MiCOM
P543, P544,P545, P546
Current Differential Relay
Software Versions 41 and 51
Hardware Suffix K
Technical Manual
P54x EN M J74
8/18/2019 Manual Covers and Contents Page
2/24
Note: The technical manual for this device gives instructions for its installation, commissioning, andoperation. However, the manual cannot cover all conceivable circumstances or include detailed
information on all topics. In the event of questions or specific problems, do not take any actionwithout proper authorization. Contact the appropriate AREVA technical sales office and requestthe necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of AREVAincluding settlements of warranties, result solely from the applicable purchase contract, which isnot affected by the contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission of AREVA, it will invalidate the warranty, and may render the product unsafe.
The AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registeredor not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
© 2006, AREVA. All rights reserved.
8/18/2019 Manual Covers and Contents Page
3/24
8/18/2019 Manual Covers and Contents Page
4/24
8/18/2019 Manual Covers and Contents Page
5/24
CONTENTS
Safety Section P54x/EN SS/D11
Update Documentation P54x/EN AD/xxx
Section 1 Introduction P54x/EN IT/G74
Section 2 Technical Data P54x/EN TD/J74
Section 3 Getting Started P54x/EN GS/B74
Section 4 Settings P54x/EN ST/B74
Section 5 Operation P54x/EN OP/B74
Section 6 Appl ication Notes P54x/EN AP/J74
Section 7 Programmable Logic P54x/EN PL/B74
Section 8 Measurements and Recording P54x/EN MR/B74
Section 9 Firmware Design P54x/EN FD/I74
Section 10 Commission ing P54x/EN CM/I74
Section 11 Maintenance P54x/EN MT/I74
Section 12 Troubleshooting P54x/EN TS/G74
Section 13 SCADA Communications P54x/EN SC/I74
Section 14 Symbols and Glossary P54x/EN SG/B74
Section 15 Installat ion P54x/EN IN/G74
Section 16 Firmware and Service Manual Version History P54x/EN VH/I74
Index
SS
N/A
IT
TD
GS
ST
OP
AP
PL
MR
FD
CM
MT
TS
SC
SG
IN
VH
Index
8/18/2019 Manual Covers and Contents Page
6/24
8/18/2019 Manual Covers and Contents Page
7/24
Documentation Update P54x/EN M/I74
MiCOM P543, P544, P545, P546 Page 1 of 6
DOCUMENTATION UPDATE FROM VERSIONS 0040 AND 0050K TO 0041 AND0051K
Since versions 0400 and 0050K (P54x/EN M/I64), several changes on existing features have been
amended or added. These are described below:
Document Ref. Section Page No. Description
- - -
EC declaration of conformity
Latest version to reflect relay software
P54x/EN IT/G74
1. 3
MiCOM documentation structure
Paragraph 1 : amended
3. 6
Product Scope
P543 and P545 features description :updated
P544 and P546 features description :updated
6
Functional overview
Row 2 of table : feature description amended
Data in row 3 of table : added
3.1 9 - 10
ANSI code 78 : added to table
Functional diagram : updated
P54x/EN TD/J74
- 3
High break contacts
Data added
- 6
Out of step
Data added
- 8
Fault locator
Data added : after disturbance records
- 9
InterMiCOM64 fiber optic teleprotection
Paragraph 2 : amended
Table : re-written
- 15 - 16
Througout
0.10…500.00/In Ω changed to
0.05…500.00/In Ω
- 16
Aided scheme 1
Send on trip data added
- 19
Out of step
Data added
8/18/2019 Manual Covers and Contents Page
8/24
P54x/EN M/I74 Documentation Update
Page 2 of 6 MiCOM P543, P544, P545, P546
Document Ref. Section Page No. Description
P54x/EN TD/J74
Continued - 19
Supervision
VTS mode data added
P54x/EN ST/B74
1.1 4
Relay settings configuration
ANSI code 78 : added to PowerSwing Blockdescription
10
Line parameters
Line impedance minimum setting : changed
from 0.1/I Ω to 0.05/In Ω
1.3.1 12 - 13
Fault resistance minimum setting : changed
from 0.1/I Ω to 0.05/In Ω
16 - 19
Distance elements (only for models withdistance option)
Throughout section : minimum setting
changed from 0.1/I Ω to 0.05/In Ω
17 R3 Ph. Res Rev. : description amended
1.3.3 18 R3 Gnd. Res Rev. : description amended
1.3.5 23
Scheme logic (basic and aided schemelogic). Only in models with distanceoption
AIDED SCHEME 1 : Send on trip dataadded
1.3.6 27 - 28
Power swing blocking
OST Mode, Z5, Z6, Z5’, Z6’, R5, R6, R5’,R6’, Blinder Angle, Delta t and Tost : dataadded
1.3.16 39
Circuit breaker fail and undercurrentfunction
Ι< Current Set : description amended
1.3.17 40
