Introduction.......................................................................................... 172Definitions ............................................................................................ 172Objectives ............................................................................................ 173Design Considerations ........................................................................ 173Design Priniples .................................................................................. 175Control Applications ............................................................................ 178Acceptance Testing ............................................................................. 181Leakage Rated Dampers .................................................................... 181Bibliography ......................................................................................... 182

    Building Management System Fundamentals ................................................................................................. 183Introduction.......................................................................................... 184Definitions ............................................................................................ 184Background ......................................................................................... 185System Configurations ........................................................................ 186System Functions ................................................................................ 189Integration of Other Systems............................................................... 196

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL ix

    Control System Applications .......................................................................................... 199Air Handling System Control Applications ...................................................................................................... 201

    Introduction.......................................................................................... 203Abbreviations ....................................................................................... 203Requirements for Effective Control ...................................................... 204Applications-General ........................................................................... 206Valve and Damper Selection ............................................................... 207Symbols ............................................................................................... 208Ventilation Control Processes ............................................................. 209Fixed Quantity of Outdoor Air Control ................................................. 211Heating Control Processes .................................................................. 223Preheat Control Processes ................................................................. 228Humidification Control Process ........................................................... 235Cooling Control Processes .................................................................. 236Dehumidification Control Processes ................................................... 243Heating System Control Process ........................................................ 246Year-Round System Control Processes .............................................. 248ASHRAE Psychrometric Charts .......................................................... 261

    Building Airflow System Control Applications ............................................................................................... 263Introduction.......................................................................................... 265Definitions ............................................................................................ 265Airflow Control Fundamentals ............................................................. 266Airflow Control Applications ................................................................. 280References .......................................................................................... 290

    Chiller, Boiler, and Distribution System Control Applications ....................................................................... 291Introduction.......................................................................................... 295Abbreviations ....................................................................................... 295Definitions ............................................................................................ 295Symbols ............................................................................................... 296Chiller System Control ......................................................................... 297Boiler System Control .......................................................................... 327Hot and Chilled Water Distribution Systems Control ........................... 335High Temperature Water Heating System Control ............................... 374District Heating Applications................................................................ 380

    Individual Room Control Applications ............................................................................................................ 395Introduction.......................................................................................... 397Unitary Equipment Control .................................................................. 408Hot Water Plant Considerations .......................................................... 424

  • ENGINEERING MANUAL OF AUTOMATIC CONTROLx

    Engineering Information .......................................................................................... 425Valve Selection and Sizing ............................................................................................................ 427

    Introduction.......................................................................................... 428Definitions............................................................................................ 428Valve Selection .................................................................................... 432Valve Sizing ......................................................................................... 437

    Damper Selection and Sizing ............................................................................................................ 445Introduction.......................................................................................... 447Definitions............................................................................................ 447Damper Selection ................................................................................ 448Damper Sizing ..................................................................................... 457Damper Pressure Drop ....................................................................... 462Damper Applications ........................................................................... 463

    General Engineering Data ............................................................................................................ 465Introduction.......................................................................................... 466Conversion Formulas and Tables ........................................................ 466Electrical Data ..................................................................................... 473Properties of Saturated Steam Data ................................................... 476Airflow Data ......................................................................................... 477Moisture Content of Air Data ............................................................... 479

    Index .......................................................................................... 483

  • SMOKE MANAGEMENT FUNDAMENTALS

    ENGINEERING MANUAL OF AUTOMATIC CONTROL 1

    CONTROLSYSTEM

    FUNDAMENTALS

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    SMOKE MANAGEMENT FUNDAMENTALS

    2

    SMOKE MANAGEMENT FUNDAMENTALS

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    3

    CONTENTS

    Control FundamentalsENGINEERING MANUAL OF AUTOMATIC CONTROL

    Introduction ............................................................................................................ 5

    Definitions ............................................................................................................ 5

    HVAC System Characteristics ............................................................................................................ 8General ................................................................................................ 8Heating ................................................................................................ 9

    General ........................................................................................... 9Heating Equipment ......................................................................... 10

    Cooling ................................................................................................ 11General ........................................................................................... 11Cooling Equipment .......................................................................... 12

    Dehumidification .................................................................................. 12Humidification ...................................................................................... 13Ventilation ............................................................................................ 13Filtration ............................................................................................... 14

    Control System Characteristics ............................................................................................................ 15Controlled Variables ............................................................................ 15Control Loop ........................................................................................ 15Control Methods .................................................................................. 16

    General ........................................................................................... 16Analog and Digital Control .............................................................. 16

    Control Modes ..................................................................................... 17Two-Position Control ....................................................................... 17

    General ....................................................................................... 17Basic Two-Position Control ......................................................... 17Timed Two-Position Control ........................................................ 18

    Step Control .................................................................................... 19Floating Control ............................................................................... 20Proportional Control ........................................................................ 21

    General ....................................................................................... 21Compensation Control ................................................................ 22

    Proportional-Integral (PI) Control .................................................... 23Proportional-Integral-Derivative (PID) Control ................................ 25Enhanced Proportional-Integral-Derivative (EPID) Control ............. 25Adaptive Control .............................................................................. 26

    Process Characteristics....................................................................... 26Load ................................................................................................ 26Lag .................................................................................................. 27

    General ....................................................................................... 27Measurement Lag ....................................................................... 27Capacitance ................................................................................ 28Resistance .................................................................................. 29Dead Time .................................................................................. 29

    Control Application Guidelines ............................................................ 29

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    4

    Control System Components ............................................................................................................ 30Sensing Elements ............................................................................... 30

    Temperature Sensing Elements ...................................................... 30Pressure Sensing Elements ............................................................ 31Moisture Sensing Elements ............................................................ 32Flow Sensors .................................................................................. 32Proof-of-Operation Sensors ............................................................ 33

    Transducers ......................................................................................... 33Controllers ........................................................................................... 33Actuators ............................................................................................. 33Auxiliary Equipment ............................................................................. 34

    Characteristics and Attributes of Control Methods .............................................................................. 35

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    5

    INTRODUCTIONThis section describes heating, ventilating, and air

    conditioning (HVAC) systems and discusses characteristics andcomponents of automatic control systems. Cross-references aremade to sections that provide more detailed information.

    A correctly designed HVAC control system can provide acomfortable environment for occupants, optimize energy costand consumption, improve employee productivity, facilitateefficient manufacturing, control smoke in the event of a fire,and support the operation of computer and telecommunicationsequipment. Controls are essential to the proper operation ofthe system and should be considered as early in the designprocess as possible.

    Properly applied automatic controls ensure that a correctlydesigned HVAC system will maintain a comfortableenvironment and perform economically under a wide range ofoperating conditions. Automatic controls regulate HVAC systemoutput in response to varying indoor and outdoor conditions tomaintain general comfort conditions in office areas and providenarrow temperature and humidity limits where required inproduction areas for product quality.

    Automatic controls can optimize HVAC system operation.They can adjust temperatures and pressures automatically toreduce demand when spaces are unoccupied and regulateheating and cooling to provide comfort conditions while limitingenergy usage. Limit controls ensure safe operation of HVACsystem equipment and prevent injury to personnel and damageto the system. Examples of limit controls are low-limittemperature controllers which help prevent water coils or heatexchangers from freezing and flow sensors for safe operationof some equipment (e.g., chillers). In the event of a fire,controlled air distribution can provide smoke-free evacuationpassages, and smoke detection in ducts can close dampers toprevent the spread of smoke and toxic gases.

