Upload
vimal-das
View
798
Download
23
Embed Size (px)
Citation preview
Rev 1.5 prdJune 13, 2006
MCM3320 QTQ Training
2 Rev 1.5 prdJune 13, 2006
Presentation Outline Introduction Features Hardware Operation System Setup and Simulator (HANDS ON) Operation (continued) Variables Interconnect HMI & Simulator (HANDS ON) InPower Applications (GROUP) Control and Component Mode Panels New Discussion/Questions/Comments
3 Rev 1.5 prdJune 13, 2006
Presentation Goals
What are the capabilities of the MCM3320? What are the board connections? How does it operate? How do I apply it? How do I set it up?
4 Rev 1.5 prdJune 13, 2006
MCM3320 Information
Lotus Notes Database “Commercial ESB Controls”
Sort by “Category”Look for “MCM3320”This presentation and other technical
information located thereAn Application Guide is in the works to provide
a one-stop document
5 Rev 1.5 prdJune 13, 2006
MCM3320 Technical Support
Documentation PGA Controls Engineering:
1. Kevin Aufderhar
2. Paul Dahlen
3. Rich Scroggins
6 Rev 1.5 prdJune 13, 2006
One-Line Feature Summary (Q2 2006)
FEATURES
G1
G2
G3
G4
Load1 Load2 Load3 Load4 Load5 Load6
MCM3320
AUX101AUX102
HMI211OperatorPanel #2
GM UM
Customer I/O
BreakersorATS
AC MeteringSource FailureGensets Start/StopMain Breaker ControlSync/Volt MatchOpen/Closed TransitionLoad RampingExtended ParallelingkW and kVAR ControlLoad DemandLoad Add / ShedSchedulerModbusDiagnostics
HMI112GensetsBargraph
HMI211UtilityBargraph
HMI211OperatorPanel #1
7 Rev 1.5 prdJune 13, 2006
Feature Validation
All available features have been testedFirmware testBench test w/simulatorLive test at Fridley Endurance Pad test facilityLive test at Fridley with real Utility Source
(transfers, sync, base load / peak shave)
FEATURES
8 Rev 1.5 prdJune 13, 2006
AC Metering3 Phase metering of genset bus and utility bus simultaneously
Phase and Total/avg metering of V, A, kW, kVAR, kVA, PF, Hz
Phase and total metering of +kWh, -kWh, +kVARh, -kVARh, kVAh for each source
CT secondaries of 1A or 5APT accepts 0-480VLL directly; external PT for higher
voltages (up to 35000V) PT and CT inputs pre-calibrated
FEATURES
9 Rev 1.5 prdJune 13, 2006
Master Sync / Volt Matchboth phase synchronization and voltage matching20 genset limit for synchronizer frequency offset range: +/- 1.0 Hz min; up to +/- 3.0Hzoutput voltage offset range: +/- 6% min; up to +/- 10%offset range generally independent of gen bus load
FEATURES
10 Rev 1.5 prdJune 13, 2006
Master Sync / Volt Match controls frequency and voltage via PCC kW and kVAR
load share lines selectable phase synchronization (default) or slip
frequency synchronization sync enable input for manual control modeoption to invert synchronizer polarity if genset and
utility swap positions in synchronizer only application (via Modbus)
FEATURES
11 Rev 1.5 prdJune 13, 2006
Permissive Sync Check sync check function is independent of synchronizer adjustable frequency window, phase window, voltage
window, and window time for permissive check includes configurable dead bus logic sync check output fail to synchronize diagnosticphase rotation mismatch diagnostic
FEATURES
12 Rev 1.5 prdJune 13, 2006
Breaker Control interface for both genset main and utility main close and open control – momentary energization until
desired position is achieveda/b and tripped breaker position inputsadjustable breaker recharge time delay to prevent fail
to close due to inadequate charge time
FEATURES
13 Rev 1.5 prdJune 13, 2006
Breaker Controlutility paralleling enable outputbreaker inhibit control inputbreaker diagnostics with appropriate system control
reactionadjustable fail to close and fail to open time delaysparalleling fail to disconnect diagnostic with
configurable system control reaction
FEATURES
14 Rev 1.5 prdJune 13, 2006
Breaker Controlanti-pump avoidance logic – external breaker position
contacts not required in series with trip coilbreaker inhibit output to control individual genset
paralleling breakers in applications with no gen main, and for backup disconnect protection capability
FEATURES
15 Rev 1.5 prdJune 13, 2006
Power Transfer Controlopen transition w/pgm transition delay, hard closed
transition (<100msec), soft load closed transition sensors (uv, ov, freq, phase rot, loss of phase, gen
bus capacity, and breaker failure)adjustable time delays (pgm transition, transfer,
retransfer, max parallel, gensets start delay, gensets stop delay)
source availability determination for both utility and genset
source connected determination for both utility and genset
FEATURES
16 Rev 1.5 prdJune 13, 2006
Power Transfer Controlgensets start/stop logic with single relay output transfer and retransfer inhibit inputsoverride input to override timers and
transfer/retransfer inhibits for immediate transfer, retransfer or genset start
auto/manual mode input
FEATURES
17 Rev 1.5 prdJune 13, 2006
Power Transfer Control test start inputadjustable test with or without loadoption to do open transition retransfer if fail to sync
occurs
FEATURES
18 Rev 1.5 prdJune 13, 2006
System TopologiesTransfer Pair (UM / GM) Common Bus (UM / no GM) Isolated Bus (GM) Isolated Bus (no GM) Master Synchronizer Only
FEATURES
19 Rev 1.5 prdJune 13, 2006
System Topologies
Transfer Pair (System Types 2,3,4,8,10,11)
Load
G1 G2 G3 G4
UM GM
MCM3320
FEATURES
20 Rev 1.5 prdJune 13, 2006
System Topologies
Common Bus (System Type 9)
Load
G1 G2 G3 G4
UM
MCM3320
FEATURES
21 Rev 1.5 prdJune 13, 2006
System Topologies
Isolated Bus w/GM (System Type 7)
Load
G1 G2 G3 G4
GM
MCM3320
FEATURES
22 Rev 1.5 prdJune 13, 2006
System Topologies
Isolated Bus Without GM (System Types 5,6)
Load
G1 G2 G3 G4
MCM3320
FEATURES
23 Rev 1.5 prdJune 13, 2006
System Topologies
Master Synchronizer Only (metering optional)
Source
G1 G2 G3 G4
MCM3320
SyncCheck
FEATURES
24 Rev 1.5 prdJune 13, 2006
Multiple MCM3320s
master inhibit input will inhibit the synchronizer and power transfer control functions
use in complex systems with multiple transfer pairs and multiple MCM3320s
external logic device is required to assert the master inhibit as required (e.g. during a retransfer sequence of multiple pairs)
future enhancement will allow automatic priority control through interconnected MCM3320s (similar to First Start Bus PT logic)
(External)
FEATURES
25 Rev 1.5 prdJune 13, 2006
Extended Paralleling MANY options available for controlling kW and kVAR in
extended paralleling mode (kVAR not applicable for PCC3100)
kW and kVAR can be independently controlled in any combination of base load (control the power @ gen bus) or peak shave (control the power @ utility bus)
load control operates independently of the number of gensets that are online
Maximum of 20 gensets kW base load control selectable as open loop or closed
loop kW peak shave control is closed loop only
FEATURES
26 Rev 1.5 prdJune 13, 2006
Extended Paralleling setpoints can be set from InPower, HMI, Modbus, or via analog
hardware 0-5V inputs extended parallel start input starts/stops the mode soft load ramping separate diagnostic for kW and kVAR if unable to acheive
setpoint within 60 seconds
FEATURES
27 Rev 1.5 prdJune 13, 2006
System Scheduler
12 program run schedules run schedules configurable for start day, start
time, duration, repeat interval, and run mode run modes: without load, with load, or extended
parallelprovides up to 6 different schedule exceptionsuses on-board Real Time Clock
FEATURES
28 Rev 1.5 prdJune 13, 2006
Real Time Clock
on-board RTC used by Scheduler function clock keeps track of year, month, day, date, hour,
minute, and second user must set the clock on first power-up clock automatically accounts for leap year configurable automatic Daylight Savings Time clock
correction clock setting will remain valid for at least 24 hours
without B+ to the board diagnostic fault occurs if clock needs to be set (scheduler
won’t run)
FEATURES
29 Rev 1.5 prdJune 13, 2006
Load Demand
Use to match online generating capacity to load in order to optimize fuel use and genset life
load demand for up to 4 gensets fixed sequence OR run-hours based adjustable shutdown and restart thresholds as well as
time delays and run hour differential 4 load demand driver outputs to connect to PCC genset
control's load demand inputs requires genset paralleling breaker position 'a' contacts
connected to 3320
FEATURES
30 Rev 1.5 prdJune 13, 2006
Load Add/Shed
adds loads in steps as gensets come online sheds loads to unload an overloaded genset bus Requires external module: AUX101/2 PCCNet I/O
Module for feeder breaker and/or ATS control supports up to 6 levels supports up to 4 gensets control up to 6 feeder breakers or ATS directly in any
combination monitoring of breaker / ATS position provided
FEATURES
31 Rev 1.5 prdJune 13, 2006
Modbus RTU intended for PLC interface published register map read/write access operational data, control, and setup variables MCM3320 is Modbus slave RS232 or RS485 connection settable address (allowing multiple MCM3320 slaves on RS485) communications setup and diagnostics
FEATURES
32 Rev 1.5 prdJune 13, 2006
Diagnostics individual On-Board LEDs for:
Utility Available
Utility Connected
Genset Available
Genset Connected
Not In Automatic
Common Warning
Heartbeat
Synchronizing
Synchronized
Fail To Sync
Modbus Communication Activity
FEATURES
33 Rev 1.5 prdJune 13, 2006
Diagnostics
GensetConnected
UtilityConnected
GensetAvailable
