4
100-Ton Air-Cooled Portable Water Chillers RUGGED DEPENDABILITY ® ® 2730 Maximilian Dr, Houston, Texas 77032 • 281-227-8400 t • 1-800-473-9178 toll free • 281-227-8404 f www.waterchillers.com FEATURES Carlyle Semi-Hermetic Reciprocating Compressors with Electrical Multi-Stage Unloading Down to 33% Stainless Steel Braze Plate Brass Service Valves Large Copper Condensing Coil with Aluminum Fins Powder Coated, Heavy Guage Steel Cabinet Rugged Stainless Steel Centrifugal Pumps with Safety Fuses Oversized Magnetic Contactors Stainless Steel Tank BENEFITS Long Life - Dependable - Economical to Operate Compact Efficiency Easy Maintenance and Effecient Rugged Protection While Allowing for Easy Maintenance and Wash Down High Flow - Long Life - Dependable Rugged Dependability - Long Life Lifetime Warranty • Allows for Field Service Without Dissassembly

Marrone & Co - water chillers

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Marrone & Co - water chillers

100-Ton Air-Cooled Portable

Water Chillers

RUGGED

DEPEND

ABILITY

®®

2730 Maximilian Dr, Houston, Texas 77032 • 281-227-8400 t • 1-800-473-9178 toll free • 281-227-8404 f www.waterchillers.com

FEATURES• Carlyle Semi-Hermetic Reciprocating

Compressors with Electrical Multi-StageUnloading Down to 33%

• Stainless Steel Braze Plate

• Brass Service Valves

• Large Copper Condensing Coil withAluminum Fins

• Powder Coated, Heavy Guage Steel Cabinet

• Rugged Stainless Steel Centrifugal Pumpswith Safety Fuses

• Oversized Magnetic Contactors

• Stainless Steel Tank

BENEFITS• Long Life - Dependable - Economical to

Operate

• Compact Efficiency

• Easy Maintenance and Effecient

• Rugged

Protection

While

Allowing

for EasyMaintenance

and

Wash

Down

• High Flow - Long Life - Dependable

• Rugged Dependability - Long Life

• Lifetime Warranty

• Allows for Field Service Without Dissassembly

Page 2: Marrone & Co - water chillers

TECHNICAL SPECIFICATION

Marrone & Co., Inc. 2730 Maximilian Dr., Houston, Texas 77032 • Phone (800) 473-9178, (281) 227-8400

Fax (800) 473- 9175, (281) 227-8404 • www.waterchillers.com TechSpec_ACWC-1200-E-_-_-40-6_(0412).doc

Model: ACWC-1200-E-_-_-40-6

Description: 100-Ton air-cooled water chiller system to provide approximately 1,200,000 Btu/hr of cooling capacity with a leaving fluid temperature of 50°F with an ambient air temperature of 95°F. Suitable for outdoor use to 40°F ambient temperature.

CAPACITY ±5% AT 50° LCWT / 95°F AMBIENT

100-TON 1,200,000 BTU/HR

COMPRESSORS (4) CARRIER SEMI-HERMETIC RECIPROCATING EVAPORATOR STAINLESS STEEL / COPPER BRAZED FLUID CONNECTION (INLET/OULET) 4” 150# FLANGE FANS / CFM 6 / 52,000 CONDENSER COILS COPPER TUBE / ALUMINUM FIN VOLTAGE/PHASE/FREQ 460V / 3Ø / 60Hz MINIMUM CIRCUIT AMPS 192.7 DIMENSIONS (APPROX.) 23’ L x 7’8” W x 8’ H WEIGHT (APPROX.) 7,460 LBS PUMP HP 20 HP PUMP OUTPUT 335 gpm @ 70 psi TANK SIZE 700 GALLON TANK CONSTRUCTION INSULATED POLYETHYLENE

Note: All specifications subject to change without notice.

CONTROLS Eight Stage PLC temperature controller with constant leaving fluid read out. Totally enclosed motors and control box.

OPERATING TEMPERATURES Process fluid: 42°F to 70°F for standard units (20°F to 70°F for low temp units) Ambient air: 40°F to 115°F for standard units (0°F for outdoor units with low ambient modifications)

REFRIGERATION COMPONENTS Carrier semi-hermetic reciprocating compressors with mechanical unloading down to 33%, sight glass, moisture indicators, balance port expansion valves, liquid line solenoids, filter drier, pump down valves, stainless steel brazed plate evaporator, fan cycling head pressure controls.

PROCESS FLUID COMPONENTS Rugged centrifugal pump, insulated polyethylene reservoir. CPVC piping.

SAFETY CONTROLS High/low pressure safety, internal overloads, thermal overloads and/or safety fuses or circuit breakers for pump, compressor and fan motors, low water flow safety with manual reset, freeze, oil pressure.

CONSTRUCTION Galvanized frame, powder coated steel cabinet.

WARRANTY One year parts / five year compressor.

Page 3: Marrone & Co - water chillers

ENGINEERING

07/2011

INSTALLATION DRAWING

100-Ton Chiller – ACWC-1200-ESIZE FSCM NO DWG NO REV

A DWG-INST_ACWC-1200-E_(0711).vsd 1SCALE 1 : 40 SHEET 1

1. Unit must have clearances for air flow/service access as follows: (air must be directed away from machine to prevent re-circulating air back into machine coil sides.)

Top - 8' unobstructedCoil sides - 3'

2 All chilled fluid piping should be insulated.3. Unit can be divided into a separate condensing unitand a chiller section. Contact Cold Shot Chillers for details.

NOTES:

21'-0" 8'-0"

LEFT END VIEWSIDE VIEW

8'-0

"

Tank Level Sight Tube

INLET CONNECTION

OUTLET CONNECTION

TOP VIEW

IN / OUT Flanges

Compressors

Condenser Fans

Chiller Section(Tank, Pump,

Evaporators, etc)

Page 4: Marrone & Co - water chillers

STAINLESS STEEL/COPPER BRAZED

PLATE EVAPORATOR

COLD SHOT CHILLERSDRAWN ENGINEERING

ISSUED

SIZE FSCM NO DWG NO REV

ACHILL WATER CIRCUIT – TYPICAL

Model “E”: Large Portable, Two Evaporators, with Flow Switch” 1

05/2011 SCALE NTS DWG-CHW_AllFlowDesigns_0511d.vsd SHEET 6

CHILLERPUMP

WATER SUPPLY

(OUT)

WATER RETURN

(IN)

TEMPERATURE SENSOR

(Temperature Controller)

INSULATEDTANK

DRAIN

FS

FLOW SWITCH

STRAINER

BUTTERFLYVALVE

BUTTERFLYVALVE

BUTTERFLYVALVE

CustomerProcess