Upload
nick-gane
View
224
Download
1
Embed Size (px)
Citation preview
7/24/2019 Mechanical Labour Book
1/68
EES Data LtdFree to Use Estimating
Labour Guide
MechanicalIssue Date August 2014
EES DATA Copyright 2014 Mechanical Installation Times ISSUE DATE:August 2014
Professional estimating made easy
7/24/2019 Mechanical Labour Book
2/68
EES DataEES Data Ltd41 George StreetCity Centre, WakefieldWest YorkshireWF1 1LW
Web: www.ees-data.co.ukEmail: [email protected]: +44 (0) 1924 200103 Fax: +44 (0) 1924 200104
Estimating + Project Management Software SystemsElectrical Estimating SoftwareMechanical Estimating SoftwarePurchase Ordering: Small Works CostingEES Database Pricing Systems: Electrical + Mechanical & PlumbingWith Installation Guidance TimesWeekly Electronic Price and Product UpdatesJob Cost Management SoftwareApplication for Payment Software
Stock Control SoftwareHeat Loss Calculator Software
EES Data Ltd .....Background
The company was setup as a consultancy in 1983 to providecontractors with independent Estimating and Design services.The companys background is engineering knowledge based withon site experience. We now have a long standing workingrelationship with some of the UKs leading M & E contractors wehave for over 25 years now been provided excellent estimatingsoftware with our own in-house priced data files with immediate
live support and assistance. We stand out because we have:
A clear understanding of contract engineering & estimating
Single monthly Fee Software Support & Updates Designed by
M & E engineers with NO year on year licence charges.
Easy to use and understand software written by engineers with
both on site and office engineering experience.
Our own superb M & E product database systems
Weekly electronic price updates with industry standard times
Excellent live remote connection for instant on line support
EES DATA Copyright 2014 Mechanical Installation Times ISSUE DATE:August
Professional estimating made easyWhy not request a fixed price quote today !
[email protected] or t: 01924 200103
7/24/2019 Mechanical Labour Book
3/68
1. The Labour install times listed within this guide are provided for estimating purposes only and as suchare estimated times supplied for general guidance purposes only. The install times must be checked bythe estimating engineer and or company management to ensure that they are suitable for use on theparticular project to which they are to be applied. The times may need to be adjusted to allow for specialworking conditions and the skill level of operatives chosen for the installation works.
2. Although every effort has been made to provide an accurate assessment against the labour installationguidance times given. As all experienced estimators and contracts engineers will appreciate, estimatingby its nature is not an exact science and differing site conditions can have a dramatic effect on any siteinstallation. Therefore it must be made clear that no guarantee of accuracy can be given by EES Dataand accordingly no responsibility can be accepted by EES Data, it's servants or agents for any loss,consequential loss or damage howsoever caused to the user or to any person, firm or company arising
out of the use of the information or data media provided within this documentation.
3. If anyone wishes to contribute any items not included within this list we will look to include anysuggestions you may have and issue you with a new revised copy.
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times Introduction
INTRODUCTION
Free to Use Book of labour installation times for use by the Mechanical and Electrical Engineering Industry.EES Data Copyright Terms of use: This book of labour installation guidance times is provided Free to use for the purpose of assisting with estimatingworking labour times on M&E projects. It is not permitted without express permission to copy or reproduce the information for electronic purposes of use withinany type of software. It is not permitted to sell, copy, rent, lease, or create a derivative works based on the whole or part of the information in this document.
7/24/2019 Mechanical Labour Book
4/68
1. All times are based on a install rate of per each or per metre
2. Installation times are based on installing equipment at a normal working height from a low scaffold,steps or similar. Additional allowance should be made for increased working heights.
3. The times given are in metric parts of a man hour, all in single man hour rates. The rates shown includefor installing equipment that requires a 2 man operation to install.
4. The times include for un-packing and placing the equipment at the location of work at ground floor level,if equipment is required to be man handled to higher structural levels of working then extra allowanceshould be made.