    HVAC control systems can also be integrated with securityaccess control systems, fire alarm systems, lighting controlsystems, and building and facility management systems tofurther optimize building comfort, safety, and efficiency.

    DEFINITIONSThe following terms are used in this manual. Figure 1 at the

    end of this list illustrates a typical control loop with thecomponents identified using terms from this list.

    Analog: Continuously variable (e.g., a faucet controlling waterfrom off to full flow).

    Automatic control system: A system that reacts to a change orimbalance in the variable it controls by adjusting othervariables to restore the system to the desired balance.

    Algorithm: A calculation method that produces a control outputby operating on an error signal or a time series of errorsignals.

    Compensation control: A process of automatically adjustingthe setpoint of a given controller to compensate forchanges in a second measured variable (e.g., outdoorair temperature). For example, the hot deck setpointis normally reset upward as the outdoor air temperaturedecreases. Also called reset control.

    Control agent: The medium in which the manipulated variableexists. In a steam heating system, the control agent isthe steam and the manipulated variable is the flow ofthe steam.

    Control point: The actual value of the controlled variable(setpoint plus or minus offset).

    Controlled medium: The medium in which the controlledvariable exists. In a space temperature control system,the controlled variable is the space temperature andthe controlled medium is the air within the space.

    Controlled Variable: The quantity or condition that is measuredand controlled.

    Controller: A device that senses changes in the controlledvariable (or receives input from a remote sensor) andderives the proper correction output.

    Corrective action: Control action that results in a change ofthe manipulated variable. Initiated when the controlledvariable deviates from setpoint.

    Cycle: One complete execution of a repeatable process. In basicheating operation, a cycle comprises one on periodand one off period in a two-position control system.

    Cycling: A periodic change in the controlled variable from onevalue to another. Out-of-control analog cycling iscalled hunting. Too frequent on-off cycling is calledshort cycling. Short cycling can harm electricmotors, fans, and compressors.

    Cycling rate: The number of cycles completed per time unit,typically cycles per hour for a heating or cooling system.The inverse of the length of the period of the cycle.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    6

    Deadband: A range of the controlled variable in which nocorrective action is taken by the controlled system andno energy is used. See also zero energy band.

    Deviation: The difference between the setpoint and the valueof the controlled variable at any moment. Also calledoffset.

    DDC: Direct Digital Control. See also Digital and Digitalcontrol.

    Digital: A series of on and off pulses arranged to conveyinformation. Morse code is an early example.Processors (computers) operate using digital language.

    Digital control: A control loop in which a microprocessor-based controller directly controls equipment based onsensor inputs and setpoint parameters. Theprogrammed control sequence determines the outputto the equipment.

    Droop: A sustained deviation between the control point andthe setpoint in a two-position control system causedby a change in the heating or cooling load.

    Enhanced proportional-integral-derivative (EPID) control:A control algorithm that enhances the standard PIDalgorithm by allowing the designer to enter a startupoutput value and error ramp duration in addition tothe gains and setpoints. These additional parametersare configured so that at startup the PID output variessmoothly to the control point with negligible overshootor undershoot.

    Electric control: A control circuit that operates on line or lowvoltage and uses a mechanical means, such as atemperature-sensitive bimetal or bellows, to performcontrol functions, such as actuating a switch orpositioning a potentiometer. The controller signal usuallyoperates or positions an electric actuator or may switchan electrical load directly or through a relay.

    Electronic control: A control circuit that operates on lowvoltage and uses solid-state components to amplifyinput signals and perform control functions, such asoperating a relay or providing an output signal toposition an actuator. The controller usually furnishesfixed control routines based on the logic of the solid-state components.

    Final control element: A device such as a valve or damperthat acts to change the value of the manipulatedvariable. Positioned by an actuator.

    Hunting: See Cycling.

    Lag: A delay in the effect of a changed condition at one point inthe system, or some other condition to which it is related.Also, the delay in response of the sensing element of acontrol due to the time required for the sensing elementto sense a change in the sensed variable.

    Load: In a heating or cooling system, the heat transfer that thesystem will be called upon to provide. Also, the workthat the system must perform.

    Manipulated variable: The quantity or condition regulatedby the automatic control system to cause the desiredchange in the controlled variable.

    Measured variable: A variable that is measured and may becontrolled (e.g., discharge air is measured andcontrolled, outdoor air is only measured).

    Microprocessor-based control: A control circuit that operateson low voltage and uses a microprocessor to performlogic and control functions, such as operating a relayor providing an output signal to position an actuator.Electronic devices are primarily used as sensors. Thecontroller often furnishes flexible DDC and energymanagement control routines.

    Modulating: An action that adjusts by minute increments anddecrements.

    Offset: A sustained deviation between the control point andthe setpoint of a proportional control system understable operating conditions.

    On/off control: A simple two-position control system in whichthe device being controlled is either full on or full offwith no intermediate operating positions available.Also called two-position control.

    Pneumatic control: A control circuit that operates on airpressure and uses a mechanical means, such as atemperature-sensitive bimetal or bellows, to performcontrol functions, such as actuating a nozzle andflapper or a switching relay. The controller outputusually operates or positions a pneumatic actuator,although relays and switches are often in the circuit.

    Process: A general term that describes a change in a measurablevariable (e.g., the mixing of return and outdoor airstreams in a mixed-air control loop and heat transferbetween cold water and hot air in a cooling coil).Usually considered separately from the sensingelement, control element, and controller.

    Proportional band: In a proportional controller, the controlpoint range through which the controlled variable mustpass to move the final control element through its fulloperationg range. Expressed in percent of primarysensor span. Commonly used equivalents arethrottling range and modulating range, usuallyexpressed in a quantity of Engineering units (degreesof temperature).

    Proportional control: A control algorithm or method in whichthe final control element moves to a positionproportional to the deviation of the value of thecontrolled variable from the setpoint.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    7

    Proportional-Integral (PI) control: A control algorithm thatcombines the proportional (proportional response) andintegral (reset response) control algorithms. Resetresponse tends to correct the offset resulting fromproportional control. Also called proportional-plus-reset or two-mode control.

    Proportional-Integral-Derivative (PID) control: A controlalgorithm that enhances the PI control algorithm byadding a component that is proportional to the rate ofchange (derivative) of the deviation of the controlledvariable. Compensates for system dynamics andallows faster control response. Also called three-mode or rate-reset control.

    Reset Control: See Compensation Control.

    Sensing element: A device or component that measures thevalue of a variable.

    Setpoint: The value at which the controller is set (e.g., thedesired room temperature set on a thermostat). Thedesired control point.

    Short cycling: See Cycling.

    Step control: Control method in which a multiple-switchassembly sequentially switches equipment (e.g.,electric heat, multiple chillers) as the controller inputvaries through the proportional band. Step controllers

    may be actuator driven, electronic, or directly activatedby the sensed medium (e.g., pressure, temperature).

    Throttling range: In a proportional controller, the control pointrange through which the controlled variable must passto move the final control element through its fulloperating range. Expressed in values of the controlledvariable (e.g., Kelvins or degrees Celsius, percentrelative humidity, kilopascals). Also calledproportional band. In a proportional roomthermostat, the temperature change required to drivethe manipulated variable from full off to full on.

