1
TABEL MEDIUM VOLTAGE XPLE INSULATED CABLE Hal 1.xls PT. KABELINDO MURNI Tbk N2XSY / NA2XSY 1.8/3 ( 3.6 ) kV Copper or Aluminium Conductor , XLPE Insulated Copper Wire / tape screened , PVC Sheathed Cable 1. Conductor : Copper or aluminum ( compacted circular stranded ) 2. Conductor screen : Extruded semi conductive compound 3. Insulation : Extruded Cross Linked Polyethylene (XLPE) 4. Insulation screen : Extruded Strippable semiconductive compound 5. Metalic Screen : Helically Overlapped copper tape 6. Inner Covering : Helically Overlapped Polyester tape 7. Outer Sheath : Extruded PVC 90° C grade MEDIUM VOLTAGE XPLE INSULATED CABLE Specification : IEC 502-2 Used for distribution indoor and outdoor installation in conduit throughs or trays or in the ground where not sustain mechanical damage Cross Section Nominal Conductor Diameter (Approx) Insulation Thickness Nominal Insulation Diameter (Approx) Sheath Thickness Nominal Cable Net Weight (Approx) Min. Bending Radius Overall Cable Diameter Std. Length per reel Cu Al ( mm 2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg / km ) ( kg / km ) ( mm ) ( mm ) ( m ) 25 6.05 2.0 10.3 1.4 400 200 190 13 1.000 35 7.1 11.3 500 250 210 14 50 8.25 12.5 600 300 240 15 70 9.9 14.1 1.5 800 400 270 17 95 11.7 15.9 1.100 500 310 19 120 13.1 17.3 1.6 1.300 600 340 21 150 14.3 18.5 1.600 700 360 22 185 16.3 20.5 1.7 2.000 800 400 24 240 18.7 22.9 1.8 2.500 1.000 450 27 300 20.9 25.1 3.100 1.200 500 29 400 23.7 27.9 1.9 3.900 1.500 560 32 500 500 26.6 2.2 31.2 2.0 5.000 1.900 620 35 630 30.3 2.4 35.3 2.2 6.400 2.400 700 3 800 34.2 2.6 39.6 2.3 8.200 3.100 780 44 Cross Section Nominal Max.DC Resistance at 20° C Conductor DC Insulation Resistance at 20° C Current Carrying Capacity at 30° C - in Air Current Carrying Capacity at 30° C - in Ground Capacitan ce per phase Inductance per phase Max.Short Circuit Current of Conductor Cu Al Cu Al Cu Al Cu Al ( mm 2 ) ( ohm / km ) ( ohm / km ) M.Ohm.km A A A A uF / km mH / km kA / Sec kA / Sec 25 0.727 1.200 900 191 147 172 132 0.261 0.345 3.73 2.49 35 0.524 0.868 700 231 178 204 157 0.299 0.327 5.18 3.45 50 0.387 0.641 277 215 239 186 0.334 0.313 7.36 4.89 70 0.268 0.443 600 345 268 291 227 0.393 0.300 10.26 6.81 95 0.193 0.320 500 418 327 344 270 0.453 0.287 13.88 9.19 120 0.153 0.253 400 481 377 388 305 0.499 0.280 17.49 11.58 150 0.124 0.206 538 425 424 337 0.539 0.274 21.81 14.43 185 0.0991 0.164 613 486 474 378 0.606 0.267 26.86 17.76 240 0.0754 0.125 300 717 574 541 435 0.685 0.260 34.78 22.98 300 0.0601 0.100 812 653 602 488 0.758 0.253 43.41 28.67 400 0.0470 0.0778 902 742 650 538 0.851 0.248 57.79 38.14 500 0.0366 0.0605 1,007 839 775 616 0.871 0.245 72.16 47.60 630 0.0283 0.0469 200 1,089 871 820 656 0.909 0.243 90.83 59.90 800 0.0221 0.0367 1.120 968 873 698 0.947 0.239 115.23 75.96 SPEC STD APL TECHNICAL DATA DIMENSIONAL DATA ELECTRICAL DATA 1 CORE

Medium Volt Xple Ins Cab h1 1core3kv

Embed Size (px)