5. The times are based on normal installation working assuming a clear non cluttered working area.
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times General Notes
GENERAL NOTES
7/24/2019 Mechanical Labour Book
5/68
STEEL TUBES MEDIUM & HEAVY (SCREWED JOINTS) A1
SEAMLESS STEEL TUBE (WELDED JOINTS) WELDS EXTRA A2
STEEL MALLEABLE IRON TUBE FITTINGS (SCREWED JOINTS) A3 to A4
STEEL TUBE FITTINGS (WELDED JOINTS) A5 to A7
COPPER TUBE INSTALLATION A8
COPPER TUBE FITTINGS A9 to A13
POLYBUTYLENE TUBE AND FITTINGS A14 to A15
ABS AND PVC-C TUBE AND FITTINGS A 16 To A18
POLYETHYLENE PE ELECTROFUSION A19
STEEL, CAST, BRASS, BRONZE, VALVES B1 to B11
PUMPS AND WATER CIRCULATORS B12 to B13
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times CONTENT 1
CONTENT OF ESTIMATING TIMES
7/24/2019 Mechanical Labour Book
6/68
COMMERCIAL BOILERS C1
DOMESTIC BOILERS C2 to C3
OIL PIPELINE ACCESSORIES AND TANKS C4
RADIATORS / CONVECTORS & TOWEL WARMERS D1 to D3
PIPE INSULATION AND LAGGING E1
RAINWATER PIPE & GUTTER SYSTEMS ABOVE GROUND F1 to F6
SOIL / VENT / DRAIN PIPE AND FITTINGS BELOW GROUND G1 to G3
WASTE PIPE FITTINGS AND OVERFLOW H1
TRAPS AND DRAIN AWAY WASTE FITTINGS I1
SANITARY SUITES AND FITTINGS J1 to J3
AIR CONDITIONING UNITS K1
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times CONTENT 2
CONTENT OF ESTIMATING TIMES
7/24/2019 Mechanical Labour Book
7/68
DUCTING SYSTEMS SPIRAL L1
DUCTING SYSTEMS FLEXIBLE L2
BELOW GROUND DRAINAGE PLASTIC L3 to L4
LAND AND SURFACE WATER DRAINAGE L5
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times CONTENT 3
CONTENT OF ESTIMATING TIMES
7/24/2019 Mechanical Labour Book
8/68
STEEL TUBES MEDIUM & HEAVY (SCREWED JOINTS)STEEL TUBE INSTALLED NORMAL WORKING HEIGHTBRACKETS & FIXINGS EXTRA
15MM 0.300
20MM 0.35025MM 0.35032MM 0.40040MM 0.50050MM 0.60065MM 0.70080MM 1.000100MM 1.500125MM 2.000150MM 2.500
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 1
STEEL TUBES (SCREWED AND WELDED)
7/24/2019 Mechanical Labour Book
9/68
SEAMLESS STEEL TUBE (WELDED JOINTS) WELDS EXTRASTEEL TUBE INSTALLED NORMAL WORKING HEIGHTWELDS, BRACKETS & FIXINGS EXTRA
15MM 0.25 200MM 2.8020MM 0.25 250MM 2.9025MM 0.30 300MM 3.10
32MM 0.35 350MM 3.6040MM 0.40 400MM 3.8050MM 0.45 450MM 4.5065MM 0.50 500MM 5.5080MM 0.70 600MM 6.00100MM 0.80 700MM 6.00125MM 1.00 800MM 7.50150MM 2.25 900MM 9.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 2
STEEL TUBES (SCREWED AND WELDED)
7/24/2019 Mechanical Labour Book
10/68
SCREWED JOINTS 15mm 20mm 25mm 32mm 40mm 50mm
BEND 0.30 0.35 0.40 0.50 0.60 0.70ELBOW 0.30 0.35 0.40 0.50 0.60 0.70TWIN ELBOW 0.45 0.50 0.60 0.75 0.90 1.00TEE 0.45 0.50 0.60 0.75 0.90 1.00SOCKET EQUAL 0.30 0.35 0.40 0.50 0.60 0.70SOCKET REDUCING 0.30 0.40 0.45 0.55 0.65 0.754 WAY UNIT 0.60 0.70 0.80 1.00 1.20 1.30UNION 0.30 0.35 0.40 0.50 0.60 0.70FLANGE 0.45 0.45 0.45 0.50 0.55 0.60BUSH REDUCING 0.15 0.15 0.15 0.20 0.20 0.25LOCKNUT 0.10 0.10 0.10 0.12 0.12 0.15NIPPLE 0.10 0.15 0.15 0.15 0.20 0.25PLUG 0.10 0.15 0.15 0.15 0.20 0.20END CAP 0.20 0.20 0.20 0.25 0.30 0.35
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 3
STEEL MALLEABLE IRON TUBE FITTINGS
7/24/2019 Mechanical Labour Book
11/68
SCREWED JOINTS 65mm 80mm 100mm 125mm 150mm
BEND 0.75 0.85 1.20 1.80 2.25ELBOW 0.75 0.85 1.20 1.80 2.25TWIN ELBOW 1.10 1.25 1.80 2.70 3.00
TEE 1.10 1.25 1.80 2.70 3.00SOCKET EQUAL 0.75 0.85 1.20 1.80 2.25SOCKET REDUCING 0.80 0.90 1.30 2.00 2.304 WAY UNIT 1.40 1.60 2.00 3.00 3.50UNION 0.75 0.85 1.20 1.80 2.20FLANGE 0.65 0.70 0.85 1.15 1.45BUSH REDUCING 0.25 0.30 0.35 0.40 0.45LOCKNUT 0.20 0.20 0.25 0.30 0.35NIPPLE 0.25 0.25 0.30 0.40 0.50PLUG 0.25 0.25 0.30 0.35 0.45END CAP 0.35 0.45 0.60 0.90 1.20
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 4
STEEL MALLEABLE IRON TUBE FITTINGS
7/24/2019 Mechanical Labour Book
12/68
1/2 3/4 1 1-1/4 1-1/2 2WELDED JOINTS 15mm 20mm 25mm 32mm 40mm 50mm
BUTT WELD 0.25 0.25 0.35 0.40 0.50 0.70
BRANCH WELD 0.30 0.30 0.45 0.60 0.75 1.00
BEND 0.40 0.50 0.70 0.80 1.00 1.30
ELBOW 0.40 0.50 0.70 0.80 1.00 1.30
TEE 0.60 0.75 1.00 1.20 1.40 1.80
EQUAL SOCKET 0.40 0.50 0.70 0.80 1.00 1.30
REDUCING SOCKET 0.40 0.50 0.70 0.80 1.00 1.30
4 WAY UNIT 0.80 1.00 1.20 1.30 1.60 1.80
SINGLE FLANGE 0.50 0.50 0.60 0.65 0.75 0.90
END CAP 0.30 0.40 0.50 0.60 0.70 0.80
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 5
STEEL TUBE FITTINGS WELDEDSTAINLESS STEEL + 30% to Times
7/24/2019 Mechanical Labour Book
13/68
2-1/2 3 4 5 6 8WELDED JOINTS 65mm 80mm 100mm 125mm 150mm 200mm
BUTT WELD 0.90 1.00 1.30 1.70 2.00 2.50
BRANCH WELD 1.30 1.50 2.00 2.60 3.00 4.50
BEND 1.80 2.10 2.60 3.40 4.00 4.50
ELBOW 1.80 2.10 2.60 3.40 4.00 4.50
TEE 2.50 2.80 3.50 4.80 5.50 6.50
EQUAL SOCKET 1.80 2.10 2.60 3.40 4.00 4.50