    Time constant: The time required for a dynamic component,such as a sensor, or a control system to reach 63.2percent of the total response to an instantaneous (orstep) change to its input. Typically used to judgethe responsiveness of the component or system.

    Two-position control: See on/off control.

    Zero energy band: An energy conservation technique thatallows temperatures to float between selected settings,thereby preventing the consumption of heating orcooling energy while the temperature is in this range.

    Zoning: The practice of dividing a building into sections forheating and cooling control so that one controller issufficient to determine the heating and coolingrequirements for the section.

    Fig. 1. Typical Control Loop.

    SETPOINT

    15

    -15

    55

    90

    RESET SCHEDULE

    HWSETPOINT

    OA TEMPERATURE

    70

    71

    64

    AUTO

    41

    INPUTOUTPUT

    -2

    PERCENTOPEN

    VALVE

    STEAM

    FLOW

    OUTDOORAIR

    OUTDOORAIR

    CONTROLPOINT

    HOT WATERRETURN

    HOT WATERSUPPLY

    HOT WATERSUPPLY

    TEMPERATURECONTROLLED

    MEDIUM

    CONTROLLEDVARIABLE

    MEASUREDVARIABLE

    MEASUREDVARIABLE

    SETPOINT

    ALGORITHM INCONTROLLER

    FINAL CONTROLELEMENT

    CONTROLAGENT

    MANIPULATEDVARIABLE

    M15127

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    8

    HVAC SYSTEM CHARACTERISTICS

    Figure 2 shows how an HVAC system may be distributed ina small commercial building. The system control panel, boilers,motors, pumps, and chillers are often located on the lower level.The cooling tower is typically located on the roof. Throughoutthe building are ductwork, fans, dampers, coils, air filters,heating units, and variable air volume (VAV) units and diffusers.Larger buildings often have separate systems for groups of floorsor areas of the building.

    Fig. 2. Typical HVAC System in a Small Building.

    The control system for a commercial building comprisesmany control loops and can be divided into central system andlocal- or zone-control loops. For maximum comfort andefficiency, all control loops should be tied together to shareinformation and system commands using a buildingmanagement system. Refer to the Building Management SystemFundamentals section of this manual.

    The basic control loops in a central air handling system canbe classified as shown in Table 1.

    Depending on the system, other controls may be requiredfor optimum performance. Local or zone controls depend onthe type of terminal units used.

    DAMPERAIR FILTER

    COOLING COIL

    FAN

    CHILLER

    PUMP

    COOLINGTOWER HEATING

    UNIT

    DUCTWORK

    VAV BOXDIFFUSER

    BOILER CONTROLPANELM10506

    GENERAL

    An HVAC system is designed according to capacityrequirements, an acceptable combination of first cost and operatingcosts, system reliability, and available equipment space.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    9

    Table 1. Functions of Central HVAC Control Loops.

    HEATING

    GENERAL

    Building heat loss occurs mainly through transmission,infiltration/exfiltration, and ventilation (Fig. 3).

    Fig. 3. Heat Loss from a Building.

    The heating capacity required for a building depends on thedesign temperature, the quantity of outdoor air used, and thephysical activity of the occupants. Prevailing winds affect therate of heat loss and the degree of infiltration. The heatingsystem must be sized to heat the building at the coldest outdoortemperature the building is likely to experience (outdoor designtemperature).

    Transmission is the process by which energy enters or leavesa space through exterior surfaces. The rate of energytransmission is calculated by subtracting the outdoortemperature from the indoor temperature and multiplying theresult by the heat transfer coefficient of the surface materials.The rate of transmission varies with the thickness andconstruction of the exterior surfaces but is calculated the sameway for all exterior surfaces:

    Energy Transmission perUnit Area and Unit Time = (TIN - TOUT) x HTC

    Where:TIN = indoor temperature

    TOUT = outdoor temperatureHTC = heat transfer coefficient

    HTC = jouleUnit Time x Unit Area x Unit Temperature

    ROOF -7CTRANSMISSION

    VENTILATION DUCT

    EXFILTRATION

    DOOR WINDOW

    PREVAILINGWINDS

    INFILTRATION

    20C

    C3971

    ControlLoop Classification Description

    Ventilation Basic Coordinates operation of the outdoor, return, and exhaust air dampers to maintainthe proper amount of ventilation air. Low-temperature protection is often required.

    Better Measures and controls the volume of outdoor air to provide the proper mix ofoutdoor and return air under varying indoor conditions (essential in variable airvolume systems). Low-temperature protection may be required.

    Cooling Chiller control Maintains chiller discharge water at preset temperature or resets temperatureaccording to demand.

    Cooling towercontrol

    Controls cooling tower fans to provide the coolest water practical under existingwet bulb temperature conditions.

    Water coil control Adjusts chilled water flow to maintain temperature.Direct expansion(DX) system control

    Cycles compressor or DX coil solenoid valves to maintain temperature. Ifcompressor is unloading type, cylinders are unloaded as required to maintaintemperature.

    Fan Basic Turns on supply and return fans during occupied periods and cycles them asrequired during unoccupied periods.

    Better Adjusts fan volumes to maintain proper duct and space pressures. Reduces systemoperating cost and improves performance (essential for variable air volume systems).

    Heating Coil control Adjusts water or steam flow or electric heat to maintain temperature.Boiler control Operates burner to maintain proper discharge steam pressure or water temperature.

    For maximum efficiency in a hot water system, water temperature should be reset asa function of demand or outdoor temperature.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    10

    Infiltration is the process by which outdoor air enters abuilding through walls, cracks around doors and windows, andopen doors due to the difference between indoor and outdoorair pressures. The pressure differential is the result oftemperature difference and air intake or exhaust caused by fanoperation. Heat loss due to infiltration is a function oftemperature difference and volume of air moved. Exfiltrationis the process by which air leaves a building (e.g., through wallsand cracks around doors and windows) and carries heat with it.Infiltration and exfiltration can occur at the same time.

    Ventilation brings in fresh outdoor air that may requireheating. As with heat loss from infiltration and exfiltration, heatloss from ventilation is a function of the temperature differenceand the volume of air brought into the building or exhausted.

    HEATING EQUIPMENT

    Selecting the proper heating equipment depends on manyfactors, including cost and availability of fuels, building sizeand use, climate, and initial and operating cost trade-offs.Primary sources of heat include gas, oil, wood, coal, electrical,and solar energy. Sometimes a combination of sources is mosteconomical. Boilers are typically fueled by gas and may havethe option of switching to oil during periods of high demand.Solar heat can be used as an alternate or supplementary sourcewith any type of fuel.

    Figure 4 shows an air handling system with a hot water coil.A similar control scheme would apply to a steam coil. If steamor hot water is chosen to distribute the heat energy, high-efficiency boilers may be used to reduce life-cycle cost. Watergenerally is used more often than steam to transmit heat energyfrom the boiler to the coils or terminal units, because waterrequires fewer safety measures and is typically more efficient,especially in mild climates.

    THERMOSTAT

    HOT WATERSUPPLY

    VALVE

    DISCHARGEAIR

    FAN

    HOT WATERRETURN C2702

    Fig. 4. System Using Heating Coil.