Supervision (VTS, CTS, Inrush detectionand special weak infeed blocking)
VT SUPERVISION : VTS mode data added
1.3.18 42
System checks (check sync. function)
CS1 Phase angle minimum setting : changedfrom 5˚ to 0˚
CS2 Phase angle minimum setting : changedfrom 5˚ to 0˚
8/18/2019 Manual Covers and Contents Page
9/24
Documentation Update P54x/EN M/I74
MiCOM P543, P544, P545, P546 Page 3 of 6
Document Ref. Section Page No. Description
P54x/EN ST/B74
Continued
1.3.19 42
Auto-reclose function
1 Pole dead time minimum setting : changed
from 0.2s to 0.05sDead time 1 minimum setting : changed from0.2s to 0.05s
1.4.1 48
System data
Software Ref. 1 and Software Ref. 2 :software version updated
1.4.7.3 56
Communications settings for DNP3.0protocol
Last 2 lines of table : added
1.4.7.4 56
Communications settings for Ethernetport
NIC Link Timeout : description amended
P54x/EN OP/B74
1.1.6 21 - 22
Mesh corner and 1½ breaker switchedsubstations
Relay calculations after Figure 10 : amended
1.2 22
Disabling/enabling differential protection
New section added
1.3 23
Differential relay compatibility withprevious versions
Paragraph 1 : re-written
Last paragraph : added
1.5.3 24
Pole dead logic
Paragraph 1 : re-written
1.20 44
Out of step detection and tripping
New section added
1.20.1 44
Out of step detection
New section added
1.20.1.1 44 - 45
Characteristic
New section added
1.20.1.2 45 - 46
Operating principle
New section added
1.23.2 58
Distance scheme POR - permissiveoverreach transfer trip
Figure 37 : updated
8/18/2019 Manual Covers and Contents Page
10/24
P54x/EN M/I74 Documentation Update
Page 4 of 6 MiCOM P543, P544, P545, P546
Document Ref. Section Page No. Description
P54x/EN OP/B74
Continued 2.1.3.1 86
Trip initiate signals
Paragraph re-written
Auto-reclose logic diagrams
Figure 66 : updated
2.1.8 92 Figure 67 : updated
2.4 105
Voltage transformer supervision - fuse fail
Paragraph 6 : added
Paragraph 7 : re-written
2.5.1 108
Differential CTS (no need of local voltage
measurements to declare CTS)
Paragraph before figure 79 : added
P54x/EN AP/J74
2.2.16 20 - 21
Out of step protection
New section added
2.2.17 21 - 22
Critical stability angle
New section added
2.2.17.1 22 - 23
Setting option recommendation
New section added
2.2.17.2 23 - 25
Blinder limits determination
New section added
2.2.17.3 25
Delta t, R5 and R6 setting determination
New section added
2.2.17.4 26
Tost (trip delay) setting
New section added
2.2.17.5 26
Blinder angle setting
New section added
2.2.17.6 26 - 27
Out of step operation on seriescompensated lines
New section added
2.2.23 28
General setting guidelines for DEF(directional ground overcurrent)
Setting data changed from : between 5 and20% In to between 10 and 20% In
8/18/2019 Manual Covers and Contents Page
11/24
Documentation Update P54x/EN M/I74
MiCOM P543, P544, P545, P546 Page 5 of 6
Document Ref. Section Page No. Description
P54x/EN PL/B74
21
Description of logic nodes
DDB number 437 : data added
25 DDB numbers 550 - 555 : data added
26 DDB numbers 556 to 575 : data added
31
DDB numbers 807 to 831 : changed to 807to 828
DDB numbers 829 - 831 : data added
1.7 39 - 40 DDB numbers 1375 - 1385 : data added
1.8 41
Factory default programmable schemelogic
Data in table : updated
Note after table : added
1.10 44
Standard relay output contact mappings
Heading changed
1.11 47 - 49
Optional high break relay output contactmappings
New section added
P54x/EN FD/I74
1.1.5 5
IRIG-B modulated or demodulated board(optional)
Heading changed
2.2 8
Co-processor board
1st sentence : re-written
2.5.3 11 - 12
High break relay board
New section added
2.5.3.1 12 - 13
High break contact applications
New section added
2.8 14
Ethernet board
Last paragraph : added
Figure 5 : added
P54x/EN CM/I74
6.2.7 43 - 44
Out of step protection (if enabled)
New section added
6.2.7.1 44
Predictive OST setting
New section added
6.2.7.2 45
OST setting
New section added
8/18/2019 Manual Covers and Contents Page
12/24
P54x/EN M/I74 Documentation Update
Page 6 of 6 MiCOM P543, P544, P545, P546
Document Ref. Section Page No. Description
P54x/EN CM/I74
Continued 6.2.7.3 45
Predictive and OST setting
New section added
6.2.7.4 45
‘Tost’ timer test
New section added
10. 58 - 72
Commissioning test record
Amended to reflect latest relay software
11. 73 - 104
Setting record
Amended to reflect latest relay software
P54x/EN IN/G74
8.