REDUCING SOCKET 1.80 2.10 2.60 3.40 4.00 4.50
4 WAY UNIT 2.80 3.40 3.80 5.00 6.50 7.50
SINGLE FLANGE 1.15 1.25 1.55 1.95 2.25 2.50
END CAP 0.90 1.00 1.30 1.70 2.00 2.25
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 6
STEEL TUBE FITTINGS WELDEDSTAINLESS STEEL + 30% to Times
7/24/2019 Mechanical Labour Book
14/68
10 12 14 16 18 20 24 28 32 36WELDED JOINTS 250mm 300mm 350mm 400mm 450mm 500mm 600mm 700mm 800mm 900mm
BUTT WELD 4.00 4.80 5.50 6.00 7.500 8.00 10.00 13.00 17.00 21.00
BRANCH WELD 5.50 7.00 8.00 9.00 12.00 14.00 14.00 17.00 21.00 25.00
BEND 6.50 7.00 9.50 11.00 14.00 16.00 18.00 21.00 25.00 29.00
ELBOW 6.50 7.00 9.50 11.00 14.00 16.00 18.00 21.00 25.00 29.00
TEE 8.50 10.00 14.00 15.00 19.00 21.00 22.00 25.00 29.00 33.00
EQUAL SOCKET 6.50 7.00 9.50 11.00 14.00 16.00 18.00 21.00 25.00 29.00
RED SOCKET 6.50 7.00 9.50 11.00 14.00 16.00 18.00 21.00 25.00 29.00
4 WAY UNIT 10.00 12.00 16.00 17.000 20.00 22.00 28.00 31.00 35.00 39.00
SINGLE FLANGE 3.45 3.90 6.00 6.50 7.000 8.50 9.50 12.50 16.00 20.00
END CAP 3.00 3.50 5.00 5.50 7.50 8.00 9.00 12.00 16.00 20.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 7
STEEL TUBE FITTINGS WELDEDSTAINLESS STEEL + 30% to Times
7/24/2019 Mechanical Labour Book
15/68
Installed Surface Fixed and Clipped Direct to Structure (Normal Working Height)
15MM 22MM 28MM 35MM 42MM 54MM 67MM 76MM 108MM 133MM 159MM
0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.70 0.80 0.90 1.00
Installed Within Unobstructed Void or Laid in Trench
15MM 22MM 28MM 35MM 42MM 54MM 67MM 76MM 108MM 133MM 159MM
0.10 0.10 0.15 0.20 0.20 0.25 0.25 0.30 0.40 0.45 0.50
Installed Within Floor Space
15MM 22MM 28MM 35MM 42MM 54MM 67MM 76MM 108MM 133MM 159MM
0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.65 0.75 0.85 0.95
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 8
COPPER TUBE INSTALLATION
7/24/2019 Mechanical Labour Book
16/68
COPPER FITTINGSCapillary Fittings
15mm 22mm 28mm 35mm 42mm 54mm 67mm 76mm 108mm
ELBOW 0.15 0.15 0.20 0.25 0.25 0.30 0.35 0.50 0.65
TEE 0.20 0.20 0.25 0.30 0.35 0.40 0.50 0.65 0.85
CROSSOVER 0.25 0.25 0.30 0.35 0.45 0.35 0.40 0.60 0.80
COUPLING 0.15 0.15 0.20 0.25 0.25 0.30 0.35 0.50 0.65
REDUCER 0.15 0.15 0.20 0.25 0.25 0.30 0.35 0.50 0.65
STOP END 0.10 0.10 0.10 0.15 0.15 0.20 0.25 0.25 0.35
TAP CONNECTOR 0.10 0.10 0.10 0.15 0.20 0.45 0.65 0.80 1.00
TANK CONNECTOR 0.30 0.30 0.30 0.35 0.35 0.55 0.60 0.85 1.00
THREADED ADAPTOR 0.20 0.20 0.25 0.30 0.30 0.35 0.35 0.40 0.40OR UNION
Example makes: Pegler Yorkshire YP
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 9
COPPER TUBE & FITTINGS
7/24/2019 Mechanical Labour Book
17/68
COPPER FITTINGSCompression Fittings 15mm 22mm 28mm 35mm 42mm 54mm 67mm 76mm 108mm
ELBOW 0.15 0.15 0.20 0.20 0.25 0.25 0.30 0.50 0.65
TEE 0.20 0.20 0.25 0.25 0.30 0.35 0.40 0.65 0.85
COUPLING 0.15 0.15 0.20 0.20 0.25 0.25 0.30 0.50 0.65
REDUCER 0.15 0.15 0.20 0.20 0.25 0.25 0.30 0.50 0.65
STOP END / PLUG 0.10 0.10 0.15 0.15 0.15 0.20 0.20 0.30 0.35
TANK CONNECTOR 0.20 0.20 0.25 0.25 0.30 0.40
TAP CONNECTOR 0.10 0.10 0.15
RADIATOR VALVE 0.20 0.20
VALVE 0.20 0.20 0.25 0.25 0.30 0.35 0.50 0.70 1.00
ADAPTOR 0.15 0.15 0.15 0.20 0.20 0.25 0.30 0.35 0.45
Example makes: Pegler Yorkshire Kuterlite
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 10
COPPER TUBE & FITTINGS
7/24/2019 Mechanical Labour Book
18/68
COPPER FITTINGSBrazing Joints & Fittings (Brazed Welded)
15mm 22mm 28mm 35mm 42mm 54mm 67mm 76mm 108mm 133mmELBOW 0.30 0.30 0.40 0.50 0.50 0.60 0.70 1.00 1.30 1.40
TEE 0.40 0.40 0.50 0.60 0.70 0.80 1.00 1.30 1.70 1.80
COUPLING 0.30 0.30 0.40 0.50 0.50 0.60 0.70 1.00 1.00 1.30
REDUCER 0.30 0.30 0.40 0.50 0.50 0.60 0.70 1.00 1.30 1.40
FLANGE 0.20 0.25 0.30 0.35 0.45 0.60 0.80 1.00 1.25 1.50
STOP END 0.20 0.25 0.30 0.35 0.45 0.60 0.80 1.00 1.25 1.50
TAP CONNECTOR 0.25 0.30 0.35 0.40 0.50
TANK CONNECTOR 0.30 0.30 0.35 0.40 0.60
BUTT WELD 0.20 0.25 0.25 0.35 0.45 0.60 0.80 1.00 1.25 1.50
BRANCH WELD 0.50 0.55 0.60 0.80 1.00 1.40 1.80 2.00 2.40 2.75
Example makes: Pegler Yorkshire Endex
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 11
COPPER TUBE & FITTINGS
7/24/2019 Mechanical Labour Book
19/68
COPPER FITTINGSPress Fit Type Joints
15mm 22mm 28mm 35mm 42mm 54mm 67mm 76mm 108mm
BEND 0.15 0.15 0.20 0.20 0.25 0.25 0.35 0.45 0.60
TEE 0.20 0.20 0.25 0.30 0.30 0.35 0.50 0.65 0.85
COUPLING 0.15 0.15 0.20 0.20 0.25 0.25 0.35 0.45 0.60
REDUCER 0.20 0.20 0.20 0.25 0.30 0.30 0.40 0.50 0.70
BRANCH 0.20 0.20 0.25 0.30 0.30 0.35 0.50 0.65 0.85
STOP END 0.10 0.10 0.15 0.15 0.20 0.20 0.25 0.30 0.35
Example makes: Pegler Yorkshire Xpress or Geberit Mapress
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 12
COPPER TUBE & FITTINGS
7/24/2019 Mechanical Labour Book
20/68
COPPER FITTINGSPush Fit Type Joints
15mm 22mm 28mm 35mm 42mm