    An air handling system provides heat by moving an air streamacross a coil containing a heating medium, across an electricheating coil, or through a furnace. Unit heaters (Fig. 5) aretypically used in shops, storage areas, stairwells, and docks.Panel heaters (Fig. 6) are typically used for heating floors andare usually installed in a slab or floor structure, but may beinstalled in a wall or ceiling.

    C2703

    UNIT HEATER

    COIL

    FAN

    STEAM ORHOT WATERSUPPLY

    CONDENSATEOR HOT WATERRETURN

    STEAM TRAP(IF STEAM SUPPLY)

    Fig. 5. Typical Unit Heater.

    C3035

    DISCHARGE AIR

    WALL

    OUTDOORAIR

    MIXINGDAMPERS

    RETURNAIR

    COOLING COIL

    DRAIN PAN

    HEATING COIL

    FAN

    Fig. 6. Panel Heaters.

    Unit ventilators (Fig. 7) are used in classrooms and mayinclude both a heating and a cooling coil. Convection heaters(Fig. 8) are used for perimeter heating and in entries andcorridors. Infrared heaters (Fig. 9) are typically used for spotheating in large areas (e.g., aircraft hangers, stadiums).

    HOT WATERSUPPLY

    HOT WATERRETURN

    GRID PANEL

    HOT WATERSUPPLY

    HOT WATERRETURN

    SERPENTINE PANELC2704

    Fig. 7. Unit Ventilator.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    11

    Fig. 8. Convection Heater.

    WARM AIR

    FINNED TUBE

    RETURN AIR

    FLOORSUPPLY

    RETURN

    TO OTHERHEATING UNITS

    FROM OTHERHEATING UNITS

    C2705

    REFLECTOR

    INFRAREDSOURCE

    C2706

    RADIANT HEAT

    Fig. 9. Infrared Heater.

    In mild climates, heat can be provided by a coil in the centralair handling system or by a heat pump. Heat pumps have theadvantage of switching between heating and cooling modes asrequired. Rooftop units provide packaged heating and cooling.Heating in a rooftop unit is usually by a gas- or oil-fired furnaceor an electric heat coil. Steam and hot water coils are availableas well. Perimeter heat is often required in colder climates,particularly under large windows.

    A heat pump uses standard refrigeration components and areversing valve to provide both heating and cooling within thesame unit. In the heating mode, the flow of refrigerant throughthe coils is reversed to deliver heat from a heat source to theconditioned space. When a heat pump is used to exchange heatfrom the interior of a building to the perimeter, no additionalheat source is needed.

    A heat-recovery system is often used in buildings where asignificant quantity of outdoor air is used. Several types of heat-recovery systems are available including heat pumps, runaroundsystems, rotary heat exchangers, and heat pipes.

    In a runaround system, coils are installed in the outdoor airsupply duct and the exhaust air duct. A pump circulates themedium (water or glycol) between the coils so that medium heatedby the exhaust air preheats the outdoor air entering the system.

    A rotary heat exchanger is a large wheel filled with metalmesh. One half of the wheel is in the outdoor air intake and theother half, in the exhaust air duct. As the wheel rotates, themetal mesh absorbs heat from the exhaust air and dissipates itin the intake air.

    A heat pipe is a long, sealed, finned tube charged with arefrigerant. The tube is tilted slightly with one end in the outdoorair intake and the other end in the exhaust air. In a heating

    application, the refrigerant vaporizes at the lower end in thewarm exhaust air, and the vapor rises toward the higher end inthe cool outdoor air, where it gives up the heat of vaporizationand condenses. A wick carries the liquid refrigerant back to thewarm end, where the cycle repeats. A heat pipe requires noenergy input. For cooling, the process is reversed by tilting thepipe the other way.

    Controls may be pneumatic, electric, electronic, digital, or acombination. Satisfactory control can be achieved usingindependent control loops on each system. Maximum operatingefficiency and comfort levels can be achieved with a controlsystem which adjusts the central system operation to thedemands of the zones. Such a system can save enough inoperating costs to pay for itself in a short time.

    Controls for the air handling system and zones are specificallydesigned for a building by the architect, engineer, or team whodesigns the building. The controls are usually installed at the jobsite. Terminal unit controls are typically factory installed. Boilers,heat pumps, and rooftop units are usually sold with a factory-installed control package specifically designed for that unit.

    COOLINGGENERAL

    Both sensible and latent heat contribute to the cooling loadof a building. Heat gain is sensible when heat is added to theconditioned space. Heat gain is latent when moisture is addedto the space (e.g., by vapor emitted by occupants and othersources). To maintain a constant humidity ratio in the space,water vapor must be removed at a rate equal to its rate of additioninto the space.

    Conduction is the process by which heat moves betweenadjoining spaces with unequal space temperatures. Heat maymove through exterior walls and the roof, or through floors,walls, or ceilings. Solar radiation heats surfaces which thentransfer the heat to the surrounding air. Internal heat gain isgenerated by occupants, lighting, and equipment. Warm airentering a building by infiltration and through ventilation alsocontributes to heat gain.

    Building orientation, interior and exterior shading, the angleof the sun, and prevailing winds affect the amount of solar heatgain, which can be a major source of heat. Solar heat receivedthrough windows causes immediate heat gain. Areas with largewindows may experience more solar gain in winter than insummer. Building surfaces absorb solar energy, become heated,and transfer the heat to interior air. The amount of change intemperature through each layer of a composite surface dependson the resistance to heat flow and thickness of each material.

    Occupants, lighting, equipment, and outdoor air ventilationand infiltration requirements contribute to internal heat gain.For example, an adult sitting at a desk produces about 117 watts.Incandescent lighting produces more heat than fluorescentlighting. Copiers, computers, and other office machines alsocontribute significantly to internal heat gain.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    12

    COOLING EQUIPMENT

    An air handling system cools by moving air across a coilcontaining a cooling medium (e.g., chilled water or arefrigerant). Figures 10 and 11 show air handling systems thatuse a chilled water coil and a refrigeration evaporator (directexpansion) coil, respectively. Chilled water control is usuallyproportional, whereas control of an evaporator coil is two-position. In direct expansion systems having more than onecoil, a thermostat controls a solenoid valve for each coil andthe compressor is cycled by a refrigerant pressure control. Thistype of system is called a pump down system. Pump downmay be used for systems having only one coil, but more oftenthe compressor is controlled directly by the thermostat.

    Fig. 10. System Using Cooling Coil.

    Fig. 11. System Using Evaporator(Direct Expansion) Coil.

    Two basic types of cooling systems are available: chillers,typically used in larger systems, and direct expansion (DX)coils, typically used in smaller systems. In a chiller, therefrigeration system cools water which is then pumped to coilsin the central air handling system or to the coils of fan coilunits, a zone system, or other type of cooling system. In a DXsystem, the DX coil of the refrigeration system is located inthe duct of the air handling system. Condenser cooling forchillers may be air or water (using a cooling tower), while DXsystems are typically air cooled. Because water cooling is moreefficient than air cooling, large chillers are always water cooled.

    Compressors for chilled water systems are usually centrifugal,reciprocating, or screw type. The capacities of centrifugal andscrew-type compressors can be controlled by varying thevolume of refrigerant or controlling the compressor speed. DXsystem compressors are usually reciprocating and, in somesystems, capacity can be controlled by unloading cylinders.Absorption refrigeration systems, which use heat energy directlyto produce chilled water, are sometimes used for large chilledwater systems.