UtilityAvailable
CommonAlarm
Not InAutomatic
Heartbeat(blink)
Fail to Sync
Blink = SyncSolid = Okto Close
LED Indicators
ModbusActivity
FEATURES
34 Rev 1.5 prdJune 13, 2006
Diagnostics On-Board seven segment LED for indication of:
System State indication of what the control is currently doing
Fault Code Readout (hold fault reset switch active for >5sec to change to fault code readout mode)
FEATURES
35 Rev 1.5 prdJune 13, 2006
Diagnostics
FEATURES
Decimal Point = Off System State
Seven Segment LED IndicatorDecimal Point = On
Active Fault Code Flashout
System State LED Output Character
Not Available - (center segment)TD Start 1TD Stop 2TD Pgm Tran 3TD Transfer 4TD Retransfer 5Synchronizing 6Sync Check OK 7Inhibit 8Unassigned 9Ramp Unload ARamp Load bManual CUtility Failure dTest EStandby JExtended Parallel H
Code Event Name Response343 Hardware Failure Warning Warning353 EEPROM Write Error Warning Warning
1121 Fail To Disconnect Warning Warning1219 Utility Main Breaker Tripped Warning Warning1222 Not In Automatic Event Event1223 Utility Bus Frequency Warning Warning1224 Genset Bus Overvoltage Warning Warning1225 Genset Bus Undervoltage Warning Warning1226 Genset Bus Frequency Warning Warning1328 Genset Main Breaker Tripped Warning Warning1335 AC Metering Out Of Range Warning Warning1444 Genset Bus Overload Warning Warning1452 Genset Main Breaker Fail To Close Warning Warning1453 Genset Main Breaker Fail To Open Warning Warning1454 Genset Main Breaker Position Contact Warning Warning1455 Utility Main Breaker Position Contact Warning Warning1456 Synchronizer Output Limit Warning Warning1457 Fail To Synchronize Warning Warning1458 Synchronizer Phase Rotation Mismatch WarningWarning1483 Common Warning Event Event1534 Load Control Output Event Event1541 Genset Failed To Come Online Warning Warning1689 Real Time Clock Power Interrupt Warning Warning1912 Utility Bus Loss Of Phase Warning Warning1913 Genset Bus Loss Of Phase Warning Warning1914 Utility Bus Phase Rotation Warning Warning1915 Genset Bus Phase Rotation Warning Warning1916 Synchronized Event Event1989 kW Load Control Output Limit Warning Warning1991 kVAR Load Control Output Limit Warning Warning1999 Maximum Parallel Time Warning Warning2328 Utility Bus Available Event Event2331 Utility Bus Undervoltage Warning Warning2332 Utility Bus Connected Event Event2333 Genset Bus Connected Event Event2358 Utility Bus Overvoltage Warning Warning2396 Utility Main Breaker Fail To Close Warning Warning2397 Utility Main Breaker Fail To Open Warning Warning2416 Calibration Checksum Warning Warning2647 Load Demand Setup Warning Warning2648 Remote IO Communication Failure Warning Warning2965 Genset Bus Available Event Event2971 Test / Extended Parallel Event Event
36 Rev 1.5 prdJune 13, 2006
Diagnostics 42 diagnostics (warnings and events) each event or warning is mappable to 8 customer low side
driver outputs active warning codes can be read out on 7segment LED on
board some warnings alter control operation warnings are latched until user fault reset events are not latched
FEATURES
37 Rev 1.5 prdJune 13, 2006
DiagnosticsCommon Alarm EventGenset Available EventGenset Connected EventSynchronized EventTest / Extended Parallel EventUtility Available EventUtility Connected EventAC Metering Out of Range WarningCalibration Checksum WarningEEPROM Write Error WarningFail To Disconnect WarningFail To Synchronize WarningGenset Main Breaker Fail To Close WarningGenset Main Breaker Fail To Open WarningGenset Main Breaker Position Contact WarningGenset Main Breaker Tripped WarningGenset Frequency WarningGenset Loss of Phase WarningGenset Overvoltage WarningGenset Phase Rotation WarningGenset Undervoltage WarningHardware Failure Warning
kVAR Load Control Output Limit WarningkW Load Control Output Limit WarningMaximum Parallel Time WarningNot In Automatic WarningReal Time Clock Power InterruptSynchronizer Output Limit WarningSynchronizer Phase Rotation Mismatch WarningUtility Main Breaker Fail To Close WarningUtility Main Breaker Fail To Open WarningUtility Main Breaker Position Contact WarningUtility Main Breaker Tripped WarningUtility Frequency WarningUtility Loss of Phase WarningUtility Overvoltage WarningUtility Phase Rotation WarningUtility Undervoltage WarningLoad Demand Setup WarningRemote IO Communications WarningGenset Bus Overload WarningGenset Failed To Come Online WarningUtility Source Unloaded Event – Coming SoonGenerator Source Unloaded Event – Coming Soon
FEATURES
38 Rev 1.5 prdJune 13, 2006
InPower V5.5
MON RS485 interface standard InPower folders: Adjustments, Faults,
Monitor, Testbuilt in Setup Tooldownload new firmware capture files
FEATURES
39 Rev 1.5 prdJune 13, 2006
InPower V5.5 Setup Tool
special application to assist with setup of the MCM3320
user friendly screens
help file
FEATURES
40 Rev 1.5 prdJune 13, 2006
MCM3320 FEATURES
High/Low Battery VoltageFlexible TopologyAnnunciator Support
In Development
41 Rev 1.5 prdJune 13, 2006
High/Low Battery Voltage
Provide faults for high and low battery voltage as sensed at the MCM3320
Details to be determined
FEATURES
42 Rev 1.5 prdJune 13, 2006
Flexible Topology
Make the MCM3320 more flexible for use in complex system topologies
Provide Extended Parallel w/o breaker controlProvide outputs for source unloaded for utility
and generatorEliminates need for Bitronics transducerAllows PLC to control breakers
FEATURES
43 Rev 1.5 prdJune 13, 2006
Feature Limits Quiz
How many gensets can be supported by the following features ?
FEATURES
•AC Metering•Synchronizing•Load Demand•Load Add / Shed•Utility Paralleling
32000kW, 10000A
20
4
4
20
44 Rev 1.5 prdJune 13, 2006
Annunciator Support
Utility Available
Utility Connected
Gen Bus Available
Gen Bus connected
Not In Auto
Common Alarm
Fail to Sync
Gen 1 Running
Gen 2 Running
Gen 3 Running
Gen 4 Running
Test
Extended Parallel
Gen Bus Overload
Load Demand
FEATURES
Priority 1 Load On
Priority 2 Load On
Priority 3 Load On
Priority 4 Load On
Priority 5 Load On
Priority 6 Load On
Shed Level 1
Shed Level 2
Shed Level 3
Shed Level 4
Shed Level 5
Annunciator 1 Layout Annunciator 2 Layout
45 Rev 1.5 prdJune 13, 2006
Feature Limits Quiz
What can Load Add / Shed support ?
FEATURES
•Load Device Types•Load Add Levels•Load Shed Levels•# of Gensets
Breaker, ATS
6
6
4
46 Rev 1.5 prdJune 13, 2006
HARDWAREMCM3320 HMI211 AUX101/2
InPower Cable HMI Harness HMI112
47 Rev 1.5 prdJune 13, 2006
Part Numbers
HARDWARE
Part Number Model Released? Description
0327-1520-01 MCM3320 Yes fully featured master control module 0327-1520-02 SYNC1320 Yes depopulated/defeatured synchronizer only module 0300-6090 HMI 211 Yes operator interface panel (can use one or two) 300-6050-01 HMI 112 Yes Bargraph panel (use 2 – one for genset bus, one for utility bus) 0541-1342 AUX101/2 Yes PCCNet IO Module with Expansion card for use with Load Add
Shed Feature (one only) 0338-4747 Yes 12 foot harness for connecting HMI to MCM3320; can be cut to
length 0630-3133 Yes MCM3320 Interconnect Wiring Diagram and Outline 0630-3136 Yes SYNC1320 Interconnect Wiring Diagram and Outline 0541-1199 Yes Cable and RS485/232 Converter Kit for connecting to controller
with InPower, Engineering Tool, or Setup Tool (Kit is for PCC1301 product, but will work with MCM3320 or SYNC1320)
48 Rev 1.5 prdJune 13, 2006
MCM3320Genset CT Inputs
(1A or 5A)
Modbus RTU(RS232)
TB6Genset PT Input(480V LL Max)
Utility PT Input(480V LL Max)
Utility CT Inputs(1A or 5A)
TB9Analog IO
TB3
TB1
TB10
TB8TB15
TB2
TB7
L1* L2* L3* L1* L2* L3*
GEN UTILITY
Switch IO / PCCNet (TB1)
Switch IO / CAN (TB3)
Breaker Status Inputs (TB10)
Breaker Control / Start Gensets (TB8)
InPower orModbus RTU
(RS485)
Switch IO /DC Power In
J14
J17
Factory Test Connector (J17)
HARDWARE (MCM3320)
49 Rev 1.5 prdJune 13, 2006
Hardwired IO
Gen Utility
Load
Gen O
penG
en Close
Gen P
ositionA
Extended Para Start
Sync Enable
Utility Source Failure
Transfer Inhibit
Retransfer Inhibit
Gen CB Tripped
Util CB Tripped
Gen P
osition B
Manual
Test Start
Fault Ack/Reset
Gen1 Available
Gen2 Available
Gen3 Available
Gen4 Available
kVAR Load Setpoint
Master Freq Bias
Master Volt Bias
Master Inhibit
Load Govern Enable
Load Demand Gen1
Load Demand Gen2
Load Demand Gen3
Load Demand Gen4
Start Gensets Relay
kW Master Load Control
Gen CB Inhibit
Util CB Inhibit
Cfg Out1 (com warn)
Cfg Out2 (fail to sync)
Cfg Out3 (gen avail)
Cfg Out4 (util avail)
Cfg Out5 (fail to discon)
Cfg Out6 (sync’d)
Cfg Out7
Cfg Out8
Relay Supply
B+ Input1
Gnd
RS485 PCCNet
RS485/232 Mon/MB
B+ Input2
Gnd
CAN (Master)
BIDIRECTIONALB+ POWER
DISCRETEINPUTS
(active low w/pullup)
DISCRETEOUTPUTS
(low side drivers)
ANALOGINPUTS(0-5V)
ANALOGOUTPUTS
GENV/I
BUS/UTILV/I
COMMUNICATIONS
Override
RELAY OUTPUTS
B+ OUTPUTS
P. Dahlen9/8/05
BREAKERINTERFACE
(discrete inputs /relay outputs)
Util O
penU
til Close
Util P
ositionAU
til Position B
Paralleling GensetsBreaker Inhibit
MCM3320 Hardware I/O
kW Load Setpoint
kVAR Master Load Control
HARDWARE (MCM3320)
50 Rev 1.5 prdJune 13, 2006
B+ Power
2 separate B+ power inputs for redundant supply of control; station battery suggested
On-board diode-OR Range: 9-32V Will ride-through starter dip Less than 1 Adc load (no external B+ loads) On-board backup of Real Time Clock (minimum 24
hours) No wakeup input; board is always awake Removal of B+ will not cause loss of any historical data
(controller on-time, kWh, etc.)