BEND 0.10 0.10 0.15 0.15 0.16
TEE 0.15 0.15 0.17 0.20 0.20
COUPLING 0.10 0.10 0.15 0.15 0.17
REDUCER 0.15 0.15 0.15 0.17 0.20
BRANCH 0.15 0.15 0.17 0.20 0.20
STOP END 0.08 0.08 0.10 0.10 0.15
Example makes: Pegler Yorkshire Tectite
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 13
COPPER TUBE & FITTINGS
7/24/2019 Mechanical Labour Book
21/68
POLYBUTYLENE TUBEPUSH FIT FITTINGS (Suitable for Hot & Cold Water & Central Heating Systems)
Surface Installed Fixed and Clipped Direct to Structure 15mm 22mm 28mm
0.15 0.15 0.20
Installed Within Floor Space 15mm 22mm 28mm
0.20 0.20 0.25
Installed Within Voids or Laid in Trench 15mm 22mm 28mm
0.10 0.10 0.15
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 14
POLYBUTYLENE TUBE AND FITTINGS
7/24/2019 Mechanical Labour Book
22/68
PUSH FIT FITTINGS(Suitable for Hot & Cold Water & Central Heating Systems) 15MM 22MM 28MM
COUPLER 0.10 0.10 0.15
ELBOW 0.10 0.10 0.15
REDUCER 0.10 0.10 0.15
TEE 0.15 0.15 0.20
STOP END 0.05 0.05 0.08
TAP CONNECTOR 0.10 0.10 0.15
TANK CONNECTOR 0.20 0.20 0.25
MALE / FEMALE ADAPTOR 0.15 0.15 0.20
VALVE OR STOPCOCK 0.15 0.15
MANIFOLD (4 PORT) 0.30 0.30
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 15
POLYBUTYLENE TUBE AND FITTINGS
7/24/2019 Mechanical Labour Book
23/68
TUBE (Solvent cement type jointing ) 16mm 20mm 25mm 32mm 40mm0.15 0.20 0.20 0.20 0.20
1/2 3/4 1 1-1/4 1-1/2FITTINGS (Solvent cement type jointing ) 16mm 20mm 25mm 32mm 40mm
BEND 0.12 0.12 0.15 0.15 0.20COUPLER 0.12 0.12 0.150 0.15 0.20REDUCER 0.12 0.12 0.15 0.15 0.20STOP END 0.10 0.10 0.10 0.10 0.12TEE OR BRANCH 0.20 0.20 0.20 0.20 0.254 WAY CROSS 0.25 0.25 0.25 0.30 0.30BALL TYPE VALVE 0.33 0.33 0.33 0.33 0.403 WAY VALVE 0.20 0.20 0.20 0.25 0.30FLANGE TYPE VALVE 0.30 0.30 0.35 0.35 0.40SCREW TYPE ADAPTOR 0.15 0.15 0.20 0.20 0.20
PIPE CLIPS 0.08 0.08 0.10 0.12 0.15
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 16
ABS AND PVC-C TUBE AND FITTINGS
7/24/2019 Mechanical Labour Book
24/68
TUBE (Solvent cement type jointing ) 50mm 63mm 75mm 90mm 110mm 160mm0.25 0.25 0.30 0.35 0.35 0.40
2 2-1/2 3 3-1/2 4 6FITTINGS (Solvent cement type jointing ) 50mm 63mm 75mm 90mm 110mm 160mmBEND 0.20 0.25 0.25 0.25 0.35 0.40
COUPLER 0.20 0.25 0.25 0.25 0.35 0.40ELBOW 0.20 0.25 0.25 0.25 0.35 0.40REDUCER 0.20 0.25 0.25 0.25 0.35 0.40STOP END 0.15 0.20 0.20 0.20 0.25 0.30TEE OR BRANCH 0.25 0.30 0.30 0.40 0.50 0.604 WAY CROSS 0.30 0.35 0.40 0.50 0.60 0.70BALL TYPE VALVE 0.45 0.45 0.45 0.50 0.50 0.503 WAY VALVE 0.30 0.35 0.35 0.45 0.60 0.70FLANGE TYPE VALVE 0.50 0.60 0.75 0.90 1.00 1.10SCREW TYPE ADAPTOR 0.25 0.25 0.30 0.35 0.40 0.50PIPE CLIPS 0.17 0.20 0.20 0.25 0.25 0.30
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 17
ABS AND PVC-C TUBE AND FITTINGS
7/24/2019 Mechanical Labour Book
25/68
TUBE (Solvent cement type jointing ) 160mm 200mm 250mm 300mm0.40 0.50 0.55 0.60
6 8 10 12FITTINGS (Solvent cement type jointing ) 160mm 200mm 250mm 300mmBEND 0.40 0.50 0.55 0.60COUPLER 0.40 0.50 0.55 0.60ELBOW 0.40 0.50 0.55 0.60REDUCER 0.40 0.50 0.55 0.60STOP END 0.30 0.40 0.45 0.50TEE OR BRANCH 0.60 0.70 0.75 0.804 WAY CROSS 0.70 0.80 0.85 0.90BALL TYPE VALVE 0.50 0.60 0.65 0.903 WAY VALVE 0.70 0.80 0.85 0.90FLANGE TYPE VALVE 1.10 1.20 1.25 1.30SCREW TYPE ADAPTOR 0.50 0.60 0.70 0.75
PIPE CLIPS 0.30 0.35 0.40 0.45
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 18
ABS AND PVC-C TUBE AND FITTINGS
7/24/2019 Mechanical Labour Book
26/68
POLYETHYLENE PIPE 20mm 25mm 32mm 50mm 63mm 90mm 110mm 125mm& FITTINGS
PIPE PER METRE 0.15 0.15 0.20 0.20 0.25 0.35 0.35 0.40COUPLER 0.20 0.20 0.30 0.35 0.40 0.50 0.70 0.90REDUCER 0.20 0.20 0.30 0.35 0.40 0.50 0.70 0.90ELBOW 0.20 0.20 0.30 0.35 0.40 0.50 0.70 0.90SADDLE 0.30 0.30 0.40 0.50 0.60 0.70 0.90 1.00TEE 0.30 0.30 0.45 0.50 0.60 0.75 0.90 1.20CAP END 0.20 0.20 0.25 0.30 0.35 0.40 0.50 0.50
POLYETHYLENE PIPE 140mm 160mm 180mm 225mm 250mm 315mm 355mm 400mm& FITTINGS
PIPE PER METRE 0.40 0.40 0.45 0.50 0.50 0.55 0.55 0.60COUPLER 1.10 1.10 1.30 1.50 1.80 2.00 2.20 2.50
REDUCER 1.10 1.10 1.30 1.50 1.80 2.00 2.20 2.50ELBOW 1.10 1.10 1.30 1.50 1.80 2.00 2.20 2.50SADDLE 1.20 1.20 1.40 1.70 1.90 2.20 2.40 2.60TEE 1.30 1.30 1.50 1.80 2.00 2.30 2.50 2.90CAP END 0.60 0.60 0.80 1.00 1.20 1.50 1.70 2.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION A 19
POLYETHYLENE PE ELECTROFUSION
7/24/2019 Mechanical Labour Book
27/68
STEAM PRESSURE AND REGULATING VALVES (SCREWED JOINTS)
15MM VALVE 0.6520MM VALVE 0.6525MM VALVE 0.8032MM VALVE 1.0040MM VALVE 1.00
50MM VALVE 1.85
SAFTEY VALVES (SCREWED JOINTS)
15MM VALVE 0.2020MM VALVE 0.2525MM VALVE 0.2532MM VALVE 0.3040MM VALVE 0.4550MM VALVE 0.60
65MM VALVE 0.7080MM VALVE 0.80100MM VALVE 1.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 1
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