    While heat pumps are usually direct expansion, a large heatpump may be in the form of a chiller. Air is typically the heatsource and heat sink unless a large water reservoir (e.g., groundwater) is available.

    Initial and operating costs are prime factors in selectingcooling equipment. DX systems can be less expensive thanchillers. However, because a DX system is inherently two-position (on/off), it cannot control temperature with the accuracyof a chilled water system. Low-temperature control is essentialin a DX system used with a variable air volume system.

    For more information control of various system equipment,refer to the following sections of this manual:

    Chiller, Boiler, and Distribution SystemControl Applications.

    Air Handling System Control Applications. Individual Room Control Applications.

    DEHUMIDIFICATION

    Air that is too humid can cause problems such as condensationand physical discomfort. Dehumidification methods circulatemoist air through cooling coils or sorption units.Dehumidification is required only during the cooling season.In those applications, the cooling system can be designed toprovide dehumidification as well as cooling.

    For dehumidification, a cooling coil must have a capacityand surface temperature sufficient to cool the air below its dewpoint. Cooling the air condenses water, which is then collectedand drained away. When humidity is critical and the coolingsystem is used for dehumidification, the dehumidified air maybe reheated to maintain the desired space temperature.

    When cooling coils cannot reduce moisture contentsufficiently, sorption units are installed. A sorption unit useseither a rotating granular bed of silica gel, activated alumina orhygroscopic salts (Fig. 12), or a spray of lithium chloride brineor glycol solution. In both types, the sorbent material absorbsmoisture from the air and then the saturated sorbent materialpasses through a separate section of the unit that applies heatto remove moisture. The sorbent material gives up moisture toa stream of scavenger air, which is then exhausted. Scavengerair is often exhaust air or could be outdoor air.

    TEMPERATURECONTROLLER

    SENSOR

    CONTROLVALVE

    CHILLED WATERSUPPLY

    CHILLEDWATERCOIL COOL AIR

    CHILLED WATER RETURN

    C2707-2

    D

    X

    TEMPERATURECONTROLLER SENSOR

    COOL AIR

    C2708-1

    EVAPORATORCOIL

    SOLENOIDVALVE

    REFRIGERANTLIQUID

    REFRIGERANTGAS

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    13

    Fig. 12. Granular Bed Sorption Unit.

    Sprayed cooling coils (Fig. 13) are often used for space humiditycontrol to increase the dehumidifier efficiency and to provide year-round humidity control (winter humidification also).

    DRY AIR

    HUMIDAIR

    ROTATINGGRANULARBED

    SORPTIONUNIT

    SCAVENGERAIR

    HEATINGCOIL

    HUMID AIREXHAUST

    C2709

    MOISTUREELIMINATORS

    SPRAYPUMP M10511

    COOLINGCOIL

    Fig. 13. Sprayed Coil Dehumidifier.

    For more information on dehumidification, refer to thefollowing sections of this manual:

    Psychrometric Chart Fundamentals. Air Handling System Control Applications.

    HUMIDIFICATION

    Low humidity can cause problems such as respiratorydiscomfort and static electricity. Humidifiers can humidify aspace either directly or through an air handling system. Forsatisfactory environmental conditions, the relative humidity ofthe air should be 30 to 60 percent. In critical areas whereexplosive gases are present, 50 percent minimum isrecommended. Humidification is usually required only duringthe heating season except in extremely dry climates.

    Humidifiers in air handling systems typically inject steamdirectly into the air stream (steam injection), spray atomizedwater into the air stream (atomizing), or evaporate heated waterfrom a pan in the duct into the air stream passing through theduct (pan humidification). Other types of humidifiers are a waterspray and sprayed coil. In spray systems, the water can be heatedfor better vaporization or cooled for dehumidification.

    For more information on humidification, refer to the followingsections of this manual:

    Psychrometric Chart Fundamentals. Air Handling System Control Applications.

    VENTILATION

    Ventilation introduces outdoor air to replenish the oxygensupply and rid building spaces of odors and toxic gases.Ventilation can also be used to pressurize a building to reduceinfiltration. While ventilation is required in nearly all buildings,the design of a ventilation system must consider the cost ofheating and cooling the ventilation air. Ventilation air must bekept at the minimum required level except when used for freecooling (refer to ASHRAE Standard 62, Ventilation forAcceptable Indoor Air Quality).

    To ensure high-quality ventilation air and minimize theamount required, the outdoor air intakes must be located toavoid building exhausts, vehicle emissions, and other sourcesof pollutants. Indoor exhaust systems should collect odors orcontaminants at their source. The amount of ventilation abuilding requires may be reduced with air washers, highefficiency filters, absorption chemicals (e.g., activated charcoal),or odor modification systems.

    Ventilation requirements vary according to the number ofoccupants and the intended use of the space. For a breakdownof types of spaces, occupancy levels, and required ventilation,refer to ASHRAE Standard 62.

    Figure 14 shows a ventilation system that supplies 100 percentoutdoor air. This type of ventilation system is typically usedwhere odors or contaminants originate in the conditioned space(e.g., a laboratory where exhaust hoods and fans remove fumes).Such applications require make-up air that is conditioned toprovide an acceptable environment.

    EXHAUST

    TOOUTDOORS

    EXHAUSTFAN

    RETURNAIR

    SPACE

    MAKE-UPAIR

    SUPPLY FAN

    COILFILTER

    OUTDOORAIR

    SUPPLY

    C2711

    Fig. 14. Ventilation System Using100 Percent Outdoor Air.

    In many applications, energy costs make 100 percent outdoorair constant volume systems uneconomical. For that reason,other means of controlling internal contaminants are available,such as variable volume fume hood controls, spacepressurization controls, and air cleaning systems.

    A ventilation system that uses return air (Fig. 15) is morecommon than the 100 percent outdoor air system. The return-air ventilation system recirculates most of the return air fromthe system and adds outdoor air for ventilation. The return-airsystem may have a separate fan to overcome duct pressure

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    14

    losses. The exhaust-air system may be incorporated into the airconditioning unit, or it may be a separate remote exhaust. Supplyair is heated or cooled, humidified or dehumidified, anddischarged into the space.

    DAMPER RETURN FAN

    RETURNAIR

    EXHAUSTAIR

    DAMPERS

    OUTDOORAIR

    MIXEDAIR

    FILTER COIL SUPPLY FAN

    SUPPLYAIR

    C2712

    Fig. 15. Ventilation System Using Return Air.

    Ventilation systems as shown in Figures 14 and 15 shouldprovide an acceptable indoor air quality, utilize outdoor air forcooling (or to supplement cooling) when possible, and maintainproper building pressurization.

    For more information on ventilation, refer to the followingsections of this manual:

    Indoor Air Quality Fundamentals. Air Handling System Control Applications. Building Airflow System Control Applications.

    FILTRATION

    Air filtration is an important part of the central air handlingsystem and is usually considered part of the ventilation system.Two basic types of filters are available: mechanical filters andelectrostatic precipitation filters (also called electronic aircleaners). Mechanical filters are subdivided into standard andhigh efficiency.