HARDWARE (MCM3320)
51 Rev 1.5 prdJune 13, 2006
PT Inputs
Nominal Range 110 – 480 V LLExternal Transformer to 35 kV LLSensing to 125% of Nominal3 Wire or 4 Wire
HARDWARE (MCM3320)
52 Rev 1.5 prdJune 13, 2006
CT Inputs
Primary from 5 to 10000 AmpsSecondary 1 Amp OR 5 AmpNo terminal block; CT on-board with holeRecommend shorting block nearby2 passes through hole for 1 Amp1 pass for 5 AmpSensing to 125%
HARDWARE (MCM3320)
53 Rev 1.5 prdJune 13, 2006
HW Discrete Inputs
22 hardwire switch inputs Inactive State: Open circuit / high impedance
(not B+)Active State: Connect to ReturnCan use local B- for return Inputs are activated by current (opto coupled)
HARDWARE (MCM3320)
54 Rev 1.5 prdJune 13, 2006
HW Discrete Inputs
Discrete Input Active State (to Gnd)
Inactive State (open cicuit)
Description
Fault Reset Reset Not Reset reset faults; engage fault readout Auto/Manual Manual Auto manual or auto breaker / sync operation Test Start Start Stop test load transfer start / stop Extended Parallel Start Start Stop extended paralleling start / stop Synchronizer Enable Active Inactive sync enable (applies in manual only) Utility Source Failure Active Inactive use if external device determines failure Transfer Inhibit Inhibit No Inhibit inhibit transfers to gens (some exceptions) Retransfer Inhibit Inhibit No Inhibit inhibit retransfers to util (some exceptions) Override Override No Override override timers and tran/retran inhibits Gen Main CB Inhibit Inhibit No Inhibit open gen main / inhibit closure Util Main CB Inhibit Inhibit No Inhibit open util main / inhibit closure Gen Main CB Tripped Tripped Not Tripped gen main breaker tripped; source not avail Util Main CB Tripped Tripped Not Tripped util main breaker tripped; source not avail Gen1 CB Position Breaker Closed Breaker Open genset #1 breaker position ('a' contact) Gen2 CB Position Breaker Closed Breaker Open genset #2 breaker position ('a' contact) Gen3 CB Position Breaker Closed Breaker Open genset #3 breaker position ('a' contact) Gen4 CB Position Breaker Closed Breaker Open genset #4 breaker position ('a' contact) Util Main CB PositionA Breaker Closed Breaker Open util main breaker position ('a' contact) Util Main CB PositionB Breaker Open Breaker Closed util main breaker position ('b' contact) Gen Main CB PositionA Breaker Closed Breaker Open gen main breaker position ('a' contact) Gen Main CB PositionB Breaker Open Breaker Closed gen main breaker position ('b' contact) Master Inhibit Inhibit No Inhibit master inhibit for multiple pair operation
HARDWARE (MCM3320)
55 Rev 1.5 prdJune 13, 2006
HW Discrete Outputs
19 hardwire discrete outputs5 relays; 14 low-side drivers low-side drivers can sink 200mAbreaker relays (4) can drive coils directly in
some limited cases; else use interposing relays
HARDWARE (MCM3320)
56 Rev 1.5 prdJune 13, 2006
HW Discrete Outputs
Output Signal Name (hardware)
Active State (Low / Energized)
Inactive State (High Impedance / Deenergized)
Description
Start Gensets Relay Run Stop form C relay to start / stop gensets (via Remote Start) Util Main CB Close Relay Active Inactive N.O. relay contact for utility main close coil Util Main CB Open Relay Active Inactive N.O. relay contact for utility main open coil Gen Main CB Close Relay Active Inactive N.O. relay contact for gen main close coil Gen Main CB Open Relay Active Inactive N.O. relay contact for gen main open coil Load Govern Enable Driver Enabled Disabled low-side driver to PCC genset's util cb position input to
put PCC in load govern mode when utility paralleled Paralleling Gensets Breaker Inhibit Driver
Inhibit All Gensets No Inhibit low-side driver to PCC genset's paralleling breaker inhibit input
Load Demand Gen1 Driver Load Demand Stop Run low-side driver to PCC genset #1 load demand input Load Demand Gen2 Driver Load Demand Stop Run low-side driver to PCC genset #2 load demand input Load Demand Gen3 Driver Load Demand Stop Run low-side driver to PCC genset #3 load demand input Load Demand Gen4 Driver Load Demand Stop Run low-side driver to PCC genset #4 load demand input Configurable Output1 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output2 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output3 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output4 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output5 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output6 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output7 Driver Driver On Driver Off activated by programmable event/warning code Configurable Output8 Driver Driver On Driver Off activated by programmable event/warning code Relay Supply B+ Output B + Output B + output for supplying relay coil high side; low side
connected to a low-side driver output
HARDWARE (MCM3320)
57 Rev 1.5 prdJune 13, 2006
HW Bidirectional Discrete
Bidirectional discrete I/O for priority arbitration (like 1st Start Bus PT)
Used in Phase 2 for priority control among multiple MCM3320s
Same connection as “Master Inhibit” (externally controlled sequencing)
HARDWARE (MCM3320)
58 Rev 1.5 prdJune 13, 2006
HW Analog Inputs
2 hardwire analog inputs kW Load Setpoint (0-5V) kVAR / PF Load Setpoint (0-5V)used for base load / peak shave setpointsalternatively set via Modbus or Trim load setpoint profiles same as
PCC3100/3200/3201
HARDWARE (MCM3320)
59 Rev 1.5 prdJune 13, 2006
HW Analog Outputs
2 hardwire analog outputs kW Master Load Control (0-5V) kVAR Master Load Control (0-5V) Used for load control commands to PCC genset load set
inputs to control soft ramping and base load / peak shave
kVAR control only available on PCC3200/3201, PCC3300 genset controllers
New Rev D board supports interconnection of analog outputs amongst multiple 3320s
HARDWARE (MCM3320)
60 Rev 1.5 prdJune 13, 2006
HW Bidirectional Analog
Two bidirectional analogs for synchronizerMaster Frequency Bias senses/drives kW load
share line to affect gen bus frequencyMaster Voltage Bias senses/drives kVAR load
share line to affect gen bus voltageOutput range -2.5 to + 5.0 Vdrives up to 20 gensets simultaneously
HARDWARE (MCM3320)
61 Rev 1.5 prdJune 13, 2006
Communications
Controller has 2 serial portsPort1
– Protocol Options• PCCNet – for HMI, IO Modules (default protocol)• Mon – for troubleshooting only (cannot download); set to
Mon mode via Modbus on Port2 or through InPower
– Physical• RS485 on TB1• Multidrop for PCCNet
HARDWARE (MCM3320)
62 Rev 1.5 prdJune 13, 2006
Communications
Port2: – Protocol Options
• Modbus RTU (MCM3320 is SLAVE)• Mon (Service Port for InPower/Setup Tools)• Controller automatically detects protocol
– Physical• RS232 on J14 (DB9 pins); Null Modem cable• RS485 2-wire on TB15• RS485 is default; control switches to RS232 when
RS232 RTS to CTS pins are jumpered by cable
HARDWARE (MCM3320)
63 Rev 1.5 prdJune 13, 2006
HMI211 Operator Panel
HMI211 PCCNet interface (4wires):B+ / GNDRS485 A / B
• Up to two HMI211’s can be connected to one MCM3320
• Use harness 0338-4747 to connect; cut to length or extend (12ft / 3.6m)
HARDWARE (HMI211)
64 Rev 1.5 prdJune 13, 2006
HMI112 Bargraph
HMI112 Bargraph PCCNet interface (4wires):B+ / GNDRS485 A / B
• Connect two HMI211’s to one MCM3320 to get both source data
HARDWARE (HMI112)
65 Rev 1.5 prdJune 13, 2006
AUX101/2 IO Module
HARDWARE (AUX101/2)
P11 (Inputs)
P10 (Ground for Inputs)
P2 (Relays)
P3(Relays)
P4(Relays)
P14 (B+ / Gnd)
P1 (PCCNet, Wakeup)
P4 (Inputs)
P3 (Relays - NC)
P2 (Relays - Com)
P1 (Relays - NO)
AUX101
AUX102
Connect to GroundedChassis
Device Number: Must Read “0” forMCM3320 Applications.To Change Device Number, Press andhold pushbutton until decimal point isilluminated. Then push buttonrepeatedly to cycle through numbersuntil it reads “0”.
Green LED: PCCNetCommuncations OK
Red LED: PCCNetCommuncations Not
OK
Relay LEDsON = Energized
Aux102 Board RevisionLevel: First letter on barcode(read from left to right) must
be “C” or higher letter.
Relay LEDsON = Energized
AUX102 connects toLoad Devices #5,6
AUX101 connects to LoadDevices #1,2,3,4
66 Rev 1.5 prdJune 13, 2006
Connections
• Modules required for Load Add Shed feature
• MCM3320 to AUX101 PCCNet interface (4 wires):B+ / GNDRS485 A / B
• 12 discrete inputs used for breaker / ATS position monitoring
• 12 form C relays used for breaker / ATS control
HARDWARE (AUX101/2)
67 Rev 1.5 prdJune 13, 2006
MCM3320 OPERATION
MCM3320 can completely manage simple systems – breaker control, synchronizing, load control, gensets start/stop, diagnostics, etc.