28/68
STANDARD BRASS / BRONZE VALVES (SCREWED JOINTS)
15MM VALVE 0.30
20MM VALVE 0.40
25MM VALVE 0.50
32MM VALVE 0.65
40MM VALVE 0.80
50MM VALVE 1.00
65MM VALVE 1.25
80MM VALVE 1.70
100MM VALVE 2.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 2
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
29/68
STANDARD BRASS / BRONZE VALVES (FLANGE JOINTS)
15MM VALVE 0.3020MM VALVE 0.3025MM VALVE 0.4032MM VALVE 0.5040MM VALVE 0.60
50MM VALVE 0.7565MM VALVE 0.9080MM VALVE 1.20100MM VALVE 1.50125MM VALVE 2.00150MM VALVE 2.50200MM VALVE 3.50250MM VALVE 5.00300MM VALVE 6.00350MM VALVE 6.50400MM VALVE 7.50450MM VALVE 8.00500MM VALVE 9.00600MM VALVE 10.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 3
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
30/68
STANDARD BRASS VALVES (COMMPRESSION JOINTS)
15MM VALVE 0.2022MM VALVE 0.2028MM VALVE 0.2535MM VALVE 0.30
42MM VALVE 0.3554MM VALVE 0.55
BALL VALVES (SCREWED JOINTS)
15MM VALVE 0.2020MM VALVE 0.2525MM VALVE 0.4032MM VALVE 0.5040MM VALVE 0.7050MM VALVE 0.8565MM VALVE 1.0080MM VALVE 1.40100MM VALVE 1.65
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 4
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
31/68
DRAIN OFF COCK VALVES (SCREWED JOINTS)
15MM VALVE 0.15
20MM VALVE 0.15
25MM VALVE 0.20
RADIATOR VALVES
15MM COMPRESION TYPE VALVE 0.20
22MM COMPRESION TYPE VALVE 0.20
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 5
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
32/68
CAST STEEL VALVES (WELDED JOINTS)
50MM VALVE 1.7065MM VALVE 2.0080MM VALVE 2.30100MM VALVE 3.00125MM VALVE 4.00150MM VALVE 5.00
200MM VALVE 6.50250MM VALVE 8.00300MM VALVE 9.50
CAST IRON VALVES (SCREWED JOINTS)
50MM VALVE 1.3065MM VALVE 1.5080MM VALVE 1.80100MM VALVE 2.80125MM VALVE 3.50
150MM VALVE 4.50200MM VALVE 6.50250MM VALVE 8.00300MM VALVE 10.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 6
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
33/68
STEAM TRAPS (SCREWED JOINTS)
15MM VALVE 0.3020MM VALVE 0.3525MM VALVE 0.4532MM VALVE 0.6040MM VALVE 0.70
50MM VALVE 0.85
CAST STEEL VALVES (FLANGE JOINTS)
50MM VALVE 0.8565MM VALVE 1.0080MM VALVE 1.35100MM VALVE 1.75125MM VALVE 2.00150MM VALVE 2.50200MM VALVE 3.50250MM VALVE 5.00300MM VALVE 6.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 7
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
34/68
STRAINERS (SCREWED JOINTS)
15MM VALVE 0.3020MM VALVE 0.4025MM VALVE 0.5032MM VALVE 0.6540MM VALVE 0.80
50MM VALVE 1.0065MM VALVE 1.2080MM VALVE 1.70100MM VALVE 2.00
STRAINERS (FLANGE JOINTS)
15MM VALVE 0.3020MM VALVE 0.3025MM VALVE 0.4032MM VALVE 0.5040MM VALVE 0.6050MM VALVE 0.7565MM VALVE 0.9080MM VALVE 1.20
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 8
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
35/68
EXPANSION JOINTS (SCREWED JOINTS)
15MM 0.25020MM 0.25025MM 0.300
32MM 0.40040MM 0.55050MM 0.65065MM 0.80080MM 0.900100MM 1.500125MM 2.100150MM 3.000200MM 4.000250MM 5.000300MM 6.000
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 9
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
36/68
7/24/2019 Mechanical Labour Book
37/68
BOLTING FLANGES TOGETHERTIME PER FLANGE
PIPE SIZE 4-BOLT FLANGE 8-BOLT FLANGE 12-BOLT FLANGE
15MM 0.250
20MM 0.25025MM 0.25032MM 0.25040MM 0.25050MM 0.25065MM 0.250 0.40080MM 0.300 0.450100MM 0.400 0.550125MM 0.600150MM 0.600 0.750200MM 0.800250MM 0.900300MM 1.200
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 11
STEEL, CAST, BRASS, BRONZE, VALVES
7/24/2019 Mechanical Labour Book
38/68
CIRCULATOR PUMP (FLANGED) ELECTRICAL CONNECTION32MM PUMP 2.00 0.75
40MM PUMP 2.50 0.75
50MM PUMP 2.50 0.75
65MM PUMP 2.80 1.00
80MM PUMP 3.00 1.00
100MM PUMP 3.50
CIRCULATOR PUMP (UNION)25MM PUMP 1.20 0.75
32MM PUMP 1.50 0.75
40MM PUMP 1.80 0.75
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 12
PUMPS AND WATER CIRCULATORS
7/24/2019 Mechanical Labour Book
39/68
DOMESTIC CENTRAL HEATING PUMP ELECTRICAL CONNECTION
22MM PUMP 1.20 0.45
28MM PUMP 1.20 0.45
SUMP PUMPS
25 TO 50MM PUMP 2.20 0.65
65 TO 100MM PUMP 4.00 0.75
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION B 13
PUMPS AND WATER CIRCULATORS
7/24/2019 Mechanical Labour Book
40/68
GAS / OIL / SOLID FUEL FIRED BOILER
KW RATING
100 24.00150 30.00225 40.00300 45.00450 60.00500 70.00625 85.00750 90.00900 100.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION C 1
COMMERCIAL BOILERS
7/24/2019 Mechanical Labour Book
41/68
WALL HUNG GAS FIRED BOILER WITH STANDARD CONVENTIONAL FLUE.
KW BTU/HR13 TO 23 45,000 TO 80,000 8.0029 TO 43 100,000 TO 150,000 16.00
FLOOR STANDING GAS FIRED BOILER WITH STANDARD CONVENTIONAL FLUE.
KW BTU/HR13 TO 23 45,000 TO 80,000 8.0029 TO 43 100,000 TO 150,000 16.00
WALL HUNG GAS FIRED BOILER WITH STANDARD BALANCED FLUE.
