CR110 MANUALPro Refrigeration, Inc
ii | ProRefrigeration,Inc
TableofContents
1 Preface ill
Disclaimer ... . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . . ill
Manufacture.Information .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... ... ill
Customer.Service... . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . . ill
2 QuickStart 1
CR110.Controller.Overview.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1
Quick.Start.Guide... .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 2
3 CR110Operation 6
CR110.Basic.Controls. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 6
Modes.Of.Operation .. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 7
Temperature.Control.(PI.Loop) ... . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 9
4 CR110Wiring 10
Basic.System.Wiring.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 10
Sensor.Wiring.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 11
CR110.Communications.Wiring.. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 11
5 Troubleshooting 12
Default.CR110.Parameters... .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 12
CR110.Troubleshooting. ... . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 13
Replacement.Parts. ... . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 15
www.prochiller.com | iii
1 Preface
ThismanualisintendedtobeusedinconjunctionwithProRefrigeration’sCR110RefrigerationController.
Thismanualwillguideyouthroughtheprocessofinstalling,configuringandtroubleshootingyourCR110RefrigerationController.
Manufactured By:ProRefrigeration,Inc.
ProRefrigerationislocatedinAuburnWA.Auburnislocated30milesfromSeattle,WAintheshadowofMt.Rainier.
Physical Address:3268thSTSWAuburn,WA98001
www.prochiller.com
Mailing Address: POBOX1528Auburn,WA98071-1528
Telephone: 253-735-9466Fax: 253-735-2631
Customer ServicePleasefeelfreetocontactcustomerservicewithanyquestionspertainingtothisoranyotherProRefrigera-tion,Incproduct.
Customer Support Hours: Monday-Friday 7am-5pm (Pacific Standard Time)
Telephone: 253-735-9466Fax: 253-735-2631Email:[email protected]
Note: CheckthefollowingURLforthelatestversionofthismanualandotherProRefrigera-tion,Incproductdocumentation.http://www.prochiller.com/support
www.prochiller.com | 1
CR110 OVERVIEW
J1:Connectto24VACorDCPowerSource.
S2 Control Switch: Thisswitchcon-trolsthepowerandfunctionoftheCR110card.
LED’s CR1-CR9:CR110outputlights.SeeCR110OutputStatusLED’sforfurtherinformation
Sensors 1-8:0-5VInputSensors.SeeSensorWiringforfurtherinformation.
{
J13: ThisistheCR110’sprimarycommunicationport.
AUX: TheAUXportcanbeusedasanadditionalcommunicationport.
J7 (Analog Output): I->C=4-20mAV->C=0-10V
J20: PortJ20isusedwhenprogram-mingtheCR110EEPROMchip.
J3:01-04 & J8:05-08: 120Voltanalogoutputs.Seebasicsystemwiringforfurtherinformation
{
C Ports: Outputpowercomingfromexternalprotectioncomponents.
120/240: Outputpowercomingfromneutral.
Fuses K1-K8:2AMP130VACoutputfuses.Seereplacementpartssectionforpartnumber.
EEPROM Chip: ThechipisloadedwithlatestversionofCR110controllersoftwareatfactory.
LED’s CR10-CR13:CR110modelights.SeeModesOfOp-erationforfurtherinformation
8-PIN CR110 Communica-tion Chip
Power Surge Suppressor
Commutation Surge Suppressor
14-PIN J7 Analog Output Control Chip
LED CR14:CR14isacommunica-tionindicatorLED.ThelightwillblinkwhenitrespondstoanRS-485Communicationsrequest.
2 | ProRefrigeration,Inc
CR110 Quick Start
STEP 1VerifythatthemainpowertothesystemisOFF.ThiscanbeaccomplishedbyconfirmingthatthedisconnecthandleisintheOFFposition
STEP 2OpentheelectricalpanelandlocatetheCompressorCircuitBreakers
Basic Operation & Features
Thetypicalchillerapplicationcanconsistofonetofourcompressors,eachcompressorcontrolledbyadedicatedCR110ControlCard.TheTPCtouchscreenInter-faceprovidesalocaldisplayandoperatorinterface.TheTPCisnotneededforsystemoperationitsimplymonitors,recordsandprovidesanoperatorinterface.