MCM3320 can be used as a component in more complex systems with whichever features are appropriate; a PLC can orchestrate the actions of the MCM3320
68 Rev 1.5 prdJune 13, 2006
MCM3320 FUNCTIONS
MCM3320 Major Functional Blocks– Application Configuration– System Information– IO Processing– AC Metering– Breaker Control– Power Transfer Control– Synchronizer & Sync Check– Load Control– Scheduler– Load Demand– Load Add/Shed– Communications– Diagnostics / History– HMI 211
69 Rev 1.5 prdJune 13, 2006
Application Configuration
Primary Settings:System Topology
Transition Type
Extended Parallel Enable
Test With Load Enable
Settings are trims (can be saved) or can be dynamically set via Modbus, InPower or HMI
FUNCTIONS
70 Rev 1.5 prdJune 13, 2006
Application Configuration
MOST IMPORTANT SETTING (set it 1st)
System TopologyTransfer Pair
Common Bus
Isolated Bus with GM
Isolated Bus without GM
Master Synchronize Only (default)
FUNCTIONS
71 Rev 1.5 prdJune 13, 2006
Application Configuration
Transition TypeOpen Transition (default)
Hard Closed Transition (<100msec overlap)
Soft Closed Transition
Extended Parallel EnableDisabled (default)
Enabled
Test With Load EnableDisabled (default)
Enabled
FUNCTIONS
72 Rev 1.5 prdJune 13, 2006
Application Configuration
Must be in Manual mode to set System Topology
Hard Closed Transition not applicable in Common Bus topology
Transition Type only applies to load transfersThus Transition Type = (Open Transition OR
Hard Closed) is compatible with Extended Parallel Enable = Enabled
FUNCTIONS
73 Rev 1.5 prdJune 13, 2006
System Information
Settings for System Phase Rotation, System Frequency, Individual Genset kW Ratings
Derived Information such as Total System Capacity, Total Online Capacity, Spare Online Capacity, etc. for use in other control function blocks
System State derived variable– Shows what system is currently doing that is most
relevant– Use for information only, not for control decisions
FUNCTIONS
74 Rev 1.5 prdJune 13, 2006
System Information
System Lockout derived variable indicating that normal control logic has been altered due to a fault
Active / Inactive latched until user fault reset must be reset for normal control operation to resume LED on HMI Conditions which make it active:
Utility Breaker Fail to Close Fault State = ActiveUtility Breaker Fail to Open Fault State = ActiveUtility Breaker Position Contact Fault State = ActiveGenset Breaker Fail to Close Fault State = ActiveGenset Breaker Fail to Open Fault State = ActiveGenset Breaker Position Contact Fault State = Active(Fail to Synchronize Fault State = Active AND Fail to Sync Lockout Enable = Enabled)Maximum Parallel Time Fault State = ActiveGenset Bus Overload Fault State = Active AND (Load Demand = Enabled OR Load Add Shed = Enabled)
FUNCTIONS
75 Rev 1.5 prdJune 13, 2006
System Information
Genset Bus Overload is detected by kW level or frequency or both (configurable)
Fault Code 1444 Used internally by Load Demand and Load Shed
functions Adjustable %kW threshold: 80-140% of online
capacity Adjustable kW delay: 0-120 sec Adjustable Hz threshold: 0.1-10 Hz below System
Frequency setting Adjustable Hz delay: 0-20 sec
FUNCTIONS
76 Rev 1.5 prdJune 13, 2006
System Setup1
FUNCTIONS
77 Rev 1.5 prdJune 13, 2006
System Setup2
FUNCTIONS
78 Rev 1.5 prdJune 13, 2006
IO Processing – Discrete Inputs
Most discrete inputs can be controlled from a hardwired input OR from a communications link such as Modbus or InPower (“<name> + Vol”)
Controller will always logically OR the two inputs Result of OR is readable at “<name> + Sw”
HW SW
Conditioning &Level
Detection Sample<Signal Name>
DebounceFunction <Signal Name>
+ " Sw"
< Signal Name > + " Vol"
FUNCTIONS
79 Rev 1.5 prdJune 13, 2006
IO Processing – Discrete Outputs
For testing and troubleshooting purposes, most discrete outputs can be directly overriden using InPower
SW HW
HW UpdateOutput
Register
(enabled)
(disabled)
<Output Signal Name><Input Signal Name>
<Output Signal Name> + " Override Cmd"
<Output Signal Name> + " Override Enable"
<Output Signal Name> + " Status"
FUNCTIONS
80 Rev 1.5 prdJune 13, 2006
AC Metering Setup
PT Primary Voltage = 110-45000 VLLPT Secondary Voltage = 110-500 VLLCT Primary Current = 5-10000 ACT Secondary Current = 5 or 1 ANominal Voltage = 110-45000 VLL
– Used for %volt scaling
FUNCTIONS
81 Rev 1.5 prdJune 13, 2006
AC Metering - Voltage
Hardware inputs autoranging: 120,240,or 480 VLL = 100% at board
Input Range: 5% to 125% of above rangesSampled every line cycle on all 3 phasesLN, LL, LN-Avg, LL-Avg, % of nominal3 or 4 Wire ConnectionsFactory calibrated to better than 1% of full scale;
field adjustable
FUNCTIONS
82 Rev 1.5 prdJune 13, 2006
AC Metering - Current
Hardware inputs autoranging: 5 A or 1A = 100% at board Input Range: 0% to 125% of above ranges Sampled every 10th line cycle L1, L2, L3 and Average True RMS with 14kHz Bandwidth 1A requires two pass thru on-board CT Factory calibrated to better than 1% of full scale; field
adjustable
FUNCTIONS
83 Rev 1.5 prdJune 13, 2006
AC Metering - Power
kW, kVAR, kVA, PF True power readings; 14kHz bandwidth
If harmonics present, kW2 + kVAR2 may not equal kVA2
Sampled every 10th line cycle Per phase and totalized to +/- 32767k Sign Convention is with respect to the Source
– Positive kW = real power delivered by source– Positive kVAR = lagging vars delivered by source– Positive PF = lagging; Negative PF = leading
FUNCTIONS
84 Rev 1.5 prdJune 13, 2006
AC Metering - Energy
kWh positive, negative, net kVARh positive, negative, net kVAh netPer phase and totalized to +/- 231
Permanently storedResettable/Settable
FUNCTIONS
85 Rev 1.5 prdJune 13, 2006
AC Metering – Time Based
Precise frequency reading 25 to 80HzPrecise sync phase angle reading -180 to +180
degreesPrecise voltage phase angle readings
– Used by loss of phase sensor
FUNCTIONS
86 Rev 1.5 prdJune 13, 2006
AC Metering Setup
FUNCTIONS
87 Rev 1.5 prdJune 13, 2006
AC Metering Calibration
FUNCTIONS
• MCM3320 is factory calibrated
• Voltage and Current can be adjusted in the field if needed
88 Rev 1.5 prdJune 13, 2006
Breaker Control
Main Breaker PositionsMain Breaker ControlMain Breaker Diagnostics
FUNCTIONS
89 Rev 1.5 prdJune 13, 2006
Main Breaker Position
‘a’ and ‘b’ contact used to determine position (default) this may change
If conflict between ‘a’ and ‘b’:1. Contact fault active2. If current on all 3 phases > threshold, then breaker
considered closed, else unknown3. Source deemed not available if current based breaker
position is ‘unknown’
Can configure for ‘a’ contact only operation, this may become the default
Breaker rack-out will cause fault and source not available
FUNCTIONS
90 Rev 1.5 prdJune 13, 2006
Main Breaker Position
In applications without GM, a virtual GM is created by collection of genset paralleling breakers
In this case, if any one or more genset paralleling breaker is closed, virtual GM is closed.
IMPORTANT: If #gens <= 4, use individual genset cb position inputs. If #gens > 4 connect cb contacts in parallel to GM position inputs. Refer to 0630-3133 dwg
FUNCTIONS
91 Rev 1.5 prdJune 13, 2006
Main Breaker Control
Separate relays for close and open Relays energize until desired position achieved Adjustable recharge time delay Built-in software interlock for open transition In applications without GM, the MCM3320 controls the
virtual gen main via the paralleling gen cb inhibit inputs on the genset controls
Breakers can be controlled manually when Auto/Manual switch input = Manual
FUNCTIONS
92 Rev 1.5 prdJune 13, 2006
Main Breaker Diagnostics
Breaker Diagnostics:Fail to Close (adjustable delay)
Fail to Open (adjustable delay)
Breaker Contacts
Breaker Tripped
Fail to Disconnect
Diagnostics results in warning and appropriate control reaction
FUNCTIONS
93 Rev 1.5 prdJune 13, 2006
Breaker Setup
FUNCTIONS
94 Rev 1.5 prdJune 13, 2006
Power Transfer Control
Sensors and Source AvailabilityOperating ModePTC State MachineTimers
FUNCTIONS
95 Rev 1.5 prdJune 13, 2006
Sensors
Both sources have these sensors:• Undervoltage
• Overvoltage *
• Under/Over Frequency *
• Phase Rotation *
• Loss of Phase *
• Main Breaker Tripped
• Fail to Close
• Position Contact Failure
If any sensor is dropped-out, the source is not available
(* = optionally enabled)
FUNCTIONS
96 Rev 1.5 prdJune 13, 2006
Sensor - Undervoltage
Sensor is always enabledConfigurable L-L or L-N sensingSettings:
– Dropout Percentage– Pickup Percentage– Dropout Delay
Pickup is instantaneousTake note how settings are converted into
actual voltages (next page)
FUNCTIONS
97 Rev 1.5 prdJune 13, 2006
Sensor - Undervoltage
Voltage, V
UnderVoltageSensorStatus
NominalSystemVoltage(100%)
PickupVoltage
DropoutVoltage
PICKED UP(good)
DROPPED OUT(bad)
Pickup Voltage = Pickup Percentage * Nominal VoltageDropout Voltage = Dropout Percentage * Pickup Percentage * Nominal Voltage
FUNCTIONS
98 Rev 1.5 prdJune 13, 2006
Sensor - Overvoltage
Sensor is optionally enabledConfigurable L-L or L-N sensingSettings:
– Dropout Percentage– Pickup Percentage– Dropout Delay
Pickup is instantaneousTake note how settings are converted into
actual voltages (next page)
FUNCTIONS
99 Rev 1.5 prdJune 13, 2006
Sensor - Overvoltage
Voltage, V
OverVoltageSensorStatus
NominalSystemVoltage(100%)
PickupVoltage
DropoutVoltage
PICKED UP(good)
DROPPED OUT(bad)
Pickup Voltage = Pickup Percentage * Dropout Percentage * Nominal VoltageDropout Voltage = Dropout Percentage * Nominal Voltage
FUNCTIONS
100 Rev 1.5 prdJune 13, 2006
Sensor - Frequency
Sensor is optionally enabled Over and Under combined in one sensor Settings:
– Center Frequency– Dropout Bandwidth– Pickup Bandwidth– Dropout Delay
Pickup is instantaneous Take note how settings are converted into actual
voltages (next page)
FUNCTIONS
101 Rev 1.5 prdJune 13, 2006
Sensor - Frequency
Frequency, Hz
FrequencySensorStatus
CenterFrequency
UpperPickupFreq
LowerPickupFreq
PICKED UP(good)
DROPPED OUT(bad)
Lower Pickup Freq = (1 - Pickup Bandwidth) * Center FrequencyUpper Pickup Freq = (1 + Pickup Bandwidth) * Center FrequencyLower Dropout Freq = (1 - Pickup Bandwidth - Dropout Bandwidth) * Center FrequencyUpper Dropout Freq = (1 + Pickup Bandwidth + Dropout Bandwidth) * Center Frequency
LowerDropoutFreq
UpperDropoutFreq
FUNCTIONS
102 Rev 1.5 prdJune 13, 2006
Sensor – Phase Rotation
Sensor is optionally enabled Compares source’s phase rotation to System Phase
Rotation setting when source is at least 60% voltage and 30Hz
Once sensor is picked up (good), sensor does not recheck until voltage/freq drop below and then back above 60%, 30Hz
Settings:– System Phase Rotation– Dropout Delay
Pickup is instantaneous
FUNCTIONS
103 Rev 1.5 prdJune 13, 2006
Sensor – Loss of Phase
Sensor is optionally enabledDropout (bad) when any phase angle between
LL phasors does not fall within 90 to 150 degrees
Settings:– Dropout Delay
Pickup is instantaneousNot same as negative sequence voltage
FUNCTIONS
104 Rev 1.5 prdJune 13, 2006
Sensors - Misc
If Main Breaker Tripped input is active, source is Not Available
If Main Breaker Fail to Close fault state is active, source is Not Available
If Main Breaker Position Contact fault state is active and current does not indicate breaker is closed, source is Not Available
FUNCTIONS
105 Rev 1.5 prdJune 13, 2006
Sensors – Source Unique
Utility source additional sensor:• Utility Source Failure switch input
Genset source additional sensor:• Genset Online Capacity Sensor *• sensor picks-up when online kW capacity exceeds
threshold. Once gen main is closed, sensor stops checking.