KW BTU/HR13 TO 23 45,000 TO 80,000 8.00
29 TO 43 100,000 TO 150,000 16.00
Times include fitting of Standard Flue System but do not include builders work
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION C 2
DOMESTIC BOILERS
7/24/2019 Mechanical Labour Book
42/68
FLOOR STANDING OIL FIRED BOILER WITH STANDARD CONVENTIONAL FLUE
KW BTU/HR13 TO 23 45,000 TO 80,000 10.0029 TO 43 100,000 TO 150,000 18.00
FLOOR STANDING SOLID FUEL BOILER WITH STANDARD CONVENTIONAL FLUE
KW BTU/HR13 TO 23 45,000 TO 80,000 10.0029 TO 43 100,000 TO 150,000 18.00
Times include fitting of Standard Flue System but o not include builders work
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION C 3
DOMESTIC BOILERS
7/24/2019 Mechanical Labour Book
43/68
PLASTIC OIL STORAGE TANKSTANK CAPACITY IN LITRES
1800 LTR 8.002500 LTR 10.003600 LTR 12.005000 LTR 14.00
10000 LTR 20.00
TANK ACCESSORIES
SIGHT GAUGE SELF CLOSING 0.50SIGHT GAUGE ADAPTER 0.25SIGHT GAUGE WITH FILTER 0.33OIL FILTER 0.25OIL LINE 0.33VENTILATOR 0.17
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION C 4
OIL PIPELINE ACCESSORIES AND TANKS
7/24/2019 Mechanical Labour Book
44/68
RADIATORS WALL MOUNTED SINGLE PANEL
HEIGHT LENGTH
300 TO 500MM 300 TO 700MM 0.50
300 TO 500MM 700 TO 1000MM 0.65
300 TO 500MM 1000 TO 1400MM 0.75
300 TO 500MM 1400 TO 2000MM 0.85
500 TO 700MM 300 TO 700MM 0.65
500 TO 700MM 700 TO 1000MM 0.75
500 TO 700MM 1000 TO 1400MM 0.85
500 TO 700MM 1400 TO 2000MM 0.90
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION D 1
RADIATORS / CONVECTORS & TOWEL WARMERS
7/24/2019 Mechanical Labour Book
45/68
RADIATORS WALL MOUNTED DOUBLE PANEL& SINGLE PANEL PLUS
HEIGHT LENGTH
300 TO 500MM 300 TO 700MM 0.65
300 TO 500MM 700 TO 1000MM 0.75
300 TO 500MM 1000 TO 1400MM 0.85
300 TO 500MM 1400 TO 2000MM 0.90
500 TO 700MM 300 TO 700MM 0.75
500 TO 700MM 700 TO 1000MM 0.85
500 TO 700MM 1000 TO 1400MM 0.90
500 TO 700MM 1400 TO 2000MM 1.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION D 2
RADIATORS / CONVECTORS & TOWEL WARMERS
7/24/2019 Mechanical Labour Book
46/68
TOWEL RAILS WALL AND FLOOR MOUNTED
WALL MOUNTED TOWEL WARMER 1.50
FLOOR MOUNTED TOWEL WARMER 1.25
RADIATOR VALVES
15MM COMPRESION TYPE VALVE 0.25
22MM COMPRESION TYPE VALVE 0.25
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION D 3
RADIATORS / CONVECTORS & TOWEL WARMERS
7/24/2019 Mechanical Labour Book
47/68
FOAM SEMI-SLIT PIPE INSULATION PER MT
15MM 0.1020MM 0.1025MM 0.1032MM 0.1240MM 0.15
FIBRE ROCKWOOL YPE PIPE INSULATION PER MT RATE
15MM 0.15 200MM 0.3020MM 0.15 250MM 0.3025MM 0.15 300MM 0.3532MM 0.20 400MM 0.4040MM 0.20 450MM 0.4050MM 0.25 500MM 0.4065MM 0.25 600MM 0.4580MM 0.25 650MM 0.45
100MM 0.25 700MM 0.45125MM 0.30 800MM 0.45150MM 0.30 1000MM 0.50
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION E 1
PIPE INSULATION AND LAGGING
7/24/2019 Mechanical Labour Book
48/68
PLASTIC GUTTER AND FITTINGS 76mm to 125mm Over 125mmInstalled at Normal Working Height
GUTTER PER METRE 0.30 0.35
SUPPORT BRACKET 0.20 0.20
JOINT BRACKET 0.20 0.20
UNION 0.20 0.20
RUNNING OUTLET 0.15 0.20
STOP END OUTLET 0.10 0.10
ANGLE 0.20 0.20
HOPPER HEAD 0.25 0.30
GUTTER LEAF GUARD PER METRE 0.08 0.10
RAINWATER GULLY / ROOF OUTLET 0.33 0.45
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION F 1
RAINWATER PIPE & GUTTER SYSTEMS
7/24/2019 Mechanical Labour Book
49/68
7/24/2019 Mechanical Labour Book
50/68
CAST IRON GUTTER AND FITTINGS 100mm 125mm 150mm
CAST IRON GUTTER PER METRE 0.80 1.00 1.25
UNION CLIP 0.20 0.20 0.25
END CAP 0.15 0.15 0.20
RUNNING OUTLET 0.25 0.30 0.30
ANGLES 0.25 0.30 0.30
FIXING BRACKET 0.25 0.25 0.30
DRIVE IN BRACKET 0.20 0.20 0.20
RAFTER BRACKET 0.25 0.25 0.30
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION F 3
RAINWATER PIPE & GUTTER SYSTEMS
7/24/2019 Mechanical Labour Book