    Filters are selected according to the degree of cleanlinessrequired, the amount and size of particles to be removed, andacceptable maintenance requirements. High-efficiencyparticulate air (HEPA) mechanical filters (Fig. 16) do not releasethe collected particles and therefore can be used for clean roomsand areas where toxic particles are released. HEPA filterssignificantly increase system pressure drop, which must beconsidered when selecting the fan. Figure 17 shows othermechanical filters.

    C2713

    CELL

    PLEATED PAPER

    AIR FLOW

    Fig. 16. HEPA Filter.

    PLEATED FILTER

    BAG FILTER

    Fig. 17. Mechanical Filters.

    Other types of mechanical filters include strainers, viscouscoated filters, and diffusion filters. Straining removes particlesthat are larger than the spaces in the mesh of a metal filter andare often used as prefilters for electrostatic filters. In viscouscoated filters, the particles passing through the filter fiberscollide with the fibers and are held on the fiber surface. Diffusionremoves fine particles by using the turbulence present in theair stream to drive particles to the fibers of the filter surface.

    An electrostatic filter (Fig. 18) provides a low pressure dropbut often requires a mechanical prefilter to collect large particlesand a mechanical after-filter to collect agglomerated particlesthat may be blown off the electrostatic filter. An electrostaticfilter electrically charges particles passing through an ionizingfield and collects the charged particles on plates with an oppositeelectrical charge. The plates may be coated with an adhesive.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    15

    Fig. 18. Electrostatic Filter.

    CONTROL SYSTEM CHARACTERISTICSThe sensor can be separate from or part of the controller and

    is located in the controlled medium. The sensor measures thevalue of the controlled variable and sends the resulting signalto the controller. The controller receives the sensor signal,compares it to the desired value, or setpoint, and generates acorrection signal to direct the operation of the controlled device.The controlled device varies the control agent to regulate theoutput of the control equipment that produces the desiredcondition.

    HVAC applications use two types of control loops: open andclosed. An open-loop system assumes a fixed relationshipbetween a controlled condition and an external condition. Anexample of open-loop control would be the control of perimeterradiation heating based on an input from an outdoor airtemperature sensor. A circulating pump and boiler are energizedwhen an outdoor air temperature drops to a specified setting,and the water temperature or flow is proportionally controlledas a function of the outdoor temperature. An open-loop systemdoes not take into account changing space conditions frominternal heat gains, infiltration/exfiltration, solar gain, or otherchanging variables in the building. Open-loop control alonedoes not provide close control and may result in underheatingor overheating. For this reason, open-loop systems are notcommon in residential or commercial applications.

    A closed-loop system relies on measurement of the controlledvariable to vary the controller output. Figure 19 shows a blockdiagram of a closed-loop system. An example of closed-loopcontrol would be the temperature of discharge air in a ductdetermining the flow of hot water to the heating coils to maintainthe discharge temperature at a controller setpoint.

    AIRFLOW

    AIRFLOW

    ALTERNATEPLATESGROUNDED

    INTERMEDIATEPLATESCHARGEDTO HIGHPOSITIVEPOTENTIAL

    THEORETICALPATHS OFCHARGES DUSTPARTICLESPOSITIVELY CHARGED

    PARTICLES

    SOURCE: 1996 ASHRAE SYSTEMS AND EQUIPMENT HANDBOOK

    PATH OFIONS

    WIRES AT HIGHPOSITIVEPOTENTIAL

    C2714

    +

    +

    +

    +

    Automatic controls are used wherever a variable conditionmust be controlled. In HVAC systems, the most commonlycontrolled conditions are pressure, temperature, humidity, andrate of flow. Applications of automatic control systems rangefrom simple residential temperature regulation to precisioncontrol of industrial processes.

    CONTROLLED VARIABLES

    Automatic control requires a system in which a controllablevariable exists. An automatic control system controls thevariable by manipulating a second variable. The second variable,called the manipulated variable, causes the necessary changesin the controlled variable.

    In a room heated by air moving through a hot water coil, forexample, the thermostat measures the temperature (controlledvariable) of the room air (controlled medium) at a specifiedlocation. As the room cools, the thermostat operates a valvethat regulates the flow (manipulated variable) of hot water(control agent) through the coil. In this way, the coil furnishesheat to warm the room air.

    CONTROL LOOP

    In an air conditioning system, the controlled variable ismaintained by varying the output of the mechanical equipmentby means of an automatic control loop. A control loop consistsof an input sensing element, such as a temperature sensor; acontroller that processes the input signal and produces an outputsignal; and a final control element, such as a valve, that operatesaccording to the output signal.

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    16

    Fig. 19. Feedback in a Closed-Loop System.

    In this example, the sensing element measures the dischargeair temperature and sends a feedback signal to the controller.The controller compares the feedback signal to the setpoint.Based on the difference, or deviation, the controller issues acorrective signal to a valve, which regulates the flow of hotwater to meet the process demand. Changes in the controlledvariable thus reflect the demand. The sensing element continuesto measure changes in the discharge air temperature and feedsthe new condition back into the controller for continuouscomparison and correction.

    Automatic control systems use feedback to reduce themagnitude of the deviation and produce system stability asdescribed above. A secondary input, such as the input from anoutdoor air compensation sensor, can provide information aboutdisturbances that affect the controlled variable. Using an input inaddition to the controlled variable enables the controller toanticipate the effect of the disturbance and compensate for it, thusreducing the impact of disturbances on the controlled variable.

    CONTROL METHODS

    GENERAL

    An automatic control system is classified by the type ofenergy transmission and the type of control signal (analog ordigital) it uses to perform its functions.

    The most common forms of energy for automatic controlsystems are electricity and compressed air. Systems maycomprise one or both forms of energy.

    Systems that use electrical energy are electromechanical,electronic, or microprocessor controlled. Pneumatic controlsystems use varying air pressure from the sensor as input to acontroller, which in turn produces a pneumatic output signal toa final control element. Pneumatic, electromechanical, andelectronic systems perform limited, predetermined controlfunctions and sequences. Microprocessor-based controllers usedigital control for a wide variety of control sequences.

    Self-powered systems are a comparatively minor but stillimportant type of control. These systems use the power of themeasured variable to induce the necessary corrective action.For example, temperature changes at a sensor cause pressureor volume changes that are applied directly to the diaphragmor bellows in the valve or damper actuator.

    Many complete control systems use a combination of theabove categories. An example of a combined system is thecontrol system for an air handler that includes electric on/offcontrol of the fan and pneumatic control for the heating andcooling coils.

    Various control methods are described in the followingsections of this manual:

    Pneumatic Control Fundamentals. Electric Control Fundamentals. Electronic Control Fundamentals. Microprocessor-Based/DDC Fundamental.

    See CHARACTERISTICS AND ATTRIBUTES OFCONTROL METHODS.

    ANALOG AND DIGITAL CONTROL

    Traditionally, analog devices have performed HVAC control.A typical analog HVAC controller is the pneumatic type whichreceives and acts upon data continuously. In a pneumaticcontroller, the sensor sends the controller a continuouspneumatic signal, the pressure of which is proportional to thevalue of the variable being measured. The controller comparesthe air pressure sent by the sensor to the desired value of airpressure as determined by the setpoint and sends out a controlsignal based on the comparison.

    The digital controller receives electronic signals from sensors,converts the electronic signals to digital pulses (values), andperforms mathematical operations on these values. Thecontroller reconverts the output value to a signal to operate anactuator. The controller samples digital data at set time intervals,rather than reading it continually. The sampling method is calleddiscrete control signaling. If the sampling interval for the digitalcontroller is chosen properly, discrete output changes provideeven and uninterrupted control performance.