12 - 19
20 - 27
P54x external connection diagrams
Figures 5 - 12 : descriptions updated
Figures 13 - 20 : added
P54x/EN VH/I74
- -
Firmware and service manual versionhistory
Amended to reflect latest relay software
8/18/2019 Manual Covers and Contents Page
13/24
Index
INDEX
A
Access level
(GS) 3-9, 11, 13, 15
(ST) 4-49, 53
(MR) 8-12
(CM) 10-13, 57, 79
Advanced setting mode
(ST) 4-12
(OP) 5-33
(AP) 6-14
Aided scheme
(ST) 4-4, 21, 23 - 25, 32 - 33
(OP) 5-23, 49, 51 - 52, 65 - 66, 74, 85, 90
(AP) 6-28, 39, 50
(CM) 10-35, 42 - 43, 45- 48, 56, 68
Aided tripping logic
(OP) 5-51, 54
Alarms
(GS) 3-4, 9, 11, 13
(ST) 4-49, 52
(FD) 9-17
Auto-reclose
(GS) 3-3
(ST) 4-5, 9, 25, 34, 44, 46, 50, 57 - 58, 60
(OP) 5-23, 46, 49, 65, 74, 85 - 99, 103 - 104,
109 - 110, 118
(AP) 6-27, 37, 49, 58 - 61(CM) 10-8, 10, 50, 68, 75, 100
Auto-reclose mode
(OP) 5-87, 90
Auxiliary supply
(OP) 5-109, 124
(AP) 6-54, 56, 64
(CM) 10-15, 18 - 21, 28 - 31, 33, 59, 63 - 64
(MT) 11-5 - 6
(IN) 15-7
B
Basic scheme
(ST) 4-21 - 23
(OP) 5-40 - 41, 65, 67
(AP) 6-19 - 20, 30
(CM) 10-56
Battery
(GS) 3-4, 6
(ST) 4-51, 61
(OP) 5-109, 124
(FD) 9-5, 8, 10, 17, 20 - 22
(CM) 10-19 - 21, 28, 30 - 31, 33, 42, 46, 74
(MT) 11-5 - 6
(IN) 15-4 - 5Binary inputs (see Opto inputs)
Broken conductor
(ST) 4-4, 30
(OP) 5-83, 108(AP) 6-36 - 37, 60
(CM) 10-74, 94
C
Capacitive charging current
(ST) 4-19, 21
(OP) 5-16, 18
(AP) 6-9 - 11
(CM) 10-55
Case dimensions
(IN) 15-9 - 10CB healthy
(ST) 4-45, 50
(OP) 5-85, 87 - 88, 117
(AP) 6-58, 60
(CM) 10-74, 100
Change of state
(MR) 8-4
Channel aided scheme
(OP) 5-23, 51
(AP) 6-28
Check synchronization
(ST) 4-9, 42, 46Slip frequency
(ST) 4-42 - 43
(OP) 5-98 - 101
Synchronism
(ST) 4-46
(OP) 5-87 - 89, 91, 98 - 100, 103, 117
(AP) 6-22, 59
System checks
(ST) 4-5, 42, 46
(OP) 5-91, 98 - 101, 103
(CM) 10-75, 99, 101
System split(ST) 4-43 - 44
(OP) 5-99 - 102
Circuit breaker condition monitoring
(ST) 4-59
(OP) 5-113 - 115
(AP) 6-61
Circuit breaker control
(ST) 4-44, 47 - 50
(OP) 5-116, 119 - 120
Circuit breaker fail
(ST) 4-5, 38 - 39
(OP) 5-80(AP) 6-36
Circuit breaker state monitoring
(OP) 5-109 - 110
Cleaning
(MT) 11-6
8/18/2019 Manual Covers and Contents Page
14/24
ndex
Clock source
(ST) 4-7
(OP) 5-132 - 134, 143
(AP) 6-38
(CM) 10-84
Commissioning tests
(ST) 4-5, 57
(OP) 5-30, 37, 86
(CM) 10-7 - 8, 38, 51, 70
(IN) 15-4
Commissioning test record
(CM) 10-58
Monitor bits
(CM) 10-9, 47
Communications
(GS) 3-5, 9, 16, 18 - 19
(ST) 4-5 - 6, 7 - 8, 40 - 41, 47, 49, 54 - 57, 62
(CM) 10-9, 14, 20, 22 - 27, 29 - 32, 35, 45, 48, 50,
52 - 53, 62 - 63, 69, 79
(MT) 11-3
(SC) 13-5 - 8, 10 - 12, 19 - 21, 24, 26 - 29
Communications interface
(FD) 9-11
(SC) 13-5
Courier
(GS) 3-7, 14 - 16
(CM) 10-7 - 9, 22 - 24, 62, 79
(SC) 13-5, 7 - 8, 10 - 12, 14 - 17, 19 - 20
DNP3.0 communication
(SC) 13-9, 21
DNP3.0 interface
(SC) 13-21
EIA(RS)485 interface