51/68
CAST IRON DOWNPIPE AND FITTINGS 50mm 63mm 100mm
CAST IRON DOWN PIPE PER METRE 0.40 0.50 0.65
RAINWATER HEADS 0.45 0.55 0.65
BENDS 0.25 0.25 0.30
DIMINISHING PIECE 0.30 0.45 0.60
OFFSETS 0.25 0.25 0.30
SHOES 0.25 0.25 0.35
SOCKETS 0.17 0.20 0.25
BRANCH 0.25 0.25 0.35
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION F 4
RAINWATER PIPE & GUTTER SYSTEMS
7/24/2019 Mechanical Labour Book
52/68
7/24/2019 Mechanical Labour Book
53/68
ALUMINIUM DOWNPIPE AND FITTINGS 63mm 100mm 150mm
ALUMINIUM DOWN PIPE PER METRE 0.40 0.50 0.65
PIPE CLIPS 0.20 0.27 0.30
RAINWATER HEADS 0.45 0.55 0.65
BENDS 0.25 0.25 0.30
OFFSETS 0.25 0.25 0.30
SHOES 0.25 0.25 0.35
SOCKETS 0.17 0.20 0.25
BRANCHES 0.25 0.25 0.35
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION F 6
RAINWATER PIPE & GUTTER SYSTEMS
7/24/2019 Mechanical Labour Book
54/68
3 4 6PVC PIPE & FITTINGS 82mm 110mm 160mm
PIPE PLAIN ENDED OR SOCKETED 0.25 0.30 0.35
PVC FITTINGSSOCKET 0.17 0.20 0.25
BRACKET 0.17 0.20 0.25BOSS PIPE 0.28 0.30 0.35BRANCH 0.25 0.25 0.25
ACCESS CAP OR PLUG 0.08 0.08 0.10BEND 0.35 0.35 0.35
ACCESS JUNCTION 0.35 0.40 0.45BEND ADJUSTABLE 0.25 0.25 0.30REDUCER 0.25 0.25 0.30VENT COWL 0.20 0.20 0.20WEATHERING SLATE 0.55 0.55 0.65CHANNEL BEND 0.20 0.20 0.25
BOTTLE GULLIES 0.45 0.50 0.60NON RETURN VALVE 0.40 0.45 0.50WEATHERING APRON 0.30 0.35 0.40
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION G 1
SOIL / WASTE /VENT / PIPE AND FITTINGS
7/24/2019 Mechanical Labour Book
55/68
LIGHTWEIGHT CAST IRON 2 3 4 5DRAINAGE (Clamp Style Joints) 50mm 70mm 100mm 125mm
PIPE PER METRE 0.30 0.35 0.40 0.45
BEND 0.30 0.35 0.50 0.70OFFSET 0.30 0.35 0.50 0.70COUPLING / SOCKET 0.30 0.33 0.33 0.40REDUCER 0.30 0.35 0.50 0.70CONNECTOR 0.40 0.40 0.60 0.80BRANCH 0.45 0.50 0.60 0.90
ADAPTOR 0.30 0.30 0.45 0.60TRAP 0.40 0.40 0.60 0.80WC CONNECTOR 0.20 0.20 0.20END CAP 0.25 0.33 0.33 0.40
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION G 2
SOIL / VENT / PIPE AND FITTINGS
7/24/2019 Mechanical Labour Book
56/68
LIGHTWEIGHT CAST IRONDRAINAGE (Clamp Style Joints) 150mm 200mm 250mm 300mm
PIPE PER METRE 0.650 0.900 1.150 1.400
BEND 0.800 1.000 1.200 1.400OFFSET 0.800 1.000 1.200 1.400COUPLING / SOCKET 0.400 0.450 0.450 0.500REDUCER 0.800 1.000 1.200 1.400CONNECTOR 1.000 1.300 1.500 1.700BRANCH 1.000 1.500 1.700 1.900
ADAPTOR 0.700 0.900 0.950 1.100TRAP 1.000 1.300 1.500 1.700END CAP 0.400 0.450 0.450 0.500
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION G 3
SOIL / VENT / DRAIN PIPE AND FITTINGS
7/24/2019 Mechanical Labour Book
57/68
WASTE AND OVERFLOW PIPE 22mm 32mm 40mmOVERFLOW PIPE PER METRE 0.15WASTE PIPE PER METRE 0.20 0.20
PLASTIC MECHANICAL TYPE FITTINGSBEND 0.12 0.12SOCKET / COUPLER 0.12 0.12TEE 0.15 0.15
PLASTIC PUSHFIT TYPE FITTINGSBEND 0.10 0.10SOCKET / COUPLER 0.10 0.10TEE 0.12 0.12
PLASTIC SOLVENT WELD TYPE FITTINGSBEND 0.12 0.12 0.10SOCKET / COUPLER 0.12 0.12 0.12TEE 0.15 0.15 0.20
COPPER FITTINGS or SIMILAR 35mm 42mm 54mmBEND 0.25 0.25 0.30SOCKET / COUPLER 0.25 0.25 0.30TEE
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION H 1
WASTE PIPE FITTINGS AND OVERFLOW
7/24/2019 Mechanical Labour Book
58/68
TRAPS AND DRAIN AWAY WASTE FITTINGS 32mm 40mm
PLASTIC TRAPSBOTTLE TRAP 0.20 0.202 PIECE TRAP 0.20 0.203 PIECE TRAP 0.25 0.25BATH TRAP 0.25 0.25SHOWER TRAY TRAP 0.25 0.25
METAL TRAPS 35mm 42mm 54mmBOTTLE TRAP 0.30 0.30 0.401 PIECE TRAP 0.30 0.30 0.402 PIECE TRAP 0.30 0.25 0.403 PIECE TRAP 0.35 0.30 0.45
WASTE AND OVERFLOW COMBINATIONS
PLASTIC WASTE 0.25 0.25
BRASS WASTE 0.25 0.33BIDET WASTE CONNECTION 0.65OVERFLOW COMBINATION 0.20 0.20
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION I 1
TRAPS AND DRAIN AWAY WASTE FITTINGS
7/24/2019 Mechanical Labour Book
59/68
FIX & INSTALL INCLUDES TAPS & WASTES.