    Figure 20 compares analog and digital control signals. Thedigital controller periodically updates the process as a functionof a set of measured control variables and a given set of controlalgorithms. The controller works out the entire computation,including the control algorithm, and sends a signal to an actuator.In many of the larger commercial control systems, an electronic-pneumatic transducer converts the electric output to a variablepressure output for pneumatic actuation of the final controlelement.

    SETPOINT

    FEEDBACKCONTROLLER SECONDARYINPUT

    CORRECTIVESIGNAL

    FINAL CONTROLELEMENT

    PROCESS DISTURBANCES

    CONTROLLEDVARIABLESENSING

    ELEMENT

    MANIPULATEDVARIABLE

    C2072

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    17

    Fig. 20. Comparison of Analogand Digital Control Signals.

    CONTROL MODES

    Control systems use different control modes to accomplishtheir purposes. Control modes in commercial applicationsinclude two-position, step, and floating control; proportional,proportional-integral, and proportional-integral-derivativecontrol; and adaptive control.

    TWO-POSITION CONTROL

    General

    In two-position control, the final control element occupiesone of two possible positions except for the brief period whenit is passing from one position to the other. Two-position controlis used in simple HVAC systems to start and stop electric motorson unit heaters, fan coil units, and refrigeration machines, toopen water sprays for humidification, and to energize anddeenergize electric strip heaters.

    In two-position control, two values of the controlled variable(usually equated with on and off) determine the position of thefinal control element. Between these values is a zone called thedifferential gap or differential in which the controller cannotinitiate an action of the final control element. As the controlledvariable reaches one of the two values, the final control elementassumes the position that corresponds to the demands of thecontroller, and remains there until the controlled variablechanges to the other value. The final control element moves tothe other position and remains there until the controlled variablereturns to the other limit.

    An example of differential gap would be in a cooling systemin which the controller is set to open a cooling valve when thespace temperature reaches 26C, and to close the valve whenthe temperature drops to 25C. The difference between the twotemperatures (1C or 1 Kelvin) is the differential gap. Thecontrolled variable fluctuates between the two temperatures.

    Basic two-position control works well for many applications.For close temperature control, however, the cycling must beaccelerated or timed.

    Basic Two-Position Control

    In basic two-position control, the controller and the finalcontrol element interact without modification from a mechanicalor thermal source. The result is cyclical operation of thecontrolled equipment and a condition in which the controlledvariable cycles back and forth between two values (the on andoff points) and is influenced by the lag in the system. Thecontroller cannot change the position of the final control elementuntil the controlled variable reaches one or the other of the twolimits of the differential. For that reason, the differential is theminimum possible swing of the controlled variable. Figure 21shows a typical heating system cycling pattern.

    Fig. 21. Typical Operation of Basic Two-Position Control.

    The overshoot and undershoot conditions shown in Figure21 are caused by the lag in the system. When the heating systemis energized, it builds up heat which moves into the space towarm the air, the contents of the space, and the thermostat. Bythe time the thermostat temperature reaches the off point (e.g.,22C), the room air is already warmer than that temperature.When the thermostat shuts off the heat, the heating systemdissipates its stored heat to heat the space even more, causingovershoot. Undershoot is the same process in reverse.

    In basic two-position control, the presence of lag causes thecontroller to correct a condition that has already passed ratherthan one that is taking place or is about to take place. Consequently,basic two-position control is best used in systems with minimaltotal system lag (including transfer, measuring, and final controlelement lags) and where close control is not required.

    ANALOG CONTROL SIGNAL

    DIGITAL CONTROL SIGNAL

    OPEN

    FINALCONTROLELEMENTPOSITION

    CLOSED

    OPEN

    FINALCONTROLELEMENTPOSITION

    CLOSED

    TIME

    TIME C2080

    TEMPERATURE(C)

    OFF

    ON

    23.5

    23

    22.5

    22

    21.5

    21

    20.5

    20

    TIME

    UNDERSHOOTCONDTION

    DIFFERENTIAL

    DIAL SETTING

    OVERSHOOT CONDTION

    C3972

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    18

    Figure 22 shows a sample control loop for basic two-positioncontrol: a thermostat turning a furnace burner on or off inresponse to space temperature. Because the thermostat cannotcatch up with fluctuations in temperature, overshoot andundershoot enable the temperature to vary, sometimesconsiderably. Certain industrial processes and auxiliaryprocesses in air conditioning have small system lags and canuse two-position control satisfactorily.

    Fig. 22. Basic Two-Position Control Loop.

    Timed Two-Position Control

    GENERAL

    The ideal method of controlling the temperature in a space isto replace lost heat or displace gained heat in exactly the amountneeded. With basic two-position control, such exact operationis impossible because the heating or cooling system is eitherfull on or full off and the delivery at any specific instant iseither too much or too little. Timed two-position control,however, anticipates requirements and delivers measuredquantities of heating or cooling on a percentage on-time basisto reduce control point fluctuations. The timing is accomplishedby a heat anticipator in electric controls and by a timer inelectronic and digital controls.

    In timed two-position control, the basic interaction betweenthe controller and the final control element is the same as forbasic two-position control. However, the controller respondsto gradual changes in the average value of the controlled variablerather than to cyclical fluctuations.

    Overshoot and undershoot are reduced or eliminated becausethe heat anticipation or time proportioning feature results in afaster cycling rate of the mechanical equipment. The result iscloser control of the variable than is possible in basic two-position control (Fig. 23).

    Fig. 23. Comparison of Basic Two-Positionand Timed Two-Position Control.

    HEAT ANTICIPATION

    In electromechanical control, timed two-position control canbe achieved by adding a heat anticipator to a bimetal sensingelement. In a heating system, the heat anticipator is connectedso that it energizes whenever the bimetal element calls for heat.On a drop in temperature, the sensing element acts to turn onboth the heating system and the heat anticipator. The heatanticipator heats the bimetal element to its off point early anddeenergizes the heating system and the heat anticipator. As theambient temperature falls, the time required for the bimetalelement to heat to the off point increases, and the cooling timedecreases. Thus, the heat anticipator automatically changes theratio of on time to off time as a function of ambient temperature.

    THERMOSTATFURNACE

    SOLENOIDGAS VALVE

    C2715

    22

    21.5

    22.5

    21

    20.5

    23

    23.5

    20

    CONTROLPOINT

    TIME C3973

    TIMED TWO-POSITION CONTROL

    22

    21.5

    22.5

    21

    20.5

    23

    23.5

    20

    OFF

    ON

    TEMPERATURE(C)

    DIFFERENTIAL

    DIAL SETTING

    UNDERSHOOTCONDITION

    TIME

    OVERSHOOTCONDITION

    BASIC TWO-POSITION CONTROL

    TEMPERATURE(C)

    OFF

    ON

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    19

    Because the heat is supplied to the sensor only, the heatanticipation feature lowers the control point as the heat requirementincreases. The lowered control point, called droop, maintains alower temperature at design conditions and is discussed morethoroughly in the following paragraphs. Energizing the heaterduring thermostat off periods accomplishes anticipating action incooling thermostats. In either case, the percentage on-time variesin proportion to the system load.