(FD) 9-11
(SC) 13-5
Ethernet
(GS) 3-5
(ST) 4-48, 56
(SC) 13-11, 24, 26, 29
(IN) 15-8
Ethernet board
(FD) 9-5, 14, 22
Ethernet port
(IN) 15-8
Fiber optic converter
(SC) 13-10, 14
GOOSE
(ST) 4-64
(SC) 13-26, 28 - 29
GOOSE input
(PL) 7-12
GOOSE output
(PL) 7-12
IEC 61850(GS) 3-5, 7
(ST) 4-48, 56, 64
(SC) 13-24 - 29
IRIG-B
(ST) 4-51, 56
(CM) 10-19 - 20, 74
(IN) 15-8
IRIG-B board
(FD) 9-5, 13, 22
Jabber
(SC) 13-6
K-BUS
(CM) 10-14, 22 - 23
(SC) 13-5, 7 - 8, 11 - 12, 14
Rear port
(GS) 3-7, 19
(ST) 4-6, 48, 54 - 55, 57
(MR) 8-5, 8
(FD) 9-5
(CM) 10-24
(SC) 13-5, 7 - 13, 16 - 17
SCADA
(CM) 10-22 - 23
(SC) 13-5, 7
Second rear communications
(FD) 9-13
(CM) 10-23 - 24
(SC) 13-11
Configuration
(GS) 3-4, 6, 8 - 9, 13, 15
(ST) 4-3, 5 - 10, 20, 26 - 27, 32 - 33, 47, 61 - 63, 65
Connection diagrams
(CM) 10-21
(IN) 15-12
Contacts (see also Output relays)
(GS) 3-5
(ST) 4-20, 37, 50, 57 - 58, 66
(FD) 9-5, 11 - 13, 15, 19, 22
(CM) 10-8 - 10, 16, 18 - 20, 22, 35 - 37, 39 - 40, 47, 59
Contact test
(ST) 4-58
(CM) 10-8, 10, 22, 47 - 48
Control inputs
(GS) 3-4, 12
(ST) 4-5, 61 - 62
(OP) 5-123 - 124(CM) 10-18, 75
(SC) 13-22
Courier (see Communications)
CT ratio
(ST) 4-20
(OP) 5-17 - 18
(AP) 6-11 - 12, 17, 30 - 31, 41, 43 - 44, 47
(CM) 10-25 - 26, 54, 58, 65, 73
CT ratio correction
(OP) 5-17 - 18
(AP) 6-11 - 12
Current reversal guard
(ST) 4-17, 19, 23
(OP) 5-56, 60 - 62
(AP) 6-29
8/18/2019 Manual Covers and Contents Page
15/24
Index
Current transformer supervision
(ST) 4-19, 21, 40
(OP) 5-23, 106 - 107
(AP) 6-60
Current transformers
(OP) 5-17, 127
Current transformer requirements
(AP) 6-62
D
Date and time
(GS) 3-11
(ST) 4-51, 53
(MR) 8-12
(CM) 10-19 - 20, 59, 74
(MT) 11-6
(SC) 13-19
Dead time
(ST) 4-44 - 46
(OP) 5-85 - 88, 91
(AP) 6-27, 49, 58 - 60
(CM) 10-100 - 101
Default display
(GS) 3-3 - 4, 9, 11, 13 - 14
(ST) 4-53
(MR) 8-12
(CM) 10-79
Default mappings
(GS) 3-5
Default programmable scheme logic(PL) 7-40
De-ionizing time
(AP) 6-59
Delta directional
(ST) 4-16, 59
(OP) 5-29, 33, 35, 37 - 38
(AP) 6-18
(CM) 10-11
Differential CTS
(OP) 5-23, 107 - 108
(AP) 6-60 - 61
Differential protection
(FD) 9-5, 18
Digital filtering
(AP) 6-18
Dimensions
(IN) 15-5, 9 - 10
Direct trip
(OP) 5-140
(AP) 6-36
Directional earth fault
(ST) 4-4, 32 - 33, 45
(OP) 5-11, 74 - 75
(AP) 6-7, 14, 31 - 32
(CM) 10-45
Directional function
(ST) 4-32
Directional overcurrent protection
(ST) 4-29
(OP) 5-70, 74
Discrimination timer
(OP) 5-91
Disposal
(MT) 11-6
Distance polarizing
(OP) 5-49
(CM) 10-88
Distance protection
(FD) 9-8, 18
Distance setup
(ST) 4-11 - 12, 17 - 18
(OP) 5-49
(AP) 6-18
(CM) 10-39 - 40, 87
Disturbance recorder(GS) 3-7 - 8, 14
(ST) 4-3, 5, 65 - 66
(MR) 8-6, 8 - 9
(FD) 9-7, 17 - 18, 20
Disturbance records
(GS) 3-4, 7, 16
(ST) 4-55
(MR) 8-8 - 9
(FD) 9-13, 20 - 21
(CM) 10-57, 71
DNP3.0 communication (see Communications)
