LOẠI 1:BTS 3012 có 2 cách đấu và khai báo cảnh báo ngoài.
1-Trường hợp BTS 3012 dùng card DEMU slot 2 subrack 0.
Phụ lục: DEMU và màu cáp eas.
LEDs and Port on the DEMU
This describes the LEDs and port on the DEMU panel. The three LEDs on the DEMU panel indicate the operating status of the DEMU. The port on the DEMU is used to import and export Boolean and analog signals.
Panel
Figure 1 shows the DEMU panel.
Figure 1 DEMU panel
LED
Table 1 lists the LEDs on the DEMU panel.
Table 1 LEDs on the DEMU panel
LED Color Description Status Meaning
RUN Green Operating indicator of the board
On There is power supply. However, the board or software is faulty.
Off There is no power supply or the board is faulty.
Blinking once every two seconds
The board is working under current configuration.
Blinking four times per second
The board communicates with the DTMU normally.
ALM Red Indicates whether there are alarms
Blinking once every two seconds
An alarm is generated.
Off No board alarm
ACT Green Service running indicator
On There is power supply and the board is in working mode.
Off There is no power supply for the board.
Port
Table 2 describes the port on the DEMU panel.
Table 2 Port on the DEMU panel
Port Type Cable Function
IN MD68 female connector
Boolean Signal Transfer Cable of the BTS3012
Exporting and importing Boolean signals
Importing analog signals
Signal Cable Between the NPMI and the DEMU of the BTS3012AE
Parent topic: DEMU
1-The BTS3012 can be configured with the following monitoring units: DEMU, EAC (EMU), DTMU, and DPMU.
List of BTS3012 User-Defined Alarm Ports
Table 1 Mapping between the monitoring unit and the monitoring signal cable
BTS Type
Monitoring Unit
Installation
Position
Port on the
Monitoring Unit
Port No.
Monitoring
Signal Cable
Wire or Connector
Wire ColorAlarm ID
Description
BTS3012
DEMUSlot 2 of
subrack 0
NA 1
BTS3012 Boolean
input cable
W1.36/W1.2
Blue/whiteAC FAILURE
6438
NA 2W1.37/W1.3
Orange/whiteDC FAILURE
6440
NA 3W1.38/W1.4
Green/whitERECT
6442
NA 4W1.39/W1.5
Brown/whiteBTS High temp
6444
NA 5W1.40/W1.6
Gray/white 6446
NA 6W1.41/W1.7
Blue/red 6448
NA 7W1.42/W1.8
Orange/red 6450
NA 8W1.43/W1.9
Green/red 6452
NA 9W1.44/W1.10
Brown/red 6454
2-Trường hợp 2: BTS 3012 hỏng DEMU thì dùng DSAC
DSAC
CO
M1
EA
CS
YN
CC
OM
2S
1+S
1-S
2+
S2-
Interface
Type Description
COM2 DB9 (female) CBUS3 extension 2
S2+S2– Phoenix socket Alarm input 2 of the power supply lightning arrester failure
S1+S1– Phoenix socket Alarm input 1 of the power supply lightning arrester failure
COM1 DB9 (female) CBUS3 extension 1
EAC DB26 (female) Six-route Boolean value input
SYNC SMA (female) Protection access of Bits clock input
Table 7 Pin assignment for the EAC signal cable
X1 End Wire Type Wire Color Alarm Output Serial Number
X1.1 Twisted pair White Alarm input 3 BOOLAEN 3
X1.10 Blue
X1.2 Twisted pair White Alarm input 4
X1.11 Orange
X1.3 Twisted pair AC
White Alarm input 5 BOOOLEAN 5
X1.12 Green
X1.4 Twisted pair DC Low
White Alarm input 6 BOOLEAN 6
X1.13 Brown
X1.5 Twisted pair Rect
White Alarm input 7 BOOLEAN 7
X1.14 Gray
X1.6 Twisted pair
BTS HIGH TEMP
Red Alarm input 8
Boolean 8X1.15 Blue
X1.7 Twisted pair Red Alarm output 4
X1.16 Green
X1.8 Twisted pair Red Alarm output 3
X1.25 Green
X1.18 Twisted pair Red Alarm output 1
X1.26 Brown
X1.9 Twisted pair Red Alarm output 2
Table 7 Pin assignment for the EAC signal cable
X1 End Wire Type Wire Color Alarm Output Serial Number
X1.17 Gray
LOẠI 2:BTS 3900 VÀ BDS3900.