AllaspectsoftheCR-110operationisbasedonpro-vidingthemostefficientoperationpossible.TheCR-110,looksatthedifferencebetweenthecoldesttemperaturesensorandtheSet-point.ItusesaPIlooptocalculateanoutputsignalfrom0to100per-cent.ThissignalisthenusedbymultipleCR-110’stostagetheliquidlinesolenoidvalveandunloaders.Theresultisaverysmoothandprecisetemperaturecon-trolwithoutshortcyclingthecompressors.Withtheeliminationofmultiplededicatedsetpointscontrollingmultiplecoolingstages,theCR110deliversaflexiblesetupwithmuchtightertemperaturevariationandcontrol.
Onamultiplecompressorsystem,eachcompres-sorutilizestwotemperaturesensorstodetectboththeChilledWaterSupplyTemperatureandChilledWaterReturnTemperature.Thisprovidesacompletefullredundantsystem.Bydefaultthecontrollerwillalternateleadcompressorsafter24hours(adjustable)ofcompressorruntime.
EachCR-110monitorsthecompressorsuctionpres-sure,suctiontemperature,anddischargepressure.Anyfailureofsensorsorexceedingtemperatureandpressurespecificationswillresultinanalarm.Analarmmodewillresultinanautomaticleadchangetothenextcom-pressorandorbackupcompressor.
www.prochiller.com | 3
STEP 6OntheCR110Card,locatetheOFF-RUN-PDtoggleswitch
STEP 7VerifythatthetoggleswitchisintheOFFposition
STEP 8TurnthemainpowertothesystemONbymovingthedisconnecthandletotheONposition
STEP 9Usingavolt-meterverifythatthemainpowervoltagematchesthatofthesystemvoltage
STEP 3SwitchthecompressorcircuitbreakerstotheOFFposition
STEP 4LocatetheCR110Cards
STEP 5RemovethecoverfromtheCR110Cards
4 | ProRefrigeration,Inc
STEP 10TurnthePROCESSPUMPswitchtotheONposi-tion.
STEP 11TurntheSTAGEswitchestotheONposition.
STEP 12TurntheCONTROLLERswitchtotheONposition.
STEP 13TurntheCONTROLLERswitchtotheONposition.
STEP 14Verifythatthetemperaturesandsystempressuresdis-playedonthecontrollerinterfacepanelareaccurate.
STEP 15Adjustthesystemsetpointto5ºFhigherthenthecurrentdisplayedtemperature.Pleasereferenceyourdisplaymanualforinstructionsonchangingsetpoint.
STEP 16Verifythatthegaugepressuresareapproximatelythesame(+-3-5psi)asthoseobservedonthecontrollerinterfacepanel.
STEP 17Performsteps12–15fortheremainingCR110Cards.
www.prochiller.com | 5
STEP 18TurntheCR110CardstoggleswitchtotheOFFposi-tion.
STEP 19Resetthelowoilpressurecontrolsforeachcompressor.
.
STEP 20SwitchthecompressorcircuitbreakerstotheONposi-tion.
STEP 21PlaceeachCR-110cardintheRUNmodebyswitch-ingtheOFF-RUN-PDtoggleswitchtotheRUNposition
STEP 22Torestoreyoursystemtonormal,readjustthesystemsetpointtotheappropriatesettingandverifyeachstageisrespondingaccordingly.
TheCR110CardisnowintheRUNMODEandshouldoperateonitsownfromthispointforwardac-
cordingtocoolingdemandandsystemsetpoint.
� | ProRefrigeration,Inc
CR110 Basic Controls
S2 Control SwitchInkeepingwiththebasicconceptofsimplicity,theactualactivecontrolsontheCR-110islimitedtooneswitch.ThisswitchislabeledS2,andislocatedintheupperrighthandcornerofthecircuitboard,andisshowninthepicturebelow.Thisisamulti-functionswitch,whichhasthreepositions.
•Pump Down: Iftheswitchisintheupposition,itwillcausethecompressortogointopumpdownmode.Itshouldpumpdownandshutoff.Thispositionislabeled‘PD’onthecircuitboard.
•Off: Centerpositionisoff.Thisshutsoffpowertothecircuitboardandeffectivelyshutsdownthesystem.Alsoplacingtheswitchintheoffpositionresetsanyalarmconditionswhichmayexist.
•Run: DownpositionisRUN.Thisenablesthesystemtoruninanormalmode,andcontroltherefrigerationsystemaccordingtotheprofilethemicroprocessorisusing.