Documentation structure
(IT) 1-3
E
Earth connection
(IN) 15-8
Earth fault protection (Ground fault)
(ST) 4-4, 33, 45
(OP) 5-50, 73 - 74, 90
(AP) 6-14, 31 - 32, 36, 50
EIA(RS)485 interface (see Communications)
Environmental conditions (EMC) (see Technical data)
Error code
(TS) 12-3 - 6
Error message
(TS) 12-4, 6
ESD
(MR) 8-7
Ethernet (see Communications)
Event records
(GS) 3-9, 15
(ST) 4-49
(MR) 8-3, 6
(FD) 9-17
(SC) 13-17
Event filtering
(MR) 8-7
8/18/2019 Manual Covers and Contents Page
16/24
ndex
Excessive fault frequency
(ST) 4-60
(OP) 5-91
(AP) 6-61
F
Factory default PSL (see Programmable scheme logic)
Failure of opto-isolated inputs
(TS) 12-7
Failure of output contacts
(TS) 12-7
Fault locator
(ST) 4-9 - 10
(FD) 9-20
(CM) 10-55
Fault record
(GS) 3-4, 7, 9, 11, 13(ST) 4-47, 49, 52, 65
(OP) 5-124 - 125, 127
(MR) 8-3, 5 - 9
(FD) 9-17, 20
(SC) 13-16 - 17
Fiber optic converter (see Communications)
Field voltage supply
(FD) 9-21
(CM) 10-21
Filtering
(OP) 5-16, 19 - 20, 39, 124
(MR) 8-7
(FD) 9-7, 10, 18 - 19
Fixed demand
(ST) 4-53
(MR) 8-11 - 13
Force 3 pole trip
(OP) 5-97
Fourier filtering
(FD) 9-19
Front panel user interface
(GS) 3-7, 9 - 10, 13
(ST) 4-53
(MR) 8-12(CM) 10-15
Front view
(GS) 3-3
Function keys
(GS) 3-3 - 4
(ST) 4-62
(OP) 5-109, 121 - 122
(FD) 9-5
Function key properties
(PL) 7-13
G
Gate properties
(PL) 7-16
Getting started
(GS) 3-3
GOOSE (see Communications)
GOOSE input (see Communications)
GOOSE output (see Communications)
GPS
(ST) 4-8
(OP) 5-13 - 16, 23, 129, 131, 145 - 147(CM) 10-33 - 34, 84 - 85
Ground distance
(ST) 4-13, 17
(OP) 5-26, 34 - 35
(AP) 6-15, 50, 53
Ground fault protection (see Earth fault)
H
Handling of electronic equipment
(IN) 15-3
Hardware overview
(FD) 9-5
Hardware suffix
(VH) 16-1
High break
(FD) 9-11 - 13
Hotkeys
(ST) 4-5, 49, 65
(OP) 5-116, 121
Hotkey menu navigation
(GS) 3-11 - 12
I
IEC curve
(OP) 5-69
IEC 60870-5-103 (see Communications)
IEC 61850 (see Communications)
IEEE C37.94
(CM) 10-32
IMx command type
(AP) 6-38
IMx fallback mode
(OP) 5-142
(AP) 6-39
Initial problem identification
(TS) 12-3
Input labels
(ST) 4-5, 47, 64
(CM) 10-75, 101
Input signal properties
(PL) 7-12
Inrush detection
(ST) 4-39, 41
(OP) 5-109(CM) 10-99
Insulation resistance tests
(CM) 10-17 - 18, 27 - 29, 31, 33
Interface units
(CM) 10-26 - 27, 29, 31, 33, 52 - 53
8/18/2019 Manual Covers and Contents Page
17/24
Index
InterMiCOM64
(ST) 4-4, 6 - 7, 9
(OP) 5-139 - 143
(AP) 6-38 - 39
(PL) 7-38
(CM) 10-11, 19, 26 - 30, 32, 47, 75
IRIG-B (see Communications)
IRIG-B board (see Communications)
J
Jabber (see Communications)
K
K-BUS (see Communications)
L
Language
(IT) 1-10
(GS) 3-4, 8, 14
(ST) 4-47 - 48
(SC) 13-11
LCD contrast
(GS) 3-4
(ST) 4-6
(CM) 10-19, 59, 75
Line parameters
(ST) 4-10, 12, 23
(OP) 5-23
(AP) 6-14
(CM) 10-40 - 41, 87
Load avoidance
(OP) 5-39
(AP) 6-18, 49 - 50
Load blinder