    TIME PROPORTIONING

    Time proportioning control provides more effective two-position control than heat anticipation control and is availablewith some electromechanical thermostats and in electronic andmicroprocessor-based controllers. Heat is introduced into thespace using on/off cycles based on the actual heat load on thebuilding and programmable time cycle settings. This methodreduces large temperature swings caused by a large total lagand achieves a more even flow of heat.

    In electromechanical thermostats, the cycle rate is adjustableby adjusting the heater. In electronic and digital systems, thetotal cycle time and the minimum on and off times of thecontroller are programmable. The total cycle time setting isdetermined primarily by the lag of the system under control. Ifthe total cycle time setting is changed (e.g., from 10 minutes to20 minutes), the resulting on/off times change accordingly (e.g.,from 7.5 minutes on/2.5 minutes off to 15 minutes on/5 minutesoff), but their ratio stays the same for a given load.

    The cycle time in Figure 24 is set at ten minutes. At a 50percent load condition, the controller, operating at setpoint,produces a 5 minute on/5 minute off cycle. At a 75 percentload condition, the on time increases to 7.5 minutes, the offtime decreases to 2.5 minutes, and the opposite cycle ratiooccurs at 25 percent load. All load conditions maintain the preset10-minute total cycle.

    10

    7.5

    5

    2.5

    0

    SELECTEDCYCLE TIME(MINUTES)

    100 75 50 25 0LOAD (%)

    ON

    OFF

    C2090

    Fig. 24. Time Proportioning Control.

    Because the controller responds to average temperature orhumidity, it does not wait for a cyclic change in the controlledvariable before signaling corrective action. Thus control systemlags have no significant effect.

    Droop in heating control is a lowering of the control point asthe load on the system increases. In cooling control, droop is araising of the control point. In digital control systems, droop isadjustable and can be set as low as one degree or even less.Figure 25 shows the relationship of droop to load.

    Fig. 25. Relationship between Control Point,Droop, and Load (Heating Control).

    Time proportioning control of two-position loads isrecommended for applications such as single-zone systems thatrequire two-position control of heating and/or cooling (e.g., agas-fired rooftop unit with direct-expansion cooling). Timeproportioning control is also recommended for electric heatcontrol, particularly for baseboard electric heat. With timeproportioning control, care must be used to avoid cycling thecontrolled equipment more frequently than recommended bythe equipment manufacturer.

    STEP CONTROL

    Step controllers operate switches or relays in sequence toenable or disable multiple outputs, or stages, of two-positiondevices such as electric heaters or reciprocating refrigerationcompressors. Step control uses an analog signal to attempt toobtain an analog output from equipment that is typically eitheron or off. Figures 26 and 27 show that the stages may bearranged to operate with or without overlap of the operating(on/off) differentials. In either case, the typical two-positiondifferentials still exist but the total output is proportioned.

    Fig. 26. Electric Heat Stages.

    22.5

    22

    21.5

    0

    0.1

    1

    DR

    OO

    P (C

    )

    CONT

    ROL

    POIN

    T (C

    )

    DESIGNTEMPERATURE

    OUTDOOR AIRTEMPERATURE

    0% 100%LOADC3974

    NO LOADTEMPERATURE

    23

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    ONOFF

    5

    4

    3

    2

    1

    DIFFERENTIAL

    THROTTLING RANGE

    22SPACE TEMPERATURE (C)

    100%0% LOADC3981

    STAGES

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    20

    Fig. 27. Staged Reciprocating Chiller Control.

    Figure 28 shows step control of sequenced DX coils and electricheat. On a rise in temperature through the throttling range at thethermostat, the heating stages sequence off. On a further rise aftera deadband, the cooling stages turn on in sequence.

    ACTUATOR

    AIRFLOW

    DAMPER

    REFERENCEPRESSURE

    PICK-UP

    STATICPRESSURE

    PICK-UP

    FLOATINGSTATIC

    PRESSURECONTROLLER

    C2717

    full on, the modulating stage returns to zero, and the sequencerepeats until all stages required to meet the load condition are on.On a decrease in load, the process reverses.

    With microprocessor controls, step control is usually donewith multiple, digital, on-off outputs since software allowseasily adjustable on-to-off per stage and interstage differentialsas well as no-load and time delayed startup and minimum onand off adjustments.

    FLOATING CONTROL

    Floating control is a variation of two-position control and isoften called three-position control. Floating control is not acommon control mode, but is available in most microprocessor-based control systems.

    Floating control requires a slow-moving actuator and a fast-responding sensor selected according to the rate of response inthe controlled system. If the actuator should move too slowly,the controlled system would not be able to keep pace withsudden changes; if the actuator should move too quickly, two-position control would result.

    Floating control keeps the control point near the setpoint atany load level, and can only be used on systems with minimallag between the controlled medium and the control sensor.Floating control is used primarily for discharge control systemswhere the sensor is immediately downstream from the coil,damper, or device that it controls. An example of floating controlis the regulation of static pressure in a duct (Fig. 29).

    SPACE ORRETURN AIR

    THERMOSTATACTUATOR

    SOLENOIDVALVES

    FAN

    DISCHARGEAIR

    DIRECT EXPANSIONCOILS

    MULTISTAGEELECTRIC HEAT

    STEPCONTROLLER

    STAGE NUMBERS6

    5

    4

    3

    2

    1

    C2716

    D

    X

    D

    X

    Fig. 28. Step Control with SequencedDX Coils and Electric Heat.

    A variation of step control used to control electric heat isstep-plus-proportional control, which provides a smoothtransition between stages. This control mode requires one ofthe stages to be a proportional modulating output and the others,two-position. For most efficient operation, the proportionalmodulating stage should have at least the same capacity as onetwo-position stage.

    Starting from no load, as the load on the equipment increases,the modulating stage proportions its load until it reaches full output.Then, the first two-position stage comes full on and the modulatingstage drops to zero output and begins to proportion its outputagain to match the increasing load. When the modulating stageagain reaches full output, the second two-position stage comes

    Fig. 29. Floating Static Pressure Control.

    In a typical application, the control point moves in and outof the deadband, crossing the switch differential (Fig. 30). Adrop in static pressure below the controller setpoint causes theactuator to drive the damper toward open. The narrowdifferential of the controller stops the actuator after it has moveda short distance. The damper remains in this position until thestatic pressure further decreases, causing the actuator to drivethe damper further open. On a rise in static pressure above thesetpoint, the reverse occurs. Thus, the control point can floatbetween open and closed limits and the actuator does not move.When the control point moves out of the deadband, thecontroller moves the actuator toward open or closed until thecontrol point moves into the deadband again.

    ONOFF

    ONOFF

    ONOFF

    ONOFF4

    3

    2

    1

    DIFFERENTIAL

    THROTTLING RANGE

    24

    SPACE TEMPERATURE (C)

    22

    100%0% LOADC3982

    STAGES

    23SETPOINT

  • ENGINEERING MANUAL OF AUTOMATIC CONTROL

    CONTROL FUNDAMENTALS

    21

    Fig. 30. Floating Control.

    VALVE

    CONTROLLER

    SENSOR

    CHILLEDWATER

    RETURNAIR

    DISCHARGEAIR

    COIL C2718

    PROPORTIONAL CONTROL

    General

    Proportional control proportions the output capacity of theequipment (e.