FUNCTIONS
106 Rev 1.5 prdJune 13, 2006
Sensors Setup (utility)
FUNCTIONS
107 Rev 1.5 prdJune 13, 2006
Sensors Setup (genset)
FUNCTIONS
108 Rev 1.5 prdJune 13, 2006
Operating Mode
Evaluates utility source status, test start / stop, and extended parallel start / stop to decides whether or not to start or stop the gensets
Prioritizes and lets PTC core logic know which direction a transfer should be going, if any
FUNCTIONS
109 Rev 1.5 prdJune 13, 2006
PTC State Machine
The core of the power transfer controlFour possible states defined by four possible
combinations of GM and UM breaker positions In each state, logic unique to that state decides
whether to turn on synchronizer and whether to open or close a breaker
FUNCTIONS
110 Rev 1.5 prdJune 13, 2006
PTC State Machine
FUNCTIONS
NoCommand
CloseUtility
CloseGenset
NoCommand
OpenUtility
CloseGenset
NoCommand
CloseUtility
OpenGenset
NoCommand
OpenUtility
OpenGenset
NOSOURCE
CONNECTED
UTILITYCONNECTED
GENSETCONNECTED
PARALLELED
T2B
T1B T4A
T3A
T4B
T1A T2A
T3B
N1N2
N3
N4
U1
U2
U3
U4
P1
P2
P3
P4
G1
G2
G3
G4
PTCNOT
ENABLED
PowerupT-INIT
T99
T0
111 Rev 1.5 prdJune 13, 2006
Timers
Start TimerStop TimerTimer in each PTC State:
– Programmed Transition Timer (No Source Connected)
– Transfer Timer (Utility Connected)
– Retransfer Timer (Genset Connected)
– Maximum Parallel Timer (Paralleled)
FUNCTIONS
112 Rev 1.5 prdJune 13, 2006
Override
Override switch input (hardwired or Modbus) Forces pending action to occur immediately Useful in certain situations / applications Overrides (bypasses) the following:
– Transfer Inhibit– Retransfer Inhibit– Start Delay– Transfer Delay– Retransfer Delay
Does NOT override:– Stop Delay– Programmed Transition Delay– Maximum Parallel Time– Gen Main CB Inhibit– Utility Main CB Inhibit
FUNCTIONS
113 Rev 1.5 prdJune 13, 2006
Synchronizer & Sync Check
Synchronizer On / OffSynchronizer ControlSync CheckSynchronizer Diagnostics
FUNCTIONS
114 Rev 1.5 prdJune 13, 2006
Synchronizer On / Off
In all cases, both sources must be ‘available’ for the synchronizer to run
With PTC function, Synchronizer turns on automatically when needed if in ‘Auto’ mode
In ‘Manual’, Sync Enable input must be active to turn on
FUNCTIONS
115 Rev 1.5 prdJune 13, 2006
Synchronizer Control
Synchronizer matches phase, frequency and voltage of gen bus to utility bus
Freq Match Closed loop PI drives kW load share lines to match freq/phase
Volt Match Closed loop PI drives kVAR load share lines to match voltage
Tuning is fairly tolerant; field adjustment not expected to be required normally
Performance is very good – much improved over existing analog master synchronizer
FUNCTIONS
116 Rev 1.5 prdJune 13, 2006
Synchronizer Control
Two Synchronizing Options:– Phase Sync (default) => gen bus phase is driven to match utility
bus
– Slip Frequency => gen bus frequency is driven to be fixed Hz higher or lower than utility bus (e.g. 0.1Hz)
Use Slip Freq option with difficult to sync applications such as natural gas
Nominal System Frequency = 45-65 Hz– Used by synchronizer – must be set to nominal operating
genset frequency
FUNCTIONS
117 Rev 1.5 prdJune 13, 2006
Sync Check
Permissive sync check with adjustable frequency, phase, voltage and dwell time window
Runs independently of synchronizer PTC function uses this to decide when to close breaker Can get sync check output by mapping sync event to a
configurable output (#6 by default) In synchronizer only applications, can also enable sync
check individually for different dead bus scenarios (dead bus sensor is included)
FUNCTIONS
118 Rev 1.5 prdJune 13, 2006
Synchronizer Diagnostics
Fail to Synchronize Warning = synchronizer has been on for Fail to Sync time (adjustable) without achieving sync check ok
Synchronizer Output Limit Warning = freq bias or volt bias drive output has been at maximum and unable to achieve sync
FUNCTIONS
119 Rev 1.5 prdJune 13, 2006
Sync Setup
FUNCTIONS
120 Rev 1.5 prdJune 13, 2006
Load Control
kW and kVAR are controlled during soft transfers and extended paralleling
MCM3320 has one analog output for kW, one for kVAR
MCM3320 drives all gensets to same % command value
PCC Genset controllers perform ramping and load governing
FUNCTIONS
121 Rev 1.5 prdJune 13, 2006
Load Control
Soft LoadingExtended Paralleling kW Control kVAR ControlDiagnosticsPerformance / Tuning
FUNCTIONS
122 Rev 1.5 prdJune 13, 2006
Soft Loading
Closed transition transfer / retransfer MCM3320 either drives load set line to +5V or 0V
depending on desired ramp direction PCC genset controllers perform the ramp based on their
own ramp time settings PCC genset controllers are doing the closed loop control
of kW and kVAR (load governing) MCM3320 disconnects appropriate source when it
senses kW below threshold
FUNCTIONS
123 Rev 1.5 prdJune 13, 2006
Extended Paralleling
Many options for how / where to control kW and kVAR
Open loop or closed loop optionsControl points at gen bus or utility busSetpoints from analog input, trim setting, or
ModbusMCM3320 controls load without knowledge of
which gensets are online
FUNCTIONS
124 Rev 1.5 prdJune 13, 2006
kW Control Options
Gen Bus % Level (open loop)
» MCM3320 puts out fixed %kW command
Gen Bus kW (closed loop)
» MCM3320 adjusts output command to get desired kW at gen bus metering point
Gen Bus kW w/Utility Constraint (closed loop)
» MCM3320 adjusts output command to get desired kW at gen bus metering point subject to maintaining utility kW greater than a threshold
Utility Bus kW (closed loop)
» MCM3320 adjusts output command to get desired kW at utility bus metering point
FUNCTIONS
125 Rev 1.5 prdJune 13, 2006
kVAR Control Options
Genset Controllers» MCM3320 does nothing» ONLY OPTION WHICH WILL WORK ON PCC3100 GENSETS
Gen Bus % Level (open loop)» MCM3320 puts out fixed %kVAR command
Gen Bus Power Factor (open loop)» MCM3320 puts out %kVAR command based on power factor
setting and what is currently being put out on the %kW command output
Gen Bus kVAR (closed loop)» MCM3320 adjusts output command to get desired kVAR at gen
bus metering point
Gen Bus Power Factor (closed loop)» MCM3320 adjusts output command to get desired power factor at
gen bus metering point
FUNCTIONS
126 Rev 1.5 prdJune 13, 2006
kVAR Control Options (cont.)
Utility Bus kVAR (closed loop)» MCM3320 adjusts output command to get desired
kVAR at utility bus metering point
Utility Bus Power Factor (closed loop)» MCM3320 adjusts output command to get desired
power factor at utility bus metering point
FUNCTIONS
127 Rev 1.5 prdJune 13, 2006
Load Setpoints - Source
kW, kVAR/PF setpoints can come from hardwired analog inputs or internal setting
Internal setting can be changed from Inpower, HMI, or Modbus
analog input (hardwired)
internal
process value
setpoint source
FUNCTIONS
128 Rev 1.5 prdJune 13, 2006
Load Setpoints – Scaling
%kW, kVAR, Power Factor vs. Input Voltage
0
10
20
30
40
50
60
70
80
90
100
110
120
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 3.25 3.5 3.75 4 4.25 4.5 4.75 5
Input Voltage, Vdc
%kW
/ %
kVA
R
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
Po
wer
Fac
tor
%kW/kVAR
PowerFactor
FUNCTIONS
129 Rev 1.5 prdJune 13, 2006
Load Setpoints – Scaling
If open loop load control, scaling of hardwired analog input is per graph
If closed loop load control, kW command level = % from graph * Total System Capacity
If power factor control, scaling always follows red line Definitions:
– Total System Capacity = sum of individual genset kW ratings– %kW = kW / Total System Capacity– %kVAR = kVAR / (Total System Capacity / 0.8)
FUNCTIONS
130 Rev 1.5 prdJune 13, 2006
Load Control Diagnostics
kW Load Control Output Limit Warning» kW command output has been at minimum or
maximum value for longer than 60 seconds
» Only applicable to closed loop modes
» means that the desired kW setpoint cannot be achieved either due to inadequate capacity or operator error
kVAR Load Control Output Limit Warning» analogous to kW diagnostic
» Means that the desired kVAR or Power Factor setpoint cannot be achieved either due to inadequate capacity or operator error
FUNCTIONS
131 Rev 1.5 prdJune 13, 2006
Load Control Setup (kW)
FUNCTIONS
132 Rev 1.5 prdJune 13, 2006
Load Control Setup (kVAR)
FUNCTIONS
133 Rev 1.5 prdJune 13, 2006
Scheduler
Scheduler operates based on up to 12 programs and 6 exceptions
Each program specifies a day of the week/time to start, how long to run, how often to repeat, and what mode to run in
Run modes are: test without load, test with load, and extended parallel
Each exception is defined by a start date/time, duration, and repeat interval
An exception will block a scheduled program from starting during the exception period
Scheduler will not run if real time clock has not been set
FUNCTIONS
134 Rev 1.5 prdJune 13, 2006
Scheduler
To use Extended Paralleling with the Scheduler, the Extended Parallel Enable must be set to Enabled
If program run mode = Extended Parallel, but Extended Parallel Enable = Disabled, there will never be extended paralleling (nothing will happen when program becomes active)
Some applications do not allow extended paralleling, so this provides one setting to disable all extended paralleling
FUNCTIONS
Extended Paralleling Clarification
135 Rev 1.5 prdJune 13, 2006
Scheduler
Scheduler will follow the Program Run Mode setting– If Program #1 Run Mode = With Load, system will run with load– If Program #1 Run Mode = Without Load, system will run without
load The setting of Test With Load Enable variable does NOT apply
to Scheduler– E.G. If Test With Load Enable = Disabled, but Program #1 Run
Mode = With Load, program will run with load Test With Load Enable only applies to Test Start switch input
(hardwired or Modbus or HMI) This may be confusing because it is different than how the
Extended Parallel Enable is used by the MCM3320
FUNCTIONS
Test With / Without Load Clarification
136 Rev 1.5 prdJune 13, 2006
Scheduler Setup
FUNCTIONS
137 Rev 1.5 prdJune 13, 2006
Program Overlapping
Do not overlap programs; overlapped program will be ignored
FUNCTIONS
Program1
Program2
Program1 Program2
Program1 Program2
Program1 runs for its entire periodProgram2 does NOT run
Program1 runs and ends. Some timelater Program2 runs and ends.