(ST) 4-15
(OP) 5-32, 35, 39 - 40, 42, 46
(AP) 6-15, 19, 24
(CM) 10-40, 66, 88
Local contact list
(TS) 12-11
Logic gates
(SG) 14-9
Logic symbols
(SG) 14-1
Logic timers
(SG) 14-7
Loopback mode
(CM) 10-8, 11, 27, 29 - 30, 32, 35 - 36, 52
Loss of load
(ST) 4-25 - 26
(OP) 5-64, 66 - 68(AP) 6-30
M
Maintenance checks
(MT) 11-3
Maintenance period
(MT) 11-3
Method of repair
(MT) 11-4
Maintenance reports
(MR) 8-5 - 6
Measurements
(GS) 3-7, 16
(ST) 4-53
(OP) 5-17, 22, 36, 81, 107, 144
(AP) 6-28, 31, 33, 37, 53
(MR) 8-3, 5, 10 - 15
(FD) 9-7, 17 - 18
(CM) 10-15, 25 - 28, 30, 32, 34, 53 - 56, 70
Menu navigation
(GS) 3-10 - 12
Menu structure
(GS) 3-3, 7 - 9, 11
Mesh corner
(OP) 5-21
(AP) 6-13
Mho expansion
(ST) 4-15
(OP) 5-31
MiCOM S1
(GS) 3-14, 16 - 17, 20 - 21(PL) 7-7 - 8
Monitor bits (see Commissioning tests)
Mounting
(TD) 2-1
(IN) 15-5 - 6
MOV
(AP) 6-26 - 27
Multiplexer link
(OP) 5-132 - 133
Mutual compensation
(ST) 4-10 - 11
(OP) 5-26, 38, 124, 126 - 127
(AP) 6-14
Mutual cutoff
(OP) 5-27
N
Negative sequence overcurrent
(ST) 4-4, 30
(OP) 5-76
(AP) 6-32
Neutral voltage displacement (see also residual voltage)
(ST) 4-35
(AP) 6-34, 53
8/18/2019 Manual Covers and Contents Page
18/24
ndex
O
Offset Mho
(OP) 5-32
Offset quadrilateral
(OP) 5-33
Oil circuit breakers
(AP) 6-61
On-load checks
(CM) 10-47, 54, 70
Open delta
(AP) 6-14, 53
Optical budgets
(OP) 5-128, 132, 145
(AP) 6-37
Optical fiber
(OP) 5-128 - 129, 131 - 133
(AP) 6-38(CM) 10-26 - 28, 30, 32, 34, 52 - 53, 70
Opto inputs
(GS) 3-6
(ST) 4-37, 47 - 48, 61, 66
(OP) 5-21, 59, 77, 90, 122, 124
(AP) 6-54 - 56
(MR) 8-4, 9
(FD) 9-10
(CM) 10-21
Opto signal properties
(PL) 7-11
OST
(OP) 5-44, 46
(AP) 6-21 - 23, 25 - 27
Predictive OST
(OP) 5-44, 46
(AP) 6-21 - 23, 25 - 26
Out of service LED
(CM) 10-20
(TS) 12-3, 5, 7
Out of step
(ST) 4-4, 26 - 27
(OP) 5-43 - 46, 140
(AP) 6-20, 22 - 27
(CM) 10-43 - 44, 67
Output relays
(ST) 4-47, 49, 57 - 58
(FD) 9-7, 10
(CM) 10-9 - 10, 21 - 22, 48, 50, 60
(MT) 11-3
Output contacts
(TD) 2-1 - 2, 12
Output labels
(ST) 4-5, 47
(CM) 10-75, 102
Output relay board
(FD) 9-11
Output signal properties
(PL) 7-12
Overvoltage protection
(ST) 4-4, 36
(OP) 5-77 - 80
(AP) 6-33, 35
P
Panel mounting
(IT) 1-10
(IN) 15-6
Password entry
(GS) 3-9, 13
Password protection
(GS) 3-9, 13
(CM) 10-15
Permissive intertrip
(OP) 5-143
Permissive scheme
(OP) 5-58 - 59, 63, 66, 139
(AP) 6-29, 38
(CM) 10-41 - 42, 46, 67 - 68
Phase correction
(OP) 5-19
(AP) 6-12, 42, 45
Phase differential
(ST) 4-19 - 20
(OP) 5-11, 143
(AP) 6-9
(CM) 10-55
Phase overcurrent protection
(ST) 4-4, 30
(OP) 5-68
IDMT
(OP) 5-68 - 69, 71, 77 - 79
Time dial
(ST) 4-20, 29, 31, 34
(OP) 5-69
Time multiplier setting
(ST) 4-20, 28 - 29, 31, 35, 37 - 38
(OP) 5-69, 77 - 79
Phase rotation
(ST) 4-10 - 11
(OP) 5-23
(CM) 10-14, 18, 54, 58, 70, 87
Phase selection
(OP) 5-28 - 30, 42, 125 - 126