BATHS AND ACCESSORIES
STANDARD 170CM BATH LIGHT DUTY 4.00STANDARD BATH HEAVY DUTY 5.00SIDE PANEL & FRAME. 1.50END PANEL & FRAME 1.00SIDE PANEL 0.50END PANEL & FRAME 0.30
WASH BASINS
BASIN INCLUDING PEDESTAL 3.00WALL MOUNTED BASIN WITH BRACKETS 3.50CORNER BASIN 2.75RECESSED BASIN 2.50INSET BASIN FOR VANITY UNIT 1.75
VANITY UNIT FLAT PACK 2.50
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION J 1
SANITARY SUITES AND FITTINGS
7/24/2019 Mechanical Labour Book
60/68
WC SUITESINCLUDES INTERNAL CISTERN WORKINGS
WC PAN FLOOR MOUNTED 1.75WC PAN WALL MOUNTED 2.50CLOSE COUPLED CISTERN 2.25LOW LEVEL CISTERN 2.25HIGH LEVEL CISTERN 3.25
BIDETS
FLOOR STANDING BIDET UNIT 3.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION J 2
SANITARY SUITES AND FITTINGS
EES DATA C i ht 2014 ISSUE DATE A t 2014
7/24/2019 Mechanical Labour Book
61/68
SHOWERS AND ENCLOSURES
SHOWER TRAY STONE RESIN 3.00
SHOWER TRAY PLASTIC 2.50
DOOR AND SIDE PANEL SHOWER ENCLOSURE 4.00
ELECTRIC SHOWER MOUNT & FIX 1.75
THERMOSTATIC MIXER TYPE SHOWER KIT 3.00
SHOWER COLUMN 3.50
PUMP 1.50
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION J 3
SANITARY SUITES AND FITTINGS
EES DATA Cop right 2014 ISSUE DATE A g st 2014
7/24/2019 Mechanical Labour Book
62/68
INDOOR UNITS
INDOOR UNIT 2.50
OUTDOOR UNIT 3.50
ELECTRIC HEATER KIT 1.10
PIPE EXIT KIT 0.33
CASSETTE UNIT 1.00
ISOLATOR 0.45
WALL HANGING BRACKET 0.33
REMOTE TEMPERATURE SENSOR 0.45
SMALL HEAT PUMP 2.00
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION K 1
AIR CONDITIONING UNITS
EES DATA Copyright 2014 ISSUE DATE: August 2014
7/24/2019 Mechanical Labour Book
63/68
SPIRAL DUCT 100-150mm 200-250mm 300-450mm 500-650mm 700-750mm 800-850mm 1000mm
DUCT 0.30 0.45 0.50 0.75 0.90 1.00 1.17
BEND 0.25 0.28 0.35 0.45 0.50 0.55 0.65
REDUCER 0.25 0.28 0.35 0.45 0.50 0.55 0.65
SADDLE 0.20 0.23 0.25 0.30 0.33 0.38 0.45
TEE 0.35 0.40 0.55 0.60 0.65 0.75 0.85
DAMPERS 0.25 0.30 0.40 0.45 0.50 0.55 0.65
GRILL 0.30 0.33 0.33 0.36 0.40 0.45 0.45
COWL 0.25 0.25 0.30 0.30 0.35 0.40 0.50
JOINT CLIP 0.25 0.25 0.30 0.35 0.35 0.40 0.40
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION L 1
SPIRAL ALUMINIUM DUCT
EES DATA Copyright 2014 ISSUE DATE: August 2014
7/24/2019 Mechanical Labour Book
64/68
FLEXIBLE DUCT 100-150mm 200-250mm 300-450mm 500-650mm 700-750mm 800-850mm 1000mm
DUCT 0.15 0.20 0.25 0.35 0.45 0.50 0.60
BEND 0.25 0.28 0.35 0.45 0.50 0.55 0.65
REDUCER 0.25 0.28 0.35 0.45 0.50 0.55 0.65
SADDLE 0.20 0.23 0.25 0.30 0.33 0.38 0.45
TEE 0.35 0.40 0.55 0.60 0.65 0.75 0.85
DAMPERS 0.25 0.30 0.40 0.45 0.50 0.55 0.65
GRILL 0.30 0.33 0.33 0.36 0.40 0.45 0.45
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION L 2
FLEXIBLE DUCT
EES DATA Copyright 2014 ISSUE DATE: August 2014
7/24/2019 Mechanical Labour Book
65/68
GROUND DRAINGE 82mm 110mm 160mm 200mm 250mm 300mm 375mm 450mm 500mm
PIPE 0.25 0.30 0.35 0.40 0.40 0.45 0.45 0.50 0.55
COUPLERS 0.17 0.20 0.25 0.28 0.28 0.30 0.35 0.40 0.45
ADAPTERS 0.25 0.25 0.28 0.28 0.28 0.30 0.30 0.45 0.45
BENDS 0.35 0.35 0.35 0.38 0.40 0.40 0.45 0.45 0.50
REDUCERS 0.25 0.25 0.30 0.33 0.35 0.35 0.40 0.40 0.45
JUNCTIONS 0.50 0.60 0.70 0.75 0.75 0.80 0.80 0.85 0.90
SOCKETS 0.20 0.25 0.25 0.28 0.30 0.30 0.35 0.40 0.45
MANIFOLDS 0.70 0.75 0.90 0.90 1.25 1.25 1.30 1.30 1.40
TEE 0.35 0.40 0.45 0.45 0.50 0.50 0.60 0.65 0.76
GULLIES 0.35 0.35 0.35 0.40 0.40 0.45 0.45 0.50 0.50
EES DATA Copyright 2014 ISSUE DATE:August 2014
ISSUE D Mechanical Installation Times SECTION L 3
BELOW GROUND DRAINAGE PLASTIC
EES DATA Copyright 2014 ISSUE DATE:August 2014
7/24/2019 Mechanical Labour Book
66/68
GROUND DRAINGE 82mm 110mm 160mm 200mm 250mm 300mm 375mm 450mm 500mm
FLOOD VALVE 0.40 0.45 0.50 0.50 0.60 0.60 0.75 0.75 0.90
CHAMBERS 0.75 0.80 1.00 1.00 1.35 1.35 1.40 1.40 1.50
RAISING PIECE 0.25 0.25 0.28 0.28 0.28 0.30 0.30 0.45 0.45
COVERS 0.25 0.25 0.25 0.25 0.30 0.30 0.40 0.40 0.50
GASKETS 0.17 0.20 0.25 0.28 0.28 0.30 0.30 0.33 0.33
END CAP 0.17 0.20 0.25 0.28 0.28 0.30 0.30 0.33 0.33
py g g
ISSUE D Mechanical Installation Times SECTION L 4
BELOW GROUND DRAINAGE PLASTIC
EES DATA Copyright 2014 ISSUE DATE:August 2014
7/24/2019 Mechanical Labour Book
67/68
GROUND DRAINGE 150mm 225mm 300mm 450mm 600mm
PIPE 0.35 0.40 0.45 0.50 0.60
COUPLERS 0.25 0.28 0.30 0.33 0.35
ADAPTERS 0.25 0.28 0.30 0.33 0.35
BENDS 0.35 0.38 0.40 0.45 0.50
REDUCERS 0.30 0.33 0.35 0.40 0.45
JUNCTIONS 0.70 0.75 0.80 0.85 0.90
SOCKETS 0.25 0.28 0.30 0.33 0.35
CHAMBERS 1.00 1.00 1.00 1.25 1.25
COVERS 0.25 0.25 0.25 0.28 0.30
FLEXIBLE COUPLER 0.5 0.40 0.45 0.50 0.60
ISSUE D Mechanical Installation Times SECTION L 5
LAND AND SURFACE WATER DRAINAGE PLASTIC
7/24/2019 Mechanical Labour Book
68/68
EES DataEES Data Ltd41 George StreetCity Centre, WakefieldWest YorkshireWF1 1LW
Web: www.ees-data.co.uk
Email: [email protected]: +44 (0) 1924 200103 Fax: +44 (0) 1924 200104
Estimating + Project Management Software SystemsElectrical Estimating SoftwareMechanical Estimating SoftwareEES Database Pricing Systems: Electrical + Mechanical & PlumbingWith Installation Guidance TimesWeekly Electronic Price and Product UpdatesJob Cost Management SoftwareApplication for Payment SoftwareStock Control SoftwarePurchase Ordering: Small Works CostingHeat Loss Calculator Software
EES DATA Copyright 2014 Mechanical Installation Times ISSUE DATE:August 2014
Professional estimating made easy