Program1 runs and ends. Program2 startsat same minute Program1 ends.
138 Rev 1.5 prdJune 13, 2006
Exception Operation
Exceptions only block the START of a program; a program started outside of the exception period will not be canceled by an exception
FUNCTIONS
Program1
Exception1Program1 runs for its entire period
Program1
Exception1Program1 does NOT run
139 Rev 1.5 prdJune 13, 2006
Priorities Utility Failure will supersede any scheduler program An active program will resume when the utility source has become
available again Two examples are shown below
FUNCTIONS
Program1 (no load)
Utility Failed
EXAMPLE#1:Utility fails while gensets running no loaddue to Program1. System will transfer loadto gensets. When utility returns, system loadwill remain on gensets until Program1 ends.(It does NOT retransfer until Program1 ends.)
Program1 (extended parallel)
Utility Failed
EXAMPLE#2:Utility fails while gensets running in parallelto utility due to Program1. System will openutility main breaker. When utility returns,system will sync across utility main, closeutility main and continue in parallel untilProgram1 ends.
UMBreaker
GMBreaker
Closed
Open
Closed
Open
UMBreaker
GMBreaker
Closed
Closed
Open
Open
Open
Open
Closed
Closed
140 Rev 1.5 prdJune 13, 2006
Clock & DST Setup
FUNCTIONS
141 Rev 1.5 prdJune 13, 2006
Operating Sequences
Normal Sequences1
Utility Fail / Return
Extended Parallel
Test (with or without load)
Sequences are affected byTransition Type
Operating priority
Faults2
1Refer to MCM3320 Operating Sequences document for listing of normal sequences2Refer to MCM3320 Abnormal Conditions Operation document for description of control reaction for
fault conditions.
FUNCTIONS
142 Rev 1.5 prdJune 13, 2006
Normal Sequence Example
Scenario:
Transfer Pair; Soft Closed Transition; Utility Fail / Return
1. Utility Failure2. TD Start3. Gensets Start / Close4. Gen Bus Available5. TD Transfer6. Open Utility Main7. TD Program Transition8. Close Gen Main9. Loads Powered by Gen Bus
10.Utility Available11.TD Retransfer12.Synchronizer On13.Sync Check OK14.Close Utility Main15.Ramp Unload Gensets16.Open Gen Main17.TD Stop18.Stop Gensets19. Loads Powered by Utility
FUNCTIONS
143 Rev 1.5 prdJune 13, 2006
Abnormal Condition ExampleScenario: Transfer Pair; Soft Closed Transition; Test With Load; UM Fails to Open
1. Test Start Initiated2. TD Start3. Gensets Start / Close4. Gen Bus Available5. TD Transfer6. Synchronizer On7. Sync Check OK8. Close Gen Main9. Ramp Load Gensets
10.Utility Unloaded11.Open Utility Main12.Utility Main Fails to Open13.Open Gen Main14.Gen Main Opens15.Open Utility Canceled16.Loads Powered by Utility17.Gensets Remain Running18.User Intervention Required
FUNCTIONS
144 Rev 1.5 prdJune 13, 2006
Operating Priorities
Operating priorities from highest to lowest:1. Utility Failure
2. Extended Parallel
3. Test
FUNCTIONS
145 Rev 1.5 prdJune 13, 2006
Load Demand
Supports 2, 3, or 4 genset systems 4 hardwired outputs to drive gensets load demand stop 4 hardwired inputs to read genset paralleling breaker
positions Shuts down/Restarts gensets based on genset bus total
kW load level Adjustable shutdown / restart thresholds and time delays Genset Sequence configurable as Fixed Sequence or
Run Hours Based
FUNCTIONS
146 Rev 1.5 prdJune 13, 2006
Load Demand Interconnect
FUNCTIONS
G1PCC3xxx
G2PCC3xxx
G3PCC3xxx
G4PCC3xxx
Gen1 Load Demand
Gen1 Breaker Position
Gen2 Load Demand
Gen2 Breaker Position
Gen3 Load Demand
Gen3 Breaker Position
Gen4 Load Demand
Gen4 Breaker Position
MCM3320
Genset Bus Currents
Genset Bus Voltages
Remote Start
147 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Genset Sequence defines shutdown order:– GenA, GenB, GenC, GenD
GenA always runs; GenD is first to shut down, last to restart, etc.
Sequence Determination:– Fixed Sequence, or Run Hours Based
Fixed Sequence is set by the operator Run Hours Based Sequence changes dynamically as run
hours accumulate on gensets – system attempts to equalize running hours on all gensets
FUNCTIONS
148 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Fixed Sequence• GenA = Gen2
• GenB = Gen1
• GenC = Gen4
• GenD = Gen3
Sequence can be changed any time – even when load demand is operating
Must issue “Refresh Sequence” command after defining the new sequence in order for it to take effect (HMI211 does this for you).
On change, only the appropriate gensets will restart, then after time delay, unnecessary gensets stop in sequence
FUNCTIONS
149 Rev 1.5 prdJune 13, 2006
Load Demand Operation Run Hours Based Sequence
• Gen1 Online Time = 100 Hr GenA (lowest hr)• Gen2 Online Time = 250 Hr GenC• Gen3 Online Time = 150 Hr GenB• Gen4 Online Time = 400 Hr GenD (highest hr)
Sequence is sorted by Online Time when:• Load Demand Enable changed to Enable• Load Demand Type changed to Run Hours Based• Refresh Sequence command changed to “Refresh”
Run Hours Differential setting will determine how frequently gensets are restarted due to hours accumulation – typically set to 50hr
Online Time is accumulated by the MCM3320 based on amount of time that GenX paralleling breaker is closed
MCM3320 does not get running hours from genset control…but operator can enter hours into MCM3320 as starting point
FUNCTIONS
150 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Normal Operation Steps1. Gensets start and come online2. Gen Main Breaker Closes (if present)3. Load Demand times “Initial Delay”4. Load Demand monitors Load vs. Gensets5. Load Demand times “Shutdown Delay” if load allows
shutting down a genset6. Load Demand tells lowest priority genset to shutdown7. Load Demand continues to monitor load8. Load Demand stops additional gensets as load allows9. Load Demand restarts gensets as load requires10. Load Demand restarts appropriate gensets if sequence
changes due to operator or run hours (as configured)
FUNCTIONS
151 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Shutdown Decision [Genset Bus Load < Shutdown Percent * (Total Online
Capacity – kW Rating of Next Genset to Shutdown)] = true continously for Shutdown Delay
Restart Decision Genset Bus Load > Restart Percent * (Total Online
Capacity) Sequence has changed due to operator or run hours Genset Bus is overloaded Genset(s) have failed Load Demand Enable changed to Disabled MCM3320 has detected a problem with AC metering
FUNCTIONS
152 Rev 1.5 prdJune 13, 2006
Load Demand Operation
FUNCTIONS
Online Capacity vs. Total Load
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 500 1000 1500 2000 2500 3000 3500 4000
Total Load, kW
On
line
Cap
acit
y, k
W
4 Gensets each rated at 1000kWShutdown Percent = 60%Restart Percent = 80%GenA = Gen1GenB = Gen2GenC = Gen3GenD = Gen4
Gen4 Stop
Gen3 Stop
Gen2 Stop
Gen4 Restart
Gen3 Restart
Gen2 Restart
Load=Capacity
153 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Overload Operation If Genset Bus Overload fault occurs, ALL load demand stopped
gensets will restart Condition is latched until overload no longer exists and operator
resets the fault Individual Genset Failure Operation
If a single genset fails, that genset is removed from the load demand logic; fault occurs
If available, a stopped genset will restart to replace the failed genset
When the failed genset comes back online, it will be readded to load demand logic and normal operation will resume
Genset Bus Failure Operation If the genset bus fails (goes “Not Available”), ALL load demand
stopped gensets will restart
FUNCTIONS
154 Rev 1.5 prdJune 13, 2006
Load Demand Operation
Minimum Online Capacity Optional function allows operator to keep more than one
genset running at all times Minimizes exposure to a single genset failure if load
demand has shut down all except one genset Example: 4 gensets rated at 1000kW each; Set Load
Demand Minimum Online Capacity = 2000kW 2 gensets will always remain running
FUNCTIONS
155 Rev 1.5 prdJune 13, 2006
Load Demand Notes
PCC3100, PCC3200/1 only support load demand in isolated bus mode
PCC3300 will support load demand in utility parallel and isolated bus mode
MCM3320 Load Demand function operates both in isolated and utility parallel modes
FUNCTIONS
156 Rev 1.5 prdJune 13, 2006
Load Demand Setup
FUNCTIONS
157 Rev 1.5 prdJune 13, 2006
Load Add ShedSupports up to 4 gensets, 6 levels of Add, 6 levels of
Shed, and status for up to 6 breakers or ATS Each Breaker or ATS can be assigned to any Add
level and any Shed levelRequires AUX101 and AUX102 moduleAdds levels in sequence as gensets (up to 4) come
online; remaining add levels are timedSheds levels in timed sequence when Genset Bus
Overload condition detected; shed stops when overload is corrected
FUNCTIONS
158 Rev 1.5 prdJune 13, 2006
Load Add Shed Interconnect
FUNCTIONS
MCM3320
Load 1
Add Shed
Load 2Add Shed
Load 3Add Shed
Load 4Add Shed
AUX101 Input1 Input2 Input1 Input2 Input1 Input2 Input1 Input2
Load 5Add Shed
Load 6Add Shed
AUX102 Input1 Input2 Input1 Input2
Ribbon
Cable
'a' contact'tripped'contact
BREAKER ATSnormalsourceposition
emergencysourceposition
Relays are shown in de-energized state.Add relays energize to add load. Two second pulse for Breaker; Continuous for ATS Shed relays energize to shed load. Continuous for both Breaker and ATS.