Pole dead
(ST) 4-24, 37, 39, 44, 46, 52
(OP) 5-23 - 26, 49, 77, 81, 86 - 88, 104 - 105
(AP) 6-59
Pole discrepancy
(OP) 5-66, 85 - 86, 98
POR (see also aided scheme or permissive scheme)
(ST) 4-23
(OP) 5-17, 55 - 58, 62(AP) 6-29, 46, 48, 51
(CM) 10-41 - 42
Power supply
(TD) 2-1 - 2, 4
8/18/2019 Manual Covers and Contents Page
19/24
Index
Power supply board
(FD) 9-5, 10 - 11
Power swing
(ST) 4-4, 15, 26 - 27
(OP) 5-42 - 44, 46
(AP) 6-7, 8, 18, 20, 22, 59
(CM) 10-11, 97
Power swing blocking
(ST) 4-4, 26 - 27
(OP) 5-43 - 44
(AP) 6-8
Power swing detection
(ST) 4-26 - 27
(OP) 5-42 - 43, 46
(CM) 10-11
Power up errors
(TS) 12-3
Product scope
(IT) 1-6
Programmable scheme logic (PSL)
(GS) 3-3, 7
(ST) 4-6, 9, 41, 50, 62 - 64
(AP) 6-19, 51, 53
(PL) 7-7, 12, 40, 52, 63, 75, 85, 97, 109, 122, 133
(MR) 8-5
(FD) 9-19
PSL editor
(PL) 7-7 - 8
PSL editor troubleshooting
(TS) 12-9
PUR (see also aided scheme or permissive scheme)
(ST) 4-23
Q
Quadrilateral element
(OP) 5-28, 32
Quadrilateral ground resistive reach
(OP) 5-35
(AP) 6-17
Quadrilateral phase resistive reach
(OP) 5-35(AP) 6-17
R
Rack mounting
(IN) 15-5
Ratings
(TD) 2-2
(GS) 3-6
(AP) 6-12, 64
(CM) 10-7, 22, 48
(MT) 11-3 - 5
Rear port (see Communications)
Rear view
(GS) 3-6
Reactance line
(ST) 4-16 - 17
(OP) 5-32 - 34, 38, 45
(AP) 6-17, 25
Re-calibration
(MT) 11-5
Receive logic
(OP) 5-51, 53, 62
Reclaim time
(ST) 4-45
(OP) 5-85, 87 - 88, 90 - 91
(AP) 6-60 - 61
(CM) 10-100
Record control
(ST) 4-5, 52
(OP) 5-124
(MR) 8-6 - 7
Records
(GS) 3-4, 7, 9, 13, 15 - 17
(ST) 4-49, 55
(OP) 5-113, 127
(MR) 8-3, 5 - 9
(CM) 10-7, 13, 52, 57, 71
Relay alarm conditions
(MR) 8-4
Remote control
(OP) 5-117
(SC) 13-5
Repair and modification authorization form (RMA)
(TS) 12-10
Repair and modification procedure
(TS) 12-10
Reset characteristic
(ST) 4-29, 31, 34
(OP) 5-69
Residual compensation
(ST) 4-10, 12, 18 - 19, 25
(OP) 5-26 - 28, 31 - 32, 34, 45, 65
(AP) 6-14, 47
Residual overvoltage
(ST) 4-4, 35 - 36
(OP) 5-79 - 80
(AP) 6-34 - 35, 53
Residual voltage
(ST) 4-35
(OP) 5-50 - 51, 74 - 75, 79
(AP) 6-28, 31 - 32, 34 - 35, 53, 60
Restore defaults
(ST) 4-3, 6
(SC) 13-22
Right hand resistive reach
(OP) 5-35
Rolling demand
(ST) 4-53(MR) 8-10, 12
8/18/2019 Manual Covers and Contents Page
20/24
ndex
S
SCADA (see Communications)
Second rear communications (see Communications)
Self testing & diagnostics
(FD) 9-21Self-check
(CM) 10-7
Send logic
(OP) 5-51, 53, 55 - 56, 58, 60, 62 - 64
(AP) 6-28 - 30
Sensitive earth fault (SEF)
(ST) 4-4, 33 - 34, 39, 46, 51
(OP) 5-73
(AP) 6-31, 36
Sequence components
(ST) 4-11
(OP) 5-23, 124Sequence counter
(OP) 5-88
Sequence voltages and currents
(MR) 8-10
Setting changes
(GS) 3-8, 11, 13 - 14
(ST) 4-52
(MR) 8-6 - 7
(FD) 9-17
Setting groups
(GS) 3-4, 12
(OP) 5-107, 122(MR) 8-6
(CM) 10-73
Setting record
(CM) 10-7, 13 - 15, 50, 73
Simple setting mode
(OP) 5-33