•Test Mode: ToenterTestMode,movetheswitchfromOFFtoRUNthenrapidlytoPD.ThiswillcausetheCR-110togointoaspecial‘TestMode’fortrou-bleshootingandinitialsetupoptions.
www.prochiller.com | �
Shutdown ShutdownmodeoccurswhentheS2ControlSwitchontheCR110isplacedinthePumpDownposition,oriftheunitisremotelyswitchedoff.InShutdown,thecompressorwillpumpdownifneeded.AremoteShut-downcanbeover-riddenbyswitchingtheS2switchonthecontrollertoOffthenbacktoRun.
Coil Dry CoilDrymodeisactivatedafterahotgasdefrost.Immediatelyafterthedefrostcycle,theliquidlinesolenoidisopenedforapre-settime,withtheevapo-ratorfansoff.Thiswillcauseanymoistureleftintheevaporatorcoiltodry.ThesettingfortheCoildryisinseconds,andisnormallysetfrom30to60seconds.Ifthisvalueissettozero,thecoildryfeaturewillbedisabled.
High Head HighHeadAlarmisactivatedwhenthedischargepressureexceedsapre-setvalue.Thisistypicallyset25to50psilessthanthemechanicalhighpressureswitch.Thisalarmisactivatedinstantaneously.WhenaHighHeadAlarmoccurs,alloutputswillshutoffandthecontrollerwilllockoutofanyothermode.ThealarmcanberesetbyusingtheS2switchonthecontrollertopowertheunitoffandthenbacktotherunpositionorthroughtherestbuttononyourdisplay.
DP Sensor Fail DPSensorFailmodeisafailureofthedischargepres-suresensor.Thisisacriticalsensor,andwillshutdownalloutputsimmediatelyifafailureisdetected.Thefailurecouldbecausedbyanumberofthings;brokenwire,sensorplugorthesensoritself.
SP Sensor Fail SPSensorFailmodeisafailureofthesuctionpressuresensor.Thisisacriticalsensor,andwillshutdownalloutputsimmediatelyifafailureisdetected.Thefailurecouldbecausedbyanumberofthings;brokenwire,sensorplugorthesensoritself.
Modes Of OperationTheCR110has16differentmodesofoperation.TheyarelistedbelowwithdetailandtheircorrespondingLEDindication.TheLED’sreferencedbelowarefromlefttorightCR10,CR11,CR12,andCR13
Standby: StandbyoccurswhenSet-pointismet.InStandby,thecompressorshouldbepumpeddownandreadytostarttherefrigerationcycle.
Refrigeration: RefrigerationmodeoccurswhentheCoolingDemandreachesthepre-settemperature.ThiswilloccurwhenthePIloopadjuststheoutputabovetheLiquidLineSolenoidOnpercentage.Inthismode,theliquidlinesolenoidisopenedandthecompressorwillstartassoonasthesuctionpressurerisestotheCompressorOnparameter.
Defrost: Defrostmodeoccurswhenadefrostcyclehasbeeninitiated.Thisinitiationcanoccurfromanumberofsources,demanddefrost,timeddefrostormanualinitiateddefrost.Thedefrostmodeappliestohotgas,electric,orairdefrost.
Pump Down: PumpDownmodeoccurswhentheRefrigerationmodehasended,orthesuctionpressurerisesabovetheturnonpointinthestandbymode.Inthepumpdownmode,theliquidlinevalveisclosedandthecompressorpumpsdowntothesuctionshutoffpoint.
Short Cycle: ShortCyclemodeisasafeguardthatpreventsthecompressorfromshuttingdownandthenrestartexces-sively.Typicallytheshortcycletimerissetforamini-mumofoneminute.
� | ProRefrigeration,Inc
Fan / Pump Failure Fan/PumpFailureindicatesafailureorshutdownoftheevaporatorfancircuitorcirculationpump,nofeed-backfromtheprovingcircuit.
Program ErrorIfalltheredLED’Sareon,andthegreenLEDison,thisindicatesaProgramErrorandwillpreventnor-maloperation.Iftheflashmemoryhasbeenrepro-grammed,thisconditionwillexist,andtheoperatingprofilewillhavetobeloaded.
Normal OperationNormalOperationisindicatedbyablinkinggreenLEDonCR2.
RS-485 CommunicationsTheLEDlocatedonCR14willblinkwhenitrespondstoaRS-485communicationsrequesttransmittedoverJ13orAUX.
CR110 Output Status LEDsTheCR110has9120voltanalogoutputs.TheyarelistedbelowwiththeircorrespondingLEDindication.