B+GNDRS485-ARS485-B
PCCNetPort
159 Rev 1.5 prdJune 13, 2006
Load Device = Breaker
FEEDER BREAKER CONTROLAdd and Shed Relays have FormC contactsAdd Relay energizes for 2 seconds to add the load; typically
used to drive breaker close coilShed Relay energizes continuously to shed the load; typically
used to drive breaker open coilUse of breaker pilot relays is recommendedAUX101 Relays: 30Vdc/250Vac,
N.O.=5A N.C.=3AAUX102 Relays: 30Vdc/250Vac, 2A
FUNCTIONS
160 Rev 1.5 prdJune 13, 2006
Load Device = Breaker
FEEDER BREAKER MONITORTwo inputs available to monitor breakerInput 1 for breaker position from ‘a’ contactInput 2 for breaker tripped status from overcurrent trip contactBreaker monitoring is provided for operator benefit only;
connections are OPTIONAL; Load Add Shed function does not use this information
FUNCTIONS
161 Rev 1.5 prdJune 13, 2006
Load Device = ATS
ATS CONTROLAdd and Shed Relays have FormC contactsAdd Relay energizes continuously to add the load; typically
used to tell ATS that it can transfer to gensetShed Relay energizes continously to shed the load; typically
used to tell ATS to shed load (go to neutral position)Use of pilot relays may not be required
FUNCTIONS
162 Rev 1.5 prdJune 13, 2006
Load Device = ATS
ATS MONITORTwo inputs available to monitor ATSInput 1 for Source 1 switch positionInput 2 for Source 2 switch positionATS Position monitor = No Source Connected, Source 1
Connected, Source 2 ConnectedATS monitoring is provided for operator benefit only;
connections are OPTIONAL; Load Add Shed function does not use this information
FUNCTIONS
163 Rev 1.5 prdJune 13, 2006
Load Level Assignment
6 Add Levels available: 1,2,3,4,5,66 Shed Levels available: 0,1,2,3,4,5Loads can be assigned to any Add Level and any
Shed LevelAdd assignment not required to match Shed
assignmentAdd Levels add in sequence 1,2,3,4,5,6Shed Levels shed in sequence 1,2,3,4,5Loads assigned to Shed Level 0 are never shedLoad Devices can be any combination of Feeder
Breaker or Automatic Transfer Switch (ATS)
FUNCTIONS
164 Rev 1.5 prdJune 13, 2006
Load Level Assignment
FUNCTIONS
165 Rev 1.5 prdJune 13, 2006
Load Add Shed Operation
Load Add Shed ModesAutomatic Genset Load AddAutomatic Genset Load ShedManual Load Add / Shed / RestoreAutomatic Utility Load Add
FUNCTIONS
166 Rev 1.5 prdJune 13, 2006
Automatic Genset Load Add Automatic Genset Load Add Example:
3 gensets; 6 add levels
FUNCTIONS
Gen2Online
Gen1Online
Gen3Online
Level 1Added
Level 2Added
Level 3Added
Level 4Added
Level 5Added
Level 6Added
TIME
Genset BusLoad AddDelay
Genset BusLoad AddDelay
Genset BusLoad AddDelay
Timed AddAfter Last GensetIs Online
167 Rev 1.5 prdJune 13, 2006
Automatic Genset Load Add
NOTE: If all gensets do not come online, the Load Add sequence will stop and remaining add levels will not be added automaticallyOption1: Operator gets all gensets running – load add
sequence completes automatically
Option2: Operator manually adds any remaining levels desired
Option3: Configure “Required Online Capacity” to force an automatic timed add of the remaining levels when online capacity is greater than or equal to this setting (assumes total load < this setting)
FUNCTIONS
168 Rev 1.5 prdJune 13, 2006
Automatic Genset Load Shed
Automatic Genset Load Shed Example
FUNCTIONS
GensetBusOverloadCondition =ACTIVE
ShedLevel 2ON
LoadShedDelay
GensetBusOverloadCondition = INACTIVE
LoadShedDelay
TIME
ShedLevel 1ON
169 Rev 1.5 prdJune 13, 2006
Automatic Genset Load Shed
Shed Levels which are ON can only be restored by: Option1: Manual restore by operator
Option2: Retransfer to Utility or Genset Main Breaker (or all genset paralleling breakers) opened and reclosed
FUNCTIONS
170 Rev 1.5 prdJune 13, 2006
Manual Load Add / Shed / Restore
When Load Bus is fed by Genset Bus, Load Add Shed feature can be put into “Manual” mode through HMI, Setup Tool, or Modbus
This is NOT the same setting as the Auto/Manual switch for the Main Breakers
Manual mode allows operator to:Turn ON specific Add Levels which have not addedRestore specific Shed Levels which are ONTurn ON Shed Levels which are OFF
FUNCTIONS
171 Rev 1.5 prdJune 13, 2006
Manual Load Add / Shed / Restore
Restoring a Shed Level does two things:Turns off the shed relays assigned to that Shed LevelTurns on the Add relays assigned to that SHED LEVEL (2
sec pulse for Breaker; continous for ATS)
Manual mode is automatically exited if certain events occur: overload, retransfer to utility, etc…
FUNCTIONS
172 Rev 1.5 prdJune 13, 2006
Automatic Utility Load Add
Upon reconnection to utility source: all Shed Levels will be turned off all Add Levels will be added in sequence
Utility add delay adjustable from 0 to 60 seconds
FUNCTIONS
All ShedLevelsOFF
UtilityMainBreakerCloses
AddLevel 3ON
AddLevel 4ON
AddLevel 5ON
AddLevel 6ON
TIME
Utility BusLoad AddDelay
Utility BusLoad AddDelay
Utility BusLoad AddDelay
AddLevel 1ON
AddLevel 2ON
Utility BusLoad AddDelay
Utility BusLoad AddDelay
1/4 sec
173 Rev 1.5 prdJune 13, 2006
Load Add Shed Setup
FUNCTIONS
174 Rev 1.5 prdJune 13, 2006
Modbus RTU
RS485 OR RS232MCM3320 is SlaveConfigurable Address, Baud, ParityRegister Map PublishedSetup, Control, and Monitor of MCM3320sSteve Prater has developed some Quantum /
Momentum PLC code
FUNCTIONS
175 Rev 1.5 prdJune 13, 2006
Modbus Register Map
40xxx -- Genset control registers 41xxx -- Transfer switch control registers 42xxx -- Master control registers (MCM3320) 4x0xx -- General data registers for genset bus 4x1xx -- General data registers for utility bus 4x2xx -- Configuration and status registers 4x3xx -- Settings – Block 1 4x4xx -- Settings – Block 2 4x5xx -- Bitmaps 4x6xx -- Switch IO 4x7xx -- Status registers continued
FUNCTIONS
176 Rev 1.5 prdJune 13, 2006
Modbus Register Map
Modbus Address System Name Modbus
Access Specifications Description
42300 System Topology Read/Write
0: Master Synchronize Only 1: Isolated Bus w/out GM 2: Isolated Bus w/GM 3: Common Bus 4: Transfer Pair Default: Master Synchronize Only
Sets the system topology. THIS RESETS OTHER APP CONFIG SETTINGS!
42301 Transition Type Read/Write
0: Open Transition 1: Hard Closed Transition 2: Soft Closed Transition Default: Open Transition
sets the type of transition that will be used
42302 Extended Parallel Enable Read/Write 0: Disabled 1: Enabled Default: Disabled
use to enable extended paralleling operation
FUNCTIONS
177 Rev 1.5 prdJune 13, 2006
Modbus RTU
Diagnostic Tools:• Message Counters• Exception Counter• CRC Counter
Available through InPower or by Modbus Diagnostic Function (code 08)
FUNCTIONS
178 Rev 1.5 prdJune 13, 2006
Faults & Events
There are faults (warnings) and events» Fault Example: UM Fail to Close» Event Example: Utility Bus Available
Each has a code number (see previous slide for list)
Three 32 bit Bitmaps of fault/event states available on Modbus
Code numbers can be used for mapping to any of 8 configurable low-side driver outputs
NOTE: When Fault 343 (Hardware Failure) is mapped to a low-side output, it is inverted. Output is ON when hardware is OK.
Fault states are latched until fault reset and condition is inactive
Events are not latched Common Warning is an event which is active if any fault
states are active
FUNCTIONS
179 Rev 1.5 prdJune 13, 2006
Faults & Events
Fault (Warning) Logic -- Ladder Diagram
Fault Condition
Fault StateReset
Fault State
FUNCTIONS
180 Rev 1.5 prdJune 13, 2006
Faults & Events Variables Available
» Three 32bit Bitmaps of fault / event states» Current Fault Code» Active Fault Code List» Active Event Code List» Historical Information Tables – see ahead
Fault Troubleshooting Document
FUNCTIONS
Code Name Type Meaning Hints
1444 Genset Bus Overload
Warning Total Kw delivered by Genset Bus is greater than or equal to Genset Bus kW Overload Threshold continuously for Genset Bus kW Overload Delay AND/OR Underfrequency Delta ( System frequency - Current Genbus frequency ) is greater than or equal to Genset Bus Underfrequency Overload Threshold continuously for Genset Bus Underfrequency Overload Delay.
Make sure gensets`s Kw power is greater than the one demanded by connected load . Check for faulted gensets. Use different meters from the built-in ones furnished in MCM3320.