(AP) 6-48
SIR setting
(ST) 4-15
(CM) 10-88
SK5 port
(SC) 13-30
Slip frequency (see Check synchronization)
Software overview
(FD) 9-6
Software version
(ST) 4-48
(VH) 16-1, 31, 34 - 36
Standard CTS
(ST) 4-40
(OP) 5-107 - 108
(AP) 6-60
Static test mode
(OP) 5-30, 37
(CM) 10-10 - 11, 38, 43
Storage
(TD) 2-3
(CM) 10-19
(IN) 15-3 - 4
Stub bus
(OP) 5-22
Supervision
(ST) 4-5, 19, 21, 28 - 32, 34, 39, 40
(OP) 5-23, 71, 74, 76, 104, 106 - 108
(AP) 6-19, 53 - 56, 60
(FD) 9-17
(CM) 10-38, 43, 47, 50, 75, 99
Synchronism (see Check synchronization)
Synchronous polarization
(OP) 5-71
System checks (see Check synchronization)
System data
(GS) 3-9, 13(ST) 4-48
(OP) 5-117, 121
(CM) 10-7, 21, 25, 73
System split (see Check synchronization)
T
Technical data
(TD) 2-1
(CM) 10-7
Type tests
(TD) 2-3Teed feeder protection
(AP) 6-50
Teleprotection
(ST) 4-6 - 7
(OP) 5-139 - 142
(AP) 6-38
Terminals
(TD) 2-1 - 4
(ST) 4-20
(OP) 5-12, 84, 133 - 134
(AP) 6-50 - 53
(IN) 15-7 - 8Test mode
(ST) 4-57 - 59, 64
(OP) 5-30, 37, 113
(CM) 10-8 - 11, 20 - 22, 27 - 30, 32, 38, 43, 47 - 48,50, 57, 84
Test pattern
(ST) 4-58 - 59, 64
(CM) 10-8, 10 - 11, 22, 27 - 30, 32, 84
Test port
(ST) 4-57 - 58
(FD) 9-8
(CM) 10-8 - 9, 36 - 37, 47 - 48
Thermal overload
(ST) 4-4, 36
(OP) 5-71 - 73
(AP) 6-30
8/18/2019 Manual Covers and Contents Page
21/24
Index
Tilt
(ST) 4-16 - 17
(OP) 5-34, 38, 45
(AP) 6-17
(CM) 10-88 - 89
Time alignment
(ST) 4-8
(OP) 5-13 - 14, 16, 130
Timer properties
(PL) 7-15
Toggle
(ST) 4-62 - 63
(OP) 5-109
Trip circuit supervision (TCS)
(AP) 6-53
Troubleshooting
(MT) 11-4
Type tests (see Technical data)
U
Undercurrent
(ST) 4-26, 37 - 39
(OP) 5-77, 80 - 81
(AP) 6-36
Undervoltage protection
(ST) 4-37
(OP) 5-77 - 78
(AP) 6-33
Universal opto isolated logic inputs (see Opto inputs)User interfaces
(GS) 3-3, 7
(FD) 9-5, 7 - 8, 17
Unpacking
(IN) 15-4
V
Virtual inputs
(PL) 7-12
(SC) 13-28
Virtual outputs
(PL) 7-12
Visual inspection
(CM) 10-15, 27, 29, 31, 33, 59, 62, 64, 66 - 67
Voltage protection
(ST) 4-4, 36 - 37, 39
(OP) 5-77 - 80
(AP) 6-33, 35, 53
(CM) 10-98
VT connections
(AP) 6-53
VT ratio
(ST) 4-5, 47, 51
(OP) 5-23, 99, 104
(AP) 6-41, 44, 47
(CM) 10-25 - 26, 54 - 55, 58, 65, 73, 75
VT supervision
(ST) 4-29 - 30, 32, 34
W
Watchdog contacts
(FD) 9-11
(CM) 10-18 - 19, 59
(MT) 11-4
Weak infeed
(ST) 4-23 - 24, 39, 41
(OP) 5-39, 56, 58 - 59, 81, 84
(AP) 6-17, 29
(CM) 10-92, 99
Weight
(TD) 2-1
Wiring
(GS) 3-6
(CM) 10-7, 15, 17 - 18, 27 - 29, 31, 33, 52 - 54, 57, 59,63 - 64, 70
(MT) 11-3 - 4
(SC) 13-7
(IN) 15-5, 7
Z
Zone 1 extension
(ST) 4-25
(OP) 5-27, 59, 64 - 65
(AP) 6-47
(CM) 10-41 - 42, 67
Zone reaches
(ST) 4-10, 12
(OP) 5-37
(AP) 6-16
8/18/2019 Manual Covers and Contents Page
22/24
ndex
8/18/2019 Manual Covers and Contents Page
23/24
8/18/2019 Manual Covers and Contents Page
24/24
P u b l i c a t i o n :
P 5 4 x / E N M / J 7 4