1- Trường hợp 1: BTS 3900,BDS3900 Dùng card UEIU:
DÙNG CÁP RJ45 nối vào port exter 0 trên card UEIU :
Để đấu cáp mạng vào thiết bị mạng người ta sử dụng một đầu kết nối gọi là Đầu RJ-45 (RJ-45 Connector). Đầu RJ-45 có 8 chân, chân số 1 được tính từ bên trái sang khi đầu RJ-45 để ngửa mặt chân tiếp xúc lên, khe đưa cáp vào hướng vào người (Xem hình bên).
- Figure 1 Panel of the UEIU
EXT-ALM0 RJ45 Four dry contact signals
-
AC :TRẮNG –CAM :CHÂN 1-2 Cáp RJ 45
DC: TRẮNG- LỤC : CHÂN 3-6
RECT :TRẮNG –DƯƠNG: CHÂN 5-4
ĐÔI THỨ 4 :TRẮNG –Nâu :boolean 8 =BTS HIGH TEMP:Chân 7-8 ( loop lại nếu chưa dùng) ( Màu dây VÀ chân cáp RJ 45 XEM BẢN GỐC PHỤ LỤC tô màu đỏ)
2-Trường hợp 2: Nếu dùng card UPEU
exter 1 : Alarm Shield Flag2 : FO
Extended SW of input alarm =yes
Alarm Voltage Definition2 : F0
Boolean 16 =BTS HIGH TEMP ( loop lại nếu chưa dùng)
Figure 1 Panel of the UPEA
EXT-ALM1 RJ45 Four dry contact signals
AC :TRẮNG –CAM:Chân 1-2 cáp RJ 45
DC: TRẮNG- LỤC:CHÂN 3-6
RECT :TRẮNG –DƯƠNG:CHÂN 5-4
ĐÔI THỨ 4 :TRẮNG –Nâu :boolean 16 =BTS HIGH TEMP:CHÂN 7-8 ( loop lại nếu chưa dùng) (màu dây VÀ chân cáp RJ45 xem phụ lục gốc tô màu đỏ)
3-Trường hợp 3: BTS 3900 dùng card DEMU ở subrack 2 slot 1 của tủ BTS 3900.
Việc khai báo giống DEMU của BTS 3012 nhưng phần port đấu AC,DC LOW,RECT, BTS High temp xem bảng phụ lục Monitoring Unit DEMU.
Phụ Lục: Cáp màu dây dùng,Port dùng DEMU BTS 3900 , UEIU port RJ45 EXTER 0, UPEU port RJ45 EXTER 1.
List of BTS3900 Series User-Defined Alarm Ports
The BTS3900 series can be configured with the following monitoring units: EMUA, APMI, UPEU, UEIU, FMU, and DPMU.
List of BTS3900 Series User-Defined Alarm Ports
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
BTS3900,
BTS3900A, or
DBS3900
The physical hardware is EMUA, which is
displayed as DEMU
on the LMT.
S1+/S1-
Slot 0 or 1 of
subrack 21
AC
Sensor-equipped cable
AC FAILURE
NA NA 6292
S2+/S2-2
DC
Sensor-equipped cable
DC LOW
NA NA 6294
S3+/S3-
3
RECT
Sensor-equipped cable
RECT FAILURE
NA NA 6296
S4+/S4-
4
BTS HIGH TEMP
Sensor-equipped cable
BTS High Temp
NA NA 6298
S5+/S5- 5Sensor-equipped cable
NA NA 6300
S6+/S6- 6Sensor-equipped cable
NA NA 6302
S7+/S7- 7Sensor-equipped cable
NA NA 6304
S8+/S8- 8 Sensor-equipped
NA NA 6306
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
cable
S9+/S9- 9Sensor-equipped cable
NA NA 6308
S10+/S10-
10Sensor-equipped cable
NA NA 6310
S11+/S11-
11Sensor-equipped cable
NA NA 6312
S12+/S12-
12Sensor-equipped cable
NA NA 6314
S13+/S13-
13Sensor-equipped cable
NA NA 6316
S14+/S14-
14Sensor-equipped cable
NA NA 6318
S15+/S15-
15Sensor-equipped cable
NA NA 6320
S16+/S16-
16Sensor-equipped cable
NA NA 6322
S17+/S17-
17Sensor-equipped cable
NA NA 6324
S18+/ 18 Sensor- NA NA 6326
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
S18-equipped cable
S19+/S19-
19Sensor-equipped cable
NA NA 6328
S20+/S20-
20Sensor-equipped cable
NA NA 6330
S21+/S21-
21Sensor-equipped cable
NA NA 6332
S22+/S22-
22Sensor-equipped cable
NA NA 6334
S23+/S23-
23Sensor-equipped cable
NA NA 6336
S24+/S24-
24Sensor-equipped cable
NA NA 6338
S25+/S25-
25Sensor-equipped cable
NA NA 6340
S26+/S26-
26Sensor-equipped cable
NA NA 6342
S27+/S27-
27 Sensor-equipped cable
NA NA 6344
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
S28+/S28-
28Sensor-equipped cable
NA NA 6346
S29+/S29-
29Sensor-equipped cable
NA NA 6348
S30+/S30-
30Sensor-equipped cable
NA NA 6350
S31+/S31-
31Sensor-equipped cable
NA NA 6352
S32+/S32-
32Sensor-equipped cable
NA NA 6354
UPEU (The
Boolean alarms of the UPEU
are reported by the GTMU.