Make sure meter calibration is OK. Check PT`s and CT`s ratios are well set in MCM3320. Make
sure PTs and CTs are operating properly. Verify that PT`s and CT`s rated values match the ones set in
MCM3320 and your system actual rated values. Make sure there is no low-frequency conditions on GenBus
due to poor quality fuel. Check your fuel supply for inappropriate conditions at
components – dirty filters, pipe size,etc.
181 Rev 1.5 prdJune 13, 2006
Historical Data
Non-volatile historical data– Controller On-Time
– Fault/Event history
– System state history
– Energy accumulators
Removal of B+ does not result in any loss of data
FUNCTIONS
182 Rev 1.5 prdJune 13, 2006
System State History
System State History» Records 20 most recent system states with COT
stamp
» Can use to track past sequence of events
FUNCTIONS
183 Rev 1.5 prdJune 13, 2006
Energy Accumulators
Per phase quantities recorded for both sources:» +kWh
» -kWh
» +kVARh
» -kVARh
» kVAh
Positive = energy delivered by the source Negative = energy absorbed by the source Accumulators can be reset Totalized values also available (calculated by MCM3320)
FUNCTIONS
184 Rev 1.5 prdJune 13, 2006
HMI 211
FUNCTIONS
185 Rev 1.5 prdJune 13, 2006
HMI 211 - LEDs
Utility Parallel = both breakers closed Lockout = System Lockout is active Warning = any warning fault state active
Remote Start = 3320 start output active Auto = auto/manual switch input = auto Manual = auto/manual switch input = manual
FUNCTIONS
186 Rev 1.5 prdJune 13, 2006
HMI 211 – Home Screen
MENU softkey: enter main navigation treeRESET softkey: reset/ack faults
FUNCTIONS
187 Rev 1.5 prdJune 13, 2006
HMI 211 – Fault PopUp
Faults pop up on screen when they occurAcknowledge with ▼ softkey (does not reset)Reset with RESET softkey
FUNCTIONS
188 Rev 1.5 prdJune 13, 2006
HMI 211 – System Op/Control
CONTROL menu tree includes user friendly screens for starting / stopping system and making operating point adjustments
Password for making Adjustments is “574”
FUNCTIONS
189 Rev 1.5 prdJune 13, 2006
HMI112 Bargraph
Bargraph Hardware Device ID Setup:
1. Press/hold button on back of bargraph until lower right LED(s) illuminate (~5sec).
2. Press again to cycle through 1, 2, 3, 4 LEDs. Genset Bus = 1 LED on, Utility Bus = 2 LEDs on.
3. Number of LEDs illuminated = device ID.
4. Wait 5 sec for control to resume operation.
• Configure Utility Scaling with InPower
• Update rate up to 10Hz; 1Hz minimum
FUNCTIONS
190 Rev 1.5 prdJune 13, 2006
HMI112 Setup
FUNCTIONS
191 Rev 1.5 prdJune 13, 2006
SYSTEM SETUP
InPower V5.5 Setup ToolPCC3xxx Genset Controller Setup
192 Rev 1.5 prdJune 13, 2006
InPower V5.5 Setup Tool
Screen by Screen ReviewUser Participation (Demo Mode or Live with
Controller)Note that Scheduler and Real Time Clock
screens will be available as a patch
SETUP
193 Rev 1.5 prdJune 13, 2006
PCC3xxx Genset Controller Setup
Configure for Utility Multiple even if only one genset Bus PT module connected on load side of genset
paralleling breaker Set TD Start, TD Stop = 0 if want MCM3320 to control
time delays (else time delays are additive) Set Load Govern Ramp Times to be compatible with
Maximum Parallel Time setting in MCM3320
SETUP
194 Rev 1.5 prdJune 13, 2006
PCC3100 Genset Controller Setup
When using MCM3320 with PCC3100s, use InPower to search on PCC3100 for parameter called "Reactive power scale". Change it from 695 to 820. Save it.
If PCC3100 is in system with PCC3200/1, set PCC3100 kVAR Balance = 29 (InPower or front panel Setup)
If these changes are not done, may experience reverse kVAR (loss of field) shutdowns or inability to synchronize
SETUP
195 Rev 1.5 prdJune 13, 2006
MCM3320 Simulator
Simulator OverviewSimulate Operating Scenarios
– Utility Fail / Return Soft CT
– Synchronizer Performance Plotting
– Test With / Without Load
– Extended Paralleling
– Faults
196 Rev 1.5 prdJune 13, 2006
MCM3320 Simulator Overview
Breaker faultsimulation
MCM3320switchinputs
MCM3320switch inputs
Gen is availablewhen genset
breaker closes
Utility buscontrol
SIMULATOR
197 Rev 1.5 prdJune 13, 2006
MCM3320 Simulator Overview
MCM3320 simulator Genset simulator
Load
Alternator
Engine
MCM3320 control PCC3100/3200
Load
Busvoltage
SIMULATOR
198 Rev 1.5 prdJune 13, 2006
InPower
199 Rev 1.5 prdJune 13, 2006
InPower DOWNLOAD
“Initial Calibration”» All trim values will revert to default settings
» Any custom settings will be lost
» Historical data will be lost
» Factory calibration data will NOT be lost
» Field calibration of voltage / current will be lost
“Update Calibration” (recommended)» Use to update controller firmware without altering
your settings or losing historical data
» Field calibration of voltage / current will remain
INPOWER
200 Rev 1.5 prdJune 13, 2006
VARIABLES
Trims (screwdriver symbol)
» Variables which can be permanently saved in EE» Nearly all settings are trims» Writing to a trim variable changes its RAM value
only» Controller always uses RAM value to operate from» Save command required to get RAM value saved in
non-volatile memory» On power-up, RAM value is loaded from EE
Volatiles (light switch symbol)
» Variables which are writeable, but only exist in RAM» On power-up, RAM value is loaded with hard-coded
default
INPOWER
201 Rev 1.5 prdJune 13, 2006
VARIABLES
Monitor Points (magnifying glass symbol)
» Read only variables in RAM
» E.G.: Utility L1-L2 Voltage
INPOWER
202 Rev 1.5 prdJune 13, 2006
Applications
Application FlexibilityParticipant Application Examples
203 Rev 1.5 prdJune 13, 2006
Application Flexibility
MCM3320 is not a PLC MCM3320 is designed to be flexible and work for
most applications Alternatives for special requirements:
1. Use PLC
2. Be clever with 3320 capabilities
3. Ask for changes to 3320
Changes to 3320 will only be implemented if change is universally useful and resources can be assigned to implement the change
APPLICATIONS
204 Rev 1.5 prdJune 13, 2006
Application Flexibility
Example1: What if the MCM3320 fails ? Map Fault Code 343 (Hardware Failure) to one of
the Configurable Low-Side Outputs (Default = Output 8)
Connect a relay to this output For this particular fault, logic is inverted: output is
energized when fault is Inactive If MCM3320 experiences an internal failure or loses
B+ power, the relay will de-energize Use relay contacts to perform desired action For example, if using Load Demand, use relay to
open circuit all load demand drives so that all gensets will run
APPLICATIONS
205 Rev 1.5 prdJune 13, 2006
Application Flexibility
Example2: What if I don’t want a Transfer to Gensets to occur if I get an AC Metering Failure (1335) ?
Map Fault Code 1335 to one of the Configurable Low-Side Outputs
Connect this output to the Transfer Inhibit input
APPLICATIONS
206 Rev 1.5 prdJune 13, 2006
Application Flexibility
Example3: What if I don’t want the Transfer or Retransfer Time Delays to occur for an Extended Parallel run ?
Turn on the Override switch input (hardwired or Modbus) at the same time as turning on the Extended Parallel switch input (hardwired or Modbus)
APPLICATIONS
207 Rev 1.5 prdJune 13, 2006
Application Examples
Participant Examples ?
APPLICATIONS
208 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 10 low voltage 4 diesel gensets 6 feeder breakers with 6 level capacity based load add/shed control Extended Parallel Control Normal Standby Operation Load demand based on engine run hours
Does this system require a PLC?
Utility Source 1
52-UM1
G1
52-G1
52-GM1
GN
52-GN
52-F1 52-FN . . .
. . .
G2
52-G2
YES
209 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 9 medium voltage 5 diesel gensets 6 feeder breakers with simple load add/shed control Extended Parallel Control Normal Standby Operation Load demand based on customer set fixed sequence
Does this system require a PLC? Utility
Source 1
52-UM1
G1
52-G1
G2
52-G2
52-F1 52-FN . . .
. . .
GN
52-GN YES
210 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 10 low voltage 4 diesel gensets 24 feeder breakers with 6 level simple load add/shed control Extended Parallel Control Normal Standby Operation Load demand based on engine run hours
Does this system require a PLC?
Utility Source 1
52-UM1
G1
52-G1
52-GM1
GN
52-GN
52-F1 52-FN . . .
. . .
G2
52-G2
NO
211 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 10 low voltage 4 gas gensets Extended Parallel Control No Standby Operation CHP application Load demand based on engine run hours
Does this system require a PLC?
Utility Source 1
52-UM1
G1
52-G1
52-GM1
GN
52-GN
52-F1 52-FN . . .
. . .
G2
52-G2
YES
212 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 9 medium voltage 3 diesel gensets 6 feeder breakers with 6 level simple load add/shed control Extended Parallel Control Normal Standby Operation Load demand based on customer set fixed sequence Utility breaker provided by others
– If we control the breaker NO, if not then YES
Does this system require a PLC? Utility
Source 1
52-UM1
G1
52-G1
G2
52-G2
52-F1 52-FN . . .
. . .
GN
52-GN MAYBE
213 Rev 1.5 prdJune 13, 2006
Project Examples
System Type 7 low voltage 9 diesel gensets Extended Parallel Control Normal Standby Operation
Does this system require a PLC?
G1
52-G1
52-GM1
GN
52-GN
52-F1 52-FN . . .
. . .
G2
52-G2 NO
214 Rev 1.5 prdJune 13, 2006
Standard Swgr ProjectOverview
MCM3320Genset Interface Board
(Connection to 4 gensests andinterconnect to additional panels)
SID(Load Add Shed Control and Status)
ExpansionBoard
(Load Add ShedControl and Status)
Control Relay Board(24 control relays to include: 12 w/single form C contact and 12 w/4 form C contacts
capable of operation all cirtcuit breaker open/close coils, need to look at manualoption could all relay that switches from MCM inputs to manual switch inputs)
CT Shorting Block
CT Shorting Block
MCM3320Genset Interface Board
(Connection to 4 gensests andinterconnect to additional panels)
CT Shorting Block CT Shorting Block
Control Mode Panel
Component Mode Panel
215 Rev 1.5 prdJune 13, 2006
MCM3320
Questions / Discussion / Comments