CR1 CondenserFan1
CR3 CondenserFan2
CR4 CondenserFan3
CR5 LiquidLineSolenoid/CoolingDemand
CR6 CirculationPump(Pump off when light is on)
CR7 Compressor
CR8 Unloader1/EvaporatorFan
CR9 Unloader2/Defrost
Low Suction Alarm LowSuctionAlarmmodeisactiveonlyintheRefrig-erationmode.Ithasbothapsivalueforthesuctionpressureaswellasanalarmtimerassociatedwithit.Ifthetimerissettozero,thealarmwillbedisabled.Thelowsuctionalarmpointshouldbesetsomewhereabovethelowoperatorshutoffpoint.Thisisaveryvaluablealarmandshouldbesetaccordingly.UsePTtablesforfreezepoints.
External Alarm ExternalAlarmmodecanbeactivatedbyanumberofexternaldevices.Oilpressure,highheadpressure,phasemonitorandcompressorprotectionmodulesaresomeoftheexternaldevicesthatcanbeusedtosu-pervisetheCR-110controller.ThesedevicesprovidepowertotheJ8-05terminalonthecontroller.Ifanyoneofthesedevicestrip,alloutputswillshutoffandthe3LED’Swillstarttoblink.After5minutestheLED’Swillcomeonsteadyandlockoutinanalarmcondition.Iftheexternalalarmisresetbeforethe5minutesisup,thennormaloperationwillberesumed.
Super Heat TheSuperHeatwindowhasahighandlowsetting,andatimedelay.TheCR-110calculatesthecompres-sorSuctionSuperHeatcontinuously,andcomparesthissettingtothealarmparameters.Mostcompressormanufacturersrecommendthesuctionsuperheatrunbetween20to40degreesF.TheSuperHeatwindowisactiveanytimethecompressorisrunning.Settingthetimedelaytozerowilldisablethisalarm.
Temperature Sensor TheTemperatureSensorFailureAlarmisactivatedwhenacontrollingtemperaturesensorisfoundoutofrange.ExamplewouldbetheRoomSensorwhenrun-ningintheSet-pointmode.
Note: Output4whenusedinachillerap-plicationisnormallyoff.Thisisforfailsafeconditions.Whenoutput4isoff,thecircula-tionpumpshouldberunning.Whenoutput4ison,thepumpisintheoffconditiontosavepower.
www.prochiller.com | �
Temperature Control
TheCR110RefrigerationControllerutilizesaPIloopthatoperatesbycomparingthechilledwaterinletsetpointandthecoldestsensor.
EverytimeaPILoopMathCalculationisperformedtheresultisanewOUTPUT.ThesystemusesthisOUTPUTtocontrolthefollowingitems:
• Liquid Line Solenoid Valve On/Off
Liquid Line Solenoid Valve is ON 1.SuctionPressureIncreases 2.CompressorStarts Liquid Line Solenoid Valve is OFF 1.SuctionPressureDecrease 2.CompressorStops
• Unloader Valve On/Off LLS ON% Reached: 1.CoolingDemandisHigh 2.CylinderLoads LLS OFF% Reached: 1.CoolingDemandisLow 2.CylinderUnloads
EachCR110RefrigerationControllercardissuppliedwithit’sowndedicatedsensorsproviding100%redun-dancy.
PI Loop ExplainedThePILoopformulaisshownbelowwithdefinations,detailsandexamples.
NEWOUTPUT=OLDOUTPUT+P+I
• P (Default is 22):+ Pispositivewhenthecoldestsensorreads abovesetpoint.- Pisnegativewhenthecoldestsensorreadsbelow setpoint.
• I (Default is 5):+ Iispsoitivewhenthecoldestsensortempera- tureisincreasing.- Iisnegativewhenthecoldestsensortempera- tureisdecreasing.
Example 1: Old Output = 5% Set Point = 28 F Inlet = 27 F Oulet = 29 F Inlet Temperature Increasing NewOutput=5+(-22)+5 =22
Example 2: Old Output = 30% Set Point = 28 F Inlet = 29 F Oulet = 30 F Inlet Temperature Decreasing NewOutput=30+22+(-5) =47
10 | ProRefrigeration,Inc
External ProtectionTherearethreedevicesthatcanremove120VpowertotheCR110cardshuttingdownthesystemandsendingthecontrollerintoanExternalAlarmtheyareshownbelow.Basic System Wiring
Thissectionshowsanoverviewofthetypicalsystem’sinstallationwiring.ThefollowingassumesanAir-CooledProChilleroperatingCR110V2.84orgrater.Belowaresomewiringexamples.Forexactwiringforyoursystempleaserefertoyoursystemselectricalschematics.