Therefore, you
should select the
GTMU when
setting the parameter
EXT-ALM1
The UPEU is configured in slot 18 or 19
of subrack
0, and the GTMU in slot 6 of subrack
0.
13
BBU Boolean alarm cable
X1.1/X1.2
Orange-white/orange
AC FAILURE
Boolean input 5+/Boolean input 5- (GND). Note: Each Boolean input is represented by one bit.
5056
14 X1.3/X1.6
Green-white/green
DC LOW
Boolean input 6+/Boolean input 6-
5058
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
s of the environment alarm signal input port.)
FAILURE (GND)
15X1.5/X1.4
Blue-white/blue
RECT FAILURE
Boolean input 7+/Boolean input 7- (GND)
5060
16X1.7/X1.8
Brown-white/brown
BTS High Temp
Boolean input 8+/Boolean input 8- (GND)
5062
EXT-ALM0
9
BBU Boolean alarm cable
X1.1/X1.2
Orange-white/orange
Boolean input 1+/Boolean input 1- (GND)
5048
10X1.3/X1.6
Green-white/green
Boolean input 2+/Boolean input 2- (GND)
5050
11X1.5/X1.4
Blue-white/blue
Boolean input 3+/Boolean input 3- (GND)
5052
12X1.7/X1.8
Brown-white/brown
Boolean input 4+/Boolean input 4- (GND)
5054
UEIU EXT- The UEIU 5 BBU X1.1/ Orange- Boolean 5040
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
(The Boolean alarms of the UEIU
are reported by the GTMU.
Therefore, you
should select the
GTMU when
setting the parameter
s of the environment alarm signal input port.)
ALM1
is configured in slot 18 or 19
of subrack
0, and the GTMU in slot 6 of subrack
0. Boolean alarm cable
X1.2white/orange
input 13+/Boolean input 13- (GND)
6X1.3/X1.6
Green-white/green
Boolean input 14+/Boolean input 14- (GND)
5042
7X1.5/X1.4
Blue-white/blue
Boolean input 15+/Boolean input 15- (GND)
5044
8X1.7/X1.8
Brown-white/brown
Boolean input 16+/Boolean input 16- (GND)
5046
EXT-ALM0
1
BBU Boolean alarm cable
X1.1/X1.2
Orange-white/orange
AC FAILURE
Boolean input 9+/Boolean input 9- (GND)
5032
2X1.3/X1.6
Green-white/green
DC LOW FAILURE
Boolean input 10+/Boolean input 10- (GND)
5034
3 X1.5/X1.4
Blue-white/blue
RECT FAILURE
Boolean input 11+/Boolean input
5036
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
11- (GND)
4X1.7/X1.8
Brown-white/brown
BTS High Temp
Boolean input 12+/Boolean input 12- (GND)
5038
The physical hardware is APMI, which is
displayed as APMU
on the LMT.
IN1
Slot 2, 3, 4, or 5 of subrack 2
1Sensor-equipped cable
NA NA 5758
IN2 2Sensor-equipped cable
NA NA 5760
IN3 3Sensor-equipped cable
NA NA 5762
DPMU Slot 2, 3, 4, or 5 of subrack 2
1Sensor-equipped cable
NA NA 6046
2Sensor-equipped cable
NA NA 6048
3Sensor-equipped cable
NA NA 6050
4Sensor-equipped cable
NA NA 6052
5 Sensor-equipped cable
NA NA 6054
Table 1 Mapping between the monitoring units and the monitoring signal cables
BTS Type
Monitoring Unit
Port on the
Monitoring Unit
Installation
Position
Port No.
Monitoring
Signal Cable
WireWire Color
Description
AlmID
6Sensor-equipped cable
NA NA 6056
7Sensor-equipped cable
NA NA 6058
BTS3900A
The physical hardware is FMUA, which is
displayed as FMU on the LMT.
SW0
Any of slots 6 through
15 in subrack 2
0Sensor-equipped cable
NA NA 9760
SW1 1Sensor-equipped cable
NA NA 9762
SW2 2Sensor-equipped cable
NA NA 9764
SW3 3Sensor-equipped cable
NA NA 9766
Parent topic: Reference Information on Setting Environment Alarms