Citation preview

Page 1: Medium Volt Xple Ins Cab h1 1core3kv

TABEL MEDIUM VOLTAGE XPLE INSULATED CABLE Hal 1.xls

PT. KABELINDO MURNI Tbk

N2XSY / NA2XSY 1.8/3 ( 3.6 ) kV Copper or Aluminium Conductor , XLPE InsulatedCopper Wire / tape screened , PVC Sheathed Cable

1. Conductor : Copper or aluminum ( compacted circular stranded )2. Conductor screen : Extruded semi conductive compound3. Insulation : Extruded Cross Linked Polyethylene (XLPE)4. Insulation screen : Extruded Strippable semiconductive compound5. Metalic Screen : Helically Overlapped copper tape6. Inner Covering : Helically Overlapped Polyester tape7. Outer Sheath : Extruded PVC 90° C grade

MEDIUM VOLTAGE XPLE INSULATED CABLE

Specification : IEC 502-2

Used for distribution indoor and outdoor installation in conduit throughs or traysor in the ground where not sustain mechanical damage

CrossSectionNominal

ConductorDiameter(Approx)

InsulationThicknessNominal

InsulationDiameter (Approx)

SheathThicknessNominal

Cable Net Weight (Approx) Min.BendingRadius

OverallCable

Diameter

Std.Lengthper reelCu Al

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg / km ) ( kg / km ) ( mm ) ( mm ) ( m )25 6.05

2.0

10.3 1.4 400 200 190 13

1.000

35 7.1 11.3 500 250 210 1450 8.25 12.5 600 300 240 1570 9.9 14.1 1.5 800 400 270 1795 11.7 15.9 1.100 500 310 19

120 13.1 17.3 1.6 1.300 600 340 21150 14.3 18.5 1.600 700 360 22185 16.3 20.5 1.7 2.000 800 400 24240 18.7 22.9 1.8 2.500 1.000 450 27300 20.9 25.1 3.100 1.200 500 29400 23.7 27.9 1.9 3.900 1.500 560 32

500500 26.6 2.2 31.2 2.0 5.000 1.900 620 35630 30.3 2.4 35.3 2.2 6.400 2.400 700 3800 34.2 2.6 39.6 2.3 8.200 3.100 780 44

CrossSectionNominal

Max.DC Resistance at 20° C Conductor

DC Insulation

Resistanceat 20° C

Current Carrying Capacity

at 30° C - in Air

Current Carrying Capacity

at 30° C - in Ground

Capacitance

per phase

Inductanceper phase

Max.Short CircuitCurrent of Conductor

Cu Al Cu Al Cu Al Cu Al( mm2 ) ( ohm / km ) ( ohm / km ) M.Ohm.km A A A A uF / km mH / km kA / Sec kA / Sec

25 0.727 1.200 900 191 147 172 132 0.261 0.345 3.73 2.4935 0.524 0.868 700 231 178 204 157 0.299 0.327 5.18 3.4550 0.387 0.641 277 215 239 186 0.334 0.313 7.36 4.8970 0.268 0.443 600 345 268 291 227 0.393 0.300 10.26 6.8195 0.193 0.320 500 418 327 344 270 0.453 0.287 13.88 9.19

120 0.153 0.253400

481 377 388 305 0.499 0.280 17.49 11.58150 0.124 0.206 538 425 424 337 0.539 0.274 21.81 14.43185 0.0991 0.164 613 486 474 378 0.606 0.267 26.86 17.76240 0.0754 0.125

300

717 574 541 435 0.685 0.260 34.78 22.98300 0.0601 0.100 812 653 602 488 0.758 0.253 43.41 28.67400 0.0470 0.0778 902 742 650 538 0.851 0.248 57.79 38.14500 0.0366 0.0605 1,007 839 775 616 0.871 0.245 72.16 47.60630 0.0283 0.0469 200 1,089 871 820 656 0.909 0.243 90.83 59.90800 0.0221 0.0367 1.120 968 873 698 0.947 0.239 115.23 75.96

SPEC

STD

APL

TECHNICAL DATA

DIMENSIONAL DATA

ELECTRICAL DATA

1 CORE