CR110 Power WiringMultiplecardsmaybepoweredfromasingletrans-former.Thecontrolpowermustbecommonforeachofthecards.Eachcardrequiresroughly6VAofpower.
Outputs 1-4CF1:CondenserFan1 CF2:CondenserFan2
CF3:CondenserFan3 CP:CirculationPump
Compressor ControlC1:Coompressor1 LL1:LiquidLineSolenoid1
UL1:Unloader1 UL2:Unloader2
Note: Output’s7&8whenusedforUnloadersoperatewithreverselogicforfailsafeoperation.Whentheoutputsarenotlittheunloadershavethecompressorcylindersloaded.
120VA
Card1 Card2
J124VDCJ124VDC
0102
03
04
CF1CF2
CF3CP
Neutral
0506
07
08
C1LL1
UL1UL2
Neutral
CC
240
120
L1
HighPressureSwitch
CompressorProtectionModule
OilSafetySwitch
Neutral
www.prochiller.com | 11
Sensor WiringAlltemperatureandpressuresensors,andcurrentswitchesuseacommon5VDC.
Input Sensor Description•0-500PSIDischargePressureTransducer.
•0-100PSISuctionPressureTransducer.
•CompressorSuctionTemperatureSensor.
•ProcessTemperatureorOutsideAmbientAirTem-peratureSensor(OPTIONALITEM)
•0-100PSIOilPressureTransducer(OPTIONALITEM)
•CirculationPump/EvaporatorFanProvingCurrentSensor
•EvaporatorGlycolInletTemperatureSensor(Canbelocatedinstoragereservoir)
•EvaporatorGlycolOutletTemperatureSensor(Canbelocatedinstoragereservoir)
CR110 Communications WiringTheinter-cardcommunicationsisdoneona2-wireRS-485busswithshield.Therearesimply3wiresthatrunbetweenallcards,connectingtheminparal-lel.Thecommunicationsbaudrateis9600.Belowaresomewiringexamples.Forexactwiringforyoursystempleaserefertoyoursystemselectricalschematics.
Typical Non-RGX Communication Wiring
Typical Wiring With RGX Communications
Note:•OutsideAmbientAirTemperatureSensormustbeusedforlowambientcontroloption.•OilPressureTransducercanbeusedtomeasurenetoilpressure.
To Controller HMI (Refer To Interface Manual)
To Controller HMI (Refer To Interface Manual)
0-100psi 0-500psi 0.5-4.5 VDC
2250 Ohm Thermistor
12 | ProRefrigeration,Inc
CR110 Default ParametersBelowisachartthatcontainsthedefaultCR110parametersforProChillerSystemswithonetofourcompressors.Fordirec-tionsonsettingtheseparameterspleaseseetheprogrammingsectionofyourinterfacemanual.
www.prochiller.com | 13
CR110 Troubleshooting
14 | ProRefrigeration,Inc
CR1
CR3
CR4
CR5
CR6
CR7
CR8
CR9
www.prochiller.com | 15
Replacement PartsThefollowingisalistofreplacementpartsfortheCR110RefrigerationController.Callforpricingandavailabil-ity.
Description Part Number
CR110ControlCard CR110-B
SuctionPressureTransducer(0-100psi) P499RCP-101C
DischargePressureTransducer(0-500psi) P499RCP-105C
TransducerCable WHA-P399-400C
TemperatureSensor A4175-21
24VDCPowerSupply PS5R-SC24
CurrentSensorSwitch RIBXKTF
AlarmCable J20-CC-ALARM-36
PowerSurgeProtector(VR2) P6KE51CACT-ND
CommunicationSurgeProtector(VR4) P6KE6.8ACCCT-ND
CommunicationChip(U2) MAX483CPA
OutputFuses(K1-K8) Z909-ND
CR110 AccessoriesThefollowingisalistofaccessoriesfortheCR110.Callforpricingandavailability.
Description Part Number
G55GrayscaleInterface G55-BW
G55ColorInterface G55-CL
TS110TouchscreenInterface TS110
RGXCommunicationGateway(WebAccess) 105-1-755
5Port24VEthernetSwitch MOX-EDS-205